FloVENT. Optimizing Data Center Cooling by Simulation. Mechanical Analysis
|
|
|
- Rosemary Morton
- 10 years ago
- Views:
Transcription
1 FloVENT Optimizing Data Center Cooling by Simulation Mechanical Analysis
2 Why Perform Airflow/Thermal Simulation in Data Centers? Why Choose FloVENT for Airflow Simulation in Data Centers? Providing adequate cooling is a major challenge for modern data center designers and operators, due to the escalating power densities associated with blade servers and other highspeed computing and switching equipment. Individual server rack heat loads now commonly exceed 10kW, and may reach over 30kW. According to a recent study [1], power consumption in US data centers doubled between 2000 and 2005, reaching in 2005 a figure approximately equal to the power consumed by all color televisions in the. Power consumption in data centers is expected to grow by a further 40% by Energy costs for power and cooling in data centers are now greater than the cost of the IT equipment itself, when amortized over a three-year period [2]. Since 1988, Mentor Graphics Mechanical Analysis Division has played a pioneering role in simulation of airflow and thermal comfort in all kinds of buildings using Computational Fluid Dynamics (CFD) techniques. As a result, FloVENT has become the most widely used, most validated, most dependable, and fastest CFD software for this type of application. You may choose to employ Mentor Graphics as a consultant, and/or license the FloVENT software for in-house use. Either way, we will help you minimize operating costs and downtime by visualizing and optimizing airflow, temperature distribution and cooling system performance. The FloVENT simulation software from Mentor Graphics creates a virtual data center with detailed 3D visualization of airflow and temperature at every point throughout the room. Armed with this vital information, you can quickly and easily: Minimize cooling power requirements and energy costs Optimize data center cooling effectiveness Ensure that temperatures are within specifications at all rack inlets and throughout the room Eliminate hot spots thus avoiding potential equipment failures and downtime Simulate transient effects (e.g. temperature build-up following CRAC failure) [1] Estimating total power consumption by servers in the US and the world, Jonathan G. Koomey, Ph.D, Staff Scientist, Lawrence Berkeley National Laboratory and Consulting Professor, Stanford University, Final report, February 15, 2007 [2] In the data center, power and cooling costs more than the IT equipment it supports, Christian L. Belady, P.E., Hewlett- Packard, Electronics Cooling Magazine, Volume 13, Number 1, February 2007 FloVENT is designed specifically for modeling heating and cooling applications so it is both easier to use and more powerful than other CFD codes when evaluating data center cooling. Mentor Graphics, Mechanical Analysis also has a team of support engineers that provide excellent support because they have a very good understanding of data center cooling issues. Ben Steinberg, Senior Engineer, American Power Conversion (APC) Ventilation and temperature distribution within a Data Center
3 Validation Columns Since 1988, FloVENT has been applied and validated in a wide variety of data center cooling applications by companies such as APC, BSRIA, BT, Emerson, HP, and IBM. In addition, FloVENT is widely used and extensively validated by building designers, engineering design consultants, and building owner/ operators for many different applications involving buildings of all types and sizes. This widespread use drives out software bugs and ensures robust simulation software that you can rely on. With Mentor Graphics and FloVENT, you can be sure that Simulation = Reality! The following technical papers are just a small selection from the huge range of papers demonstrating that the world s leading companies rely on FloVENT for data center cooling simulations. Validation Papers The following is a partial list of technical papers that