Lifetone Technology HLAC150-series Bedside Fire Alarm and Clock Specifications and Features

Size: px
Start display at page:

Download "Lifetone Technology HLAC150-series Bedside Fire Alarm and Clock Specifications and Features"

Transcription

1 Lifetone Technology HLAC150-series Bedside Fire Alarm and Clock Specifications and Features 1. INTRODUCTION AND DEVICE CLASSIFICATION 2. PRODUCT SAFETY LISTINGS 3. STANDARDS AND REGULATORY COMPLIANCE 4. SMOKE ALARM INPUT SENSITIVITY 5. EMERGENCY ALARM AND ALERTING OUTPUTS 6. SAFETY AND INTERNAL MONITORING 7. POWER 8. DURABILITY 9. TESTING 10. ADDITIONAL FUNCTIONALITY 11. DIMENSIONS AND WEIGHT 1. INTRODUCTION AND DEVICE CLASSIFICATION The HLAC Bedside Fire Alarm & Clock is a UL-listed accessory to single- and multiplestation smoke alarms, as defined by UL 217, Standard for Safety for Single- and Multiple- Station Smoke Alarms. It is AC-powered with 7-day battery backup. The HLAC combines an alarm clock with acoustic smoke-alarm detection. Its output includes a UL 217-compliant low-frequency (520 Hz) acoustic alarm and UL compliant tactile alerting by means of a vibrating disk called a bed shaker. These two technologies have been shown to be most effective for waking and emergency arousal of children, people with hearing loss, older adults, and people intoxicated by alcohol. Those groups comprise the people most at risk of dying in a nighttime fire emergency in the United States. Because of these scientific findings, the residential and commercial chapters of NFPA 72 (2010 edition, Ch. 7, Ch. 11) have been recently reviewed and updated to mandate lowfrequency (520 Hz) square-wave smoke or fire alarms in residences and commercial sleeping rooms occupied by people with hearing loss. In time this will extend to all commercial sleeping rooms. The HLAC meets these requirements. 2. PRODUCT SAFETY LISTING 2.1. The HLAC is listed by UL to UL 217 Standard for Safety for Single- and Multiple- Station Smoke Alarms, Sixth Edition, October 2008, with revisions through October The HLAC is listed by UL as a low-frequency sounder, for use with both residential smoke alarms and commercial notification appliances, with or without optional bed shaker The HLAC is listed by UL to UL 1971 Signaling Devices for the Hearing Impaired when used with bed shaker Listings may be verified by means of the UL Online Certifications Directory by searching with "Lifetone Technology" or "S24639" (the Lifetone Technology file number). Click on the category label on the right of the search results to view the listing file card with details about the listing. HLAC150-series Specifications & Features Page 1 of 7

2 3. STANDARDS AND REGULATORY COMPLIANCE UL 217, ULC S531, and UL 1971 as described in Section 2, Product Safety Listings National Fire Alarm Code NFPA 72, 2007, and subsequent editions through Meets pending NFPA 72 requirements and recommendations through ANSI S Audible Emergency Evacuation Signal, 1990 ISO-8201 Audible Emergency Evacuation Signal, 1987 RoHS compliant Complies with California Proposition SMOKE ALARM INPUT SENSITIVITY 4.1. The HLAC detects acoustic T-3 smoke-detector alarm sounds, defined by ISO 8201, UL 217, NFPA 72 and ANSI S3.41, in the range of 2800 Hz to 3600 Hz. 1 The T-3 temporal pattern 2 is illustrated here: 4.2. The HLAC detects T-3 alarm sounds at 10 dba above relatively stable background noise levels up to 85 dba. At low and stable background noise levels (20 to 30 dba), sensitivity may be greater The response time is 30 seconds, or seven T-3 cycles, within the specified sensitivity level The HLAC150 series uses an adaptive threshold algorithm to provide optimized sensitivity where desirable, in order to minimize nuisance alarms or HLAC alarm cascade in installations with multiple HLAC units. 3 1 Standards in effect prior to 2014 do not specify the frequency of the T-3 evacuation signal of a smoke alarm. Smoke alarms typically use piezo crystal sounders that operate in that range. Sounders using speakers or bells have harmonics in that range. 2 UL 217, 6th Ed, Oct 2008, section 34.3, requires a T-3 signal period of 4 seconds ±10% for at least the first eight cycles of the smoke alarm output. The installed base contains a significant number of T-3 smoke alarms that exceed this tolerance. The HLAC150 series responds to T-3 periods ranging from 2.8 to 5.4 seconds in duration. However, the T-3 period is required to be consistent for at least the first eight T-3 cycles. Some First Alert talking alarms made in 2010 and before do not meet this UL 217 requirement and therefore are not compatible with the HLAC. 3 The HLAC will detect and respond to the sound of another HLAC alarm. This is useful in environments such as large residences with single-station alarms. But it may be a nuisance in other environments, such as adjacent apartments where testing with live smoke alarms is required. If the HLAC150 series is set up with a nearby in-room alarm, the adaptive threshold will allow it to ignore an HLAC alarm from an adjacent apartment, assuming 20 dba of sound attenuation provided by walls and distance. HLAC150-series Specifications & Features Page 2 of 7

3 4.5. The threshold is established during setup. The user is instructed to set up the HLAC150 series with the most distant smoke alarm that should be detected. The HLAC sets its threshold to that sound-pressure level minus 10 db, making the unit sensitive to a slightly fainter alarm than the one used at setup. There is no adaptive effect if the sound-pressure level of the setup alarm is below 20 dba, and sensitivity will be at a maximum in normal operation (section 4.2). In the case of multiple interconnected alarms, Lifetone recommends that the HLAC be set up with the nearest smoke alarm, to minimize interference from more distant asynchronous alarms An enhanced sensitivity mode is initiated for 2 minutes when the HLAC is silenced. The sound level required for detection in enhanced sensitivity mode is the same as that for the normal mode, but only two T-3 cycles are required. 5. EMERGENCY ALARM AND ALERTING OUTPUTS 5.1. The HLAC emits a low-frequency (520 Hz) acoustic emergency alarm tone in the international T-3 evacuation signal pattern (UL 217, section 34.3; NFPA 72; ANSI S3.41; and ISO 8201), in addition to flashing a "FIRE" message and activating a vibrating bed shaker The HLAC150 series also interpolates a loud baritone voice message saying "Fire! Get out!" into the 1.5-second interval between the sets of T-3 pulses The T-3 emergency alarm acoustic power is at least 85 dba at 3 feet or at the pillow (UL 217 section 65.4) The bed-shaker alerting device is provided as standard equipment, with provision for optional use The pulsating emergency bed shaker alarm pattern and vibration signal strength are as specified by UL 1971 section , b The emergency alarm will cease after 10 minutes if not silenced. However, the HLAC enters enhanced-sensitivity mode for 2 minutes, and will sound the alarm again within 15 seconds if the smoke alarm signal recurs or is still present There is a temporary silence function for the HLAC emergency alarm (UL 217 section 7.1) that is activated by pressing the TEST/SILENCE button on the back of the unit. However, if the smoke alarm signal remains present, the HLAC will declare an alarm again within 15 seconds To alert the user to missing or depleted batteries, the HLAC employs acoustic, visual (flashing orange screen with "BATT"), and tactile (vibratory) stimuli Bed-shaker status and fault condition alerts are provided by acoustic and visual (flashing orange screen with "beds", in the case of a fault) messages. An LCD icon indicates that the bed shaker is plugged in The bed shaker is a standard accessory, but its use is optional. The HLAC can be set up to operate without a bed shaker by not plugging it in at setup. If set up with the bed shaker, the HLAC can be reconfigured without the bed shaker by conducting a manual self test without the bed shaker. To restore use of the bed shaker, it need only be plugged back in at any time Absence of AC power is indicated by an unlit power LED and by a flashing wall plug icon on the LCD screen. HLAC150-series Specifications & Features Page 3 of 7

