Installation Manual BRIDGE ALARM SYSTEM BR-1000

Size: px
Start display at page:

Download "Installation Manual BRIDGE ALARM SYSTEM BR-1000"

Transcription

1 Installation Manual BRIDGE SYSTEM BR-000 SAFETY INSTRUCTIONS...i SYSTEM CONFIGURATION...ii EQUIPMENT LISTS...iii. HOW TO INSTALL THE EQUIPMENT...-. Bridge Panel...-. Processor Unit...-. Cabin Panel, Timer Reset Panel...-. AC-DC Power Supply...-. Watertight Timer Reset Panel...-. HOW TO CONNECT EXTERNAL EQUIPMENT...-. Connections Inside the Processor Unit...-. AC-DC Power Supply...-. Connection of IN/REMOTE ACK OUT/LOCAL ACK IN/ OPERATOR FITNESS IN Signals...-. HOW TO SET AND CHECK THE SYSTEM...-. How to Set and Connect the PC for Maintenance...-. Settings for Bridge Panel BR Settings for Processor Unit BR System Operation Check Service Menu...-. How to Edit the Alarm List...- APPENDIX JIS CABLE GUIDE...AP- PACKING LISTS... A- OUTLINE DRAWINGS... D- INTERCONNECTION DIAGRAMS... S- PROCESSOR UNIT CONNECTION LISTS... S- All brand and product names are trademarks, registered trademarks or service marks of their respective holders.

2 * * * *

3 SAFETY INSTRUCTIONS Read these safety instructions before you install the equipment. WARNING CAUTION Indicates a condition that can cause death or serious injury if not avoided. Indicates a condition that can cause minor or moderate injury if not avoided. Warning, Caution Prohibitive Action Mandatory Action WARNING Do not open the equipment unless authorized. This equipment uses high voltage which can cause electrical shock if mishandled. Turn off power at switchboard before starting the installation. Fire or electrical shock can result if the power is on. Be sure to connect to the correct power supply. Connection to a wrong power supply can cause fire or bodily injury. Do not disassemble or modify the equipment. Fire, electrical shock or bodily injury can result. CAUTION Securely ground (protection earth) the equipment. Ineffective ground can cause electrical shock. Use the correct fuse. Use of a wrong fuse can cause fire. Follow the compass safe distances shown in the table below to prevent interference to a magnetic compass. Unit BR-00 BR-00 BR-00 BR-00 BR-00 PR-0 Standard compass 0.0 m.8 m 0.0 m 0.0 m 0.0 m 0.90 m Steering compass 0. m. m 0.0 m 0.0 m 0.0 m 0.0 m i

4 SYSTEM CONFIGURATION BRIDGE PANEL BR-00 VDR GPS 00-/ 00-0 VAC VDC AC-DC POWER SUPPLY PR-0 ETHERNET HUB HUB-0 PROCESSOR UNIT BR-00 PROCESSOR UNIT BR-00 Autopilot ( lines) IAS ( lines) CABIN PANEL BR-00 - units TIMER RESET PANEL BR-00 WATERTIGHT TIMER RESET PANEL BR-00 - units External Siren REMOTE ACK OUT ( lines) LOCAL ACK IN ( lines) OPERATOR FITNESS IN ( lines) IN (8 lines) - Dashed lines indicate optional equipment. - Environment category: All units protected from weather. SYSTEM FAIL OUT ( lines) ii

5 EQUIPMENT LISTS Standard Supply Name Type Code No. Qty Remarks Bridge Panel BR-00 - Processor Unit BR-00 - Cabin Panel BR units Timer Reset BR units Panel AC-DC Power Supply Unit PR-0 - Installation Materials CP Cable MJ-ASPF00-0 ( ) + CP-00. See packing list at back of manual. CP For BR-00, BR-00. See packing list at back of manual. CP For PR-0.See packing list at back of manual. Spare Parts SP Fuse FGB0-A V A PBF, pcs. ( ) iii

6 Optional Supply Name Type Code No. Remarks Watertight Timer Reset Panel BR-00 - Installation Materials CP See packing list at back of manual. Processor Unit BR-00 - Cabin Panel BR-00 - Timer Reset Panel BR-00 - Ethernet Hub HUB-0 - Hanger FP For BR-000 Cable Assy. MJ-ASPF000-00C For VDR, m MJ-ASPF000-00C For VDR, 0 m MJ-ASPF000-00C For GPS, m MJ-ASPF000-00C For GPS, 0 m LAN Cable Set CP m cable, two connectors CP m cable, two connectors CP m cable, two connectors iv

7 . HOW TO INSTALL THE EQUIPMENT NOTICE Do not apply paint, anti-corrosive sealant or contact spray to coating or plastic parts of the equipment. Those items contain organic solvents that can damage coating and plastic parts, especially plastic connectors. Install the equipment following the points shown below. Select a location where the temperature and humidity are moderate and stable. Keep the equipment away from the exhaust vents. Provide ventilation to keep the equipment cool. Select a location where vibration and shock are minimal. Leave space at the sides and rear of the unit for maintenance. Follow the safe compass distances on page i to prevent the interference to a magnetic compass.. Bridge Panel Flush mount Fasten the Bridge Panel to the cutout with the hardware supplied.. Prepare a cutout in a console. See the outline drawing and the illustration shown below for dimensions. ±0. (.0±0.0) 0±0. (.±0.0) ±0. (.0±0.0).±0. (.0±0.0).±0. (.0±0.0). (0.8) 8± (.±0.0) R. (0.09) ± (8.0±0.0) Dimensions in millimeters (inches) -

8 . HOW TO INSTALL THE EQUIPMENT. Screw in six threaded rods (supplied) at the back of the unit.. Attach the flush mounting sponge (supplied) at the rear of the unit.. Set the unit to the cutout.. From the rear side, fasten the unit to the console panel with six sets of flat washers, spring washers and hexagonal nuts. Flush Mounting Sponge Flat Washer Spring Washer Hexagonal Nut Threaded Rod Desktop mount (optional hanger) The optional hanger lets you install the Bridge Panel on a desktop.. Fasten the hanger with four x0 self-tapping screws (supplied).. Screw the knobs into the unit.. Set the unit to the hanger then tighten the knobs. (0.9) Fixing Hole -φ(0.) (0.9) 8(.9) 9±(.±0.) 8±0. (.±0. (.80) (.8) 0 Dimensions in millimeters (inches) -

9 . HOW TO INSTALL THE EQUIPMENT. Processor Unit A maximum of two processor units can be installed, including the optional unit. To install the no. processor unit, the Ethernet Hub HUB-0 is required. (For additional information, see the instruction manual (C000) for the HUB-0.) Fasten the processor unit to a bulkhead or the deck as shown below.. Make four pilot holes for φ0 coach bolts or four fixing holes for M0 bolts. See the drawing below for mounting dimensions.. Fasten the unit with φ0 coach bolts or M0 bolts. (Supply bolts locally.) 0±(.±0.0) -φ(0.) Fixing Hole (0.) (0.8) 8(.) (.0) 8±(.9±0.0) 9(.) (.9) R (0.) (0.) 0±(.±0.0) Dimensions in millimeters (inches) Bulkhead mounting dimensions for the processor unit -

10 . HOW TO INSTALL THE EQUIPMENT. Cabin Panel, Timer Reset Panel The Cabin Panel and Timer Reset Panel have the same dimensions. Flush-mount the units as shown below. A maximum of 0 channels of Cabin Panels connect to one Processor Unit. (Four of the 0 channels can be connected in parallel for a total of channels.) Install the 0 channels of Cabin Panels in the Captain s quarters, the back-up navigation officers quarters, and public areas. The system has five channels to test wire continuity in the Cabin Panels. Install Cabin Panels in the captain s quarters and officers quarters independently to conduct the wiring continuity test independently.. Prepare a cutout in the location. See the outline drawing and the figure shown below for dimensions. 8±0.(.±0.0) ±(.9±0.0) -Pilot Holes ±0.(.9±0.0) 0±(.±0.0) Dimensions in millimeters (inches). Unfasten four screws from the front side of the unit to remove the rear cover.. Put the connection cable through one of the two rubber bushes and set the rear cover to the cutout. (Select the rubber bush most suitable for your installation.). Fasten the rear cover with four x self-tapping screws (supplied).. Detach the WAGO connector from the PCB. Attach the wires to the WAGO connector. See Chapter for how to attach the wires to a WAGO connector.. Attach the WAGO connector to the PCB. As shown in the illustration at right, run the cable along the left side of the connector and fix the cables to the connector with a cable tie. -

11 . HOW TO INSTALL THE EQUIPMENT. Draw out excess cable from the cable entrance, set the unit into the rear cover and fasten the screws unfastened at step. 00(.9) 8±0.(.±0.0) TIMER RESET PANEL 8. (0.).(.8) Ground Terminal WATCH RESET TEST BRIDGE ±0.(.9±0.0) 0(.) Rubber Bush BRIDGE SYSTEM Dimensions in millimeters (inches) Connector Rubber Bush. AC-DC Power Supply This bridge alarm system connects to both AC and DC power supplies. AC power for normal use, and DC power when AC power is lost. Fasten the unit to a desktop with four x self-tapping screws (supplied). (There is no need to open the cover to install the unit.) 8(.) ±(0.±0.0) Fixing Hole -φ(0.). (.) (.) 00±(.9±0.0) Dimensions in millimeters (inches) -

12 . HOW TO INSTALL THE EQUIPMENT. Watertight Timer Reset Panel Flush mount the Watertight Timer Reset Panel as follows:. Prepare a cutout in the mounting location and make six holes. 0±0.(.0±0.0) 9±(.8±0.0) 0±0.(.±0.0) Fixing Hole -φ(0.) ±(.00±0.0) ±0.(.9±0.0) Dimensions in millimeters (inches). Unfasten two screws from the rear side to remove the lid. Put the connection cable through the rubber bush.. Detach the WAGO connector from the PCB. Attach the wires to the WAGO connector.. Attach the WAGO connector to the PCB. Close the rear lid.. Set the unit to the cutout. From the rear side, fasten the unit with six sets of bolts, flat washers, spring washers and hexagonal nuts. Flat Washer Spring Washer Hexgonal Nut Ground Terminal Screw for Lid Connector Screw for Lid Rubber Bush (Select one.) -

13 . HOW TO CONNECT EXTERNAL EQUIPMENT The cables described in this manual are shown as Japanese Industrial Standard (JIS). Use the JIS Cable Guide in Appendix to find the equivalent cables locally.. Connections Inside the Processor Unit All signal cables are connected to the Processor Unit. Refer to the figure shown below for connections. Record the name of each device and signal connected to the Processor Unit in the list provided at the back of this manual. This information is needed when you set the alarms in Chapter. PROCESSOR UNIT BR-00 * Ground Terminal (beneath clamp) IV-sq. Cable Clamp (Lay armor of each cable in clamp and tighten clamp.) BRIDGE PANEL BR-00 Navigator (Max. 8 lines) Navigator (Max. types) TIMER RESET PANEL BR-00 WATERTIGHT TIMER RESET PANEL BR-00 Navigator (Max. types) PE-PTX-BL-CB LAN Cable MPYC-X TB - TB IN Signal (Alarm input) MPYC-X TB - TB REMOTE ACK OUT Signal (Alarm stop) MPYC- TB8 - TB (Max. units) MPYC-X TB - TB LOCAL ACK IN Signal (Alarm stop) TTYCS- TB, TB MODBUS IN/OUT IAS* ( lines) MPYC- CABIN PANEL (0 channels) BR-00 TB8/TB9, TB - TB (Two cabin panels can be connected to TB - TB via the junction box.) DPYC-. VDC AC-DC POWER SUPPLY UNIT PR-0 MPYC- TB Autopilot AUTO PILOT MODE IN (Autopilot mode input) MPYC- TB AC-DC POWER PF IN SUPPLY UNIT PR-0 (POWER FAIL IN) MPYC- TB0 External Siren EXTERNAL SIREN OUT MPYC-X TB, TB8 OPERATOR FITNESS IN Signal MPYC- TB, TB SYSTEM FAIL OUT Signal Navigator (Max. lines) VDR, IAS ( lines) * If the number of alarm signals to be connected is greater than 9, use the Ethernet Hub (option) and the No. Processor Unit. You cannot connect Cabin Panels or Timer Reset Panels to the No. Processor Unit. Connect to #-# (AC POWER FAIL) of TB in the No. Processor Unit. * IAS=Integrated Automation System -

14 . HOW TO CONNECT EXTERNAL EQUIPMENT BRIDGE PANEL BR-00 PROCESSOR UNIT BR-00 PE-PTX-BL-CB LAN Cable * Ground Wire IV-sq * * * MJ-ASPF00-0 Power Cable VDC MJ-ASPF000-00C, m MJ-ASPF C, 0m MJ-ASPF000-00C, m MJ-ASPF000-00C, 0m AC-DC POWER SUPPLY UNIT PR-0 * Attach EMI core to both LAN cable and power cable, at approx. 0 to 0 mm from the cable end that connects to the BRIDGE PANEL. Fasten core with cable ties as shown below. VDR GPS EMI core Attach cable ties at ends. EMI core -

15 . HOW TO CONNECT EXTERNAL EQUIPMENT CABIN PANEL BR-00 TIMER RESET PANEL BR-00 WATERTIGHT TIMER RESET PANEL BR-00 WAGO Connector Ground terminal on cabinet Ground wire, IV-sq (Attach crimp-on lug and fasten.) WAGO connector PROCESSOR UNIT BR-00 Ground wire, IV-sq (Attach crimp-on lug and fasten.) PROCESSOR UNIT BR-00 How to prepare the MPYC-type cable Prepare the cable as shown below. Connect the cables to related WAGO connectors. Sheath L Armor Remove paint approx. 0 mm L=Distance from cable clamp to terminal connection Connect wires to WAGO connector Cut sheath. 0 0 Vinyl tape Set this part in cable clamp and fasten clamp. How to prepare MPYC-type cable -

16 . HOW TO CONNECT EXTERNAL EQUIPMENT How to prepare cable DPYC-. Approx. 0 Sheath Armor 0 Cut sheath. Taping Crimp-on lug Inner diameter φ Outer diameter φ Set this part in cable clamp and fasten clamp. How to prepare cable TTYCS- How to prepare the cable DYPC-. L Shield Cut vinyl sheath. Remove paint. 0 L=Distance from cable clamp to terminal connection Pull out cables from shield then solder vinyl wire to shield. Connect wires to WAGO connector Connect to ground terminal inside. Vinyl tape Set this part in cable clamp. How to prepare the cable TTYCS- -

