1 Approval Standard for Single-Ply, Polymer-Modified Bitumen Sheet, Built-Up Roof (BUR) and Liquid Applied Roof Assemblies for use in Class 1 and Noncombustible Roof Deck Construction Class Number 4470 June FM Approvals LLC. All rights reserved.
2 Foreword The FM Approvals certification mark is intended to verify that the products and services described will meet stated conditions of performance, safety and quality useful to the ends of property conservation. The purpose of Approval Standards is to present the criteria for FM Approval of various types of products and services, as guidance for FM Approvals personnel, manufacturers, users and authorities having jurisdiction. Products submitted for certification by FM Approvals shall demonstrate that they meet the intent of the Approval Standard, and that quality control in manufacturing shall ensure a consistently uniform and reliable product. Approval Standards strive to be performance-oriented. They are intended to facilitate technological development. For examining equipment, materials and services, Approval Standards: a) must be useful to the ends of property conservation by preventing, limiting or not causing damage under the conditions stated by the Approval listing; and b) must be readily identifiable. Continuance of Approval and listing depends on compliance with the Approval Agreement, satisfactory performance in the field, on successful re-examinations of equipment, materials, and services as appropriate, and on surveillance audits of the manufacturing facility. FM Approvals LLC reserves the right in its sole judgment to change or revise its standards, criteria, methods, or procedures.
3 TABLE OF CONTENTS 1 INTRODUCTION Purpose Scope Basis for Requirements Basis for Approval Basis for Continued Approval Effective Date System of Units Applicable Documents Definitions GENERAL INFORMATION Approval Application Requirements Requirements for Samples for Examination GENERAL REQUIREMENTS Review of Documentation Markings Manufacturer s Installation Instructions Calibration Test Sample Production PERFORMANCE REQUIREMENTS AND TESTS Combustibility From Above the Roof Deck Combustibility From Below the Roof Deck Wind Uplift Resistance Hail Damage Resistance Test Water Leakage Resistance Test Foot Traffic Resistance Test Corrosion Resistance Test Susceptibility to Heat Damage Test NCC (Noncombustible Core) Rated Roof Insulation (optional rating) Dynamic Puncture Resistance Rating of Roof Covers (optional rating) Solar Reflectance of Roof Surfaces (optional) OPERATIONS REQUIREMENTS Demonstrated Quality Control Program Surveillance Audit Program Installation Inspections Manufacturer's Responsibilities APPENDIX A: UNITS OF MEASUREMENT APPENDIX B: FM APPROVALS CERTIFICATION MARKS APPENDIX C: SMALL SCALE TESTS... 25
4 1 INTRODUCTION 1.1 Purpose This standard states Approval requirements for single-ply, polymer-modified bitumen sheet, built-up roof (BUR) and liquid applied roof assemblies Approval criteria may include, but are not limited to, performance requirements, marking requirements, examination of manufacturing facility(ies), audit of quality assurance procedures, and a surveillance program. 1.2 Scope This standard applies to all single-ply, polymer-modified bitumen sheet, built-up roof (BUR) and liquid applied roof assemblies intended to protect the building and its occupancy from the weather elements of nature The performance of a roof assembly depends on all components that make up the assembly, beginning with the deck and its securement to the structure to the uppermost layer exposed to the weather. It is therefore necessary to evaluate the entire roof assembly as a single entity This standard is intended to evaluate only those hazards investigated and is not intended to determine suitability for the end use of a product This standard evaluates single-ply, polymer-modified bitumen sheet, built-up roof (BUR) and liquid applied roof assemblies for their performance in regard to fire from above and below the structural deck, simulated wind uplift, corrosion of metal parts, susceptibility from hail storm damage, foot traffic, puncture resistance (optional), solar reflectance (optional) and water leakage. 1.3 Basis for Requirements The requirements of this standard are based on experience, research and testing and/or the standards of other organizations. The advice of manufacturers, users, trade associations and loss control specialists was also considered Meeting these requirements will qualify a single-ply, polymer-modified bitumen sheet, built-up roof (BUR) or liquid applied roof assembly as FM Approved. An FM Approved roof assembly is not a significant fire hazard and can withstand wind uplift forces, hail stones, etc., when installed in accordance with all Approval requirements. Products which meet all of the requirements identified in this Standard may not be FM Approved if other conditions which adversely affect performance exist or if the intent of this standard is not met. Approval requirements prohibit substitution of components in the roof assembly without prior authorization from FM Approvals Products having characteristics not anticipated by this standard which do not conform to these requirements shall be permitted to be FM Approved if performance equal, or superior, to that required by this Standard is demonstrated, or they meet the intent of this standard. FM Approvals 1
5 1.4 Basis for Approval Approval is based upon (1) satisfactory evaluation of the product when used in a roof assembly and (2) the manufacturer in the following major areas: Examination and tests on production samples to evaluate: the suitability of the component product for use in a roof assembly; the performance of the component product as part of a roof assembly as specified by the manufacturer and required by FM Approvals; and, as far as practical, the durability and reliability of the component product when used as part of a roof assembly An examination of the manufacturing facilities and audit of quality control procedures to evaluate the manufacturer s ability to consistently produce the component product which is examined and tested, and the marking procedures used to identify the product. These examinations may be repeated as part of FM Approvals surveillance audit program. 1.5 Basis for Continued Approval Continued Approval is based upon: production or availability of the component product as FM Approved; the continued use of acceptable quality control procedures; satisfactory field experience; compliance with the terms stipulated in the Approval Report; satisfactory re-examination of production samples for continued conformity to requirements; and satisfactory Surveillance Audits conducted as part of FM Approvals product follow-up program. 1.6 Effective Date The effective date of an Approval Standard mandates that all products tested for Approval after the effective date shall satisfy the requirements of that standard. Products FM Approved under a previous edition shall comply with the new version by the effective date or else forfeit Approval. The effective date shall apply to the entire Approval Standard, or, where so indicated, only to specific paragraphs of the standard The effective date for this standard is December 31, 2012 for compliance with all requirements. 1.7 System of Units Units of measurement used in this Standard are United States (U.S.) customary units. These are followed by their arithmetic equivalents in International System (SI) units, enclosed in parentheses. The first value stated shall be regarded as the requirement. The converted equivalent value may be approximate. Appendix A lists the selected units and conversions to SI units for measures appearing in this standard. Conversion of U.S. customary units is in accordance with Standard for Use of the International System of Units (SI): The Modern Metric System, BSR/IEEE/ASTM SI 10. FM Approvals 2
6 1.8 Applicable Documents The following standards, test methods, and practices are referenced in this standard: AISI (American Iron and Steel Institute) - North American Specification for the Design of Cold-Formed Steel Structural Members, 2007 Edition, AISI S ASTM International (American Society for Testing and Materials) - Standard Method for Determination of Solar Reflectance Near Ambient Temperature Using a Portable Reflectometer, ASTM C Standard Test Method for Heat of Combustion of Liquid Hydrocarbon Fuels by Bomb Calorimeter, ASTM D240 - Standard Test Method for Ash from Petroleum Products, ASTM D482 - Standard Test Method for Tensile Properties of Plastics, ASTM D638 - Standard Test Methods for Coated Fabrics, ASTM D751 -Standard Method for Apparent Density of Rigid Cellular Plastics, ASTM D Standard Test Method for Climbing Drum Peel for Adhesives, ASTM D Standard Test Method for Determining Ignition Temperature of Plastics, ASTM D Heat Of Combustion Of Liquid Hydrocarbon Fuels By Bomb Calorimeter (Precision Method) ASTM D (2005) - Gross Calorific Value Of Coal And Coke, ASTM D Gross Calorific And Ash Value Of Waste Materials, ASTM D Standard Test Method for Static Puncture Resistance of Roofing Membrane Specimens, ASTM D Standard Test Method for Dynamic Puncture Resistance of Roofing Membrane Specimens, ASTM D Standard Test Method for Corrosion Resistance of Ferrous Metal Fastener Assemblies Used in Roofing and Waterproofing, ASTM D Standard Test Method for Determining Water Migration Resistance Through Roof Membranes, ASTM D Fire Tests of Roof Coverings, ASTM E108 - Standard Test Method for Autoignition Temperature of Liquid Chemicals, ASTM E659 - Gross Calorific Value Of Refuse-Derived Fuel By The Bomb Calorimeter, ASTM E711-87(2004) - Standard Test Methods for Measurement of Synthetic Polymer Material Flammability Using a Fire Propagation Apparatus (FPA), ASTM E2058 FM Approvals 3
7 - Standard Practice for Operating Fluorescent Light Apparatus for UV Exposure of Nonmetallic Materials, ASTM G154 DIN (German Institute for Standardization) - Sulfur dioxide corrosion testing in a saturated atmosphere, DIN EN - Test Procedure, EN 13823, Reaction To Fire Tests For Building Products - Building Products Excluding Floorings Exposed To The Thermal Attack By A Single Burning Item EOTA, European Organisation for Technical Approvals - Guideline for European Technical Approval of Systems of Mechanically Fastened Flexible Roof Waterproofing Membranes, ETAG 006, Amended April 2007 FM Approvals - Test Procedure, 12 x 24 ft Wind Uplift Tests for Single Ply and Multi Ply Roof Coverings using Positive Static Pressure - Test Procedure, 12 x 24 ft Wind Uplift Tests for Single Ply and Multi Ply Roof Coverings using Reduced Pressure - Test Procedure, 12 x 24 ft Wind Uplift Tests for Single Ply and Multi Ply Roof Coverings using a Combination of Positive and Reduced Static Pressure - Test Procedure, 5 x 9 ft Wind Uplift Tests for Single Ply and Multi Ply Roof Coverings using Positive Static Pressure - Test Procedure, 5 x 9 ft Wind Uplift Tests for Single Ply and Multi Ply Roof Coverings using Reduced Pressure - Test Procedure, 2 x 2 ft Wind Uplift Test for Fully Adhered Roof Coverings - Test Procedure, Corrosion Resistance Testing For Stress Plates, Batten Bars, and Fasteners Used to Secure Membranes and Insulations in Roof Construction - Test Procedure, Corrosion Resistance Testing For Stress Plates, Batten Bars, and Fasteners Used to Secure Membranes and Insulations in Roof Construction assessed to ETAG 006 in support of CE Marking to CPD - Test Procedure, Test Method for Determining the Susceptibility to Hail Damage of Roof Coverings - Test Procedure, Test Method for Ultraviolet (UV) Weathering of Roof - Test Procedure, 6 x 6 Delamination Tests for Roofing Adhesives and Substrates Using Tensile Loading - Test Procedure, Membrane Delamination Tests for Roofing Membranes and Substrates Using Tensile Loading - Test Procedure, Membrane Peel Tests for Roof Membrane Seam or Cover Tape/Cover Strip Combination using Tensile Loading FM Approvals 4
8 - Test Procedure, Pull Out Tests for Fastener/Roof Deck Combinations and Pull Through Tests for Fastener/Stress Plate or Batten Bar Combinations using Tensile Loading - Test Procedure, Pull Through Tests for Roofing Membranes and Substrates Using Tensile Loading - Test Procedure, Test Method for Determining the Foot Traffic Resistance of Roof Coverings - Test Method for Determining the Susceptibility to Heat Damage of Roof Insulation - Test Procedure, Standard Test Method for Surface Burning Characteristics of Building Materials - Test Procedure, Reaction to Fire Tests - Ignitability of Building Products Subjected to Direct Impingement of Flame - Part 2: Single-Flame Source Test - Test Procedure, Pull Over for Roofing Membranes with Stress Plates Using Tensile Loading - Approval Standard 4451 for Profiled Steel Panels for use as Decking in Class 1 Insulated Roof Construction - Evaluating the Simulated Wind Uplift Resistance of Roof Assemblies Using Static Positive and/or Negative Differential Pressures, American National Standard, ANSI/FM Approvals Approval Standard 4880 for Class 1 Fire Ratings of Insulated Wall or Roof/Ceiling Panels, Interior Finish Materials or Coatings and Exterior Wall System ISO (International Organization for Standardization) - Metallic and other non-organic coatings- sulfur dioxide test with general condensation of moisture, EN ISO 6988: Reaction to Fire Tests for Building Products - Determination of the Heat of Combustion, ISO 1716: Reaction to Fire Tests for Building Products - Non-Combustibility Test, ISO 1182 NFPA (National Fire Protection Association) - Standard Method of Fire Tests for Determining the Heat Release Rate of Roofing Assemblies with Combustible Above-Deck Roofing Components, NFPA Definitions For purposes of this standard, the following terms apply: Adhesive Adhesive is used in roof construction to adhere roof coverings to roof coverings as in lap construction. It is also used to bond roof coverings to the substrate below or to adhere insulation to the substrate. Depending on the use, the adhesive could be in either a liquid form, semi liquid form, reactive liquid form or a solid form as in a tape or as in hot asphalt which is solid until heated. Air Retarder - A layer or layers of material or a laminate used to reduce the flow of air from the building interior into a roof assembly. An air retarder is sealed to the underside of the roof cover at all penetrations and around the entire perimeter of the roof. FM Approvals 5