4 6. SAFETY AND INTERNAL MONITORING 800 Research Parkway, Suite The HLAC will detect only smoke alarms that emit a UL 217-compliant T-3 smoke alarm signal (UL 217, 34.3). Because there are older alarms in the installed base that do not use a T-3 smoke alarm signal, the HLAC requires a smoke alarm compatibility test when power is applied As a fail-safe feature, the HLAC constantly monitors its internal program functioning and integrity. In the event of a failure of the detection program, there will be acoustic, LCD visual (flashing orange screen with "8888"), and tactile (vibratory) alerts The unit cannot be used for any purpose while a program failure alert is in progress, and all power must be removed to stop it. The unit cannot be used as a stand-alone daily alarm clock if the smoke-alarm detection program fails Emergency detection and alarm output take precedence over the wakeup alarm function and battery and bed-shaker error notification (UL 217 section 6.1) There is capability for simultaneous display of multiple user-correctable status notifications as flashing text and icons on the LCD screen, including low-battery condition and bed-shaker faults The bed shaker is water resistant to a level 3 standard ingress-protection (IP) condition code, defined by IEC 60529, Degrees of Protection Provided by Enclosures. The bed shaker is washable and spray resistant but will not withstand immersion There is continuous bed-shaker supervisory monitoring and error notification for an electrical open or short-circuit condition at 2-second intervals unless the unit has been configured to operate without the bed shaker There is monitoring of the bed-shaker connection status at 2-second intervals, independent of bed-shaker open or short status, with error notification for a disconnected condition at 5-second intervals, unless the unit has been configured to operate without the bed shaker The bed shaker will cease operation if the case temperature exceeds 110 F (43.3 C), and will resume operation when temperature falls below 100 F (37.8 C). The bed shaker will operate for at least 12 minutes before case temperature exceeds the upper limit There is no electrical power exposed at the bed-shaker connection if the bed shaker is not connected, or if the bed shaker is open or short There is provision for functional self-test of acoustic input and output functions and the optional bed shaker at first power-on, and manually at user discretion. If a self-test is failed, an unmistakable failure notification is presented (described in sections 6.2 and 6.3), and the unit cannot be used as a clock alone The HLAC enforces the requirement for the presence of functional external smoke alarms when power is first applied. If an active UL 217-compliant T-3 smoke alarm is not present and functional during the setup test, the failure notification is presented until all power is removed. The unit cannot be set up as a stand-alone clock. 4 4 Because there are some older homes with smoke alarms made before 1999 that may use a different audible signal, the presence of T-3 alarms cannot be assumed, but must be demonstrated when the unit is installed. The smoke alarm compatibility or setup test required by the power-up sequence enforces this. See user documentation for procedural details. HLAC150-series Specifications & Features Page 4 of 7

5 6.13. At setup, the HLAC150 series requires two consecutive T-3 cycles from a smoke detector Silencing the HLAC emergency alarm does not disable detection. The unit places itself in enhanced-sensitivity mode for 2 minutes after the alarm is silenced Sensitivity is enhanced after silencing to minimize the potential for ignoring an emergency alarm. The HLAC will respond to a continued T-3 alarm within 15 seconds. In the event of a smoke-detector false alarm from cooking aerosols, the smoke alarm must be silenced first, and then the HLAC Bedside Fire Alarm and Clock. Otherwise the HLAC will detect the smoke alarm again within 15 seconds. 7. POWER 7.1. The HLAC is AC powered, with 7-day battery backup (UL 217 section 14.1, , ). The unit will operate on batteries for a period of 168 cumulative hours without AC power, and provide 10 minutes of full-power alarm output The power supply is an AC/DC Class II UL-approved power adapter. Input: volts, 50/60 Hz, 500 ma. Output: 1.5 A, 6.5 VDC. Plug style: NEMA 1-15, unpolarized Battery monitoring and low-battery alert is in accordance with UL 217 section A low-battery alert is issued at 1-minute intervals when the remaining power is insufficient for 24 hours of operation on battery alone There is a visible AC power indicator (UL 217 section ) in the form of a red LED The bed shaker contains a 6 VDC, 1-amp motor with an eccentric weight. Power is supplied by a 6-foot cord and plug to make it detachable. 8. DURABILITY 8.1. The endurance and physical-abuse resistance of the HLAC clock and alarm detection unit are to standards specified by applicable portions of UL 217 (sections 47-49, 50-51, 53-54, 56-58, 66, 69, 71, and 76) The bed-shaker endurance and physical-abuse resistance are to standards specified by UL 1971 sections 31, 34, 42, 43, 44, and The bed shaker offers an expected service life of 120 cumulative hours of activation The bed shaker is water resistant to a level-3 ingress-protection (IP) standard as defined by IEC The bed shaker is not immersible. 9. TESTING 9.1. The HLAC has a manual test function initiated by pressing the TEST/SILENCE button on the back of the unit when an alarm is not in progress. When the TEST/SILENCE button is pressed, the HLAC displays "TEST" on the screen and conducts a test of its microphone, speaker, and alarm output. This is similar to the audible test function provided by smoke alarms, with the addition of the microphone and speaker test In addition to the manual test of microphone, speaker, and alarm output, the HLAC may be functionally tested with all of a user's installed smoke alarms by first simulating an emergency by presenting 7 or 8 consecutive T-3 signals to initiate an HLAC alarm. This is most easily accomplished by means of a smoke alarm that will HLAC150-series Specifications & Features Page 5 of 7

