ADVISORY BOARD CALENDAR
|
|
|
- Jasper Ramsey
- 10 years ago
- Views:
Transcription
1 48300CO 07A0545CO Lowy & Donnath, Inc th Avenue Carry over from November 14, 2007 meeting. NYPH 523 East 70th Street 48359CO 07A0567CO Wade Electric, Inc th Street Long Island City NY Need side of ATS. Job finalized 2/25/08. East River Science Park 450 East 29th Street 48395CO 07A0650CO Connectrac 163 Leslie Street Dallas TX Carry over from December 12, 2007 meeting. Requested approval for use in New York City of your Steel Receptacle and Cover. 8-Wire, 4-Circuit power jumper and infeed, and floor-mounted raceway components Connectrac U Series 48396CO 07A0651CO Connectrac 163 Leslie Street Dallas TX Carry over from December 12, 2007 meeting. Requested approval for the use in New York City of your Duplex Receptacle System with 24 flex conduit and floor-mounted raceway Components. Connectrac I Series CO 07A0652CO Connectrac 163 Leslie Street Dallas TX Carry over from December 12, 2007 meeting. Requested approval for use in New York City of Steel Junction Box with 24 flex conduit and floormounted raceway components. Connectrac M Series. Wednesday, August 19, 2015 Page 1 of 13
2 48401CO Quantum Electric Corporation Northern Blvd. Carry over from December 12, 2007 meeting. Requesting permission not to file full Advisory Board drawings for the addition of a new 200 amp service switch that will provide power to a limited service fire pump Community Service nd Street A0001 Campell and Dawes Ltd. Electl Contrs th Street Kew Gardens NY HSBC-Cooling Tower 119 West 39th Street A0002 Adco Electrical Corporation 201 Edward Curry Avenue Staten Island NY Beacon Capital Hold $ th Avenue 1) Provide paralleling switchgear in Advisory Board SDS( i.e. bus dimensions etc). 2) Provide GFP on paralleling switchgear breakers. 3) Indicate generator neutral/ground point A0003 Red Wing Electric of New York East Williston Avenue Floral Park NY ) Explain ground on 200 amp disconnect switch. 2) 4 conductors shall feed the 400 amp service switch. 3) Fuse type not provided Grand Central Parkway East Elmhurst NY Ok, but $ A0004 Red wing Electric of New York East Williston Avenue Floral Park NY ) Service entrance conductor size from meter to service switch not shown. 2) 2nd fusing not shown st Avenue Astoria NY Ok, but $ Wednesday, August 19, 2015 Page 2 of 13
3 A0005 Allran Electric of NY 120 Broadway, 36th Floor AOL 770 Broadway A0006 M.O.S. Electrical Contracting Corp. 4340B Katonah Avenue Bronx NY Confirm primary switch and fuse of 500 KVA transformer can handle transformer in rush. Job finalized 2/25/ West 57th Street A0007 CRM Electric Corporation 601 West 26th Street, Suite Adam C. Powell Jr. & 127th Stre A0008 Innovative Electric of New York, Inc Cross Bronx Expressway Bronx NY Prospect Avenue Apartments 890 Prospect Avenue Bronx NY A0009 Techno-Volt Electric, Inc th Street Flushing NY Vernon Boulevard Long Island City NY Wednesday, August 19, 2015 Page 3 of 13
4 A0010 Matros Automated Electl Constn Corp. 214 West 29th Street Broad Street A0011 L.E.A. Electric Corp Sixth Avenue, 11th Floor Union Square West A0012 Five Star Electric Corp st Street Ozone Park NY Columbus Avenue A0013 Kew Electric Inc Hylan Blvd. Staten Island NY Eighth Avenue 3/26/14 Swapped A-Rev 3 and B-Rev 4. 3/24/15 Swapped A-Revision 4 and B Revision 5. 8/17/15 Swapped drawing B-Revision 6. No more as built swaps for this job A0014 gel Power & Light Electrical Contractors, L 32 East 31st Street, Suite ) Provide coordination per for elevator disconnects. 2) Provide coordination for service switch #2 and tenant DP. Job finalized 7/1/ East 101st Street Wednesday, August 19, 2015 Page 4 of 13
5 A0015 Pinnacle Electric st Avenue Richmond Hill NY One Hunters Point 5-49 Borden Avenue Long Island City NY 1) How is life safety metered. 2) Fire pump has fused switch, only 1 allowed. 3) Indicate neutral term and ground connector for FP service switch. Job finalized 4/7/ A0016 Genmar Electrical Contracting Corp rd Avenue Ozone Park NY FedEX Distribution Center Hold $ East 132nd Street Bronx NY 1) Verify if Con-ED is feeding the CT. 2) FCO switches to be lockable and identified. 3) Provide bus size from service switch to panel. 4) FCO to be connected before neutral line. 5) FA ATS being fed at 460V on generator side. 6) Identify if generator neutral is grounded. 7) confirm generator is adequately sized to operate FP. 8) FCO not permitted at 460V. 9) Indicate clearance from disconnect switch adjacent to FP disconnect A0017 Five Star Electric Corp st Street Ozone Park NY Amsterdam Avenue 1) Verify that copper conductors are being used between 2000 amp switch to detail trough. 2) Show tap detail in trough. 3) FP feeder to be rated. 4) Provide second door. Job finalized 5/15/ A0018 June Electric Corp Continental Avenue, Suite 5E Bronx NY East 34th Street 1) 2500 amp fire pump service switch is not located 12" from the switchboard. 2) Switch for manual fire pump is undersized, should be 400 amps. 3) Feed to manual fire pump not fire rated. 4) Fusing per DP-C does not coordinate with service switch fuse. Job finalized 3/3/08. 11/18/14 Swapped 1 of 1 Revision A0019 alvatore Campisi & Sons Electl Contrs, Inc 453 Onderdonk Avenue Ridgewood NY Tap bus to vertical section of new distribution section undersized. Job finalized 2/27/ th Avenue Wednesday, August 19, 2015 Page 5 of 13