9 Bitumen - A class of amorphous black or dark colored (solid, semi-solid, or viscous) substances, natural or manufactured, composed principally of high molecular weight hydrocarbons, soluble in carbon disulfide, and found in petroleum asphalts, coal tars and pitches, wood tars and asphalts. Board Stock Insulation - A board stock insulation has a core of, or is comprised of one of the following materials: APA-rated oriented strand board (OSB), asphalt/glass, glass-based, gypsum; mineral wool, perlite, polyisocyanurate/polyurethane foam, expanded polystyrene foam (EPS), extruded polystyrene foam (XPS), wood fiber or other suitable material. The material, the number of board stock layers, and the position of the product within an assembly will determine whether it is classified as an insulation, cover board or thermal barrier. Built-Up Roof - A built-up roof (BUR) is a continuous semi-flexible roof membrane consisting of multiple plies of saturated felts, coated felts, fabrics, or mats assembled in place with alternate layers of bitumen or cold adhesive. Cementitious Wood Fiber Roof Deck - A factory fabricated roof deck consisting of wood fibers and cementitious binder. It is supplied in a 2 in. (50 mm) minimum thickness with tongue and groove side and end joints. Cover Board - A board stock product used over insulation. It is applied as the top layer of some multilayer insulation assemblies. Crack During wind uplift testing, when an insulation is stressed to the point that it separates from itself while continuing to maintain the applied uplift pressure without catastrophic failure of the test assembly. Crease - During wind uplift testing, when insulation is stressed to the point that it bends at a sharp, defined angle, without breaking. Often a crack will form on the opposite face of the insulation board Deck - The deck is one of the structural components of the roof assembly to which the roof system may be secured. Delamination - Separation of the plies in a roof membrane or system in any laminated roofing material or component, e.g., laminated layers of rigid insulation or the felt plies in a built-up roof or separation of any membrane from the substrate to which it is adhered. Fasteners - A fastener is a mechanical securement device used alone or in combination with a stress distributor to secure various components of a roof assembly. Fully Adhered - Fully adhered describes roof coverings that have been bonded to the substrate using a compatible adhesive throughout the entire surface of the roof. Gypsum Roof Deck - Gypsum roof decks consist of a slurry of gypsum cement placed over steel reinforcing mesh and permanent form boards. Heat Weld - Heat welding is a method of melting and fusing together the overlapping edges of separate sheets or sections of polymer modified bitumen, thermoplastics, or some uncured thermoset roofing membranes by the application of heat and pressure. Insulation - Insulation is any of a variety of materials designed to reduce the flow of heat, either from, or into, a building. Lightweight Insulating Concrete Insulation - A type of insulation comprised of portland cement, lightweight aggregate or preformed foam or hybrid combination of these. It may be applied with or without the use of expanded polystyrene (EPS) board encapsulated within the lightweight insulating concrete. FM Approvals 6
10 Liquid Applied Roof Cover - Liquid applied roof coverings arrive on the roof in a liquid state and are spray, brush or roller applied using proprietary procedures and could include a reinforcing fabric. Mechanically Fastened - Mechanically fastened describes roof covers or base sheets that have been attached to the substrate, deck or structure at defined intervals using fasteners with or without stress distributors. Minor delamination In wind uplift testing, an area approximately 1% of the test sample. For a 12 x 24 ft (3.7 x 7.3 m) test an area of 3 ft 2 (0.28 m 2 ); for a 5 x 9 ft (1.5 x 2.7 m) test an area of 0.5 ft 2 (0.05 m 2 ), whereby two adhered components which are intended to be in contact are not in contact. Multi-Ply Roof Cover - A roof cover consisting of zero or one base ply layer, zero to many plies and zero or one cap ply layer adhered to each other with an adhesive and together form a thick multi-layer weatherproof roof covering. For assemblies with base sheets (mechanically attached), the base sheet is not included when defining the number of plies of the roof cover. Multi-ply covers contain a minimum of two plies. Noncombustible The property of a material to not ignite or burn. Not capable of igniting and burning under the conditions described in Section 4.9. Partially Adhered - Roof coverings that have been bonded to the substrate using a compatible adhesive applied in spots or ribbons across the surface of the roof. Presecurement - The use of insulation with certain mechanically fastened single ply roof covers requires preliminary attachment of the insulation to the deck. The proper securement procedure using mechanical fasteners (fastener/plate combination used for roofing) requires a minimum of two (2) FM Approved fasteners per board for insulations having any one dimension no greater than 48 in. (1220 mm) and a minimum of four (4) fasteners for insulation boards having any one dimension greater than 48 in. (1220 mm). Installations which require preliminary fastening are referenced in the applicable roof cover assembly. Recover - New roof components are installed over the existing roof cover. Re-Roof - Stripping off the existing roof system of all membranes, insulations, fasteners, etc., down to bare roof deck. For steel deck re-roof, up to 15 lbs/sq ft (0.72 kg/sq m) of asphalt can remain on the deck. Rigid Cover Board A hard, dense board, which, in the sole judgment of FM Approvals and through testing, has demonstrated the ability to act in a composite manner with the steel deck to increase the Moment of Inertia and the Section Modulus and thus the wind uplift capacity of the roof assembly. In this case, the board must be used over minimum 1.5 in. (38 mm) thick insulation and secured to the deck, either alone or in combination with the roof cover, using fasteners placed within a contributory area of less than or equal to 1 ft 2 (0.09 m 2 ) per fastener. Roof Assembly - A system of interacting roof components (including the roof deck) designed to weatherproof and, normally, to insulate a building's top surface. Roof Cover - The layer of a roof assembly designed to protect the building components from the weather. Roof System - A system of interacting roof components (not including the roof deck) designed to weatherproof and, normally, to insulate a building's top surface. Service Wind Load The uplift load resulting from a windstorm that a roof assembly must resist. The service load is equal to one half of the rated load in psf (kpa). Single Ply Roof Cover - Factory produced single ply roof covers consist of sheets of EPDM, PVC, TPO, CSPE or several variations of these. Modified bitumen covers applied in a single layer (no base or ply sheets) are considered single ply roof covers. FM Approvals 7
11 Solar Reflectance The fraction of incident solar radiation upon a surface that is reflected from the surface. Spray Foam Insulation - The field applied spray foam insulation systems consist of multiple components delivered to the job site where they are mixed and sprayed in place prior to applying the roof cover. Steel Roof Deck Corrugated metal used as a structural component to support a roof system. Stress Distributor (Plate/Batten Bar) - A stress distributor (plate/batten bar) is a metal or plastic disk or bar which is used in conjunction with a fastener to secure roof components and designed to distribute a concentrated load over a larger surface area. Structural Concrete Roof Deck - Structural concrete decks are generally monolithic, cast in place decks or precast concrete plank. These decks have a minimum compressive strength of 2500 psi (17.2 mpa) and a density of approximately 150 lb/ft 3 (2400 kg/m 3 ). Roof assemblies on structural concrete are considered noncombustible. Structure - The structure is the building framework to which the roof deck, or in some instances the roof cover, is fastened. Surfacing - Surfacing is the top layer or layers of a roof assembly, specified or designed to protect the underlying roofing from direct exposure to the weather. Thermoplastic - Polymers which soften when heated and harden when cooled. This process is repetitive provided the material is not heated above the point at which decomposition occurs. Thermoset - A material that solidifies or sets irreversibly when heated. This property is usually associated with cross linking of the molecules induced by heat, chemical reaction or radiation. Treated Wood Roof Deck - Impregnated fire-retardant treated lumber or plywood. The deck thickness must be a minimum nominal 2 in. (50 mm) for lumber and 3/4 in. (19 mm) for plywood. Lumber shall be tongue-andgroove or splined together at side joints. Plywood must be exterior glue grade and contain tongue-and-groove or shiplap longitudinal edges. Thermal Barrier - A board stock insulation placed on the roof deck to slow the temperature rise to the roof system during an interior building fire and to delay involvement of the roof system in the fire. Vapor Retarder - A layer or layers of material or a laminate used to reduce the flow of water vapor into a roof assembly. A vapor retarder is not sealed to the underside of the roof cover. Weld - A weld is a type of securement whereby metal or plastic products are joined together through heat or solvent fusion. Wind Uplift - Wind uplift is the force generated by wind on a roof system or components in a roof system resulting from wind-induced pressure. 2 GENERAL INFORMATION Roof assemblies are constructed on site. They consist of several component layers beginning with a structural deck and ending with a weathering surface. Component layers that may be found in a roof assembly are: FM Approvals 8
12 coating or surfacing, roof covering, cover board, insulation, air or vapor retarder, thermal barrier and structural decking. Securements are used to hold the various components together and generally consist of a combination of adhesives, welds and/or mechanical fasteners. 2.1 Approval Application Requirements To apply for Approval the manufacturer, or its authorized representative, should submit a request to: Materials Director FM Approvals 1151 Boston-Providence Turnpike PO Box 9102 Norwood, MA U.S.A. The manufacturer shall provide the following preliminary information with any request for Approval consideration: A complete list of all roof assembly combinations being submitted for Approval consideration. The components that make up each roof assembly. These components include a roof covering, structural deck and one or more of the following: coating or surfacing, cover board, insulation, air or vapor retarder and thermal barrier and the method of securing all components for each separate assembly. Essentially, all components in the finished roof assembly shall be identified by manufacturer, product trade name, method of installation and the ratings desired for each combination. All ratings which are desired, or expected, for each assembly include: ASTM E108 class A, B, or C with maximum roof slope; Wind Uplift rating, Class 1-60, 1-75, etc. Hail Damage Rating, MH or SH; NCC (Noncombustible Core) Rated Roof Insulation (optional); Dynamic Puncture Resistance Rating (optional) Solar Reflectance of Roof Surfaces (optional) The number and location of manufacturing facilities. All documents shall contain the manufacturer's name, document number or other form of reference, title, date of last revision and revision level. All documents shall be provided with English translation. 2.2 Requirements for Samples for Examination Following authorization of an Approval examination, the manufacturer may be required to submit samples for examination and testing based on the Approvals requested. Sample requirements will be determined by FM Approvals following review of the preliminary information Requirements for samples may vary depending on design features, results of prior or similar testing and results of any foregoing tests The manufacturer shall submit samples representative of production. Any decision to use test data generated using prototypes is at the sole discretion of FM Approvals. FM Approvals 9