6 produce T-3 signals as long as the test button is held down. After silencing by the button on the back, the HLAC operates in enhanced sensitivity mode for 2 minutes. During that time the HLAC will respond to two T-3 cycles of a smoke alarm. Each time such an alarm is detected and the HLAC is silenced with the silence button, the 2-minute period of enhanced sensitivity begins again. The user may move from one smoke alarm to another inside the 2-minute time windows, testing with each one, to establish the limits of detection in a household with multiple smoke alarms. The adaptive threshold is active during the functional test, so the actual smoke alarm sound level required for detection during normal operation is demonstrated during functional testing. 10. ADDITIONAL FUNCTIONALITY The HLAC is a full-function bedside wake-up alarm clock There is a large-digit 12- or 24-hour time display of inches (29 mm) Clock accuracy is ±1 second per day on main AC power or battery backup power There is an acoustic (520 Hz intermittent tone), visual (flashing time display), and (vibratory) wake-up alarm The 520 Hz wake-up alarm tone is a rapid, fixed-interval, adjustable-volume tone that is easily distinguishable from the T-3 emergency signal The tactile wake-up alert is a constant vibration easily distinguished from the pulsating emergency alarm The wake-up alarm has high and low volume levels. However, the emergency alarm is always sounded at maximum volume When on backup power, the wake-up alarm will sound once during the first 24 hours of a sustained AC power outage. The ensures a reliable wake-up function if a temporary power outage happens to coincide with the time the wake-up alarm is scheduled The illuminated LCD time display offers three levels of brightness (high, low and off). When on AC power, the LCD time display is lit at the selected level of brightness When on backup battery power the LCD screen is off, but when the SNOOZE bar is pressed the LCD screen is illuminated for 5 seconds The day of the week is displayed in addition to the calendar date The 12/24 hour format for time of day and alarm time display is selectable There is a 10-minute repeating snooze function for the wake-up alarm. An alarm status icon flashes during the silent snooze period to indicate that the wake-up alarm is still active The HLAC is a fire safety device; the clock function is secondary. Therefore the unit must be set up with a smoke alarm. The HLAC cannot be used for the alarm clock function alone. 11. DIMENSIONS AND WEIGHT The main unit measures approximately 8½" wide 4½" high 3¾" deep, excluding the AC power cord. The power cord is 6' long. HLAC150-series Specifications & Features Page 6 of 7

7 11.2. The main unit weighs approximately 1½ lb without batteries, or 2 lb 12 oz with batteries inserted The bed shaker attachment, excluding cord, measures approximately 4" in diameter 1¼" thick. The bed-shaker cord is 6' long The bed shaker weighs approximately 7 oz. Lifetone Doc #HLACFS HLAC150-series Specifications & Features Page 7 of 7

Low Frequency Notification Appliances

Low Frequency Notification Appliances A P P L I C A T I O N S G U I D E Low Frequency Notification Appliances APPLICATIONS GUIDE: LOW FREQUENCY NOTIFICATION APPLIANCES Low Frequency Notification Appliances Contents Introduction...3 Waking

More information

User Manual of WT 493

User Manual of WT 493 User Manual of WT 493 Introduction Congratulations on your purchase of this smart unit. This unit can be used as a radio to catch the latest news and enjoy the beautiful music; it can also be used as an

More information

FIRE CODE INTERPRETATION

FIRE CODE INTERPRETATION FIRE CODE INTERPRETATION March 2008 ISSUE: Existing Fire Alarm Systems FCI-08-06 Page 1 of 9 The purpose of this bulletin is to identify conditions where a building fire alarm system may be subject to

More information

Technological Advances in Smoke Alarms

Technological Advances in Smoke Alarms Technological Advances in Smoke Alarms Introduction Smoke alarms are designed to detect a fire in its early stages and alert people so they have time to safely escape the dwelling unit or building. The

More information

LTR Series Uninterruptible Power Systems 700 VA - 2.1 KVA. General Specification

LTR Series Uninterruptible Power Systems 700 VA - 2.1 KVA. General Specification 08/17/12 Rev2 LTR Series General Specification 700 VA to 2.1 KVA 1.0 General LTR Series Uninterruptible Power Systems 700 VA - 2.1 KVA General Specification This specification describes the features and

More information

SPECIAL CODES AUXILIARY CODES SYSTEM NOTES

SPECIAL CODES AUXILIARY CODES SYSTEM NOTES Installing/Service Company Monitoring Center SPECIAL CODES Master Code Duress Code AUXILIARY CODES "Quick Arm" " Chime" 08 02 09 03 10 04 11 05 12 06 13 07 14 SYSTEM NOTES Exit Delay Time Entry Delay Time

More information

CHANGES IN NFPA 72 NATIONAL FIRE ALARM CODE 1999 2002

CHANGES IN NFPA 72 NATIONAL FIRE ALARM CODE 1999 2002 CHANGES IN NFPA 72 NATIONAL FIRE ALARM CODE 1999 2002 Three new chapters were added. What was chapter 1 in 1999 was reorganized into chapters 1 (Fundamentals), 2 (Referenced Publications), and 3 (Definitions).

More information

Programming Guide. http://www.reecominc.com. Model: R-1630C

Programming Guide. http://www.reecominc.com. Model: R-1630C Programming Guide S.A.M.E Digital Weather / All Hazards Alert Radio CEA-2009-A Certified Alert Receiver Model: R-1630C Public Alert Certified Reecom Electronics Inc. http://www.reecominc.com Features:

More information

527 CMR: BOARD OF FIRE PREVENTION REGULATIONS

527 CMR: BOARD OF FIRE PREVENTION REGULATIONS 527 CMR 31.00: CARBON MONOXIDE ALARMS Section 31.01: Purpose and Scope 31.02: Definitions 31.03: General Installation Provisions 31.04: Specific Installation Provisions 31.05: Carbon Monoxide Protection:

More information

CITY OF PHILADELPHIA DEPARTMENT OF LICENSES AND INSPECTIONS ANNUAL CERTIFICATION FOR FIRE ALARM SYSTEMS

CITY OF PHILADELPHIA DEPARTMENT OF LICENSES AND INSPECTIONS ANNUAL CERTIFICATION FOR FIRE ALARM SYSTEMS CITY OF PHILADELPHIA DEPARTMENT OF LICENSES AND INSPECTIONS ANNUAL CERTIFICATION FOR FIRE ALARM SYSTEMS PROPERTY ADDRESS (BRT Address Required) TESTING CONTRACTOR (Name and Address) License No. ANNUAL

More information

MXD3G User Manual Revision 0 July 29, 2013

MXD3G User Manual Revision 0 July 29, 2013 MXD3G User Manual Revision 0 July 29, 2013 Manufactured by Mytrex, Inc. 10321 South Beckstead Lane South Jordan, UT 84095 (801) 571-4121, Fax (801) 571-4606 Toll Free (800) 688-9576, Fax (877) 571-4606

More information

ERS-2400B. PERS-2400B Personal Emergency Reporting System

ERS-2400B. PERS-2400B Personal Emergency Reporting System PERS-2400B Personal Emergency Reporting System ERS-2400B Durability and Versatility for Emergency Reporting Solutions Create a customized and comprehensive Personal Emergency Reporting System with the