have validated the use of FloVENT for data center cooling or similar applications. Visit our website for a full list. Cooling Solutions for IT, BSRIA Guidance Document Nigel Pavey, Foreman Roberts William Booth, BSRIA Stuart Hall, Flomerics Ltd Experimental-Numerical Comparison for a High-Density Data Center: Hot Spot Heat Fluxes in Excess of 500 W/ft² Saurabh K. Shrivastava, American Power Conversion Corporation Madhusudan Iyengar, IBM Systems & Technology Group Bahgat G. Sammakia, Dept. of Mechanical Engineering Roger Schmidt, IBM Systems & Technology Group 2455 James W. VanGilder, American Power Conversion Corporation Airflow Uniformity Through Perforated Tiles in a Raised-Floor Data Center James W. VanGilder, American Power Conversion Corporation Roger R. Schmidt, IBM Corporation Dimensionless Parameters for Energy-Effecient Data Center Design Ratnesh K. Sharma and Cullen E. Bash, Hewlett-Packard Laboratories 1. Room and Structure From design drawings, CAD or site survey 2 Ventilation Air handling device specifications from libraries based on manufacturers data Room Height Air Handling Device Room Length Return Cable Cutouts Supply Glazing - if any Void Height Floor Grilles Obstructions in Void e.g. Cable Trays A Non-Trial-and-Error CFD-Based Method For Balancing Airflow Through Floor Tiles in Raised-Floor Data Centers Jim VanGilder, Flomerics Raised Floor Computer Data Center: Effect on Rack Inlet Temperatures of Chilled Air Exiting both the Hot and Cold Aisles Roger Schmidt, Ethan Cruz, IBM Corporation Thermal Trends and Inflections Influencing the IT Roadmap David S. De Lorenzo, Intel Labs Thermal Considerations in Cooling Large Scale High Compute Density Data Centers Chandrakant D. Patel, Ratnesh Sharma, Cullen E. Bash and Abdlmonem Beitelmal, Hewlett-Packard Laboratories The Performance of Displacement Cooling Systems in Telecom Applications Ari Kemppainen, Ericsson R&D, Sweden CFD Modeling of High Compute Density Data Centers to Assure System Inlet Air Specifications Chandrakant D. Patel, Cullen E. Bash and Christian Belady, Hewlett- Packard Laboratories Lennart Stahl and Danny Sullivan, Emerson Energy Systems 3. Equipment Details and specifications of equipment housed in cabinets from data center configuration management system and manufacturers data 4 Simulation Results Information about: - Temperatures - Pressures - Air flow paths and velocities Cabinets Obstructions e.g. PDUs A Fresh Approach to Cooling Network Equipment Peter Kiff, BT Networks and Systems
4 FloVENT in Data Center Design and Operation Data center cooling simulation using FloVENT contributes to both: New-build designs to evaluate design cooling performance, identify and remedy cooling problems or likely hot spots ahead of build; optimize layout and cooling to minimize power consumption; investigate possible cooling system failures and system redundancy; and Ongoing operation and change management to assess and monitor intended and ongoing operational changes in equipment layout, cooling system, space utilization, etc, whilst minimizing cooling energy costs. Contact us today! Visit or call us direct at any of our worldwide offices listed on the back of this brochure. Of these the second is assuming increasing importance, as data center layout changes and equipment upgrades occur more and more frequently. Clearly the operation of present-day data centers involves a multiplicity of issues in addition to cooling asset lifecycle management, power infrastructure, network mapping, capacity planning, change management, and many more. FloVENT can be used alongside whatever data center management system is being used to address these, so as to provide a complementary thermal audit of cooling performance. This enables the operator to assess the potentially critical impact on cooling of the continual operational changes inevitable in present-day data centers. You may choose to employ Mentor Graphics as a consultant, and/or license the FloVENT software for in-house use. Either way, we will help you minimize