13 2.2.4 It is the manufacturer's responsibility to provide any necessary test fixtures or special tools, such as those which may be required to evaluate the products for Approval. 3 GENERAL REQUIREMENTS 3.1 Review of Documentation During the initial investigation and prior to physical testing, the manufacturer's specifications and roof assembly details shall be reviewed to assess the ease and practicality of installation and use. Each roof component shall be capable of being used within the limits of the Approval investigation. 3.2 Markings Marking on the product or, if not possible due to size, on its packaging or label accompanying the product, shall include the following information: name and address of the manufacturer or marking traceable to the manufacturer; date of manufacture or code traceable to date of manufacture or lot identification; model number, model type and/or product trade name as appropriate. When hazard warnings are needed, the markings shall be universally recognizable The product trade name, model number or model type identification shall correspond with RoofNav, the manufacturer's catalog designation and shall uniquely identify the product as FM Approved. The manufacturer shall not place this trade name or model number identification on any other product unless covered by a separate agreement with FM Approvals The Approval Mark (see Appendix B) shall be displayed visibly and permanently on the product and/or packaging as appropriate. The manufacturer shall not use this Mark on any other product unless such product is covered by a separate FM Approvals Approval Report All markings shall be legible and durable. 3.3 Manufacturer s Installation Instructions The manufacturer shall provide the user with printed instructions to demonstrate proper installation procedures to be followed by installers. As part of the approval examination, and at the sole discretion of FM Approvals, at least one inspection of the field installation during and/or after completion shall be required. In some cases, a continued program of inspections shall be necessary to assess the application procedures or changes within the application techniques. 3.4 Calibration All examinations and tests performed in evaluation to this Standard shall use calibrated measuring instruments traceable and certified to acceptable national standards. FM Approvals 10
14 3.5 Test Sample Production All products submitted for testing shall be representative of production run material. The need to monitor the manufacture of the test specimens shall be at the sole discretion of FM Approvals. 4 PERFORMANCE REQUIREMENTS AND TESTS - This standard is intended to evaluate a finished roof assembly for its performance as it relates to fire (from above and below the structural deck), simulated wind uplift, corrosion of metal parts, susceptibility from hail storm damage, foot traffic, puncture resistance and water leakage. - Tests of alternate constructions may be waived if considered less hazardous than those previously tested. - Screening tests may be used to identify critical components for use in full scale testing or to evaluate components as alternate to those already tested and found to be satisfactory via the full scale tests described in Sections 4.1 through 4.11 below. Alternate components must perform to an equal or higher level than the component qualified via large scale testing. Refer to the Appendix C of this Standard for acceptable screening tests. If the nature of a product requires the use of a test not shown in Appendix C, the test may be used at the sole discretion of FM Approvals. - Confirming tests may be required, at the sole discretion of FM Approvals, depending on design features and results of any foregoing tests. - Following a test failure, a re-test of an identical or similar assembly shall be at the sole discretion of FM Approvals and with a technical justification of the conditions or reasons for the failure. When a test specimen fails to meet the Approval acceptance criteria for a given classification/rating, two successful test specimens of the same or similar construction must meet the Approval acceptance criteria to qualify for the given classification/rating. For each failed specimen, two successful test specimens are required. Any test specimen that fails more than three times is no longer considered a candidate for FM Approval. - Prior to testing, roof assemblies shall be permitted to cure for a maximum period of 28 days. 4.1 Combustibility From Above the Roof Deck Testing for combustibility from above the roof deck shall be in accordance with Fire Tests of Roof Coverings, ASTM E108, ASTM International. The tests shall include spread of flame, intermittent flame and burning brand as applicable Conditions of Acceptance for Combustibility from Above the Roof Deck Spread of Flame test: - For Class A, the maximum flame spread of the sample materials shall not exceed 72 in. (1830 mm). - For Class B, the maximum flame spread of the sample materials shall not exceed 96 in. (2440 mm). - For Class C, the maximum flame spread of the sample materials shall not exceed 156 in. (3960 mm). FM Approvals 11
15 - There shall be no excessive lateral flame spread which is defined as flames extending to the two lateral edges of the exposed roof covering or coating beyond 12 in. (305 mm) from the ignition source. - There shall be no portion of the roof covering material blown or falling off of the test deck in the form of flaming or glowing brands that continue to glow after reaching the floor. - There shall be no portion of the roof deck that fall in the form of particles that continue to glow after reaching the floor Intermittent Spread of Flame and Burning Brand tests for Classes A, B, or C - There shall be no portion of the roof covering material blown or falling off of the test deck in the form of flaming or glowing brands that continue to glow after reaching the floor. - There shall be no exposure of the deck or sustained flaming on the underside of the deck. - There shall be no portion of the roof deck that fall in the form of particles that continue to glow after reaching the floor. 4.2 Combustibility From Below the Roof Deck Testing for combustibility from below the roof deck shall be in accordance with Standard Method of Fire Tests for Determining the Heat Release Rate of Roofing Assemblies with Combustible Above-Deck Roofing Components, NFPA 276 or in accordance with Approval Standard for Class 1 Fire Ratings of Insulated Wall or Roof/Ceiling Panels, Interior Finish Materials or Coatings and Exterior Wall System, FM Standard Conditions of Acceptance for Combustibility from Below the Roof Deck The roof assembly, when subjected to the NFPA 276 test, shall not exhibit fuel contribution rates in excess of the values shown in the following table There shall be no dropping of flaming particles into the furnace or uncontrolled flaming on the exterior surface of the sample The roof assembly, when evaluated in accordance with Approval Standard for Class 1 Fire Ratings of Insulated Wall or Roof/Ceiling Panels, Interior Finish Materials or Coatings and Exterior Wall System, FM Standard 4880 shall meet the fire performance requirements of FM Standard Wind Uplift Resistance Time Interval Maximum Fuel Contribution Rate min Btu/ft 2 /min (kw/m 2 ) (77.6) (73.8) (68.1) Avg. (30 min) 285 (54.0) Testing for wind uplift resistance shall be in accordance with ANSI/FM Approvals 4474, Evaluating the Simulated Wind Uplift Resistance of Roof Assemblies Using Static Positive and/or Negative Differential Pressures. The tests shall include the 12 x 24 ft (3.7 x 7.3 m) simulated wind uplift pressure test, the 5 x 9 ft (1.5 x 2.7 m) simulated wind uplift pressure test or the simulated wind uplift pull test. The minimum rating required for FM Approval is Class The maximum rating available is Class Ratings between 1-60 and are available in increments of 15. The rating assigned to the assembly shall be the maximum simulated uplift resistance pressure which the assembly maintains for one (1) minute without failure. In FM Approvals 12
16 addition, the assembly must maintain the service wind load for one (1) minute without visible cracking or visible creasing of the insulation or cover board. Multiple cracks or creases in the same insulation or cover board, which would impair performance is indicative of catastrophic failure, shall not be permitted. Crack or crease length in the same insulation or cover board, in excess of one half the minimum board dimension; e.g., 24 in. (1220 mm) for a 48 x 96 in. (1220 x 2440 mm) board shall not be permitted x 24 ft (3.7 x 7.3 m) Simulated Wind Uplift Pressure Test The 12 x 24 ft (3.7 x 7.3 m) simulated wind uplift pressure test procedure is used to determine the simulated wind uplift resistance of the following types of roof assemblies: 1) Assemblies other than those evaluated via the uplift pull test or 5 x 9 ft uplift pressure test. 2) Assemblies that utilize mechanical fasteners, adhesives, hot asphalt, heat welding, self adhesive components or combination thereof, to secure insulations, a base ply, plies or a cap ply sheet, exterior coverings and other components, in single or multi-layered constructions, to one another and to the roof deck. Note: Adhesive and hot asphalt securement to steel roof deck is not permitted. 3) Assemblies that utilize steel, FR treated wood, structural concrete, cementitious wood fiber or gypsum roof decks having a minimum thickness of 2 in. (51 mm). 4) Assemblies that utilize batten bars or rows of fasteners spaced less than or equal to 144 in. (3660 mm) on center with maximum in-row securement spacing of 48 in. (1220 mm). 5) Assemblies that utilize an air retarder. For wind ratings of Class 1-90 and below, the assembly must also meet the service load (half of the rated load) without the air barrier in place. For wind ratings above Class 1-90, the assembly must perform to the rated level with and without the air barrier in place. 6) Assemblies that do not overstress the structural deck when subjected to service wind loads. Stresses induced to steel roof decking shall be determined by rational analysis using Allowable Strength Design (ASD) principles and shall not exceed the allowable stresses per the North American Specification for the Design of Cold-Formed Steel Structural Members, AISI S and Approval Standard for Profiled Steel Panels for use as Decking in Class 1 Insulated Roof Construction, FM Standard ) The test sponsor shall supply calculations used to determine the stresses Conditions of Acceptance for 12 x 24 Simulated Wind Uplift Pressure Test All fasteners and stress distributors shall: a) remain securely embedded into, or through, the roof deck and other structural substrates to which they are being fastened to or through; b) not pull through, become dislodged, disconnected or disengaged from stress distributors, seams or substrates; c) not fracture, separate or break All insulations and cover boards shall: a) not fracture, break or pull through, or over, fastener heads or stress distributors; b) not delaminate or separate from their facers or adjacent components to which they have FM Approvals 13
17 been adhered; c) be permitted to deflect between points of mechanical securement provided that the insulation boards do not fracture, crack or break. EXCEPTIONS: Visible cracking or visible creasing of the insulation or cover board, as indicated by the top surface of the roof cover, when less than or equal to one half the minimum board dimension, shall be permitted provided ultimate failure does not occur as noted in Section All membranes shall: a) not tear, puncture, fracture or develop any through openings; b) not delaminate or separate from adjacent components. EXCEPTIONS: 1) Mechanically fastened membranes shall be permitted to separate and deflect from adjacent components at locations where they are not fastened, 2) partially adhered membranes shall be permitted to separate and deflect from adjacent components at locations where adhesive placement was not intended, 3) tearing of membrane at fastener/stress distributors is allowed up to ultimate failure, 4) minor delamination is allowed provided it does not continue to grow in size by more than 50% from the end of one pressure level through the end of the following pressure level All adhesives shall maintain full contact with all the surfaces of all components to which it has been applied to, or comes in contact with, without any separation, delamination, fracture, cracking or peeling of the adhesive or its bond. EXCEPTION: Minor delamination is allowed provided it does not continue to grow in size by more than 50% from the end of one pressure level through the end of the following pressure level All roof decks shall: a) maintain their structural integrity during the entire classification period; b) not fracture, split, crack, permanently deform or allow for fastener withdrawal Stresses induced to steel roof decking shall be determined by rational analysis, supplied by the test sponsor, and shall not exceed the allowable stresses per the North American Specification for the Design of Cold-Formed Steel Structural Members, AISI S and Approval Standard for Profiled Steel Panels for use as Decking in Class 1 Insulated Roof Construction, FM Standard Exception: For reroof over steel deck, rigid cover boards may be used to stiffen existing decks which do not meet wind design pressures. When a rigid cover board is used, the allowable bending stress of the deck shall be permitted to be increased by 40% All other components, including seams, base sheets, base plies, plies and cap plies, shall not tear, puncture, fracture, disengage, dislodge, disconnect, delaminate or develop any through openings The theoretical load per fastener (pressure x contributory area) does not exceed the pullout resistance of the fastener per Section C x 9 ft (1.5 x 2.7 m) Simulated Wind Uplift Pressure Test The 5 x 9 ft (1.5 x 2.7 m) simulated wind uplift pressure test procedure is used to determine the simulated wind uplift resistance of the following types of roof assemblies with a maximum wind uplift rating of Class 1-90: 1) Assemblies that utilize mechanical fasteners, adhesives, hot asphalt, heat welding, self adhesive components or combination thereof, to secure insulations, a base ply, plies or a cap ply sheet, exterior coverings and other components, in single or multi-layered constructions, to one another and to the roof deck. Note: Adhesive and hot asphalt securement to steel roof deck is not permitted. 2) Assemblies that utilize air pervious decks to include cementitious wood fiber, steel, wood or fiber reinforced plastic roof decks. FM Approvals 14