More information

Weather Radio Alarm Clock

Weather Radio Alarm Clock 1200093 User s Guide Weather Radio Alarm Clock Thank you for purchasing your Weather Radio Alarm Clock from RadioShack. Please read this user s guide before installing, setting up, and using your new weather

More information

-Helping to make your life betterwww.person-to-person.net

-Helping to make your life betterwww.person-to-person.net Household Telephone Management System Built on Interceptor ID Technology Owner/Operation Manual Telephone Management System- Model P2P101 Call Receiver - Model P2P301 (Receiver may be sold separately)

More information

SECURITY SYSTEM NOTES SPECIAL CODES ENTRY / EXIT DELAY TIMES ARM / DISARM CODES

SECURITY SYSTEM NOTES SPECIAL CODES ENTRY / EXIT DELAY TIMES ARM / DISARM CODES SECURITY SYSTEM NOTES Installing/Service Company For Service Call SPECIAL CODES "Chime" Digit 1 "Partial Arm" Digit 2 "Quick Arm" Digit 3 ENTRY / EXIT DELAY TIMES Exit Delay Time Entry Delay Time Secondary

More information

SECTION 13850 DETECTION AND ALARM

SECTION 13850 DETECTION AND ALARM SECTION 13850 DETECTION AND ALARM PART 1 GENERAL 1.01 SUMMARY A. Section Includes 1. Control Panel 2 Associated Equipment B. Products Installed But Not Supplied Under This Section 1. Section 16140 - Wiring

More information

Carbon Monoxide (CO) Detection PRODUCTS. Accessories Conventional Detectors

Carbon Monoxide (CO) Detection PRODUCTS. Accessories Conventional Detectors Carbon Monoxide (CO) Detection PRODUCTS Accessories Conventional Detectors 2 Complete CO Detection The system-connected CO1224T and CO1224TR CO detectors with RealTest provide early warning by using reliable

More information

PORTABLE ALARM CLOCK. Dual Alarm. FM Radio. Wake-up Sounds. USB Phone Charger G-1CR

PORTABLE ALARM CLOCK. Dual Alarm. FM Radio. Wake-up Sounds. USB Phone Charger G-1CR G-BUZZ PORTABLE ALARM CLOCK Dual Alarm FM Radio Wake-up Sounds USB Phone Charger G-1CR Welcome Alarm clocks can be boring. Get ready to shake things up with your new G-BUZZ. Slap the snooze for more ZZZ

More information

NetworX NX-6V2. LED Keypad User Manual

NetworX NX-6V2. LED Keypad User Manual NetworX NX-6V2 LED Keypad User Manual POWER Light is on when AC power is present; flashes to indicate a low battery condition. ARMED Light is on when armed; off when disarmed; flashes to indicate a previous

More information

GC2 Panel User Guide

GC2 Panel User Guide GC2 Panel User Guide ENGLISH (International) WIRELESS SECURITY SYSTEM WARNING: OWNER S I NSTRUCTION NOTICE Not to be removed by anyone except occupant THIS PAGE INTENTIONALLY LEFT BLANK CONTENTS System

More information

OHIO BOARD OF BUILDING STANDARDS. Smoke Alarms and Fire Safety

OHIO BOARD OF BUILDING STANDARDS. Smoke Alarms and Fire Safety OHIO BOARD OF BUILDING STANDARDS Smoke Alarms and Fire Safety Updated January 2016 2 UNDERSTANDING THE TERMINOLOGY Detector. An initiation device suitable for connection to a circuit that has a sensor

More information

2007 ICC FINAL ACTION AGENDA

2007 ICC FINAL ACTION AGENDA 907.2.1.1 System initiation in Group A occupancies with an occupant load of 1,000 or more. Activation of the fire alarm in Group A occupancies with an occupant load of 1,000 or more shall initiate a signal

More information

SECURITY SYSTEM NOTES AREA LISTINGS SPECIAL CODES ENTRY / EXIT DELAY TIMES ARM / DISARM CODES ZONE DESCRIPTIONS

SECURITY SYSTEM NOTES AREA LISTINGS SPECIAL CODES ENTRY / EXIT DELAY TIMES ARM / DISARM CODES ZONE DESCRIPTIONS SECURITY SYSTEM NOTES Installing/Service Company For Service Call Area 1 Area 2 Area 3 AREA LISTINGS SPECIAL CODES "Quick Arm" Digit "Partial Arm" Digit "Chime" Digit ENTRY / EXIT DELAY TIMES Exit Delay

More information

Lockout Specification BW Clip Maintenance-free single gas detector

Lockout Specification BW Clip Maintenance-free single gas detector Lockout Specification BW Clip Maintenance-free single gas detector The gas detector must satisfy the following. Physical Specifications Size (d x w x h ) Physical detector size shall be no larger than

More information

Sonic Boom Travel & Bed side Alarm Clock with Bed Shaker Model SB200ss-v3

Sonic Boom Travel & Bed side Alarm Clock with Bed Shaker Model SB200ss-v3 Sonic Boom Travel & Bed side Alarm Clock with Bed Shaker Model SB200ss-v3 IMPORTANT Please read these instructions carefully before use and retain for future reference. See operating instructions on back.

More information

The Mission Critical Fire Protection Experts

The Mission Critical Fire Protection Experts The Mission Critical Fire Protection Experts Protection Systems Protection Systems HFC-227ea / FM200 / FE-227 FE-25 / ECARO-25 Novec 1230 Inergen / Argonite Halon Drop-in Systems High and Low Pressure

More information

CLARK COUNTY FIRE DEPARTMENT Fire Hazard & Prevention Services

CLARK COUNTY FIRE DEPARTMENT Fire Hazard & Prevention Services CLARK COUNTY FIRE DEPARTMENT Fire Hazard & Prevention Services 575 E. Flamingo Road, Las Vegas, NV 89119 (702) 455-7316 FAX (702) 455-7347 105.8a-6.1 TITLE: FIRE ALARM SYSTEM REQUIREMENTS SCOPE: This guideline

More information

Proposed changes to the Acceptable Solution for Building Code clause F7 (Warning Systems) Proposed amended Acceptable Solution for Warning Systems

Proposed changes to the Acceptable Solution for Building Code clause F7 (Warning Systems) Proposed amended Acceptable Solution for Warning Systems Proposed changes to the Acceptable Solution for Building Code clause F7 (Warning Systems) Appendix A Proposed amended Acceptable Solution for Warning Systems s in the grey boxes form part of the proposed

More information

SECTION 16853 ZONED (DC LOOP) FIREALARM SYSTEM

SECTION 16853 ZONED (DC LOOP) FIREALARM SYSTEM SECTION 16853 ZONED (DC LOOP) FIRE-ALARM SYSTEM PART 1 - GENERAL 1.1 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General and Supplementary Conditions and Division 1

