ROOF DECK SECUREMENT AND ABOVE-DECK ROOF COMPONENTS

Size: px
Start display at page:

Download "ROOF DECK SECUREMENT AND ABOVE-DECK ROOF COMPONENTS"

Transcription

1 FM Global Property Loss Prevention Data Sheets 1-29 September 2010 Page1of40 ROOF DECK SECUREMENT AND ABOVE-DECK ROOF COMPONENTS Note to Insureds of Factory Mutual Insurance Company: Contact the local FM Global office before beginning any roofing work. Table of Contents Page 1.0 SCOPE Changes LOSS PREVENTION RECOMMENDATIONS Introduction Construction and Location General Vapor Retarders (Barriers)Design and Installation Recommendations Roof Insulation Insulation and Roof Cover Fasteners Recover and Reroof ConstructionDesign and Installation Recommendations Structural Concrete, FM Approved Fiber Reinforced Cement and Lightweight Insulating Concrete (LWIC) Decks: Design and Installation Recommendations Single-Ply Membrane Covers and Multi-Ply covers with Mechanically Attached Base Sheets Asphalt and BUR Installation Recommendations Roof Covers Adhered to Mechanically Attached Base SheetsFastener Installation Recommendations Liquid Applied Roof CoversInstallation Recommendations Mechanically Fastened Base Sheet Assemblies Over Wood DecksDesign and Installation Recommendations Roof Deck Span and Securement for Wind Loads Lightweight Insulating Concrete Roof Decks Cementitious Wood Fiber Roof Deck Recommendations Lumber and Plywood Deck Structural Concrete Roof Deck Recommendations Torch Application of Modified Bitumen Roof Covers Field Wind Uplift Tests Cold-Process Adhesives Fiberglass Reinforced Plastic (FRP) Roof Deck SUPPORT FOR RECOMMENDATIONS Supplemental Information Class 1 and 2 Roof Decks Wind Uplift Resistance, Non-Ballasted Roof Covers Wind Uplift Resistance, Ballasted Systems Compatibility With Substrate External Combustibility Recover Construction Wind Uplift Wind Damage Inferior Construction Steel Deck No part of this document may be reproduced, stored in a retrieval system, or transmitted, in whole or in part, in any form or by any means, electronic, mechanical, photocopying, recording, or otherwise, without written permission of Factory Mutual Insurance Company.

2 Page 2 FM Global Property Loss Prevention Data Sheets 4.0 REFERENCES FM Global Others APPENDIX A GLOSSARY OF TERMS APPENDIX B DOCUMENT REVISION HISTORY List of Figures Fig. 1. Hailstorm hazard map for United States (areas between dashed lines subject to severe hailstorms and need an SH hail rated roof) Fig. 2. Insulation and vapor barrier mechanically fastened to steel deck Fig. 3. Fastener placement 2 4 ft ( m) boards Fig. 4. Fastener placement 3 4 ft ( m) boards Fig. 5. Fastener placement 4 4 ft ( m) boards Fig. 6. Fastener placement 4 8 ft ( m) boards Fig. 7. Alternate corner increase for mechanically attached single-ply membranes Fig. 8. Fastener layout for 36 in. (914 mm) wide base sheet Fig. 9a. Side lap fastening: interlocking seam Fig. 9b. Side lap fastening: overlap seam Fig. 10. Two deck fasteners per support, one into each bar joist top flange Fig. 11. Torch application of upper ply to a mechanically fastened base sheet Note adhesive pooling at the leading edge of the roll Fig. 12a/12b. 4 4 ft ( m) insulation boards secured with nine fasteners per board List of Tables Table 1. Recommended Rating of Field, Perimeter, and Corner Areas (Zones 1, 2, and 3) for Enclosed Buildings... 5 Table 2. Weight Needed of No. 3 Round Stone Ballast, Parapet 36 in. (914 mm) Table 3. Weight Needed of No. 3 Round Stone Ballast, Parapet > 36 in. (914 mm) Table 4. Weight Needed of Paver Blocksnot T&G, Beveled or Strapped to Each Other, Parapet 36 in. (914 mm) Table 5. Weight Needed of Paver Blocksnot T&G, Beveled or Strapped to Each Other, Parapet > 36 in. (914 mm) Table 6. Weight Needed of Paver BlocksT&G, Beveled or Strapped to Each Other, Parapet 36 in. (914 mm) Table 7. Weight Needed of Paver BlocksT&G Beveled or Strapped to Each Other, Parapet > 36 in. (914 mm) Table 8. Base Sheet Fastener Coverage for Non-FM Approved Combinations, ft 2 per Fastener Table 9. Standard 36 in. (0.9 m) Base Sheet Fastening (Non-FM Approved Components). (See Fig. 8.). 24 Table 10. Minimum Metal Disk or Fastener Head Size (Base Sheet Fasteners) Table 11. Allowable 2 Uniform Uplift Pressure Table 12. Nail pullout strength per in. (25 mm) of penetration... 31

3 Roof Deck Securement and Above-Deck Roof Components 1-29 FM Global Property Loss Prevention Data Sheets Page SCOPE This data sheet provides recommendations for the proper securement of various roof decks to supporting members, and for the proper design and installation of above-deck roof components. Items covered include roof covers, insulation, vapor retarders, fasteners, and recover assemblies. This data sheet is intended to be used in conjunction with Data Sheet 1-28, Wind Design. Prefabricated panel roofs, lap seam, and standing seam roofs are covered in Data Sheet 1-31, Metal Roof Systems. Other data sheets with information on roofing include: Data Sheet 1-28, Wind Design Data Sheet 1-30, Repair of Wind Damaged Roof Systems Data Sheet 1-32, Existing PVC Roof Covers Data Sheet 1-33, Safeguarding Torch-Applied Roof Installations Data Sheet 1-49, Perimeter Flashing Data Sheet 1-52, Field Uplift Tests Data Sheet 1-54, Roof Loads For New Construction (which covers positive [snow, ponding] loads) For roofs of buildings divided by maximum foreseeable loss (MFL) fire walls, refer to Data Sheet 1-22, Criteria for Maximum Foreseeable Loss Fire Walls and Space Separation. 1.1 Changes September Minor editorial changes were made for this revision. 2.0 LOSS PREVENTION RECOMMENDATIONS 2.1 Introduction The recommendations provided in this document are not intended to supersede the requirements of any FM Approval (see Appendix A for definition). FM Approval listings outline the field-of-roof securement requirements. Some listings also may contain specific roof corner/perimeter fastening methods. This data sheet outlines other roof perimeter/corner fastening methods. Use the recommendations to supplement the listings in the Approval Guide, a publication of FM Approvals. Where appropriate, recommendations are grouped in each section as Design, Installation, and Maintenance. Roof systems are FM Approved only for certain wind uplift ratings. All recommendations are for systems used within their FM Approval limits. Generally, recommendations regarding internal fire ratings (Class 1 or 2) are not applicable to structural concrete and gypsum roof decks, as these decks are rated noncombustible (internally) regardless of the above-deck components due to the substantial thermal barrier offered by the deck itself. Form boards used with gypsum decks may themselves be combustible. 2.2 Construction and Location General These recommendations are applicable to all systems except as noted Design Recommendations Except for ballasted systems that are not FM Approved, ensure all installations use components and systems (roof deck, insulation, fasteners, roof cover, etc.) that are FM Approved for use together on the particular deck. Use of individually FM Approved components, not FM Approved for use together, does not

4 Page 4 FM Global Property Loss Prevention Data Sheets constitute an FM Approved or recommended assembly. Use of FM Approved systems is universally recommended and is implied for all applicable assemblies whether or not specifically stated in the recommendation All FM Approved materials are required to have the FM Approval mark on the packaging or the material itself. Materials without proper labeling are not FM Approved and cannot be accepted Ensure the roof deck design and installation are in accordance with the Approval Guide, RoofNav and Data Sheets 1-28, Wind Design, 1-49, Perimeter Flashing (and 1-31, Metal Roof Systems, where applicable) Use FM Approved perimeter flashing systems, where available. Secure wood nailers in accordance with Data Sheet 1-49, Perimeter Flashing, and follow other guidelines in that document where FM Approved flashings are not available Ensure roof slope is a minimum of 1 ( 1 4 in./ft, 21 mm/m). This can be accomplished by varying the column heights or using an FM Approved tapered insulation system. Refer to Data Sheet 1-54, Roof Loads for New Construction Installation Recommendations It is essential that thorough supervision by the building owner s qualified representative is provided during all roof construction to ensure quality of workmanship and adherence to FM Approval standards and project specifications When installing torch-applied roof covers, follow the recommendations in Data Sheet 1-33, Safeguarding Torch-Applied Roof Installation, and recommendation Do not store combustible roofing materials in buildings under construction unless an adequate sprinkler system is in service. Use combustible adhesives and solvents with caution. Use FM Approved safety cans where appropriate. Do not allow smoking on roofs at any time. Do not allow flammable liquids or solvents to enter confined spaces. Ensure the facility s emergency response team oversees all roofing work Make a minimum of two 10 lb (4.5 kg) ABC fire extinguishers available on the roof during roof construction and repairs Due to possible high concentrated loads from the rolls of membrane and gravel carts, caution is needed when moving these materials across the roof. To prevent over-stressing the deck when the weight of individual rolls of single-ply membrane exceeds 1100 lb (500 kg), use precautions such as shorter deck spans or plywood sheets over steel deck to reduce point loads Fill the space between nailers in roof expansion joints with noncombustible, compressible insulation such as glass, mineral, or ceramic fiber type Provide adequate separation and/or noncombustible insulation between hot exhaust stacks and combustible roof deck and above deck roof components. See DS 1-13, Chimneys, for details Ensure roof insulation or cover boards are dry and surfaces are free of debris or dirt prior to adhering roof covers to them. This will help ensure complete adhesion of the cover to its substrate Maintenance Recommendation Inspect roof systems and flashing semi-annually and after storms. During inspection, note and repair any holes or deterioration of the covering, opened seams, backed-out fasteners, loose anchorages, loose flashing, membrane shrinkage, etc. Replace any wet insulation when making roof repairs. Inspect and clean drains as needed. Maintain written records Wind Uplift Resistance: Design Recommendations Determine the roof wind uplift design pressure and recommended FM Approvals wind uplift ratings for roof assemblies (decks and above-deck components) per Data Sheet 1-28, Wind Design or RoofNav Ratings Calculator. Do not use any system beyond its FM Approval rating, except where enhancements are allowed by this document.