18 3) Assemblies with mechanically secured roof covers with securement row spacing less than, or equal to, 48 in. (1220 mm) on center with maximum in-row securement spacing of 24 in. (610 mm). 4) Assemblies with mechanically secured roof covers with securements (spot or grid affixed) spacing less than, or equal to, 24 x 48 in. (610 x 1220 mm) on center. 5) Assemblies with mechanically secured insulation (maximum 48 x 96 in. (1220 x 2440 mm) board) with a maximum contributory securement area of 5.33 ft² (0.50 m²) per fastener, e.g. 6 fasteners on a 48 x 96 in. (1220 x 2440 mm) board size Conditions of Acceptance for 5 x 9 Simulated Wind Uplift Pressure Test All fasteners and stress distributors shall: a) remain securely embedded into, or through, roof decks and other structural substrates to which they are being fastened to or through; b) not pull through, become dislodged, disconnected or disengaged from distributors, seams or substrates; c) not fracture, separate or break All insulations and cover boards shall: a) not fracture, break or pull through, or over, fastener heads or distributors; b) not delaminate or separate from their facers or adjacent components to which they have been adhered; c) be permitted to deflect between points of mechanical securement provided that the insulation boards do not fracture, crack or break. EXCEPTIONS: Visible cracking or visible creasing of the insulation or cover board, as indicated by the top surface of the roof cover, when less than or equal to one half the minimum board dimension, shall be permitted provided ultimate failure does not occur as noted in Section All membranes shall: a) not tear, puncture, fracture or develop any through openings; b) not delaminate or separate from adjacent components. EXCEPTIONS: 1) Mechanically fastened membranes shall be permitted to separate and deflect from adjacent components at locations where they are not fastened, 2) partially adhered membranes shall be permitted to separate and deflect from adjacent components at locations where adhesive placement was not intended, 3) tearing of membrane at fastener/stress distributor is allowed up to ultimate failure, 4) minor delamination is allowed provided it does not continue to grow in size by more than 50% from the end of one pressure level through the end of the following pressure level All adhesives shall maintain full contact with all the surfaces of all components to which it has been applied to, or comes in contact with, without any separation, delamination, fracture, cracking or peeling of the adhesive or its bond. EXCEPTION: minor delamination is allowed provided it does not continue to grow in size by more than 50% from the end of one pressure level through the end of the following pressure level All roof decks shall: a) maintain their structural integrity during the entire classification period; b) not fracture, split, crack or allow for fastener withdrawal Stresses induced to steel roof decking shall be determined by rational analysis, supplied by the test sponsor, and shall not exceed the allowable stresses per the North American Specification for the Design of Cold Formed Steel Structural Members, AISI S and Approval Standard for Profiled Steel Panels for use as Decking in Class 1 Insulated Roof Construction, FM Standard All other components, including seams, base sheets, base plies, plies and cap plies, shall not tear, puncture, fracture, disengage, dislodge, disconnect, delaminate or develop any through openings. FM Approvals 15
19 The theoretical load per fastener (pressure x contributory area) does not exceed the pullout resistance of the fastener per Section C Simulated Wind Uplift Pull Test The simulated wind uplift pull test procedure is used to determine the simulated wind uplift resistance of the following types of roof assemblies: 1) Assemblies with components (cover board, insulation, vapor retarder) either partially or fully adhered to monolithic structural concrete roof decks or gypsum or lightweight concrete cast over monolithic structural concrete. When substrates are partially adhered in ribbons, the adhesive is applied in rows spaced less than, or equal to, 12 in. (305 mm) on center. 2) Assemblies where the single ply roof cover is fully adhered to a cover board, insulation or deck. 3) Assemblies where the multi ply roof cover is partially adhered to a cover board, insulation or deck. When partially adhered in ribbons, the adhesive is applied in rows spaced less than, or equal to, 12 in. (305 mm) on center. 4) Assemblies with a base sheet partially adhered to an insulation or deck and with a rigid insulation adhered above the base sheet. 5) Assemblies with a maximum rigid insulation board size of 48 x 48 in. (1220 x 1220 mm). EXCEPTION: Boards with thicknesses less than or equal to in. (16 mm) and with sufficient flexibility so they will lay flat, without curling or bending toensure complete adhesion can be up to 48 x 96 in. (1220 x 2440 mm). Note: For assemblies with all components fully adhered, the final rating for the assembly is determined by dividing the maximum pressure load maintained for 60 seconds by 0.85 and rounding down to the next increment of 15 psf (0.7 kpa) up to a maximum rating of Conditions of Acceptance for Simulated Wind Uplift Pull Test All insulations shall 1) not fracture or break; 2) not delaminate or separate from their facers or adjacent components to which they have been adhered All membranes shall not delaminate or separate from adjacent components All adhesive shall maintain full contact between all the surfaces of all components to which it has been applied to, or comes in contact with, without any separation, delamination, fracture, cracking or peeling of the adhesive or its bond All other components, including seams, base sheets, base plies, plies and cap plies, shall not tear, puncture, fracture, disengage, dislodge, disconnect, delaminate or develop any through openings. 4.4 Hail Damage Resistance Test Testing for hail damage resistance shall be in accordance with Test Procedure, Test Method for Determining the Susceptibility to Hail Damage of Roof Coverings, FM Approvals, LLC. The minimum rating required for Approval is Class 1-MH. FM Approvals 16
20 4.4.1 Conditions of Acceptance for Hail Damage Resistance Both unconditioned (unweathered) and conditioned (weathered) samples of roof cover are inspected for damage. Neither the roof cover nor the field seam (if present) shall show any signs of cracking or splitting. The field seam shall not show any signs of cracking, splitting, separation, or rupture when examined closely under 10X magnification. Under adhered conditions, minor separation of the roof cover from the substrate (directly under the impact area) is acceptable for monolithic decks only (i.e. structural concrete or gypsum) or lightweight insulating concrete insulation. 4.5 Water Leakage Resistance Test Testing for water leakage resistance shall be in accordance with Standard Test Method for Determining Water Migration Resistance Through Roof Membranes, ASTM D7281, ASTM International Conditions of Acceptance for Water Leakage Resistance There shall be no signs of water leakage during the 7 day period. In addition, there shall be no signs of water leakage during, or after, the pressure cycles. 4.6 Foot Traffic Resistance Test Testing for foot traffic resistance shall be in accordance with Test Procedure, Test Method for Determining the Foot Traffic Resistance of Roof Coverings and Insulation, FM Approvals, LLC Conditions of Acceptance for Foot Traffic Resistance Roof Cover - There shall be no sign of tearing or cracking of the protective cover causing exposure of the plastic, glass fibers, foam or other compressible core material. Insulation - The top surface of the roof insulation shall resist puncture. Under this same loading the roof insulation shall not fracture over rib openings when the deck conforms to Approved gauge-span limits. 4.7 Corrosion Resistance Test Testing for corrosion resistance shall be in accordance with Standard Test Method for Corrosion Resistance of Ferrous Metal Fastener Assemblies Used in Roofing and Waterproofing, ASTM D6294, ASTM International or Guideline for European Technical Approval of Systems of Mechanically Fastened Flexible Roof Waterproofing Membranes, ETAG 006, Amended April 2007, EOTA, European Organisation for Technical Approvals Conditions of Acceptance for Corrosion Resistance Through visual inspection, the amount of red rust is determined. Staining is not considered red rust. A sample passes the corrosion test when no specimen has a corrosion area of greater than 15%. Any sign of coating blistering, peeling, or cracking is cause for failure. 1) For threaded fasteners, the measure of rust is based on the fastener area above the substrate through which the threads are driven. FM Approvals 17
21 2) For hammered fasteners, the measure of rust is based on the fastener area above the substrate into which the fastener is hammered. It excludes the portion impacted by the hammering device. 3) For stress plates, the measure of rust is based on the top and bottom surfaces. It excludes 1/16 in. (1.6 mm) inward from the outside perimeter of the top and bottom surfaces and 1/32 in. (0.8 mm) concentrically outward from the perimeter edge of the center hole on the top and bottom surface. 4) For batten bars, the measure of rust is based on the top and bottom surfaces. It excludes 1/16 in. (1.6 mm) inward from the outside perimeter of the top and bottom surfaces and 1/32 in. (0.8 mm) concentrically outward from the perimeter edge of all holes on the top and bottom surface. 4.8 Susceptibility to Heat Damage Test The susceptibility to heat damage test procedure is used to assess the damage to roof insulation from exposure to radiant heat as a result of an interior building fire. Susceptibility to heat damage testing is for insulations applied directly to decks other than concrete. Testing for susceptibility to heat damage shall be in accordance with Test Method for Determining the Susceptibility to Heat Damage of Roof Insulation, FM Approvals, LLC Conditions of Acceptance for Susceptibility to Heat Damage The insulation shall not be decomposed, discolored or otherwise damaged beyond a depth of 1 8 in. (3 mm). There shall also be no curling or bowing of the sample. 4.9 NCC (Noncombustible Core) Rated Roof Insulation (optional rating) Homogeneous and non-homogeneous roof insulation may be rated as NCC (noncombustible core) when it meets the requirements shown below. Individual layers of non-homogeneous insulation boards must meet the requirements shown below when the layer thickness is greater than or equal to 0.10 in. (2.5 mm) Testing for Noncombustible Core Rated Roof Insulation shall be permitted to be in accordance with Test Procedure, ASTM E2058, Measurement of Synthetic Polymer Material Flammability Using a Fire Propagation Apparatus (FPA), FM Approvals, LLC and with Test Procedure, ISO 1716, Reaction-to-Fire Tests for Building Products - Determination of the Heat of Combustion, FM Approvals, LLC and ASTM D482, Standard Test Method for Ash from Petroleum Products Conditions of Acceptance for NCC (Noncombustible Core) Rated Roof Insulation Per ASTM D482, Standard Test Method for Ash from Petroleum Products, the samples shall have a minimum content of 90% ash. When a single test produces a result of less than 90%, two (2) additional tests shall be permitted to be conducted. The results of all three (3) tests shall be averaged. When averaged, the result shall not be less than 90% ash. Per ASTM E2058, Standard Test Methods for Measurement of Synthetic Polymer Material Flammability Using a Fire Propagation Apparatus (FPA), when tested at an applied heat flux of 50 kw/m 2 in air enriched to 40% oxygen.. No visible flaming of the insulation core material (without adhesive or facers) shall occur during the entire test. The test shall be terminated at 15 minutes if the mass loss from the sample has ceased and/or if visible vapors (if present) have ceased to be generated. If, at 15 minutes, the sample still exhibits mass loss and/or visible vapors, the test shall continue until the mass loss and/or visible vapors cease. Testing shall be in accordance with Test Procedure, ASTM E2058, Measurement of Synthetic Polymer Material Flammability Using a Fire Propagation Apparatus (FPA). FM Approvals 18