6 A0020 J.A. Lee Electric, Inc th Avenue Metro PCS 29 West 47th Street A0021 J.A. Lee Electric, Inc th Avenue Sprint Wireless Broadband 425 East 25th Street A0022 Hugh O Kane Electric Company, Inc. 90 White Street Rockefeller Group Hold $ th Avenue 1) Show tap details of bus duct on 10th and C1 levels. 2) How long are taps to panels off of bus duct tap. 3) Clarify DP concourse and distribution switchboard on 10th floor with physical drawings from Galaxy and show interlock buses. 4) Remove neutral bond in panel DPH-RP-1. 5) Bus feeding amp service switches undersized A0023 Primiano Electric Co th Avenue, 6th Floor Grand Hyatt Hotel 109 East 42nd Street A0024 Red Wing Electric of New York East Williston Avenue Floral Park NY th Avenue College Point NY 1) Second fusing not shown, short circuit calculations. 2) Cut sheet of service switch not provided. 3) Supplemental ground not provided. 4) Clarify neutral in service switch. Ok, but $ Wednesday, August 19, 2015 Page 6 of 13
7 A0025 Red Wing Electric of New York East Williston Avenue Floral Park NY ) Remove neutral bond and supplemental ground in 200 amp disconnect switch. 2) Show tap detail in trough after the new 800 amp service switch Rockaway Blvd. Jamaica NY Ok, but $ A0026 GMA Electrical Corporation 201 Edward Curry Avenue, 2nd Floor Staten Island NY The total fusing cannot exceed the rating of the 500 MCM conductor. Job finalized 2/16/10. Advanced Realty West 23rd Street A0027 Eldor Electric, LLC th Street College Point NY FDNY LIC Shop th Street Long Island City NY A0028 Atlas-Acon Electric Service Corp. 283 Hudson Street East 42nd Street A0029 Seong Jin Electric Inc th Street Woodside NY Kew Gardens Road Queens NY Wednesday, August 19, 2015 Page 7 of 13
8 A0030 Sigma Electric, Inc rd Street, Suite 1-M Elmhurst NY Sheraton Hotel 222 Duffield Street Brooklyn NY A0031 Five Star Electric Corp st Street Ozone Park NY Queens Family Courthouse Apts Parsons Blvd. Jamaica NY A0032 J.G. Electrical Installations, Inc th Place Ridgewood NY NY Downtown Hospital 170 Williams Street A0033 Dooley Electric Company, Inc rd Avenue Brooklyn NY Salvation Army 120 West 14th Street 1) Change existing 2500 amp fuses in service switch #2 to 2000 amps with signage. 2) Provide control on generator board to trip open load band in emergency mode. Job finalized 2/25/ A0034 A & M Electrical Service, Inc nd Avenue Brooklyn NY West 88th Street Wednesday, August 19, 2015 Page 8 of 13
9 A0035 A & M Electrical Service, Inc rd Avenue Brooklyn NY John Street A0036 Petrocelli Electric Co., Inc Queens Plaza North Emergency feeds for life safety not tapped from line side of emergency generators switchboard. Weill Cornell Hold $ East 61th Street A0037 Forest Electric Corp. Two Pennsylvania Plaza, 4th Floor Furman Street Brooklyn NY 1) Show service entrance to switchboards, bus on sets. 2) 4000 amp fuse in Board A oversized. 3) Fire pump service switch not remote from the switchboard. Job finalized 2/25/ A0038 Pinnacle Electric st Avenue Richmond Hill NY Broad Street Hold $ ) Fire pump switch feed tapped from switchboard section that contains a switch. 2) Fire pump circuit not shown on drawing. 3) Fire pump circuit not shown must be fire rated. 4) Note on drawing must indicate fire pump and painted red. 5) Fire pump metered twice A0039 Tru-Val Electric Corporation 2550 Park Avenue Bronx NY Show short circuit curves. Job finalized 5/19/08. P.S. 142M 100 Attorney Street Wednesday, August 19, 2015 Page 9 of 13
10 A0040 W.T.G. Electric, Inc Beach Channel Drive Rockaway Park NY Marymount Manhattan College 221 East 71st Street A0041 J.A. Lee Electric, Inc th Avenue Relocate 200 amp service switch above meter pan. Job finalized 2/27/08. Metro PCS-Hunter College 450 West 41st Street A0042 J.A. Lee Electric, Inc th Avenue Conductor size on load side of meter and 200 amp disconnect switch not shown. Sprint Wireless Broadband Ok, but $ East 66th Street A0043 Forest Electric Corp. Two Pennsylvania Plaza, 4th Floor Bell Atlantic 1633 Broadway M.O.S. Electrical Contracting Corp. 4340B Katonah Avenue Bronx NY Requesting permission due to lack of room inside of the existing service room to install a new service switch in an adjacent room, where signage will be provided. 315 West 57th Street Wednesday, August 19, 2015 Page 10 of 13
