Reference Guide: SmartDesign Approach: Common Data Center Challenges:

Size: px
Start display at page:

Download "Reference Guide: SmartDesign Approach: Common Data Center Challenges:"

Transcription

1 Smart Solutions Reference Guide Solutions For Business-Critical Continuity 1100kW Tier 3 With High Density Design Intelligent, Integrated Infrastructure for the Data Center Reference Guide: 1100kW Tier 3 With High Density The SmartDesign from Emerson Network Power uses a perimeter/room-based approach to deliver efficiency, availability, capacity and control, that allows you to be prepared for what s next. Our approach helps to create, maintain and grow data centers that meet customer challenges through innovative systems, industry-best practices and local data center specialists who fully understand how to solve these problems. This sample reference scenario, 1100kW Tier 3 With High Density, illustrates one possible example of how the SmartDesign approach can be used to create a high-performance IT infrastructure. To find out more about the SmartDesign approach and view more Reference Scenarios, visit SmartSolutionsDesigns.com SmartDesign Approach: Lower energy bills by $122,000/yr Generate PUE of 1.19 Save 38% in OPEX Lower TCO by 21% over base Reduce rack count by 65% Common Data Center Challenges: Limited availability and capacity Insufficient and inefficient cooling capabilities Piecemeal infrastructure that is difficult to manage Space constraints Energy inefficiencies Budgetary constraints Complexities that limit growth Save 60% in floor space Provide high Tier 3 availability Obtain over 97% UPS efficiency Improve flexibility and scalability Leverage density of 20kW/rack SmartDesign Benefits: Proven power solutions that deliver efficiency, scalability and reliability Precision cooling that controls the temperature, humidity and airflow Effective monitoring and control Efficient space utilization Improved PUE Lower TCO Flexible and scalable configurations

2 Data Center Design Overview Efficiency. Availability. Capacity. One Approach. This innovative reference design uses efficient refrigerantbased rear door heat exchangers and chilled water economization alongside a highly efficient tier 3 power configuration to deliver high capacity within a smaller space. The design blends efficiency, availability and scalability to deliver an optimized infrastructure. Use this design approach when: Climate allows for economization Data center floor space is to be minimized Tier 3 availability is desired Benefits of this application: Free cooling saves energy Higher density improves efficiency Dual bus reduces downtime Design Summary This data center integrates power and cooling in a Tier 2 mechanical and a Tier 3 electrical configuration to support a 1.1MW load. (2) Liebert CW 114kW base cooling (56) Liebert XDR rear door heat exchangers (56) DCF Optimized Racks (8) Liebert XDP refrigerant pumping units (2) Liebert NXL1100kVA/1100kW UPS 2N Dual Bus configuration (12) Liebert PPC PDU (12) Liebert FDC PDU (2) Liebert TVSS (2) ASCO ATS (112) Liebert MPX rack PDU Liebert Nform, Avocent Data Center Planner This design delivers: Operating/energy savings Lower data center footprint More efficient rack utilization Free cooling using fluid economization Simplified scalability High capacity, high efficiency UPS Protected dual bus architecture Operational DCIM control and factory local service 2

3 Data Center Overview Premium Base Minimum Mech. Redundancy 20%, Electrical Tier 4 This SmartDesign Miniumum Mech. Redundancy 35%, Electrical Tier 3 Cost Savings (vs. Base) Cost Advantage Building Costs Engineering/Contracting, Building, Ceiling/Floor, Lights, Fire Suppression $6,500,000 $5,100,000 $1,400,000 22% Infrastructure Racks & Install $450,000 $118,000 $332,000 74% Mechanicals & Install $1,600,000 $2,400,000 -$800,000-50% Electricals & Install $10,200,000 $7,400,000 $2,800,000 27% Total CapEx $18,750,000 $15,018,000 $3,732,000 20% Infrastructure Energy Costs $313,000 $147,000 $122,000 45% Water Usage $23,500 $23,500 $0 0% Total Annual Energy Cost $292,500 $170,500 $122,000 42% 5 Year OpEx $1,462,500 $852,500 $610,000 42% 5 Year TCO $20,212,500 $15,870,500 $4,342,000 21% * Using Columbus, OH weather table, base utilizes (14) Liebert CW 084, (4) Liebert 750kVA without Eco-mode energy optimization. Utility costs of $.08/kw-h electric, $1.99 per k gallon water. Total power efficiency of 89% for base, 94% average for this SmartDesign (1.5% loss of PDU, 1.5% loss for lighting). SmartSolutionsDesigns.com 3

4 Applied Cooling Approach Efficient Refrigerant-Based Heat Exchangers and Chilled Water Economization Shown below is a sample SmartDesign cooling scenario using our innovative refrigerant high density systems along with base chilled water cooling with economization in a 1.1MW data center. This facility uses a water cooled centrifugal chiller system with series fluid side economizer. Using this design a customer only needs 56 IT racks at 20 kw per rack. There is a 36 inch raised floor with space above dropped ceiling used as return air pathway. The precision cooling units use (2) Liebert CW 114 with Liebert icom and EC fans, and the Liebert XD system with (56) of the Liebert XDR attached to the racks and (8) Liebert XDP pumping units. Hot aisle, cold aisle arrangement is optional. * Liebert systems identified are repeated in the gallery on the left. This cooling approach includes: Water-cooled centrifugal chiller system Base humidification 36-inch raised floor Space above dropped ceiling utilized as a return-air pathway Service, support and data center design expertise from Emerson Network Power Total RF Data Center Footprint Room Perimeter Total Racks 56 kw per Rack Total kw 69x ft lf kw 1100kW Gallery Footprint (2) 495 ft 2 Precision Cooling AC Power Racks and Integrated Cabinets Liebert XDR EC Fans Liebert icom Liebert CW 114 Liebert XDP This innovative data center packs tremendous computing power into a very efficient space for remarkable savings. The layout shown is one representation. Another option when working with Liebert XDRs is to arrange in a cascading aisle configuration. Naturally, air movement is front to back and returned to the cooling unit(s) via a pathway. 4