22 Per ISO 1716:2002, Reaction to Fire Tests for Building Products - Determination of the Heat of Combustion, the insulation core shall have a maximum heat of combustion of 2.0 kj/g (860 BTU/lb). When a single test produces a result of greater than 2.0 kj/g (860 BTU/lb), two (2) additional tests shall be permitted to be conducted. The results of all three (3) tests shall be averaged. When averaged, the result shall be less than 2.0 kj/g (860 BTU/lb). Testing shall be in accordance with Test Procedure, ISO 1716, Reaction-to-Fire Tests for Building Products - Determination of the Heat of Combustion, FM Approvals, LLC Dynamic Puncture Resistance Rating of Roof Covers (optional rating) Testing for the Dynamic Puncture Resistance Rating of Roof Covers shall be permitted to be in accordance with ASTM D5635, Standard Test Method for Dynamic Puncture Resistance of Roofing Membrane Specimens Ratings for the Dynamic Puncture Resistance Rating of Roof Covers The energy rating for the Dynamic Puncture Resistance Rating of Roof Covers shall be the maximum energy attained for which three successive test specimens do not puncture when tested in accordance with ASTM D5635, Standard Test Method for Dynamic Puncture Resistance of Roofing Membrane Specimens. The Dynamic Puncture Resistance Ratings available are shown as 5 J (Joule) through 50 J (Joule) in the following table: Test Mass [lbm / kg] Rating Test Mass [lbm / kg] Rating Not Rated NR 12.1 / J 2.2 / J 13.2 / J 3.3 / J 14.3 / J 4.4 / J 15.4 / J 5.5 / J 16.5 / J 6.6 / J 17.6 / J 7.7 / J 18.7 / J 8.8 / J 19.8 / J 9.9 / J 20.9 / J 11.0 / J 22.0 / J 4.11 Solar Reflectance of Roof Surfaces (optional) Testing for the Solar Reflectance of Roof Surfaces shall be permitted to be in accordance with ASTM C1549, Standard Method for Determination of Solar Reflectance Near Ambient Temperature Using a Portable Reflectometer Results for Solar Reflectance of Roof Surfaces The measured solar reflectances, arithmetic average of the measured reflectances, and if appropriate, the standard deviation of the set of measurements will be reported when tested in accordance with ASTM C1549, Standard Method for Determination of Solar Reflectance Near Ambient Temperature Using a Portable Reflectometer. FM Approvals 19
23 5 OPERATIONS REQUIREMENTS A quality assurance program is required to assure that the FM Approved roof assembly components produced by the manufacturer shall present the same quality and reliability as the specific roof components examined. Design quality, conformance to design and performance are the areas of primary concern. Design quality is determined during the examination and tests, and is documented in the Approval Report. Continued conformance to this standard is verified by the Surveillance Audit. Quality of performance is determined by field performance and by periodic reexamination and testing. 5.1 Demonstrated Quality Control Program The manufacturer shall demonstrate a quality assurance program which specifies controls for at least the following areas: existence of corporate quality assurance guidelines; incoming quality assurance, including testing; in process quality assurance, including testing; final inspection and tests; equipment calibration; drawing and change control; packaging and shipping; and handling and disposition of non-conforming materials Documentation/Manual There should be an authoritative collection of procedures/policies. It should provide an accurate description of the quality management system while serving as a permanent reference for implementation and maintenance of that system. The system should require that sufficient records are maintained to demonstrate achievement of the required quality and verify operation of the quality system Records To assure adequate traceability of materials and products, the manufacturer shall maintain a record of all quality assurance tests performed, for a minimum period of two years from the date of manufacture Drawing and Change Control The manufacturer shall establish a system of product configuration control that shall allow no unauthorized changes to the product. Changes to FM Approved products or to critical documents identified in the Approval Report, must be reported to, and authorized by, FM Approvals prior to implementation for production. The manufacturer shall assign an appropriate person or group to be responsible for, and require that, proposed changes to FM Approved products be reported to FM Approvals before implementation. The manufacturer shall notify FM Approvals of changes in the product or of persons responsible for keeping FM Approvals advised by means of FM Approvals Form 797, FM Approved Product/Specification-Tested Revision Report or Address/Main Contact Change Report. Records of all revisions to all FM Approved products shall be maintained. FM Approvals 20
24 5.2 Surveillance Audit Program An audit of the manufacturing facility is part of the Approval investigation to verify implementation of the quality assurance program. Its purpose is to determine that the manufacturer's equipment, procedures, and quality program are maintained to insure a uniform product consistent with that which was tested and FM Approved These surveillance audits shall be conducted periodically, but at least annually, by FM Approvals or its representatives FM Approved products or services shall be produced, or provided, at, or from, the location(s) audited by FM Approvals and as specified in the Approval Report. Manufacture of products bearing the Approval Mark is not permitted at any other location without prior written authorization by FM Approvals. 5.3 Installation Inspections Field inspections may be conducted to review an installation. The inspections are conducted to assess ease of application, and conformance to written specifications. When more than one application technique is used, one or all may be inspected at the discretion of FM Approvals. 5.4 Manufacturer's Responsibilities The manufacturer shall notify FM Approvals of changes in product construction, components, raw materials, physical characteristics, coatings, component formulation or quality assurance procedures prior to implementation. FM Approvals 21
25 APPENDIX A: UNITS OF MEASUREMENT Length: Energy: Force: Pressure: in. "inches"; (mm "millimeters") mm = in. x 25.4 ft "feet"; (m "meters") m = ft x ft-lb "foot pound"; (J "joule") J = ft-lb x lb "pounds"; (N "Newton") N = lb x psi "pounds per square inch"; (bar "bar") kpa = psi x psf pounds per square foot kpa = psf x Heat Release Rate: Temperature: Mass Btu/min "British thermal units per minute"; (kw "kilowatts") kw = Btu/min F "degrees Fahrenheit"; ( C "degrees Celsius") C = ( F - 32) x oz ounce ; (gr gram ) gr = oz x FM Approvals 22
26 APPENDIX B: FM APPROVALS CERTIFICATION MARKS FM Approvals certifications marks are to be used only in conjunction with products or services that have been Approved by FM Approvals and in adherence with usage guidelines. FM APPROVED mark: Authorized by FM Approvals as a certification mark for any product that has been FM Approved. There is no minimum size requirement for the mark, but it must be large enough to be readily identifiable. The mark should be produced in black on a light background, or in reverse on a dark background. Cast-On FM Approvals marks: Where reproduction of the FM Approved mark described above is impossible because of production restrictions, use these modified versions of the FM Approved mark. There is no minimum size requirement for the mark, but it must be large enough to be readily identifiable. FM Approved Mark with C only: Authorized by FM Approvals as a certification mark for any product that has been evaluated by FM Approvals in accordance with Canadian codes and standards. There is no minimum size requirement for the mark, but it must be large enough to be readily identifiable. The mark should be produced in black on a light background, or in reverse on a dark background. FM Approved mark with C and US : Authorized by FM Approvals as a certification mark for any product that has been evaluated by FM Approvals in accordance with US and Canadian codes and standards. There is no minimum size requirement for the mark, but it must be large enough to be readily identifiable. The mark should be produced in black on a light background, or in reverse on a dark background. FM Approvals 23
27 FM Approvals Certification Marks USAGE GUIDELINES All FM Approvals certification marks are the sole property of FM Approvals LLC ( FM Approvals ) and are registered or the subject of applications for registration in the United States and many other countries. They are for use only according to these guidelines. FM Approvals certification marks may be used only on FM Approved products and related product packaging, in advertising material, catalogs and news releases. Use of FM Approvals certification marks on such material is not a substitute for use of the complete FM Approvals certification mark on FM Approved products and/or product packaging. No FM Approvals certification mark or aspect thereof may be incorporated as part of a business name, Internet domain name, or brand name/trademark for products/ product lines. This includes both design aspects (the FM Approvals diamond, etc.) and word aspects ( FM, Approved, etc.). The use of any FM Approvals certification mark as a trademark is strictly prohibited. The Approval Standard number or class number may not be incorporated as part of a business name, Internet domain name, or brand name/trademark for products/ product lines. For example, a company may not say ABC Company s 4100 Fire Door is FM Approved ; the proper terminology is, ABC Company s Fire Door is FM Approved per Approval Standard FM Approvals certification marks, except for the FM Approvals Quality System Registration mark, may not be used on business stationery/cards/signage because this could mischaracterize the relationship with FM Approvals. Additionally, these items should not reference any FM Approvals certification mark. Products or services may not be marketed under any mark or name similar to FM Global, FM Approvals or any of the FM Approvals certification marks. Further, products or services may not be marketed to imply a relationship beyond the scope of any Approval made by FM Approvals. When an FM Approvals certification mark is used in advertising material or on product packaging, all material must reflect the specific circumstances under which the product was FM Approved. The material must clearly differentiate between products that are FM Approved and those that are not, and may not, in any way, imply a more substantial relationship with FM Approvals. A company may not reference the intent to submit a product for Approval or the expectation that a company will have a certain product FM Approved in the future. For example, a company may not state, Approval by FM Approvals pending or Approval by FM Approvals applied for. FM Approvals certification marks should not be preceded or followed by a qualifier that indicates a degree of certification or acceptability. For example, exceeds, first or only may not be used to qualify any FM Approvals certification mark. Only original artwork issued by FM Approvals should be used. The FM Approvals certification marks should not be altered in any way other than to resize the artwork proportionately. Unacceptable uses of the marks include, but are not limited to, adding/deleting wording or artwork, reducing the artwork to an illegible size, animation or distortion. The text of the FM Approvals certification marks may not be translated into any language other than English. FM Approvals certification marks must appear in a size and location that is readily identifiable, but less prominent than the name of the owner of the certification or the manufacturer/seller/distributor of the certified products. FM Approvals 24
28 APPENDIX C: SMALL SCALE TESTS The following small scale tests are used to screen and/or compare the properties of individual roof components or roof components used in combination with other components that make up complete roof assemblies. The purpose of these tests is 1) to identify via small scale test procedures critical combinations of components to include in large scale tests 2) to determine if FM Approval may be extended to alternate components after full scale tests have been completed and 3) to assess physical characteristics necessary for the continued performance of a component when installed within a roof assembly. The decision to extend FM Approval to any components via small scale testing shall be at the sole discretion of FM Approvals. Alternate components must perform to an equal or higher level than the component qualified via large scale testing. If the nature of a product or change requires the use of a test not shown below, the test may be used at the sole discretion of FM Approvals. C.1 Pull Through Tests for Roofing Membranes Using Tensile Loading C.1.1 Results Pull through tests for roofing membranes using tensile loading shall be in accordance with Test Procedure, Pull Through Tests for Roofing Membranes and Substrates Using Tensile Loading, FM Approvals, LLC. 1) The result shall be the highest force attained by the sample during the test. 2) The overall sample results shall be determined based on the average of three (3) tests. If the standard deviation of the three values divided by the mean is greater than 20%, up to two (2) additional tests shall be conducted to bring the standard deviation of all values divided by the mean to less than, or equal to, 20%. If after five (5) tests the standard deviation of all five (5) values divided by the mean remains greater than 20%, the results of all five (5) tests shall be used to determine the final average. C.2 Pull Through Tests for Roof Insulation Using Tensile Loading C.2.1 Results Pull through tests for roof insulation using tensile loading shall be in accordance with Test Procedure, Pull Through Tests for Roofing Membranes and Substrates Using Tensile Loading, FM Approvals, LLC. 1) The result shall be the highest force attained by the sample during the test. 2) The overall sample results shall be determined based on the average of three (3) tests. If the standard deviation of the three values divided by the mean is greater than 20%, up to two (2) additional tests shall be conducted to bring the standard deviation of all values divided by the mean to less than, or equal to, 20%. If after five (5) tests the standard deviation of all five (5) values divided by the mean remains greater than 20%, the results of all five (5) tests shall be used to determine the final average. FM Approvals 25