5 Roof Deck Securement and Above-Deck Roof Components 1-29 FM Global Property Loss Prevention Data Sheets Page Ensure all new, re-roof, and recover construction uses an appropriate wind-uplift-rated FM Approved roof system where available. Ensure the roof field fastening is per FM Approvals RoofNav listing. Note: For ballasted systems, see sections to Because there are higher uplift forces on the roof corners and perimeter, these areas need additional securement over that, which is FM Approved for the field of the roof. Refer to Data Sheet 1-28 for corner/perimeter definitions and dimensions. Ensure any whole or partial insulation board or roof cover/base sheet width (when the roll is parallel to the building edge) that falls within the calculated perimeter or corner has the increased securement applied over the entire board or roof cover/base sheet width. There are several acceptable methods for increasing the uplift resistance of the roof in the corners and perimeters. Do one of the following: Where the FM Approvals RoofNav listing includes a roof perimeter and/or corner fastening method, it can be used. Use a roof system with the appropriate FM Approval wind uplift rating in each area per Table 1. Use the appropriate prescriptive recommendation noted in section , within the limits of acceptability. An alternative is to use an adhered roof cover (adhered across the entire roof) that is adequately wind rated for the field of the roof and, in the perimeter and corner areas, use a mechanically attached roof cover (see Table 1 and ) that is either: a) FM Approved for wind pressures in the perimeter and corner areas, or b) FM Approved for the field of roof pressure per Table 1 and enhanced in the perimeter and corner areas per recommendation by reducing the distance between rows of fasteners. In either case a) or b) above, fasten a termination bar over the cover or base sheet (with suitable weatherproofing provided) and into the deck every 6 in. (150 mm) on center. Use minimum no. 15 screws at the junction of the fully adhered areas with the adhered and mechanically fastened areas. Table 1. Recommended Rating of Field, Perimeter, and Corner Areas (Zones 1, 2, and 3) for Enclosed Buildings Minimum Wind Rating for FM Approved Deck/Above-Deck/Entire 1 Assembly Roof Field Area Design Pressure, p, (psf) 2 Roof Field Area Enclosed Bldg. Roof Perimeter Area Enclosed Bldg. Roof Corner Area Enclosed Bldg. p <p < p <p < p <p < p <p < p <p < p <p < p <p < p Base the minimum wind rating on the roof field area rating when perimeter/corner areas are enhanced per this data sheet and other pertinent FM Global Data Sheets (1-29, 1-31, etc.). Base the minimum wind rating on the respective area rating when perimeter/corner area enhancements are not done, or are not acceptable. 2 For roofs with higher field area design pressures, or to interpolate needed perimeter and corner ratings when the field requirements are between levels, multiply the needed field area design pressure from Table 3, 4 or 5 (of D.S. 1-28) by a safety factor of 2.0 and the respective pressure coefficient per Table 6 of D.S. 1-28, and round up to the next highest 15 psf rating interval. 3 Ratings above apply to enclosed buildings, with roof slopes 7 and roof heights 60 ft (18 m).

6 Page 6 FM Global Property Loss Prevention Data Sheets Prescriptive Enhancement Options: Perimeter and Corner a) For all deck types, where roof covers are adhered to some combination of mechanically fastened insulation, cover board, or thermal barriers, prescriptive enhancements may be used for securement of the perimeter and corner areas, as long as one of the conditions below applies: 1. The building is in a non-hurricane prone region where the design wind speed does not exceed 90 mph and the roof height does not exceed 75 ft (23 m). Note the roof height is limited to 30 ft (9.1 m) if the building is located in surface roughness exposure D (see DS 1-28) and the building is partially enclosed. Or, 2. The recommended field of roof rating needed per DS 1-28 does not exceed Class 1-75 (3.6 kpa). Or, 3. The building is in a non-hurricane-prone region (see Appendix A) and the recommended field of roof rating per DS 1-28 does not exceed Class 1-90 (4.3 kpa). For any of the three conditions above, increase the number of fasteners per board over the FM Approved field-of-roof spacing by the following: 50% minimum in the roof perimeter, but at least one fastener per 2 ft 2 (1 per 0.19 m 2 ). It is not necessary to install fasteners closer than one per 1 ft 2 (1 per 0.09 m 2 ). One fastener per 1 ft 2 (1 per 0.09 m 2 ) in corner areas. Round up to the next whole number of fasteners, if necessary b) For all locations (including hurricane-prone regions), where a Class 1-90 wind rated system is needed for the field-of-roof, use the following generic assemblies in the perimeter and corner areas to provide acceptable wind resistance in those areas: Option 1 Minimum in. (38 mm) thick, FM Approved, Class 1 insulation laid loose directly on the deck. Minimum 1 2 in. (12. 7 mm) thick, FM Approved, water resistant, primed (factory or field primed) gypsum cover board over the insulation. Primer can be omitted if roof cover / coverboard combination meets a Class or greater without a primer. Through-fasten both layers to the steel deck with FM Approved minimum No. 14 ( 1 4 in., 6.4 mm) screws and flat-bottom metal stress plates. Use 24 fasteners per 4 by 8 ft (1.2 by 2.4 m) board in the perimeter, and 32 fasteners per 4 by 8 ft (1.2 by 2.4 m) board in the corners. Roof cover a fully mopped, minimum 3-ply BUR; or a minimum 2-ply mod bit system with all plies fully mopped and/or torch applied per FM Approval requirements. Option 2 Minimum 2 in. (50 mm) thick, FM Approved, Class 1 insulation laid loose directly on the deck. Note: a lesser insulation thickness may be used if included in any Class 1 fire-rated assembly with the other components above it, but not less than in. (38 mm) thick. Minimum 7 16 in. (11.1 mm) thick, oriented strand board (OSB) cover board over the insulation. Ensure the OSB is APA (American Plywood Association) rated for Exposure 1, with exterior type adhesive. Through-fasten both layers to the steel deck with FM Approved minimum No. 14 ( 1 4 in., 6.4 mm) screws and flat-bottom metal stress plates. Note: if screws have oversized heads and are specifically approved for OSB or OSB composite boards, stress plates are not required. Use 24 fasteners per 4 by 8 ft (1.2 by 2.4 m) board in the perimeter, and 32 fasteners per 4 by 8 ft (1.2 by 2.4 m) board in the corners. Roof cover a minimum 3-ply BUR or minimum 2-ply mod bit system with all plies fully mopped, per FM Approval requirements.

7 Roof Deck Securement and Above-Deck Roof Components 1-29 FM Global Property Loss Prevention Data Sheets Page 7 c) For areas where the criteria in the recommendations above are exceeded, ensure the roof system used in the perimeter and corner areas is FM Approved for the specific wind rating recommended in the perimeter and corner areas (see Table 1). Alternatively, install either a mechanically attached single-ply membrane, or a multi-ply roof cover with a mechanically attached base sheet in accordance with Note: Insulation and thermal barriers under mechanically fastened roof covers in assemblies that DO NOT incorporate air or vapor retarders do not have to increase the insulation fastening over the field of roof spacing For components adhered with urethane-based adhesives, asphalt, or other adhesives in ribbons, spots, etc., reduce the spacing between ribbons or spots over the FM Approved field-of-roof spacing as noted below (round down to a dimension that is practical with respect to board sizes, etc.): In the roof perimeter, not more than 60% of the field-of-roof spacing between rows or area In the roof corners, not more than 40% of the field-of-roof spacing between rows or area Note: If the FM Approval rating for wind meets the criteria in Table 1 for the perimeter or corner area, no further reduction is needed in those areas. Example: A particular roof cover as FM Approved is adhered with a urethane-based adhesive in ribbons at 1 ft (0.3 m) on center in the field of the roof. The perimeter would need a ribbon spacing of 6 in. (150 mm) and the corners would need a ribbon spacing equal to 4 in. (100 mm) on-center. Note: these spacings were rounded down slightly for practicality For mechanically attached single-ply membranes, and multi-ply covers with a mechanically attached base sheet, refer to section For mechanically attached base sheets, refer to section or if the base sheet is fastened directly to a wood deck For ballasted systems, refer to section For steel decks, increase the number of deck fasteners at each joist or purlin support over the field-of-roof FM Approvals RoofNav listing in accordance with Shorter spans that yield an equivalent increase in deck securement strength are acceptable, but may not always be practical External Fire ResistanceDesign Recommendations Assemblies having an American Society for Testing and Materials (ASTM) E108 Class A rating are preferred in all cases, and are specifically recommended as follows: a) Where the exterior fire exposure to the roof is severe. b) On the entire roof of buildings subdivided by MFL fire walls. Refer to Data Sheet 1-22, Criteria for Maximum Foreseeable Loss Fire Walls and Space Separation, for details on additional surface protection needed adjacent to the wall and roof protection for buildings where MFL space separation is a factor. c) For occupancies particularly susceptible to smoke or water damage ASTM E108 Class C rated assemblies are not recommended on any roofs >10,000 ft 2 (930 m 2 ) The use of pea gravel surfacing installed in accordance with is considered to provide a Class A exterior fire exposure rating. While not normally recommended in hurricane-prone regions due to its potential to become windborne debris, it may be accepted in hurricane-prone regions (such as where required adjacent to fire subdivisions), provided that all gravel remaining at the end of the installation is fully embedded into the bitumen and there is no loose gravel nested on top. The following method will provide such compliance: a) Aggregate is applied into a flood coat of hot bitumen, and allowed to cool and harden. b) Loose aggregate is pushed away, a second flood coat is applied, and the loose gravel is applied back into the second flood coat and allowed to cool and harden. c) Any remaining loose gravel is removed from the site.

8 Page 8 FM Global Property Loss Prevention Data Sheets Hail Resistance: Design Recommendations Use only FM Approved roof cover systems meeting the severe hail (SH) criteria in the hail storm hazard area shown in Figure 1. Unless specifically FM Approved with other surface treatments, built-up roofs (BUR) may be used in SH and MH areas, provided: they are covered with gravel at a minimum of 400 lb per square (19.5 kg/m 2 ) or slag at a minimum of 300 lb per square (14.6 kg/m 2 ). (See Appendix A, Glossary, for definition of square.) aggregate is in accordance with ASTM D1863. aggregate is applied into a minimum 60 lb per square (2.9 kg/m 2 ) bitumen flood coat. Note: Do not use pea gravel in regions prone to hurricanes, typhoons ancd tropical cyclones except where installed in accordance with section Otherwise, use FM Approved coatings in lieu of pea gravel For U.S. locations outside the hail area, MH or SH rated systems can be used At locations outside the U.S., MH rated systems can be used unless local weather records indicate the need for greater hail resistance. Generally, consider SH rated systems for locations with an average of three or more hail storms per year Internal Fire ResistanceNoncombustible, Class 1, and Class 2 AssembliesDesign and Installation Recommendations As all FM Approved roof systems are Class 1 or noncombustible, Class 1 or noncombustible assemblies are recommended in all cases. When there is an existing Class 2 deck and an unsprinklered concealed space below the deck, refer to Data Sheet 1-12, Ceilings and Concealed Spaces, for fire protection guidance Class 2 steel roof decks can be converted to Class 1 by applying an FM Approved undercoating. If this is done, adhere to the following recommendations: Ensure the underside of the deck is clean before coatings are applied. Ensure FM Approved coatings are applied by applicators licensed by the coating manufacturer. Do not use cellulose-based undercoatings in high humidity occupancies as the fire retardant chemicals are water soluble and can leach out of the coating. Do not use steel deck undercoatings where combustible residue can accumulate on the surface Vapor Retarders (Barriers)Design and Installation Recommendations These recommendations outline vapor retarder applications that maintain Class 1 and appropriate wind uplift ratings If a vapor retarder is used, ensure it is FM Approved and applied in a single layer placed directly on the deck. Side and end laps are sealed using FM Approved adhesive. The remaining roof components are then installed with fasteners driven through the retarder into the deck (Fig. 2). The components above the FM Approved vapor retarder can be any combination of materials FM Approved for use together on the particular deck. Some systems are FM Approved with the retarder installed above a base layer of insulation; see section below On panel-type decks (decks with seams such as steel, wood, pre-cast planks, etc.), if a vapor retarder is installed below the insulation or coverboard of a mechanically secured single-ply membrane (per recommendation above), secure the insulation or coverboard with FM Approved insulation fasteners and plates using one of the following options: 1. A rate of 1 per 2 ft 2 (1 per 0.19 m 2 ) throughout the entire roof area, OR 2. A rate throughout the entire roof area that will obtain a minimum 1-90 uplift FM Approval with an adhered single-ply roofing membrane as specified in a RoofNav listing. The insulation/coverboard type used below the mechanically secured membrane must match that specified by the RoofNav listing for the adhered membrane, and the thickness of the insulation/coverboard must be equal to or greater than that specified by the RoofNav listing. A vapor retarder is located on the warm side of the roof or sandwiched between insulation layers. The vapor retarder is sealed to the exterior walls of the building, but not necessarily to the underside of the roof cover.