5 Applied Cooling Equipment and Best Practices Let s Compare: Premium Conventional This SmartDesign Capacity 1.1MW 1.1MW Dimensions sq ft Total 6,603 DC 4,819 Total 2,691 DC 1,701 Racks 7kW per Rack 20kW per Rack Raised Floor Chiller Plant Dual 300T Water cooled centrifugal 48F EWT, 60F LWT, 85F RAT SD: 25hp CW pumps, 20hp cond pumps, 40 hp tower fans Dual 300T Water cooled centrifugal 48F EWT, 60F LWT, 85F RAT VFD: 25hp CW pumps, 20hp cond pumps, 40 hp tower fans Economizer Series fluid Series fluid AC Liebert CW 084 kw standard fan/motor (2) Liebert CW 114 kw, EC plugs fans in floor (56) Liebert XDR, (8) Liebert XDP Airflow Ceiling return pathway Ceiling return pathway Containment None None * Images not to scale Equipment Overview Technologies Benefits Best Practices Overview: Liebert CW 114 kw Chilled water pre-packaged systems. Dedicated systems allow for easier scalability and redundancy. Proven, reliable operation provides humidity control and air filtration. Highly manageable and serviceable. Efficient components. Maximize the return temperature at the cooling units to improve capacity and efficiency Liebert icom Controls Advanced controls ensure superb efficiency through teamwork, seperate fan and capacity control, unit rotation and more. Match cooling capacity and airflow with IT loads EC Fans Improved airflow performance and efficiency. Energy savings of 20-30% over traditional designs. Liebert XDR Fanless heat exchanger provides outstanding energy savings - no added floor space - higher computing density saves energy and data center space - uses only server fans to move air over the coils - no cooling fans required - use with or without hot aisle/cold aisle layout. Utilize cooling designs that reduce component power Liebert XDP Intelligent isolating pumping interface between the building chilled water system and the pumped refrigerant circuit. Fluid Economizer Incorporated into the chiller plant heat rejection loop to cool the fluid during appropriate times reducing pump operations. Enhance data center operations with management and control systems For even greater improvements, you could raise the chiller temp 2-3 F above 48 F SmartSolutionsDesigns.com 5

6 SWBD, 4000A, 480V, 3Ø, 4W+G ISOLATION N LOAD 2000A 2000A 2000A 1600A 4000A UPS BYPASS 1100KVA UPS MODULE A CB1 BFB BATTERY STRING #B2 CB2 SS 3000 KVA 13,200V / 480V DIST SWBD, 2000A MBB 2000A TVSS FPC A1 4000A 1600A FPC A3 FDC A2 FDC A2 FDC A2 FDC A2 BYPASS E 2500 KVA GENERATOR A SWBD, 1600A, 480V, 3Ø, 4W+G 150A 150A 150A 150A FPC A5 FDC A1 FDC A1 FDC A1 FDC A1 FDC A3 FDC A3 FDC A3 FDC A3 FDC A5 FDC A5 FDC A5 FDC A5 FPC A2 FPC A4 FPC A6 FDC A4 FDC A4 FDC A4 FDC A4 FDC A6 FDC A6 FDC A6 FDC A6 E N SS Applied Power Approach Tier 3, Efficient, 2N Power with Two-Stage Distribution The power approach utilized in this scenario supports a Tier 3, 1.1 MW data center. Both the UPS and electrical distribution configurations are optimized for maximum efficiency, availability and capacity. Electrical Power Design: Our Tier kW operation utilizes (2) separate utility transformers and (2) separate main utility switchgear modules. The UPS system consists of (2) Liebert NXL 1100kVA/1100kW UPS 2N Dual Bus configuration. Backup power generation provided by two (2)2.5MW Generators in (2N) configuration. Electrical Distribution Design: Design distribution to consist of six (6) pairs of 225kVA Liebert PPCs in a dual bus configuration. They in turn will receive power from a UPS distribution panel board. Each Liebert PPC powers a Liebert FDC, which then deliver power to the racks via the Liebert MPX PDU. Close up of Bus A of an A/B Bus Power System in a Tier 3 Architecture 3000 KVA 13,200V / 480V 2500 KVA GENERATOR 1 ISOLATION BYPASS 4000A TVSS 4000A N E LOAD SWBD, 4000A, 480V, 3Ø, 4W+G 2000A 2000A 2000A 1600A 4000A UPS BYPASS 1600A SWBD, 1600A, 480V, 3Ø, 4W+G 1100KVA UPS MODULE A DIST SWBD, 2000A 150A 150A 150A 150A CB1 BFB SS MBB 2000A CB2 BATTERY STRING #B2 FPC A1 FPC A3 FPC A5 FDC A1 FDC A1 FDC A1 FDC A1 FDC A3 FDC A3 FDC A3 FDC A3 FDC A5 FDC A5 FDC A5 FDC A5 FPC A2 FPC A4 FPC A6 One-Line Snapshot of Both A/B Buses FDC A2 FDC A2 FDC A2 FDC A2 FDC A4 FDC A4 FDC A4 FDC A4 FDC A6 FDC A6 FDC A6 FDC A6 6

7 Applied Power Equipment Equipment Overview Technologies Liebert NXL1100kVA/ 1100kW UPS 2N Dual Bus configuration Liebert FPC/PPC Liebert FDC Liebert MPX Rack PDU Liebert TVSS ASCO ATS Infrastructure Management Benefits Robust and efficient double conversion UPS. Resilient stack-up performance Protects from all electrical conditions. Efficiency rivals transformerfree systems. Power factor rated at near unity. Reliable and flexible isolated power conditioning and distribution process significant power to many circuits. Flexible, fast, in row power distribution for high capacity connections to the racks. Intelligent rack power distribution creates a very smart, scalable and flexible system. Hot swappable modules, receptacle level control and management. Single or three phase. Flexible mounting. Facility-wide and Panel Mount versions remove electrical surges in the power stream. Reliable switches for critical performance. Albér Battery Monitoring: Identifies issues in batteries and extends product lifespan. Liebert Nform: Distributed monitoring and alarm management of critical devices. Increase availability. Best Practices Overview: Obtain the power system designed to match your needs for availability and efficiency (tiers, redundancy, voltages, distribution) Leverage the optimum design for electrical scalability and modularity to meet current and future needs Enhance data center operations with management and control systems Rely on local service and support to ensure proper designs, maintenance and assessments Equipment Room (2) 1,446 ft 2 Avocent DCP: Data center planner manages assets, capacities and room/rack layouts. Supporting Data Center PDUs in gallery Liebert CW 114 Cooling Unit Liebert NXL UPS Batteries Switchgear Liebert PPC/PDU SmartSolutionsDesigns.com 7