operating costs and downtime by visualizing and optimizing airflow, temperature distribution and cooling system performance for all your data center projects. The benefits of undertaking CFD analysis are truly realized by Mentor Graphics Mechanical Analysis Division, their visual representations of temperatures and airflows have been the key on several of our projects. We provide a computational test bed to evaluate airflow and thermal behaviour of current and future data center designs, and operational changes. Armed with this vital information, you can quickly and easily: Minimize cooling power requirements and energy costs Optimize data center cooling effectiveness Ensure that temperatures are within specifications at all rack inlets and throughout the room Eliminate hot spots thus avoiding potential equipment failures and downtime Derek Morgan, Technical Director, WSP Group Plc
5 Mentor Graphics Corporate Headquarters 8005 S.W. Boeckman Rd. Wilsonville, OR Tel: +1 (503) Fax: +1 (503) Mechanical Analysis Division Offices UK 81 Bridge Road Hampton Court Surrey KT8 9HH United Kingdom Tel: + 44 (0) Fax: +44 (0) France Immeuble Le Pasteur 13/15 rue Jeanne Braconnier Meudon La Forêt France Tel: +33 (0) Fax: +33 (0) China Rm Jin Mao Tower 88 Century Blvd, Pudong New Area Shanghai China Tel: Fax: Canway Building Room 1512, No.66 Nan Li Shi Lu Beijing China Tel: Fax: Raiffeisenstr 16 D Filderstadt Tel: Fax: Hanauer Landstraße Frankfurt am Main Tel: +49 (0) Fax: +49 (0) Italy Palazzo F1 Milanofiori Assago MI Italy Tel: Fax: Sweden Kista Science Tower Kista Sweden Tel Fax India Salarpuria Touchstone Survey # 15/1A & 14 Kadubeesanahalli, Varthur Hobli Sarjapur Ring Road Bangalore, India Tel: Fax: Japan Gotenyama Garden 7-35, Kita-shinagawa 4-chome Shinagawa-ku, Tokyo , Japan Tel: Fax: Singapore 238A Thomson Road #23-07 Novena Square Tower A Singapore Tel: Fax: Nickerson Road, Suite 200 Marlborough MA Tel: +1 (508) Fax: +1 (508) Plaza on the Lake, Suite 310 Austin TX Tel: +1 (512) Fax : +1 (512) Ridder Park Drive San Jose CA Tel: +1 (408) Fax: +1 (408) Mechanical Analysis Please visit our website at: Copyright 2009 Mentor Graphics Corp Mentor Graphics is a registered trademark of Mentor Graphics Corporation. All other trademarks mentioned in this document are trademarks of their respective owners
Airflow Simulation Solves Data Centre Cooling Problem
Airflow Simulation Solves Data Centre Cooling Problem The owner s initial design for a data centre in China utilized 40 equipment racks filled with blade servers spread out in three rows along the length
Fundamentals of CFD and Data Center Cooling Amir Radmehr, Ph.D. Innovative Research, Inc. [email protected]
Minneapolis Symposium September 30 th, 2015 Fundamentals of CFD and Data Center Cooling Amir Radmehr, Ph.D. Innovative Research, Inc. [email protected] Learning Objectives 1. Gain familiarity with Computational
11 Top Tips for Energy-Efficient Data Center Design and Operation
11 Top Tips for Energy-Efficient Data Center Design and Operation A High-Level How To Guide M e c h a n i c a l a n a l y s i s W h i t e P a p e r w w w. m e n t o r. c o m When is Data Center Thermal
Introducing Computational Fluid Dynamics Virtual Facility 6SigmaDC
IT Infrastructure Services Ltd Holborn Gate, 330 High Holborn, London, WC1V 7QT Telephone: +44 (0)20 7849 6848 Fax: +44 (0)20 7203 6701 Email: [email protected] www.itisltd.com Introducing Computational
The New Data Center Cooling Paradigm The Tiered Approach
Product Footprint - Heat Density Trends The New Data Center Cooling Paradigm The Tiered Approach Lennart Ståhl Amdahl, Cisco, Compaq, Cray, Dell, EMC, HP, IBM, Intel, Lucent, Motorola, Nokia, Nortel, Sun,
Introducing the. Virtual Facility
Introducing the Virtual Facility At future facilities, we have developed a groundbreaking methodology enabling owner/operators to improve the performance of a data centre throughout its entire lifecycle.
High Density Data Centers Fraught with Peril. Richard A. Greco, Principal EYP Mission Critical Facilities, Inc.