29 C.3 6 x 6 Delamination Tests for Roofing Adhesives and Substrates Using Tensile Loading C.3.1 Results 6 x 6 delamination tests for roofing adhesives and substrates using tensile loading shall be in accordance with Test Procedure, 6 x 6 Delamination Tests for Roofing Adhesives and Substrates Using Tensile Loading, FM Approvals, LLC. 1) The result shall be the highest force attained by the sample during the test. 2) The overall sample results shall be determined based on the average of three (3) tests. If the standard deviation of the three values divided by the mean is greater than 20%, up to two (2) additional tests shall be conducted to bring the standard deviation of all values divided by the mean to less than, or equal to, 20%. If after five (5) tests the standard deviation of all five (5) values divided by the mean remains greater than 20%, the results of all five (5) tests shall be used to determine the final average. C.4 Membrane Delamination Tests for Roofing Membranes and Substrates Using Tensile Loading C.4.1 Results Membrane delamination tests for roofing membranes and substrates using tensile loading shall be in accordance with Test Procedure, Membrane Delamination Tests for Roofing Membranes and Substrates Using Tensile Loading, FM Approvals, LLC. 1) The result shall be the highest force attained by the sample during the test. 2) The overall sample results shall be determined based on the average of three (3) tests. If the standard deviation of the three values divided by the mean is greater than 20%, up to two (2) additional tests shall be conducted to bring the standard deviation of all values divided by the mean to less than, or equal to, 20%. If after five (5) tests the standard deviation of all five (5) values divided by the mean remains greater than 20%, the results of all five (5) tests shall be used to determine the final average C.5 Membrane Peel Tests for Roof Membrane Seam or Cover Tape/Cover Strip Combination using Tensile Loading C.5.1 Results Membrane peel tests for roof membrane seam or cover tape/cover strip combination using tensile loading shall be in accordance with Test Procedure, Membrane Peel Tests for Roof Membrane Seam or Cover Tape/Cover Strip Combination using Tensile Loading, FM Approvals, LLC. 1) The result shall be the highest force attained by the sample during the test. 2) The overall sample results shall be determined based on the average of three (3) tests. If the standard deviation of the three values divided by the mean is greater than 20%, up to two (2) additional tests shall be conducted to bring the standard deviation of all values divided by the mean to less than, or equal to, 20%. If after five (5) tests the standard deviation of all five (5) values divided by the mean remains greater than 20%, the results of all five (5) tests shall be used to determine the final average. FM Approvals 26
30 C.6 Pull Out Tests for Fastener/Roof Deck Combinations and Pull Through Tests for Fastener/Stress Plate or Batten Bar Combinations using Tensile Loading C.6.1 Results Pull out tests for fastener/roof deck combinations and pull through tests for fastener/stress plate or batten bar combinations using tensile loading shall be in accordance with Test Procedure, Pull Out Tests for Fastener/Roof Deck Combinations and Pull Through Tests for Fastener/Stress Plate or Batten Bar Combinations using Tensile Loading, FM Approvals, LLC. 1) The result shall be the highest force attained by the sample during the test. 2) The overall sample results shall be determined based on the average of three (3) tests. If the standard deviation of the three values divided by the mean is greater than 20%, up to two (2) additional tests shall be conducted to bring the standard deviation of all values divided by the mean to less than, or equal to, 20%. If after five (5) tests the standard deviation of all five (5) values divided by the mean remains greater than 20%, the results of all five (5) tests shall be used to determine the final average. C.7 Insulation Breaking Load Test using Tensile Loading Insulation breaking load tests using tensile loading shall be in accordance with Test Procedure, Test Method for Determining the Insulation Breaking Load using Tensile Loading, FM Approvals, LLC. C.7.1 Results 1) The result shall be the highest force attained by the sample during the test. 2) The overall sample results shall be determined based on the average of three (3) tests. If the standard deviation of the three values divided by the mean is greater than 20%, up to two (2) additional tests shall be conducted to bring the standard deviation of all values divided by the mean to less than, or equal to, 20%. If after five (5) tests the standard deviation of all five (5) values divided by the mean remains greater than 20%, the results of all five (5) tests shall be used to determine the final average. C.8 Pull Over Test Procedure for Roofing Membranes with Stress Plates Using Tensile Loading Pull over test procedure for roofing membranes with stress plates using tensile loading shall be in accordance with Pull Over Test Procedure for Roofing Membranes with Stress Plates Using Tensile Loading, FM Approvals, LLC. C.8.1 Results 1) The result shall be the highest force attained by the sample during the test. 2) The overall sample results shall be determined based on the average of three (3) tests. If the standard deviation of the three values divided by the mean is greater than 20%, up to two (2) additional tests shall be conducted to bring the standard deviation of all values divided by the mean to less than, or equal to, 20%. If after five (5) tests the standard deviation of all five (5) values divided by the mean remains greater than 20%, the results of all five (5) tests shall be used to determine the final average. FM Approvals 27
31 C.9 EN 13823, Building Products Excluding Floorings Exposed to the Thermal Attack by a Single Burning Item conducted in accordance with Test Procedure, EN 13823, Reaction To Fire Tests For Building Products - Building Products Excluding Floorings Exposed To The Thermal Attack By A Single Burning Item, FM Approvals, LLC C.10 ISO , Reaction to Fire Tests - Ignitability of Building Products Subjected to Direct Impingement of Flame - Part 2: Single-Flame Source Test conducted in accordance with Test Procedure, Reaction to Fire Tests - Ignitability of Building Products Subjected to Direct Impingement of Flame - Part 2: Single-Flame Source Test, FM Approvals, LLC C.11 ASTM E84 - Standard Test Method for Surface Burning Characteristics of Building Materials conducted in accordance with Test Procedure, Standard Test Method for Surface Burning Characteristics of Building Materials, FM Approvals, LLC C.12 ASTM D1929, Standard Test Method for Determining Ignition Temperature of Plastics conducted in accordance with Test Procedure, ASTM D (Reapproved 2001) E1, Standard Test Method For Determining Ignition Temperature Of Plastics, FM Approvals, LLC C.13 ASTM D240, Standard Test Method for Heat of Combustion of Liquid Hydrocarbon Fuels by Bomb Calorimeter conducted in accordance with Test Procedure, ASTM Oxygen Bomb Testing: ASTM D Heat Of Combustion Of Liquid Hydrocarbon Fuels By Bomb Calorimeter, ASTM D (2005) Heat Of Combustion Of Liquid Hydrocarbon Fuels By Bomb Calorimeter (Precision Method), ASTM D Gross Calorific And Ash Value Of Waste Materials, ASTM D Gross Calorific Value Of Coal And Coke, ASTM E711-87(2004) Gross Calorific Value Of Refuse-Derived Fuel By The Bomb Calorimeter, FM Approvals, LLC C.14 ISO 1716, Determination of the Heat of Combustion conducted in accordance with Test Procedure, ISO 1716, Reaction-to-Fire Tests for Building Products - Determination of the Heat of Combustion, FM Approvals, LLC C.15 ISO 1182, Reaction to Fire Tests for Building Products - Non-Combustibility Test conducted in accordance with Test Procedure, ISO 1182 Reaction To Fire Test For Building Products - Non-Combustibility Test, FM Approvals, LLC. C.16 ASTM D638 - Standard Test Method for Tensile Properties of Plastics C.17 ASTM D Standard Test Method for Climbing Drum Peel for Adhesives C.18 ASTM D751 - Standard Test Methods for Coated Fabrics C.119 ASTM D Standard Method for Apparent Density of Rigid Cellular Plastics FM Approvals 28
Class Number 4470. April 2010. 2010 FM Approvals LLC. All rights reserved.
Approval Standard for Single-Ply, Polymer-Modified Bitumen Sheet, Built-Up Roof (BUR) and Liquid Applied Roof Assemblies for use in Class 1 and Noncombustible Roof Deck Construction Class Number 4470 April
CHAPTER 7: Building Systems ROOFING SYSTEMS
ROOFING SYSTEMS Purpose Examples 1. Shingle roof system 2. Metal roof with blanket insulation 3. Metal roof with rigid insulation 4. Built-up asphalt roof system 5. Single-ply roof system 6. Modified Bitumen
COMMERCIAL BUILDING APPLICATIONS
EXPANDED POLYSTYRENE FOR COMMERCIAL BUILDING APPLICATIONS www.falconfoam.com Commercial Building Ap Expanded Polystyrene Insulation Falcon Foam leads the commercial building industry with products that
ROOFING APPLICATION STANDARD (RAS) No. 150 PRESCRIPTIVE BUR REQUIREMENTS
ROOFING APPLICATION STANDARD (RAS) No. 150 PRESCRIPTIVE BUR REQUIREMENTS 1. 2. 3. 3.0 Scope 1.1 This application standard shall be used where the authority having jurisdiction has adopted its use, and
Roofing Systems. There are many different systems, each with it's own special requirements and benefits. Browse through all the options below.
Roofing Systems There are many different systems, each with it's own special requirements and benefits. Browse through all the options below. BUR (Built-Up Roofing) Built-Up-Roofing, BUR is a roof that
Approval Standard for Flammability of Absorbent Battery Acid Spill Containment Pillows
Approval Standard for Flammability of Absorbent Battery Acid Spill Containment Pillows Class Number 4955 June 2009 2009 by FM Approvals LLC. All rights reserved. Foreword The FM Approvals certification
STANDARD REQUIREMENTS FOR BONDING OR MECHANICAL ATTACHMENT OF INSULATION PANELS AND MECHANICAL ATTACHMENT OF ANCHOR AND/OR BASE SHEETS TO SUBSTRATES
ROOFING APPLICATION STANDARD (RAS) No. 117 STANDARD REQUIREMENTS FOR BONDING OR MECHANICAL ATTACHMENT OF INSULATION PANELS AND MECHANICAL ATTACHMENT OF ANCHOR AND/OR BASE SHEETS TO SUBSTRATES Scope 1.1.
RESIDENTIAL ROOFING & RE-ROOFING, ROOF VENTILATION AND ROOF SHEATHING REQUIREMENTS MICHIGAN RESIDENTIAL CODE 2000
RESIDENTIAL ROOFING & RE-ROOFING, ROOF VENTILATION AND ROOF SHEATHING REQUIREMENTS MICHIGAN RESIDENTIAL CODE 2000 SECTION R905 REQUIREMENTS FOR ROOF COVERINGS R905.1 Roof covering application. Roof coverings
Low-slope reroofing guidelines
Low-slope reroofing guidelines by Thomas Bollnow and Joan P. Crowe, AIA The NRCA Roofing and Waterproofing Manual, Fifth Edition, contains reroofing guidelines for steep- and low-slope roofing. The August
Approval Standard for Class 1 Fire Rating of Building Panels or Interior Finish Materials
Approval Standard for Class 1 Fire Rating of Building Panels or Interior Finish Materials Class Number 4880 October 2015 2015 FM Approvals LLC. All rights reserved. Foreword The FM Approvals certification
1. Adhered KEE membrane roofing system. 2. Mechanically fastened KEE membrane roofing system.
SECTION 075416 - PART 1 - GENERAL 1.1 SUMMARY A. Section Includes: 1. Adhered KEE membrane roofing system. 2. Mechanically fastened KEE membrane roofing system. 1.2 PERFORMANCE REQUIREMENTS A. Solar Reflectance
NRDCA 400 GUIDELINE FOR FIELD APPLICATION of LIGHTWEIGHT INSULATING CONCRETE REROOFING/RECOVER SYSTEMS
NRDCA 400 GUIDELINE FOR FIELD APPLICATION of LIGHTWEIGHT INSULATING CONCRETE REROOFING/RECOVER SYSTEMS The (NRDCA) has prepared this document to provide customers and installers information that the industry
Re-Cover Board-3. Insulation for Above the Deck ROOF WALL SPECIALTY
Insulation for Above the Deck WALL SPECIALTY PRODUCT DESCRIPTION Rmax Re-Cover Board-3 is an energy-efficient thermal insulation board composed of a closed-cell polyisocyanurate (polyiso) foam core bonded
Roofing Systems. New Applications / Re-Roofing / Maintenance
Roofing Systems New Applications / Re-Roofing / Maintenance New Roof Installation In terms of the design and installation of an original roofing system (in conjunction with the construction of a new building),
Laboratory Report P12850.03.09. Simulated Wind Uplift Testing of Adhered Single-Ply Roofing Systems in accordance with FM Standard 4470, Appendix C
Simulated Wind Uplift Testing of Adhered Single-Ply Roofing Systems in accordance with FM Standard 4470, Appendix C Prepared for: 2100 River Edge Parkway, Suite 175 Atlanta, GA 30328 Date of Issuance:
HIGH PERFORMANCE PRE-APPLIED SYSTEM FOR BLIND SIDE & BELOW GRADE WATERPROOFING APPLICATIONS
BSW HIGH PERFORMANCE PRE-APPLIED SYSTEM FOR BLIND SIDE & BELOW GRADE WATERPROOFING APPLICATIONS BSW is a fully reinforced Pre-Applied system membrane designed for horizontal and vertical external blind-side
ANSI/SPRI WD-1 Wind Design Standard Practice for Roofing Assemblies. Table of Contents. 1.0 Introduction...2. 2.0 Methodology...2
Standard Practice f Table of Contents 1.0 Introduction...2 2.0 Methodology...2 Appendix A...7 Insulation Board Fastening Patterns 4 feet 4 feet Boards Adhered Membranes...8 Insulation Board Fastening Patterns
Building Owners Guide to a Duro-Last System!
Building Owners Guide to a Duro-Last System Table of Contents Section 1: Introduction to Duro-Last Roofing Systems Section 2: Benefits of a Duro-Last Roofing System Section 3: Comparing a Duro-Last Roof
SECTION 07560 FLUID APPLIED ROOFING (LIGHT TRAFFIC DECKS OVER CONCRETE)
SECTION 07560 FLUID APPLIED ROOFING (LIGHT TRAFFIC DECKS OVER CONCRETE) PART 1 GENERAL 1.1 DESCRIPTION 1. Fluid applied flexible acrylic waterproofing system over concrete. This work shall include the
Class Number 4880. May 2010. 2010 FM Approvals LLC. All rights reserved.
