Thinking Outside the Box Server Design for Data Center Optimization
|
|
|
- Horatio Jenkins
- 9 years ago
- Views:
Transcription
1 Thinking Outside the Box Server Design for Data Center Optimization Marie Ross, Senior Applications Engineer Tom Gregory, Consultant Engineer October 2013 The benefits of analyzing thermal performance using computational fluid dynamic (CFD) models at the board and server level are well understood. This practice, established for decades, has proven to be more cost effective with respect to product design while yielding faster times to market than earlier nonsimulation methods. In addition, thermal margins have been drastically reduced without compromising performance and reliability. For the same reasons, data center designers also rely on CFD to ensure the most cost effective room layout without compromising server inlet air flow and temperature. An extensive amount of data is required to accurately simulate a data center. This includes thermal models of the installed IT equipment. Typically server manufacturers do not provide sufficient thermal information about their products for data center simulation. Currently only the outer dimensions, name plate power and maximum operating temperature are readily available, but for meaningful data center results, information regarding flow rates, vent geometry, and typical power consumption is also essential. Until recently, migrating this information across the simulation supply chain was difficult. However, with 6SigmaDC s suite of thermal modeling tools, the process has become seamless. Now, detailed, validated thermal models at the server level can be used in data center models to provide solid, reliable predictions of facility operations. Using 6SigmaET, the thermal details of the server can be characterized, and a simplified version, using a control volume (or black box) approach can be used by the rest of the 6SigmaDC software to predict airflows and heat dissipations at the rack and room levels. This paper will explore the creation and use of a simplified server model (SSM) using the full suite of 6SigmaDC software. A detailed server model of the Facebook Open Compute Windmill Server will be created in 6SigmaET. This detailed model will be simplified and the SSM will be used to verify the design of the Open Compute Rack and an example data center. The paper will discuss the benefits and limitations of thermal simulation at the server, rack and data center level. The process followed can be seen in figure 1 overleaf. Finally, a comparison will be made between using a SSM in a data center simulation and using basic server data readily available today, this will be conducted in a failure scenario. Air flows and temperatures will re-assessed and a discussion presented. Ju Future Facilities 6SigmaET Thinking Outside the Box Server Design for Data Center Optimization 1
2 Server Simulation Detailed simulation of the motherboard and server. Simplify Server A simplified server model is created from the detailed server simulation. Rack Simulation Simulation of the Open Rack with simplified server models. The rack will be simulated in a rack test environment. Data Center Simulation Simulation of a typical modern data center. Figure 1 Methodology Detailed Server Modeling the server in detail allows IT equipment designers to optimize and verify the design before manufacture. It provides an understanding of the airflow requirements, optimum component placement, and flow patterns. It is also critical for heat sink selection and flow guides. For the Windmill server, this level of analysis provides insights on the perfect baffling structure to ensure air flow through both the CPU heatsinks as well as the memory cards. The server model, based on Intel s Windmill server, can be found on the Open Compute website ( The CAD drawings were downloaded, and Open Compute specifications were imposed (Figure 2) in a 6SigmaET model. Total power dissipation is 236 W W per memory card, 50 W per CPU, 6.2 W from the Drive, 0.5 W from the power interface, with the remainder being evenly distributed on the motherboard. The model was simulated in an open test chamber environment with a supply temperature of 26.5 C. This supply temperature was chosen as it is just below the ASHRAE specified maximum inlet temperature of 27 C. Figure 2: Detailed Server Model Future Facilities 6SigmaET Thinking Outside the Box Server Design for Data Center Optimization 2
3 Flow Rate (CFM) Simplified Server It is not possible within a reasonable timescale to model thousands of duplicated detailed thermal server models in a rack or data center simulation. However, this is not an issue as the internal layout of the server has been verified and validated through simulation and test. In this case, after the detailed model was finalized in 6SigmaET, a SSM was created. The SSM are shown in Figure 3. Figure 3 Simplified server model. Front and rear view. Vents highlighted in red. A SSM treats all internal components as a black box. It is calculated by using the detailed server model and creates a simplified chassis, which includes the vent geometry, flow rate and heat dissipation. This SSM includes sufficient information so that the airflow through the data center can be accurately predicted. In reality when the cold aisle in the data center is contained there is potential it will become pressurized. In this situation more air will be forced through the server than if the server was placed in open space. To account for this, both 6SigmaRack and 6SigmaRoom have an input called the Coefficient of Excess Flow, the value for which is calculated within the detailed server model. The coefficient is obtained by running the detailed model in 6SigmaET at various inlet velocities to assess its impedance. This impedance curve is then validated within 6SigmaRack to ensure that pressure drop meets that provided with the rack. Figure 4 shows the impedance curve comparison between the rack and server level models for this case study Pressure (Pa) Detailed Simplified Figure 4: Comparison between detailed and simplified servers Future Facilities 6SigmaET Thinking Outside the Box Server Design for Data Center Optimization 3