High Density Data Centers Fraught with Peril Richard A. Greco, Principal EYP Mission Critical Facilities, Inc. Microprocessors Trends Reprinted with the permission of The Uptime Institute from a white
Data centers have been cooled for many years by delivering
The Increasing Challenge of Data Center Design and Management: Is CFD a Must? Mark Seymour, Christopher Aldham, Matthew Warner, Hassan Moezzi Future Facilities, San Jose, California, USA Mark Seymour,
Thinking Outside the Box Server Design for Data Center Optimization
Thinking Outside the Box Server Design for Data Center Optimization Marie Ross, Senior Applications Engineer Tom Gregory, Consultant Engineer October 2013 The benefits of analyzing thermal performance
AEGIS DATA CENTER SERVICES POWER AND COOLING ANALYSIS SERVICE SUMMARY
AEGIS DATA CENTER SERVICES POWER AND COOLING ANALYSIS SERVICE SUMMARY The Aegis Services Power and Assessment Service provides an assessment and analysis of your data center facility and critical physical
Data Centre Energy Efficiency Operating for Optimisation Robert M Pe / Sept. 20, 2012 National Energy Efficiency Conference Singapore
Data Centre Energy Efficiency Operating for Optimisation Robert M Pe / Sept. 20, 2012 National Energy Efficiency Conference Singapore Introduction Agenda Introduction Overview of Data Centres DC Operational
Managing Cooling Capacity & Redundancy In Data Centers Today
Managing Cooling Capacity & Redundancy In Data Centers Today About AdaptivCOOL 15+ Years Thermal & Airflow Expertise Global Presence U.S., India, Japan, China Standards & Compliances: ISO 9001:2008 RoHS
Elements of Energy Efficiency in Data Centre Cooling Architecture
Elements of Energy Efficiency in Data Centre Cooling Architecture Energy Efficient Data Center Cooling 1 STULZ Group of Companies Turnover 2006 Plastics Technology 400 Mio A/C Technology 200 Mio Total
Education Evolution: Scalable Server Rooms George Lantouris Client Relationship Manager (Education) May 2009
Education Evolution: Scalable Server Rooms George Lantouris Client Relationship Manager (Education) May 2009 Agenda Overview - Network Critical Physical Infrastructure Cooling issues in the Server Room
Using Simulation to Improve Data Center Efficiency
A WHITE PAPER FROM FUTURE FACILITIES INCORPORATED Using Simulation to Improve Data Center Efficiency Cooling Path Management for maximizing cooling system efficiency without sacrificing equipment resilience
A Comparative Study of Various High Density Data Center Cooling Technologies. A Thesis Presented. Kwok Wu. The Graduate School
A Comparative Study of Various High Density Data Center Cooling Technologies A Thesis Presented by Kwok Wu to The Graduate School in Partial Fulfillment of the Requirements for the Degree of Master of
Benefits of. Air Flow Management. Data Center
Benefits of Passive Air Flow Management in the Data Center Learning Objectives At the end of this program, participants will be able to: Readily identify if opportunities i where networking equipment
Increasing Energ y Efficiency In Data Centers
The following article was published in ASHRAE Journal, December 2007. Copyright 2007 American Society of Heating, Refrigerating and Air- Conditioning Engineers, Inc. It is presented for educational purposes
CFD-Based Operational Thermal Efficiency Improvement of a Production Data Center
CFD-Based Operational Thermal Efficiency Improvement of a Production Data Center Umesh Singh, Amarendra K Singh, Parvez S and Anand Sivasubramaniam Tata Consultancy Services Ltd., India ABSTRACT Effective
Airflow and Cooling Performance of Data Centers: Two Performance Metrics
2008, American Society of Heating, Refrigerating and Air-Conditioning Engineers, Inc. (www.ashrae.org). Published in ASHRAE Transactions, Vol. 114, Part 2. For personal use only. Additional reproduction,
GREEN FIELD DATA CENTER DESIGN WATER COOLING FOR MAXIMUM EFFICIENCY. Shlomo Novotny, Vice President and Chief Technology Officer, Vette Corp.
GREEN FIELD DATA CENTER DESIGN WATER COOLING FOR MAXIMUM EFFICIENCY Shlomo Novotny, Vice President and Chief Technology Officer, Vette Corp. Overview Data centers are an ever growing part of our economy.