17 . HOW TO CONNECT EXTERNAL EQUIPMENT How to connect wires to a WAGO connector Push Terminal opener Wire Twist WAGO connnector Procedure. Twist core.. Set terminal opener as above and push.. Insert core into hole.. Release terminal opener.. Pull wire to confirm it is correctly inserted. How to connect wires to a WAGO connector. AC-DC Power Supply AC-DC POWER SUPPLY PR-0 Ground Wire (protective) IV-sq PROCESSOR UNIT BR-00 TB MPYC- AC FAIL OUT DPYC-., pcs. VDC OUT BR-00 BR-00 Ship s switchboard DPYC-. 00/0 VAC IN DPYC-. VDC IN Connect to battery via ship s mains -

18 . HOW TO CONNECT EXTERNAL EQUIPMENT Power Specifications The AC-DC Power Supply PR-0 is for connection to a 00-0 VAC ship s mains. For 00- VAC ship s mains, change both the tap connection and the terminal connection. Attach the correct power supply label (supplied) to the front of the unit, at the location shown below. Ship s Mains Tap Connection Terminal Connection Power Supply Label 00-0 VAC SEL 0 V See (a) below VAC.-.A φ 0/0 Hz 00- VAC SEL V See (b) below. 00- VAC.-.A φ 0/0 Hz Unfasten screw to detach cover. Cover FRONT PANEL (a) 00-0 VAC BLACK GRAY J Relay Coil Terminal (b) 00- VAC BLACK GRAY FRONT PANEL 8 SEL V SEL 0V Tap Connection (Pull firmly to detach.) Attach power supply label here. Heatsink AC FAIL J sets contact signal output. Default setting is normally closed (# and # pins connected (for serial no. 0 and after). For serial no. 0 and before, normal opened (# and # connected). Match this setting with setting of BR-00 (default is normal close ). AC Power Switch (When DC power is used, this switch is inoperative; DC power is supplied regardless of switch position.) -

19 . HOW TO CONNECT EXTERNAL EQUIPMENT. Connection of IN/REMOTE ACK OUT/ LOCAL ACK IN/OPERATOR FITNESS IN Signals This system has 8 IN signal input terminals for the connection of navigation equipment. Connect radar, ECDIS, GPS navigator, navigational echo sounder, etc. that have OUT terminals to the IN terminals in the Processor Unit BR- 00. Connect all lines of the equipment having multiple OUT terminals. REMOTE ACK OUT signal output terminals are provided. The purpose of these terminals is to output the stop alarm in response to alarm input from external equipment. This system outputs only one REMOTE ACK OUT signal, without reference to the number of IN signals input from a device. The LOCAL ACK IN signal is an alarm stop signal that is sent to external equipment in response to IN signal input from the external equipment. This equipment receives this signal to stop the buzzer at this equipment. input signal terminals are provided. Seven OPERATOR FITNESS IN signal input terminals are provided. This signal is output from external equipment to validate operator presence when the operator operates the external equipment. This system watches for this signal at fixed intervals, and if the signal is not received the system outputs an alarm. The illustrations on the next several pages show how to connect FURUNO make IMO radar, ECDIS, GPS navigator, and navigational echo sounder. -

20 . HOW TO CONNECT EXTERNAL EQUIPMENT Connection of ECDIS FEA-0 FEA-0 BR-00 TB LOCAL ACK IN * LOCAL ACK OUTSIDE CHANNEL LIMIT WAYPOINT APPROACH DEPTH BELOW LIMIT BACKUP NAVIGATION NAVIGATION SENSOR OPERATOR FITNESS ANY ECDIS J ST0+ ST0- ST0+ ST0- ST0+ ST0- ST0+ ST0- J ST0+ ST0- ST0+ ST0- ST0+ ST0- ST08+ ST08- TB/TB IN * 8 TB OPERATOR FITNESS IN * BUZZER STOP J STI9 STI0 NC NC NC NC TB REMOTE ACK OUT * + - *: This connection is an example. Other terminals which have the same line can also be used. -8

21 Connection of IMO radar FAR-0. HOW TO CONNECT EXTERNAL EQUIPMENT FAR-0 Series BR-00 * * * * J _0 0 0 _ OPERATOR FITNESS OPERATOR FITNESS EXT_ALM_ACK_N SYS_FAIL_H SYS_FAIL_C P P P P P P TTYCS- TB IN * 8 TB LOCAL ACK IN * TB OPERATOR FITNESS IN * TB REMOTE ACK OUT * * * * Set on menu of FAR-0. * MENU / / OUT to select alarm to output. * MENU / / OUT to select alarm to output. * MENU / / 8 OUT and select ACK OUT. * MENU / / 9 OUT and select OPERATOR FITNESS. (* and * are normal close signals; * and * are normal open signals.) + - *: This connection is an example. Other terminals which have the same line can also be used. -9

22 . HOW TO CONNECT EXTERNAL EQUIPMENT Connection of Navigational Echo Sounder FE-00 NAVIGATIONAL ECHO SOUNDER FE-00 RELAY DISTRIBUTION BOX NC NO COM TB BR-00 TB IN * *: This connection is an example. Other terminals which have the same line can also be used. Connection of GPS Navigator GP-0 GP-0 BR-00 DATA J ALM-H > > ALM-C > > TB IN * *: This connection is an example. Other terminals which have the same line can also be used. -0

23 . HOW TO SET AND CHECK THE SYSTEM This chapter shows you how to set the system according to the equipment connected. To make the procedure as easy as possible, an Excel file is used. The Excel file is downloaded from the internet to a PC. The installer enters the settings in the Excel file then uploads the contents of the file to this system. The Excel file can be used again to set this bridge alarm system on another ship. You can set the system from the Bridge Panel, but that method takes longer than if you use the Excel file. After you have uploaded the contents of the Excel file to the Bridge Panel, you can make small adjustments from the Bridge Panel. The system accepts 8 channels of IN signals. These channels are connected to the terminals TB-TB in the Processor Unit. Connect the channels in terminals and write down channel order to prevent confusion, following the interconnection diagram. For example, connect the channel no. to #/ of TB and the channel no. 8 to #/8 of TB. Connect other signals and the Cabin Panels according to the interconnection diagram. To connect an IAS, see the instructions of the manufacturer of the IAS to set the Modbus. (Modbus is the communications protocol used by the IAS.). How to Set and Connect the PC for Maintenance PC Prepare a laptop PC that meets the requirements shown below. OS: English or Japanese version Windows XP, or Windows Vista ( bit) Microsoft Excel: Excel 000 or higher (English or Japanese version) Serial port (If there is no serial port on the laptop, use a serial USB converter cable (driver). Set the IP of the PC as shown below. IP address: xxx (xxx=any value except, or ) The IP addresses of the bridge alarm equipment are BR-00: , No. BR-00: , No. BR-00: Subnet mask:...0 If you change the IP address on this file, the upload and download connection points change. See Network sheet on page - for information. Excel file The Excel files to use to set this system are on the FURUNO WEB SERVICE. Access this website and download the following two files: BR00CONF.xls BR00CONF.xls Note: These files contain macro functions. When you open the files, make sure you activate the macro functions. -

24 . HOW TO SET AND CHECK THE SYSTEM Connection Connect the PC as shown below according to system configuration. PC for Maintenance LAN SERIAL Bridge Panel BR-00 PC for Maintenance LAN Processor Unit BR-00 Single processor unit connection Bridge Panel BR-00 LAN PC for Maintenance LAN Ethernet Hub HUB-0 LAN No. Processor Unit BR-00 Serial LAN Serial No. Processor Unit BR-00 (option) Two processor unit connection -

25 . Settings for Bridge Panel BR-00. HOW TO SET AND CHECK THE SYSTEM The setting data to be uploaded from the PC to the BR-00 are as shown below. Settings - Alarm/Definition file update, backup - Network settings - Modbus settings, etc. PC for Maintenance Check, results LAN Bridge Panel BR-00 Setting procedure The procedure shown below shows how to do all settings collectively. (You can make small adjustments from the BR-00.) Note: Before you do this procedure, write down the connections (terminal number, name of equipment connected, signal name) made in the Processor Unit. Use the list at the back of this manual to record this data. Refer to the list to do this procedure.. Connect the BR-00 to the PC as shown in the illustration on page -.. Open the Definition FIle Update & Backup screen from the BR-00 as follows: ) Press the BRILL key while you press the ACK key to turn on the BR-00. The window below appears, where you are asked to enter the password. Enter Password ) Press the up, down, left and right arrows on the Cursor pad followed by the LIST and ESC keys. This is the password to open the Maintenance Mode menu. Note: If the password is wrong you are asked to turn off the power. Press the BRILL key for more than 0 seconds to turn off the power. Redo the procedure from step. -

26 . HOW TO SET AND CHECK THE SYSTEM This is the Maintenance Mode menu. Maintenance Mode Self Test Menu Definition File Update & Back-up Factory Default Press [BRILL] key for 0 seconds to power off. ) Press the up or down arrow to select Definition File Update & Back-up then press the ENTER key. Definition File Update & Back-up Connecting to Maintenance PC Press [ESC] to exit.. Open the Excel file BR00CONF from the PC. -

27 . HOW TO SET AND CHECK THE SYSTEM. Open the Config sheet then click the Upload & Download button on the sheet to show the following display.. Confirm that the IP address for the BR-00 is Click the Download button to download the current settings (default values). A bar moves to the right as the download progresses and the message Complete appears when the download is completed.. Set each of the 0 sheets according to the equipment in the system. See the next section for how to enter the values.. After you have entered all settings, reopen the Config sheet and click the Upload & Download button. Click here Config sheet 8. Check that the IP address is correct then click the Upload button to upload the data to the BR-00. -

28 . HOW TO SET AND CHECK THE SYSTEM 9. Confirm that the data is uploaded to the BR-00. The yellow progress bar moves to the right as the upload progresses. The message Complete appears when the upload is completed. At the Bridge Panel, the indication at the screen center changes from Now Writing to Connecting to Maintenance PC when the upload is completed. Definition File Update & Back-up Definition File Update & Back-up Now Writing. Connecting to Maintenance PC Press [ESC] to exit. 0.At the PC, select a name for the updated definition file and save the file. Select a name that is easy to remember, for example, name of ship. If you are setting up for several ships, save a file under the name of each ship..press the BRILL key more than 0 seconds on the BR-00 to turn off the power. Disconnect the PC from the BR-00. -

29 . HOW TO SET AND CHECK THE SYSTEM [BR-00 SETTINGS] This paragraph describes the settings on each sheet in the Excel file. Channel sheet The Channel sheets set the input and output channels of the Processor Unit BR-00.. Logical Channel Logical channel. Do not change the setting.. Digital/Modbus Select to use contact signal or Modbus signal. 0: Contact signal (digital channel) : Modbus Adjustment is normally not required. -

30 . HOW TO SET AND CHECK THE SYSTEM. IN/OUT Select the function of the signal, input or output. 0: Input : Output Adjustment is normally not required.. Processor Unit No. (Same as Input Unit on the Alarm List editing screen) For contact signal (digital channel), select either the standard BR-00 or the optional BR-00. -: Modbus (For no use) : Standard supply BR-00 : Optional supply BR-00 Adjustment is normally not required. (The default setting is as follows:, AL00-AL08 (for standard BR-00), -, AL09-AL09 (for Modbus),, AL09-AL (optional BR-00), -, AL-AL-9 (for Modbus). DIgital Channel (Same as Channel Number/Modbus Address on the Alarm List editing screen) Set input channel number of the BR-00. Adjustment is normally not required.. Modbus Address (Input) (Same as Channel Number/Modbus Address on Alarm List editing screen.) Set Modbus address at input side (alarm at IAS side, etc.). Range: - Note: Adjustment is normally not required, but consult with the IAS maker.. Modbus Address(Output) Set Modbus address at output side (alarm at BR-000, etc.) Range: -8-8

31 . HOW TO SET AND CHECK THE SYSTEM Group sheet. Group Number Set group number. Adjustment is normally not required.. Local ACK IN Set Local ACK IN group. Adjustment is normally not required.. Remote ACK OUT Set Remote ACK IN group. Adjustment is normally not required. Group sheet -9

32 . HOW TO SET AND CHECK THE SYSTEM CPanel sheet The CPanel sheet has settings for the Cabin Panels. Before you do this procedure, record the terminal numbers (TB-TB) where the Cabin Panels are connected in the Processor Unit. The Cabin Panel connected to TB has the name CP00 on this sheet. The Cabin Panel connected to TB has the name CP00. CPanel sheet. Panel Number. Cabin Panel LED(Alarm). Cabin Panel LED(Duty). Cabin Panel Buzzer. IAS Panel Control. Cabin Panel Test Channel Do not change the settings of items -.. Panel Type Set the type of each Cabin Panel. 0: Cabin Panel fitted in Captain s room : Cabin Panel installed in the quarters of the officer(s) selected as back-up officer candidate. The Captain of the ship selects which officer is to be the back-up officer. : Cabin Panel installed in public areas - lobby, dining room, leisure room, etc. 8. Panel Name Enter the name for each Cabin Panel. Use title of person or name of room. A maximum of 0 alphanumeric characters can be used for panel name. -0

33 . HOW TO SET AND CHECK THE SYSTEM TPanel sheet The TPanel sheet sets the Timer Reset Panel. Do not change the settings on this sheet. TPanel sheet -

34 . HOW TO SET AND CHECK THE SYSTEM Alarm sheet The Alarm sheet sets the alarms.. Tag Number Do not change this setting.. Channel Number Give tag numbers to alarm logical channels. Adjustment is normally not required.. Alarm Text (Same as Alarm Text on the Alarm List editing screen.) Set the name of each alarm. You can use alphanumeric characters, and the name can have a maximum of characters including spaces. Give Tag Numbers (Channel Numbers) according to terminal location on the Processor Unit BR-00 as follows. Enter the name of the alarm connected to TB #/ in the input box for Tag Number. - TB #/: Tag Number (Channel Number AL00) - TB #/: Tag Number (Channel Number AL00) - TB #/8: Tag Number 8 (Channel Number AL08) -