8 Power Approach Benefits Energy Efficient UPS Power 100% 96% 92% 88% Typical Load Liebert NXL 1100kVA/1100kW UPS 84% Intelligent EcoMode AC-AC (UPS Dual Conversion) 80% 10% 20% 30% 40% 50% 60% 70% 80% 90% 100% Reduce or eliminate downtime costs of $507,000/event. Creating, maintaining and expanding data centers with Emerson Network Power With Emerson Network Power and the SmartDesign approach, there s virtually no limit to what you can solve and how you can design the optimal data center. PDU Efficiency Curve Liebert PPC/FPC 0% 20% 30% 40% 50% 75% 100% Efficiency through performance based TCO. The SmartDesign approach helps data centers save money while still ensuring mission-critical availability. Using the innovative equipment and industry-best practices that this approach offers, you can avoid the costly expenses associated with system failures and down times. Did you know? Average data centers experience 5.12 power outages every two years Outage duration averages 106 minutes System recovery is estimated at 3 times the duration of the outage (318 on average) This means that on average, each unplanned outage costs $507,000*. *Read the Ponemon white paper on costs of downtime at Emerson Network Power. The global leader in enabling Business-Critical Continuity. AC Power Embedded Computing Infrastructure Management & Monitoring Connectivity Embedded Power Outside Plant DC Power Industrial Power Power Switching & Controls For more examples of the high-efficiency and highcapacity data centers that the SmartDesign approach can create, maintain and grow, visit our website. Contact a local data center specialist to discuss your situation. They can assist you with technical advice, configuration development and energy analysis to support your unique design needs. The SmartDesign Approach Efficient Economical Simplified Controllable To see more Reference Scenarios, visit today. While every precaution has been taken to ensure accuracy and completeness in this literature, Liebert Corporation assumes no responsibility, and disclaims all liability for damages resulting from use of this information or for any errors or omissions Liebert Corporation. All rights reserved throughout the world. Specifications subject to change without notice. All names referred to are trademarks or registered trademarks of their respective owners. Liebert is a registered trademark of the Liebert Corporation. SL-11505C (R01-14) EmersonNetworkPower.com Precision Cooling Racks & Integrated Cabinets Services Business-Critical Continuity, Emerson Network Power and the Emerson Network Power logo are trademarks and service marks of Emerson Electric Co Emerson Electric Co.

SmartDesign Intelligent, Integrated Infrastructure For The Data Center. Solutions For Business-Critical Continuity

SmartDesign Intelligent, Integrated Infrastructure For The Data Center. Solutions For Business-Critical Continuity SmartDesign Intelligent, Integrated Infrastructure For The Data Center Solutions For Business-Critical Continuity Prepare Your Data Center For What s Next Efficiency. Availability. Capacity. Control. One

More information

7 Best Practices for Increasing Efficiency, Availability and Capacity. XXXX XXXXXXXX Liebert North America

7 Best Practices for Increasing Efficiency, Availability and Capacity. XXXX XXXXXXXX Liebert North America 7 Best Practices for Increasing Efficiency, Availability and Capacity XXXX XXXXXXXX Liebert North America Emerson Network Power: The global leader in enabling Business-Critical Continuity Automatic Transfer

More information

Data Center Consolidation Trends & Solutions. Bob Miller Vice President, Global Solutions Sales Emerson Network Power / Liebert

Data Center Consolidation Trends & Solutions. Bob Miller Vice President, Global Solutions Sales Emerson Network Power / Liebert Data Center Consolidation Trends & Solutions Bob Miller Vice President, Global Solutions Sales Emerson Network Power / Liebert Agenda Traditional Data Centers Drivers of a Changing Environment Alternate

More information

Combining Cold Aisle Containment with Intelligent Control to Optimize Data Center Cooling Efficiency

Combining Cold Aisle Containment with Intelligent Control to Optimize Data Center Cooling Efficiency A White Paper from the Experts in Business-Critical Continuity TM Combining Cold Aisle Containment with Intelligent Control to Optimize Data Center Cooling Efficiency Executive Summary Energy efficiency

More information

Microsoft Technology Center: Philadelphia

Microsoft Technology Center: Philadelphia A Customer Success from the Experts in Business-Critical Continuity TM. Background Microsoft Technology Center: Philadelphia Microsoft Technology Centers are collaborative, state-of-the-art facilities

More information

Liebert CRV Row-Based Cooling Intelligent Precision Cooling For Data Center Equipment. Precision Cooling For Business-Critical Continuity

Liebert CRV Row-Based Cooling Intelligent Precision Cooling For Data Center Equipment. Precision Cooling For Business-Critical Continuity Liebert Row-Based Cooling Intelligent Precision Cooling For Data Center Equipment Precision Cooling For Business-Critical Continuity The Intelligent Data Center Cooling Solution: Liebert Trust the industry

More information

Scalable. Affordable. Flexible. Fast.

Scalable. Affordable. Flexible. Fast. Modular Data Center Solutions Scalable. Affordable. Flexible. Fast. Build the data center you need today with the flexibility to meet tomorrow s challenges The only constant in business is change. Fluctuations

More information

Power Management Strategies for High-Density IT Facilities and Systems. A White Paper from the Experts in Business-Critical Continuity TM

Power Management Strategies for High-Density IT Facilities and Systems. A White Paper from the Experts in Business-Critical Continuity TM Power Management Strategies for High-Density IT Facilities and Systems A White Paper from the Experts in Business-Critical Continuity TM Executive Summary Increases in data center density and diversity

More information

Protecting Our Information, Protecting Our Resources

Protecting Our Information, Protecting Our Resources Solutions For Business-Critical Continuity Protecting Our Information, Protecting Our Resources Energy Efficient Power And Cooling For IT And Telecommunications Network Infrastructures The Challenge You

More information

Seven Best Practices for Increasing Efficiency, Availability and Capacity: The Enterprise Data Center Design Guide

Seven Best Practices for Increasing Efficiency, Availability and Capacity: The Enterprise Data Center Design Guide Seven Best Practices for Increasing Efficiency, Availability and Capacity: The Enterprise Data Center Design Guide A White Paper from the Experts in Business-Critical Continuity TM Table of Contents Introduction...