Managing Data Centre Heat Issues
Managing Data Centre Heat Issues Victor Banuelos Field Applications Engineer Chatsworth Products, Inc. 2010 Managing Data Centre Heat Issues Thermal trends in the data centre Hot Aisle / Cold Aisle design
Dealing with Thermal Issues in Data Center Universal Aisle Containment
Dealing with Thermal Issues in Data Center Universal Aisle Containment Daniele Tordin BICSI RCDD Technical System Engineer - Panduit Europe [email protected] AGENDA Business Drivers Challenges
Air, Fluid Flow, and Thermal Simulation of Data Centers with Autodesk Revit 2013 and Autodesk BIM 360
Autodesk Revit 2013 Autodesk BIM 360 Air, Fluid Flow, and Thermal Simulation of Data Centers with Autodesk Revit 2013 and Autodesk BIM 360 Data centers consume approximately 200 terawatt hours of energy
Analysis of the UNH Data Center Using CFD Modeling
Applied Math Modeling White Paper Analysis of the UNH Data Center Using CFD Modeling By Jamie Bemis, Dana Etherington, and Mike Osienski, Department of Mechanical Engineering, University of New Hampshire,
Verizon SMARTS Data Center Design Phase 1 Conceptual Study Report Ms. Leah Zabarenko Verizon Business 2606A Carsins Run Road Aberdeen, MD 21001
Verizon SMARTS Data Center Design Phase 1 Conceptual Study Report Ms. Leah Zabarenko Verizon Business 2606A Carsins Run Road Aberdeen, MD 21001 Presented by: Liberty Engineering, LLP 1609 Connecticut Avenue
Data center TCO; a comparison of high-density and low-density spaces
White Paper Data center TCO; a comparison of high-density and low-density spaces M.K. Patterson, D.G. Costello, & P. F. Grimm Intel Corporation, Hillsboro, Oregon, USA M. Loeffler Intel Corporation, Santa
Airflow Uniformity through Perforated Tiles in a Raised-Floor Data Center
Airflow Uniformity through Perforated Tiles in a Raised-Floor Data Center White Paper 121 Revision 1 by James W. VanGilder, P.E., APC by Schneider Electric Roger R. Schmidt, Ph.D., P.E., IBM Corporation
How to Meet 24 by Forever Cooling Demands of your Data Center
W h i t e P a p e r How to Meet 24 by Forever Cooling Demands of your Data Center Three critical aspects that are important to the operation of computer facilities are matching IT expectations with the
Using CFD for optimal thermal management and cooling design in data centers
www.siemens.com/datacenters Using CFD for optimal thermal management and cooling design in data centers Introduction As the power density of IT equipment within a rack increases and energy costs rise,
The Benefits of Supply Air Temperature Control in the Data Centre
Executive Summary: Controlling the temperature in a data centre is critical to achieving maximum uptime and efficiency, but is it being controlled in the correct place? Whilst data centre layouts have
Control Strategies for Plenum Optimization in Raised Floor Data Centers
Control Strategies for Plenum Optimization in aised Floor Data Centers Keke Chen, Clifford C. Federspiel, David M. Auslander, Cullen E. Bash, Chandrakant D. Patel Enterprise Software and Systems Laboratory
Hot Air Isolation Cools High-Density Data Centers By: Ian Seaton, Technology Marketing Manager, Chatsworth Products, Inc.
Business Management Magazine Winter 2008 Hot Air Isolation Cools High-Density Data Centers By: Ian Seaton, Technology Marketing Manager, Chatsworth Products, Inc. Contrary to some beliefs, air is quite
HP Data Center Services
HP Data Center Services HP Technology Services - Per Event Services Technical data Enterprise-class data center facility infrastructures need to support both current IT objectives and new equipment and
- White Paper - Data Centre Cooling. Best Practice
- White Paper - Data Centre Cooling Best Practice Release 2, April 2008 Contents INTRODUCTION... 3 1. AIR FLOW LEAKAGE... 3 2. PERFORATED TILES: NUMBER AND OPENING FACTOR... 4 3. PERFORATED TILES: WITH
Cooling Capacity Factor (CCF) Reveals Stranded Capacity and Data Center Cost Savings
WHITE PAPER Cooling Capacity Factor (CCF) Reveals Stranded Capacity and Data Center Cost Savings By Lars Strong, P.E., Upsite Technologies, Inc. Kenneth G. Brill, Upsite Technologies, Inc. 505.798.0200
Energy Performance Optimization of Server Room HVAC System
International Journal of Thermal Technologies E-ISSN 2277 4114 2 INPRESSCO, All Rights Reserved Available at http://inpressco.com/category/ijtt/ Research Article Manoj Jadhav * and Pramod Chaudhari Department
How Row-based Data Center Cooling Works
How Row-based Data Center Cooling Works White Paper 208 Revision 0 by Paul Lin and Victor Avelar Executive summary Row-based data center cooling is normally regarded as a cold air supply architecture that
W H I T E P A P E R. Computational Fluid Dynamics Modeling for Operational Data Centers
W H I T E P A P E R Computational Fluid Dynamics Modeling for Operational Data Centers 2 Executive Summary Improving Effectiveness of CFD Technology in Cooling of Data Centers IT managers continue to be
Specialty Environment Design Mission Critical Facilities
Brian M. Medina PE Associate Brett M. Griffin PE, LEED AP Vice President Environmental Systems Design, Inc. Mission Critical Facilities Specialty Environment Design Mission Critical Facilities March 25,
How High Temperature Data Centers & Intel Technologies save Energy, Money, Water and Greenhouse Gas Emissions
Intel Intelligent Power Management Intel How High Temperature Data Centers & Intel Technologies save Energy, Money, Water and Greenhouse Gas Emissions Power and cooling savings through the use of Intel
Prediction Is Better Than Cure CFD Simulation For Data Center Operation.