9 Roof Deck Securement and Above-Deck Roof Components 1-29 FM Global Property Loss Prevention Data Sheets Page 9 Gander Churchill St. Johns Hudson Bay Buchans Gulf of St. Lawrence Ja mes Bay Sidney Charlottetown Chatham Halifax Quebec Sioux Lookout Bangor Montreal Winnipeg Seattle Port Arthur Spokane Montpelier Ottawa Portland In ternational Falls Concord Saranac Lake Boston Duluth Toronto Helena Fargo Bismarck Albany Baker City Providence Hartford Aberdeen Buffalo Boise Philadelphia Ludington Sheridan Pierre Minneapolis Pittsburgh Detroit Trenton Milwaukee Pocatello Harrisburg Sioux Falls Eureka Baltimore Cleveland Red Bluff Lander Chicago Washington DC Fort Wayne Moline Reno Columbus Cincinnati North Platte Sacramento Salt Lake City Indian apolis Kahoka San Francisco Norfolk Charleston Springfield Kansas City Topeka Saint Louis Louisville Wytheville Fresno Knoxville Wichita Ashville Springfield Las Vegas Nashville Joplin Memphis Santa Fe Chattanooga Charleston Amarillo Atlanta Phoenix Birmingham San Diego Savannah Montgomery Tucson Dallas Mobile El Paso Jacksonville New Orleans Tampa San Antonio Houston Gulf of Mexico Miami NEWFOUNDLAND Prince Rupert CANADA Prince George Edmonton The Pas Prince Albert Amherst Saskatoon Kamloops C algary Vancouver Penticton Kapuskasing Regina Nelson Cranbrook Medicine Hat Gulf of Maine Havre Sault St Marie Huntsville Lake Superior Marquette London Green Bay Souix City Des Moines Cheyenne Richmond Denver Williston Lake Huron Billings Lake Michigan Atlantic Ocean Raleigh Pueblo Fort Smith Little Rock Shreveport Jackson Columbia Los Angeles Oklahoma City Gulf of California MEXICO Fig. 1. Hailstorm hazard map for United States (areas subject to severe hailstorms and need an SH hail rated roof) H ecate Strait Clayoquot Victoria Pacific Ocean Exposure to Damaging Hailstorms Moderate Severe No Data Kilometers Miles 2009 Factory Mutual Insurance Company. All rights reserved

10 Page 10 FM Global Property Loss Prevention Data Sheets Fig. 2. Insulation and vapor barrier mechanically fastened to steel deck. An air barrier is used with a mechanically fastened roof cover and is located directly above the roof deck. The air barrier is sealed to the underside of the roof cover, but not necessarily to the exterior walls of the building. In theory, an air barrier improves wind uplift resistance of the roof assembly by preventing air flow into the space below the roof cover and transferring a portion of the uplift load to the insulation. It should be noted that even for properly installed air barrier systems, roof penetrations made after the installation of an air barrier system can hamper the wind performance of an air barrier system if the air barrier is not sealed to the underside of the roof cover after the penetration cut is made. Consequently, there are special FM Approval restrictions on air barrier systems Fastener penetration of the vapor retarder can be avoided by using an FM Approved fastened/adhered assembly. Ensure all materials are FM Approved for use in combination. Ensure substitution of materials is not made Do not mop asphalt/felt vapor retarders directly on to any deck (this would result in a Class 2 roof) except structural concrete Roof Insulation Design Recommendations Ensure insulation boards are FM Approved for the specific application, including specific roof cover, fasten/mop construction, multiple layers, etc. Using assemblies that are not FM Approved can result in a Class 2 and/or inferior roof construction. However, combinations that may not be FM Approved but can be accepted are noted in sections , , and It is acceptable to use multiple layers of FM Approved insulation, mechanically secured through all layers, provided all of the following are true: All layers are the same insulation. The total insulation thickness is not greater than the maximum FM Approved thickness of the insulation. The mechanical fastening and wind uplift rating are per the FM Approval of the top layer. The roof cover/insulation/fastener combination is FM Approved Insulation board sizes listed in the Approval Guide are the minimum FM Approved sizes. Boards up to 4 8 ft ( m) can be used except as noted in section (with a proportional increase in fasteners, adhesive ribbons, etc. rounding up to the next whole number). Do not use boards smaller than FM Approved except per section

11 Roof Deck Securement and Above-Deck Roof Components 1-29 FM Global Property Loss Prevention Data Sheets Page The maximum recommended insulation board size, if the board is adhered with asphalt or adhesive, is 4 4 ft ( m). Exception: Flexible boards such as maximum 1 2 in. (13 mm) thick wood fiber or 5 8 in. (16 mm) gypsum board may be adhered at board sizes up to 4 8 ft ( m) Installation Recommendations Stagger insulation board joints in one direction (the shorter sides staggered if boards are not square). Support the two opposite sides of each board on steel deck flanges, as close as practical to the center of the flange with a minimum bearing width of 1 in. (25 mm). Trim board edges if they veer off the flange center When insulation boards are cut, as is common at the roof edge to produce staggered joints, secure each piece with the appropriate number of fasteners, adhesive ribbons, etc. for the full board times the percentage area of the piece, rounding up to the next whole number Install only as much insulation or gypsum-based board as can be covered each working day. Seal loose roof cover edges at the end of each day to minimize moisture damage. Do not allow water to run in steel deck ribs under completed roof sections Ensure insulation is set on pallets or dunnage and protected from the weather and sunlight prior to installation. Do not allow plastic to cover the insulation as it can allow condensation. A breathable material, such as canvas, is recommended Ensure FM Approved job-mixed material (like LWIC) is installed by applicators licensed by the manufacturer. Steel deck that meets the insulation manufacturer s span and gauge requirements is necessary to support the application equipment. Such systems are a possible option when penetration of the deck with mechanical fasteners is not desired Provide preliminary securement of insulation boards when mechanically fastened roof covers are used (single-plies or multi-plies with fastened base sheets). Install a minimum of two fasteners per4x4ft(1.2 x 1.2 m) board or four fasteners per 4x8ft(1.2 x 2.4 m) board, unless the manufacturer requires a greater number. Additional insulation fastening is not required in the perimeter and corner areas. Where a vapor retarder is used below a mechanically fastened roof cover, see section Insulation and Roof Cover Fasteners Design Recommendations FM Approved insulation fasteners are the only FM Approved and recommended method of securing insulation boards or other boardstock materials to steel deck. Some fasteners are FM Approved for other deck materials When fastener pull-out tests are performed on new construction to evaluate the deck integrity or evaluate decks that are not FM Approved, run a minimum of five tests and use the average value. See section for the number of tests for recover/reroof construction When pull-out tests are done, base the fastener density on the more conservative of either the FM Approved spacing for the fastener plate/insulation/roof cover combination, or the spacing needed based on the average pull-out performance. Example: An existing deck is oriented strand board (OSB). The fastener/insulation/roof cover combination is FM Approved for 4 fasteners per 4 4 ft ( m) board for Class 1-90 on steel deck. The calculated load per fastener would be 360 lb (1600 N) ([4 ft 2 /fastener][90 psf] = 360 lb/fastener). If the proposed fastener achieved a pull-out resistance of 360 lb (1600 N) or more in the deck, the FM Approved spacing would be used. If the fastener achieved a resistance of less than 360 lb (1600 N), for example 300 lb (1335 N), calculate the spacing as follows: (16 ft 2 )(90 psf)/(300 lb) = 4.8 fasteners per board; use five fasteners per board in the roof field. Additional fasteners would be needed in the corners and perimeter per section The percentage increase would be applied to five fasteners per board, not four Installation Recommendations Install fasteners only through dry substrates. Wet constructions can cause deterioration of fasteners, including FM Approved corrosion-resistant fasteners. Exception: Fasteners FM Approved for use in new lightweight insulating concrete decks are designed to be tolerant of the moisture present at the time of installation.

12 Page 12 FM Global Property Loss Prevention Data Sheets Use only FM Approved fastener/plate combinations. Do not install stress distribution plates from one manufacturer with another manufacturer s fastener unless the combination is FM Approved Fasteners must be driven perpendicular to the deck to be effective. Particular caution is needed with tapered insulations Use the manufacturer s proprietary installation tool. A less desirable option is a properly adjusted screw gun, having a depth-sensing clutch, to avoid over-driving or under-driving screw-type fasteners Recommended Fastener Embedment: Sructural concrete: 1to1 1 2 in. (25-38 mm), Wood decks: Minimum 1 in. (25 mm). Note: For 3 4 in. (19 mm) thick plywood deck, approximately 1 4 in. (6 mm) of the screw will protrude through the deck underside. Steel deck: For screw-type fasteners in new construction, use the shortest screw that is at least 3 4 in. (19 mm) longer than the assembly being secured. Ensure fasteners engage the deck top flange. For recover steel deck construction, the fastener must be long enough to be driven through the existing roof system and into the deck at least 3 4 in. (19 mm). While top flange engagement is recommended in all cases, for recover construction, it is acceptable for insulation fasteners to engage the bottom flange of the deck. Ensure fasteners securing mechanically attached roof covers engage the top flange of the deck in all constructions. For other deck types: Follow the FM Approval requirements and manufacturers specifications Ensure insulation fastener placement is per Figures 3, 4, 5, and 6. If a particular insulation has a different required FM Approved fastener pattern, use that. Each fastener must engage the intended deck flange. This results in a spacing tolerance of approximately ± 1.5 in. (± 38 mm) for wide-rib deck if the edge of the board was at the centerline of the deck top flange. For smooth decks, such as plywood or concrete and steel deck in the direction of deck ribs, a maximum tolerance of ± 1.5 in. (± 38 mm) is acceptable.

13 Roof Deck Securement and Above-Deck Roof Components 1-29 FM Global Property Loss Prevention Data Sheets Page 13 Fig. 3. Fastener placement 2 4 ft( m) boards.

14 Page 14 FM Global Property Loss Prevention Data Sheets Fig. 4. Fastener placement 3 4 ft ( m) boards.

15 Roof Deck Securement and Above-Deck Roof Components 1-29 FM Global Property Loss Prevention Data Sheets Page 15 Fig. 5. Fastener placement 4 4 ft ( m) boards.