Approval Standard for Class 1 Fire Rating of Insulated Wall or Wall and Roof/Ceiling Panels, Interior Finish Materials or Coatings and Exterior Wall Systems Class Number 4880 May 2010 2010 FM Approvals
Built-up roofing solutions with rigid insulation boards on concrete decks for new-build and refurbishment E-a5
Cl Sfb (27-9) Rn7 M2 December 2004 Built-up roofing solutions with rigid insulation boards on concrete decks for new-build and refurbishment E-a5 Fesco, Fesco S, Retrofit, Retrofit S, Fesco Fillet, PF,
Approval Standard for Fume Exhaust Ducts or Fume and Smoke Exhaust Ducts
Approval Standard for Fume Exhaust Ducts or Fume and Smoke Exhaust Ducts Class Number 4922 April 2001 2002 FM Approvals LLC. All rights reserved. Foreword The FM Approvals certification mark is intended
FAST FACTS ADVANTAGES OF MULTI PLY BUILT-UP ROOFING. Asphalt Roofing Manufacturers Association
FAST FACTS ADVANTAGES OF MULTI PLY BUILT-UP ROOFING Roofing Manufacturers Association Why is a built-up roof considered a multi-ply roof? ARMA defines a built-up roofing system as a roof where multiple
WATERPROOFING OF REINFORCED CONCRETE FLAT ROOF 12
WATERPROOFING OF REINFORCED CONCRETE FLAT ROOF 12 87 88 GOOD INDUSTRY PRACTICES 12 WATERPROOFING OF REINFORCED CONCRETE FLAT ROOF 12.1 BACKGROUND Most roofs in Singapore are constructed using reinforced
If you are a web registered user of ArlingontPermits.com you may also request an inspection at:
TECHNICAL BULLETIN Community Development & Planning, Building Inspections TOPIC: Permits & Inspections for Roofing Replacement Effective November 1, 2011 Revised This Technical Bulletin will provide contractors
FOUNDATION INSULATING SYSTEM, INCLUDING WATERPROOFING AND DAMP PROOFING
FOUNDATION INSULATING SYSTEM, INCLUDING WATERPROOFING AND DAMP PROOFING insulation installed on foundation walls must be separated from the building interior with a code approved thermal barrier. Foam
DIVISION: 07 00 00 THERMAL AND MOISTURE PROTECTION SECTION: 07 41 13 METAL ROOF PANELS REPORT HOLDER: FIRESTONE BUILDING PRODUCTS COMPANY, LLC
0 ICC ES Report ICC ES (800) 423 687 (62) 699 043 www.icc es.org 000 Most Widely Accepted and Trusted ESR 3422 Reissued 09/201 This report is subject to renewal 09/2016. DIVISION: 07 00 00 THERMAL AND
Approval Standard for Plastic Suspended Ceiling Panels
Approval Standard for Plastic Suspended Ceiling Panels Class Number 4651 February 1978 2002 FM Approvals LLC. All rights reserved. Foreword The FM Approvals certification mark is intended to verify that
EXPANDED POLYSTYRENE (EPS) INSULATION BOARD SPECIFICATIONS
EXPANDED POLYSTYRENE (EPS) INSULATION BOARD SPECIFICATIONS 1. SCOPE 1.1 This specification covers the type, physical properties and dimensions of Expanded Polystyrene Insulation Board intended for use
NEW ELECTRICAL SUBSTATION Building 300 SECTION 07 53 23 ETHYLENE-PROPYLENE-DIENE-MONOMER ROOFING WORK
ETHYLENE-PROPYLENE-DIENE-MONOMER ROOFING WORK PART 1 GENERAL 1.1 REFERENCES The publications listed below form a part of this specification to the extent referenced. The publications are referred to within
Roof Systems Overview
Roof Systems Overview Cold Applied Built-Up Roofing Systems BURmastic Tremco s line of cold applied built-up roofing systems. BURmastic 200 Combines Tremco s expertise in asphalt blending technology with
Dubai Municipality Standard DMS 1: Part 5: 2004
Specification for precast concrete blocks Part 5: Normal-weight concrete-polystyrene sandwich masonry blocks Issue Date Revision Revision Description Prepared by Approved by Authorized by 19/12/2004 Issue
ROOF ASSEMBLIES CHAPTER 9
CHAPTER 9 ROOF ASSEMBLIES SECTION R901 GENERAL R901.1 Scope. The provisions of this chapter shall govern the design, materials, construction and quality of roof assemblies. SECTION R902 ROOF CLASSIFICATION
CHESTERFLEX ROOF WATERPROOFING MEMBRANES
CI/SfB (47) Ln2 Chesterfelt Ltd CHESTERFLEX ROOF WATERPROOFING MEMBRANES Certificate No 94/3062 DETAIL SHEET 2 Product THIS DETAIL SHEET RELATES TO CHESTERFLEX ROOF WATERPROOFING MEMBRANES, POLYESTER REINFORCED
APPENDIX 1: ATTACHMENT REQUIREMENTS FOR WIND UPLIFT RESISTANCE
APPENDIX 1: ATTACHMENT REQUIREMENTS FOR WIND UPLIFT NCE Table Application Type Description Page 1A-1 Wood New, Reroof (Tear-Off), Recover C-1 Mechanically Attached Insulation, Bonded Roof Cover 4 1A-2
Requirements for Fire Protection of Light Weight Floor Systems **Act 1 Revisited**
PHRC Webinar Series Tuesday, September 9, 2014 1:00 pm Requirements for Fire Protection of Light Weight Floor Systems **Act 1 Revisited** Presented by: Bryan Heitzmann Credit(s) earned on completion of
Residential Roofing Guide
Residential Roofing Guide TABLE OF CONTENTS Building Detail and Accessories...... 1 Panel Introduction and Handling...... 2 Cutting and Trimming.... 3 Roof Preparation..... 3 Roof Slope..... 3 Re-roofing...
Waterproofing System for Wastewater Tanks in Petrochemical Industries and Refineries
Waterproofing System for Wastewater Tanks in Petrochemical Industries and Refineries Introduction Wastewater of petrochemical industries and refineries contains high amounts of emulsified aliphatic or
Naue GmbH&Co.KG. Quality Control and. Quality Assurance. Manual. For Geomembranes
Naue GmbH&Co.KG Quality Control and Quality Assurance Manual For Geomembranes July 2004 V.O TABLE OF CONTENTS 1. Introduction 2. Quality Assurance and Control 2.1 General 2.2 Quality management acc. to
!!! !!!! !!! !!! !!! !!! !!!!!!!!! Table of Contents! Section 1: Most Common Types of Flat Roofing! Section 2: Better Understand Your Flat Roof!
Table of Contents Section 1: Most Common Types of Flat Roofing Section 2: Better Understand Your Flat Roof Section 3: Flat Roofing Cost in 2015: Four Factors that Dictate Section 4: Planning A Flat Roofing
0845 0098 980 www.nicholsonsts.com
0845 0098 980 www.nicholsonsts.com ROOFTRAK The IFP is revolutionising the way we fix things to roofs. Technical Director of a leading UK roofing system manufacturer The ROOFTRAK-IFP A revolutionary solution
DIVISION 23 HEATING, COOLING, AIR CONDITIONING AND VENTILATION
SECTION 230713- ALUMAGUARD ENGINEER SPECIFICATION DIVISION 23 HEATING, COOLING, AIR CONDITIONING AND VENTILATION PART 1 - GENERAL 1.1 RELATED DOCUMENTS A. Drawings and general provisions of the Contract,
COMMERCIAL ROOFING. Learning Objectives. Commercial Roofing Fundamentals May 2, 2012
COMMERCIAL ROOFING The Fundamentals Firestone Building Products is a Registered Provider with the American Institute of Architects Continuing Education Systems. Credit earned on completion of this program
Product Guide Specification
Reef Industries, Inc. 9209 Almeda Genoa Rd. Houston, Texas 77075 Toll Free (800) 231-6074 Phone (713) 507-4251 Fax (713) 507-4295 Web Site www.reefindustries.com E-Mail [email protected] Product Guide
Annex of the certificate (Page 1/6) Accreditation Scope
As a Testing Laboratory Annex of the certificate (Page 1/6) Accreditation Scope Address: Küçük Çiğli Mh. 8780/1 Sk. No:5 Çiğli 35681 İZMİR / TÜRKİYE Phone : 0 232 376 24 25 Fax : 0 232 386 33 98 E-Mail
High Performance PSA in Sheet Membrane in Water Protection
High Performance PSA in Sheet Membrane in Water Protection Xia Cao, Senior R&D Chemist, W. R. Grace, Cambridge MA 02140 Jyoti Seth, Strategic Program Leader, W. R. Grace, Cambridge MA 02140 Concrete is
DIVISION: 06 00 00 WOOD, PLASTICS AND COMPOSITES SECTION: 06 05 83 SHOP APPLIED WOOD COATINGS SECTION: 06 16 00 SHEATHING REPORT HOLDER:
0 ICC ES Report ICC ES (800) 423 6587 (562) 699 0543 www.icc es.org 000 Most Widely Accepted and Trusted ESR 1365 Reissued 04/2016 This report is subject to renewal 04/2017. DIVISION: 06 00 00 WOOD, PLASTICS
Peel & Seal Self-Stick Roofing Solutions
Peel & Seal Self-Stick Roofing Solutions Ideal for Low Slope Applications Waterproof and Weatherproof Energy Efficient Tough and Durable Versatile, Effective Sealing Around Protrusions Perfect for Vents,
COMPARATIVE PERFORMANCE OF EPDM RUBBER ROOFING MEMBRANE AS PROTECTION AGAINST HAIL DAMAGE
www.epdmroofs.org COMPARATIVE PERFORMANCE OF EPDM RUBBER ROOFING MEMBRANE AS PROTECTION AGAINST HAIL DAMAGE By Ric Vitiello President Forensic Roof Consulting and Hail Damage Assessment Training www.benchmark-services.com
Final inspections are completed by site visit only. Access to fenced yards shall be planned.
ROOFING RESIDENTIAL BUILDING INSPECTIONS DEPARTMENT www.ci.blaine.mn.us This handout is intended only as a guide and is based in part on the 2015 Minnesota State Building Code, Blaine City ordinances,
Site Inspection Report
Site Inspection Report Project Title: 1 Canada Square Location: 1 Canada Square, Canary Wharf, London Date of Inspection: 16/05/12 System / Products: TBA (suggested flame free application) Attendees: G
GYPSUM BOARD, GYPSUM PANEL PRODUCTS AND PLASTER
CHAPTER 25 GYPSUM BOARD, GYPSUM PANEL PRODUCTS AND PLASTER User note: Code change proposals to this chapter will be considered by the IBC Structural Code Development Committee during the 2016 (Group B)
738-B-297 POLYMERIC CONCRETE BRIDGE DECK OVERLAY. (Adopted 02-20-14)
POLYMERIC CONCRETE BRIDGE DECK OVERLAY (Adopted 02-20-14) Description The polymeric concrete bridge deck overlay shall consist of an epoxy polymer that acts together with special aggregate to form an overlay
Durapax Coal Tar BUR Application Guide
400 Old Reading Pike, Suite 304 Pottstown, PA 19464 Tel: 610-579-9075 Fax: 610-323-0115 www.durapax.com Durapax Coal Tar BUR Application Guide DESIGN CONSIDERATIONS The proper specifications of any roof
Roofing. Sarnafil S 327-15EL. Polymeric membrane for roof waterproofing. Product Description
Roofing Product Data Sheet Edition 02.2015 Identification no: 02 09 01 01 201 0 150000 Version no. 04 Sarnafil S 327-15EL Polymeric membrane for roof waterproofing Product Description Sarnafil S 327-15EL
Please read the entire document before purchasing and installing any of these products
Please read the entire document before purchasing and installing any of these products USA SBS UNDERLAYMENT ROOFING UNDERLAYMENT SBS Mineral Surfaced MINERAL SURFACE CAP SHEET Ice and Water Protection
SECTION 07530 SINGLE PLY MEMBRANE ROOFING. 4. Minor repair to adjacent clay tile roofing and flashings.
SECTION 07530 PART 1 - GENERAL 1.01 DESCRIPTION A. This Section includes the flowing: 1. Removal of existing roofing membrane. Existing bur roof has one overlay and penetration mastic is asbestos containing.
Roof Restoration System. For building owners, property management firms and facility managers. seamless possibilities
Roof Restoration System For building owners, property management firms and facility managers seamless possibilities Extending your roof life Think of your existing older roof custom fit with a seamless,
SECTION 07 42 13 METAL WALL PANELS
Mitsubishi Plastics Composites America, Inc. 401 Volvo Parkway Chesapeake, VA 23320 Phone: (800) 422-7270 Fax: (757) 436-1896 E-mail: [email protected] www.alpolic-northamerica.com This MANU-SPEC utilizes
ITEM 599.06060008 THERMOPLASTIC MEMBRANE ROOFING
DESCRIPTION Construct adhered membrane roofing system, roof insulation, and vapor retarder in accordance with these specifications. MATERIALS: General: Provide installed roofing membrane and base flashings
NRCA s steep-slope manual is thoroughly revised for 2013
Photo courtesy of Boone Brothers Roofing, Omaha, Neb. NRCA s steep-slope manual is thoroughly revised for 2013 by Maciek Rupar 38 www.professionalroofing.net MARCH 2013 P ublished in January, The NRCA
Tremco Fire Protection Systems Group Technical Bulletin
Compartmentalization products and design play a key role in protecting lives and property from fire. Understanding the tools and techniques available for firestopping is of utmost importance to designers,
SECTION 07550 - MODIFIED BITUMINOUS MEMBRANE ROOFING. A. Vapor barrier (base ply); cover board at existing roof deck.
