Integrated Development and Assessment of New Thermoplastic High Voltage Power Cable Systems
|
|
|
- Alan Maxwell
- 10 years ago
- Views:
Transcription
1 21, rue d Artois, F PARIS B1-215 CIGRE 2012 http : // Integrated Development and Assessment of New Thermoplastic High Voltage Power Cable Systems Mike FAIRHURST (1), Ankit GOWADIA (1), Gary STEVENS*(2), Ben PHILPOT (2), Janet THOMAS (2), James PILGRIM (3) and Paul LEWIN (3) 1 National Grid PLC, Warwick Technology Park, Warwick CV34 6DA, UK 2 GnoSys Global Ltd., The Surrey Research Park, Guildford GU2 7YD, UK 3 ECS, University of Southampton, Southampton, SO17 1BJ, UK SUMMARY European policy drivers exist to improve the design and deployment of power cable systems in transmission networks, particularly the whole life cycle of future low carbon networks. As part of a new power cable development project called SUSCABLE, a new high temperature and recyclable thermoplastic blend HV power cable has been proposed and a new approach has been developed to carry out integrated assessment of multiple performance factors. From materials selection and cable manufacture to cable rating in common deployment situations, along with network constraint and life cycle assessment, the outputs were integrated to enable the whole life performance of the newly proposed cables to be critically assessed. This is the first time such an approach to integrated performance assessment has been carried out. LEETS is a methodology and software tool which brings together these multiple assessments and enables comparison of different cable technologies, their manufacture and deployment with account of the local environmental and end of life management options. This method is ideally suited to carrying out assessments in response to the requirements of various stakeholders, be it the materials supplier, the cable manufacturer or the utility deploying and operating the cable. High voltage cables typically use XLPE as the dielectric but it is energy intensive to produce and difficult to manufacture and recycle. New cable designs utilizing new thermoplastic blend insulation materials are capable of operating at higher conductor temperatures, are not cross-linked, and offer significant economic and environmental benefits across the complete life cycle. This paper will illustrate, through the use of a new LEETS-Cable model, how alternative cable systems can be compared across the whole life cycle including manufacture, deployment, operation and end of life management. The paper will discuss how potential benefits are assessed using the model which integrates cable rating and system studies with account of the deployment environment for cable operation under both continuous and fault conditions. KEYWORDS Power cable systems, transmission networks, high temperature cables, cable ratings, integrated assessment, whole life assessment, economics and environmental, thermoplastic blend insulation [email protected]
2 INTRODUCTION There are many environmental drivers at a European level requiring the improvement of the design and deployment of power cable systems. These include the European Carbon Strategy, the EU Waste Framework Directive, the move to low carbon networks and green procurement - these affect industry across the whole cable life cycle from manufacture to deployment and end of life management. Economic factors are providing a force for change in materials supply and the need for process energy reduction during manufacture. So, coupled environmental and economic drivers are becoming more important for efficient cable production and in meeting procurement requirements including increasingly those satisfying green procurement policies. Tools In order to respond to these drivers, there are many methods for assessing the economic and environmental performance of products at production level, but few that deal with the whole life cycle. These methods include Life Cycle Assessment (LCA), Life Cycle Costing (LCC) and Total Cost Assessment (TCA) and a raft of technical approaches and studies. However, there hasn t been an approach to these assessments which aims to bring all aspects together in one methodology and tool. LEETS and LCC LEETS is a methodology and software tool 1 which brings together multiple assessments and enables them to be used to compare cable technologies, and their manufacture and deployment with account of the local environment and end of life management options. LCC is a new integrated life cycle cost and risk assessment methodology, which addresses whole life costs from original planning, to construction, operation and eventually the management of end-of-life of assets. The approach was developed to support asset investment and policy by enabling optimum solutions to be identified, taking into account economic, environmental, health and safety and social costs, with explicit account of hazards and risks, including those arising from asset failure 2. HV Cables High voltage cables typically use XLPE as the dielectric material. While this has excellent performance characteristics, it is energy intensive to produce, requires cross-linking followed by degassing and it is difficult to recycle. New cable designs based on new uncrosslinked thermoplastic materials have been developed. These can operate at higher conductor temperatures if required; potentially up to 150 C. These were the subject of a recent UK Technology Strategy Board project. METHODOLOGY An integrated methodology was applied bringing together materials selection, cable manufacture, cable ratings for common deployments, along with network constraint and life cycle assessment. The outputs were integrated to enable integration of whole life performance via the LEETS-Cable model which included other environmental impacts and parallel economic and risk factors. LCA Goal The goal of the life cycle study was to evaluate the environmental impacts of manufacturing, cable deployment, operation and end of life management. The benchmark scenario chosen was a typical XLPE cable technology for HVAC transmission currently employed by National Grid in the UK. The new cable used the same cable construction but with thermoplastic replacement of the XLPE. Functional Unit The functional unit (or unit of service provided by the cable circuit) was chosen to provide a fair comparison of the performance of alternative cable designs in different, yet common deployments and load conditions in the context of anticipated network applications identified by system constraint studies. This included a number of operational extremes ranging from low load factor continuous operation to high load factor and high peak transmission conditions requiring the maximum cable operating temperature for relatively short periods of time under emergency conditions - typically from 1