16 Page 16 FM Global Property Loss Prevention Data Sheets Fig. 6. Fastener placement 4 8 ft ( m) boards. For fastening densities not shown, the following guidelines apply: Ensure edge fasteners are 6 in. (152 mm) from the board edges, with tolerance as above. Ensure fasteners are evenly distributed over the board area. Ensure all fasteners engage the top flange of steel deck. (See note for recover construction, section above.) Recover and Reroof ConstructionDesign and Installation Recommendations This section covers planned recover and reroof operations. For repairs after wind damage has occurred, refer to Data Sheet 1-30, Repair of Wind Damaged Roof Systems Reroof ConstructionRemoval and Replacement of Above-Deck Components Reroof construction is generally preferred to recover construction due to the potential for moisture damage with recover construction from existing wet insulation inadvertently left in place.

17 Roof Deck Securement and Above-Deck Roof Components 1-29 FM Global Property Loss Prevention Data Sheets Page When reroofing, inspect the existing deck securement and, if necessary, fasten the deck per Data Sheet 1-28, Wind Design, prior to installation of the above-deck components When reroofing over a steel deck where the original assembly had been adhered with asphalt, do one of the following: Use an insulation specifically FM Approved for reroofing; that allows up to 15 lb per square (72 kg/100 m 2 ) of asphalt to remain on the deck. Remove all asphalt from the deck and install a system FM Approved for new construction Recover ConstructionExisting Components Remain All recover recommendations and FM Approvals are based on the assumption that there is only one existing roof system. If more than one roof system is in place (building has already been recovered), use reroof construction If recover construction is considered, perform the following actions: Remove all wet materials prior to application of the new roof system, with wet insulation being replaced with dry material. Cut out blisters. Roof cover blistering or rusting deck may be an indication that the existing insulation is wet. When this is observed, take one of the following steps: Reroof, as opposed to recover. See section Conduct an infrared or nuclear examination to detect any high-moisture content. If moisture is detected with one of these nondestructive methods, confirm the results by cutting out 1 1ft ( m) samples or roof cores as needed to determine the extent of wet insulation Recovermechanically attached recover systems. If the existing construction is dry, an FM Approved recover system can be applied over it. Ensure the entire assembly (insulation, fasteners, and roof cover) is FM Approved in combination for recover construction on the particular deck Ensure the thickness of the recover system is within the FM Approval limits. Most systems are limited to a maximum 1 in. (25 mm) thick roof insulation. A greater thickness may affect the Class 1 fire rating of the completed system. Installation of an FM Approved Class 1 recover assembly over an existing Class 2 roof system will not upgrade the assembly to Class 1. However, it would be possible to upgrade the external fire resistance rating (E108) with the addition of an FM Approved roof cover system When brooming gravel from the roof, do not pile it in one area. This can overload structural members causing collapse Do not use recover constructions using additional plies adhered directly to an existing BUR unless the entire assembly is FM Approved. This would essentially result in a 6- or 7-ply BUR over the insulation (3- or 4-ply existing BUR plus 3 plies added), most likely creating a Class 2 roof assembly When reroofing or recovering over gypsum, cementitious wood fiber, or lightweight insulating concrete decks, verify fastener pull-out performance with field tests. Perform 5 pull-out tests per 50,000 ft 2 (4650 m 2 ) using FM Approved fastening or a minimum of 5 tests. Run additional tests if inconsistent results are obtained. On larger roofs, the number of tests above the minimum can be reduced if consistent results are obtained. Fastener spacing is calculated per section It is not necessary to run pull-out tests of fasteners FM Approved for installation in steel deck, structural concrete, nominal 3 4 in. (19 mm) plywood, or nominal 2 in. (51 mm) lumber decks, unless the condition of the deck is in question Structural Concrete, FM Approved Fiber Reinforced Cement and Lightweight Insulating Concrete (LWIC) Decks: Design and Installation Recommendations NOTE: also see section for LWIC and for Structural Concrete Decks When an FM Approved asphaltic adhesive or asphalt is used to secure components to these decks, prime the deck with an FM Approved primer at the FM Approved rate, or with an ASTM D-41 asphalt cut-back primer at 0.75 to 1.25 gal per square (3.0 to 5.1 L/10 m 2 ).

18 Page 18 FM Global Property Loss Prevention Data Sheets Single-Ply Membrane Covers and Multi-Ply covers with Mechanically Attached Base Sheets Loss experience has shown that even properly secured single-ply roof covers can be damaged by windborne debris such as metal panels and broken glass. In areas prone to hurricanes, typhoons and tropical cyclones (see DS 1-28), use more durable roof covers. This would include multi-ply roof covers or single-ply membranes that are considerably thicker than the FM Approved minimum. Many single-ply membranes are manufactured in thicknesses up to to in. vs. the minimum FM Approved thickness of to in General Single-ply membranes can deteriorate when exposed to certain materials commonly discharged onto the roof. Also separate these membranes from incompatible substrate materials. In particular, ensure single-ply membranes do not come into contact with asphalt or coal tar-based materials. Ensure EPDM membranes are not exposed to gasoline, oil, solvents, or animal fats. Ensure PVC membranes are not in direct contact with EPS. Follow the manufacturer s recommendations for protection or separation Some FM Approved single-ply membranes are formulated with fire retardants on the top side only. Install these systems with that surface up. Membranes with this requirement are labeled on the underside THIS SIDE DOWN/IN Mechanically Attached Single-ply Membranes and Multi-Ply Covers with Mechanically Attached Base Sheets: Design Recommendations In the roof corners and perimeter, ensure the distance between rows of roof cover fasteners or batten bars are the following maximum percentages of the FM Approved spacing. Use the reduced spacing in all FM Approval classifications: Roof Perimeter: Distance between rows is 60% of the FM Approved roof field spacing, or one row of intermediate fasteners is provided in between. Roof Corners: Distance between rows is 40% of the FM Approved roof field spacing or two rows of intermediate fasteners are provided in between. An alternative for Class 1-90 and below (on steel deck) is to install perimeter fastener rows (60% of roof field as above) in both directions in the corners (any wind class acceptable for other types of decks). Refer to Figure 7. When the cover overlaps in the corner areas, install these fasteners from above the uppermost cover layer. For single-plies fastened along the side laps: Increased fastening density for single-ply membranes is often obtained by using narrower sheets. For single-ply membranes or base sheets, intermediate rows of fasteners may be installed through the sheet with a cover strip or additional plies applied over the fasteners, in accordance with the manufacturer s instructions. Use one intermediate row in the perimeter and two intermediate rows in the corners. Fastening increase is not always obtained by increasing the number of fasteners along each row, unless substantiated by FM Approval test data or otherwise done to provide a more practical spacing and distribution of wind loads. In some cases, such as over wood decks (see ) or LWIC, or with mod bit base sheets in high wind areas, enhanced securement for base sheets is provided by reducing the fastener spacing within and between rows in order to provide a uniform distribution (see section for examples). When steel deck is used, the fastener spacing across the deck ribs must be in even multiples of the deck rib spacing (6 in. or 150 mm for in. or 38 mm deep deck) to ensure the fastener engages the top deck flange. See Example 1. For point-attached membranes: Increased fastening density is obtained by decreasing the spacing between fastener points in one or both directions. Ensure total tributary area to each fastener is no more than 60% and 40% in the perimeter and corners, respectively, of the FM Approved roof field spacing. See Example 2. Example 1: A batten-attached system with FM Approved fastener spacing for Class 1-60 of rows 6 ft (1.8 m) on center and screws 6 in. (152 mm) on center would use 3.6 ft (1.1 m) maximum on center row spacing, with 6 in. (152 mm) on-center screw spacing in the perimeter and 2.4 ft (0.7 m) maximum on-center row spacing with 6 in. (152 mm) on-center screw spacing in the corners. In this case, rows of roof cover fasteners should extend across the deck ribs in all areas to properly distribute the load to points of deck securement. Since the needed wind uplift rating is limited, an option would be to use row spacing of 3 ft (0.9 m) maximum in both directions in the corners per Figure 7, and

19 Roof Deck Securement and Above-Deck Roof Components 1-29 FM Global Property Loss Prevention Data Sheets Page 19 Notes: 1. Fastener spacing along all rows is the same as field spacing. 2. See section for restrictions on fastener rows parallel to steel deck ribs. 3. If two layers of membrane are installed in the corner areas, all fasteners must secure the top layer. Fig. 7. Alternate corner increase for mechanically attached single-ply membranes. Note: Fastener spacing along all rows is the same as field spacing.

20 Page 20 FM Global Property Loss Prevention Data Sheets Example 2: A point-attached system with FM Approved fastener spacing for Class 1-90 of in. ( mm) could use a spacing of in. ( mm) in the perimeter. A in. ( mm) spacing may be needed for steel deck applications depending on deck rib direction. A spacing of in. ( mm) in the corners could be used. A in. ( mm) may be needed for steel deck applications depending on deck rib direction Mechanically Attached Single-Ply Membranes and Multi-Ply Covers with Mechanically Attached Base PliesInstallation Recommendations Ensure all roof cover fasteners engage the top flanges of steel deck Install batten bars and fastener rows perpendicular to steel deck ribs. Exception: for Class 1-75 and below, fastener rows and batten bars can be installed parallel to the building edge within the defined building perimeter width if: a) the distance between fastener rows in this area is 3 ft (0.9 m), and b) two FM Approved deck fasteners or minimum 5 8 in. (16 mm) diameter welds are installed through each lower deck flange (every 6 in., 150 mm on center) Where acceptable to the roof cover manufacturer, in lieu of seaming numerous partial single-ply membrane sheets in the rake areas, an FM Approved batten bar may extend across the perimeter width, midway between rows of fasteners and be fastened to the deck. Adhere a membrane strip of a minimum width as recommended by the manufacturer over the batten bar and the edges caulked to maintain water-tightness, if needed. Similar enhancements may be provided in the corner areas using two intermediate batten bars Provide deck securement as follows when the FM Approved (field-of-roof) spacing between rows of roof cover fasteners exceeds 6 ft (1.8 m): a) Use only FM Approved deck fasteners to secure the deck. Ensure the spacing within rows of deck fasteners in the field-of-roof does not exceed the spacing within rows of roof cover fasteners. b) Double the deck fastening in the roof perimeter. For example, if roof cover fasteners are 12 in. (300 mm) on center in the field, provide deck fasteners 12 in. on center in the field (per a.) and provide deck fasteners at 6 in. (150 mm) centers in the perimeter. If cover fasteners are 6 in. (150 mm) on center in the field, provide deck fasteners at 6 in. centers in the field (per a.) and provide two deck fasteners at 6 in. (150 mm) centers in the perimeter. c) In corner areas, use the same number of deck fasteners as for the perimeter, but with ¾ in. diameter washers. Ensure washers are carbon steel with a in. (8.4 mm) center hole and are minimum in. (1.6 mm) thick Ballasted Single-Ply Membrane: Design Recommendations Do not use stone-ballasted roofs on buildings taller than 150 ft (46 m) high, or in areas with design wind speeds 100 mph (45 m/s) (See Data Sheet 1-28, Wind Design) or beyond the acceptable limits of Tables 2 or 3. These limitations do not apply to paver ballasted systems To ensure the quality of the materials, component compatibility, and Class 1 undeside fire exposure ratings, ensure individual components in ballasted systems are FM Approved for use in combination. Typically, the combination would be FM Approved for adhered or mechanically attached applications. Use only FM Approved membranes in ballasted applications Ensure stone ballast in loose-laid systems is clean, smooth, well-rounded gravel meeting the gradation requirements of Standard Size No. 3 for Coarse Aggregate per ASTM D448 (nominal 1 to 2 in. [25 to 50 mm] diameter) Ensure the density of stone ballast is approximately 165 pcf (2650 kg/m 3 ). Do not use lightweight stone such as limestone Apply stone ballast per Table 2 or 3. Install paver blocks per Tables 4 to 7. Ensure square edge pavers are a minimum of 1 ft 2 (0.1 m 2 ). Ensure beveled/strapped pavers are a minimum of 0.89 ft 2 (0.08 m 2 ) (8 16 in., [ mm]). All weights are the minimum recommended weights.