11 48447 Atlas-Acon Electric Service Corp. 283 Hudson Street Requesting permission to install a seventh service in a building where the switch will supply power to a sprinkler booster pump. 300 East 42nd Street Kew Electric Inc Hylan Blvd. Staten Island NY Requesting permission to install concrete encased service entrance conductors in Schedule 80 rigid nonmetallic PVC conduits. 785 Eighth Avenue DVL Consulting Engineers Inc. 137 Fifth Avenue Requesting permission to install concrete encased service laterals and service entrance conductors in rigid non metallic PVC conduits. PS 829R 98 Grant Street Tompkinsville NY Five Star Electric Corp st Street Ozone Park NY Requesting permission to install concrete encased service entrance conductors in non metallic fiberglass reinforced epoxy conduits. 805 Columbus Avenue ACP Electrical Contracting, Inc. 412 West 48th Street with the stipulation that the rating of the enclosed fuse is rated 2 amperes or less. Requesting permission to install bayonet type overcurrent protective devices rated 3 to 5 amps inside of the dwelling unit circuit breaker panels to provide untamperable power for submetering. 65 West 90th Street Wednesday, August 19, 2015 Page 11 of 13
12 48452 A & M Electrical Service Inc nd Avenue Brooklyn NY Requesting permission to install life safety automatic transfer switches inside of a fire pump room. 55 John Street Stanco Systems Electrical Contracting 4061 Victory Boulevard Staten Island NY Requesting permission to tap temporary power from the load side of a 3000 amp service switch to feed a temporary 400 amp second fusing that will provide power to scaffolding that will be in use less than one year Empire State Building 34th Street & Fifth Avenue Pinnacle Electric st Avenue Richmond Hill NY Requesting permission to tap power to supply a fire pump from the load side of a CT that is located in the same switchbaord section that contains a service switch. Denied $ Genmar Electrical Contracting Corp rd Avenue Ozone Park NY Requesting permission due to existing commercial building condition problems, to allow the new service equipment to be installed on the exterior of the building supplied by underground rigid nonmetallic PVC conduits Leggett Avenue Bronx NY Excel Electric Co., Inc. 207 West 25th Street, 9th Floor Requesting permission due to creating an extreme financial distress to leave as installed 23 three family homes that are wired without the common area's branch circuits being supplied by a separate public, light and power meter and panelboard Crystal St, Flatlands Ave., Montauk Brooklyn NY Wednesday, August 19, 2015 Page 12 of 13
13 A0044 Janmar Lighting 730 W. Golden Grove Way Convina GA With the stipulation that Model Requested approval for use in New York City of your Luminescent T Ceramic Metal Halide (CMH) portable track fixtures. Model/Series Numbers: 736, 737, 738, 739, 740, 741, 744, 752, 756, 756SL and A0045 Illumivision Inc th Str. Edmonton Alberta, Canada T6B2J8 Requested approval for use in New York City of your LED Lighting Fixtures. Model/Series Numbers: LX White/RGB, Highlite, Lightwave Bar White/RGB, Mini White/RGB, Smartflo, Power supplies Approved $ A0046 Thomas & Betts Corp T & B Blvd. Memphis TN Requested approval for use in New York City of your Conduit Expansion Coupling. Model/Series Numbers: XJG-Series ½" to 5" Trade Sizes Approved $ Wednesday, August 19, 2015 Page 13 of 13
ADVISORY BOARD CALENDAR
45232CO 03A0564CO Jacoby Electric Corp. 10-40 Borden Avenue Long Island City NY 11101 Carryover from October 15, 2003 meeting. New School University 55 West 13th Street 45233CO 03A0565CO Dooley Electric
ACTIVE PROPRIETARY SCHOOLS HAVING BPSS-APPROVED PCA OR HHA TRAINING PROGRAMS
ACTIVE PROPRIETARY SCHOOLS HAVING BPSS-APPROVED PCA OR HHA TRAINING PROGRAMS (s. means since and indicates the date of approval for the particular curriculum). updated 10/15/2015 CHANGES FROM LAST LIST:
SCHEDULE FOR SEPTEMBER 2013
SCHEDULE FOR SEPTEMBER 2013 Mon., Sept. 2 Wed., Sept. 4 LABOR DAY ROSH HASHANAH BEGINS AT SUNDOWN Tuesday KEEPERS---140 Woodbine St., Bergenfield, NJ Sept. 10 201-387-2900 Wednesday QUEENS FRESH MEADOWS
GROWTH MANAGEMENT DEPARTMENT 201 SE 3 rd ST, (Second Floor), Ocala, FL 34471 (352) 629-8421; FAX: (352) 629-8264
BUILDING CODE GUIDELINES FOR ELECTRICAL INSPECTIONS Building Code compliance is the obligation of design professionals and/or contractors. Plan Review and Inspection Guidelines are intended to be used
A New and Unique Way to Care for New Yorkers
The Advantage of ADVANTAGECARE PHYSICIANS The right care... At EmblemHealth, we know care is at the heart of every successful community. That s why it is the cornerstone of our innovative community initiatives
Customer Low-Voltage Switchboards Service Cable Terminal Compartment Arrangements and Clearances
Page 50 of 100 Customer Low-Voltage Switchboards Service Cable Terminal Compartment Arrangements and Clearances (Replaces A-190556) THIS CUSTOMER REFERENCE SPECIFICATION (CRS) IS PART OF THE RULES FOR
All work must conform to the National Electric Code, latest edition, and all other applicable codes and regulations.