4 Rack Many thermal issues in the data center are caused by rack issues as opposed to the data center environment Rack level thermal analysis gives designers and room operators insights related to the rack thermal design. Is it properly designed? Are face plates necessary? What is the effect of cabling? It provides useful knowledge related to air flow such as issues with recirculation within the rack, or insufficient air flow from the floor grille. It also enables the data center designer or operator to determine the maximum IT load that can be installed in the rack. In this study, a 6SigmaRack model of the Open Compute rack was also created from a CAD model. Thermally insignificant features were removed. Three Windmill servers were installed in to each shelf (Figure 5). Fifteen shelves of Windmill servers and three power supplies were installed in to the rack. The SSM was used to represent the servers. The rack was then installed in a 6SigmaRack Test Chamber environment (Figure 6). The model represents a contained cold aisle with sufficient airflow through the floor grille to meet the equipment airflow requirements. The supply temperature was set to 26.5 C, which is the same as the server simulation. Figure 5: Windmill server configuration within rack tray Figure 6: Open Compute rack simulation Future Facilities 6SigmaET Thinking Outside the Box Server Design for Data Center Optimization 4
5 Data Center Data Center, or Room, scale models provide the necessary information to design the facility s cooling system. For example the airflow produced from the ACUs can be designed to match the airflow requirements of the installed IT equipment. These simulations can be used to validate the data center conceptual design before it becomes operational, and racks that are able to meet the equipment s cooling requirements can be chosen. Modeling can also determine proper placement of new IT equipment to the room. For this study, a model of a typical modern data center was created, as shown in Figure 7. It was designed with 12 rows and 150 racks housing 45 server each, which gives a total of 6750 servers. The total load of the data center is 1716 kw. The data center has 14 air cooling units (ACUs), which provides N+1 redundancy. The racks were modeled in 6SigmaRack and imported into 6SigmaRoom where the data center simulations were performed. 6SigmaRoom has extensive thermal model libraries of equipment found in a data center. The six Power Distribution Units (PDU) as well as the 14 ACU objects were obtained from these libraries. The obstructions from both the network and power cabling were also modeled. Figure 7: Data Center Simulation Future Facilities 6SigmaET Thinking Outside the Box Server Design for Data Center Optimization 5
6 Failure Scenario To show the difference between using SSMs and current design practices, the above methodology was redone using server data that is typically available: outer dimensions, name plate power and maximum operating temperature. The inflow and outflow were assumed to be the same dimensions as the front and back of the server, and a fixed flow rate was set as a ratio to the server input power 120cfm/kW which is typical engineering assumption Both scenarios operated within design specifications for a fully functional data center. However, both have N+1 redundancy to ensure that if an ACU unit were to fail, the servers would continue to function and receive adequate airflow at the proper temperature. The next study was set to analyze what would happen if one of the cooling units were to fail. The ACU that has been red-crossed in Figure 8 was turned off and a simulation with both models was run. Figure 8: Data Center Failure Scenario Future Facilities 6SigmaET Thinking Outside the Box Server Design for Data Center Optimization 6
7 Results The Windmill server simulation results were analyzed and no thermal design issues were found. All components were operating below their maximum operating temperature (Figure 9). The air guides ensure that the airflow passes over the CPU heatsinks and memory cards. Figure 9: Server Surface Temperature plot The rack level simulation of the Open Compute Rack were also analysed and, as can be seen in figure 10, no thermal issues were found. The rack is well designed and there are few paths for recircualtion. All equipment receives sufficent aiflow below 27 C, which is the ASHRAE specfication. The equipment at the top of the rack receives slightly warmer air due to some recirculated air coming over the top of the equipment. The recirculation does not cause any thermal issues. Figure 10: Mean inlet temperature of servers The data center simulation was performed in 6SigmaRoom and the results of the simulation were analyzed. There are no overheating servers in the data center. Figure 11 shows the ASHRAE temperature plot for the data center. The cooling was configured using the data center model and SSM to match the cooling requirements of IT. This design is an idealized one with no thermal issues. Its purpose is to illustrate the methodology of data center design using SSMs. Figure 11: ASHRAE Temperature plot and Floor Grille temperature plot Future Facilities 6SigmaET Thinking Outside the Box Server Design for Data Center Optimization 7