Prediction Is Better Than Cure CFD Simulation For Data Center Operation. This paper was written to support/reflect a seminar presented at ASHRAE Winter meeting 2014, January 21 st, by, Future Facilities.
Unified Physical Infrastructure SM (UPI) Strategies for Smart Data Centers
Unified Physical Infrastructure SM (UPI) Strategies for Smart Data Centers Deploying a Vertical Exhaust System www.panduit.com WP-09 September 2009 Introduction Business management applications and rich
Optimizing Network Performance through PASSIVE AIR FLOW MANAGEMENT IN THE DATA CENTER
Optimizing Network Performance through PASSIVE AIR FLOW MANAGEMENT IN THE DATA CENTER Lylette Macdonald, RCDD Legrand Ortronics BICSI Baltimore 2011 Agenda: Discuss passive thermal management at the Rack
How To Run A Data Center Efficiently
A White Paper from the Experts in Business-Critical Continuity TM Data Center Cooling Assessments What They Can Do for You Executive Summary Managing data centers and IT facilities is becoming increasingly
Data Center 2020: Delivering high density in the Data Center; efficiently and reliably
Data Center 2020: Delivering high density in the Data Center; efficiently and reliably March 2011 Powered by Data Center 2020: Delivering high density in the Data Center; efficiently and reliably Review:
Statement Of Work. Data Center Power and Cooling Assessment. Service. Professional Services. Table of Contents. 1.0 Executive Summary
Statement Of Work Professional Services Data Center Power and Cooling Assessment Data Center Power and Cooling Assessment Service 1.0 Executive Summary Table of Contents 1.0 Executive Summary 2.0 Features
Energy and Cost Analysis of Rittal Corporation Liquid Cooled Package
Energy and Cost Analysis of Rittal Corporation Liquid Cooled Package Munther Salim, Ph.D. Yury Lui, PE, CEM, LEED AP eyp mission critical facilities, 200 west adams street, suite 2750, Chicago, il 60606
Data center upgrade proposal. (phase one)
Data center upgrade proposal (phase one) Executive Summary Great Lakes began a recent dialogue with a customer regarding current operations and the potential for performance improvement within the The
Data Center Airflow Management Retrofit
FEDERAL ENERGY MANAGEMENT PROGRAM Data Center Airflow Management Retrofit Technology Case Study Bulletin: September 2010 Figure 1 Figure 2 Figure 1: Data center CFD model of return airflow short circuit
Effect of Rack Server Population on Temperatures in Data Centers
Effect of Rack Server Population on Temperatures in Data Centers Rajat Ghosh, Vikneshan Sundaralingam, Yogendra Joshi G.W. Woodruff School of Mechanical Engineering Georgia Institute of Technology, Atlanta,
Investigation into the energy consumption of a data center with a thermosyphon heat exchanger
Article Mechanical Engineering July 2011 Vol.56 No.20: 2185 2190 doi: 10.1007/s11434-011-4500-5 SPECIAL TOPICS: Investigation into the energy consumption of a data center with a thermosyphon heat exchanger
Optimum Climate Control For Datacenter - Case Study. T. Prabu March 17 th 2009
Optimum Climate Control For Datacenter - Case Study T. Prabu March 17 th 2009 Agenda 2 About EDEC (Emerson) Facility Data Center Details Design Considerations & Challenges Layout Design CFD Analysis Of
IT White Paper MANAGING EXTREME HEAT: COOLING STRATEGIES FOR HIGH-DENSITY SYSTEMS
IT White Paper MANAGING EXTREME HEAT: COOLING STRATEGIES FOR HIGH-DENSITY SYSTEMS SUMMARY As computer manufacturers pack more and more processing power into smaller packages, the challenge of data center
Energy Efficiency Opportunities in Federal High Performance Computing Data Centers
Energy Efficiency Opportunities in Federal High Performance Computing Data Centers Prepared for the U.S. Department of Energy Federal Energy Management Program By Lawrence Berkeley National Laboratory
Energy Management Services