More information

Energy Efficient Cooling Solutions for Data Centers

Energy Efficient Cooling Solutions for Data Centers A White Paper from the Experts in Business-Critical Continuity TM Energy Efficient Cooling Solutions for Data Centers Introducing an Emerson Network Power tool for evaluating cooling system total cost

More information

Maximizing Data Center Efficiency, Capacity and Availability through Integrated Infrastructure

Maximizing Data Center Efficiency, Capacity and Availability through Integrated Infrastructure Maximizing Data Center Efficiency, Capacity and Availability through Integrated Infrastructure Efficiencies and Cost Benefits Intrinsic to Integrated Infrastructure Solutions A White Paper from the Experts

More information

How To Run A Data Center Efficiently

How To Run A Data Center Efficiently Seven Best Practices for Increasing Efficiency, Availability and Capacity: The Enterprise Data Center Design Guide A White Paper from the Experts in Business-Critical Continuity TM Table of Contents Introduction...

More information

How To Make A Data Center More Efficient

How To Make A Data Center More Efficient IT Solutions for Business-Critical Continuity Emerson Network Power Data Center Infrastructure Many Needs. One Source. Emerson Network Power, a division of Emerson Electric Co., is a global company that

More information

Data Center Infrastructure Management Managing the Physical Infrastructure for Greater Efficiency

Data Center Infrastructure Management Managing the Physical Infrastructure for Greater Efficiency Data Center Infrastructure Management Managing the Physical Infrastructure for Greater Efficiency Infrastructure Management & Monitoring for Business-Critical Continuity TM DATA CENTER INFRASTRUCTURE MANAGEMENT

More information

How To Save Energy On A Power Supply

How To Save Energy On A Power Supply Technical Note: Using EC Plug Fans to Improve Energy Efficiency of Chilled Water Cooling Systems in Large Data Centers A Technical Note from the Experts in Business-Critical Continuity Introduction A U.S.

More information

IT White Paper MANAGING EXTREME HEAT: COOLING STRATEGIES FOR HIGH-DENSITY SYSTEMS

IT White Paper MANAGING EXTREME HEAT: COOLING STRATEGIES FOR HIGH-DENSITY SYSTEMS IT White Paper MANAGING EXTREME HEAT: COOLING STRATEGIES FOR HIGH-DENSITY SYSTEMS SUMMARY As computer manufacturers pack more and more processing power into smaller packages, the challenge of data center

More information

Liebert CW 26-181kW Chilled Water Cooled Precision Air Conditioning For Data Centers

Liebert CW 26-181kW Chilled Water Cooled Precision Air Conditioning For Data Centers Liebert CW 26-181kW Chilled Water Cooled Precision Air Conditioning For Data Centers Precision Cooling For Business-Critical Continuity A Chilled Water Precision System That Handles The Most Demanding

More information

Liebert : The Right Cooling For IT Environments. Precision Cooling For Business-Critical Continuity

Liebert : The Right Cooling For IT Environments. Precision Cooling For Business-Critical Continuity Liebert : The Right Cooling For IT Environments Precision Cooling For Business-Critical Continuity New Challenges To IT System Uptime Many IT professionals are finding that dedicated precision cooling

More information

HESS Corporation. Background. Case Summary. Results

HESS Corporation. Background. Case Summary. Results Background HESS increasingly depends on technology to support oil exploration and production. When the company first transitioned from mainframe to blade server technology for its most intense processing

More information

Virginia Tech. Background. Case Summary. Results

Virginia Tech. Background. Case Summary. Results Background Virginia Tech When Virginia Tech initiated plans to build a supercomputer by clustering hundreds of desktop computers, it had ambitious goals for the performance of the new system and a very

More information

Modular architecture for high power UPS systems. A White Paper from the experts in Business-Critical Continuity

Modular architecture for high power UPS systems. A White Paper from the experts in Business-Critical Continuity Modular architecture for high power UPS systems A White Paper from the experts in Business-Critical Continuity Abstract Today, more than ever before, energy efficiency and cost-savings are among the top

More information

Liebert CRV Row-Based Cooling Intelligent Precision Cooling For Data Center Equipment

Liebert CRV Row-Based Cooling Intelligent Precision Cooling For Data Center Equipment Liebert CRV Row-Based Cooling Intelligent Precision Cooling For Data Center Equipment The Intelligent Data Center Cooling Solution: Liebert CRV Trust the industry leader in Precision Cooling to deliver

More information

Liebert APM from 30-150 kw. The Compact Row-Based UPS With FlexPower Technology TM

Liebert APM from 30-150 kw. The Compact Row-Based UPS With FlexPower Technology TM Liebert APM from 30-150 kw The Compact Row-Based UPS With FlexPower Technology TM Emerson Network Power, a division of Emerson, is a global company that combines technology with design to supply innovative

More information

DataCenter.BZ. Background. Case Summary. & dark fiber solutions

DataCenter.BZ. Background. Case Summary. & dark fiber solutions A Customer Success from the Experts in Business-Critical Continuity TM. DataCenter.BZ & dark fiber solutions Background Headquartered in Columbus, Ohio, DataCenter.BZ provides enterprisegrade data center

More information

Hospital IT and Facilities Special Report Top concerns in the hospital include budget, power requirements

Hospital IT and Facilities Special Report Top concerns in the hospital include budget, power requirements Hospital IT and Facilities Special Report Top concerns in the hospital include budget, power requirements A White Paper from the Experts in Business-Critical Continuity Executive Summary Budget and power

More information

Economizer Fundamentals: Smart Approaches to Energy-Efficient Free-Cooling for Data Centers

Economizer Fundamentals: Smart Approaches to Energy-Efficient Free-Cooling for Data Centers A White Paper from the Experts in Business-Critical Continuity TM Economizer Fundamentals: Smart Approaches to Energy-Efficient Free-Cooling for Data Centers Executive Summary The strategic business importance

More information

Ten Steps to Increasing Data Center Efficiency and Availability through Infrastructure Monitoring

Ten Steps to Increasing Data Center Efficiency and Availability through Infrastructure Monitoring Ten Steps to Increasing Data Center Efficiency and Availability through Infrastructure Monitoring A White Paper from the Experts in Business-Critical Continuity Summary The first decade of the 21st century

More information

Liebert EFC from 100 to 350 kw. The Highly Efficient Indirect Evaporative Freecooling Unit

Liebert EFC from 100 to 350 kw. The Highly Efficient Indirect Evaporative Freecooling Unit Liebert EFC from 100 to 350 kw The Highly Efficient Indirect Evaporative Freecooling Unit Liebert EFC, the Highly Efficient Indirect Evaporative Freecooling Solution Emerson Network Power delivers innovative