8 Figure 12 shows a comparison between using SSM versus using design assumptions in the data center simulation. This is done is a failure scenario, as specified above, the red cross indicates the failed ACU. The plots below show the number of cabinets which contain overheating equipment. Data Center model, using server models created from the detailed server simulation Data Center model, using server models based on basic assumptions Figure 12 If the data center model was created using server models based on basic assumptions the data center operator would come to the conclusion that the cooling in the data center is insufficent and increase the cooling capacity. This would be incorrect and would reduce the efficency of the data center. Though it is beyond the scope of this paper, after the building costs, operationsal costs are the highest. Over specificying the cooling equipment can cost operators million per year in unnessessary energy bills. Future Facilities 6SigmaET Thinking Outside the Box Server Design for Data Center Optimization 8
9 Conclusion Like for IT equipment simulation, using CFD for data centers is a useful tool for design validation and troubleshooting. It allows for a detailed assessment of the heat and air flow patterns that will emanate from the selected IT equipment as these are intricately linked. Without validated and accurate information about the server, a data center simulation will never be correct, and the design will reflect that even in idealized conceptual designs. To save on solving time, simplified IT equipment models, SSM, can be used to exchange relevant data between electronic simulation and data center simulation tools. Careful consideration must be taken, however, to ensure that specific data is not lost both at the rack and room level as well as within the server. The server model must be a finalized, detailed design before it can be characterized flow and heat dissipation patterns. These are then used as boundary conditions to define a black box without compromising accuracy. This can be done in 6SigmaET, and seamlessly integrated into either 6SigmaRack or 6SigmaRoom. Incorporating the SSM in the rack and data center analysis enables a far better design than those currently done. This innovative approach can save the data center operator millions in energy costs per year. With 6SigmaDC, the entire electronics supply chain can be optimized for functionality, reliably and operational costs. UK Corporate Headquarters North America Japan Future Facilities Limited. 1 Salamanca Street London SE1 7HX Tel: +44 (0) Fax: +44 (0) [email protected] Future Facilities Inc Gateway Place, Suite 110 San Jose CA Tel: Fax: [email protected] Future Facilities KK S2 bldg. 5F Shinjuku Shinjuku-Ku, Tokyo Tel: +81 (0) Fax: +81 (0) [email protected] Future Facilities 6SigmaET Thinking Outside the Box Server Design for Data Center Optimization 9
Introducing the. Virtual Facility
Introducing the Virtual Facility At future facilities, we have developed a groundbreaking methodology enabling owner/operators to improve the performance of a data centre throughout its entire lifecycle.
Easy-to-Use CFD for Electronics Design. Thermal Design in Half the Time
Easy-to-Use CFD for Electronics Design Thermal Design in Half the Time Introducing 6SigmaET 6SigmaET is a thermal modelling tool that uses advanced computational fluid dynamics (CFD) to create accurate
Introducing Computational Fluid Dynamics Virtual Facility 6SigmaDC
IT Infrastructure Services Ltd Holborn Gate, 330 High Holborn, London, WC1V 7QT Telephone: +44 (0)20 7849 6848 Fax: +44 (0)20 7203 6701 Email: [email protected] www.itisltd.com Introducing Computational
Using Simulation to Improve Data Center Efficiency
A WHITE PAPER FROM FUTURE FACILITIES INCORPORATED Using Simulation to Improve Data Center Efficiency Cooling Path Management for maximizing cooling system efficiency without sacrificing equipment resilience
Verizon SMARTS Data Center Design Phase 1 Conceptual Study Report Ms. Leah Zabarenko Verizon Business 2606A Carsins Run Road Aberdeen, MD 21001
Verizon SMARTS Data Center Design Phase 1 Conceptual Study Report Ms. Leah Zabarenko Verizon Business 2606A Carsins Run Road Aberdeen, MD 21001 Presented by: Liberty Engineering, LLP 1609 Connecticut Avenue
Using CFD for optimal thermal management and cooling design in data centers
www.siemens.com/datacenters Using CFD for optimal thermal management and cooling design in data centers Introduction As the power density of IT equipment within a rack increases and energy costs rise,
Data centers have been cooled for many years by delivering
The Increasing Challenge of Data Center Design and Management: Is CFD a Must? Mark Seymour, Christopher Aldham, Matthew Warner, Hassan Moezzi Future Facilities, San Jose, California, USA Mark Seymour,
Analysis of the UNH Data Center Using CFD Modeling
Applied Math Modeling White Paper Analysis of the UNH Data Center Using CFD Modeling By Jamie Bemis, Dana Etherington, and Mike Osienski, Department of Mechanical Engineering, University of New Hampshire,
Great Lakes Data Room Case Study
Great Lakes Data Room Case Study WeRackYourWorld.com Problem: During a warm summer period in 2008, Great Lakes experienced a network outage due to a switch failure in the network enclosure. After an equipment
AisleLok Modular Containment vs. Legacy Containment: A Comparative CFD Study of IT Inlet Temperatures and Fan Energy Savings
WH I TE PAPE R AisleLok Modular Containment vs. : A Comparative CFD Study of IT Inlet Temperatures and Fan Energy Savings By Bruce Long, Upsite Technologies, Inc. Lars Strong, P.E., Upsite Technologies,
Dealing with Thermal Issues in Data Center Universal Aisle Containment
Dealing with Thermal Issues in Data Center Universal Aisle Containment Daniele Tordin BICSI RCDD Technical System Engineer - Panduit Europe [email protected] AGENDA Business Drivers Challenges
Air, Fluid Flow, and Thermal Simulation of Data Centers with Autodesk Revit 2013 and Autodesk BIM 360
Autodesk Revit 2013 Autodesk BIM 360 Air, Fluid Flow, and Thermal Simulation of Data Centers with Autodesk Revit 2013 and Autodesk BIM 360 Data centers consume approximately 200 terawatt hours of energy
High Density Data Centers Fraught with Peril. Richard A. Greco, Principal EYP Mission Critical Facilities, Inc.