More information

Cellular Medical Alert User s Guide

Cellular Medical Alert User s Guide Cellular Medical Alert User s Guide What s in the Box 70 F MAY 03 FRI 10:05 AM RESET 70 F Volume: 10:05 AM RESET RESET + TEST TEST Cellular Base Station Neck Pendant and/or Wrist Button Setup Guide Cellular

More information

SECURITY SYSTEM NOTES. EMERGENCY ACTIVATION KEYS (check if enabled) PROGRAMMED FUNCTIONS

SECURITY SYSTEM NOTES. EMERGENCY ACTIVATION KEYS (check if enabled) PROGRAMMED FUNCTIONS SECURITY SYSTEM NOTES Installing/Service Company For Service Call Installation Date / / Central Station Duress Code EMERGENCY ACTIVATION KEYS (check if enabled) Fire Auxiliary Emergency Police PROGRAMMED

More information

SECURITY SYSTEM NOTES SPECIAL CODES. Security System Configuration

SECURITY SYSTEM NOTES SPECIAL CODES. Security System Configuration Installing / Service Company: SECURITY SYSTEM NOTES For Service Call: Master Code SPECIAL CODES Duress Code Security System Configuration Auxiliary Code(s) Quick Arm" Digit: 2 9 3 10 4 11 5 12 6 13 7 14

More information

NC State University Design and Construction Guidelines Division 26 Fire Alarm Systems

NC State University Design and Construction Guidelines Division 26 Fire Alarm Systems NC State University Design and Construction Guidelines Division 26 Fire Alarm Systems 1.0 Purpose A. The following guideline provides the minimum standards and requirements for fire alarm systems. 2.0

More information

Fire Pump Controllers Remote Alarm Panels

Fire Pump Controllers Remote Alarm Panels Fire Pump Controllers Remote Alarm Panels Remote Alarm Panels 1.8 Remote Alarm Panels FDAP-M Electric... DFDAP-M Diesel... Product Specifications... 2 6 9 Features 1-1 DFDAP-M / FDAP-M Remote Alarm Panel

More information

SECURITY SYSTEM NOTES. Security System Configuration

SECURITY SYSTEM NOTES. Security System Configuration Installing / Service Company: For Service Call: SECURITY SYSTEM NOTES Security System Configuration Master Code: Auxiliary Code(s) 2 3 4 5 6 "Quick Arm" Digit: Exit Delay Time Auxiliary Exit Delay Time

More information

How To Make A Fire Alarm System More Effective

How To Make A Fire Alarm System More Effective $20.00 The Fire Alarm Requirements NFPA 72 & 101 ANSI 117.1 ADAAG Gentex Corporation Fire Protection Products Group 10985 Chicago Dr. Zeeland, MI 49464 1-800-436-8391 1-800-436-8392 (fax) As one of Gentex

More information

ADA COMPLIANT BOX STYLE TELEPHONE INSTALLATION, PROGRAMMING AND OPERATING INSTRUCTIONS FOR MODEL PBX

ADA COMPLIANT BOX STYLE TELEPHONE INSTALLATION, PROGRAMMING AND OPERATING INSTRUCTIONS FOR MODEL PBX ADA COMPLIANT BOX STYLE TELEPHONE INSTALLATION, PROGRAMMING AND OPERATING INSTRUCTIONS FOR MODEL PBX INSTALLATION INSTRUCTIONS Step 1. Determine the position for the Hands-free phone in the elevator phone

More information

OM2260VW2 USER MANUAL VERIZON WIRELESS HOME PHONE CONNECT

OM2260VW2 USER MANUAL VERIZON WIRELESS HOME PHONE CONNECT OM2260VW2 USER MANUAL VERIZON WIRELESS HOME PHONE CONNECT Welcome to Verizon Wireless Thank you for choosing Verizon Wireless Home Phone Connect. You re now connected to the power of America s most reliable

More information

Back-UPS Pro 1300/1500 Installation and Operation

Back-UPS Pro 1300/1500 Installation and Operation Back-UPS Pro 1300/1500 Installation and Operation Inventory Safety Do not install the Back-UPS in direct sunlight, in excessive heat, humidity, or in contact with fluids. Connect the battery bu059a bu058a

More information

SECURITY SYSTEM NOTES

SECURITY SYSTEM NOTES SECURITY SYSTEM NOTES Installing/Service Company For Service Call Central Station Duress Code FUNCTION CODES Function Code Controls Function This system is is not partitioned. EMERGENCY ACTIVATION KEYS

More information

SECURITY SYSTEM NOTES

SECURITY SYSTEM NOTES SECURITY SYSTEM NOTES Installing/Service Company For Service Call Central Station Duress Code FUNCTION CODES Function Code Controls Function EMERGENCY ACTIVATION KEYS (check if enabled) Fire Auxiliary

More information

Fire Alarm System Plans Submittal Guidelines For New and Existing Systems

Fire Alarm System Plans Submittal Guidelines For New and Existing Systems Fire Alarm System Plans Submittal Guidelines For New and Existing Systems SCOPE The Temecula Fire Prevention Bureau (TFPB) has established the following requirements for the submittal of all fire alarms,

More information

Wireless Security System

Wireless Security System Wireless Security System 2GIG-CNTRL2 (2GIG-CP2) User s Guide WARNING: Owner s Instruction Notice Not to be removed by anyone except occupant The Go!Control Security System Congratulations on your ownership

More information

FIRST ALERT INSTRUCTION MANUAL FOR FA 270 KEYPADS SECURITY SYSTEM

FIRST ALERT INSTRUCTION MANUAL FOR FA 270 KEYPADS SECURITY SYSTEM FIRST ALERT INSTRUCTION MANUAL FOR FA 270 KEYPADS SECURITY SYSTEM Page 0 Table of Contents Introduction 1 System Basics.. 1 Burglary Protection.. 1 Fire Protection.. 1 Security Codes. 1 Zones and Partitions

More information

Model SBB500SS-v3. Sonic Boom Alarm Clock & Bed Shaker OPERATION INSTRUCTIONS

Model SBB500SS-v3. Sonic Boom Alarm Clock & Bed Shaker OPERATION INSTRUCTIONS Model SBB500SS-v3 Sonic Boom Alarm Clock & Bed Shaker OPERATION INSTRUCTIONS IMPORTANT Please read these instructions carefully before use and retain for future reference. See operating instructions on

More information

Firmware version: 1.10 Issue: 7 AUTODIALER GD30.2. Instruction Manual

Firmware version: 1.10 Issue: 7 AUTODIALER GD30.2. Instruction Manual Firmware version: 1.10 Issue: 7 AUTODIALER GD30.2 Instruction Manual Firmware version: 2.0.1 Issue: 0.6 Version of the GPRS transmitters configurator: 1.3.6.3 Date of issue: 07.03.2012 TABLE OF CONTENTS

More information

527 CMR: BOARD OF FIRE PREVENTION REGULATIONS

527 CMR: BOARD OF FIRE PREVENTION REGULATIONS 527 CMR 24.00: FIRE WARNING SYSTEMS INSTALLED IN BUILDINGS WITHIN THE COMMONWEALTH OF MASSACHUSETTS Section 24.01: Purpose 24.02: Scope 24.03: Definitions 24.04: Approval of Design 24.05: Power Supply

More information

Module 5. Fire and Emergency Alarm System Part I- Basics

Module 5. Fire and Emergency Alarm System Part I- Basics Module 5 Fire and Emergency Alarm System Part I- Basics 1 This module will describe: 1. Components and the arrangements of components in fire and emergency alarm systems. 2. How these systems work. 3.