More information

AIRAH Presentation April 30 th 2014

AIRAH Presentation April 30 th 2014 Data Centre Cooling Strategies The Changing Landscape.. AIRAH Presentation April 30 th 2014 More Connections. More Devices. High Expectations 2 State of the Data Center, Emerson Network Power Redefining

More information

Emerson Network Power Rack PDU Solutions Rack Power Distribution For Critical IT Equipment. AC Power For Business-Critical Continuity

Emerson Network Power Rack PDU Solutions Rack Power Distribution For Critical IT Equipment. AC Power For Business-Critical Continuity Emerson Network Power Rack PDU Solutions Rack Power Distribution For Critical IT Equipment AC Power For Business-Critical Continuity Enhanced Performance And Management Of Dynamic IT Spaces IT space is

More information

The Pros and Cons of Modular Systems

The Pros and Cons of Modular Systems The Pros and Cons of Modular Systems Kevin Brown, Vice President Global Data Center Offer Schneider Electric Schneider Electric 1 Foundational BUSINESS OVERVIEW Rev 2 Desired characteristics of pre-fabricated

More information

Data Center Precision Cooling: The Need For A Higher Level Of Service Expertise. A White Paper from the Experts in Business-Critical Continuity

Data Center Precision Cooling: The Need For A Higher Level Of Service Expertise. A White Paper from the Experts in Business-Critical Continuity Data Center Precision Cooling: The Need For A Higher Level Of Service Expertise A White Paper from the Experts in Business-Critical Continuity Executive Summary Today s data centers are changing rapidly,

More information

How To Run A Data Center Efficiently

How To Run A Data Center Efficiently A White Paper from the Experts in Business-Critical Continuity TM Data Center Cooling Assessments What They Can Do for You Executive Summary Managing data centers and IT facilities is becoming increasingly

More information

Knürr DCL Modular Rack Cooling from 6 kw to 60 kw

Knürr DCL Modular Rack Cooling from 6 kw to 60 kw Knürr DCL Modular Rack Cooling from 6 kw to 60 kw Emerson Network Power Business-Critical Continuity so your success continues! Core competencies AC Power Connectivity DC Power Embedded Computing Embedded

More information

In Row Cooling Options for High Density IT Applications

In Row Cooling Options for High Density IT Applications In Row Cooling Options for High Density IT Applications By Ramzi Y. Namek, PE, LEED AP, BD+C; Director of Engineering 1 Users wishing to deploy high density IT racks have several In Row Cooling solutions

More information

Future-Proof the Banking and Finance Data Center

Future-Proof the Banking and Finance Data Center Future-Proof the Banking and Finance Data Center Reinier Dungca Rey Perea Marketing Manager, Southeast Asia and North Asia Manager, Local Technical Support Emerson Network Power Emerson Network Power Philippines

More information

Ten Steps to Increasing Data Center Efficiency and Availability through Infrastructure Monitoring

Ten Steps to Increasing Data Center Efficiency and Availability through Infrastructure Monitoring Ten Steps to Increasing Data Center Efficiency and Availability through Infrastructure Monitoring A White Paper from the Experts in Business-Critical Continuity Summary The first decade of the 21st century

More information

Data Center Infrastructure Management Managing the Physical Infrastructure for Greater Efficiency

Data Center Infrastructure Management Managing the Physical Infrastructure for Greater Efficiency Data Center Infrastructure Management Managing the Physical Infrastructure for Greater Efficiency Infrastructure Management & Monitoring for Business-Critical Continuity TM DATA CENTER INFRASTRUCTURE MANAGEMENT

More information

DCIM Readiness on the Rise as Significant Data Center Capacity Remains Unused. A Research Report from the Experts in Business-Critical Continuity TM

DCIM Readiness on the Rise as Significant Data Center Capacity Remains Unused. A Research Report from the Experts in Business-Critical Continuity TM DCIM Readiness on the Rise as Significant Data Center Capacity Remains Unused A Research Report from the Experts in Business-Critical Continuity TM Introduction Data center management is in a stage of

More information

Proper Application of 415V Systems in North American Data Centers. A White Paper from the Experts in Business-Critical Continuity

Proper Application of 415V Systems in North American Data Centers. A White Paper from the Experts in Business-Critical Continuity Proper Application of 415V Systems in North American Data Centers A White Paper from the Experts in Business-Critical Continuity Introduction Increasing pressure to reduce operating expenses and be more

More information

How To Improve Energy Efficiency In Data Center Management

How To Improve Energy Efficiency In Data Center Management A White Paper from the Experts in Business-Critical Continuity TM Data Center Users Group Special Report Energy efficiency and capacity concerns increase Fall 2012 Survey Results Executive Summary The

More information

Revolutionizing Data Center Infrastructure Management

Revolutionizing Data Center Infrastructure Management Infrastructure Management & Monitoring for Business-Critical Continuity TM Revolutionizing Data Center Infrastructure Management The Trellis Platform A Real-Time Solution to Continuous Performance Improvement

More information

Data Center Solutions - The Containerized Evolution

Data Center Solutions - The Containerized Evolution Data Center Solutions - The Containerized Evolution Power IT Cooling 7 th Green Connected World Tsikogias Thanassis Data Centers Solutions Architect, IT Business Athens 2015 1 We are the global specialist

More information

Data Center Technology: Physical Infrastructure

Data Center Technology: Physical Infrastructure Data Center Technology: Physical Infrastructure IT Trends Affecting New Technologies and Energy Efficiency Imperatives in the Data Center Hisham Elzahhar Regional Enterprise & System Manager, Schneider

More information

Data Center Rack Systems Key to Business-Critical Continuity. A White Paper from the Experts in Business-Critical Continuity TM

Data Center Rack Systems Key to Business-Critical Continuity. A White Paper from the Experts in Business-Critical Continuity TM Data Center Rack Systems Key to Business-Critical Continuity A White Paper from the Experts in Business-Critical Continuity TM Executive Summary At one time, data center rack enclosures and related equipment

More information

Five Strategies for Cutting Data Center Energy Costs Through Enhanced Cooling Efficiency

Five Strategies for Cutting Data Center Energy Costs Through Enhanced Cooling Efficiency Five Strategies for Cutting Data Center Energy Costs Through Enhanced Cooling Efficiency A White Paper from the Experts in Business-Critical Continuity TM Executive Summary As electricity prices and IT

More information

Liebert Data Center Services. Services For Business-Critical Continuity

Liebert Data Center Services. Services For Business-Critical Continuity Liebert Data Center Services Services For Business-Critical Continuity Emerson Network Power Liebert Services, Your Data Center Services Expert The Strength and Resources of Emerson Emerson, a 150 year