DIVISION 16 ELECTRICAL SECTION 16100 - ELECTRICAL PART 1 - GENERAL SCOPE All electrical work as shown on the drawings and as necessary to provide a complete electrical system. Include primary service,
THE ADVANTAGE OF ADVANTAGECARE PHYSICIANS
THE ADVANTAGE OF ADVANTAGECARE PHYSICIANS THE RIGHT CARE... At EmblemHealth, we know care is at the heart of every successful community. That s why it is the cornerstone of our innovative community initiatives
BASIC FACTS ABOUT THE FAMILY EVICTION PREVENTION SUPPLEMENT (FEPS) PROGRAM
Brooklyn Neighborhood Office 111 Livingston Street - 7th Fl. T (718) 722-3100 www.legal-aid.org Blaine (Fin) V. Fogg President BASIC FACTS ABOUT THE FAMILY EVICTION PREVENTION SUPPLEMENT (FEPS) PROGRAM
Electrical Service Guidelines
Electrical Service Guidelines Middle Tennessee Electric Membership Corporation Revised: May 23, 2013 MTEMC's Electrical Guidelines TABLE OF CONTENTS Right-of-Way Clearance Guide 3 MTEMC Requirements 4
Questions and Answers for Heating and A/C Contractors
1. How do we accomplish grounding of furnaces and / or water heaters on two wire circuits? 250.134 Equipment Fastened in Place or Connected by Permanent Wiring Methods (Fixed) Grounding. Unless grounded
Top Commercial / Residential Electrical Requirements *
Department of Community Development Building Division 4800 West 92 nd Avenue Westminster, Colorado 80031 For Information call (303) 658-2075 Fax (303) 706-3922 www.westminsterpermits.com Top Commercial
INDUSTRIAL AND COMMERCIAL SERVICE TRANSFORMER & METERING INSTALLATION SPECIFICATION
INDUSTRIAL AND COMMERCIAL SERVICE TRANSFORMER & METERING INSTALLATION SPECIFICATION February 2013 NOTE: If conflict exists between St. Thomas Energy s Conditions of Service and this document, the Conditions
Engineers Edge, LLC PDH & Professional Training
510 N. Crosslane Rd. Monroe, Georgia 30656 (770) 266-6915 fax (678) 643-1758 Engineers Edge, LLC PDH & Professional Training Copyright, All Rights Reserved Engineers Edge, LLC An Introduction to Interior
How To Get A Power Line Extension
GUIDELINES FOR COMMERCIAL ELECTRIC SERVICE HOOKUP 1 Steps to Commercial Service Pay the Design Deposit Commercial Buildings: Up to 1, sq ft = $1,. 1, 5, sq ft = $2,. Over 5, sq ft = $3,. Commercial jobs
BASIC NEC CODE RULES AND DESIGN PRACTICE
BASIC NEC CODE RULES AND DESIGN PRACTICE Wire Ampacity and Size Circuit Breaker Size 1. Maximum loading for any branch circuit is 80% of rating of circuit for ampacity of wire for any load. NEC 220-2,
2014 NEC Guide Lines for Home Owner Doing Electrical Work on their Property
2014 NEC Guide Lines for Home Owner Doing Electrical Work on their Property A brief summary of the most used code references for residential wiring State of Idaho Division of Building Safety Electrical
Electrical for Detached Garages: Updated Feb 19, 2016 for 2015 CE Code in force Jan. 1, 2016. Underground branch circuit feeding a detached garage:
Electrical for Detached Garages: Updated Feb 19, 2016 for 2015 CE Code in force Jan. 1, 2016 * Garage construction requires permits (electrical, building) * Permits must be applied for at the time. * Dial
B R O N X. 25 United Bronx Parents, Inc. 966 Prospect Avenue, 1st & 2nd Floor (718) 617-6060
25 United Bronx Parents, Inc. 966 Prospect Avenue, 1st & 2nd Floor (718) 617-6060 26 Argus Community, Inc. 760 East 160th Street, (718) 401-5700 27 Osborne Treatment Services, Inc. 801-809 Westchester
City of Riverside Building & Safety Division Phone: (951) 826-5697 www.riversideca.gov
City of Riverside Building & Safety Division Phone: (951) 826-5697 www.riversideca.gov PHOTOVOLTAIC PERMITTING GUIDELINES The information provided in this document is general and is intended only as a
SOLAR PV STANDARD ELECTRICAL PLAN Microinverter Systems for Single Family Dwellings
*** Provide this document to the inspector along with ALL system installation instructions *** Project Address: Scope: Standard plan for the installation of grounded microinverter solar PV systems, not
City of San Diego Residential Photovoltaic Systems Inspection Guidelines
City of San Diego Residential Photovoltaic Systems Inspection Guidelines The purpose of inspections by DSD staff is to ensure compliance with the California Electrical Code (CEC), other applicable codes
GED PLUS PROGRAM DIRECTORY
GED PLUS PROGRAM DIRECTORY BRONX BROOKLYN MANHATTAN QUEENS STATEN ISLAND GED Plus helps students earn their GED plus prepares them for college and career options. Students 18-21 years old can choose to
3. TYPES OF SERVICE AVAILABLE. 3.1 Scope
3. TYPES OF SERVICE AVAILABLE 3.1 Scope UI supplies 60 hertz, alternating current with different voltage and ampere ratings. Not all voltage and ampere ratings are available throughout the entire service
GED Plus Locations. Program Site name Address Borough. Bronx GED Plus Hub/Referral Center at Bronx Regional High 1010 Rev. James Polite Avenue Bronx
Program Site name Address Borough Bronx GED Plus Hub/Referral Center at Bronx Regional High 1010 Rev. James Polite Avenue Bronx School GED Plus at Bronx Community College Future Now 2155 University Avenue
Element D Services Electrical
Service and PART 1 - GENERAL 1.01 OVERVIEW A. This Section includes design standards and requirements for electrical service and distribution. This is a design standard and is not intended to be used as
Electrical. This section applies to the design and installation of building power distribution systems.