35 . HOW TO SET AND CHECK THE SYSTEM If the No. processor unit is installed, enter tag numbers as shown below. - No. BR-00 TB #/: Tag Number 9 (Channel Number AL09) - TB #/: Tag Number 98 (Channel Number AL098) Enter a name for the alarm that clearly identifies the type of alarm. These names appear on the Bridge Alarm Display and the Auto Alarm Pop-up Display. Example: No. Radar CPA/TCPA/GZ No. Radar System Fail No. GPS off-track. Group Number (Same as Group Number on the Alarm List editing screen.) Collect like alarms into a group. Range: -, is for Modbus. Examples: Assign the four lines of alarm signals from the No. radar that are connected to TB in the No. processor unit to Group. Assign the four lines of alarm signals from the No. radar that are connected to TB in the No. processor unit to Group. Assign the eight lines of alarm signals from the ECDIS that are connected to TB and TB to Group. Assign the four lines of alarm signals from a GPS navigator that are connected to #/ of TB to Group.. Alarm Priority/Status Assign priority to each alarm. Check with ship personnel to set priority. Priority appears on the Bridge Alarm Display and the Auto Alarm Pop-up Display. 0: Emergency : Urgency : Primary : Secondary. Type of Signal Set the type of contact signal for each alarm. Set according to equipment connected. 0: AL Open (Contact signal opens when an alarm is generated - NC.) : AL Close (Contact signal closes when an alarm is generated - N0.) : Modbus. Active/Inactive Activate or deactivate each alarm. (The Bridge Panel ignores an alarm set as inactive.) 0: Inactive : Active 8. Alarm Extended Extend or don t extend an alarm at the BR-000 if the BUZ STOP and ACK keys are not operated after a device is restored to normal operation after generating an alarm. 0: OFF (Alarm is not extended. Alarm is canceled at the BR-000 after the alarm is cleared from a device. : ON (Alarm is extended. Alarm is sent to the Cabin Panels (depending on mode) if the BUZ STOP and ACK keys are not operated.) -

36 . HOW TO SET AND CHECK THE SYSTEM 9. Alarm Type Enable or disable the repeat alarm for Modbus. When a normal alarm is generated and the repeat alarm address changes, the alarm changes to a repeat alarm. (Not related to contact signal.) 0: Normal Alarm (No repeat alarm) : Repeat Alarm (With repeat alarm) Note: For Modbus. Consult with the IAS maker. 0.Repeat Alarm Channel Number If the Alarm Type is Repeat Alarm, the repeat alarm is generated when the address of the corresponding logical channel changes..vdr Output or don t output the ALR sentence to a VDR when related alarm is generated. 0: Disable (no output) : Enable (output) -

37 . HOW TO SET AND CHECK THE SYSTEM Menu sheet The Menu sheet has settings for the Administrator menu and the Service menu. The Administrator menu has items that can be adjusted by ship authorities (like the Captain) according to navigation status. The installer can keep the default settings. See the BR-000 Operator s Manual for information about the Administrator menu. AC Power Fail [Administrator menu]. Mode Select Set the operating mode. 0: Harbour Mode : Attended Mode : One-Man Mode. Back-up Officer Select Select the back-up officer (Range: 0-9). 0: Cabin Panel : Cabin Panel... 9: Cabin Panel 0 -

38 . HOW TO SET AND CHECK THE SYSTEM Select the Cabin Panels that are set as Back-up Officer with the item Panel Type on the CPanel sheet.. Captain Back-up Set if the Cabin Panel in the Captain s room is to give the audible alarm in the nd phase of an alarm or not. 0: DIsable (no audible alarm) : Enable (audible alarm sounds). Watch Time Interval Select Set the watch time interval. Range: - (m). All Back-up Officer Call Interval Select the time interval between the end of the nd phase and the start of the rd phase. The time unit is seconds. 0: 90 : 0 : 0 : 80. Use Key Beep A beep sounds when a key is operated. This beep can be turned on or off. 0: Disable (no beep) : Enable (beep) [System Setting menu]. IMO/DNV Mode Select Set the specification for the timing of watch alarm generation, IMO or DNV, See Chapter in the Operator s Manual for information about this setting. 0: IMO (International Maritime Organization) : DNV (Det Norske Veritas, Norwegian classification society). Buzzer Type Set the buzzer type for continuous or intermittent. 0: Continuous : Intermit. Bridge Panel Buzzer Tone Set the buzzer frequency for the buzzer at the BR-00. Range: (Hz) In 0 Hz increments. Adjustment is normally not required.. No. Processor Unit Connection Set whether the optional BR-00 is connected or not. 0: Disable (no connection) : Enable (connected) -

39 . HOW TO SET AND CHECK THE SYSTEM. Use External Siren Use an external siren or not. 0: DIsable (don t use) : Enable (use). IAS Connection Set whether IAS is connected or not. 0: Disable (no connection) : Enable (connected). AC Power Fail Set the #-# terminals of TB in the processor unit as normally closed or normally open. 0: Normally closed : Normally open [Color Setting menu] The setting for each color is shown on the sheet with numbers. Refer to the table and figure below for description and location of items.. Basic Color Setting Item Location Background () Font () Frame () High Light () Parameter Display Background () Parameter Display Font () Parameter Display Frame () Parameter Display Arrow (8) -

40 . HOW TO SET AND CHECK THE SYSTEM () High Light BRIDGE Basic Color Setting Description Set () Font WATCH Background Font MODE ONEMAN Frame High Light Parameter Display - Background BACK-UP C/OFFICER - Font - Frame TIME INTERVAL - Arrow MIN () Background () Frame () Parameter Display Frame () Parameter Display Font Captain Back-up Disable () Parameter Display Background (8) Parameter Display Arrow () High Light. Bridge Alarm Color Setting Item Location Bridge Alarm Display Page () BRIDGE Font () () BRIDGE Font () Bridge Alarm Display Page BRIDGE Tag Description Priority WATCH No. Radar Sys Fail No. Radar Sys Fail Secondary Secondary MODE ONEMAN No. Radar Sys Fail No. Radar CPA/TCPA/GZ Secondary Urgency BACK-UP C/OFFICER No. Radar CPA/TCPA/GZ No. Radar CPA/TCPA/GZ No. RADAR System Error Urgency Urgency Secondary TIME INTERVAL 008 No. RADAR System Error Secondary MIN -8

41 . HOW TO SET AND CHECK THE SYSTEM. WATCH Color Setting Item Location WATCH Font () () WATCH Font BRIDGE BRIDGE SYSTEM BR-000 WATCH MODE ONEMAN NO BACK-UP C/OFFICER TIME INTERVAL MIN. MODE Color Setting Item Location MODE Font () Parameter Font () MODE Background () ATTEND, ONEMAN Background () BRIDGE BRIDGE SYSTEM BR-000 () MODE Background () ATTEND, ONEMAN Background WATCH MODE ONEMAN BACK-UP C/OFFICER () MODE Font NO () Parameter Font TIME INTERVAL MIN -9

42 . HOW TO SET AND CHECK THE SYSTEM. BACK-UP Color Setting Item Location BACK-UP Font () Parameter Font () Background () BRIDGE BRIDGE SYSTEM BR-000 () Background WATCH MODE ONEMAN BACK-UP C/OFFICER NO () BACK-UP Font () Parameter Font TIME INTERVAL MIN. TIME INTERVAL Color Setting Item Location TIME INTERVAL Font () Parameter Font () Background () BRIDGE BRIDGE SYSTEM BR-000 WATCH () Background MODE ONEMAN BACK-UP C/OFFICER TIME INTERVAL MIN NO () TIME INTERVAL Font () Parameter Font -0

43 . HOW TO SET AND CHECK THE SYSTEM [Test Mode menu] The test mode checks the system for proper operation. See section. for information.. Test Mode ON/OFF Turn test mode ON/OFF. 0: OFF (normal operation) : ON. Time Visual/Audible Alarm Set the time interval for the Prewarning and nd phase of the watch alarm to use in the test mode. Range: - (s). Watch Time Interval Set the watch time interval to use in the test mode. Range: 0-0 (s). All Back-up Officer Call Interval Set the time interval to use between the nd and rd phases in the test mode. Range: 0-0 (s). Buzzer Silence Sound or don t sound the buzzer in the test mode. 0: Disable (no buzzer) : Enable (buzzer sounds) Network sheet The network sheet sets the network. These settings cannot be entered or changed from the Bridge Panel.. Bridge Panel IP Address Enter the IP address of the BR-00. Adjustment is normally not required.. No. Processor Unit IP Address. No. Processor Unit IP Address Set the IP address of the No. and No. Processor Unit. (These are settings for the bridge panel, so it may be necessary to change the setting for the No. Processor Unit.) Adjustment is normally not required.. Subnet Mask Set the subnet mask. Adjustment is normally not required. -

44 . HOW TO SET AND CHECK THE SYSTEM Modbus sheet Modbus is the communications protocol used between the IAS and this system. These settings cannot be entered or changed from the Bridge Panel. Note: For Modbus; consult with the IAS maker. The BR-000 cannot be used with an IAS unless settings are compatible with one another.. Modbus Mode Set the Modbus mode. 0: RTU : ASCII. Range of IAS Address(Start) Set the start address at the IAS side. Alarm data generated at the IAS is written into the IAS address at the IAS side. Range: - Adjustment is normally not required, but may be required depending on the make of the IAS.. Range of IAS address(end) Set the end address at the IAS side. Range: - Adjustment is normally not required, but may be required depending on the make of the IAS.. Range of BR-000 Address(Start) Set the start address at the BR-000 side. Generated alarm data is written into the BR-000 address at the BR-000 side. Range: -8 Adjustment is normally not required, but may be required depending on the make of the IAS.. Range of BR-000 Address(End) Set the end address at the BR-000 side. Range: -8 Adjustment is normally not required, but may be required depending on the make of the IAS. -

45 . HOW TO SET AND CHECK THE SYSTEM Serial sheet Set the serial port of the BR-00. Set the items according to the equipment connected. This procedure cannot be done from the Bridge Panel. [NMEA]. Baudrate Set baudrate of NMEA port. : 800 bps 9: 800 bps Note: Do not use setting 9 (800 bps) since BR-00 has no isolation.. Data Bit Set data bit of NMEA port. : bit : 8 bit. Stop Bit Set stop bit of NMEA port. 0: bit : bit. Parity Set parity of NMEA port. 0: None : Even : Odd [NMEA]. Baudrate Set baudrate of NMEA port. : 800 bps 9: 800 bps (no use) Note: Do not use setting 9 (800 bps) since BR-00 has no isolation. -

46 . HOW TO SET AND CHECK THE SYSTEM Merged sheet Settings for a Merged System. A Merged System uses the Cabin Panels of an IAS to forward the alarms generated at the BR-000. (The Cabin Panels of the BR-000 are not installed.) Consult with the IAS maker. Range: -8 Config sheet The Config sheet shows the software version of the BR-00. Modification of the contents of this sheet is not necessary. Use the sheet to upload and download data. -

47 . HOW TO SET AND CHECK THE SYSTEM. Settings for Processor Unit BR-00 Connect the PC to the BR-00 as shown below. Do the procedure below to update the BR-00. Settings - Network settings - Serial communications settings - Modbus settings PC for Maintenance Serial port Check, results LAN Processor Unit BR-00 Serial port Serial Software update How to update the BR-00 This section shows you how to update the BR-00. This is the only procedure available to update the BR-00.. Connect the PC to the BR-00 and turn on the Bridge Panel.. Open the Maintenance Excel file BR00CONF from the PC.. Open the Config sheet and click the Upload & Download button to show the BR-000 Maintenance window.. Check that the IP address for the BR-00 is correct then click the Download button.. Change the settings on the Processor Unit sheet. See Description of settings for BR-00 on the next page. -

48 . HOW TO SET AND CHECK THE SYSTEM. After you have set all items, reopen the Config sheet and click the Upload & Download button.. Check that the IP address shown in the window is correct. 8. Click the Upload button to upload setting data. When the uploading is completed, the message Complete appears. 9. Give a name to the updated definition file and save the file. Select a name that is easy to remember; for example, name of ship. 0.Disconnect the PC from the BR-00. Open the BR-00 then push the Reset button inside. RESET button S ON -

49 . HOW TO SET AND CHECK THE SYSTEM Description of settings for BR-00 Processor Unit sheet H [Network] Enter network settings here.. IP Address Set the IP address for the BR-00. Adjustment is normally not required.. Subnet mask Set the subnet mask for the BR-00. Adjustment is normally not required. [UART], [UART] UART and UART are settings for the serial lines for terminals TB- and TB- in the Processor Unit.. Modbus(RTU) / Modbus(ASCII) / NMEA Select a Modbus mode or NMEA for UART. 0: Modbus(RTU) : Modbus(ASCii) : NMEA (no use). Baudrate Set baudrate of UART. 0: DIPSW : 800 bps : 900 bps : 900 bps : 800 bps For 0(DIPSW), see the table below to set baud rate with DIP switch S, inside the BR-00. See page - for the location of S. S # S # Baudrate(bps) for TB- S # S # Baudrate(bps) for TB

50 . HOW TO SET AND CHECK THE SYSTEM. Data Bit Set data bit of UART. 0: bit : 8 bit. Stop Bit Set stop bit of UART. 0: bit : bit. Parity Set parity of UART. 0: None : Even : Odd [Modbus]. Slave Address Set slave address. Range: -. IAS Address(Start) Set the start address at the IAS side. (Range: -) Adjustment is normally not required, but may be required depending on the make of the IAS. If change is necessary, set this address the same as that for Range of IAS Adddress(Start) at the BR-00.. IAS address(end) Set the end address at the IAS side. (Range: -) Adjustment is normally not required, but may be required depending on the make of the IAS. If change is necessary, set this address the same as that for Range of IAS Adddress(End) at the BR-00.. BR Address(Start) Set the start address at the BR-000 side. (Range: -8) Adjustment is normally not required, but may be required depending on the make of the IAS. If change is necessary, set this address the same as that for Range of BR Adddress(Start) at the BR-00.. BR Address(End) Set the end address at the BR-000 side. (Range: -8) Adjustment is normally not required, but may be required depending on the make of the IAS. If change is necessary, set this address the same as that for Range of BR Adddress(End) at the BR

51 . HOW TO SET AND CHECK THE SYSTEM Config sheet The Config sheet shows the software version of the BR-00. Use this sheet to upload and download setting data. Modification of this sheet is not necessary. After entering all settings, click the Upload & Download button, enter the IP address of the BR-00 then click the Upload button to upload the setting data. -9

52 . HOW TO SET AND CHECK THE SYSTEM. System Operation Check You check the system operation from the Test Mode Menu. This method is faster than checking the bridge alarm and watch alarm through normal operation. Operation with the test mode active [Bridge alarm] The Initial Setting Display and the Alarm List editing screen cannot be opened when a bridge alarm is active. Press the BUZ STOP and ACK keys to stop an alarm. The system goes into Pending state then you can open the menu. To show the Initial Setting Display, press the ESC key and Pending Alarm appears at the screen center. Press the MENU key to show the display. Pending means that the buzzer has been stopped and alarm acknowledged, but the cause of the alarm has not yet been removed. [Watch alarm] The Initial Settings Display can be shown when a watch alarm is active. When a watch alarm is active and the MENU key is pressed, the audible alarm stops (audible alarms stop even if the alarm is sent to the next stage) and the window for password entry appears. The watch timer restarts after a watch alarm is stopped. If the bridge alarm and watch alarm are generated simultaneously, priority is given to the bridge alarm. In that case, the Initial Setting Display cannot be opened. Do the following to check operation. Note that the system returns to the standby display if there is no menu operation in 0 seconds.. Press the MENU key, and the message Enter Password appears. BRIDGE BRIDGE SYSTEM BR-000 WATCH MODE ONEMAN BACK-UP C/OFFICER NO Enter Password TIME INTERVAL MIN -0