More information

Daker DK 1, 2, 3 kva. Manuel d installation Installation manual. Part. LE05334AC-07/13-01 GF

Daker DK 1, 2, 3 kva. Manuel d installation Installation manual. Part. LE05334AC-07/13-01 GF Daker DK 1, 2, 3 kva Manuel d installation Installation manual Part. LE05334AC-07/13-01 GF Daker DK 1, 2, 3 kva Index 1 Introduction 24 2 Conditions of use 24 3 LCD Panel 25 4 Installation 28 5 UPS communicator

More information

tattletale User Guide Consumer unit version 2.48 1 P a g e

tattletale User Guide Consumer unit version 2.48 1 P a g e tattletale User Guide Consumer unit version 2.48 1 P a g e Contents Basic 1... 4 Base Unit Features... 4 Initial Setup... 4 Arming... 5 Disarming... 5 Quiet Button... 5 Settings... 5 Settings 2... 6 Quick

More information

Installation and Operation Back-UPS 1250, 1300, 1500

Installation and Operation Back-UPS 1250, 1300, 1500 Installation and Operation Back-UPS 1250, 1300, 1500 Inventory bu001a Safety and General Information This unit is intended for indoor use only. Do not operate this unit in direct sunlight, in contact with

More information

Control/Communicator Installation Manual

Control/Communicator Installation Manual DAS NETWORX NX-8 Control/Communicator Installation Manual Page General Description... 2 Ordering Information... 2 Option Definitions... 2 Programming the LED Code Pads... 4 Programming the NX-8... 8 Types

More information

SPL 2-00/-01 OPERATION INSTRUCTIONS

SPL 2-00/-01 OPERATION INSTRUCTIONS SPL 2-00/-01 OPERATION INSTRUCTIONS Powerline Ethernet Adapter 500 Mbps EN Read and keep Operation Instructions SPL 2-00/-01 Safety Notes Do NOT use this product near water, for example, in a wet basement

More information

FIRE ALARM SYSTEM TECHNICAL SPECIFICATIONS Page 1 of 10

FIRE ALARM SYSTEM TECHNICAL SPECIFICATIONS Page 1 of 10 TECHNICAL SPECIFICATIONS Page 1 of 10 FIRE DETECTION AND ALARM SYSTEM Scope Furnish a complete 24V DC conventional, electrically supervised, zone annunciated, fire detection and alarm system as specified

More information

SMART SENSOR COLLECTION

SMART SENSOR COLLECTION TEMPERATURE SENSOR This sensor measures temperature in degrees Celsius or Fahrenheit. It works with all SensorHawk base units (SensorHawk-2, SensorHawk-8 and SensorHawk8/20) as well as the SecurityHawk-8

More information

RHODE ISLAND DIVISION OF STATE FIRE MARSHAL

RHODE ISLAND DIVISION OF STATE FIRE MARSHAL RHODE ISLAND DIVISION OF STATE FIRE MARSHAL Smoke Alarm and Carbon Monoxide Brochure JOHN E. CHARTIER STATE FIRE MARSHAL 118 PARADE STREET PROVIDENCE, RI 02909 DAYS 401-462-4200 24 Hr. 401-222-2331 FAX#

More information

Industrial-Grade UPS System Heavy-duty power protection for harsh industrial environments

Industrial-Grade UPS System Heavy-duty power protection for harsh industrial environments Industrial-Grade UPS System Heavy-duty power protection for harsh industrial environments Model #: SM2000RMX Heavy-duty, industrial-grade metal housings Shock and vibration rated to MIL-STD-810D 19 inch

More information

Module 4, Lesson 12 Fire Alarm Systems

Module 4, Lesson 12 Fire Alarm Systems Student Manual Module 4, Lesson 12 Fire Alarm Systems Performance Objectives At the conclusion of this lesson, you will be able to: Identify the components and functions of a fire alarm system and determine

More information

Residential Gateway (RG) Battery Backup

Residential Gateway (RG) Battery Backup Residential Gateway (RG) Battery Backup BU3DC000-12V User Manual Table of Contents Page Introduction... 3 Safety Information... 3 System Requirements... 3 Package Contents... 4 Recycling... 4 Product Layout

More information

How To Install A Carbon Monoxide Detector

How To Install A Carbon Monoxide Detector NASSAU COUNTY FIRE COMMISSION OFFICE OF THE FIRE MARSHAL Nassau County Public Safety Center 1194 Prospect Avenue Westbury, New York 11590 (516) 573-9900 / nassaucountyny.gov Chief Fire Marshal Scott D.

More information

USER MANUAL CHARGING STATIONS FOR ELECTRIC VEHICLES

USER MANUAL CHARGING STATIONS FOR ELECTRIC VEHICLES USER MANUAL CHARGING STATIONS FOR ELECTRIC VEHICLES 204.CAxxx 204.CBxxx 204.UBxxx 204.WBxxx MP36289 1 ZP90856-GB-6 INDICE 1 SYSTEM DESCRIPTION... 4 1.1 MODES OF OPERATION... 4 2 USER INTERFACE... 6 2.1

More information

SURGE PROTECTIVE DEVICES (SPDs) LOW VOLTAGE AC INTEGRATED SURGE PROTECTION FOR ELECTRICAL DISTRIBUTION SYSTEMS SECTION 16671A SECTION 16671A

SURGE PROTECTIVE DEVICES (SPDs) LOW VOLTAGE AC INTEGRATED SURGE PROTECTION FOR ELECTRICAL DISTRIBUTION SYSTEMS SECTION 16671A SECTION 16671A SURGE PROTECTIVE DEVICES (SPDs) INTEGRATED UNITS LOW VOLTAGE AC SURGE PROTECTION FOR ELECTRICAL DISTRIBUTION SYSTEMS PART 1 GENERAL 01 02 03 SCOPE The Contractor shall furnish and install the Surge Protective