Basis of Design This section applies to the design and installation of building power distribution systems. Design Criteria This section contains the architectural, structural and mechanical provisions
ELECTRICAL CONTRACTORS THE UNIVERSITY OF TENNESSEE KNOXVILLE, TENNESSEE SECTION 16050 PAGE 1
KNOXVILLE, TENNESSEE SECTION 16050 PAGE 1 PART 1 - GENERAL 1.01 RELATED DOCUMENTS: SECTION 16050 A. Drawings and general provisions of Contract, including General and Supplementary Conditions and Division-1
IRRIGATION PUMPING Table of Contents - Section 900
IRRIGATION PUMPING Table of Contents - Section 900 PARAGRAPH 900.1 GENERAL 1 900.2 METERING REQUIREMENTS 1 900.3 CUSTOMER S CONTROL EQUIPMENT 2 900.4 SERVICE CONDUCTOR REQUIREMENTS 2 900.5 RECOMMENDATIONS
Significant Changes in the 2011 NEC Prepared by Bryan Holland City of North Port
Significant Changes in the 2011 NEC Prepared by Bryan Holland City of North Port Code-Wide Code Change Section 90.5(C). Fine Print Notes are now referred to as "Informational Notes." The purpose, intent,
SINGLE FAMILY DWELLING ELECTRICAL SERVICES RATED 225 TO 600 AMPS
SINGLE FAMILY DWELLING ELECTRICAL SERVICES RATED 225 TO 600 AMPS A. PURPOSE 1. The following information includes the basic permit application requirements for a 120/240 volt single phase Electrical Service
ELECTRICAL INSPECTION BULLETIN (Effective 2000-03-01)
ELECTRICAL INSPECTION BULLETIN (Effective 2000-03-01) Rule 28-900 Standby Generator Installations Due to the increasing number of standby generator installations being established to maintain continuity
Homeowner Information Guide Electrical Safety. British Columbia Safety Authority
Homeowner Information Guide Electrical Safety British Columbia Safety Authority The following information should be carefully reviewed before performing any electrical work. The information contained in
County of Riverside Building and Safety Department
County of Riverside Building and Safety Department Mike Lara Director Photovoltaic Permitting Guidelines The information provided in this document is general and is intended only as a guide. Each project
METER REQUIREMENTS GENERAL REQUIREMENTS SECTION D
12 - ELECTRIC SERVICE HANDBOOK SECTION D METER REQUIREMENTS This chapter gives you information on Central Lincoln s metering requirements. It's divided into three sections: General requirements This section
Below is a list of neighborhood sites where someone will prepare your taxes for FREE. Refer to the Key for important eligibility information.
Below is a list of neighborhood sites where someone will prepare your taxes for FREE. Refer to the Key for important eligibility information. Key Sites with this icon are Volunteer Income Tax Assistance
Services. Three Phase Service
Services Primary Service vs Secondary Service Overhead vs Underground Common Service Types Three Phase Wye Closed Open Delta Corner Grounded Center Tapped Open Single Phase Three Phase Service Wye Delta
4300 Ashford Dunwoody Road Atlanta, GA 30346 (Rich s Perimeter Mall) Tommy Women s Jeans - Installation of wall units & fixtures
McFay Contracting, Client Project List Please call us or visit our website for more information. McFay Contracting, Inc. 885 Albany Ave. Brooklyn, NY 11203 718-462-5757 www.mcfaycontracting.com Projects:
MISCELLANEOUS ELECTRICAL JOBS REQUIRING PERMITS
MISCELLANEOUS ELECTRICAL JOBS REQUIRING PERMITS 01. SAFETY INSPECTION of service equipment at FPL Power Source 02. Construction GFI power outlets (Temp Pole for Construction) 03. 90 day temporary power
Customer Metering and Services Guide
This document is an uncontrolled copy and may not be the most current copy. The most current copy is available at www.atcoelectric.com. This document is the property of ATCO Electric and may be updated
BERTHOLD ELECTRIC GENERATOR CONNECTION CABINET
BERTHOLD ELECTRIC GENERATOR CONNECTION CABINET Berthold Electric Company s Generator Connection Cabinet provides a quick and convenient station to connect a portable generator to a facility s main service
ELECTRICIAN TRADE REGULATION
Province of Alberta APPRENTICESHIP AND INDUSTRY TRAINING ACT ELECTRICIAN TRADE REGULATION Alberta Regulation 274/2000 With amendments up to and including Alberta Regulation 122/2014 Office Consolidation
ELECTRIC METERING COMMERCIAL & INDUSTRIAL
ELECTRIC METERING COMMERCIAL & 1.0 INDEX 1.0 INDEX 2.0 SCOPE 3.0 GENERAL REQUIREMENTS 4.0 METER LOCATIONS 5.0 UNDERGROUND TERMINATIONS 6.0 METERING TRANSFORMER ENCLOSURES 7.0 SINGLE CUSTOMER METER INSTALLATIONS
UNIVERSITY OF WASHINGTON Facilities Services Design Guide. Electrical. Switchboards. Basis of Design. Design Evaluation
Basis of Design This section applies to the design relating to low voltage switchboards. Design Criteria UW Class N1 facilities main switchboards shall be rear accessible. The main, tie and feeder breakers
RESIDENTIAL ELECTRICAL REQUIREMENTS (REVISED 3/28/2008) PERMIT REQUIREMENTS:
RESIDENTIAL ELECTRICAL REQUIREMENTS (REVISED 3/28/2008) PERMIT REQUIREMENTS: Signed completed Electrical Permit application form. Minnesota law requires all electrical work is to be performed by licensed,
List of Agencies and Organizations to Which Copies of this Document are Sent
Chapter 26: List of Agencies and Organizations to Which Copies of this Document are Sent The following list identifies the agencies and organizations to which a Notice of Availability of the MIS/DEIS is
ARC FLASH CALCULATIONS & LABELING REQUIREMENTS
ARC FLASH CALCULATIONS & LABELING REQUIREMENTS Presented by: Edmund Elizalde EYP Mission Critical Facilities, Inc. Slides by: Lonnie Lindell SKM Systems Analysis, Inc. 1 Agenda NEC 110.16 NFPA 70E IEEE
Grounding & Bonding Why it is done And How to Install Properly
Grounding & Bonding Why it is done And How to Install Properly The technical information provided herein is to assist qualifi ed persons in planning and installing electric service to farms and residences.