More information

Precision Cooling for Business-Critical Continuity. Liebert PCW. Cool the Cloud

Precision Cooling for Business-Critical Continuity. Liebert PCW. Cool the Cloud Precision Cooling for Business-Critical Continuity Cool the Cloud Whether a data center houses three or 1000 IT racks, deployment of new technologies with high power densities are impacting the power and

More information

How To Get The Most Out Of Your Data Center Service From Liebert

How To Get The Most Out Of Your Data Center Service From Liebert Data Center Services Liebert Services For Business-Critical Continuity Liebert Services, Your Data Center Services Expert The Strength and Resources of Emerson Emerson, a 150 year old, FORTUNE 120 company

More information

Data Centre Testing and Commissioning

Data Centre Testing and Commissioning Data Centre Testing and Commissioning What is Testing and Commissioning? Commissioning provides a systematic and rigorous set of tests tailored to suit the specific design. It is a process designed to

More information

CUSTOMER EXPERIENCE CENTER

CUSTOMER EXPERIENCE CENTER v CUSTOMER EXPERIENCE CENTER ABOUT THE CUSTOMER EXPERIENCE CENTER MAKE YOUR DATA CENTER AS DYNAMIC AS YOUR BUSINESS Emerson Network Power continuously strives to provide the best solutions by working collaboratively

More information

GREEN DATA CENTER DESIGN

GREEN DATA CENTER DESIGN Jeffrey Menig Global Facilities Facility Engineering The application of multiple available technologies resulting in improved energy optimization without significantly increasing capital investment. A

More information

Creating an IT Infrastructure that Adapts to Your Business PLAYBOOK

Creating an IT Infrastructure that Adapts to Your Business PLAYBOOK Creating an IT Infrastructure that Adapts to Your Business PLAYBOOK F O R C H A N G E For decades, data centers have been over-provisioned two or even three times over in an attempt to plan for growth.

More information

Title: Design of a Shared Tier III+ Data Center: A Case Study with Design Alternatives and Selection Criteria

Title: Design of a Shared Tier III+ Data Center: A Case Study with Design Alternatives and Selection Criteria Tier 3+ 1 Title: Design of a Shared Tier III+ Data Center: A Case Study with Design Alternatives and Selection Criteria Abstract: Schoolcraft College is constructing a High Availability (HA) Data Center

More information

DISCONTINUED PRODUCT. Infrastructure Management & Monitoring For Business-Critical Continuity. Liebert icom-do. User Manual

DISCONTINUED PRODUCT. Infrastructure Management & Monitoring For Business-Critical Continuity. Liebert icom-do. User Manual Infrastructure Management & Monitoring For Business-Critical Continuity Liebert icom-do User Manual TABLE OF CONTENTS 1.0 INTRODUCTION............................... 1 2.0 INSTALLATION...............................

More information

National Grid Your Partner in Energy Solutions

National Grid Your Partner in Energy Solutions National Grid Your Partner in Energy Solutions National Grid Webinar: Enhancing Reliability, Capacity and Capital Expenditure through Data Center Efficiency April 8, 2014 Presented by: Fran Boucher National

More information

Reducing Data Center Energy Consumption

Reducing Data Center Energy Consumption Reducing Data Center Energy Consumption By John Judge, Member ASHRAE; Jack Pouchet, Anand Ekbote, and Sachin Dixit Rising data center energy consumption and increasing energy costs have combined to elevate

More information

Data Center Components Overview

Data Center Components Overview Data Center Components Overview Power Power Outside Transformer Takes grid power and transforms it from 113KV to 480V Utility (grid) power Supply of high voltage power to the Data Center Electrical Room

More information

Energy Efficiency and Availability Management in Consolidated Data Centers

Energy Efficiency and Availability Management in Consolidated Data Centers Energy Efficiency and Availability Management in Consolidated Data Centers Abstract The Federal Data Center Consolidation Initiative (FDCCI) was driven by the recognition that growth in the number of Federal

More information

CANNON T4 MINI / MICRO DATA CENTRE SYSTEMS

CANNON T4 MINI / MICRO DATA CENTRE SYSTEMS CANNON T4 MINI / MICRO DATA CENTRE SYSTEMS Air / Water / DX Cooled Cabinet Solutions Mini Data Centre All in One Solution: Where there is a requirement for standalone computing and communications, or highly

More information

Enterprise Remote Monitoring

Enterprise Remote Monitoring Enterprise Remote Monitoring Alarm Management, Predictive Maintenance, Advanced Network Security Services For Business-Critical Continuity Can You Really Afford Not To Know? Loss of productivity and the

More information

Optimum Climate Control For Datacenter - Case Study. T. Prabu March 17 th 2009

Optimum Climate Control For Datacenter - Case Study. T. Prabu March 17 th 2009 Optimum Climate Control For Datacenter - Case Study T. Prabu March 17 th 2009 Agenda 2 About EDEC (Emerson) Facility Data Center Details Design Considerations & Challenges Layout Design CFD Analysis Of

More information

Best in class: Designing and delivering Emerson s state-of-the-art global data center

Best in class: Designing and delivering Emerson s state-of-the-art global data center Best in class: Designing and delivering Emerson s state-of-the-art global data center A Customer Success Background As computing and IT technology increasingly enabled real-time global business operations

More information

Managing Data Centre Heat Issues

Managing Data Centre Heat Issues Managing Data Centre Heat Issues Victor Banuelos Field Applications Engineer Chatsworth Products, Inc. 2010 Managing Data Centre Heat Issues Thermal trends in the data centre Hot Aisle / Cold Aisle design

More information

Unified Infrastructure Monitoring, Access and Control

Unified Infrastructure Monitoring, Access and Control A White Paper from the Experts in Business-Critical Continuity Unified Infrastructure Monitoring, Access and Control Streamline Infrastructure Management with a Single, Multi-Purpose Appliance the Avocent

More information

Dealing with Thermal Issues in Data Center Universal Aisle Containment

Dealing with Thermal Issues in Data Center Universal Aisle Containment Dealing with Thermal Issues in Data Center Universal Aisle Containment Daniele Tordin BICSI RCDD Technical System Engineer - Panduit Europe Daniele.Tordin@Panduit.com AGENDA Business Drivers Challenges