RESIDENTIAL ROOFING & RE-ROOFING, ROOF VENTILATION AND ROOF SHEATHING REQUIREMENTS MICHIGAN RESIDENTIAL CODE 2000

RESIDENTIAL ROOFING & RE-ROOFING, ROOF VENTILATION AND ROOF SHEATHING REQUIREMENTS MICHIGAN RESIDENTIAL CODE 2000 RESIDENTIAL ROOFING & RE-ROOFING, ROOF VENTILATION AND ROOF SHEATHING REQUIREMENTS MICHIGAN RESIDENTIAL CODE 2000 SECTION R905 REQUIREMENTS FOR ROOF COVERINGS R905.1 Roof covering application. Roof coverings

More information

NRDCA 400 GUIDELINE FOR FIELD APPLICATION of LIGHTWEIGHT INSULATING CONCRETE REROOFING/RECOVER SYSTEMS

NRDCA 400 GUIDELINE FOR FIELD APPLICATION of LIGHTWEIGHT INSULATING CONCRETE REROOFING/RECOVER SYSTEMS NRDCA 400 GUIDELINE FOR FIELD APPLICATION of LIGHTWEIGHT INSULATING CONCRETE REROOFING/RECOVER SYSTEMS The (NRDCA) has prepared this document to provide customers and installers information that the industry

More information

CHAPTER 7: Building Systems ROOFING SYSTEMS

CHAPTER 7: Building Systems ROOFING SYSTEMS ROOFING SYSTEMS Purpose Examples 1. Shingle roof system 2. Metal roof with blanket insulation 3. Metal roof with rigid insulation 4. Built-up asphalt roof system 5. Single-ply roof system 6. Modified Bitumen

More information

ROOFING APPLICATION STANDARD (RAS) No. 150 PRESCRIPTIVE BUR REQUIREMENTS

ROOFING APPLICATION STANDARD (RAS) No. 150 PRESCRIPTIVE BUR REQUIREMENTS ROOFING APPLICATION STANDARD (RAS) No. 150 PRESCRIPTIVE BUR REQUIREMENTS 1. 2. 3. 3.0 Scope 1.1 This application standard shall be used where the authority having jurisdiction has adopted its use, and

More information

STANDARD REQUIREMENTS FOR BONDING OR MECHANICAL ATTACHMENT OF INSULATION PANELS AND MECHANICAL ATTACHMENT OF ANCHOR AND/OR BASE SHEETS TO SUBSTRATES

STANDARD REQUIREMENTS FOR BONDING OR MECHANICAL ATTACHMENT OF INSULATION PANELS AND MECHANICAL ATTACHMENT OF ANCHOR AND/OR BASE SHEETS TO SUBSTRATES ROOFING APPLICATION STANDARD (RAS) No. 117 STANDARD REQUIREMENTS FOR BONDING OR MECHANICAL ATTACHMENT OF INSULATION PANELS AND MECHANICAL ATTACHMENT OF ANCHOR AND/OR BASE SHEETS TO SUBSTRATES Scope 1.1.

More information

Best Practices in Roof Design: Sustainable Energy Efficient Reroofing

Best Practices in Roof Design: Sustainable Energy Efficient Reroofing Best Practices in Roof Design: Sustainable Energy Efficient Reroofing Best Practice Roof Design: Sustainable Energy Efficient Reroofing Presented by Edis Oliver, PE Principal 9511 Lake Creek Parkway Austin,

More information

Re-Cover Board-3. Insulation for Above the Deck ROOF WALL SPECIALTY

Re-Cover Board-3. Insulation for Above the Deck ROOF WALL SPECIALTY Insulation for Above the Deck WALL SPECIALTY PRODUCT DESCRIPTION Rmax Re-Cover Board-3 is an energy-efficient thermal insulation board composed of a closed-cell polyisocyanurate (polyiso) foam core bonded

More information

1. Adhered KEE membrane roofing system. 2. Mechanically fastened KEE membrane roofing system.

1. Adhered KEE membrane roofing system. 2. Mechanically fastened KEE membrane roofing system. SECTION 075416 - PART 1 - GENERAL 1.1 SUMMARY A. Section Includes: 1. Adhered KEE membrane roofing system. 2. Mechanically fastened KEE membrane roofing system. 1.2 PERFORMANCE REQUIREMENTS A. Solar Reflectance

More information

Residential Roofing Guide

Residential Roofing Guide Residential Roofing Guide TABLE OF CONTENTS Building Detail and Accessories...... 1 Panel Introduction and Handling...... 2 Cutting and Trimming.... 3 Roof Preparation..... 3 Roof Slope..... 3 Re-roofing...

More information

PERIMETER FLASHING. Table of Contents

PERIMETER FLASHING. Table of Contents FM Global Property Loss Prevention Data Sheets 1-49 February 1985 Revised September 2000 Page1of25 PERIMETER FLASHING Table of Contents Page 1.0 SCOPE... 3 1.1 Changes... 3 2.0 LOSS PREVENTION RECOMMENDATIONS...

More information

COMMERCIAL BUILDING APPLICATIONS

COMMERCIAL BUILDING APPLICATIONS EXPANDED POLYSTYRENE FOR COMMERCIAL BUILDING APPLICATIONS www.falconfoam.com Commercial Building Ap Expanded Polystyrene Insulation Falcon Foam leads the commercial building industry with products that

More information

Asphalt Shingle Application Requirements

Asphalt Shingle Application Requirements Alberta Allied Roofing Association Asphalt Shingle Application Requirements Section 1 Roof Decks 1.1 General Asphalt Shingles are not permitted to be installed directly over rigid insulation. When Asphalt

More information

NEW ELECTRICAL SUBSTATION Building 300 SECTION 07 53 23 ETHYLENE-PROPYLENE-DIENE-MONOMER ROOFING WORK

NEW ELECTRICAL SUBSTATION Building 300 SECTION 07 53 23 ETHYLENE-PROPYLENE-DIENE-MONOMER ROOFING WORK ETHYLENE-PROPYLENE-DIENE-MONOMER ROOFING WORK PART 1 GENERAL 1.1 REFERENCES The publications listed below form a part of this specification to the extent referenced. The publications are referred to within

More information

Information About Filing a Case in the United States Tax Court. Attached are the forms to use in filing your case in the United States Tax Court.

Information About Filing a Case in the United States Tax Court. Attached are the forms to use in filing your case in the United States Tax Court. Information About Filing a Case in the United States Tax Court Attached are the forms to use in filing your case in the United States Tax Court. It is very important that you take time to carefully read

More information

Durapax Coal Tar BUR Application Guide

Durapax Coal Tar BUR Application Guide 400 Old Reading Pike, Suite 304 Pottstown, PA 19464 Tel: 610-579-9075 Fax: 610-323-0115 www.durapax.com Durapax Coal Tar BUR Application Guide DESIGN CONSIDERATIONS The proper specifications of any roof

More information

Roofing Systems. There are many different systems, each with it's own special requirements and benefits. Browse through all the options below.

Roofing Systems. There are many different systems, each with it's own special requirements and benefits. Browse through all the options below. Roofing Systems There are many different systems, each with it's own special requirements and benefits. Browse through all the options below. BUR (Built-Up Roofing) Built-Up-Roofing, BUR is a roof that

More information

Final inspections are completed by site visit only. Access to fenced yards shall be planned.

Final inspections are completed by site visit only. Access to fenced yards shall be planned. ROOFING RESIDENTIAL BUILDING INSPECTIONS DEPARTMENT www.ci.blaine.mn.us This handout is intended only as a guide and is based in part on the 2015 Minnesota State Building Code, Blaine City ordinances,

More information

Building Owners Guide to a Duro-Last System!

Building Owners Guide to a Duro-Last System! Building Owners Guide to a Duro-Last System Table of Contents Section 1: Introduction to Duro-Last Roofing Systems Section 2: Benefits of a Duro-Last Roofing System Section 3: Comparing a Duro-Last Roof

More information

The existing roof angle change terminations and flashings when sound and intact can be reused.

The existing roof angle change terminations and flashings when sound and intact can be reused. January 2, 2015 Summary Specification Re-Skinning an Existing Roof Maintenance and Repair Warranty Upgrade for Up to 30 Years Re-Skinning Over an Existing Roof with a New C-EPDM Membrane Using The Existing

More information

Low-slope reroofing guidelines

Low-slope reroofing guidelines Low-slope reroofing guidelines by Thomas Bollnow and Joan P. Crowe, AIA The NRCA Roofing and Waterproofing Manual, Fifth Edition, contains reroofing guidelines for steep- and low-slope roofing. The August

More information

APPENDIX 1: ATTACHMENT REQUIREMENTS FOR WIND UPLIFT RESISTANCE

APPENDIX 1: ATTACHMENT REQUIREMENTS FOR WIND UPLIFT RESISTANCE APPENDIX 1: ATTACHMENT REQUIREMENTS FOR WIND UPLIFT NCE Table Application Type Description Page 1A-1 Wood New, Reroof (Tear-Off), Recover C-1 Mechanically Attached Insulation, Bonded Roof Cover 4 1A-2

More information

WATERPROOFING OF REINFORCED CONCRETE FLAT ROOF 12

WATERPROOFING OF REINFORCED CONCRETE FLAT ROOF 12 WATERPROOFING OF REINFORCED CONCRETE FLAT ROOF 12 87 88 GOOD INDUSTRY PRACTICES 12 WATERPROOFING OF REINFORCED CONCRETE FLAT ROOF 12.1 BACKGROUND Most roofs in Singapore are constructed using reinforced

More information

Roof Inspection Report 3840 Greenway Circle, Lawrence Kansas, 66046 Sauer-Danfoss Building

Roof Inspection Report 3840 Greenway Circle, Lawrence Kansas, 66046 Sauer-Danfoss Building Roof Inspection Report 3840 Greenway Circle, Lawrence Kansas, 66046 Sauer-Danfoss Building Prepared For: Ms Marilyn Bittenbender Colliers International 805 New Hampshire St Lawrence Kansas, 66046 Prepared

More information

SINGLE FAMILY RESIDENCE HURRICANE MITIGATION APPLICATION

SINGLE FAMILY RESIDENCE HURRICANE MITIGATION APPLICATION SINGLE FAMILY RESIDENCE HURRICANE MITIGATION APPLICATION As of October 1, 2007, this mitigation form must be submitted as part of the roofing permit application package. Secondary water barrier (if applicable)

More information

APPLICATION INFORMATION FOR RESIDENTIAL ROOFING AND RESIDENTIAL ROOFING PACKET

APPLICATION INFORMATION FOR RESIDENTIAL ROOFING AND RESIDENTIAL ROOFING PACKET Environmental Protection and Growth Management Department PERMITTING, LICENSING AND CONSUMER PROTECTION DIVISION 1 N. University Drive, Box #302 Plantation, Florida 33324 954-765-4400 www.broward.org/permittingandlicensing

More information

ANSI/SPRI WD-1 Wind Design Standard Practice for Roofing Assemblies. Table of Contents. 1.0 Introduction...2. 2.0 Methodology...2

ANSI/SPRI WD-1 Wind Design Standard Practice for Roofing Assemblies. Table of Contents. 1.0 Introduction...2. 2.0 Methodology...2 Standard Practice f Table of Contents 1.0 Introduction...2 2.0 Methodology...2 Appendix A...7 Insulation Board Fastening Patterns 4 feet 4 feet Boards Adhered Membranes...8 Insulation Board Fastening Patterns

More information

0845 0098 980 www.nicholsonsts.com

0845 0098 980 www.nicholsonsts.com 0845 0098 980 www.nicholsonsts.com ROOFTRAK The IFP is revolutionising the way we fix things to roofs. Technical Director of a leading UK roofing system manufacturer The ROOFTRAK-IFP A revolutionary solution

More information

PROPER GUTTER AND DOWNSPOUT SIZING

PROPER GUTTER AND DOWNSPOUT SIZING PROPER GUTTER AND DOWNSPOUT SIZING DESIGN OF ROOF DRAINAGE SYSTEMS ROOF DRAINAGE The roof is one of the most essential parts of a building as it protects occupants, contents, and interior of the structure

More information

ICC-ES Evaluation Report Reissued March 1, 2011 This report is subject to renewal in one year.