February, 2012 Energy Management Services Data centers & IT environments are often critical to today s businesses, directly affecting operations and profitability. General & Mechanical Services has the
Data Center Equipment Power Trends
Green field data center design 11 Jan 2010 by Shlomo Novotny Shlomo Novotny, Vice President and Chief Technology Officer, Vette Corp. explores water cooling for maximum efficiency - Part 1 Overview Data
Reducing Room-Level Bypass Airflow Creates Opportunities to Improve Cooling Capacity and Operating Costs
WHITE PAPER Reducing Room-Level Bypass Airflow Creates Opportunities to Improve Cooling Capacity and Operating Costs By Lars Strong, P.E., Upsite Technologies, Inc. 505.798.000 upsite.com Reducing Room-Level
International Telecommunication Union SERIES L: CONSTRUCTION, INSTALLATION AND PROTECTION OF TELECOMMUNICATION CABLES IN PUBLIC NETWORKS
International Telecommunication Union ITU-T TELECOMMUNICATION STANDARDIZATION SECTOR OF ITU Technical Paper (13 December 2013) SERIES L: CONSTRUCTION, INSTALLATION AND PROTECTION OF TELECOMMUNICATION CABLES
Rittal Liquid Cooling Series
Rittal Liquid Cooling Series by Herb Villa White Paper 04 Copyright 2006 All rights reserved. Rittal GmbH & Co. KG Auf dem Stützelberg D-35745 Herborn Phone +49(0)2772 / 505-0 Fax +49(0)2772/505-2319 www.rittal.de
Data center lifecycle and energy efficiency
Data center lifecycle and energy efficiency White Paper Lifecycle management, thermal management, and simulation solutions enable data center energy modernization Introduction Data centers are coming under
Data Center Cooling & Air Flow Management. Arnold Murphy, CDCEP, CDCAP March 3, 2015
Data Center Cooling & Air Flow Management Arnold Murphy, CDCEP, CDCAP March 3, 2015 Strategic Clean Technology Inc Focus on improving cooling and air flow management to achieve energy cost savings and
EXPERIMENTAL CHARACTERIZATION OF TRANSIENT TEMPERATURE EVOLUTION IN A DATA CENTER FACILITY
EXPERIMENTAL CHARACTERIZATION OF TRANSIENT TEMPERATURE EVOLUTION IN A DATA CENTER FACILITY Rajat Ghosh, Pramod Kumar Vikneshan Sundaralingam Yogendra Joshi [email protected] G.W. Woodruff School
How High Temperature Data Centers & Intel Technologies save Energy, Money, Water and Greenhouse Gas Emissions
Intel Intelligent Power Management Intel How High Temperature Data Centers & Intel Technologies save Energy, Money, Water and Greenhouse Gas Emissions Power savings through the use of Intel s intelligent
RAISED-FLOOR DATA CENTER: PERFORATED TILE FLOW RATES FOR VARIOUS TILE LAYOUTS
Paper Presented at ITHERM 2004 Ninth Intersociety Conference on Thermal and Thermomechanical Phenomena in Electronic Systems June 1-4, Las Vegas, NV RAISED-FLOOR DATA CENTER: PERFORATED TILE FLOW RATES
How To Improve Energy Efficiency Through Raising Inlet Temperatures
Data Center Operating Cost Savings Realized by Air Flow Management and Increased Rack Inlet Temperatures William Seeber Stephen Seeber Mid Atlantic Infrared Services, Inc. 5309 Mohican Road Bethesda, MD
Unified Physical Infrastructure (UPI) Strategies for Thermal Management
Unified Physical Infrastructure (UPI) Strategies for Thermal Management The Importance of Air Sealing Grommets to Improving Smart www.panduit.com WP-04 August 2008 Introduction One of the core issues affecting
Computational Fluid Dynamics (CFD) Modeling Service
Eaton Data Center Services Computational Fluid Dynamics (CFD) Modeling Service Executive Summary Improve data center energy performance As organizations fill data center enclosures with increasing numbers
Unique Airflow Visualization Techniques for the Design and Validation of Above-Plenum Data Center CFD Models
Unique Airflow Visualization Techniques for the Design and Validation of Above-Plenum Data Center CFD Models The MIT Faculty has made this article openly available. Please share how this access benefits