High Density Data Centers Fraught with Peril Richard A. Greco, Principal EYP Mission Critical Facilities, Inc. Microprocessors Trends Reprinted with the permission of The Uptime Institute from a white
How To Improve Energy Efficiency Through Raising Inlet Temperatures
Data Center Operating Cost Savings Realized by Air Flow Management and Increased Rack Inlet Temperatures William Seeber Stephen Seeber Mid Atlantic Infrared Services, Inc. 5309 Mohican Road Bethesda, MD
Airflow Simulation Solves Data Centre Cooling Problem
Airflow Simulation Solves Data Centre Cooling Problem The owner s initial design for a data centre in China utilized 40 equipment racks filled with blade servers spread out in three rows along the length
Sealing Gaps Under IT Racks: CFD Analysis Reveals Significant Savings Potential
TECHNICAL REPORT Sealing Gaps Under IT Racks: CFD Analysis Reveals Significant Savings Potential By Lars Strong, P.E., Upsite Technologies, Inc. Bruce Long, Upsite Technologies, Inc. +1.888.982.7800 upsite.com
Prediction Is Better Than Cure CFD Simulation For Data Center Operation.
Prediction Is Better Than Cure CFD Simulation For Data Center Operation. This paper was written to support/reflect a seminar presented at ASHRAE Winter meeting 2014, January 21 st, by, Future Facilities.
Data Center 2020: Delivering high density in the Data Center; efficiently and reliably
Data Center 2020: Delivering high density in the Data Center; efficiently and reliably March 2011 Powered by Data Center 2020: Delivering high density in the Data Center; efficiently and reliably Review:
APC APPLICATION NOTE #92
#92 Best Practices for Designing Data Centers with the InfraStruXure InRow RC By John Niemann Abstract The InfraStruXure InRow RC is designed to provide cooling at the row and rack level of a data center
INFLUENCE OF VARIATION IN CPU UTILIZATION ON THE RACK LEVEL FAN CONFIGURATION AS A COOLING TECHNIQUE FOR HIGH END SERVERS SHREYAS NAGARAJ
INFLUENCE OF VARIATION IN CPU UTILIZATION ON THE RACK LEVEL FAN CONFIGURATION AS A COOLING TECHNIQUE FOR HIGH END SERVERS by SHREYAS NAGARAJ Presented to the Faculty of the Graduate School of The University
Computational Fluid Dynamic Investigation of Liquid Rack Cooling in Data Centres
School of something School of Mechanical Engineering FACULTY OF OTHER ENGINEERING Computational Fluid Dynamic Investigation of Liquid Rack Cooling in Data Centres A. Almoli 1, A. Thompson 1, N. Kapur 1,
DataCenter 2020: hot aisle and cold aisle containment efficiencies reveal no significant differences
DataCenter 2020: hot aisle and cold aisle containment efficiencies reveal no significant differences November 2011 Powered by DataCenter 2020: hot aisle and cold aisle containment efficiencies reveal no
Virtual Data Centre Design A blueprint for success
Virtual Data Centre Design A blueprint for success IT has become the back bone of every business. Advances in computing have resulted in economies of scale, allowing large companies to integrate business
How High Temperature Data Centers & Intel Technologies save Energy, Money, Water and Greenhouse Gas Emissions
Intel Intelligent Power Management Intel How High Temperature Data Centers & Intel Technologies save Energy, Money, Water and Greenhouse Gas Emissions Power and cooling savings through the use of Intel
Data Center Components Overview
Data Center Components Overview Power Power Outside Transformer Takes grid power and transforms it from 113KV to 480V Utility (grid) power Supply of high voltage power to the Data Center Electrical Room
Education Evolution: Scalable Server Rooms George Lantouris Client Relationship Manager (Education) May 2009
Education Evolution: Scalable Server Rooms George Lantouris Client Relationship Manager (Education) May 2009 Agenda Overview - Network Critical Physical Infrastructure Cooling issues in the Server Room
Saving energy in the Brookhaven National Laboratory Computing Center: Cold aisle containment implementation and computational fluid dynamics modeling
Saving energy in the Brookhaven National Laboratory Computing Center: Cold aisle containment implementation and computational fluid dynamics modeling Student Intern Earth and Environmental Engineering,
AEGIS DATA CENTER SERVICES POWER AND COOLING ANALYSIS SERVICE SUMMARY
AEGIS DATA CENTER SERVICES POWER AND COOLING ANALYSIS SERVICE SUMMARY The Aegis Services Power and Assessment Service provides an assessment and analysis of your data center facility and critical physical
Benefits of. Air Flow Management. Data Center
Benefits of Passive Air Flow Management in the Data Center Learning Objectives At the end of this program, participants will be able to: Readily identify if opportunities i where networking equipment
USE OF FLOW NETWORK MODELING (FNM) FOR THE DESIGN OF AIR-COOLED SERVERS
USE OF FLOW NETWORK MODELING (FNM) FOR THE DESIGN OF AIR-COOLED SERVERS Robin Steinbrecher Intel Corporation 2800 Center Drive Dupont, WA 98327 [email protected] Amir Radmehr, Kanchan M. Kelkar,
W H I T E P A P E R. Computational Fluid Dynamics Modeling for Operational Data Centers
W H I T E P A P E R Computational Fluid Dynamics Modeling for Operational Data Centers 2 Executive Summary Improving Effectiveness of CFD Technology in Cooling of Data Centers IT managers continue to be
GUIDE TO ICT SERVER ROOM ENERGY EFFICIENCY. Public Sector ICT Special Working Group
GUIDE TO ICT SERVER ROOM ENERGY EFFICIENCY Public Sector ICT Special Working Group SERVER ROOM ENERGY EFFICIENCY This guide is one of a suite of documents that aims to provide guidance on ICT energy efficiency.