ICC-ES Evaluation Report Reissued March 1, 2011 This report is subject to renewal in one year. ICC-ES Evaluation Report www.icc-es.org (800) 423-6587 (562) 699-0543 ESR-900* Reissued March, 20 This report is subject to renewal in one year. A Subsidiary of the International Code Council DIVISION:

More information

SECTION 07550 - MODIFIED BITUMINOUS MEMBRANE ROOFING. A. Vapor barrier (base ply); cover board at existing roof deck.

SECTION 07550 - MODIFIED BITUMINOUS MEMBRANE ROOFING. A. Vapor barrier (base ply); cover board at existing roof deck. SECTION 07550 - PART I GENERAL 1.01 SECTION INCLUDES A. Vapor barrier (base ply); cover board at existing roof deck. B. Roof insulation at new roof deck. C. Modified bitumen membrane. D. Fluid applied

More information

Please read the entire document before purchasing and installing any of these products

Please read the entire document before purchasing and installing any of these products Please read the entire document before purchasing and installing any of these products USA SBS UNDERLAYMENT ROOFING UNDERLAYMENT SBS Mineral Surfaced MINERAL SURFACE CAP SHEET Ice and Water Protection

More information

HIGH PERFORMANCE PRE-APPLIED SYSTEM FOR BLIND SIDE & BELOW GRADE WATERPROOFING APPLICATIONS

HIGH PERFORMANCE PRE-APPLIED SYSTEM FOR BLIND SIDE & BELOW GRADE WATERPROOFING APPLICATIONS BSW HIGH PERFORMANCE PRE-APPLIED SYSTEM FOR BLIND SIDE & BELOW GRADE WATERPROOFING APPLICATIONS BSW is a fully reinforced Pre-Applied system membrane designed for horizontal and vertical external blind-side

More information

Roofing Systems. New Applications / Re-Roofing / Maintenance

Roofing Systems. New Applications / Re-Roofing / Maintenance Roofing Systems New Applications / Re-Roofing / Maintenance New Roof Installation In terms of the design and installation of an original roofing system (in conjunction with the construction of a new building),

More information

CHAPTER VII. TITLE: STANDARDS FOR NEW ROOFING July 2015 CONSTRUCTION, RE-ROOFING CONSTRUCTION AND ROOFING SYSTEM GUARANTEE REQUIREMENTS

CHAPTER VII. TITLE: STANDARDS FOR NEW ROOFING July 2015 CONSTRUCTION, RE-ROOFING CONSTRUCTION AND ROOFING SYSTEM GUARANTEE REQUIREMENTS TITLE: STANDARDS FOR NEW ROOFING CONSTRUCTION, RE-ROOFING CONSTRUCTION AND ROOFING SYSTEM GUARANTEE REQUIREMENTS Responsible Organization: Office of Facilities Planning Instructions: This Manual supersedes

More information

FOUNDATION INSULATING SYSTEM, INCLUDING WATERPROOFING AND DAMP PROOFING

FOUNDATION INSULATING SYSTEM, INCLUDING WATERPROOFING AND DAMP PROOFING FOUNDATION INSULATING SYSTEM, INCLUDING WATERPROOFING AND DAMP PROOFING insulation installed on foundation walls must be separated from the building interior with a code approved thermal barrier. Foam

More information

CITY OF WHITE BEAR LAKE BUILDING INSPECTION DEPARTMENT 4701 Highway 61 White Bear Lake, MN 55110 Fax: 651-429-8503. Re-Roofing: Asphalt Shingles

CITY OF WHITE BEAR LAKE BUILDING INSPECTION DEPARTMENT 4701 Highway 61 White Bear Lake, MN 55110 Fax: 651-429-8503. Re-Roofing: Asphalt Shingles CITY OF WHITE BEAR LAKE BUILDING INSPECTION DEPARTMENT 4701 Highway 61 White Bear Lake, MN 55110 Fax: 651-429-8503 Re-Roofing: Asphalt Shingles This is a summary of the standard requirements based on the

More information

DIVISION: 07 00 00 THERMAL AND MOISTURE PROTECTION SECTION: 07 41 13 METAL ROOF PANELS REPORT HOLDER: FIRESTONE BUILDING PRODUCTS COMPANY, LLC

DIVISION: 07 00 00 THERMAL AND MOISTURE PROTECTION SECTION: 07 41 13 METAL ROOF PANELS REPORT HOLDER: FIRESTONE BUILDING PRODUCTS COMPANY, LLC 0 ICC ES Report ICC ES (800) 423 687 (62) 699 043 www.icc es.org 000 Most Widely Accepted and Trusted ESR 3422 Reissued 09/201 This report is subject to renewal 09/2016. DIVISION: 07 00 00 THERMAL AND

More information

www.icc-es.org (800) 423-6587 (562) 699-0543 A Subsidiary of the International Code Council *Revised April 2014

www.icc-es.org (800) 423-6587 (562) 699-0543 A Subsidiary of the International Code Council *Revised April 2014 ICC-ES Evaluation Report ESR-1647* Issued July 2013 This report is subject to renewal August 1, 2015. www.icc-es.org (800) 423-6587 (562) 699-0543 A Subsidiary of the International Code Council DIVISION:

More information

CertainTeed. Self-Adhering Roof Systems for Low Slope Residential Roofs

CertainTeed. Self-Adhering Roof Systems for Low Slope Residential Roofs CertainTeed Self-Adhering Roof Systems for Low Slope Residential Roofs Goes down fast. Stays on strong. Flintlastic SA performs in all the right ways. What s more important to you? Speed of installation,

More information

DIVISION: 07 00 00 THERMAL AND MOISTURE PROTECTION SECTION: 07 32 16 CONCRETE ROOF TILES REPORT HOLDER:

DIVISION: 07 00 00 THERMAL AND MOISTURE PROTECTION SECTION: 07 32 16 CONCRETE ROOF TILES REPORT HOLDER: 0 ICC ES Report ICC ES (800) 423 6587 (562) 699 0543 www.icc es.org 000 Most Widely Accepted and Trusted ESR 1900 Reissued 03/2016 This report is subject to renewal 03/2017. DIVISION: 07 00 00 THERMAL

More information

CHICAGO ROOFING CONTRACTORS ASSOCIATION

CHICAGO ROOFING CONTRACTORS ASSOCIATION CHICAGO ROOFING CONTRACTORS ASSOCIATION JANUARY 22, 2016 Roofing Claims & Lawsuits Stephen M. Phillips Hendrick, Phillips, Salzman & Flatt, P.C. 230 Peachtree Street, Suite 2500 Atlanta, GA 30303 (404)

More information

CERTIFICATE NAME OF PRODUCT MANUFACTURER PRODUCT DESCRIPTION CERTIFICATION PROCEDURE. No VTT C-6044-10 Date of issue 11.10.2010, Updated July 1, 2011

CERTIFICATE NAME OF PRODUCT MANUFACTURER PRODUCT DESCRIPTION CERTIFICATION PROCEDURE. No VTT C-6044-10 Date of issue 11.10.2010, Updated July 1, 2011 CERTIFICATE NAME OF PRODUCT No VTT C-6044-10 Date of issue 11.10.2010, Updated July 1, 2011 H-CONTROL REFLEX+ reflective insulating vapour control layer for roof and wall applications MANUFACTURER ACTIS

More information

SECTION 07530 SINGLE PLY MEMBRANE ROOFING. 4. Minor repair to adjacent clay tile roofing and flashings.

SECTION 07530 SINGLE PLY MEMBRANE ROOFING. 4. Minor repair to adjacent clay tile roofing and flashings. SECTION 07530 PART 1 - GENERAL 1.01 DESCRIPTION A. This Section includes the flowing: 1. Removal of existing roofing membrane. Existing bur roof has one overlay and penetration mastic is asbestos containing.

More information

Protecting Roofing Systems Against Windstorm Damage

Protecting Roofing Systems Against Windstorm Damage Protecting Roofing Systems Against Windstorm Damage This brochure is made available for informational purposes only in support of the insurance relationship between FM Global and its clients. This information

More information

HURRICANE MITIGATION RETROFITS FOR EXISTING SITE-BUILT SINGLE FAMILY RESIDENTIAL STRUCTURES

HURRICANE MITIGATION RETROFITS FOR EXISTING SITE-BUILT SINGLE FAMILY RESIDENTIAL STRUCTURES HURRICANE MITIGATION RETROFITS FOR EXISTING SITE-BUILT SINGLE FAMILY RESIDENTIAL STRUCTURES 101 Retrofits Required. Pursuant to Section 553.844 553.884, Florida Statutes, strengthening of existing site-built,

More information

CONTINENTAL MATERIALS, INC. ALL-WEATHER APP INSTALLATION GUIDELINES

CONTINENTAL MATERIALS, INC. ALL-WEATHER APP INSTALLATION GUIDELINES CONTINENTAL MATERIALS, INC. ALL-WEATHER APP INSTALLATION GUIDELINES Page 1 APP INSTALLATION GUIDELINES This guide provides instructions for the installation of CMI All Weather APP roofing materials. Any

More information

Record of Work Experiences Trade Qualifier or Pre-Apprenticeship Credits ROOFER

Record of Work Experiences Trade Qualifier or Pre-Apprenticeship Credits ROOFER Department of Advanced Education and Skills Apprenticeship and Trades Certification Division Record of Work Experiences Trade Qualifier or Pre-Apprenticeship Credits ROOFER Note to Apprenticeship Applicants

More information

Design No. P736 September 26, 2003. Restrained Assembly Ratings 1, 1-1/2 or 2 Hr. (See Items 3, 7 and 8A)

Design No. P736 September 26, 2003. Restrained Assembly Ratings 1, 1-1/2 or 2 Hr. (See Items 3, 7 and 8A) Design No. P736 September 26, 2003 Restrained Ratings 1, 1-1/2 or 2 Hr (See Items 3, 7 and 8A) Ratings 1, 1-1/2 or 2 Hr (See Items 3, 7 and 8A) Beam Ratings 1, 1-1/2 or 2 Hr (See Items 7 and 8A) 1. Beam

More information

ISO Types 1-6: Construction Code Descriptions

ISO Types 1-6: Construction Code Descriptions ISO 1 Frame (combustible walls and/or roof) Class 1B Buildings where the exterior walls are wood or other combustible materials, including construction where the combustible materials are combined with

More information

EPDM System Repair and Cleaning

EPDM System Repair and Cleaning EPDM single-ply roof systems have represented a third of the volume of the low-sloped commercial market for close to twenty years. The majority of these roofs were installed to receive the manufacturer

More information

CF-Mesa, CF-Light Mesa, CF-Flute, CF-Metl-Plank, CF-Striated, CF-Santa Fe, CF-Architectural Flat, CF...