ELECTRICAL GUIDELINES FOR SINGLE-FAMILY HOME OWNERS:
ELECTRICAL GUIDELINES FOR SINGLE-FAMILY HOME OWNERS: Chapter 12 of the Burlington Code of ordinances allows owner occupants of single family homes to do their own wiring if they choose. If you choose to
INSTALLATION GUIDELINES for SOLAR PHOTOVOLTAIC SYSTEMS 1
City of Cotati Building Division 201 W. Sierra Ave. Cotati, CA 94931 707 665-3637 Fax 792-4604 INSTALLATION GUIDELINES for SOLAR PHOTOVOLTAIC SYSTEMS 1 Any PV system on a new structures should be included
A. Shop Drawing submittals shall include, but not be limited to, the following:
SECTION 26 05 53 IDENTIFICATION FOR ELECTRICAL SYSTEMS PART 1 - GENERAL 1.1 RELATED DOCUMENTS: A. The Conditions of the Contract and applicable requirements of Divisions 0 and 1 and Section 26 00 01, Electrical
San Diego Area Chapter International Code Council
San Diego Area Chapter International Code Council Code Reference Subject Page 90.7 110.14 110.26 11 0.26(E) (2) Approval of Electrical Equipment Torque Requirements Electrical Equipment Rooms Outdoor dedicated
Fire Alarm System Plans Review Checklist Property location Date of Review
Fire Alarm System Plans Review Checklist Property location Date of Review 1. Is application completed in entirety? 2. Are the plans review fee submitted with the application? 3. Does floor plan include
NYC Department of Education Building Condition Assessment Survey 2014-2015 2014-12-12 08:48AM 2014-12-17 10:39AM. Description Mechanical Room Basement
School: InspectionId Asset Data Inspection Type Building Assessment Survey 204-205 P.S. 86 - BRONX, 2756 RESERVOIR AVENUE, BRONX, NY, 0468 Time In Last Edited 0677 ELECTRICAL 204-2-2 08:48AM 204-2-7 0:39AM
GUIDELINES FOR WIRING SINGLE FAMILY DWELLING UNITS
GUIDELINES FOR WIRING SINGLE FAMILY DWELLING UNITS This guideline has been prepared to assist the owner/occupant of a single family dwelling with compliance to the requirements of the National Electrical
CONSOLIDATED EDISON CO. OF NEW YORK, INC. 4 IRVING PLACE NEW YORK, NY 10003 DISTRIBUTION ENGINEERING DEPARTMENT SUBSTATION & EQUIPMENT SECTION
CONSOLIDATED EDISON CO. OF NEW YORK, INC. 4 IRVING PLACE NEW YORK, NY 10003 DISTRIBUTION ENGINEERING DEPARTMENT SUBSTATION & EQUIPMENT SECTION SPECIFICATION EO-5023 REVISION 3 MARCH 2003 REQUIREMENTS FOR
MTA UNIVERSAL STATION PEDESTRIAN BRIDGE Los Angeles, CA. Project Manual and Specification 100% PE SUBMITTAL TABLE OF CONTENTS
Los Angeles, CA Project Manual and Specification DIVISION 1 GENERAL CONDITIONS 01 01 10 STATEMENT OF WORK 01 11 00 SUMMARY OF THE WORK 01 14 05 METRO (OWNER) - DIRECTED STOPPAGES 01 20 00 PRICE AND PAYMENT
Electrical Code Regulation
Electrical Code Regulation St. Clair County has adopted the 2005 National Electrical Code in its entirety for the unincorporated areas of the county and all communities that have contracted with the county
OPEN ITEMS LIST - CONSTRUCTION Project Name: East Central Middle School - Jackson County CLA#: 11003
OPEN ITEMS LIST - CONSTRUCTION Project Name: East Central Middle School - Jackson County CLA#: 11003 No. Discipline Sent to Name Item Date Noted Date Resolved How item was resolved Electrical Contractor
INSPECTION GUDELINES
GENERAL REQUIREMENTS Building permit and approved set of plans Building permit on the card is the same as on the route "If this is not the first inspection, read inspection records and notes on permit
PREFACE. Your comments or suggestions are welcome and appreciated. They should be sent to:
PREFACE UL developed the Dead-Front Switchboard Marking Guide for code authorities, electric utilities, contractors, installers, users, designers, and other interested parties to aid in understanding deadfront
Residential Electrical Inspection. Checklist
443 Lafayette Road N. St. Paul, Minnesota 55155 www.doli.state.mn.us Residential Electrical Inspection (651) 284-5064 1-800-DIAL-DLI Fax: (651) 284-5743 TTY: (651) 297-4198 Checklist Generally, Minnesota
NYC Build it Back Repair Program
NYC Build it Back Repair Program Registered Contractors Choose Your Own Contractor Option* Last updated 12/1/15 The contractors listed below have registered for the NYC Build it Back Repair Choose Your
Commercial/Industrial Electricity
1 ELC 210 Commercial/Industrial Electricity Course Package Presented and Approved July 31, 2008 2 Contact person(s) DAVE WHITE Date of proposal to JULY 31, 2008 Curriculum Committee NEW COURSE PACKAGE
DESIGN AND CONSTRUCTION STANDARDS SPECIFICATION GUIDELINES 33 70 00
SECTION 33 70 00 - ELECTRICAL DISTRIBUTION CONCRETE ENCASED PRIMARY DUCTBANK SYSTEMS Duct Banks shall be installed by qualified electrical contractors. Provide type EB PVC 5 inch duct equal to Carlon #68716
ELECTRICAL SAFETY Information Bulletin
ELECTRICAL SAFETY Information Bulletin January 2016 CEC-10 [rev-9] Page 1 of 8 CANADIAN ELECTRICAL CODE SUBJECT: Section 10 Grounding and Bonding Rule 10-204 Grounding Connections for Alternating-Current
What are the basic electrical safety issues and remedies in solar photovoltaic installations?