Driving Data Center Efficiency Through the Adoption of Best Practices
Data Center Solutions 2008 Driving Data Center Efficiency Through the Adoption of Best Practices Data Center Solutions Driving Data Center Efficiency Through the Adoption of Best Practices Executive Summary
Reducing the Annual Cost of a Telecommunications Data Center
Applied Math Modeling White Paper Reducing the Annual Cost of a Telecommunications Data Center By Paul Bemis and Liz Marshall, Applied Math Modeling Inc., Concord, NH March, 2011 Introduction The facilities
Cooling Audit for Identifying Potential Cooling Problems in Data Centers
Cooling Audit for Identifying Potential Cooling Problems in Data Centers By Kevin Dunlap White Paper #40 Revision 2 Executive Summary The compaction of information technology equipment and simultaneous
Understanding How Cabinet Door Perforation Impacts Airflow by Travis North
& design deployment The first step in determining the proper perforation for an application is to understand the airflow requirements of the equipment that will be used in the cabinet. Understanding How
Data center upgrade proposal. (phase one)
Data center upgrade proposal (phase one) Executive Summary Great Lakes began a recent dialogue with a customer regarding current operations and the potential for performance improvement within the The
11 Top Tips for Energy-Efficient Data Center Design and Operation
11 Top Tips for Energy-Efficient Data Center Design and Operation A High-Level How To Guide M e c h a n i c a l a n a l y s i s W h i t e P a p e r w w w. m e n t o r. c o m When is Data Center Thermal
A Comparative Study of Various High Density Data Center Cooling Technologies. A Thesis Presented. Kwok Wu. The Graduate School
A Comparative Study of Various High Density Data Center Cooling Technologies A Thesis Presented by Kwok Wu to The Graduate School in Partial Fulfillment of the Requirements for the Degree of Master of
Energy Efficient Data Center Design. Can Ozcan Ozen Engineering Emre Türköz Ozen Engineering
Energy Efficient Data Center Design Can Ozcan Ozen Engineering Emre Türköz Ozen Engineering 1 Bio Can Ozcan received his Master of Science in Mechanical Engineering from Bogazici University of Turkey in
Modeling Rack and Server Heat Capacity in a Physics Based Dynamic CFD Model of Data Centers. Sami Alkharabsheh, Bahgat Sammakia 10/28/2013
Modeling Rack and Server Heat Capacity in a Physics Based Dynamic CFD Model of Data Centers Sami Alkharabsheh, Bahgat Sammakia 1/28/213 2 ES2 Vision To create electronic systems that are self sensing and
Supporting Cisco Switches In Hot Aisle/Cold Aisle Data Centers
CABINETS: ENCLOSED THERMAL MOUNTING MANAGEMENT SYSTEMS WHITE PAPER Supporting Cisco Switches In Hot Aisle/Cold Aisle Data Centers 800-834-4969 [email protected] www.chatsworth.com All products
Strategies for Deploying Blade Servers in Existing Data Centers
Strategies for Deploying Blade Servers in Existing Data Centers By Neil Rasmussen White Paper #125 Revision 1 Executive Summary When blade servers are densely packed, they can exceed the power and cooling
How High Temperature Data Centers & Intel Technologies save Energy, Money, Water and Greenhouse Gas Emissions
Intel Intelligent Power Management Intel How High Temperature Data Centers & Intel Technologies save Energy, Money, Water and Greenhouse Gas Emissions Power savings through the use of Intel s intelligent
Selecting Rack-Mount Power Distribution Units For High-Efficiency Data Centers
C P I P O W E R M A N A G E M E N T WHITE PAPER Selecting Rack-Mount Power Distribution Units For High-Efficiency Data Centers By Anderson Hungria Sr. Product Manager of Power, Electronics & Software Published
Fundamentals of CFD and Data Center Cooling Amir Radmehr, Ph.D. Innovative Research, Inc. [email protected]
Minneapolis Symposium September 30 th, 2015 Fundamentals of CFD and Data Center Cooling Amir Radmehr, Ph.D. Innovative Research, Inc. [email protected] Learning Objectives 1. Gain familiarity with Computational
Small Data / Telecommunications Room on Slab Floor
Small Data / Telecommunications Room on Slab Floor Small Data / Telecommunications Room on Slab Floor During a warm summer period in 2008, Great Lakes experienced a network outage due to a switch failure
Data Center Cooling: Fend Off The Phantom Meltdown Of Mass Destruction. 670 Deer Road n Cherry Hill, NJ 08034 n 877.429.7225 n
Data Center Cooling: Fend Off The Phantom Meltdown Of Mass Destruction How To Preserve Your Servers And Prevent Overheating Your high-performance, multiprocessor servers are working hard, computing tons
How To Run A Data Center Efficiently