3 one hour to ten or more hours. Hence the study used 1 kilometre of a 3 phase 400kV HVAC cable circuit consisting of 1 cable per phase and a base load of 35% of continuous rating. System Boundary The system boundary includes product and material flows as well as energy use and emissions to air, water and land. It also highlights areas where there is potential for materials to be diverted from current disposal practices of incineration and landfill to recovery for further use i.e. re-use/recycling. Figure 1: Whole Life Assessment System Boundary At each of the stages in the life cycle a variety of inputs/outputs occur, such as raw materials, products, energy and environmental emissions. Figure 1 details the stages identified for the production of the primary cable, from raw material supply, to cable manufacture and deployment, then operation and finally material recovery and recycling. The study and the Leets-Cable model assess each stage in the life cycle but the study is implemented as a streamlined model to capture the most important impacts and ensure the focus is maintained on cable performance. The cost and environmental impacts associated with putting in place the local infrastructure for deployment of the cable are also considered. Cable Manufacture The production of each of the raw materials used in the cable construction is assessed in addition to the actual cable production process. So the original production of the polymer sheathing compound, the insulation polymer, the semi-conductor compound and the metallic conductor material (electrorefined copper) are all considered. The LCA for cable manufacture differentiates between extrusion followed by heated pipe catenary crosslinking in the case of the benchmark XLPE cable and extrusion 2
4 combined with controlled cooling for thermoplastic blend cables. The extrusion of the cable is assumed to be carried out on a vertical extrusion line or heated crosslinking catenary. In this paper the degassing stage is not included so the XLPE performance appears better than it will be in practice. Cable Deployment An assessment of cable deployment was made and there was no difference between cable types. Deployment options included cable tunnel deployment and direct buried in ducts or troughs with backfill. Transport to site was also considered with usual haulage and cable drum weight constraints. Some key differences arise in relation to the effective number of cable joints used in deployment as the maximum length between joints increases for smaller conductor and cable sizes. Cable joint performance is not considered in this paper but has been the subject of other studies. The deployment type will have an impact on the cable rating. Tunnel deployments limit cable current because of constraints on cooling arising from air flow limits particularly for long stretches of tunnel. The operation of directly buried cables is also limited by soil heating and drying effects which limit heat transfer. This is particularly evident in rural environments. Operation Network studies were carried out on a number of typical UK circuits to obtain representative inputs on circuit constraints and needs. The operational phase of the cable life cycle was modelled, particularly in regard to the cable rating and I 2 R losses. Cable ratings studies, using finite element static and dynamic models, were applied to all deployment cases in order to compare the new cable with conventional XLPE insulated cables. LEETS-Cable used this data as part of the integrated assessment. Additionally, National Grid carried out assessments of potential system failures in key locations. This established the system loadings that might occur and therefore the suitability of either conventional XLPE insulated cables or new high temperature cables in a number of specific situations. End of Life End of life scenarios were created for both the XLPE and new cables including materials recycling, incineration with energy recovery and landfill as possibilities. RESULTS Essential conclusions Deployment of the cable has a significant economic cost and environmental impact in addition to that of cable production and operation of the cable circuit. The operation of the cable circuit and the conductor power losses (I 2 R losses) are a dominant factor in overall environmental performance. As the copper conductor is largely responsible for losses the new and XLPE cables will perform the same for the same ampacity and conductor size. The differences in whole life performance are clear when the manufacturing and end of life management are considered as shown for global warming potential (GWP) in Figure 2. This may be compared with the GWP impact of different deployments (see Figure 2) and with the annual GWP contribution from lifetime operation of the cable circuit - see Figure 3, which shows the impact of the change in energy mix with time due to greater anticipated use of renewables generation in the future. Reducing copper conductor size must be traded-off against increase I 2 R losses the smaller the conductor cross section, the larger the losses and reduced ability to handle higher emergency ratings. These trade-offs were explored and the conclusion reached was that larger conductor size is more favourable from a whole life perspective particularly when recycling is accounted for. 3