SECTION 07550 - PART I GENERAL 1.01 SECTION INCLUDES A. Vapor barrier (base ply); cover board at existing roof deck. B. Roof insulation at new roof deck. C. Modified bitumen membrane. D. Fluid applied
HOT ASPHALT BUILT-UP ROOFING SYSTEMS MORE LAYERS MEANS MORE PROTECTION
HOT ASPHALT BUILT-UP ROOFING SYSTEMS MORE LAYERS MEANS MORE PROTECTION ADVANCED TECHNOLOGY FROM OWENS CORNING TRUMBULL ASPHALT TruLo Lo Odor and TruLo Max asphalt raising the roof on asphalt performance.
Asphalt Shingle Application Requirements
Alberta Allied Roofing Association Asphalt Shingle Application Requirements Section 1 Roof Decks 1.1 General Asphalt Shingles are not permitted to be installed directly over rigid insulation. When Asphalt
2.18 INTERIOR & EXTERIOR FINISHES 2.18.1 VAPOR & AIR BARRIERS
2.18 INTERIOR & EXTERIOR FINISHES 2.18.1 VAPOR & AIR BARRIERS The LOGIX wall assembly has no need for an additional vapor barrier, the solid concrete core covered with the low permeance EPS (Type II) foam
STAYFLEX CORROSION CONTROL AND THERMAL INSULATION SYSTEM
STAYFLEX CORROSION CONTROL AND THERMAL INSULATION SYSTEM Installed in Pre-engineered Steel Buildings Provides Lowest Cost Construction Method for CORROSIVE AND WET Environments PREFERRED SOLUTIONS, INC.
SECTION 15190 HVAC INSULATION. A. All work specified in this Section is subject to the provisions of Section 15010.
SECTION 15190 HVAC INSULATION PART ONE - GENERAL PART 1 - GENERAL 1.01 DESCRIPTION A. All work specified in this Section is subject to the provisions of Section 15010. B. All insulation products shall
CERTIFICATE NAME OF PRODUCT MANUFACTURER PRODUCT DESCRIPTION CERTIFICATION PROCEDURE. No VTT C-6044-10 Date of issue 11.10.2010, Updated July 1, 2011
CERTIFICATE NAME OF PRODUCT No VTT C-6044-10 Date of issue 11.10.2010, Updated July 1, 2011 H-CONTROL REFLEX+ reflective insulating vapour control layer for roof and wall applications MANUFACTURER ACTIS
Sika Membran System For Sealing and Waterproofing Construction Gaps in Building Façades
Construction Sika For Sealing and Waterproofing Construction Gaps in Building Façades Waterproof and Airtight Flexible Seal Controlled Vapour Diffusion Bonds to any Building Substrate Prevents Interstitial
September 3, 2009. Ric Boyd, Public Works Director Ketchikan Gateway Borough 344 Front St. Ketchikan, AK 99901
September 3, 2009 Ric Boyd, Public Works Director Ketchikan Gateway Borough 344 Front St. Ketchikan, AK 99901 RE: Ketchikan Gateway Borough Gateway Recreation Center Roof Observations and Intrusive Inspections
Best Practices in Roof Design: Sustainable Energy Efficient Reroofing
Best Practices in Roof Design: Sustainable Energy Efficient Reroofing Best Practice Roof Design: Sustainable Energy Efficient Reroofing Presented by Edis Oliver, PE Principal 9511 Lake Creek Parkway Austin,
CORNING CABLE SYSTEMS GENERIC SPECIFICATION FOR TIGHT BUFFER OPTICAL FIBER CABLES FOR INTER- AND INTRABUILDING APPLICATIONS.
CORNING CABLE SYSTEMS GENERIC SPECIFICATION FOR TIGHT BUFFER OPTICAL FIBER CABLES FOR INTER- AND INTRABUILDING APPLICATIONS September 2006 Revision 7 Corning Cable Systems reserves the right to update
- - - - Steel Panel Frame. Exterior Steel Sheeting. Optional Rigid Insulation. Optional Steel Insulation Liner
The Kelly Klosure pre-framed modular panel has 4 components that are factory finished to create an easy and versatile bolt-together system in the field. Steel Panel Frame Exterior Steel Sheeting Optional
CRS Sales & Marketing
TPO - Technology CRS Sales & Marketing Presenter: Gena Miller Thank you AIA, Sign In Sheet (1 Hour CEU-HSW) Division of CRS, Inc. (Commercial Roofing Specialties) 5 Locations (4 state of GA, 1 state of
CHAPTER VII. TITLE: STANDARDS FOR NEW ROOFING July 2015 CONSTRUCTION, RE-ROOFING CONSTRUCTION AND ROOFING SYSTEM GUARANTEE REQUIREMENTS
TITLE: STANDARDS FOR NEW ROOFING CONSTRUCTION, RE-ROOFING CONSTRUCTION AND ROOFING SYSTEM GUARANTEE REQUIREMENTS Responsible Organization: Office of Facilities Planning Instructions: This Manual supersedes
HEB 38 BLANCO AND WEST AVENUE FLUID APPLIED EPDM RUBBER ROOF RECOVERY SYSTEM APPLICATION
HEB 38 BLANCO AND WEST AVENUE FLUID APPLIED EPDM RUBBER ROOF RECOVERY SYSTEM APPLICATION David Marut TEST CASE REPORT July 1, 2014 Case Study Pro Guard EPDM Super Coat Liquid Rubber Membrane Roof System
07 21 19 Guide Specification STAYFLEX CORROSION CONTROL AND THERMAL INSULATION SYSTEM
07 21 19 STAYFLEX CORROSION CONTROL AND THERMAL INSULATION SYSTEM 7819 Broadview Road Cleveland, OH 44131 800-522-4522 February, 2011 SPEC NOTE: This guide specification is intended for use when specifying
ICC-ES Evaluation Report Reissued March 1, 2011 This report is subject to renewal in one year.
ICC-ES Evaluation Report www.icc-es.org (800) 423-6587 (562) 699-0543 ESR-900* Reissued March, 20 This report is subject to renewal in one year. A Subsidiary of the International Code Council DIVISION:
THERMAL INSULATION MATERIALS TEST METHOD SELECTION LIST
THERMAL INSULATION MATERIALS TEST METHOD SELECTION LIST Instruction: Check each test method for which you are requesting accreditation. An asterisk beside the NVLAP Test Method Code indicates that proficiency
07 5423-1 THERMOPLASTIC-POLYOLEFIN ROOFING (TPO) Data Center
PART 1 GENERAL 1.01 SECTION INCLUDES SECTION 07 5423 THERMOPLASTIC-POLYOLEFIN ROOFING (TPO) Data Center A. Tear off existing roof system down to wood deck and install new Thermoplastic membrane roofing
WATERPROOFING FOR CONCRETE STRUCTURES
MANUAL OF CONTRACT DOCUMENTS FOR ROAD WORKS VOLUME 1 SPECIFICATION FOR ROAD WORKS SERIES 2000 WATERPROOFING FOR CONCRETE STRUCTURES Contents Clause Title Page 2001 General 2 2002 Protection of Bridge Deck
BDA Agrément BAR 14-030/02/A
Number BAR 14-030//A Replaces: BAR 14-030/01/A Date 2014.03.15 Project number 13-B-0739 Validity See www.bda.nl System Supplier (Certificate holder) BDA ADVIES BDA Agrément BAR 14-030//A EcoProof TM ST
Construction. SikaProof A-08 Edge, A-12 Edge. Fully bonded FPO sheet membrane in L-shape for the SikaProof A waterproofing system. Product Description
Product Data Sheet Edition 15/10/2014 Identification no: 02 07 04 10 300 0 000002 SikaProof A Edge SikaProof A-08 Edge, A-12 Edge Fully bonded FPO sheet membrane in L-shape for the SikaProof A waterproofing
DENSO WATERPROOFING SYSTEMS
DENSO WATERPROOFING SYSTEMS Approved Quality Management System AS/NZS ISO 9001:2008 Lloyds Register Certificate N o Mel 0927759 Denso (Australia) Pty Ltd A MEMBER OF WINN & COALES INTERNATIONAL 411 413
Memtec Single Ply PVC Membrane Roofing and Waterproofing Technology. Modern Efficient Performance Cost Effective Flat Roofing Systems
Memtec Single Ply PVC Membrane Roofing and Waterproofing Technology Modern Efficient Performance Cost Effective Flat Roofing Systems Introduction A complete range of Memtec Roofing and Waterproofing Single
GUIDELINE SPECIFICATIONS
GUIDELINE SPECIFICATIONS GORDON SOFFIT-SHIELD - An Exterior Metal Soffit System DIVISION 05 5800 or DIVISION 07 7700 Note To Specifier: SOFFIT-SHIELD should be installed by tradesmen that are experienced
Chapter 2 Basis of design and materials
Chapter 2 Basis of design and materials 2.1 Structural action It is necessary to start a design by deciding on the type and layout of structure to be used. Tentative sizes must be allocated to each structural
Test report P 7013-E. InoPaz H2O. Pazkar LTD. Alon Tavor Industrial Zone AFULA 18000 / Israel. J. Magner Dipl.-Ing. N. Machill.
Kiwa Polymer Institut GmbH Quellenstraße 3 65439 Flörsheim-Wicker Tel. +49 (0)61 45-5 97 10 Fax +49 (0)61 45-5 97 19 www.kiwa.de Test report P 7013-E Testing order: Test of the waterproofing system based
CHAPTER 6 CONSTRUCTION TYPES
CHAPTER 6 CONSTRUCTION TYPES SECTION 601 GENERAL 601.1 Scope. Provisions of this chapter shall govern the classification of construction type by materials and fire resistance of its elements and the use
BLACK JACK ALL WEATHER ROOF COATING
PAGE: 1 of 6 PRINT DATE: 16/09/2004 BLACK JACK ALL WEATHER ROOF COATING DESCRIPTION BLACK JACK ALL WEATHER ROOF COATING is a solvent based, full bodied black brushable compound with added fibres for reinforcement.
Firestone Modified Bitumen Roofing Systems DURABLE. RELIABLE. SUSTAINABLE
Firestone Modified Bitumen Roofing Systems DURABLE. RELIABLE. SUSTAINABLE I n t r o d u c t i o n t o M o d i Acres of Roofing. Decades of Performance. Over the past 20 years, Firestone Building Products
CONDENSATION IN REFRIDGERATED BUILDINGS
CONDENSATION IN REFRIDGERATED BUILDINGS By: Steve Salisbury Nov. 10, 2010 (revised Nov. 14, 2013) Introduction The following discussion reviews the basic causes of condensation in refrigerated buildings
Fire Preventive and Fireproof Performance Test and Evaluation Procedure Manual
BR BO-01-02 Effective from June 1, 2000 Revision: March 26, 2002 Fire Preventive and Fireproof Performance Test and Evaluation Procedure Manual (Unofficial Manual) Technical Appraisal Department, Building
COMMERCIAL & LOW SLOPED ROOF SPECIALISTS TOTAL NDL SYSTEM MANUFACTURER WARRANTIES
C COMMERCIAL & LOW SLOPED ROOF SPECIALISTS We are equipped to handle the largest of your commercial roof needs. Whether storm damage or simply needing a new commercial roof due to age, Cobalt allows you
Self-Stick Roofing Solutions
Peel & Seal Self-Stick Roofing Solutions Ideal for Low Slope Applications Waterproof and Weatherproof Energy Efficient Tough and Durable Versatile, Effective Sealing Around Protrusions Perfect for Vents,
DIVISION: 07 00 00 THERMAL AND MOISTURE PROTECTION SECTION: 07 32 16 CONCRETE ROOF TILES REPORT HOLDER:
0 ICC ES Report ICC ES (800) 423 6587 (562) 699 0543 www.icc es.org 000 Most Widely Accepted and Trusted ESR 1900 Reissued 03/2016 This report is subject to renewal 03/2017. DIVISION: 07 00 00 THERMAL
Avoiding Air Barrier Pitfalls
Avoiding Air Barrier Pitfalls Design & Durability November 2013 Air barriers, when correctly installed, help buildings achieve high levels of energy efficiency by decreasing heat loss. For example, great
Fiberglas, Exterior Wall Thermal Insulation
PROJECT ENGINEER RESPONSIBILITY: This is a general specification guide, intended to be used by experienced construction professionals, in conjunction with good construction practice and professional judgment.