More information

Power Distribution Considerations for Data Center Racks

Power Distribution Considerations for Data Center Racks Power Distribution Considerations for Data Center Racks Power Distribution Considerations for Data Center Racks Table of Contents 3 Overview 4 At what voltage do you run all the IT equipment? 4 What electrical

More information

Elements of Energy Efficiency in Data Centre Cooling Architecture

Elements of Energy Efficiency in Data Centre Cooling Architecture Elements of Energy Efficiency in Data Centre Cooling Architecture Energy Efficient Data Center Cooling 1 STULZ Group of Companies Turnover 2006 Plastics Technology 400 Mio A/C Technology 200 Mio Total

More information

Blade Servers and Beyond: Adaptive Cooling for the Next Generation of IT Systems. A White Paper from the Experts in Business-Critical Continuity

Blade Servers and Beyond: Adaptive Cooling for the Next Generation of IT Systems. A White Paper from the Experts in Business-Critical Continuity Blade Servers and Beyond: Adaptive Cooling for the Next Generation of IT Systems A White Paper from the Experts in Business-Critical Continuity Executive Summary In enterprise data centers, designers face

More information

The High Performance Floormount Indoor Package Cooling Solution. Precision Cooling for Business-Critical Continuity

The High Performance Floormount Indoor Package Cooling Solution. Precision Cooling for Business-Critical Continuity Liebert HPF The High Performance Floormount Indoor Package Cooling Solution Precision Cooling for Business-Critical Continuity We re Emerson Network Power, backed by Emerson, a global company that brings

More information

Green Data Centre Design

Green Data Centre Design Green Data Centre Design A Holistic Approach Stantec Consulting Ltd. Aleks Milojkovic, P.Eng., RCDD, LEED AP Tommy Chiu, EIT, RCDD, LEED AP STANDARDS ENERGY EQUIPMENT MATERIALS EXAMPLES CONCLUSION STANDARDS

More information

DATA CENTER COOLING INNOVATIVE COOLING TECHNOLOGIES FOR YOUR DATA CENTER

DATA CENTER COOLING INNOVATIVE COOLING TECHNOLOGIES FOR YOUR DATA CENTER DATA CENTER COOLING INNOVATIVE COOLING TECHNOLOGIES FOR YOUR DATA CENTER DATA CENTERS 2009 IT Emissions = Aviation Industry Emissions Nations Largest Commercial Consumers of Electric Power Greenpeace estimates

More information

Containerized Infrastructure Solutions Fast and efficient deployment, anywhere, anytime

Containerized Infrastructure Solutions Fast and efficient deployment, anywhere, anytime Containerized Infrastructure Solutions Fast and efficient deployment, anywhere, anytime Containerized Infrastructure for Business-Critical Continuity Are you deploying a remote site faster than you can

More information

Rack Power Distribution For Critical IT Equipment More efficient Simpler Better

Rack Power Distribution For Critical IT Equipment More efficient Simpler Better Rack Power Distribution For Critical IT Equipment More efficient Simpler Better Enhanced Performance and Management of Dynamic IT Spaces Enhance Business Agility, Efficiency and Availability with Emerson

More information

DATA CENTER ASSESSMENT SERVICES

DATA CENTER ASSESSMENT SERVICES DATA CENTER ASSESSMENT SERVICES ig2 Group Inc. is a Data Center Science Company which provides solutions that can help organizations automatically optimize their Data Center performance, from assets to

More information

Opportunity of Energy Saving in electrical path is lesser as compared to other areas

Opportunity of Energy Saving in electrical path is lesser as compared to other areas Data Centre Power Map ` Energy Optimization Techniques Data Center Power Chain Venkat Rao B Country Manager Power Products Data Center Power Draws Cooling About 35 40 % Sources of Energy Waste Fans / Blowers

More information

IN YOUR OFFICE SPACE DEPLOY A DATA CENTER. Don t Let Desktop Systems Threaten Your Network Security pg.12. Use DCIM To Reduce Data Center Risk pg.

IN YOUR OFFICE SPACE DEPLOY A DATA CENTER. Don t Let Desktop Systems Threaten Your Network Security pg.12. Use DCIM To Reduce Data Center Risk pg. DEPLOY A DATA CENTER IN YOUR OFFICE SPACE Trends for the Data Center 2015 pg.2 Use DCIM To Reduce Data Center Risk pg.4 Don t Let Desktop Systems Threaten Your Network Security pg.12 Spring 2015 Welcome!

More information

Liebert GXT MT+ CX UPS, 1000VA - 3000VA Intelligent, Reliable UPS Protection. AC Power for Business-Critical Continuity

Liebert GXT MT+ CX UPS, 1000VA - 3000VA Intelligent, Reliable UPS Protection. AC Power for Business-Critical Continuity Liebert GXT MT+ CX UPS, 1000VA - 3000VA Intelligent, Reliable UPS Protection AC Power for Business-Critical Continuity Liebert GXT MT+ CX UPS, 1000VA -3000VA Intelligent, Reliable UPS Protection Liebert

More information

The Four Trends Driving the Future of Data Center Infrastructure Design and Management

The Four Trends Driving the Future of Data Center Infrastructure Design and Management The Four Trends Driving the Future of Data Center Design and Management A White Paper from the Experts in Business-Critical Continuity TM Introduction Throughout the first decade of the 21st century, countless

More information

IPSIP M series-m Modular Data Center

IPSIP M series-m Modular Data Center IPSIP M series-m Modular Data Center IPSIP MODULAR TECHNOLOGIES. 1 With the rapid development of cloud computing and mobile Internet businesses, the growth of IT density and energy consumption are bringing

More information

Applying Proper Cable Management In IT Racks A Guide For Planning, Deployment And Growth

Applying Proper Cable Management In IT Racks A Guide For Planning, Deployment And Growth Applying Proper Cable Management In IT Racks A Guide For Planning, Deployment And Growth Integrated Cabinet Solutions For Business-Critical Continuity Why Proper Cable Management Is So Important Your rack

More information

Re Engineering to a "Green" Data Center, with Measurable ROI

Re Engineering to a Green Data Center, with Measurable ROI Re Engineering to a "Green" Data Center, with Measurable ROI Alan Mamane CEO and Founder Agenda Data Center Energy Trends Benchmarking Efficiency Systematic Approach to Improve Energy Efficiency Best Practices

More information

Data Center Planning. PUE Overview

Data Center Planning. PUE Overview Data Center Planning PUE Overview Steve Carter, Americas Managing Principal Charles Prawdzik Jr., Project Manager HP Critical Facility Services delivered by EYP Mission Critical Facilities, Inc. 2008 Hewlett-Packard

More information

Considerations for a Highly Available Intelligent Rack Power Distribution Unit. A White Paper on Availability

Considerations for a Highly Available Intelligent Rack Power Distribution Unit. A White Paper on Availability Considerations for a Highly Available Intelligent Rack Power Distribution Unit A White Paper on Availability Introduction Data centers are currently undergoing a period of great change. Data center managers

More information

Our data centres have been awarded with ISO 27001:2005 standard for security management and ISO 9001:2008 standard for business quality management.