5 Figure 2: Whole life GWP by cable type for direct buried deployment excluding power losses Figure 3: Lifetime annual GWP for operation of the cable circuit at 35% rated load with account of anticipated changes in UK energy mix. The difference in GWP of tunnel deployment and the other deployment scenarios is a factor of 8 relative to surface troughs and 78 relative to direct buried, as shown in Figure 4. Re-using the tunnel at end of life significantly reduces the GWP in the second cable life cycle. It is instructive to compare the net contributions to GWP of the different phases of the life cycle for the lowest impact deployment case - directly buried cables. For this case, Figure 5 shows that integrated whole life operational impact is significantly larger than that from other phases of the life cycle including cable manufacturing - a factor of 3.5 larger. In contrast, if cable tunnel deployment is used, the operational GWP is comparable to that of the deployment (compare Figures 4 and 5). 4
6 GWP 100 Tonne Equiv. CO Direct buried Surface troughs Tunnels 0 Deployment Figure 4: Cable deployment comparison based on GWP. Life cycle carbon impacts are very sensitive to energy mix, as shown in Figure 3. The LEETS-Cable model provides many options for pre-defined forecasts of long term changes internationally as well as in the UK with account of increased renewable generation. Operational impacts were based on UK forecasts. The life cycle data for manufacture of the cables also incorporates a variety of generation mixes as components may be sourced from a number of different countries with their own generation mix profile ) iv u E q O C s e n (to 500 P W G XLPE New Design 0 Manufacturing Deployment Operation End of Life -500 Life Cycle Stage Figure 5 Whole Life GWP for direct buried XLPE and new design cables 5
7 Operating new cables at 150 C compared to 90 C for XLPE leads to a significant increase in transmission losses, especially at higher loads (Figure 6). However, this is usually only for very short periods in comparison with the whole life of the cable, so the overall its impact is relatively small Direct Buried Losses Per MW (actual) MJ / Yr XLPE 150C % Continuous Rating Figure 6: Annual transmission losses by load and cable type Manufacturing process energy is substantially lower for the new cable design due to there being no need for cross-linking as shown Figure 7 and which contains no contribution for degassing. The overall carbon saving of the new cable was 125 tco 2 across the life (60 years) compared to XLPE. The lower process energy for the copper of the new thermoplastic cable arises because of lower net energy required for conductor heating during processing and the absence of the crosslinking process step. 9.0E E E E+06 Processing Energy (KJ) 5.0E E E+06 Conductor Inner Semi Dielectric Outer Semi Screen Oversheath 2.0E E E+00 XLPE Insulation Cable Type New Insulation Figure 7: Processing energy during cable manufacture 6
8 Cable procurement and construction costs The cable procurement cost and end of life costs have been taken from a report by the Highland Council in Scotland (for an XLPE system) 3. This makes it clear that the costs may not be accurate and were difficult to obtain. The construction costs were taken from an LCC asset policy study carried out by GnoSys Global Ltd for National Grid 4. Operation Operation and maintenance costs are also estimated in the Highland Report 3. For tunnels, a figure has been included for the operation of cooling fans based on data provided by National Grid. The costs of operational losses were evaluated as those appropriate to a large industrial user. Currently, the losses are not paid for explicitly; rather the cost is incorporated into the price that distribution networks pay the generators. However, this may change in the future. The fault outage costs are also those that commonly apply in the UK. The longest time a circuit is likely to be in a fault state is 6 hours and the energy which should have been transmitted in this time at 35% load is calculated. Stakeholder Perspectives Manufacturers To better understand a manufacturer s perspective there are two key factors that must be considered: material supply cost and process energy costs. Using international materials pricing, there is a materials cost reduction of approximately 14% for the new insulation material compared to XLPE and an overall cable cost reduction of about 17% is expected when all materials are considered. The additional process energy used can be quantified in terms of the energy supply cost. If we assume electrically sourced heating, then using the same price (5.5p/kWh) the processing costs could be significantly reduced as shown in Figure 8. So overall, lower process costs and marginally lower materials supply costs offer distinct advantages to the primary cable cost of the thermoplastic cable this does not include a consideration of XLPE cable degassing costs and accessory costs. Figure 8: Process energy costs for cable manufacture using electricity excluding embedded energy costs associated with materials as supplied. TSO s Emergency rating studies concluded that if a double cable circuit was replaced with a single new thermoplastic based cable circuit and operated up to 90 C prior to the fault, the 6hr emergency rating could be significantly enhanced by between 40 to 50% and this would reduce system constraint costs in the event of a fault. Key TSO benefits with the new cable are the ability to relax constraints during 7