53 . HOW TO SET AND CHECK THE SYSTEM. Press the up, down, left and right arrow pads on the Cursor pad followed by the LIST and ESC keys. This is the password to open the Service menu. BRIDGE Alarm WATCH Alarm MODE ONEMAN Service Menu Description System Setting Menu Cabin Panel Setting Menu Color Setting Menu Test Mode Menu Set BACK-UP C/OFFICER TIME INTERVAL MIN. Press the down arrow to select (highlight) Test Mode Menu then press the ENTER key. The values shown in the Set column are those uploaded from the PC. BRIDGE WATCH MODE ONEMAN BACK-UP C/OFFICER Test Mode Menu Description Set T e s t M ode O N / OFF OFF > T im e V is ua l / Audio Alarm s e c > Watch Time Interval sec > All Back-up Offcer Call Interval sec > Buzzer Silence Disable TIME INT MIN. With Test Mode ON/OFF selected, press the ENTER key. T e s t Mode ON/OFF OFF. Press the right arrow to select ON then press the ENTER key. T e s t M ode ON/OFF ON. Press the ESC key to show the following window. Do you want to save? Yes No Cancel. Select Yes then press the ENTER key. To return to the Service Menu without making any changes, select No then press the ENTER key. Select Cancel and press the ENTER key to close the window and return to the Test Mode menu. -

54 . HOW TO SET AND CHECK THE SYSTEM When Yes is selected and the MODE box at the left side of the display shows TEST MODE and the test mode starts. TEST MODE HARBOUR TEST MODE ATTENDED TEST MODE ONEMAN Note: To stop the test mode, select OFF at step in this procedure, press the ENTER key then do steps and. Make sure you quit the test mode by this method. The test mode generates the watch alarm faster than the normal method. Check that the Bridge Panel and all Timer Reset Panels and Cabin Panels operate normally. To check the bridge alarm, create a condition that causes an external equipment to generate an alarm. Check that all units of the system respond to the alarm. The alarm timing is shown in the illustration below and on the next page. - TIMER RESET - OPERATOR FITNESS - ACK If none of the above, alarm is forwarded BRIDGE PANEL TIMER RESET PANEL (incl. watertight type) Back-up nav. officer quarters and CABIN PANELS in all public areas Timer starts Watch Time Interval (0-0 s) After specified interval elapses st Prewarning stage Visual ALM* Visual ALM* + Audible ALM Time Visual/Audible Alarm Alarm setting (- s) *Red flashing at Bridge Panel, yellow flashing at Timer Reset Panel Visual ALM* + Audible ALM NO BUZZER STOP NO ACK Alarm forwarded nd stage Visual ALM (lighting) + Audible ALM BUZZER STOP ACK Visual ALM (lighting) + Audible ALM Timer reset All nav. officer quarters and CABIN PANELS in all public areas All Back-up Offcer Call Interval (0-0 s) rd stage Visual ALM (lighting) + Audible ALM Watch alarm sequence in test mode -

55 . HOW TO SET AND CHECK THE SYSTEM BRIDGE PANEL TIMER RESET PANEL (incl. watertight type) Back-up nav. officer quarters and CABIN PANELS in all public areas External equipment generates alarm st stage Visual ALM (red flashing) + Audible ALM (buzzer) Time Visual/Audible Alarm setting (- s) If NO BUZ STOP NO ACK, then alarm is forwarded Visual ALM (flashing) + Audible ALM nd stage Visual ALM (lighting) + Audible ALM NO BUZZER STOP NO ACK Alarm forwarded Visual ALM (lighting) + Audible ALM BUZZER STOP ACK Timer reset Back-up nav. officer quarters and CABIN PANELS in all public areas All Back-up Officer Call Interval (0-0 s) rd stage Visual ALM (lighting) + Audible ALM Bridge alarm sequence in test mode The Test Mode menu has various alarm-related parameters that can be changed. Adjustment is not normally required. Menu item: Time Visual / Audible Alarm (sec) Set the time interval for the visual and audible alarms in the test mode. T im e Visual / Audible Alarm (sec) sec The range is - (s). Use the left or right arrow to set. Menu item: Watch Time Interval Set the watch time interval for the test mode. Watch Time Interval (sec) 0 sec The setting range is 0-0 (s). The selected interval appears in the TIME INTERVAL box at the lower left corner. -

56 . HOW TO SET AND CHECK THE SYSTEM Menu item: All Back-up Officer Call Interval Set the time interval of the nd stage in the test mode. The range is 0-0 (s). All Back-up Officer Call Interval (sec) 0 sec Menu item: Buzzer Silence Enable or disable the buzzer for the bridge alarm and the watch alarm released from all panel units in the test mode. Lamps light or flash in both settings. Buzzer Silence Disable Buzzer Silence Enable. Service Menu The Service menu is for use by the service technician. The procedure for setting the system is described in section. and.. To make minor adjustments, do the procedure shown below... System Setting Menu The system returns to the standby display if there is no menu operation in 0 seconds.. Press the MENU key. The message "Enter Password" appears. BRIDGE BRIDGE SYSTEM BR-000 WATCH MODE ONEMAN BACK-UP C/OFFICER NO Enter Password TIME INTERVAL MIN -

57 . HOW TO SET AND CHECK THE SYSTEM. Press the up, down, left and right arrows on the Cursor pad followed by the LIST and ESC keys. This is the password to open the Service menu. BRIDGE Alarm WATCH Alarm MODE ONEMAN Service Menu Description System Setting Menu Cabin Panel Setting Menu Color Setting Menu Test Mode Menu Set BACK-UP C/OFFICER TIME INTERVAL MIN. System Setting Menu is selected (highlighted); press the ENTER key. BRIDGE WATCH MODE ONEMAN BACK-UP C/OFFICER TIME INTERVAL MIN DNV / IMO Mode Select Buzzer Type Description B ridge Panel B uzzer Tone (Hz) No. Processor Unit Connection Use External Siren IAS Connection AC Power Fail System Setting Menu Set IMO Continuous 0Hz No No Enable AL Open. DNV/ IMO Mode Select is selected; press the ENTER key. DNV / IMO M ode S e le c t IMO DNV / IMO M ode S e le c t DNV. Press the left or right arrow to select IMO or DNV. See Chapter in the Operator s Manual for a description of the IMO and DNV modes.. Press the ENTER key.. If required, set other items. -

58 . HOW TO SET AND CHECK THE SYSTEM 8. After you set all items required, press the ESC key to quit. You are asked if you are sure to save the settings. BRIDGE WATCH MODE ONEMAN BACK-UP C/OFFICER TIME INTERVAL MIN System Setting Menu Description Set DNV V/ I M O M ode S e le c t Buzzer Type IMO Continuous Bridge Panel Do you Buzzer want Tone to save? 0Hz No. Processor Yes Unit Connection No Cancel No Use External Siren Disable IAS Connection Enable AC Power Fail AL Open 9. Select Yes then press the ENTER key. Your settings are saved and the Service menu is redisplayed. To return to the Service Menu without making any changes, select No then press the ENTER key. Select Cancel then press the ENTER key to close the window and return to the Test Mode menu. Description of System Setting Menu Menu item Options Function DNV/ IMO Mode Select DNV, IMO Select the timing specification of alarm forwarding in the watch alarm. DNV: Det Norske Veritas IMO: International Maritime Organization Buzzer Type Continuous, Intermit Select buzzer type. Continuous: Continuous buzzer Intermit: Intermittent buzzer Bridge Panel Buzzer Tone (Hz) Hz Set the frequency of the buzzer released from the Bridge Panel. No. Processor Unit Connection Enable, Disable Select whether the No. Processor Unit is connected or not. Enable: Connected Disabled: Not connected Use External Siren Enable, Disable Use external siren or not. Enable: Use external siren. Disable: Don t use external siren. IAS Connection Enable, Disable Select whether IAS is connected or not. Enable: Connected Disable: Not connected AC Power Fail AL Close, AL Open Set input terminals #, # of TB in BR-00. AL Close: Close, normally open AL Open: Open, normally closed -

59 . HOW TO SET AND CHECK THE SYSTEM.. Cabin Panel Setting Menu The purpose of this menu is to give names to the Cabin Panels. Record beforehand where the Cabin Panels are connected (TB-TB) on the Processor Unit.. At the Service menu, select Cabin Panel Setting Menu then press the ENTER key. BRIDGE WATCH MODE ONEMAN BACK-UP C/OFFICER Cabin Panel Setting Menu Description Description Cabin Panel Cabin Panel Cabin Panel Cabin Panel Cabin Panel Cabin Panel 8 Cabin Panel Cabin Panel 9 Cabin Panel Cabin Panel 0 TIME INTERVAL MIN. Cabin Panel is selected; press the ENTER key. BRIDGE WATCH Description Panel Type Panel Name Cabin Panel Set Captain Capt. MODE ONEMAN BACK-UP C/OFFICER TIME INTERVAL MIN. Panel Type is selected; press the ENTER key. The panel type selection window appears. Panel Type Captain Panel Type Back-up Panel Type Public. Use the left or right arrow to select a type then press the ENTER key. Captain: For the Cabin Panel installed in the Captain s room. Back-up: For the Cabin Panel installed in the sleeping quarters of the backup officer. Consult with the Captain of the ship to set this item. Public: For the Cabin Panel installed in a public area. -

60 . HOW TO SET AND CHECK THE SYSTEM. Select Panel Name then press the ENTER key. The Panel Name entry window appears. The names for cabin panels are contained in the definition file. If required, you can change the name here. Panel Name Capt.. Enter the title of the person who uses the room or the name of the room. Press the ENTER key. The name can have up to 0 alphanumeric characters. See the illustration below for how to enter name.. Enter the name for other Cabin Panels if necessary. 8. Press the ESC key to close the window. 9. Select Yes then press the ENTER key to save settings and return to the Service menu. How to enter data When you open the data input window, a flashing cursor is to right of the entered alphabet. The keyboard appears together with the text input box and the alphabet q is selected (highlighted). Menu item Alarm Text Input field No. Ra da r CPA / TCPA / GZI Input cursor: Red vertical bar Item selected (yellow highlight) _ = ` q w e r t y u i o p [ ] \ a s d f g h j k l ; z x c v b n m. / End Caps Shift BS Space Software keyboard. Use the Cursor pad on the Bridge Panel to put the cursor on [ ] on the keyboard.. Press the ENTER key. The input cursor moves to the input field.. Do steps and to set the cursor to the right of the character to change.. Use the up or down arrow on the Bridge Panel to select BS on the keyboard.. Press the ENTER key. The character to the left of the cursor is erased.. Use the up or down arrow on the Bridge Panel to select the character to input then press the ENTER key. The selected character appears to the left of the cursor.. After you have finished selecting characters, select End on the keyboard then press the ENTER key. The keyboard is erased. -8

61 .. Color Setting Menu. HOW TO SET AND CHECK THE SYSTEM The Color Setting menu sets the background color, font color, etc. Menu item: Basic Color Setting. At the Service menu, select Color Setting Menu then press the ENTER key to show the Color Setting Menu. BRIDGE WATCH MODE ONEMAN BACK-UP C/OFFICER Color Setting Menu Description Basic Color Setting B ridge Alarm Color S etting Watch Alarm Color Setting M ODE Color Setting BACK-UP Color Setting TIME INTERVAL Color Setting Set TIME INTERVAL MIN. Basic Color Setting menu is selected; press the ENTER key. BRIDGE WATCH MODE ONEMAN BACK-UP C/OFFICER TIME INTERVAL MIN Basic Color Setting Description Set Background Font Frame High Light Parameter Display - Background - Font -Frame - Arrow. Background is selected; press the ENTER key. A thick blue cursor frames the currently selected color in the Color Palette. BRIDGE WATCH MODE ONEMAN BACK-UP C/OFFICER TIME INTERVAL MIN Basic Color Setting Description Set Color Pallet Background Font Frame High Light Parameter r Display -l Ba a c k ground - Font - Frame - Arrow Currently selected color A blue cursor frames the currently selected color.. Use the arrow pads to select a color then press the ENTER key. The Color Palette is erased and the selected color appears in the Set column.. Use the up or down arrow to select another item for which to set color. See the table on the next page for a description of each item. -9

62 . HOW TO SET AND CHECK THE SYSTEM. After you have set all items, press the ESC key. The save confirmation window appears.. Select Yes then press the ENTER key. Menu item No. of colors Function Location* Background 0 colors Background color () Font 0 colors Normal font color () Frame 0 colors Normal frame color () High Light 0 colors Color of the highlight cursor () Parameter Display Background Parameter Display Font Parameter Display Frame Parameter Display Arrow 0 colors Background color for the Parameter Setting Display 0 colors Font color for the Parameter Setting Display 0 colors Color of the frame in the Parameter Setting Display 0 colors Color of the arrow in the Parameter Setting Display () () () (8) * See page -8 for location. Bridge Alarm Color Setting Set colors for the bridge alarm related displays, such as the Auto Alarm Pop-up Display that appears when a bridge alarm is generated. Menu item No. of colors Function Location* Bridge Alarm Display Page 0 colors Color for page number in the Bridge Alarm Display Page () BRIDGE Font 0 colors Color for BRIDGE () * See page -8 for location. Watch Alarm Color Setting Select the font color for the WATCH indication. Menu item No. of colors Function Location* WATCH Font 0 colors Color for WATCH () * See page -9 for location. -0

63 . HOW TO SET AND CHECK THE SYSTEM MODE Color Setting Select the colors related to the MODE indication. Menu item No. of colors Function Location* MODE Font 0 colors Color for MODE () Parameter Font 0 colors Color for the parameter () MODE Background 0 colors Background color for MODE () ATTEND, ONEMAN Background 0 colors Background color for ATTEND, ONEMAN () * See page -9 for location. BACK-UP Color Setting Select the colors related to the BACK-UP indication. Menu item No. of colors Function Location* BACK-UP Font 0 colors Color for BACK-UP () Parameter Font 0 colors Color for the parameter () Background 0 colors Background color for BACK-UP () * See page -0 for location. TIME INTERVAL Color Setting Select the colors related to the TIME INTERVAL indication. Menu item No. of colors Function Location* TIME INTER- VAL Font 0 colors Color for TIME INTERVAL () Parameter Font 0 colors Color for the parameter () Background 0 colors Background color for TIME INTERVAL () * See page -0 for location. -