CF-Mesa, CF-Light Mesa, CF-Flute, CF-Metl-Plank, CF-Striated, CF-Santa Fe, CF-Architectural Flat, CF... Building Insulations - Walls and Ceilings (FM Approval Numbers 4411, 4651, 4880, 4881, 4882) Insulating materials may occur in building construction to reduce heat or sound transmission through a wall,

More information

PREMIUM LAMINATED ASPHALT SHINGLES Dallas, TX Tuscaloosa, AL Phillipsburg, KS

PREMIUM LAMINATED ASPHALT SHINGLES Dallas, TX Tuscaloosa, AL Phillipsburg, KS Application Instructions for THESE ARE THE MANUFACTURER S APPLICATION INSTRUCTIONS FOR THE ROOFING CONDITIONS DESCRIBED. TAMKO BUILDING PRODUCTS, INC. ASSUMES NO RESPONSIBILITY FOR LEAKS OR OTHER ROOFING

More information

FAST FACTS ADVANTAGES OF MULTI PLY BUILT-UP ROOFING. Asphalt Roofing Manufacturers Association

FAST FACTS ADVANTAGES OF MULTI PLY BUILT-UP ROOFING. Asphalt Roofing Manufacturers Association FAST FACTS ADVANTAGES OF MULTI PLY BUILT-UP ROOFING Roofing Manufacturers Association Why is a built-up roof considered a multi-ply roof? ARMA defines a built-up roofing system as a roof where multiple

More information

The Building Group First Tuesdays First Saint Paul s Lutheran Church 1301 North LaSalle Street, Chicago, Illinois

The Building Group First Tuesdays First Saint Paul s Lutheran Church 1301 North LaSalle Street, Chicago, Illinois Wiss, Janney, Elstner Associates, Inc. 10 South LaSalle Street, Suite 2600 Chicago, Illinois 60603 312.372.0555 tel 312.372.0873 fax www.wje.com The Building Group First Tuesdays October 2, 2012 Jason

More information

ROOF INSPECTION & MAINTENANCE

ROOF INSPECTION & MAINTENANCE Physical Plant Administration Facilities Maintenance Department ROOF INSPECTION & MAINTENANCE All roofs require periodic inspection and maintenance in order to perform as designed and to provide a long

More information

Commercial Roof Management

Commercial Roof Management Disclaimer: This material is designed and intended for general informational purposes only, and is not intended, nor shall it be construed or relied upon, as specific legal advice. Roof damage is a leading

More information

DIVISION: 06 00 00 WOOD, PLASTICS AND COMPOSITES SECTION: 06 05 83 SHOP APPLIED WOOD COATINGS SECTION: 06 16 00 SHEATHING REPORT HOLDER:

DIVISION: 06 00 00 WOOD, PLASTICS AND COMPOSITES SECTION: 06 05 83 SHOP APPLIED WOOD COATINGS SECTION: 06 16 00 SHEATHING REPORT HOLDER: 0 ICC ES Report ICC ES (800) 423 6587 (562) 699 0543 www.icc es.org 000 Most Widely Accepted and Trusted ESR 1365 Reissued 04/2016 This report is subject to renewal 04/2017. DIVISION: 06 00 00 WOOD, PLASTICS

More information

6 RETROFITTING POST & PIER HOUSES

6 RETROFITTING POST & PIER HOUSES Retrofitting Post & Pier Houses 71 6 RETROFITTING POST & PIER HOUSES by James E. Russell, P.E. 72 Retrofitting Post & Pier Houses Retrofitting Post & Pier Houses 73 RETROFITTING POST AND PIER HOUSES This

More information

Excerpts from the Canadian National Building Code (NBC)

Excerpts from the Canadian National Building Code (NBC) Excerpts from the Canadian National Building Code (NBC) Reproduced here with Permission of the Copyright Owner, the National Research Council of Canada, Institute for Research in Construction. For more

More information

Mark Cramer Inspection Services, Inc.

Mark Cramer Inspection Services, Inc. Mark Cramer Inspection Services, Inc. 492 Twentieth Avenue, Indian Rocks Beach, FL 34635-2970 (727) 595-4211 Fax (727) 596-7583 Certified Member #12085 American Society of Home Inspectors Construction

More information

CI SfB. (4-) Nn2. Onduline. Mini Profile. Onduline Garden Roof Range. Onduline Building Products Ltd

CI SfB. (4-) Nn2. Onduline. Mini Profile. Onduline Garden Roof Range. Onduline Building Products Ltd CI SfB (4-) Nn2 Onduline Mini Profile Onduline Garden Roof Range Onduline Building Products Ltd Onduline Garden Roof Range Onduline Mini Profile The new Onduline Mini Profile sheets have been designed

More information

Air-Conditioning, Heating, and Refrigeration Institute. Sheet Metal and Air-Conditioning Contractors National Association

Air-Conditioning, Heating, and Refrigeration Institute. Sheet Metal and Air-Conditioning Contractors National Association Air-Conditioning, Heating, and Refrigeration Institute Sheet Metal and Air-Conditioning Contractors National Association GUIDELINE B-1997 ACKNOWLEDGEMENT These guidelines for Roof Mounted Outdoor Air-

More information

Read and understand all installation instructions and precautions before installing. GENERAL APPLICATION INSTRUCTIONS

Read and understand all installation instructions and precautions before installing. GENERAL APPLICATION INSTRUCTIONS AC TOPSEAL SELF-ADHERED, GRANULAR SURFACED, SINGLE PLY, LOW SLOPE ROLLED ROOFING 3 X 33.3 = 100 SQ. FT. 10 YEAR MATERIAL LIMITED WARRANTY For Use on Porches / Sheds / Utility Buildings / Accessory Buildings

More information

Drexel Metals Inc. DMC 100SS 16oz min. Copper Mechanical Seam Metal Roof System over Plywood

Drexel Metals Inc. DMC 100SS 16oz min. Copper Mechanical Seam Metal Roof System over Plywood Drexel Metals Inc. DMC 100SS 16oz min. Copper Mechanical Seam Metal Roof System over Plywood Section 07411 Metal Roof Panels Part 1 General 1.1 Summary A. This section includes the following: a. Factory-formed

More information

Department of Veterans Affairs Quarterly Notice to Congress on Data Breaches Third Quarter of Fiscal Year 2015 April 1, 2015 through June 30, 2015

Department of Veterans Affairs Quarterly Notice to Congress on Data Breaches Third Quarter of Fiscal Year 2015 April 1, 2015 through June 30, 2015 VHA 4/1/15 VISN 01 Boston, MA 1 0 4/15/15 VISN 01 Boston, MA 1 0 4/22/15 VISN 01 Boston, MA 10 0 4/24/15 VISN 01 Boston, MA 1 0 4/27/15 VISN 01 Boston, MA 0 1 4/29/15 VISN 01 Boston, MA 0 1 4/30/15 VISN

More information

Firestone SBS Modified Bitumen Roofing System Design and Application Guide

Firestone SBS Modified Bitumen Roofing System Design and Application Guide SBS Modified Bitumen Roofing System Design and Application Guide October, 2013 Table of Contents 1.01 Introduction... 1 1.01.1.1 General Considerations... 1 1.01.1.2 Warranty... 3 1.01.1.3 QUALITY ASSURANCE...

More information

TARRANT COUNTY DETAIL STANDARDS

TARRANT COUNTY DETAIL STANDARDS TARRANT COUNTY DETAIL STANDARDS 1. Standard Coping 2. Coping at End Wall 3. Standard Sheet Metal Engagement Details 4. Gravel Guard 5. Gravel Guard Wall Termination 6. Gravel Guard, Gutter, and Downspout

More information

Chapter 3 Pre-Installation, Foundations and Piers

Chapter 3 Pre-Installation, Foundations and Piers Chapter 3 Pre-Installation, Foundations and Piers 3-1 Pre-Installation Establishes the minimum requirements for the siting, design, materials, access, and installation of manufactured dwellings, accessory

More information

ROOF ASSEMBLIES CHAPTER 9

ROOF ASSEMBLIES CHAPTER 9 CHAPTER 9 ROOF ASSEMBLIES SECTION R901 GENERAL R901.1 Scope. The provisions of this chapter shall govern the design, materials, construction and quality of roof assemblies. SECTION R902 ROOF CLASSIFICATION

More information

September 3, 2009. Ric Boyd, Public Works Director Ketchikan Gateway Borough 344 Front St. Ketchikan, AK 99901

September 3, 2009. Ric Boyd, Public Works Director Ketchikan Gateway Borough 344 Front St. Ketchikan, AK 99901 September 3, 2009 Ric Boyd, Public Works Director Ketchikan Gateway Borough 344 Front St. Ketchikan, AK 99901 RE: Ketchikan Gateway Borough Gateway Recreation Center Roof Observations and Intrusive Inspections

More information

STAYFLEX CORROSION CONTROL AND THERMAL INSULATION SYSTEM

STAYFLEX CORROSION CONTROL AND THERMAL INSULATION SYSTEM STAYFLEX CORROSION CONTROL AND THERMAL INSULATION SYSTEM Installed in Pre-engineered Steel Buildings Provides Lowest Cost Construction Method for CORROSIVE AND WET Environments PREFERRED SOLUTIONS, INC.