9 post-fault operation. In some cases this could be from 20 minutes using an XLPE cable to 6 or even 24 hours using the new design. If the cost of cable supply is close to or possibly lower than that of XLPE cables the additional insurance value and future proofing of the new cables offers significant network whole life cost benefits. CONCLUSIONS The LEETS-Cable model has been developed to be applicable to any power cable system. It may be further complemented by whole life cost assessment accounting for planned outage and cable and accessory risk of failure. The cable model combines environmental impacts with economic and operational data to enable trade-offs in cable design and manufacture in relation to operation to be critically assessed. With whole life costing it also allows the incorporation of lifetime risk 2. The environmental GWP impacts for cable manufacturing are small compared to the impact of lifetime operational impacts but comparable to cable tunnel deployment impacts. Although in this paper we have concentrated on GWP, other environmental impact factors were also analysed and these should also be considered to obtain a more complete picture of the whole life environmental performance. Economic analysis showed that the process energy involved in the production of the two different cable systems has a significant effect on the cost of cable manufacture. The new cable is likely to give a significant cost benefit in terms of energy consumption during manufacture. When manufacturing only was considered it was no surprise that the main contributors to GWP were the manufacture of the copper and dielectric components of the cable. The new cable design showed a reduction in GWP of the main wall dielectric component. When the end of life was also considered, carbon credits were gained for the recovery of copper and other recoverable cable components. This increased the difference between the two dielectric components since the new design dielectric component is fully recyclable. When considering environmental impacts in isolation, it would appear that the optimum cable design would use a small conductor size consistent with current rating requirements. However cable rating studies revealed that I 2 R losses under continuous operation were too large for smaller conductor sizes to be practical. Therefore for most applications larger conductor size is more desirable. System emergency and constraint studies carried out by National Grid concluded that if a double circuit was replaced with a single thermoplastic based cable circuit and operated to 90 C prior to the fault, the 6hr emergency rating would help to reduce the system costs in an event of a fault. TSO benefits centre on the ability to relax constraints during post-fault operation. In some cases this could be from 20 minutes using an XLPE cable to 6 or even 24 hours using the new design. It is important to consider the LCA findings of the whole life cycle in conjunction with the results of the cable ratings studies, emergency ratings studies and the economic analysis in order to establish tradeoffs to optimise cable design, cable deployment and in principle cable operation. BIBLIOGRAPHY [1] G C Stevens, B Philpot, P Haywood, S. Jayasinghe and C Smith. Life Cycle Economic and Environmental Assessment of Transmission Systems (LEETS) (C3-205, CIGRE 2008) [2] G C Stevens, A Mitchel, P. Scobie, D Culley and J Fitch. New Life Cycle Costing and Risk Approaches to (CIRED 2011 to be published) see also CIGRE [3] The Highland Council. Cairngorms National Park Authority & Scottish Natural Heritage Undergrounding of Extra High Voltage Transmission Lines. (Jacobs Babtie, 2005). [4] GnoSys Global Ltd (National Grid), Co-location of High Voltage Cable Systems Within Tunnels, (2010). 8
SHE Transmission. 2015_10_30 Transmission Losses Strategy Rev 2.0 October 2015
SHE Transmission 2015_10_30 Transmission Losses Strategy Rev 2.0 October 2015 Summary This paper presents SHE Transmission s views and approach on the impact of transmission losses on the transmission
PB POWER ISLAND OF IRELAND CAVAN-TYRONE AND MEATH-CAVAN 400KV PROJECTS PRELIMINARY BRIEFING NOTE OVERHEAD AND UNDERGROUND ENERGY TRANSMISSION OPTIONS
ISLAND OF IRELAND CAVAN-TYRONE AND MEATH-CAVAN 400KV PROJECTS PRELIMINARY BRIEFING NOTE OVERHEAD AND UNDERGROUND ENERGY TRANSMISSION OPTIONS FEBRUARY 2008 PB POWER PB Power Page i EXECUTIVE SUMMARY General
E-Highway2050 WP3 workshop April 15 th, 2014 Brussels
E-Highway2050 WP3 workshop April 15 th, 2014 Brussels High voltage underground and subsea cable technology options for future transmission in Europe Ernesto Zaccone, Chairman Europacable High Voltage Systems
Cable Consulting International
Cable Consulting International Brian Gregory BSc, CEng, MIEEE, FIEE Technical Director www.cableconsulting.net Alan Williams BSc, CEng, MIEE Senior Consultant 1 FEASIBILITY STUDY for 500 kv AC UNDERGROUND
M. GELDON Brugg Kabel CZ. Ing. D. RÚŽEK PREdistribuce. Switzerland Czech Rep. Czech Rep. Czech Rep., Switzerland Germany
21, rue d Artois, F-75008 PARIS Paper number CIGRE 2012 http : //www.cigre.org 6 characters (to be provided later) Correlation between calculated transmission capacity and actual one D. WALD* Eifelkabel
Respecting the environment
MAIN FEATURE CHAPTER I RESEARCH WITH AN EYE ON THE FUTURE Respecting the environment Low power losses and a lesser visual impact on the landscape make Gas-Insulated Lines (GIL) a very environmentally friendly
AMSC s Superconductor Cable Technologies for Electric Utilities
International Workshop 2014 AMSC s Superconductor Cable Technologies for Electric Utilities Michael Ross, P.E. Managing Director of Superconductor Power Systems AMSC Corporate Facts Headquartered in MA,
Fault location on power cables. Fault location on power cables
Fault location on power cables Fault location on power cables Contents: 1. Introduction 2. Construction of power cables 3. Cable faults 01. Introduction Fault location on communication and power cables
A clean energy solution from cradle to grave
Environmental Product Declaration A clean energy solution from cradle to grave Offshore wind power plant employing SWT-6.0-154 siemens.com / wind 2 Assessing the performance of a wind power plant The environmental
State, trends and evolutions of HV/EHV power cables systems and contributions of SC B1 to their ongoing progress
0611-048-Mep229 12/12/06 6:44 Page 22 State, trends and evolutions of HV/EHV power cables systems and contributions of SC B1 to their ongoing progress Reinhard SCHROTH, Chairman of SC B1 2002-2006 High
EFFICIENT ELECTRICAL ENERGY TRANSMISSION AND DISTRIBUTION INTERNATIONAL ELECTROTECHNICAL COMMISSION
EFFICIENT ELECTRICAL ENERGY TRANSMISSION AND DISTRIBUTION INTERNATIONAL ELECTROTECHNICAL COMMISSION EFFICIENT ELECTRICAL ENERGY TRANSMISSION AND DISTRIBUTION 1 EFFICIENT ELECTRICAL ENERGY TRANSMISSION
Network Standard Advice No. 1420C 9/6/2011
Network Standard Advice No. 1420C 9/6/2011 TO: Customers, Service Providers and Ausgrid Staff. Advisory Note on Changes to the Use of 11kV Cable Types. Introduction This Network Standard Advice (NSA) provides