64 . HOW TO SET AND CHECK THE SYSTEM. How to Edit the Alarm List If modification of the data uploaded from the PC is required, follow the procedure in this section to modify the settings from the Bridge Panel. When the Alarm List editing screen is active, the system operates as follows: The system monitors the bridge alarm and watch alarm when the Alarm List editing screen is in use, but does not generate alarms. When you quit the Alarm List editing screen, the system generates bridge alarm if there is an alarm active. If an alarm is generated when the Alarm List editing screen is active, the BRIDGE box on the Bridge Panel flashes red, but the audible alarm does not sound from the Bridge Panel or Timer Reset Panel and no alarms are forwarded. The timer is reset when you quit the Alarm List editing screen. The st stage of the bridge alarm operates. You cannot use the Alarm List editing screen if a bridge alarm is active or the watch alarm is past the nd stage, If an alarm is generated, press the BUZ STOP and ACK keys to stop the alarms. Then you can use the Alarm List editing screen. After you acknowledge a bridge alarm with the ACK key, the Bridge Panel shows Pending until the cause for the alarm is removed. You can use the Alarm List editing screen in this condition. When you quit the Alarm List editing screen, the bridge alarm and watch alarm timers are reset. If the cause of the bridge alarm has not been removed, the bridge alarm starts from the st stage. Alarm List editing screen The system restores the standby display when there is no menu operation in 0 seconds. Settings are not saved when this occurs.. At the standby display, press the LIST key to show the Bridge Alarm Display.. Press the EDIT key, and the message "Enter Password" appears. BRIDGE WATCH MODE ONEMAN BACK-UP C/OFFICER TIME INTERVAL MIN Tag Description 00 No. Radar Sys Fail 00 No. Radar Sys Fail 00 No. Radar Sys Fail 00 No. Radar Enter CPA/TCPA/GZ Password 00 No. Radar CPA/TCPA/GZ 00 No. Radar CPA/TCPA/GZ 00 No. RADAR System Error 008 No. RADAR System Error Priority Secondary Secondary Secondary Urgency Urgency Urgency Secondary Secondary -

65 . HOW TO SET AND CHECK THE SYSTEM. Press the up, down, left and right arrows on the Cursor pad followed by the LIST and ESC keys. This is the password to open the Alarm List editing screen. Page numbers appear at the top of the screen and the currently selected page number flashes. The cursor selects the first item in the selected page. Selected page no. flashes every 0. s. BRIDGE WATCH MODE ONEMAN BACK-UP C/OFFICER TIME INTERVAL MIN Tag Description Priority No. Radar Sys Fail No. Radar Sys Fail No. Radar Sys Fail No. Radar CPA/TCPA/GZ No. Radar CPA/TCPA/GZ No. Radar CPA/TCPA/GZ No. RADAR System Error No. RADAR System Error Secondary Secondary Secondary Urgency Urgency Urgency Secondary Secondary. Use the left or right arrow to select the page to edit.. Use the up or down arrow to select the item to edit then press the ENTER key. For example, if you select Tag 00 on page, the screen looks like the one shown below. This tag is for the input signal connected to #/8 of TB in the Processor Unit. Tag 00 on page is for the input signal connected to #/ of TB in the Processor Unit. BRIDGE WATCH MODE ONEMAN BACK-UP C/OFFICER 00 No. Radar CPA/TCPA/GZ Description Set Input Unit Channel Number/Modbus Address PU 0 Alarm Text Group Number 0 Alarm Priority / Status Urgency Type of Signal AL Close Active / Inactive Active BRIDGE WATCH MODE ONEMAN BACK-UP C/OFFICER 00 No. Radar CPA/TCPA/GZ Description Set Alarm Type Normal Repeat Alarm Address Send to VDR Disable TIME INTERVAL MIN Alarm Extend ON TIME INTERVAL MIN As shown in the illustration there are items per input signal.. Use the arrow pads to select the item to edit then press the ENTER key. For example, select Active/Inactive. The following window appears. Current setting BRIDGE WATCH MODE ONEMAN BACK-UP C/OFFICER TIME INTERVAL MIN 00 No. Radar CPA/TCPA/GZ Description Set Input Unit Channel Number/Modbus Address Alarm Text Active / Inactive Group Number Active Alarm Priority / Status Type of Signal PU 0 0 Urgency AL Close Active / Inactive Active Alarm Extend ON. Use the left or right arrow to select setting then press the ENTER key. -

66 . HOW TO SET AND CHECK THE SYSTEM 8. After you have set all items required, press the ESC key. 9. To change another input signal, do steps through 8. 0.Press the ESC key to quit. Description of Items in Alarm List editing screen () Input Unit Set the medium which receives the alarm signals. PU: No. Processor Unit PU: No. Processor Unit Modbus: Modbus PU is not shown when No. Processor Unit Connection is set for Disabled. () Channel Number/Modbus Address Select digital channel or Modbus address. Use digital channel if Input Unit (above) is set for PU or PU. In that case the setting range is For Modbus, the setting range is C hannel Number/Modbus Address 0 0 See the previous section for how to enter alphanumeric data. () Alarm Text Edit the name of the alarm for connected equipment. The name can have up to alphanumeric characters. You can use upper case, lower case, numerals and symbols. If there are many alarm signals connected, be sure to select a name which identifies the alarm clearly. Characters are entered the same as described in the previous section. Alarm names are shown on the Bridge Alarm Display and Auto Alarm Pop-up Display. Alarm Text () Group Number This system allows you to register in groups the equipment that transmits the REMOTE ACK OUT signal (buzzer stop) and receives the LOCAL ACK IN signal (buzzer stop). - PU, PU: Modbus: 0-09 For example, four types of alarm signals from the No. radar are connected to the system. Assign a group number to those alarm signals. Group Number 0 0 -

67 . HOW TO SET AND CHECK THE SYSTEM () Alarm Priority/Status Set priority and status for the alarm selected. Consult with ship personnel to decide alarm priority. Priority is shown on the Bridge Alarm Display and Auto Alarm Pop-up Display. Alarm Priority / Status Secondary Alarm Priority / Status Primary Alarm Priority / Status Urgency Alarm Priority / Status Emergency () Type of Signal Set the type of contact signal input from external equipment, among the three choices described below. - AL Open: Contact signal opens when an alarm is generated (NC signal). - AL Close: Contact signal closes when an alarm is generated (NO signal). - Modbus: Modbus setting () Active / Inactive Make an alarm active or inactive. Active: Selected alarm is watched by the system. Alarm name in the Alarm List is white. Inactive: Selected alarm is not watched by the system. Alarm name in the Alarm List is gray. Active / Inactive Inactive Active / Inactive Active BRIDGE WATCH MODE ONEMAN BACK-UP C/OFFICER TIME INTERVAL MIN Tag Description Priority No. Radar Sys Fail No. Radar Sys Fail No. Radar Sys Fail No. Radar CPA/TCPA/GZ No. Radar CPA/TCPA/GZ No. Radar CPA/TCPA/GZ No. RADAR System Error No. RADAR System Error Secondary Secondary Secondary Urgency Urgency Urgency Secondary Secondary Active: Alarm name in white Inactive: Alarm name in gray -

68 . HOW TO SET AND CHECK THE SYSTEM (8) Alarm Extend This is a special feature. If an external equipment recovers normally before the BUZ STOP and ACK keys on the bridge are operated, select whether to extend or don t extend an alarm condition until the BUZ STOP and ACK keys are operated. 0: OFF (Don t extend alarm) : ON (Extend alarm) Alarm Extend OFF Alarm Extend ON (9) Alarm Type Set the type of alarm to use for the Modbus alarm, repeat alarm or normal alarm. Alarm Type Normal Alarm Type Repeat (0) Repeat Alarm Address Set the Modbus address to processed as a Repeat Alarm, when Alarm Type is set for Repeat. This setting is invalid when Alarm Type is set for Normal. The setting range is Repeat Alarm Address () Send to VDR Output or don t output the ALR sentence to the VDR when a related alarm is generated. - Disable: No output - Enable: Output the ALR sentence Send to VDR Disable Send to VDR Enable -

69 APPENDIX JIS CABLE GUIDE Cables listed in the manual are usually shown as Japanese Industrial Standard (JIS). Use the following guide to locate an equivalent cable locally. JIS cable names may have up to alphabetical characters, followed by a dash and a numerical value (example: DPYC-.). For core types D and T, the numerical designation indicates the cross-sectional Area (mm ) of the core wire(s) in the cable. For core types M and TT, the numerical designation indicates the number of core wires in the cable.. Core Type. Insulation Type D T M TT Double core power line Triple core power line mm Multi core P Ethylene Propylene 0.mm twisted pair communications (Q = quad cable). Sheath Type Y Vinyl DPYC. Armor Type. Shielding Type. Core Sheath C Steel Y Corrosive resistant S -S All cores in one sheath Individually sheathed cores TPYC EX: DPYCYS -. MPYC - Designation type Core Area (mm ) Designation type # of cores MPYC- TTYCS- The following reference table lists gives the measurements of JIS cables commonly used with Furuno products: Core Cable Core Cable Type Area Diameter Diameter Type Area Diameter Diameter DPYC-..mm.mm.mm TPYCY-..mm.mm.mm DPYC-..mm.0mm.8mm TPYCY-..mm.0mm.mm DPYCY-..mm.0mm.8mm TPYCY- mm.mm.9mm DPYCYS-..mm.mm.mm TPYCYS-..mm.mm.mm DPYCYS-..mm.0mm.mm MPYC- mm.9mm 0.0mm MPYC- mm.9mm.mm MPYC- MPYCY- mm.9mm.mm mm.9mm 9.0mm MPYCY-9 mm.9mm.0mm TTYCS- 0.mm.mm 0.mm TTYCS-Q 0.mm.mm.mm TTYCS- 0.mm.mm.mm TTYCYS- 0.mm.mm.mm AP-

70 A- A-

71 A- A-

72 A-

73

74

75

76

77

78

79

80 A B C D IAS MODBUS IN/OUT MODBUS IN/OUT 制 御 部 PROCESSOR UNIT BR-00 IN - IN -8 IN 9- IN - IN -0 IN - IN -8 IN 9- IN - IN -0 IN - IN -8 8 J TX-P TX-N RX-P NC NC RX-N NC NC TB TB 8 TB 9 0 TB TB TB TB8 8 TB9 9 0 TB0 TB TB TB 8 * IV-sq. * DPYC-. * PE-PTX-BL-CB,//0m RJ FR-FTPC-CY RJ MPYC * (-) (+) TB TB RXA RXB ISOG TXA TXB JP JP JP JP JP TB RXA RXB ISOG TXA TXB JP JP JP JP JP TB/ RXA RXB ISOG TXA TXB JP JP JP JP JP * TTYCS- P P TD-A TD-B -ISO RD-A RD-B -ISO * * 航 法 装 置 NAV EQUIPMENT TB8 V WA BA BUZ STP RST TB9 V WA BA BUZ STP RST TB0 V WA BA BUZ STP RST TB V WA BA BUZ STP RST TB A+ COM B+ TB A+ COM B+ TB TB8 8 MPYC- * MPYC- * MPYC- * MPYC- * MPYC * 同 上 DITTO TD-A TD-B -ISO RD-A RD-B -ISO IAS * TTYCS- * または OR TB0 A COM NC NC TB AP AP PF NC NC 8 * MPYC- * MPYC- MPYC- * 同 上 DITTO 同 上 DITTO 同 上 DITTO 同 上 DITTO VDR OR IAS VDR OR IAS AUTOPILOT オートパイロット PR-0 TB(,) TIMER RESET PANEL TIMER RESET PANEL TIMER RESET PANEL TIMER RESET PANEL SYSTEM FAIL OUT / OPERATORS FITNESS IN - OPERATORS FITNESS IN - EXTERNAL SIREN OUT AUTOPILOT MODE IN/PF IN 同 上 DITTO 同 上 DITTO 同 上 DITTO 同 上 DITTO 同 上 DITTO 同 上 DITTO 同 上 DITTO 同 上 DITTO 同 上 DITTO 同 上 DITTO 同 上 DITTO 航 法 装 置 NAV EQUIPMENT NETWORK TX-P TX-N RX-P NC NC RX-N NC NC 8 ブリッジパネル BRIDGE PANEL BR-00 MJ-ASPF00,.m TB MJ-ASPF (+) シロ WHT A CN (+) (-) クロ BLK (-) E ミト リ GRN MJ-ASPF NMEA * MJ-ASPF000,/0m,φ シロ WHT クロ BLK RD-C NC SHIELD NMEA TD-A TD-B RD-H RD-C +V SHIELD * IV-sq. VDR GPS RX-H RX-C TD-A TD-B * MJ-ASPF000,0m,φ MJ-ASPF000,m,φ キ YEL ミト リ GRN AC/DC POWER SUPPLY UNIT PR-0 IV-sq. * VDC TB ACIN ACIN DCIN+ DCIN- TB ACFAIL ACFAIL 注 記 *) 造 船 所 手 配 *)オプション NOTE *: SHIPYARD SUPPLY. *: OPTION. *: MAX. CABIN PANELS CAN BE INSTALLED AT ANOTHER ROOM. *)キャビンパネルは 最 大 台 まで 分 岐 可 能 *) 信 号 種 類 に 応 じてジャンパー 設 定 を 変 更 する *: CHANGE JUMPER SETTING AS SIGNAL LEVEL. DRAWN CHECKED APPROVED SCALE DWG No. /Mar/09 /Mar/09 MASS kg REF.No. TITLE 00/0VAC φ,0/0hz TB(,) BR-00 * DPYC-. * DPYC-. * MPYC- P MJ-ASPF P TB V DTY ALM BUZ TB V DTY ALM BUZ TB V DTY ALM BUZ TB V DTY ALM BUZ TD-A TD-B RD-H P P P P BR-00 CABIN PANEL CABIN PANEL CABIN PANEL CABIN PANEL CABIN PANEL V DUTY ALM BUZ TEST NC 8 8 TB8 CABINTEST TB9 CABINTEST CABINTEST CABINTEST CABINTEST TB V DTY ALM BUZ TB TB TB TB TB TB 8 TB REMOTE ACK OUT - REMOTE ACK REMOTE ACK REMOTE ACK OUT - OUT -9 OUT 0- LOCAL ACK IN - LOCAL ACK IN -8 LOCAL ACK IN 9- CABIN PANEL CABIN PANEL CABIN PANEL8 CABIN PANEL9 CABIN PANEL0 V DUTY ALM BUZ TEST NC V DUTY ALM BUZ TEST NC BR-00 # (TEST) BR-00 # (TEST) BR-00 # (TEST) BR-00 #-#0 (TEST) * MPYC- * MPYC- 同 上 DITTO BR-00 # JB * 同 上 DITTO BR-00 # 同 上 DITTO BR-00 # 同 上 DITTO BR-00 # JB * JB * * MPYC- * MPYC- TB9() CABINTEST TB V DTY ALM BUZ TB8 V DTY ALM BUZ TB9 V DTY ALM BUZ TB0 V DTY ALM BUZ TB V DTY ALM BUZ JB * 同 上 DITTO BR-00 # 同 上 DITTO BR-00 #8 * 同 上 DITTO BR-00 #9 * 同 上 DITTO BR-00 #0 同 上 DITTO 同 上 DITTO 同 上 DITTO 同 上 DITTO 同 上 DITTO 航 法 装 置 NAV EQUIPMENT 航 法 装 置 NAV EQUIPMENT * MPYC * MPYC V WATCH_ALM BRIDGE_ALM BUZZER BUZZER_STOP TIMER_RESET * IV-sq. タイマーリセットパネル TIMER RESET PANEL BR-00/00 * MPYC- MPYC- * EXT.SIREN 外 部 サイレン 電 源 POWER SUPPLY JB * JB * JB * キャビンパネル CABIN PANEL BR-00 # * IV-sq. キャビンパネル CABIN PANEL * BR-00 # * IV-sq. 選 択 標 準 :- 台 SELECTIVE STANDARD: BETWEEN AND SETS キャビンパネル CABIN PANEL BR-00 # * IV-sq. T.YAMASAKI BR-000 T.TAKENO C0-C0- B 名 称 NAME ブリッジアラームシステム 相 互 結 線 図 BRIDGE SYSTEM INTERCONNECTION DIAGRAM