A White Paper from the Experts in Business-Critical Continuity TM Data Center Cooling Assessments What They Can Do for You Executive Summary Managing data centers and IT facilities is becoming increasingly
Managing Cooling Capacity & Redundancy In Data Centers Today
Managing Cooling Capacity & Redundancy In Data Centers Today About AdaptivCOOL 15+ Years Thermal & Airflow Expertise Global Presence U.S., India, Japan, China Standards & Compliances: ISO 9001:2008 RoHS
Managing Data Centre Heat Issues
Managing Data Centre Heat Issues Victor Banuelos Field Applications Engineer Chatsworth Products, Inc. 2010 Managing Data Centre Heat Issues Thermal trends in the data centre Hot Aisle / Cold Aisle design
COMPARATIVE ANALYSIS OF WIDELY USED AIR CONTAINMENT SYSTEMS IN COMMERCIAL DATA CENTERS FOR MAXIMUM COOLING PERFORMANCE KASTURI RANGAN RAJAGOPALAN
COMPARATIVE ANALYSIS OF WIDELY USED AIR CONTAINMENT SYSTEMS IN COMMERCIAL DATA CENTERS FOR MAXIMUM COOLING PERFORMANCE by KASTURI RANGAN RAJAGOPALAN Presented to the Faculty of the Graduate School of The
Data center lifecycle and energy efficiency
Data center lifecycle and energy efficiency White Paper Lifecycle management, thermal management, and simulation solutions enable data center energy modernization Introduction Data centers are coming under
Application of CFD modelling to the Design of Modern Data Centres
Application of CFD modelling to the Design of Modern Data Centres White Paper March 2012 By Sam Wicks BEng CFD Applications Engineer Sudlows March 14, 2012 Application of CFD modelling to the Design of
Cooling Capacity Factor (CCF) Reveals Stranded Capacity and Data Center Cost Savings
WHITE PAPER Cooling Capacity Factor (CCF) Reveals Stranded Capacity and Data Center Cost Savings By Lars Strong, P.E., Upsite Technologies, Inc. Kenneth G. Brill, Upsite Technologies, Inc. 505.798.0200
Free Cooling in Data Centers. John Speck, RCDD, DCDC JFC Solutions
Free Cooling in Data Centers John Speck, RCDD, DCDC JFC Solutions Why this topic Many data center projects or retrofits do not have a comprehensive analyses of systems power consumption completed in the
Benefits of Cold Aisle Containment During Cooling Failure
Benefits of Cold Aisle Containment During Cooling Failure Introduction Data centers are mission-critical facilities that require constant operation because they are at the core of the customer-business
Green Data Centre: Is There Such A Thing? Dr. T. C. Tan Distinguished Member, CommScope Labs
Green Data Centre: Is There Such A Thing? Dr. T. C. Tan Distinguished Member, CommScope Labs Topics The Why? The How? Conclusion The Why? Drivers for Green IT According to Forrester Research, IT accounts
Improving Data Center Energy Efficiency Through Environmental Optimization
Improving Data Center Energy Efficiency Through Environmental Optimization How Fine-Tuning Humidity, Airflows, and Temperature Dramatically Cuts Cooling Costs William Seeber Stephen Seeber Mid Atlantic
Elements of Energy Efficiency in Data Centre Cooling Architecture
Elements of Energy Efficiency in Data Centre Cooling Architecture Energy Efficient Data Center Cooling 1 STULZ Group of Companies Turnover 2006 Plastics Technology 400 Mio A/C Technology 200 Mio Total
How to Build a Data Centre Cooling Budget. Ian Cathcart
How to Build a Data Centre Cooling Budget Ian Cathcart Chatsworth Products Topics We ll Cover Availability objectives Space and Load planning Equipment and design options Using CFD to evaluate options
Data Centers. Comparing Data Center & Computer Thermal Design
Data Centers Comparing Data Center & Computer Thermal Design By Michael K. Patterson, Ph.D., P.E., Member ASHRAE; Robin Steinbrecher; and Steve Montgomery, Ph.D. The design of cooling systems and thermal
Cooling a hot issue? MINKELS COLD CORRIDOR TM SOLUTION
Cooling a hot issue? MINKELS COLD CORRIDOR TM SOLUTION The heat load in data centers is increasing rapidly, the adaptation of a cooling strategy is often necessary. Many data centers and server rooms use
Data Centre Cooling Air Performance Metrics
Data Centre Cooling Air Performance Metrics Sophia Flucker CEng MIMechE Ing Dr Robert Tozer MSc MBA PhD CEng MCIBSE MASHRAE Operational Intelligence Ltd. [email protected] Abstract Data centre energy consumption
Energy Performance Optimization of Server Room HVAC System
International Journal of Thermal Technologies E-ISSN 2277 4114 2 INPRESSCO, All Rights Reserved Available at http://inpressco.com/category/ijtt/ Research Article Manoj Jadhav * and Pramod Chaudhari Department
IMPROVING DATA CENTER EFFICIENCY AND CAPACITY WITH AISLE CONTAINMENT
DATA CENTER RESOURCES WHITE PAPER IMPROVING DATA CENTER EFFICIENCY AND CAPACITY WITH AISLE CONTAINMENT BY: STEVE HAMBRUCH EXECUTIVE SUMMARY Data centers have experienced explosive growth in the last decade.