More information

SMOKE DETECTOR INSTALLATION PROGRAM The Burlington Ordinance Perspective

SMOKE DETECTOR INSTALLATION PROGRAM The Burlington Ordinance Perspective SMOKE DETECTOR INSTALLATION PROGRAM The Burlington Ordinance Perspective The National Fire Alarm Code, NFPA 72, sets the minimum requirements of performance, selection, use and location of automatic detection

More information

Automatic Phone-Out Home Monitoring Systems

Automatic Phone-Out Home Monitoring Systems Automatic Phone-Out Home Monitoring Systems Power Outage and Freeze Alarm Model Number: THP202 Power Outage, Freeze and Flood Alarm Product Description Model Number: THP201 These monitoring systems are

More information

SFC-200 SERIES FIRE ALARM CONTROL PANELS. SFC-200 Series Fire Alarm Control Panels. Features. Description

SFC-200 SERIES FIRE ALARM CONTROL PANELS. SFC-200 Series Fire Alarm Control Panels. Features. Description SFC-200 SERIES FIRE ALARM CONTROL PANELS SFC-200 Series Fire Alarm Control Panels Description Summit s SFC-200 Series fire alarm control panels consist of six and twelve zone models which are equipped

More information

HONEYWELL COMMERCIAL FIRE/BURG PANEL UL LISTING REQUIREMENTS (Compiled from VistaFBPT Installation Instructions 800-09617V1 Rev A 11/12)

HONEYWELL COMMERCIAL FIRE/BURG PANEL UL LISTING REQUIREMENTS (Compiled from VistaFBPT Installation Instructions 800-09617V1 Rev A 11/12) HONEYWELL COMMERCIAL FIRE/BURG PANEL UL LISTING REQUIREMENTS (Compiled from VistaFBPT Installation Instructions 800-09617V1 Rev A 11/12) UL864 (Commercial Fire) Compliance General Requirements The VISTA-128FBPT/VISTA250FBPT

More information

EKOS Cart. Instructions for Use

EKOS Cart. Instructions for Use EKOS Cart Instructions for Use EKOS Corporation 11911 North Creek Parkway South Bothell, WA 98011 USA (425) 415-3100 (tel) (425) 415-3102 (fax) [email protected] (e-mail) - 1-4913-002 REV E Intended Use

More information

SECURITY SYSTEM NOTES SPECIAL CODES AUXILIARY ARM / DISARM CODES ENTRY / EXIT DELAY TIMES ZONE DESCRIPTIONS

SECURITY SYSTEM NOTES SPECIAL CODES AUXILIARY ARM / DISARM CODES ENTRY / EXIT DELAY TIMES ZONE DESCRIPTIONS SECURITY SYSTEM NOTES Installing/Service Company For Service Call SPECIAL CODES Master Code Duress Code "Quick Arm" Digit "Chime" Digit "Entry-Guard" Digit AUXILIARY ARM / DISARM CODES 02 12 22 03 13 23

More information

Using the UPSMON-Plus Monitoring Software

Using the UPSMON-Plus Monitoring Software Using the UPSMON-Plus Monitoring Software With UPSMON-Plus UPS Monitoring software, you can: Monitor battery level, load level, input and output current. Schedule daily, weekly, or monthly battery self

More information

Fire Alarm System Plans Review Checklist Property location Date of Review

Fire Alarm System Plans Review Checklist Property location Date of Review Fire Alarm System Plans Review Checklist Property location Date of Review 1. Is application completed in entirety? 2. Are the plans review fee submitted with the application? 3. Does floor plan include

More information

Wireless Security System

Wireless Security System Wireless Security System 2GIG-CP2 User s Guide WARNING: Owner s Instruction Notice Not to be removed by anyone except occupant The Go!Control Security System Congratulations on your ownership of a Go!Control

More information

User's Guide. Integrating Sound Level Datalogger. Model 407780. Introduction

User's Guide. Integrating Sound Level Datalogger. Model 407780. Introduction User's Guide 99 Washington Street Melrose, MA 02176 Phone 781-665-1400 Toll Free 1-800-517-8431 Visit us at www.testequipmentdepot.com Back to the Extech 407780 Product Page Integrating Sound Level Datalogger

More information

Using Your. Security System. With LED Keypad S5030, S5031, S5032

Using Your. Security System. With LED Keypad S5030, S5031, S5032 Using Your Security System With LED Keypad S5030, S5031, S5032 Contents 1 Overview Your Security System... 1 How Your Security System Works... 2 Your System's Programming... 3 Getting Used to Your System...

More information

Destiny 4100. Destiny 4100. Owners Manual

Destiny 4100. Destiny 4100. Owners Manual Destiny 4100 Destiny 4100 Owners Manual TABLE OF CONTENTS INTRODUCTION Control Panel...3 Detection Devices...3 Telephone Keypads...3 GLOSSARY... 4-5 LOCAL PHONE ACCESS Using Your Telephones As Keypads...6

More information

USER INSTRUCTIONS CONTENTS

USER INSTRUCTIONS CONTENTS CONTENTS Full Set [1]...2 Part Set [2]...2 Night Set [3]...3 Unsetting...3 Unsetting after or during an alarm...3 Testing the system [5]...3 Isolating zones [6]...4 Reprogramming codes [8]...4 Chime facility

More information

DELAWARE STATE FIRE MARSHAL FIRE ALARM SYSTEM CERTIFICATE OF INSTALLATION

DELAWARE STATE FIRE MARSHAL FIRE ALARM SYSTEM CERTIFICATE OF INSTALLATION Phone System Owner Phone System Engineered by: of Record Drawings: of System Manuals: of Test Reports: System Installer 1. GENERAL INFORMATION Phone Delaware License No: Certificate Holder No. System Supplier

More information

SOUND LEVEL METER 94405

SOUND LEVEL METER 94405 SOUND LEVEL METER 94405 INSTRUCTION MANUAL REC FAST A/C 1. SAFETY INFORMATION Read the following safety information carefully before attempting to operate or service the meter. Use the meter only as specified

More information

LCD -based Intelligent Burglar Alarm System. User Guide. Ver 2.0

LCD -based Intelligent Burglar Alarm System. User Guide. Ver 2.0 LCD -based Intelligent Burglar Alarm System User Guide Ver 2.0 Table of Content 1. Introduction... 2 1.1 General Description... 3 1.2 System Features... 3 2. Anatomy of the LCD-based Intelligence Burglar

More information

Rancho Cucamonga Fire Protection District Prevention Bureau Standard

Rancho Cucamonga Fire Protection District Prevention Bureau Standard Rancho Cucamonga Fire Protection District Prevention Bureau Standard Title: Fire Alarm and Monitoring Systems Standard # 9-3 Effective: May 2002 Number of Pages: 7 Revised: January 2014 INTENT The intent

More information

BS5839 Part 1:2002 Overview

BS5839 Part 1:2002 Overview BS5839 Part 1:2002 Overview 1 Contents Introduction So why is the current standard being revised? The brief for the new standard Changes to structure of current Standard Enhanced certification of Fire