81 制 御 部 PROCESSOR UNIT BR-00(No.) 制 御 部 PROCESSOR UNIT BR-00(No.) * A PR-0 TB(,) 8 * DPYC-. J MOD-Z0,m RJ RJ 8 J 8 TB PF TB (+) (-) STP LAN CABLE (CAT) RJ TX-P TX-N RX-P RJ NC NC RX-N NC NC TX-P TX-N RX-P NC NC RX-N NC NC 8 DPYC-. * TB (+) (-) B C PE-PTX-BL-CB m RJ MJ-ASPF00,.m RJ CN CN MJ-ASPF TX-P TX-N RX-P (+) (-) シロ WHT A クロ BLK ミト リ GRN NC NC RX-N ブリッジパネル BRIDGE PANEL BR-00 NC NC シロ WHT クロ BLK 8 8 IV-sq. * イーサネットハブ ETHERNET HUB HUB-0 * VHP-MVVS0.xC,.m JUNCTION BOX * TPYC-. * * IV-sq. TB (+) (-) E AC/DC POWER SUPPLY UNIT TB ACIN ACIN DCIN+ DCIN- TB * PR-0 ACFAIL ACFAIL D 注 記 *) 造 船 所 手 配 *)オプション NOTE *: SHIPYARD SUPPLY. *: OPTION. * DPYC-. * DPYC-. 00/0VAC φ,0/0hz VDC * MPYC- BR-00(No.) DRAWN /May/08 CHECKED /May/08 APPROVED SCALE DWG.No. T.YAMASAKI T.TAKENO MASS kg REF.No. C0-C0- A TITLE 名 称 NAME BR-000 ブリッジアラームシステム(No.) 相 互 結 線 図 BRIDGE SYSTEM (No.) INTERCONNECTION DIAGRAM

82 PROCESSOR UNIT CONNECTION LIST S- IN REMOTE ACK OUT Terminal No. Device Signal Name, Type Terminal No. Device TB #/ TB #/ #/ #/ #/ #/ #/8 #/8 TB #/ TB #/ #/ #/ #/ #/ #/8 #/8 TB #/ #/ TB #/ #/ #/ #/8 #/ TB #/ #/8 #/ #/ TB #/ #/8 #/ #/ LOCAL ACK IN #/8 Terminal No. Device TB #/ TB #/ #/ #/ #/ #/ #/8 #/8 TB #/ #/ TB #/ #/ #/ #/8 #/ TB #/ #/8 #/ #/ TB8 #/ #/8 #/ TB #/ #/ #/ #/8 #/ #/8 TB9 #/ #/ OPERATOR FITNESS IN #/ Terminal No. Device #/8 TB #/ #/ TB0 #/ #/ #/ #/8 #/ TB8 #/ #/8 #/ #/ TB #/ #/ CABIN PANEL #/ Terminal No. Device #/8 TB TB TB #/ TB #/ TB #/ TB #/8 TB TB8 TB #/ TB9 #/ TB0 #/ TB #/8

83 No. PROCESSOR UNIT (option) CONNECTION LIST S- IN REMOTE ACK OUT 端 子 台 Device Signal Name, Type Terminal No. Device TB #/ TB #/ #/ #/ #/ #/ #/8 #/8 TB #/ TB #/ #/ #/ #/ #/ #/8 #/8 TB #/ #/ TB #/ #/ #/ #/8 #/ TB #/ #/8 #/ #/ TB #/ #/8 #/ #/ LOCAL ACK IN #/8 Terminal No. Device TB #/ TB #/ #/ #/ #/ #/ #/8 #/8 TB #/ #/ TB #/ #/ #/ #/8 #/ TB #/ #/8 #/ #/ TB8 #/ #/8 #/ TB #/ #/ #/ #/8 #/ #/8 TB9 #/ #/ OPERATOR FITNESS IN #/ Terminal No. Device #/8 TB #/ #/ TB0 #/ #/ #/ #/8 #/ TB8 #/ #/8 #/ #/ TB #/ #/ #/ #/8 TB #/ #/ #/ #/8 TB #/ #/ #/ #/8

AMI MARINE (UK) LTD BRIDGE NAVIGATIONAL WATCH ALARM SYSTEM (BNWAS) Operation Manual KW810

AMI MARINE (UK) LTD BRIDGE NAVIGATIONAL WATCH ALARM SYSTEM (BNWAS) Operation Manual KW810 AMI MARINE (UK) LTD BRIDGE NAVIGATIONAL WATCH ALARM SYSTEM (BNWAS) Operation Manual KW810 This Manual and the information contained therein is the property of AMI Marine (UK) Ltd. It must not be reproduced

More information

OPERATION MANUAL. MV-410RGB Layout Editor. Version 2.1- higher

OPERATION MANUAL. MV-410RGB Layout Editor. Version 2.1- higher OPERATION MANUAL MV-410RGB Layout Editor Version 2.1- higher Table of Contents 1. Setup... 1 1-1. Overview... 1 1-2. System Requirements... 1 1-3. Operation Flow... 1 1-4. Installing MV-410RGB Layout

More information

User Manual Revision 1.400 English Converter / Adapter Ethernet to RS232 / RS485 (Order Code: HD67038-2 HD67038-2-M HD67038-25 HD67038-25-M)

User Manual Revision 1.400 English Converter / Adapter Ethernet to RS232 / RS485 (Order Code: HD67038-2 HD67038-2-M HD67038-25 HD67038-25-M) Document code: MN67038-2_ENG Revision 1.400 Page 1 of 25 User Manual Revision 1.400 English Converter / Adapter Ethernet to RS232 / RS485 (Order Code: HD67038-2 HD67038-2-M HD67038-25 HD67038-25-M) for

More information

MAKING MODERN LIVING POSSIBLE. AK-SC255 On-Site Installation Guide DANFOSS ELECTRONIC CONTROLS & SENSORS

MAKING MODERN LIVING POSSIBLE. AK-SC255 On-Site Installation Guide DANFOSS ELECTRONIC CONTROLS & SENSORS MAKING MODERN LIVING POSSIBLE AK-SC255 On-Site Installation Guide DANFOSS ELECTRONIC CONTROLS & SENSORS How to Use This Guide Read this Guide completely as you install and start up your new AK-SC 255 controller.

More information

Manual for Fire Suppression & Methane Detection System

Manual for Fire Suppression & Methane Detection System Manual for Fire Suppression & Methane Detection System Fogmaker North America Post address: 150 Gordon Dr Exton, PA 19341 Delivery address: 150 Gordon Dr Exton, PA 19341 Tel: 610-265-3610 Fax: 610-265-8327

More information

AC-115 Compact Networked Single Door Controller. Installation and User Manual

AC-115 Compact Networked Single Door Controller. Installation and User Manual AC-115 Compact Networked Single Controller Installation and User Manual December 2007 Table of Contents Table of Contents 1. Introduction...5 1.1 Key Features... 6 1.2 Technical Specifications... 7 2.

More information

HyperAccess Access Control System

HyperAccess Access Control System Control System We manufacture, an advanced PC based access control solution that will give you control over who has access to your building. With you can control access on hundreds of doors for up to 10,000

More information

ENET-710. ENET-710 - Ethernet Module ENET-710 JAN / 06 FOUNDATION

ENET-710. ENET-710 - Ethernet Module ENET-710 JAN / 06 FOUNDATION ENET-710 ENET-710 - Ethernet Module JAN / 06 ENET-710 FOUNDATION E N E T 7 1 0 ME smar www.smar.com Specifications and information are subject to change without notice. Up-to-date address information is

More information

Firmware version: 1.10 Issue: 7 AUTODIALER GD30.2. Instruction Manual

Firmware version: 1.10 Issue: 7 AUTODIALER GD30.2. Instruction Manual Firmware version: 1.10 Issue: 7 AUTODIALER GD30.2 Instruction Manual Firmware version: 2.0.1 Issue: 0.6 Version of the GPRS transmitters configurator: 1.3.6.3 Date of issue: 07.03.2012 TABLE OF CONTENTS

More information

* DISCLAIMER: Contents. How to Use This Guide: COMMERCIAL INSTALL GUIDE 2

* DISCLAIMER: Contents. How to Use This Guide: COMMERCIAL INSTALL GUIDE 2 COMMERCIAL INSTALL GUIDE 2 Contents How to Use This Guide: The first section of this guide is designed to assist you with the installation of your DECK Monitoring hardware. The revenue grade meter and

More information

How to read this guide

How to read this guide How to read this guide The following shows the symbols used in this Quick start guide with descriptions and examples. Symbol Description Example P oint Reference Caution [ ] This symbol explains information

More information

Application/Connection Examples

Application/Connection Examples This Quick Start Guide is designed to familiarize the user with the connection and configuration of the DTS-305 DIN rail mounted single / 3 phase power & energy meter with RS-485 or TCP communications.

More information

The GV-I/O Box 8 Ports provides 8 inputs and 8 relay outputs, and supports both DC and AC output voltages.

The GV-I/O Box 8 Ports provides 8 inputs and 8 relay outputs, and supports both DC and AC output voltages. GV-I/O Box 8 Ports The GV-I/O Box 8 Ports provides 8 inputs and 8 relay outputs, and supports both DC and AC output voltages. Key Features 8 inputs and 8 outputs are provided. Up to 9 pieces of GV-I/O

More information

Network Interface Panel User s Guide NPD4747-01 EN

Network Interface Panel User s Guide NPD4747-01 EN User s Guide NPD4747-01 EN Contents Contents Copyright and Trademarks Safety Instructions Important Safety Instructions... 4 Cautions and Notes... 4 Getting to Know Your Network Interface Panel Package

More information

GV- RK1352 Card Reader

GV- RK1352 Card Reader GV- RK1352 Card Reader The GV-RK1352 is a card reader with keypad, designed to recognize PIN codes, identification cards or both. Featured with the Wiegand and RS-485 outputs, the unit can be connected

More information

M1000 Process Alarm Monitor

M1000 Process Alarm Monitor Data Sheet Process Alarm Monitor Reliable Supervision and Control 10 inputs with LED indications Supports both NO/NC input contacts 10 open collector outputs Built-in siren relay Text label for alarm descriptions

More information

Software User Guide UG-461

Software User Guide UG-461 Software User Guide UG-461 One Technology Way P.O. Box 9106 Norwood, MA 02062-9106, U.S.A. Tel: 781.329.4700 Fax: 781.461.3113 www.analog.com ezlinx icoupler Isolated Interface Development Environment

More information

LEN s.r.l. Via S. Andrea di Rovereto 33 c.s. 16043 CHIAVARI (GE) Tel. +39 0185 318444 - Fax +39 0185 472835 mailto: [email protected] url: http//www.len.

LEN s.r.l. Via S. Andrea di Rovereto 33 c.s. 16043 CHIAVARI (GE) Tel. +39 0185 318444 - Fax +39 0185 472835 mailto: len@len.it url: http//www.len. MA511 General Index 1 INTRODUCTION... 3 1.1 HARDWARE FEATURES:... 4 2 INTERFACE... 5 2.1 KEYBOARD... 6 2.2 POWER ON... 7 2.3 POWER OFF... 7 2.4 DETECTOR CONNECTION... 7 2.5 DETECTOR SUBSTITUTION...7 3

More information

Bluetooth to Serial Adapter

Bluetooth to Serial Adapter Bluetooth to Serial Adapter Third Edition, Oct 2007 Version 3.0 771-BTS1009C3-001 Contents 1.0 Features....P.2 2.0 Package Content....P.2 3.0 Hard Drives Requirement.P.2 4.0 Specifications.P.3 5.0 Pin

More information

EDI Distributor Control Interface Wiring and Setup Instructions

EDI Distributor Control Interface Wiring and Setup Instructions Universal I/O EDI Distributor Control Interface Wiring and Setup Instructions EDI UNIVERSAL I/O INTERFACE MODULE The only interface needed for EDI-V5 controls Network compatible with all older EDI controls

More information

PCS300 Universal IP Reporting Module V1.0

PCS300 Universal IP Reporting Module V1.0 PCS300 Universal IP Reporting Module V1.0 Reference and Installation Manual Patents: One or more of the following US patents may apply: 7046142, 6215399, 6111256, 6104319, 5920259, 5886632, 5721542, 5287111,

More information

CMC-DN01 DeviceNet Slave Communication Card Operation Manual

CMC-DN01 DeviceNet Slave Communication Card Operation Manual CMC-DN01 DeviceNet Slave Communication Card Operation Manual 2011-12-26-A Warning This operation manual provides introduction on the functions, specifications, installation, basic operation and settings

More information

The GV-I/O Box 16 Ports provides 16 inputs and 16 relay outputs, and supports both DC and AC output voltages.