What are the basic electrical safety issues and remedies in solar photovoltaic installations? Presented by: Behzad Eghtesady City of Los Angeles Department of Building and Safety Topics Covered Photovoltaic
Requirements for the Attachment of Communication Cable Facilities on PPL Poles
Page 99 of 137 Requirements for the Attachment of Communication Cable Facilities on Replaces: URS-3002 URS-3004 URS-101C-304 A-157649 Page 100 of 137 Reference Notes for Drawings: General 1. The term communication
New York Building Congress
New York Building Congress November 7, 2013 Frederick E. Smith, P.E. Senior Vice President and Chief Engineer, CPM What is NYCT 228 miles of structure 432 miles of tunnel lighting 722 miles of track (630
Application of Four-Pole Circuit Breakers within Data Centers
Application of Four-Pole Circuit Breakers within Data Centers December 2013/AT324 by Frank Waterer, Fellow Engineer, Schneider Electric Engineering Services Make the most of your energy SM Revision #1
Sub-Bid Contractor Update Statement. Tab A - Invitation for Bids. Tab B - Instructions to Bidders
INTRODUCTORY INFORMATION TABLE OF CONTENTS 00 0101 PROJECT TITLE PAGE PROCUREMENT REQUIREMENTS (PROJECT MANUAL) Tab A - Invitation for Bids Tab B - Instructions to Bidders Tab C Bid Form for General Bids
Submit shop drawings for equipment provided under this section Shop drawings shall indicate:
Section 16435 - SWITCHBOARDS Introduction Part 1 - General Reference The work under this section is subject to requirements of the Contract Documents including the General Conditions, Supplementary Conditions,
2a. IEM Indoor Metal Clad Medium Voltage Switchgear 15KV 16346-1. 2a. Section 16346 INDOOR METAL CLAD MEDIUM VOLTAGE SWTICHGEAR (Std.
2a. IEM Indoor Metal Clad Medium Voltage Switchgear 15KV 16346-1 2a. Section 16346 INDOOR METAL CLAD MEDIUM VOLTAGE SWTICHGEAR (Std. Relays) Part 1 General 1.1 CONDITIONS AND REQUIREMENTS: A. Refer to
NEC 2014 Code Changes
NEC 2014 Code Changes Articles 400-408.55 CHANGES FROM 2011 TO 2014 CODE ARE IN RED Chapter 4 Equipment for General Use ARTICLE 400 Flexible Cords and Cables 400.4 Types Flexible cords and flexible cables
DIVISION 00 - PROCUREMENT AND CONTRACTING REQUIREMENTS
DIVISION 00 - PROCUREMENT AND CONTRACTING REQUIREMENTS NOTICE TO BIDDERS BID FORM INSTRUCTIONS TO BIDDERS CONTRACTOR S BID FOR PUBLIC WORK - FORM 96 MINORITY AND WOMEN S BUSINESS ENTERPRISE PARTICIPATION
Now available on your iphone!
Now available on your iphone! 1 2 3 4 West 53rd Street Columbus Avenue West 64th Str West 77th Street West 76th Street West 75th Street West 74th Street West 73rd Street West 72nd Street West 71st
Hyperlinks are Inactive
Prepared by: NIB/EOB PLANNING GUIDE FOR SINGLE CUSTOMER SUBSTATIONS SERVED FROM TRANSMISSION LINES 05503 Department: Electric T&D Section: T&D Engineering and Technical Support Approved by: G.O. Duru (GOD)
B. Related Sections: 1. Section 26 05 33 - Raceway and Boxes for Electrical Systems.
SECTION 262726 - WIRING DEVICES PART 1 - GENERAL 1.1 SUMMARY A. Section includes wall switches; wall dimmers; receptacles; multioutlet assembly; and device plates and decorative box covers. B. Related
For Sale - $11,000,000 - Negotiable Excellent User Opportunity -
4770 White Plains Road Bronx, New York For Sale - $11,000,000 - Negotiable Excellent User Opportunity - Jerry Houlihan GHP Office Realty One West Red Oak Lane White Plains, New York 10604 Phone: 914.642.9300
PLEASE NOTE. For more information concerning the history of these regulations, please see the Table of Regulations.
PLEASE NOTE This document, prepared by the Legislative Counsel Office, is an office consolidation of this regulation, current to August 1, 2013. It is intended for information and reference purposes only.