Undergrounding high voltage electricity transmission. The technical issues
Undergrounding high voltage electricity transmission The technical issues This is an interactive PDF document with clickable links from the contents to all sections and back and also to URL and email links.
SP Energy Networks 2015 2023 Business Plan
Environmental Discretionary Reward Scheme 1 SP Energy Networks 2015 2023 Business Plan Executive summary SP Distribution Ltd SP Manweb plc July 2013 RIIO ED1 Business Plan 2015 to 2023 2 A Message from
Lifecycle Strategy DISPOSAL AND DIVESTMENT
Lifecycle Strategy DISPOSAL AND DIVESTMENT Document 07/10/2013 Page 1 of 19 C O P Y R I G H T 2013 T R A N S P O W E R N E W Z E A L A N D L I M I T E D. A L L R I G H T S R E S E R V E D This document
HIGH-CAPACITY HIGH TEMPERATURE SUPERCONDUCTING POWER CABLES
HIGH-CAPACITY HIGH TEMPERATURE SUPERCONDUCTING POWER CABLES Jean-Maxime SAUGRAIN NEXANS Corporate VP Technical IASS Workshop Postdam May 13, 2011 Rationale High-capacity High Temperature Superconducting
Stephen G. Whitley, Senior Vice President & Chief Operating Officer
Peter T. Brandien Vice President, System Operations To: Stephen G. Whitley, Senior Vice President & Chief Operating Officer From: Peter T. Brandien Re: Discussion of Cable Technologies Under Evaluation
SPACE CHARGE ACCUMULATION UNDER THE EFFECTS OF TEMPERATURE GRADIENT ON SOLID DIELECTRIC DC CABLE
ISBN 978--658-9 Proceedings of the 6 th International Symposium on High Voltage Engineering Copyright c 9 SAIEE, Innes House, Johannesburg SPACE CHARGE ACCUMULATION UNDER THE EFFECTS OF TEMPERATURE GRADIENT
HV Submarine Cable Systems Design, Testing and Installation
HV Submarine Cable Systems Design, Testing and Installation CIGRE Ireland Technical Seminar 6 th October 2010 Robert Donaghy Senior Consultant Engineer, ESB International Presentation Overview Applications
KNOW YOUR OPTIONS: 69 KV XLPE POWER CABLE
Know Your Options: 69 kv XLPE Power Cable 3 material and size material is a matter of both customer preference and required current carrying capacity Copper conductor common for larger loads When both
Session Five: Modern XLPE Materials for Extruded Energy Cable Systems
Session Five: Modern XLPE Materials for Extruded Energy Cable Systems Abstract Hakan Lennartsson Senior Technical Service Manager, Borouge Hong Kong Pte. Ltd. The first medium voltage cables using extruded
KNOW YOUR OPTIONS: 230 KV POWER CABLES
KNOW YOUR OPTIONS: 230 KV POWER CABLES 71 CONDUCTOR MATERIAL AND SIZE Conductor material is a matter of both customer preference and required current carrying capacity At 230 kv, copper is most common
Rainwater Harvesting
Rainwater Harvesting With climate change now a reality rather than a speculated possibility, the demand on water resources has gone up, whilst the amount of water available for supply has gone down. Forth
KALPANA INDUSTRIES LTD. TECHNICAL DATA SHEET
1 KALPANA INDUSTRIES LTD. TECHNICAL DATA SHEET KI XL - 03 / KI-SC 10 TWO COMPONENT AMBIENT CURABLE POLYETHYLENE COMPOUND FOR INSULATION OF LOW VOLTAGE POWER CABLE DESCRIPTION : KI polyethylene compound
Section 5 161 kv Power Cables
Know Your Options: 161 kv Power Cable 61 material and size material is a matter of both customer preference and required current carrying capacity Copper conductor common for larger loads When both copper
Removal of EP 20 10 00 02 SP High Voltage Cable
TN 018: 2014 Technical Note For queries regarding this document [email protected] www.asa.transport.nsw.gov.au TN 018: 2014 Issued date 12 March 2014 Effective dates 12 March 2014 Subject:
Big Yellow Group PLC Basis of Reporting 1st April 2012 31st March 2014 Corporate Social Responsibility
Big Yellow Group PLC Basis of Reporting 1st April 2012 31st March 2014 Corporate Social Responsibility Deloitte LLP provides independent and limited assurance of selected subject matters in our annual
4 IX D N E P P A Installation methods Current-carrying capacity and voltage drop for cables Reference method IET Wiring Matters
8 Appendix 4 of BS 7671 by Mark Coles Appendix 4, Current-carrying capacity and voltage drop for cables and flexible cords, has seen significant changes with the publishing of BS 7671:2008. This article
Smarter Buildings & Management of Buildings
Green Building Regional Conference and Exhibition 2011 : Innovations in Green Buildings Smarter Buildings & of Buildings Sreenath P V Vice-President, IBM India Ltd November 25, 2011 Agenda IBM s Smarter
Discussion Group C32D: Support of transmission cables in manholes
Discussion Group C32D: Support of transmission cables in manholes IEEE Insulated Conductors Committee Meeting May 22-25, 2011 St. Petersburg Beach, Florida 1 Agenda This Meeting Introduction Review of
AORC Technical meeting 2014
http : //www.cigre.org B1-1055 AORC Technical meeting 2014 220 kv Long Distance Underground HVAC Cable Circuit NAVEED RAHMAN Nexans Olex Melbourne, Australia SUMMARY In 2009, the Victorian state government
The new 525 kv extruded HVDC cable system
The new 525 kv extruded HVDC cable system World s most powerful extruded cable system Anders Gustafsson, Markus Saltzer, Andreas Farkas, Hossein Ghorbani, Tobias Quist, Marc Jeroense High Voltage Cables
How To Monitor Water Penetration In A Cable Screen
Detection and location of high voltage cable sheath damage with Water Penetration Monitoring*) Purpose of Monitoring System The expected lifetime of high voltage underground cables is more than 40 years,
An Introduction to High Voltage Direct Current (HVDC) Underground Cables
Page 1 An Introduction to High Voltage Direct Current (HVDC) Underground Cables Brussels, 10 October 2011 An Introduction to High Voltage Direct Current (HVDC) Underground Cables Page 2 Table of content
NETWORK OUTPUT MEASURES METHODOLOGY Authors: National Grid, SP Transmission PLC, Scottish Hydro Electric Transmission Limited
NETWORK OUTPUT MEASURES METHODOLOGY Authors: National Grid, SP Transmission PLC, Scottish Hydro Electric Transmission Limited TABLE OF CONTENTS 1.0 Purpose and Scope...2 1.1 Methodology Purpose...2 2.0
CABLE MONITORING SOLUTION