More information

HERITAGE WOODGATE LAMINATED ASPHALT SHINGLES Dallas, TX

HERITAGE WOODGATE LAMINATED ASPHALT SHINGLES Dallas, TX Application Instructions for THESE ARE THE MANUFACTURER S APPLICATION INSTRUCTIONS FOR THE ROOFING CONDITIONS DESCRIBED. TAMKO BUILDING PRODUCTS, INC. ASSUMES NO RESPONSIBILITY FOR LEAKS OR OTHER ROOFING

More information

WESTERN COOL ROOF SYSTEMS Sustainable - Energy Efficient FLUID APPLIED REINFORCED ROOF SYSTEM

WESTERN COOL ROOF SYSTEMS Sustainable - Energy Efficient FLUID APPLIED REINFORCED ROOF SYSTEM WESTERN COOL ROOF SYSTEMS Sustainable - Energy Efficient FLUID APPLIED REINFORCED ROOF SYSTEM SPECIFICATION NO. SMAA-2P-8xE UPGRADE SMOOTH SURFACE / CAP SHEET / SINGLE PLY 2 PLY POLYESTER REINFORCED ACRYLIC

More information

H-Stud Area Separation Wall System

H-Stud Area Separation Wall System 12 TH EDITION 09 21 16.33/NGC H-Stud Area Separation Wall System 09 21 16.33 139 H-STUD AREA SEPARATION WALL SYSTEM The fire-protection of gypsum-based Area Separation Walls is demonstrated in dramatic

More information

After reading this lesson you will be able to: 12.3 IMPORTANCE OF ROOF 12.4 TYPES OF ROOF IN A HOUSE

After reading this lesson you will be able to: 12.3 IMPORTANCE OF ROOF 12.4 TYPES OF ROOF IN A HOUSE 86 :: Certificate in Construction Supervision (CIVIL) 12 ROOF 12.1 INTRODUCTION The structure provided to cover the house surface (floor) is known as roof. For different situation and requirement, it is

More information

service above and beyond

service above and beyond service above and beyond Simon Roofing Creed Our top priority is to provide exceptional service to our customer. If we should stumble along the way, someone, anyone must immediately step up, take charge

More information

Georgia State University. Urban Life Building Roof Replacement

Georgia State University. Urban Life Building Roof Replacement ENGINEERING AND ENVIRONMENTAL 140 DECATUR STREET SE, ATLANTA, GA 30303 GEORGIA STATE UNIVERSITY - FACILITIES DESIGN & CONSTRUCTION 34 BROAD STREET, SUITE 100 ATLANTA, GA 30303 DRAWING INDEX A-0 PROJECT

More information

ITEM 599.06060008 THERMOPLASTIC MEMBRANE ROOFING

ITEM 599.06060008 THERMOPLASTIC MEMBRANE ROOFING DESCRIPTION Construct adhered membrane roofing system, roof insulation, and vapor retarder in accordance with these specifications. MATERIALS: General: Provide installed roofing membrane and base flashings

More information

Inspecting to a higher standard.

Inspecting to a higher standard. Inspecting to a higher standard. Rob Hopkin Silver Spring, MD 20902 Monday, June 2, 2014 ProTec Inspection Services Inc. 19736 Selby Ave Poolesville, MD 20837 301-972-8531 www.protec-inspections.com rob@protec-inspections.com

More information

RECOATING AND RENEWING SPF ROOFING SYSTEMS

RECOATING AND RENEWING SPF ROOFING SYSTEMS RECOATING AND RENEWING SPF ROOFING SYSTEMS Procedures, Regional Differences and type of coating systems Bruce Schenke Premium Spray Products REASONS TO RECOAT/RENEW Add a new coating layer to renew the

More information

Page & Turnbull imagining change in historic environments through design, research, and technology

Page & Turnbull imagining change in historic environments through design, research, and technology DCI+SDE STRUCTURAL EVALUATIONS OFFICE BUILDING, TOOL SHED & WATER TANK, AND BLACKSMITH & MACHINE SHOP BUILDINGS SAN FRANCISCO, CALIFORNIA [14290] PRIMARY PROJECT CONTACT: H. Ruth Todd, FAIA, AICP, LEED

More information

COMPARATIVE PERFORMANCE OF EPDM RUBBER ROOFING MEMBRANE AS PROTECTION AGAINST HAIL DAMAGE

COMPARATIVE PERFORMANCE OF EPDM RUBBER ROOFING MEMBRANE AS PROTECTION AGAINST HAIL DAMAGE www.epdmroofs.org COMPARATIVE PERFORMANCE OF EPDM RUBBER ROOFING MEMBRANE AS PROTECTION AGAINST HAIL DAMAGE By Ric Vitiello President Forensic Roof Consulting and Hail Damage Assessment Training www.benchmark-services.com

More information

How To Know If A Reflective Roofmembrane Is More Efficient

How To Know If A Reflective Roofmembrane Is More Efficient Wiss, Janney, Elstner Associates, Inc. 9511 North Lake Creek Parkway Austin, Texas 78717 512.257.4800 tel 512.219.9883 fax Texas Registered Engineering Firm F-0093 www.wje.com Sustainable Energy Efficient

More information

ANSI/SPRI Wind Design Standard Practice for Roofing Assemblies

ANSI/SPRI Wind Design Standard Practice for Roofing Assemblies Approved September 19, 2007 ANSI/SPRI WD-1 ANSI/SPRI Wind Design Standard Practice for Roofing Assemblies TABLE OF CONTENTS Section Page 1.0 INTRODUCTION...........................................................

More information

If you are a web registered user of ArlingontPermits.com you may also request an inspection at:

If you are a web registered user of ArlingontPermits.com you may also request an inspection at: TECHNICAL BULLETIN Community Development & Planning, Building Inspections TOPIC: Permits & Inspections for Roofing Replacement Effective November 1, 2011 Revised This Technical Bulletin will provide contractors

More information

FIRESTONE BUILT-UP ROOFING SYSTEMS APPLICATION GUIDE 3/14/2011

FIRESTONE BUILT-UP ROOFING SYSTEMS APPLICATION GUIDE 3/14/2011 FIRESTONE BUILT-UP ROOFING SYSTEMS APPLICATION GUIDE TABLE OF CONTENTS 2.01.1 GENERAL......2 2.02.1 JOB SITE CONSIDERATIONS (CAUTION AND WARNINGS)...2 2.03.1 ROOF SUBSTRATE PREPARATION...2 2.04.1 WOOD

More information

Built-up roofing solutions with rigid insulation boards on concrete decks for new-build and refurbishment E-a5

Built-up roofing solutions with rigid insulation boards on concrete decks for new-build and refurbishment E-a5 Cl Sfb (27-9) Rn7 M2 December 2004 Built-up roofing solutions with rigid insulation boards on concrete decks for new-build and refurbishment E-a5 Fesco, Fesco S, Retrofit, Retrofit S, Fesco Fillet, PF,

More information

ROOF ASSEMBLIES AND ROOFTOP STRUCTURES

ROOF ASSEMBLIES AND ROOFTOP STRUCTURES CHAPTER 15 ROOF ASSEMBLIES AND ROOFTOP STRUCTURES SECTION 1501 GENERAL 1501.1 Scope. The provisions of this chapter shall govern the design, materials, construction and quality of roof assemblies, and

More information

BLACK JACK ALL WEATHER ROOF COATING

BLACK JACK ALL WEATHER ROOF COATING PAGE: 1 of 6 PRINT DATE: 16/09/2004 BLACK JACK ALL WEATHER ROOF COATING DESCRIPTION BLACK JACK ALL WEATHER ROOF COATING is a solvent based, full bodied black brushable compound with added fibres for reinforcement.

More information

!!! !!!! !!! !!! !!! !!! !!!!!!!!! Table of Contents! Section 1: Most Common Types of Flat Roofing! Section 2: Better Understand Your Flat Roof!

!!! !!!! !!! !!! !!! !!! !!!!!!!!! Table of Contents! Section 1: Most Common Types of Flat Roofing! Section 2: Better Understand Your Flat Roof! Table of Contents Section 1: Most Common Types of Flat Roofing Section 2: Better Understand Your Flat Roof Section 3: Flat Roofing Cost in 2015: Four Factors that Dictate Section 4: Planning A Flat Roofing

More information

Property Policyholder Risk Improvement Report and Hurricane Survey

Property Policyholder Risk Improvement Report and Hurricane Survey Risk Engineering Property Policyholder Risk Improvement Report and Hurricane Survey Zurich Services Corporation Risk Engineering 1400 American Lane Schaumburg, IL 60196-1056 847.605.6000 Fax: 847.605.7854

More information

RACKING AND ATTACHMENT CRITERIA FOR EFFECTIVE MEMBRANE ROOF SYSTEM INTEGRATION Public Version 1: July 9, 2012

RACKING AND ATTACHMENT CRITERIA FOR EFFECTIVE MEMBRANE ROOF SYSTEM INTEGRATION Public Version 1: July 9, 2012 RACKING AND ATTACHMENT CRITERIA FOR EFFECTIVE MEMBRANE ROOF SYSTEM INTEGRATION Public Version 1: July 9, 2012 Commercial rooftops represent the most available, sustainable and secure real estate for new

More information

GUIDELINE SPECIFICATIONS

GUIDELINE SPECIFICATIONS GUIDELINE SPECIFICATIONS GORDON SOFFIT-SHIELD - An Exterior Metal Soffit System DIVISION 05 5800 or DIVISION 07 7700 Note To Specifier: SOFFIT-SHIELD should be installed by tradesmen that are experienced

More information

SECTION 07400 STANDING SEAM METAL ROOF

SECTION 07400 STANDING SEAM METAL ROOF SECTION 07400 STANDING SEAM METAL ROOF PART 1 - GENERAL 1.01 SECTION INCLUDES A. Work described in this section includes pre-formed standing seam metal roofing system complete with clips, perimeter and

More information

Site Inspection Report

Site Inspection Report Site Inspection Report Project Title: 1 Canada Square Location: 1 Canada Square, Canary Wharf, London Date of Inspection: 16/05/12 System / Products: TBA (suggested flame free application) Attendees: G

More information

CHAPTER 6 ASPHALT ROLL ROOFING

CHAPTER 6 ASPHALT ROLL ROOFING CHAPTER 6 ASPHALT ROLL ROOFING Section I. DESCRIPTION AND GENERAL DISCUSSION 6.1.1 General 6.1.3 Mineral-Surfaced Asphalt roll roofing is roofing in sheet form Mineral-surfaced roll roofing is composed

More information

GENERAL REQUIREMENTS HENRY WARRANTED COMMERCIAL ROOFING SYSTEMS

GENERAL REQUIREMENTS HENRY WARRANTED COMMERCIAL ROOFING SYSTEMS GENERAL REQUIREMENTS HENRY WARRANTED COMMERCIAL ROOFING SYSTEMS 1.0 STATEMENT OF POLICY The overall performance of a roofing system can be affected by factors other than the roof system installation. Henry

More information

DIVISION: 07 00 00 THERMAL AND MOISTURE PROTECTION SECTION: 07 32 16 CONCRETE ROOF TILES REPORT HOLDER: BORAL ROOFING

DIVISION: 07 00 00 THERMAL AND MOISTURE PROTECTION SECTION: 07 32 16 CONCRETE ROOF TILES REPORT HOLDER: BORAL ROOFING 0 ICC-ES Report ICC-ES (800) 423-6587 (562) 699-0543 www.icc-es.org 000 Most Widely Accepted and Trusted ESR-1647 Reissued 08/2015 This report is subject to renewal 08/2016. DIVISION: 07 00 00 THERMAL

More information

Memtec Single Ply PVC Membrane Roofing and Waterproofing Technology. Modern Efficient Performance Cost Effective Flat Roofing Systems

Memtec Single Ply PVC Membrane Roofing and Waterproofing Technology. Modern Efficient Performance Cost Effective Flat Roofing Systems Memtec Single Ply PVC Membrane Roofing and Waterproofing Technology Modern Efficient Performance Cost Effective Flat Roofing Systems Introduction A complete range of Memtec Roofing and Waterproofing Single

More information

Residential Deck Safety, Construction, and Repair

Residential Deck Safety, Construction, and Repair Juneau Permit Center, 4 th Floor Marine View Center, (907)586-0770 This handout is designed to help you build your deck to comply with the 2006 International Residential Building code as modified by the

More information