More information

Conventional Fire Detection and Extinguishant Control System Specification

Conventional Fire Detection and Extinguishant Control System Specification Conventional Fire Detection and Extinguishant Control System Specification Page 1 of 9 Scope Furnish a complete 24VDC Conventional, electrically supervised, combined fire detection and extinguishant release

More information

Bold items are particular to the City of Euless

Bold items are particular to the City of Euless EULESS FIRE DEPARTMENT FIRE MARSHAL S OFFICE INFORMATION LINE: Revised 2/12 Fire Chief Wes Rhodes Fire Marshal Paul Smith EFD-FMO 3-2 2009 International Fire & Building Code as Amended NFPA Standards Adopted

More information

A-307. Mobile Data Terminal. Android OS Platform Datasheet

A-307. Mobile Data Terminal. Android OS Platform Datasheet A-307 Mobile Data Terminal Android OS Platform Datasheet Revision 1.1 July, 2013 Introduction A-307 Platform Overview Introduction A-307 Platform Overview The A-307 provides Original Equipment Manufacturers

More information

PRODUCT SHEET OUT1 SPECIFICATIONS

PRODUCT SHEET OUT1 SPECIFICATIONS OUT SERIES Headphones OUT2 BNC Output Adapter OUT1 High Fidelity Headphones OUT1A Ultra-Wide Frequency Response Headphones OUT3 see Stimulators OUT100 Monaural Headphone 40HP Monaural Headphones OUT101

More information

466-1936 Rev E October 2004 ZZZ*(6HFXULW\FRP. Part No: 60-883-95R. CareGard. User Guide

466-1936 Rev E October 2004 ZZZ*(6HFXULW\FRP. Part No: 60-883-95R. CareGard. User Guide ) *(6HFXULW\ 466-1936 Rev E October 2004 ZZZ*(6HFXULW\FRP Part No: 60-883-95R CareGard User Guide FCC Notices FCC Part 15 Information to the User Changes or modifications not expressly approved by GE Security

More information

SECTION 16721 FIRE ALARM AND DETECTION SYSTEM

SECTION 16721 FIRE ALARM AND DETECTION SYSTEM 1. GENERAL 1.1. Related Documents: 1.2. Scope: 1.1.1. The general provisions of the Contract, including General and Supplementary Conditions and General Requirements apply to the work specified in this

More information

616, 626, 636 & 646 Keypads

616, 626, 636 & 646 Keypads 616, 626, 636 & 646 Keypads User s Manual TABLE OF CONTENTS 1.0 BASIC OPERATION...2 2.0 ACCESS CODES...4 3.0 ARMING & DISARMING...6 4.0 PANIC ZONES...13 5.0 KEY ACCESS PROGRAMMING.14 6.0 ADDITIONAL FEATURES...15

More information

DIGITAL ALARM CLOCK RADIO

DIGITAL ALARM CLOCK RADIO DIGITAL ALARM CLOCK RADIO INSTRUCTION MANUAL For information and support, www.lenco.eu CR3302 LENCO ENG FM ONLY IM 98 x1 1 11/5/2009 9:14:35 CAUTION RISK OF ELECTRIC SHOCK DO NOT OPEN WARNINGS ATTENTION

More information

LYNX Touch L5200 Series Security System

LYNX Touch L5200 Series Security System LYNX Touch L5200 Series Security System User Guide 800-16083V1 12/14 Rev. A LYNX Touch L5200 Series Your Honeywell security system is designed for use with devices manufactured or approved by Honeywell

More information

Model: 616-146v2 Quick Setup Guide DC: 071015 Atomic Projection Alarm with Indoor and Outdoor Temperature

Model: 616-146v2 Quick Setup Guide DC: 071015 Atomic Projection Alarm with Indoor and Outdoor Temperature Model: 616-146v2 Quick Setup Guide DC: 071015 Atomic Projection Alarm with Indoor and Outdoor Temperature Snooze/Backlight BUTTONS Time, Alarm with Snooze, & Calendar Projection Arm Rotates 180 Indoor/Outdoor

More information

User s Guide. Security Systems D220

User s Guide. Security Systems D220 User s Guide Security Systems D220 Table of Contents About This User s Guide... 3 Introduction... 3 Security System Basics... 4 Controlled Points... 5 24-Hour Points... 6 Keypad Keys... 6 Keypad Lights...

More information

EDA-Z5008 & Z5020. Radio Fire Alarm System. User Manual

EDA-Z5008 & Z5020. Radio Fire Alarm System. User Manual EDA-Z5008 & Z5020 Radio Fire Alarm System User Manual Electro-Detectors Ltd. Electro House, Edinburgh Way Harlow, Essex, CM20 2EG UK Tel: 01279 635668. Fax 01279 450185 Email: [email protected]

More information

LYNX Touch L7000 Series Security System

LYNX Touch L7000 Series Security System LYNX Touch L7000 Series Security System User Guide 800-16084 12/13 Rev. A LYNX Touch L7000 Series Your Honeywell security system is designed for use with devices manufactured or approved by Honeywell for

More information

ER102. Emergency Crank Weather Radio Owner s Manual. www.midlandradio.com

ER102. Emergency Crank Weather Radio Owner s Manual. www.midlandradio.com ER102 Emergency Crank Weather Radio Owner s Manual Table of Contents Welcome to the World of Midland Electronics Major ER102 Features ER102 Controls and Functions ER102 Power Sources - Built-in Rechargeble

More information

CR9971 2 Band Auto Set Dual Alarm Clock Radio ROBERTS. Sound for Generations. Please read this manual before use

CR9971 2 Band Auto Set Dual Alarm Clock Radio ROBERTS. Sound for Generations. Please read this manual before use ROBERTS Sound for Generations CR9971 2 Band Auto Set Dual Alarm Clock Radio Please read this manual before use Contents Contents... 1 Controls...2-5 Switching on... 6 Setting the time manually... 6 Setting

More information

FLORIDA ATLANTIC UNIVERSITY FIRE ALARM SYSTEM INSTALLATION MANUAL

FLORIDA ATLANTIC UNIVERSITY FIRE ALARM SYSTEM INSTALLATION MANUAL FLORIDA ATLANTIC UNIVERSITY FIRE ALARM SYSTEM INSTALLATION MANUAL January, 2003 Environmental Health and Safety Florida Atlantic University 777 Glades Rd. Boca Raton, FL 33431 Phone: 561-297-3129 Fax:

More information

ST815 Illumination Sensor with LCD

ST815 Illumination Sensor with LCD ST815 Illumination Sensor with LCD The Illumination Sensor with LCD (refer to as Illumination Sensor hereafter) is a Z-Wave TM enabled device which is fully compatible with any Z-Wave TM enabled network.

More information