POWER CABLE MONITORING SOLUTION Kuljit Singh BSc Honours MIEE(IET,UK) Dan Watley Ph. D, B.A MEng (UK), MIEEE, UK 8-9 November 2011 PREDICT WITH CERTAINTY Definition DTS: Distributed Temperature Sensor
SP Energy Networks 2015 2023 Business Plan
SP Energy Networks 2015 2023 Business Plan Updated March 2014 Annex 132kV Cable Strategy SP Energy Networks 27 March 2014 132kV Cable Strategy March 2014 Issue Date Issue No. Document Owner Amendment Details
Chemical resistance Accidental
Industrial flexible cable, insulation and outer sheath in elastomer Description Application TITANEX flexible cable is intended for installations with moving equipment, electric appliances and for building
Two different types of cables are used in primary airfield lighting circuits: - unshielded cables and - shielded cables
Two different types of cables are used in primary airfield lighting circuits: - unshielded cables and - shielded cables Classically both cables have a single AWG 8 copper conductor or a cross section of
Protect the value of your HV fluid-filled cable network through full life-cycle maintenance
Protect the value of your HV fluid-filled cable network through full life-cycle maintenance a complete network service package Since the 1930s, Nexans and its parent companies have pioneered fluid-filled
Offshore Wind China 2010 Bergen, 15th March 2010. Olivier Angoulevant Nexans Norway AS
Offshore Wind China 2010 Bergen, 15th March 2010 Olivier Angoulevant Nexans Norway AS At the core of performance At the core of performance : a worldwide leader Worldwide leader in cables, cabling systems
Overhead lines Asset Management in the Belgian network. S. GERMAIN K. VAN DAM B. RISSE JF. GOFFINET Elia Belgium
21, rue d Artois, F-75008 PARIS B2-208 CIGRE 2012 http : //www.cigre.org Overhead lines Asset Management in the Belgian network. S. GERMAIN K. VAN DAM B. RISSE JF. GOFFINET Elia Belgium SUMMARY The Belgian
Environmental Performance Data Calculation Standards
Environal Performance Data Calculation Standards Subject Period: April 1, 2012 March 31, 2013 Scope : Fujitsu and Fujitsu Group (For details, refer to the List of Companies Covered by the Report on Environal
B1-102. EHV XLPE CABLE SYSTEMS UP TO 400 kv - MORE THAN 10 YEARS FIELD EXPERIENCE
21, rue d'artois, F-75008 Paris http://www.cigre.org B1-102 Session 2004 CIGRÉ EHV XLPE CABLE SYSTEMS UP TO 400 kv - MORE THAN 10 YEARS FIELD EXPERIENCE W.G. Weissenberg U. Rengel R. Scherer Brugg Kabel
RCP2 Portfolio Overview Document
RCP2 Portfolio Overview Document Portfolio: Expenditure Class: Base Capex Expenditure Category: Grid Replacement & Refurbishment As at date: 15 November 2013 Expenditure Forecast Real 2012/13 NZ$ (m) 2015-2016
Summary of Electric Transmission Assessment Report
Summary of Electric Transmission Assessment Report January 2010 Assessment and Analysis of the State-Of-the-Art High-Voltage Electric Transmission Systems with Specific Focus on High-Voltage Direct Current
LIFE-CYCLE IMPACTS AND COSTS OF MANGANESE LOSSES AND RECOVERY DURING FERROMANGANESE PRODUCTION
LIFE-CYCLE IMPACTS AND COSTS OF MANGANESE LOSSES AND RECOVERY DURING FERROMANGANESE PRODUCTION L.A. Westfall 1, M.H. Cramer 1, J. Davourie 1, D. McGough 2 and M. Ali 1 1 Hatch Ltd., 2800 Speakman Drive,
Energy from digester gas. Optimised biogas utilisation
Energy from digester gas Optimised biogas utilisation The complete solution The complete solution Our company ENER-G designs, installs and operates biogas combined heat and power (CHP) systems for a variety
HIGH- AND EXTRA-HIGH-VOLTAGE GLOBAL CABLE SYSTEM SOLUTIONS Rely On Our Experience... Experience Our Capabilities
HIGH- AND EXTRA-HIGH-VOLTAGE GLOBAL CABLE SYSTEM SOLUTIONS Rely On Our Experience... Experience Our Capabilities RELY ON OUR EXPERIENCE... EXPERIENCE OUR CAPABILITIES For close to half a century, Silec
ELECTRICAL INSULATION TESTING OF HV EQUIPMENT UP TO 33kV
1. SCOPE This document details PowerSystems requirements for electrical testing of HV Equipment up to and including 33kV. 2. ISSUE RECORD This is a Reference document. The current version of Controlled
THE PATHWAY TO POWER HIGH-VOLTAGE CABLES
THE PATHWAY TO POWER HIGH-VOLTAGE CABLES TABLE OF CONTENTS HIGH-VOLTAGE CABLES 3 Advantages of XLPE-insulated cable systems 3 PROPOSAL 4 Cable systems 4 Providing System Solutions 4 Continuous temperature
Offshore Wind Farm Export Cable Current Rating Optimisation
Offshore Wind Farm Export Cable Current Rating Optimisation James Pilgrim 1, Simon Catmull 2, Richard Chippendale 1, Richard Tyreman 3 and Paul Lewin 1 1. Tony Davies High Voltage Laboratory, Southampton
SUPERCONDUCTING CABLE SYSTEMS
SUPERCONDUCTING CABLE SYSTEMS INTRODUCTION An aging and inadequate power grid is widely seen as one of the greatest obstacles to the restructuring of power markets in the United States, Europe and elsewhere.
University of Melbourne Symposium on ICT Sustainability Dan Pointon 25 November 2008
University of Melbourne Symposium on ICT Sustainability Dan Pointon 25 November 2008 Contents Welcome and Introduction Chapter 1: Data centre energy recap Chapter 2: Co-generation Chapter 3: CTC case study
Offshore Platform Powered With New Electrical Motor Drive System
Offshore Platform Powered With New Electrical Motor Drive System Authors: Jan O. Lamell, M.Sc E.E. ABB Automation Technologies Presenters: Thomas Johansson, M.Sc E.E. ABB Automation Technologies Timothy
environment briefing02
PRODUCED BY THE SAFETY, HEALTH & ENVIRONMENT GROUP OF THE ENERGY NETWORKS ASSOCIATION - JULY 2006 environment briefing02 transporting electricity Overhead Lines or Underground Cables? Introduction The
Evolion Li-ion battery. Saft s proven ultra-compact solution for telecom applications
Evolion Li-ion battery Saft s proven ultra-compact solution for telecom applications Saft: Providing energy for today s telecom installations Saft has a complete range of specialised batteries for a wide
Summary of risks with conductive and nonconductive plastic pipes at retail petrol stations
Summary of risks with conductive and nonconductive plastic pipes at retail petrol stations Introduction Harold Walmsley, Harold Walmsley Electrostatics Ltd, 23/01/2010 This note summarises my views on
Gulf Cable & Electrical Ind. Co.