Statement Of Work. Data Center Power and Cooling Assessment. Service. Professional Services. Table of Contents. 1.0 Executive Summary
Statement Of Work Professional Services Data Center Power and Cooling Assessment Data Center Power and Cooling Assessment Service 1.0 Executive Summary Table of Contents 1.0 Executive Summary 2.0 Features
Data Centre/Server Room Containment: How to Get More Cooling Capacity without Adding Additional AC
Data Centre/Server Room Containment: How to Get More Cooling Capacity without Adding Additional AC About us Data centre consulting World-class products Expert national team Mike Hassaballa, Applications
Data Centre Energy Efficiency Operating for Optimisation Robert M Pe / Sept. 20, 2012 National Energy Efficiency Conference Singapore
Data Centre Energy Efficiency Operating for Optimisation Robert M Pe / Sept. 20, 2012 National Energy Efficiency Conference Singapore Introduction Agenda Introduction Overview of Data Centres DC Operational
The Benefits of Supply Air Temperature Control in the Data Centre
Executive Summary: Controlling the temperature in a data centre is critical to achieving maximum uptime and efficiency, but is it being controlled in the correct place? Whilst data centre layouts have
Cabinets 101: Configuring A Network Or Server Cabinet
Cabinets 101: Configuring A Network Or Server Cabinet North, South and Central America White Paper May 2012 www.commscope.com Contents Background Information 3 What is a network or server cabinet? 3 What
Thermal Analysis, Heat Sink Design and Performance Verification for GE Fanuc Intelligent Platform s WANic 3860 Packet Processor PCI Card
CASE STUDY Thermal Analysis, Heat Sink Design and Performance Verification for GE Fanuc Intelligent Platform s WANic 3860 Packet Processor PCI Card Challenge When GE Fanuc Intelligent Platforms, a leading
HIGHLY EFFICIENT COOLING FOR YOUR DATA CENTRE
HIGHLY EFFICIENT COOLING FOR YOUR DATA CENTRE Best practices for airflow management and cooling optimisation AIRFLOW MANAGEMENT COLD AND HOT AISLE CONTAINMENT DC ASSESSMENT SERVICES Achieving true 24/7/365
Server Chassis and Triplet Hardware v1.0
Server Chassis and Triplet Hardware v1.0 Author: Steve Furuta, Mechanical Designer 1 Scope This document describes the technical specifications for the custom chassis used in Open Compute Project servers
Using Computational Fluid Dynamics (CFD) for improving cooling system efficiency for Data centers
Data Centre Best Practises Workshop Using Computational Fluid Dynamics (CFD) for improving cooling system efficiency for Data centers Shishir Gupta 17 th March 2009 You are Here Introduction to CFD Data
Optimum Climate Control For Datacenter - Case Study. T. Prabu March 17 th 2009
Optimum Climate Control For Datacenter - Case Study T. Prabu March 17 th 2009 Agenda 2 About EDEC (Emerson) Facility Data Center Details Design Considerations & Challenges Layout Design CFD Analysis Of
Unified Physical Infrastructure (UPI) Strategies for Thermal Management
Unified Physical Infrastructure (UPI) Strategies for Thermal Management The Importance of Air Sealing Grommets to Improving Smart www.panduit.com WP-04 August 2008 Introduction One of the core issues affecting
IT Cost Savings Audit. Information Technology Report. Prepared for XYZ Inc. November 2009
IT Cost Savings Audit Information Technology Report Prepared for XYZ Inc. November 2009 Executive Summary This information technology report presents the technology audit resulting from the activities
The New Data Center Cooling Paradigm The Tiered Approach
Product Footprint - Heat Density Trends The New Data Center Cooling Paradigm The Tiered Approach Lennart Ståhl Amdahl, Cisco, Compaq, Cray, Dell, EMC, HP, IBM, Intel, Lucent, Motorola, Nokia, Nortel, Sun,
Flow in data racks. 1 Aim/Motivation. 3 Data rack modification. 2 Current state. EPJ Web of Conferences 67, 02070 (2014)
EPJ Web of Conferences 67, 02070 (2014) DOI: 10.1051/ epjconf/20146702070 C Owned by the authors, published by EDP Sciences, 2014 Flow in data racks Lukáš Manoch 1,a, Jan Matěcha 1,b, Jan Novotný 1,c,JiříNožička
Power and Cooling for Ultra-High Density Racks and Blade Servers
Power and Cooling for Ultra-High Density Racks and Blade Servers White Paper #46 Introduction The Problem Average rack in a typical data center is under 2 kw Dense deployment of blade servers (10-20 kw
Enclosure and Airflow Management Solution
Enclosure and Airflow Management Solution CFD Analysis Report Des Plaines, Illinois December 22, 2013 Matt Koukl- DECP Mission Critical Systems Affiliated Engineers, Inc. Contents Executive Summary...