The GV-I/O Box 16 Ports provides 16 inputs and 16 relay outputs, and supports both DC and AC output voltages. GV-I/O Box 16 Ports The GV-I/O Box 16 Ports provides 16 inputs and 16 relay outputs, and supports both DC and AC output voltages. Key Features 16 inputs and 16 outputs are provided. Up to 9 pieces of GV-I/O

More information

GSM AD05 Slave GSM Auto Dialer- Instruction Manual

GSM AD05 Slave GSM Auto Dialer- Instruction Manual GSM AD05 Slave GSM Auto Dialer- Instruction Manual Please read these instructions before you start the installation Features LCD display Programmable 9 x 32 digit phone numbers for each trigger. 10 second

More information

Voice Over Internet Protocol (VoIP) Configuration

Voice Over Internet Protocol (VoIP) Configuration (VoIP) Configuration ENGINEERING REPORT No: 02-003 Introduction This report describes interfacing the IPCS VoIP Gateway Model EGW-902 to an ESTeem Model 192E Wireless Ethernet radio modem in a demonstration

More information

Taurus Super-S3 LCM. Dual-Bay RAID Storage Enclosure for two 3.5-inch Serial ATA Hard Drives. User Manual March 31, 2014 v1.2 www.akitio.

Taurus Super-S3 LCM. Dual-Bay RAID Storage Enclosure for two 3.5-inch Serial ATA Hard Drives. User Manual March 31, 2014 v1.2 www.akitio. Dual-Bay RAID Storage Enclosure for two 3.5-inch Serial ATA Hard Drives User Manual March 31, 2014 v1.2 www.akitio.com EN Table of Contents Table of Contents 1 Introduction... 1 1.1 Technical Specifications...

More information

QUICK REFERENCE MANUAL

QUICK REFERENCE MANUAL PIONEER PLASMA DISPLAY SYSTEM QUICK REFERENCE MANUAL PDP-501HD: PLASMA DISPLAY PANEL PDP-501R: MEDIA RECEIVER PDP-501S-LR: SPEAKERS TABLE OF CONTENTS 1.0 CHOOSE THE INSTALLATION SITE...2 2.0 SET UP THE

More information

Business/Home GSM Alarm System. Installation and User Manual

Business/Home GSM Alarm System. Installation and User Manual Business/Home GSM Alarm System Installation and User Manual Brief Introduction: GSM 900/1800/1900 bands, can be used in most parts of the world Full duplex communication with the host Monitor the scene

More information

INSTRUCTION MANUAL DATA EXTRACTION PROCEDURE MODEL VR-3000/VR-3000S DO NOT OPEN. Important material for the exclusive use by Investigating Authorities

INSTRUCTION MANUAL DATA EXTRACTION PROCEDURE MODEL VR-3000/VR-3000S DO NOT OPEN. Important material for the exclusive use by Investigating Authorities INSTRUCTION MANUAL DATA EXTRACTION PROCEDURE MODEL VR-3000/VR-3000S DO NOT OPEN Important material for the exclusive use by Investigating Authorities All brand and product names are trademarks, registered

More information

NeoGate TG Series Installation Guide

NeoGate TG Series Installation Guide NeoGate TG Series Installation Guide Version: V1.1 Yeastar Technology Co., Ltd. Date: Sept. 2, 2014 http://www.yeastar.com 1/14 Contents NeoGate TG Series Installation Guide 1. Preparation before Installation...

More information

OPERATING INSTRUCTIONS Model ST-888 DTMF ANI/ENI Display Decoder

OPERATING INSTRUCTIONS Model ST-888 DTMF ANI/ENI Display Decoder P R O D U C T G R O U P OPERATING INSTRUCTIONS Model ST-888 DTMF ANI/ENI Display Decoder Manual # 600-0901 November 30, 1999 Rev. D - 99068 DESCRIPTION The ST-888 Mobilecall Display Decoder is a desktop

More information

Daker DK 1, 2, 3 kva. Manuel d installation Installation manual. Part. LE05334AC-07/13-01 GF

Daker DK 1, 2, 3 kva. Manuel d installation Installation manual. Part. LE05334AC-07/13-01 GF Daker DK 1, 2, 3 kva Manuel d installation Installation manual Part. LE05334AC-07/13-01 GF Daker DK 1, 2, 3 kva Index 1 Introduction 24 2 Conditions of use 24 3 LCD Panel 25 4 Installation 28 5 UPS communicator

More information

3.5 EXTERNAL NETWORK HDD. User s Manual

3.5 EXTERNAL NETWORK HDD. User s Manual 3.5 EXTERNAL NETWORK HDD User s Manual Table of Content Before You Use Key Features H/W Installation Illustration of Product LED Definition NETWORK HDD Assembly Setup the Network HDD Home Disk Utility

More information

How To Program An Autodialer

How To Program An Autodialer GJD HYL005 GSM Autodialer Instruction Manual Please read these instructions before you start the installation Features: LCD display. Programmable 9 x 32 digit phone numbers for each trigger. 10 second

More information

Innovative Electronics for a Changing World INDEX

Innovative Electronics for a Changing World INDEX Innovative Electronics for a Changing World INDEX 1. SYSTEM DESCRIPTION 2. BOARD CONNECTIONS terminals and indicators 3. CONNECTION DIAGRAM 4. START UP GUIDE and passwords 5. HOME PAGE 6. STATUS PAGE 7.

More information

Adaptability to Enhanced Security

Adaptability to Enhanced Security Installer Guide Adaptability to Enhanced Security AdapTec Plus combines power supply and door access controller features in a compact casing for an encrypted and secure I/O function, enhancing door access

More information

Modbus RTU (RS-485) TCP/IP (Ethernet)

Modbus RTU (RS-485) TCP/IP (Ethernet) Eaton Innovative Technology PEM PC Software Installation and Operation Instruction Manual: IM01005006E Rev. 2 March 2007 Modbus RTU (RS-485) TCP/IP (Ethernet) Effective Date 3/2007 For more information

More information

HCS-3300/3302/3304 USB Remote Programmable Laboratory Grade Switching Mode Power Supply

HCS-3300/3302/3304 USB Remote Programmable Laboratory Grade Switching Mode Power Supply 1. INTRODUCTION HCS-3300/3302/3304 USB Remote Programmable Laboratory Grade Switching Mode Power Supply User Manual This family of efficient, upgraded SMPS with small form factor, auto cross over CV CC,

More information

Adaptability to Enhanced Security

Adaptability to Enhanced Security Installer Guide Adaptability to Enhanced Security AdapTec Plus combines power supply and door access controller features in a compact casing for an encrypted and secure I/O function, enhancing door access

More information

PK5500 v1.1 Installation Instructions

PK5500 v1.1 Installation Instructions PK5500 v1.1 Installation Instructions 1 2 3 4 5 6 7 8 9 * 0 # WARNING: Please refer to the System Installation Manual for information on limitations regarding product use and function and information on

More information

Vroom Hardware manual ver. 1.00 Code 114VROOHWE00. Vroom CANBUS USER INTERFACE WITH LCD GRAPHIC DISPLAY AND WITH TEMPERATURE AND HUMIDITY SENSOR

Vroom Hardware manual ver. 1.00 Code 114VROOHWE00. Vroom CANBUS USER INTERFACE WITH LCD GRAPHIC DISPLAY AND WITH TEMPERATURE AND HUMIDITY SENSOR Vroom CANBUS USER INTERFACE WITH LCD GRAPHIC DISPLAY AND WITH TEMPERATURE AND HUMIDITY SENSOR ENGLISH HARDWARE MANUAL ver. 1.00 CODE 114VROOHWE00 page 1 of 22 Important Important Read these instructions

More information

Memcom Emergency Telephone

Memcom Emergency Telephone Memcom Emergency Telephone Installation Guide Ref No. 450 900 (GB) Version 2 + + Simple wiring for quick installation + + Integrated LCD display shows you what you have programmed + + All code based programming

More information

User Manual. EtherUSB

User Manual. EtherUSB User Manual EtherUSB USB Ethernet Access Point for PDA V 2.0 Clarinet Systems, Inc. Clarinet Systems, Inc. http://www.clarinetsys.com Page 1 Publication Revision No. Control Table Rev. No. Date Contents

More information

RN-XV-RD2 Evaluation Board

RN-XV-RD2 Evaluation Board RN-XV-RD2 Evaluation Board 2012 Roving Networks. All rights reserved. -1.01Version 1.0 9/28/2012 USER MANUAL OVERVIEW This document describes the hardware and software setup for Roving Networks RN-XV-RD2

More information

1 Serial RS232 to Ethernet Adapter Installation Guide

1 Serial RS232 to Ethernet Adapter Installation Guide Installation Guide 10/100 Mbps LED (amber color ) Link/Activity LED (green color ) 1. Introduction Thank you for purchasing this 1-port RS232 to Ethernet Adapter (hereinafter referred to as Adapter ).

More information

HAM841K ALARM CONTROL PANEL FOR COMMERCIAL AND RESIDENTIAL SECURITY SYSTEMS

HAM841K ALARM CONTROL PANEL FOR COMMERCIAL AND RESIDENTIAL SECURITY SYSTEMS ALARM CONTROL PANEL FOR COMMERCIAL AND RESIDENTIAL SECURITY SYSTEMS USER MANUAL USER MANUAL ALARM CONTROL PANEL FOR COMMERCIAL AND RESIDENTIAL SECURITY SYSTEMS INTRODUCTION The (HA-841K) is a complete

More information

MANUAL PC1000R [email protected]

MANUAL PC1000R INFO@APART-AUDIO.COM MANUAL PC1000R [email protected] Features The APart PC1000R is a professional multisource CD/USB/SD card music player, equipped with balanced and unbalanced analog outputs, coaxial and optical digital

More information

Application Note - Connecting an Electricity Meter to SolarEdge Devices (Europe and APAC)

Application Note - Connecting an Electricity Meter to SolarEdge Devices (Europe and APAC) February 2015 February 2015 Application Note - Connecting an Electricity Meter to SolarEdge Devices (Europe and APAC) This document describes how to connect an electricity meter to a SolarEdge device (inverters,

More information

BIT COMMANDER. Serial RS232 / RS485 to Ethernet Converter

BIT COMMANDER. Serial RS232 / RS485 to Ethernet Converter BIT COMMANDER Serial RS232 / RS485 to Ethernet Converter (Part US2000A) Copyrights U.S. Converters 1 Contents Overview and Features... 3 Functions..5 TCP Server Mode... 5 Httpd Client Mode.5 TCP Auto mode....6

More information

PU-USBX. USB over Ethernet Extender OPERATION MANUAL

PU-USBX. USB over Ethernet Extender OPERATION MANUAL PU-USBX USB over Ethernet Extender OPERATION MANUAL Safety Precautions Please read all instructions before attempting to unpack or install or operate this equipment, and before connecting the power supply.

More information

www.sebury.com.cn Digital Keypad Use s Manual

www.sebury.com.cn Digital Keypad Use s Manual K3 K4 www.sebury.com.cn Digital Keypad Use s Manual Contents Introduction Introduction Specifications Intramural Interface Circuit 3 Mounting 3 Wiring 5 Power UP 7 Engineer Programming Mode 7 The K3/K4

More information

32 Transferring Projects and Data

32 Transferring Projects and Data 32 Transferring Projects and Data This Chapter explains how to transfer GP-Pro EX project files to the GP and how to transfer the project files stored on the GP to your PC. Please start by reading 32.1

More information

RN-WIFLY-EVAL-UM. WiFly Evaluation Kit. 2012 Roving Networks. All rights reserved. RN-WIFLY-EVAL-UM Version 1.32r 10/9/2012 USER MANUAL

RN-WIFLY-EVAL-UM. WiFly Evaluation Kit. 2012 Roving Networks. All rights reserved. RN-WIFLY-EVAL-UM Version 1.32r 10/9/2012 USER MANUAL WiFly Evaluation Kit 2012 Roving Networks. All rights reserved. Version 1.32r 10/9/2012 USER MANUAL OVERVIEW This document describes the hardware and software setup for Roving Networks evaluation kits,

More information

is then retained absolutely without interruption.

is then retained absolutely without interruption. Page 1 of 11 DC UPS uninterruptible power supplies - DC UPS module 15 A Compact design, only 50 mm wide Absolutely interruption-free buffering of power failures through immediate electronic connection

More information

SNMP Web card. User s Manual. Management Software for Uninterruptible Power Supply Systems

SNMP Web card. User s Manual. Management Software for Uninterruptible Power Supply Systems SNMP Web card User s Manual Management Software for Uninterruptible Power Supply Systems Table of Contents 1. Overview... 3 1.1 Introduction... 3 1.2 Features... 3 1.3 Overlook... 3 1.4 Installation and

More information

Bluetooth HC-06 with serial port module Easy guide

Bluetooth HC-06 with serial port module Easy guide 1 Bluetooth HC-06 with serial port module Easy guide This manual consists of 3 parts: PART 1. Overview of Bluetooth HC-06 module with serial port. PART 2. Installing Bluetooth HC-06 module with Bolt 18F2550

More information

ALARMS-xx. Remote Alarm Unit Setup Guide 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24 25 26 27 28 29 30 31 32 RESET ALL

ALARMS-xx. Remote Alarm Unit Setup Guide 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24 25 26 27 28 29 30 31 32 RESET ALL Remote Alarm Unit Setup Guide 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24 25 26 27 28 29 30 31 32 RESET ALL User s Guide Version 1.0 07/01/2009 Michael Stevens & Partners Ltd. has made

More information

Infrastructure Management & Monitoring For Business-Critical Continuity. Liebert AC4. User Manual

Infrastructure Management & Monitoring For Business-Critical Continuity. Liebert AC4. User Manual Infrastructure Management & Monitoring For Business-Critical Continuity Liebert AC4 User Manual TABLE OF CONTENTS 1.0 INTRODUCTION 1.1 Methods of Viewing and Configuring the Liebert AC4..............................