CONTENTS INTRODUCTION PRODUCT RANGE I PRODUCT DATA TABLES XLPE INSULATED 600/1000V CABLES Two Core Cables CU/XLPE/PVC/LC/PVC/SWA/PVC 1 Three Core Cables CU/XLPE/PVC/LC/PVC/SWA/PVC 2 Four Core Cables CU/XLPE/PVC/LC/PVC/SWA/PVC
An Introduction to Product Takeback
An Introduction to Product Takeback Overview Driving forces behind product takeback Product takeback legislation Product end-of-life options Reverse logistics Case study Motivation for Product Takeback
Feasibility Study of Deep Water Power Cable Systems. Enrico Colombo CESI S.p.A
Feasibility Study of Deep Water Power Cable Systems Enrico Colombo CESI S.p.A Layout of Presentation The Study Context, Objectives, Participants Study Approach & Methodology Assessments and Findings Implementation
Wind turbines on your land. Renewable energy development for landowners
Wind turbines on your land Renewable energy development for landowners Diversification By diversifying into wind energy, landowners have an opportunity to receive a regular, guaranteed income for up to
Distributed Temperature Monitoring of Energy Transmission and Distribution Systems
1 m 40000m0 range 61850 IEC spatial resolution Distributed Temperature Monitoring of Energy Transmission and Distribution Systems Ensuring a Reliable Supply of Electrical Power for Today s World www.en-sure.pro
State of the art sustainability marketing tools
State of the art sustainability marketing tools Anne-Marie Imrell ABB AB 2003 ABSTRACT This report belongs to the DANTES project that is supported by the EU Life Environment Program. Examination of how
Recycling of end-of-life building glass
Recycling of end-of-life building glass Glass for Europe s contribution June 2013 The increased attention paid to resource efficiency, sustainable use of natural resources and sustainable buildings has
BES 6001 Issue 3 Guidance Document
BES 6001 Issue 3 Guidance Document This guide is intended to give an understanding of BES6001:2014 Framework Standard for Responsible Sourcing. It is not a controlled document. 3.2.1 Responsible Sourcing
COFELY DISTRICT ENERGY DELIVERING LOW CARBON SUSTAINABLE ENERGY SOLUTIONS
COFELY DISTRICT ENERGY DELIVERING LOW CARBON SUSTAINABLE ENERGY SOLUTIONS UK s largest provider of Direct Energy schemes COFELY District Energy is the UK s largest district energy company serving users
Calculating the cost of HVAC air filters
Thomas Carlsson R&D Director Table of Contents: Abstract 2 Background 3 Project Aim 3 Results 4 Conclusions 6 Abstract A computer program for calculating and optimising the filter cost in a ventilation
EHV Cable Installation Technology for Tunnels and Ducts in Japan. S. TSUCHIYA T. IIDA Y. MORISHITA Tokyo Electric Power Company
21, rue d Artois, F-75008 PARIS B1_109_2012 CIGRE 2012 http : //www.cigre.org EHV Installation Technology for Tunnels and Ducts in Japan S. TSUCHIYA T. IIDA Y. MORISHITA Tokyo Electric Power Company Kansai
Comparison between Gas- and Air Insulated Network Concepts with the Life Cycle Cost Method
Comparison between Gas- and Air Insulated Network Concepts with the Life Cycle Cost Method Ingo Jeromin, Gerd Balzer, Technische Universität Darmstadt, Jürgen Backes, Richard Huber, EnBW Regional AG Stuttgart
6 CONSIDERATION OF ALTERNATIVES
6 CONSIDERATION OF ALTERNATIVES 6.1.1 Schedule 4 of the Town and Country Planning (Environmental Impact Assessment) (Scotland) Regulations 2011 sets out the information for inclusion in Environmental Statements
Ampacity simulation of a high voltage cable to connecting off shore wind farms
Ampacity simulation of a high voltage cable to connecting off shore wind farms Eva Pelster 1, Dr. David Wenger 1 1 Wenger Engineering GmbH, Einsteinstr. 55, 89077 Ulm, [email protected] Abstract:
WHITEPAPER CABLE CONDUCTOR SIZING
WHITEPAPER CABLE CONDUCTOR SIZING FOR MINIMUM LIFE CYCLE COST Bruno De Wachter, Walter Hulshorst, Rodolfo di Stefano July 2011 ECI Available from www.leonardo-energy.org/node/156451 Document Issue Control
ENERGY EFFICIENT DATA CENTRES AND STORAGE. Peter James University of Bradford
ENERGY EFFICIENT DATA CENTRES AND STORAGE Peter James University of Bradford ABOUT US 1998 Co-founded world s first NGO on GreenIT EU Expert Advisors/Project Managers on ICT & Energy Efficiency; Environmental
SAMI Microstar (SAMI MM, MD, MS)
1 ABB Oy 18.2.2000 Product Support TLC/Ari Niskanen SAMI Microstar (SAMI MM, MD, MS) Recycling information for drive of type SAMI Microstar Table of contents TABLE OF CONTENTS...1 1. INTRODUCTION...2 2.