Cooling Capacity Factor (CCF) Reveals Stranded Capacity and Data Center Cost Savings
WHITE PAPER Cooling Capacity Factor (CCF) Reveals Stranded Capacity and Data Center Cost Savings By Kenneth G. Brill, Upsite Technologies, Inc. Lars Strong, P.E., Upsite Technologies, Inc. 505.798.0200
How To Improve Energy Efficiency In A Data Center
Google s Green Data Centers: Network POP Case Study Table of Contents Introduction... 2 Best practices: Measuring. performance, optimizing air flow,. and turning up the thermostat... 2...Best Practice
How to Meet 24 by Forever Cooling Demands of your Data Center
W h i t e P a p e r How to Meet 24 by Forever Cooling Demands of your Data Center Three critical aspects that are important to the operation of computer facilities are matching IT expectations with the
Element D Services Heating, Ventilating, and Air Conditioning
PART 1 - GENERAL 1.01 OVERVIEW A. This section supplements Design Guideline Element D3041 on air handling distribution with specific criteria for projects involving design of a Data Center spaces B. Refer
Improving Rack Cooling Performance Using Airflow Management Blanking Panels
Improving Rack Cooling Performance Using Airflow Management Blanking Panels By Neil Rasmussen White Paper #44 Revision 3 Executive Summary Unused vertical space in open frame racks and rack enclosures
FAC 2.1: Data Center Cooling Simulation. Jacob Harris, Application Engineer Yue Ma, Senior Product Manager
FAC 2.1: Data Center Cooling Simulation Jacob Harris, Application Engineer Yue Ma, Senior Product Manager FAC 2.1: Data Center Cooling Simulation Computational Fluid Dynamics (CFD) can be used to numerically
Center Thermal Management Can Live Together
Network Management age e and Data Center Thermal Management Can Live Together Ian Seaton Chatsworth Products, Inc. Benefits of Hot Air Isolation 1. Eliminates reliance on thermostat 2. Eliminates hot spots
University of St Andrews. Energy Efficient Data Centre Cooling
Energy Efficient Data Centre Cooling St. Andrews and Elsewhere Richard Lumb Consultant Engineer Future-Tech Energy Efficient Data Centre Cooling There is no one single best cooling solution for all Data
APC APPLICATION NOTE #112
#112 Best Practices for Deploying the InfraStruXure InRow SC By David Roden Abstract The InfraStruXure InRow SC (ACSC100 and ACSC101) is a self-contained air conditioner for server rooms and wiring closets.
Optimizing Network Performance through PASSIVE AIR FLOW MANAGEMENT IN THE DATA CENTER
Optimizing Network Performance through PASSIVE AIR FLOW MANAGEMENT IN THE DATA CENTER Lylette Macdonald, RCDD Legrand Ortronics BICSI Baltimore 2011 Agenda: Discuss passive thermal management at the Rack
Data Center Technology: Physical Infrastructure
Data Center Technology: Physical Infrastructure IT Trends Affecting New Technologies and Energy Efficiency Imperatives in the Data Center Hisham Elzahhar Regional Enterprise & System Manager, Schneider
Specialty Environment Design Mission Critical Facilities
Brian M. Medina PE Associate Brett M. Griffin PE, LEED AP Vice President Environmental Systems Design, Inc. Mission Critical Facilities Specialty Environment Design Mission Critical Facilities March 25,
Effect of Rack Server Population on Temperatures in Data Centers
Effect of Rack Server Population on Temperatures in Data Centers Rajat Ghosh, Vikneshan Sundaralingam, Yogendra Joshi G.W. Woodruff School of Mechanical Engineering Georgia Institute of Technology, Atlanta,