Modeling Rack and Server Heat Capacity in a Physics Based Dynamic CFD Model of Data Centers. Sami Alkharabsheh, Bahgat Sammakia 10/28/2013
Modeling Rack and Server Heat Capacity in a Physics Based Dynamic CFD Model of Data Centers Sami Alkharabsheh, Bahgat Sammakia 1/28/213 2 ES2 Vision To create electronic systems that are self sensing and
Data Center Technology: Physical Infrastructure
Data Center Technology: Physical Infrastructure IT Trends Affecting New Technologies and Energy Efficiency Imperatives in the Data Center Hisham Elzahhar Regional Enterprise & System Manager, Schneider
Cooling Audit for Identifying Potential Cooling Problems in Data Centers
Cooling Audit for Identifying Potential Cooling Problems in Data Centers By Kevin Dunlap White Paper #40 Revision 2 Executive Summary The compaction of information technology equipment and simultaneous
Cost Model for Planning, Development and Operation of a Data Center
Cost Model for Planning, Development and Operation of a Data Center Chandrakant D. Patel, Amip J. Shah 1 Internet Systems and Storage Laboratory HP Laboratories Palo Alto HPL-005-107(R.1) June 9, 005*
What to Consider When Designing Next-Generation Data Centers
Research Publication Date: 10 September 2010 ID Number: G00201044 What to Consider When Designing Next-Generation Data Centers David J. Cappuccio Leading-edge data centers are designed for flexibility,
Server Room Thermal Assessment
PREPARED FOR CUSTOMER Server Room Thermal Assessment Analysis of Server Room COMMERCIAL IN CONFIDENCE MAY 2011 Contents 1 Document Information... 3 2 Executive Summary... 4 2.1 Recommendation Summary...
Combining Cold Aisle Containment with Intelligent Control to Optimize Data Center Cooling Efficiency
A White Paper from the Experts in Business-Critical Continuity TM Combining Cold Aisle Containment with Intelligent Control to Optimize Data Center Cooling Efficiency Executive Summary Energy efficiency
Cooling a hot issue? MINKELS COLD CORRIDOR TM SOLUTION
Cooling a hot issue? MINKELS COLD CORRIDOR TM SOLUTION The heat load in data centers is increasing rapidly, the adaptation of a cooling strategy is often necessary. Many data centers and server rooms use
HIGHLY EFFICIENT COOLING FOR YOUR DATA CENTRE
HIGHLY EFFICIENT COOLING FOR YOUR DATA CENTRE Best practices for airflow management and cooling optimisation AIRFLOW MANAGEMENT COLD AND HOT AISLE CONTAINMENT DC ASSESSMENT SERVICES Achieving true 24/7/365
Data Center Power Consumption
Data Center Power Consumption A new look at a growing problem Fact - Data center power density up 10x in the last 10 years 2.1 kw/rack (1992); 14 kw/rack (2007) Racks are not fully populated due to power/cooling
BRUNS-PAK Presents MARK S. EVANKO, Principal
BRUNS-PAK Presents MARK S. EVANKO, Principal Data Centers of the Future and the Impact of High Density Computing on Facility Infrastructures - Trends, Air-Flow, Green/LEED, Cost, and Schedule Considerations
EXAMPLE OF A DATA CENTRE BUILD
EXAMPLE OF A DATA CENTRE BUILD BT Harmondsworth Data Centre Hall 2 Upgrade Temperature Control have been involved in providing specialist to data centres for over 20 years, starting from providing specialist
Liquid Cooling Solutions for DATA CENTERS - R.M.IYENGAR BLUESTAR LIMITED.
Liquid Cooling Solutions for DATA CENTERS - R.M.IYENGAR BLUESTAR LIMITED. Presentation Goals & Outline Power Density Where we have been- where we are now - where we are going Limitations of Air Cooling
Energy Efficient Thermal Management of Data Centers
Energy Efficient Thermal Management of Data Centers Yogendra Joshi l Editors Pramod Kumar Energy Efficient Thermal Management of Data Centers Editors Yogendra Joshi G.W. Woodruff School of Mechanical
Reducing Data Center Energy Consumption
Reducing Data Center Energy Consumption By John Judge, Member ASHRAE; Jack Pouchet, Anand Ekbote, and Sachin Dixit Rising data center energy consumption and increasing energy costs have combined to elevate