XLPE PRODUCTION PLANT FOR THIRUVALLA UNIT OF TRACO CABLE LTD
PROJECT PROFILE ON XLPE PRODUCTION PLANT FOR THIRUVALLA UNIT OF TRACO CABLE LTD Prepared by: TRACO CABLE COMPANY LIMITED IV TH FLOOR, KSHB OFFICE COMPLEX PANAMPILLY NAGAR KOCHI-682036 September 2012 PROJECT
DISCUSSION OF CROSS-LINKED POLYETHYLENE INSULATED CABLES FOR UNDERGROUND PORTIONS OF THE MIDDLETOWN-NORWALK 345 kv PROJECTS.
DISCUSSION OF CROSS-LINKED POLYETHYLENE INSULATED CABLES FOR UNDERGROUND PORTIONS OF THE MIDDLETOWN-NORWALK 345 kv PROJECTS December 20, 2004 David W. Forrest Rachel I. Mosier 1. EXECUTIVE SUMMARY CL&P
Undergrounding high voltage electricity transmission lines. The technical issues
Undergrounding high voltage electricity transmission lines The technical issues Contents Introduction 03 National Grid electricity transmission 03 an overview Section 1 Insulating underground cables 04
Environmental Certification BMW i3
Environmental Certification BMW i3 Goal, scope and system boundary: The scope of the study was an environmental assessment of all processes and materials involved in the product life cycle of BMW i3. All
Waste management and disposal:
Waste management and disposal: A best practice business guide An ebook produced by FCC Environment 01 Waste management and disposal: a strategy for success Introduction Your guide to waste management FCC
Environmental Benefits of Thin Computing A comparison of the environmental impacts of conventional desktop and thin computing
Environmental Benefits of Thin Computing A comparison of the environmental impacts of conventional desktop and thin computing This White Paper has been prepared for Wyse Technology Inc. March 2009 Overview
Resource efficiency in the UK whisky sector
Case Study: UK Drinks Sector Resource efficiency in the UK whisky sector Reducing water, material and packaging use in the whisky sector. Resource efficiency in the UK whisky sector 2 WRAP s vision is
Electricity Terminology. Simplifying energy management
Simplifying energy management AMR Automated Meter Reading - automatic collection of data from meters which is transferred to a central database for billing and/or analysis. Balancing Mechanism The mechanism
TAN δ (DELTA) CABLE TESTING OVERVIEW AND ANSWERS TO FREQUENTLY ASKED QUESTIONS. What Is Tan δ, Or Tan Delta?
TAN δ (DELTA) CABLE TESTING OVERVIEW AND ANSWERS TO FREQUENTLY ASKED QUESTIONS What Is Tan δ, Or Tan Delta? Tan Delta, also called Loss Angle or Dissipation Factor testing, is a diagnostic method of testing
ES281 COMPANY-SPECIFIC APPENDICES TO ENA ENGINEERING RECOMMENDATION G81 PART 1
ES281 COMPANY-SPECIFIC APPENDICES TO ENA ENGINEERING RECOMMENDATION G81 PART 1 Design and Planning Specification for New Low Voltage Installations for Housing Developments 1. SCOPE This appendix to ENA
HUGO BOSS ENVIRONMENTAL COMMITMENT. Our claim. Our approach
HUGO BOSS ENVIRONMENTAL COMMITMENT HUGO BOSS assumes responsibility for future generations. This entails that we also pursue our high standards for quality and performance in environmental protection.
CABLE ASSET MANAGEMENT PREDICT WITH CERTAINTY. Kuljit Singh BSc Honours MIEE(IET,UK) 5 June 2014
CABLE ASSET MANAGEMENT PREDICT WITH CERTAINTY Kuljit Singh BSc Honours MIEE(IET,UK) 5 June 2014 Definitions International Workshop 2014 DTS: Distributed Temperature Sensor DCR: Dynamic Cable Ratings (
MEASUREMENTS OF THRUST LOAD IN CABLE SYSTEMS SEMI-RIGIDLY INSTALLED IN DUCT / MANHOLE STRUCTURES
MEASUREMENTS OF THRUST LOAD IN CABLE SYSTEMS SEMI-RIGIDLY INSTALLED IN DUCT / MANHOLE STRUCTURES Riccardo BODEGA, Prysmian Cables and Systems, The Netherlands, [email protected] Henk GEENE,
SSE s criteria used for GHG emissions reporting
SSE s criteria used for reporting 1 Introduction This document details the annual greenhouse gas emissions reporting approach used by SSE Plc to report the tonnes of carbon dioxide equivalent (CO2e) during
Intensium Max. A range of ready-to-install containerised energy storage for renewable energies and grid management
Intensium Max A range of ready-to-install containerised energy storage for renewable energies and grid management Saft Li-ion technology covers every energy storage need from kilowatts to megawatts The
MV CABLE TYPE C 33-226
MV CABLE TYPE C 33-226 Standards : CENELEC HD 620 C 33-226 Rated voltage Rated voltage : 12/20 (24) kv Design 1 Stranded aluminium, class 2 conductor 2 Extruded conducting screen on conductor 3 XLPE insulation
NETWORK OUTPUT MEASURES CONSULTATION
NETWORK OUTPUT MEASURES CONSULTATION Great Britain s electricity transmission network transmits high-voltage electricity from where it is produced to where it is needed throughout the country. It broadly
Environmental Product Declaration
Environmental Product Declaration PVDF-System According to EN 15804 Circling and distribution of purified water in a pharmaceutical plant Georg Fischer Piping Systems Ltd. Ebnatstrasse 111 CH-8201 Schaffhausen
GHG Protocol Product and Supply Chain Initiative. Proposed List of Technical Topics
Page 1 World Business Council for Sustainable Development GHG Protocol Product and Supply Chain Initiative Proposed List of Technical Topics Seven technical working groups have been established to develop