More information

SIP Proxy Server. Administrator Installation and Configuration Guide. V2.31b. 09SIPXM.SY2.31b.EN3

SIP Proxy Server. Administrator Installation and Configuration Guide. V2.31b. 09SIPXM.SY2.31b.EN3 SIP Proxy Server Administrator Installation and Configuration Guide V2.31b 09SIPXM.SY2.31b.EN3 DSG, DSG logo, InterPBX, InterServer, Blaze Series, VG5000, VG7000, IP590, IP580, IP500, IP510, InterConsole,

More information

Model 5511 Filler Controller User s Manual Version 1.1 October 2011

Model 5511 Filler Controller User s Manual Version 1.1 October 2011 Thompson Scale Company WEIGHING SYSTEMS & PACKAGING MACHINERY CONTROLS 2758 Bingle Road Houston, Texas 77055 Phone: 713/932-9071 Fax: 713/932-9379 www.thompsonscale.com Model 5511 Filler Controller User

More information

Keep it Simple Timing

Keep it Simple Timing Keep it Simple Timing Support... 1 Introduction... 2 Turn On and Go... 3 Start Clock for Orienteering... 3 Pre Start Clock for Orienteering... 3 Real Time / Finish Clock... 3 Timer Clock... 4 Configuring

More information

Current Monitoring Kit

Current Monitoring Kit Current Monitoring Kit QUICK START GUIDE DO090-6 CONTENTS Issues: 1) 2.10.02 WP A4 format 2) 2.10.02 Added safety warning 3) 17.3.06 Word A5 format. S1: Removed relay modules. S2: Added MI010. S4.1: added

More information

NeoGate TA Series Quick Installation Guide

NeoGate TA Series Quick Installation Guide NeoGate TA Series Quick Installation Guide Version: V1.1 Yeastar Technology Co., Ltd. Date: November 18, 2014 http://www.yeastar.com 1/15 Contents NeoGate TA Series Quick Installation Guide 1. Preparation

More information

CM705B - Universal Expander Module CM707B - Plug On Zone Expander Security Systems

CM705B - Universal Expander Module CM707B - Plug On Zone Expander Security Systems CM705B - Universal Expander Module CM707B - Plug On Zone Expander Security Systems EN Security System CM705B CM705B - Universal Expander Module The CM705B universal expander provides a cost effective way

More information

CSP Combined Series. Telephone Door Entry. with. Proximity Keyfob Access

CSP Combined Series. Telephone Door Entry. with. Proximity Keyfob Access CSP Combined Series Telephone Door Entry with Proximity Keyfob Access PD-094 Issue 3 General Description The CSP series systems are combined Door Entry Telephone and Proximity Access Systems. The entrance

More information

PM1122 INT DIGITAL INTERFACE REMOTE

PM1122 INT DIGITAL INTERFACE REMOTE PM1122 INT DIGITAL INTERFACE REMOTE PM1122 INT front panel description: 1. Clear wireless remotes knob: push this button for more than 2 seconds to clear the list of all assigned wireless remote settings

More information

About This Guide SolarEdge Configuration Tool Software Guide. About This Guide

About This Guide SolarEdge Configuration Tool Software Guide. About This Guide About This Guide 3 About This Guide This user guide is intended for Photovoltaic (PV) system owners, installers, technicians, maintainers, administrators and integrators who are authorized to configure

More information

ViewPower. User s Manual. Management Software for Uninterruptible Power Supply Systems

ViewPower. User s Manual. Management Software for Uninterruptible Power Supply Systems ViewPower User s Manual Management Software for Uninterruptible Power Supply Systems Table of Contents 1. ViewPower Overview... 2 1.1. Introduction...2 1.2. Structure...2 1.3. Applications...2 1.4. Features...2

More information

Elvey is a leading distributor of electronic security equipment in Africa. Our vision is to assist in the protection of people and property by

Elvey is a leading distributor of electronic security equipment in Africa. Our vision is to assist in the protection of people and property by Elvey is a leading distributor of electronic security equipment in Africa. Our vision is to assist in the protection of people and property by providing quality, innovative products and solutions to the

More information

Name Description Model Number. Parameters Min. Typ. Max. Note. Vaux Voltage 9.8 V 12 V 13.2 V Auxiliary Supply Voltage

Name Description Model Number. Parameters Min. Typ. Max. Note. Vaux Voltage 9.8 V 12 V 13.2 V Auxiliary Supply Voltage Description Supports DALI interface driver Programming Supports 0-10V Programmable Driver Programming Supports Other Controllers (TDD-ANPNx, SDD-AAPNx) Off-line programming capability Auto programming

More information

Energy Communication Unit (ECU)

Energy Communication Unit (ECU) Altenergy Power System Energy Communication Unit (ECU) Installation and User Manual (For ECU-3 V3.8) ALTENERGY POWER SYSTEM INC. All rights reserved TABLE OF CONTENTS 1.0 Introduction... 2 2.0 Installation...

More information

Ultra Thin Client TC-401 TC-402. Users s Guide

Ultra Thin Client TC-401 TC-402. Users s Guide Ultra Thin Client TC-401 TC-402 Users s Guide CONTENT 1. OVERVIEW... 3 1.1 HARDWARE SPECIFICATION... 3 1.2 SOFTWARE OVERVIEW... 4 1.3 HARDWARE OVERVIEW...5 1.4 NETWORK CONNECTION... 7 2. INSTALLING THE

More information

TIME BOX BIOMETRIC TECHNICAL INSTRUCTIONS AND QUICK START GUIDE IT IS RECOMMENDED TO READ THIS MANUAL BEFORE OPERATING THE SYSTEM

TIME BOX BIOMETRIC TECHNICAL INSTRUCTIONS AND QUICK START GUIDE IT IS RECOMMENDED TO READ THIS MANUAL BEFORE OPERATING THE SYSTEM TIME BOX BIOMETRIC TECHNICAL INSTRUCTIONS AND QUICK START GUIDE IT IS RECOMMENDED TO READ THIS MANUAL BEFORE OPERATING THE SYSTEM BODET Software B.P. 402 Boulevard du Cormier F-49302 CHOLET Cedex www.bodet.com

More information

GSM HOME SECURITY SYSTEM

GSM HOME SECURITY SYSTEM Cell /Mobile phone home security system GSM HOME SECURITY SYSTEM Model : GSM-120 TABLE OF CONTENTS 1. FEATURES... 1 2. APPLICATION... 2 3. SPECIFICATIONS... 3 4. FRONT PANEL & LAYOUT DESCRIPTION...6 5.

More information

DRO-210i LOAD BALANCING ROUTER. Review Package Contents

DRO-210i LOAD BALANCING ROUTER. Review Package Contents DRO-210i LOAD BALANCING ROUTER Review Package Contents Make sure that the package contains the following items. DRO-210i Load Balancing Router 2 Straight Ethernet Cables 1 Cross Over Ethernet Cable 1 Power

More information

Plena Voice Alarm System. Software Manual Configuration Software

Plena Voice Alarm System. Software Manual Configuration Software Plena Voice Alarm System en Software Manual Configuration Software Plena Voice Alarm System Software Manual Table of Contents en 3 Table of Contents Table of Contents...3 1. Introduction...7 1.1 Purpose...7

More information

TrueAlarm Fire Alarm Systems

TrueAlarm Fire Alarm Systems TrueAlarm Fire Alarm Systems UL, ULC, CSFM Listed; FM Approved; MEA (NYC) Acceptance* Fire Alarm System Accessories, 4190 Series PC Annunciator with Multi-Client Capability Features Fire alarm control

More information

BARDIC. 4 & 8 Zone Fire Panels Zircon range. Data, installation, operation and maintenance. by Honeywell

BARDIC. 4 & 8 Zone Fire Panels Zircon range. Data, installation, operation and maintenance. by Honeywell Data, installation, operation and maintenance 4 & 8 Zone Fire Panels Zircon range BARDIC by Honeywell LED flashing LED Continuous FAULT DISABLE/TEST Power General Fault Sounder Fault/ Disable System Fault

More information

F453. TiF453. User guide 10/11-01 PC

F453. TiF453. User guide 10/11-01 PC F453 TiF453 User guide 10/11-01 PC 2 TiF453 User guide Contents 1. Hardware and Software requirements 4 2. Installation 4 1.1 Minimum Hardware requirements 4 1.2 Minimum Software requirements 4 3. Fundamental

More information

INSTALLATION GUIDE. Card Reader & Controller with KIM Swipe Reader for Solitaire 850 / 950 / 850L Learnlok PK2930

INSTALLATION GUIDE. Card Reader & Controller with KIM Swipe Reader for Solitaire 850 / 950 / 850L Learnlok PK2930 INSTALLATION GUIDE Card Reader & Controller with KIM Swipe Reader for Solitaire 850 / 950 / 850L Learnlok PK2930 Card Reader and Controller Model 3.5 with KIM Swipe Reader Table of Contents 1. Features..................................

More information

How To Power A Power Control On An Ip40 (Ipl) With A Power Supply (Iplug) With An Ip20 Controller (Iphones) With Power Control (Power Control) With No Antenna) With The Ip20 (Power)

How To Power A Power Control On An Ip40 (Ipl) With A Power Supply (Iplug) With An Ip20 Controller (Iphones) With Power Control (Power Control) With No Antenna) With The Ip20 (Power) MODEL NUMBER: ISC910-1-0-GB-XX ISC911-5-0-GB-XX IXP20 CONTROLLER SPECIFICATIONS Working Environment Plastic Housing... Power ImproX IXP20 Controller INSTALLATION MANUAL Designed to work in an indoor (dry)

More information

Back-UPS Pro 1300/1500 Installation and Operation

Back-UPS Pro 1300/1500 Installation and Operation Back-UPS Pro 1300/1500 Installation and Operation Inventory Safety Do not install the Back-UPS in direct sunlight, in excessive heat, humidity, or in contact with fluids. Connect the battery bu059a bu058a

More information

AUTOMATIC TRANSFER SWITCH CONTROL UNIT OPERATOR S MANUAL

AUTOMATIC TRANSFER SWITCH CONTROL UNIT OPERATOR S MANUAL ATS-220 AUTOMATIC TRANSFER SWITCH CONTROL UNIT OPERATOR S MANUAL For Use in 208 to 240 Volts Single and 3 Phase ATS Systems With 110Volt AC or DC Control Motors and selenoids 4501 NW 27 ave Miami FL 33142

More information

USER MANUAL. PingBrother EPIW104 managed passive poe switch & IP watchdog

USER MANUAL. PingBrother EPIW104 managed passive poe switch & IP watchdog USER MANUAL PingBrother EPIW104 managed passive poe switch & IP watchdog CONTENT Content... 2 Chapter 1... 3 1.1 Preface... 3 1.2 CE mark warning... 3 1.3 FCC warning... 4 Chapter 2... 5 2.1 Physical description...

More information

JNIOR. Overview. Get Connected. Get Results. JNIOR Model 310. JNIOR Model 312. JNIOR Model 314. JNIOR Model 410

JNIOR. Overview. Get Connected. Get Results. JNIOR Model 310. JNIOR Model 312. JNIOR Model 314. JNIOR Model 410 The INTEG is an Ethernet I/O (digital, analog) device that monitors and controls a small set of process signals. functions as both basic I/O for integration with another application or system AND as a

More information

Standalone recorder instruction

Standalone recorder instruction Standalone recorder instruction 1,Product profile... 2 2. Hardware interface... 2 2.1 2 &4 &8 channel standalone recorder front panel... 2 2.2 8&16 channel standalone recorder device interface... 3 3,

More information

Vision Engravers and Routers PRE-Installation Guide. 2015 Vision Engraving & Routing Systems

Vision Engravers and Routers PRE-Installation Guide. 2015 Vision Engraving & Routing Systems Vision Engravers and Routers PRE-Installation Guide Revised: 8/19/2015 Vision Engravers and Routers PRE-Installation Guide All rights reserved. No parts of this work may be reproduced in any form or by

More information

JKW-IP. IP Video Entry System. QuikStart Guide

JKW-IP. IP Video Entry System. QuikStart Guide 1210 JKW-IP IP Video Entry System QuikStart Guide This is an abbreviated instruction manual for installation purposes. Please see the JKW-IP Installation Manual and JKW-IP Operation Manual for complete

More information

SCD Server. SCD Server Pro

SCD Server. SCD Server Pro SCD Server SCD Server Pro SCD Server & SCD Server Pro 9850-000387-01 - Page 1 of 8 SCD Server and SCD Server Pro The SCD Server is a 2U high DMX generator, running the ZerOS Operating System and emulating

More information

Installation and Operation. Manual

Installation and Operation. Manual S e a N e t - A l a r m U S B Installation and Operation Manual Hardware Version V 1.1 Software Version 1.00 March 2009 2004 All Rights Reserved http://www.gadgetpool.de 2004 Alle Rechte vorbehalten [email protected]

More information

V2.0 Attendance System Hardware Suite Guide Instructions Manual

V2.0 Attendance System Hardware Suite Guide Instructions Manual CONTENTS TA920 V2.0 Attendance System Hardware Suite Guide Instructions Manual Chapter One - Introduction 1.1 Communication Port 5 1.2 Power Source Control. 5 1.3 Attendance Users. 6 1.4 Registering Ways..

More information

MCR1900 Media Converter 19-Slot Chassis

MCR1900 Media Converter 19-Slot Chassis MCR1900 Media Converter 19-Slot Chassis Installation Guide Part #5500304-11 Copyright Statement This document must not be reproduced in any way whatsoever, either printed or electronically, without the

More information

HDCVI Series DVR Quick Start Guide

HDCVI Series DVR Quick Start Guide HDCVI Series DVR Quick Start Guide Version 1.1.0 Welcome Thank you for purchasing our HDCVI DVR! This quick start guide will help you become familiar with our HDCVI DVR in a very short time. Before installation

More information

HG600/HG800. Hydro-Power Unit. Installation and Operation Guide

HG600/HG800. Hydro-Power Unit. Installation and Operation Guide HG600/HG800 Hydro-Power Unit Installation and Operation Guide Copyright 04 HydroSpin, All rights reserved. The data contained in this document is proprietary to HydroSpin. It is disclosed to the receiving

More information

Advantium 2 Plus Alarm

Advantium 2 Plus Alarm ADI 9510-B Advantium 2 Plus Alarm INSTALLATION AND OPERATING INSTRUCTIONS Carefully Read These Instructions Before Operating Carefully Read These Controls Corporation of America 1501 Harpers Road Virginia

More information

GV-Keyboard. User's Manual V2.0

GV-Keyboard. User's Manual V2.0 GV-Keyboard User's Manual V2.0 Before attempting to connect or operate this product, please read these instructions carefully and save this manual for future use. 2007 GeoVision, Inc. All rights reserved.

More information

Network Camera. Quick Operation Guide V4.0.1

Network Camera. Quick Operation Guide V4.0.1 Network Camera Quick Operation Guide V4.0.1 Thank you for purchasing our product. If there are any questions, or requests, please do not hesitate to contact the dealer. This manual applies to DS-2CD8253F-EI(Z),

More information

EV-1000 Series DVR. Quick Operation Guide. Version 1.0.0

EV-1000 Series DVR. Quick Operation Guide. Version 1.0.0 EV-1000 Series DVR Quick Operation Guide Version 1.0.0 Thank you for purchasing our product. If there is any question or request, please do not hesitate to contact dealer. This manual is applicable to

More information

Quick Start Guide. Cisco Small Business. 300 Series Managed Switches

Quick Start Guide. Cisco Small Business. 300 Series Managed Switches Quick Start Guide Cisco Small Business 300 Series Managed Switches Welcome Thank you for choosing the Cisco 300 Series Managed Switch, a Cisco Small Business network communications device. This device

More information

Network Management Card. User Manual

Network Management Card. User Manual User Manual 1 Contents Contents 2 Chapter 1 Overview 3 1.1 NMC package contents 4 1.2 NMC CD Resources 4 1.3 Features 4 1.4 NMC Applications 5 Chapter 2 NMC parameters setting via serial COM port 6 2.1

More information