How to estimate the cost of installing an Electrical Distribution Center (EDC)
How to estimate the cost of installing an Electrical Distribution Center (EDC) Candidate Number 0112233 June 2012 Table of Contents 1) Introduction 3 2) Types and Methods of Measurement 3 5 3) Specific
MEDIUM VOLTAGE CE-BF SWITCHBOARDS. UP TO 40.5 kv. CE - BF - C - en - REV.00 2012.4
CE - BF - C - en - REV.00 2012.4 APPLICATION CE-BF Switchbords up to 40.5 kv are designed for use in public and industrial distribution system up to 40,5KV for the operation and protection of lines, transformers,
The Service Entrance. Technical Terms Drip loop Insulator Meter Meter enclosure
This sample chapter is for review purposes only. Copyright The Goodheart-Willcox Co., Inc. All rights reserved. 10 The Entrance Objectives Information in this chapter will enable you to: List the components
SEATTLE CITY OF ASSESSMENTS. Northwest Senior Center 5431 32nd Ave NW. Teen Parent Home 339 22nd Ave E
Northwest Senior Center 5431 32nd Ave NW Teen Parent Home 339 22nd Ave E Central Area Motivation Program (CAMP) 722 18th Ave Central Area Senior Center (CASC) 500 30th Ave S South Park Area Redevelopment
Learning Module 13: Panelboards and Switchboards. 101 Basic Series
Learning Module 13: Panelboards and Switchboards 101 Basic Series What You Will Learn We ll step through each of these topics in detail: Introduction 4 Definitions 4 Similarities Between Panelboards and
MONTGOMERY COUNTY EXECUTIVE REGULATION Offices of the County Executive. 101 Monroe Street. Rockville, Maryland 20850
Montgomery County Regulation on: ADOPTION OF THE 2008 NATIONAL ELECTRICAL CODE DEPARTMENT OF PERMITTING SERVICES Issued by County Executive Regulation # 15-09 Authority: Code Section 17-2 and 17-3 Supersedes:
Wentz Concert Hall and Fine Arts Center 171 E. Chicago Avenue Naperville, IL 60540. Existing Electrical Systems Will Lesieutre
Existing Electrical Systems Lighting/Electrical Option Faculty Consultant: T. Dannerth Wentz Concert Hall and Fine Arts Center 171 E. Chicago Avenue Naperville, IL 60540 The following report discusses
PALM BEACH COUNTY AMENDMENTS TO THE NATIONAL ELECTRICAL CODE, 1999 EDITION
PALM BEACH COUNTY AMENDMENTS TO THE NATIONAL ELECTRICAL CODE, 1999 EDITION CODING: Words underlined are additions to the 1999 NEC Words stricken are deletions to the 1999 NEC Adopted by Ordinance 99-73
How does NYC Rapid Repairs work?
NYC Rapid Repairs is a program to make your home safe for return. The City is working with contractors to assess damage to your home from Hurricane Sandy and make the necessary repairs so that you and
ADDENDUM NO. 2 TO PROJECT NO. 43153
ADDENDUM NO. 2 TO PROJECT NO. 43153 CONSTRUCTION WORK, MECHANICAL WORK, PLUMBING WORK, ELECTRICAL WORK PROVIDE VISITOR CENTER BUILDING AND SITE IMPROVEMENTS FIVE RIVERS ENVIRONMENTAL EDUCTION CENTER 56
SECTION.3400 - MECHANICAL: ELECTRICAL: PLUMBING
SECTION.3400 - MECHANICAL: ELECTRICAL: PLUMBING 10A NCAC 13D.3401 HEATING AND AIR CONDITIONING Heating and cooling systems shall meet the American Society of Heating, Refrigerating, and Air Conditioning
26 0533 Raceway and Boxes for Electrical Systems Page 1 of 7
Last Update: November, 2015 A. Conduits: Consultant s Handbook Page 1 of 7 1. All conductors for each and every electrical system shall be installed in a raceway except communications and A/V systems which
Personalized Directory July 8, 2013. Search Criteria. ZIP Code: 11205
Search Criteria Personalized Directory July 8, 2013 Facility Type: Ancillary Facility Distance: Within 25 miles ZIP Code: 11205 Specialty: Our network is always evolving, so once you've chosen the doctor,
Addendum #2 Contract UK-11-13
Addendum #2 Contract UK-11-13 Utilities Kingston Purchase and Replacement of Switchgear at Kingston Hydro Substation MS11 March 25, 2011 Delivered to: All RFP recipients Total number of pages: Nine (9)
How To Plan Out An Array Of Solar Panels
CITY OF DOWNEY COMMUNITY DEVELOPMENT, BUILDING AND SAFETY 11111 Brookshire Avenue Downey, CA 90241 562.904.7142 (www.downeyca.org) B SECTION 01/01/2011 EFFECTIVE DATE PHOTOVOLTAIC 032 FORM NUMBER 2013
QUESTIONS and ANSWERS RFB 745-15-9894, Metal Clad Switchgear and Power Control Room
QUESTIONS and ANSWERS RFB 745-15-9894, Metal Clad Switchgear and Power Control Room 1) When you click on the UTHSCSA Drawing the site takes you to the E-1 drawing no other. Will there be other drawings
TENANT DESIGN MANUAL UPDATED JULY 2015
TENANT DESIGN MANUAL UPDATED JULY 2015 PROJECT OVERVIEW Grapevine Mills is located at the interchange of SR 121 and Grapevine Mills Parkway. It is centrally located just 20 miles northwest of Dallas and