Our data centres have been awarded with ISO 27001:2005 standard for security management and ISO 9001:2008 standard for business quality management. AIMS is Malaysia and South East Asia s leading carrier neutral data centre operator and managed services provider. We provide international class data storage and ancillary services, augmented by an unrivaled

More information

A White Paper from the Experts in Business-Critical Continuity TM. Best Practices in Protecting the Technology Systems Revolutionizing Healthcare

A White Paper from the Experts in Business-Critical Continuity TM. Best Practices in Protecting the Technology Systems Revolutionizing Healthcare A White Paper from the Experts in Business-Critical Continuity TM Best Practices in Protecting the Technology Systems Revolutionizing Healthcare Executive Summary Technology systems such as electronic

More information

High-density modular data center making cloud easier. Frank Zheng Huawei

High-density modular data center making cloud easier. Frank Zheng Huawei High-density modular data center making cloud easier Frank Zheng Huawei 2012-10-10 Content 1 2 3 4 Cloud s impact to data center Concerns of DC construction 4S DC making cloud easier Success stories Cloud?

More information

PAYGO for Data Center -- Modular Infrastructure

PAYGO for Data Center -- Modular Infrastructure PAYGO for Data Center -- Modular Infrastructure Introduction The infrastructure costs for Data Centers are increasing at a significant pace. Construction costs and their environmental impact are also soaring.

More information

Energy Efficiency Opportunities in Federal High Performance Computing Data Centers

Energy Efficiency Opportunities in Federal High Performance Computing Data Centers Energy Efficiency Opportunities in Federal High Performance Computing Data Centers Prepared for the U.S. Department of Energy Federal Energy Management Program By Lawrence Berkeley National Laboratory

More information

Tour of new eircom Data Centre Blanchardstown by Dervan Engineering Consultants 11 th March 2015

Tour of new eircom Data Centre Blanchardstown by Dervan Engineering Consultants 11 th March 2015 Tour of new eircom Data Centre Blanchardstown by Dervan Engineering Consultants 11 th March 2015 Presentation Outline Mechanical Overview Chillers and Pumps Pipework and Ancillaries In Row Cooling Units

More information

Defining Quality. Building Comfort. Precision. Air Conditioning

Defining Quality. Building Comfort. Precision. Air Conditioning Defining Quality. Building Comfort. Precision Air Conditioning Today s technology rooms require precise, stable environments in order for sensitive electronics to operate optimally. Standard comfort air

More information

Data Centre Basiglio, Milan Flexible, advanced and efficient by design.

Data Centre Basiglio, Milan Flexible, advanced and efficient by design. Data Centre Basiglio, Milan Flexible, advanced and efficient by design. TelecityGroup Via Francesco Sforza 13 Milano 3 City 20080 Basiglio MI Italy Tel: +39 02 36679500 it.info@telecity.com www.telecitygroup.it

More information

AEGIS DATA CENTER SERVICES POWER AND COOLING ANALYSIS SERVICE SUMMARY

AEGIS DATA CENTER SERVICES POWER AND COOLING ANALYSIS SERVICE SUMMARY AEGIS DATA CENTER SERVICES POWER AND COOLING ANALYSIS SERVICE SUMMARY The Aegis Services Power and Assessment Service provides an assessment and analysis of your data center facility and critical physical

More information

Cooling Small Server Rooms Can Be. - Jim Magallanes Computer Room Uptime: www.cruptime.com Uptime Racks: www.uptimeracks.com

Cooling Small Server Rooms Can Be. - Jim Magallanes Computer Room Uptime: www.cruptime.com Uptime Racks: www.uptimeracks.com Cooling Small Server Rooms Can Be Inexpensive, Efficient and Easy - Jim Magallanes Computer Room Uptime: www.cruptime.com Uptime Racks: www.uptimeracks.com Server Rooms Description & Heat Problem Trends

More information

Free Cooling in Data Centers. John Speck, RCDD, DCDC JFC Solutions

Free Cooling in Data Centers. John Speck, RCDD, DCDC JFC Solutions Free Cooling in Data Centers John Speck, RCDD, DCDC JFC Solutions Why this topic Many data center projects or retrofits do not have a comprehensive analyses of systems power consumption completed in the

More information

Data Center Rack Level Cooling Utilizing Water-Cooled, Passive Rear Door Heat Exchangers (RDHx) as a Cost Effective Alternative to CRAH Air Cooling

Data Center Rack Level Cooling Utilizing Water-Cooled, Passive Rear Door Heat Exchangers (RDHx) as a Cost Effective Alternative to CRAH Air Cooling Data Center Rack Level Cooling Utilizing Water-Cooled, Passive Rear Door Heat Exchangers (RDHx) as a Cost Effective Alternative to CRAH Air Cooling Joshua Grimshaw Director of Engineering, Nova Corporation

More information

Liquid Cooling Solutions for DATA CENTERS - R.M.IYENGAR BLUESTAR LIMITED.

Liquid Cooling Solutions for DATA CENTERS - R.M.IYENGAR BLUESTAR LIMITED. Liquid Cooling Solutions for DATA CENTERS - R.M.IYENGAR BLUESTAR LIMITED. Presentation Goals & Outline Power Density Where we have been- where we are now - where we are going Limitations of Air Cooling

More information

RagingWire Enterprise Solutions

RagingWire Enterprise Solutions Background Enterprise Solutions was founded in May 2000 to be an enterprise-class Managed Services Provider (emsp) that could provide and support colocated data center services for Fortune 1000 customers.

More information

Business white paper. A new approach to industrialized IT. HP Flexible Data Center

Business white paper. A new approach to industrialized IT. HP Flexible Data Center Business white paper A new approach to industrialized IT HP Flexible Data Center Table of contents 4 Introduction 4 Levels of modularity 5 What is HP Flexible DC? 5 HP Flexible DC features 6 The core-and-quadrant

More information