Design of electrical power system for a 1000MW nuclear power generating station

Size: px
Start display at page:

Download "Design of electrical power system for a 1000MW nuclear power generating station"

Transcription

1 Design of electrical power system for a 1000MW nuclear power generating station K Raja, K Yesunadam Dept. of Electrical & Electronics Engineering, Lingaya s Institute of Management & Technology, Vijayawada, India. {raja.k233, kondayesunadam1}@gmail.com Abstract The successful operation of any nuclear power generating stations depends on the electrical power supply systems. The electrical power supply systems have normal, emergency power systems and uninterruptable power supply systems. These systems play a vital role to operate and safely shutdown the reactor during both normal and anticipated conditions. The objective of this paper is design the electrical power system for a 1000MW nuclear power generating station. For nuclear power generating stations the emphasis is based on the design of systems is based upon nuclear safety, personal safety reliability and economic considerations. This typical electrical system is designed for generalized nuclear power generating station irrespective of type of nuclear plant. The reference for this design was based on IEEE papers & standards. This work covers the designing of the electrical power system for a nuclear power generating station. Keywords- Normal power supply systems (NPS), Emergency power supply Systems (EPS), UPS systems. I. INTRODUCTION The typical system has a net output of 1000 MW. In achieving this station relies on auxiliary plant and services whose electrical power is supplied from the AC power systems. The total connected load is in excess of 100 MW. The electrical system is the main source of power to the reactor cooling auxiliaries during normal operation, for the protection system and the safety systems during normal and fault conditions. This paper will consider the designs of both the Emergency power supply systems [1] and the Normal power supply systems [2]. Both offsite (grid) and on-site (Diesel generators) electrical power supply systems are provided and the reliability of both these systems has direct effect on the safety of the plant. The electrical power supply systems design is as follow: Off-site power system(grid connection) Turbo-Generator and its auxiliaries. Class IV-Normal AC power supply systems Class1E-Emergency power supply systems. (Class III AC Emergency power supply system. Class II-AC supply from battery & Inverter Class -1 DC supply from batteries.) Variable speed drives, Preheating systems, Lighting, cabling and protection systems II. NORMAL POWER SUPPLY SYSTEM The Normal Power supply System connects the power station to the National Transmission System (Grid) and distributes power throughout the power station at system voltages postulated by engineering considerations. This power is used both for auxiliaries required to operate the power station and to supply the Emergency power supply Systems with its preferred source of power. This power is also called as Off-site power The designed system has bus voltage of 11kV. Safety Design Bases The MPS provides power to process plant not forming a part of the essential systems but which may make a significant contribution to nuclear safety,their availability is desirable for nuclear operation and safety To supply power to auxiliary loads with a high reliability and integrity so as to limit the number of challenges to the EPS All supplies are designed to be continuously available during routine operation s including those associated with a reactor trip with the grid[3] 11 kv System The connection of the NPS to the grid is in the power station's 400kV substation. The substation is designed to operate with both bus-coupler breakers and both bus-section breakers closed. Individual circuits supplying the NPS will be selected to either the main busbar or the reserve busbar. The system has two unit buses and two station buses. This system has generator transformer, unit auxiliary transformers, station transformer as shown in figure

2 3.3kV System The 3.3kV NPS derives its power supply only from the 11 kv NPS. The system consists of buses termed unit bus and station bus. The unit bus generally supply auxiliaries and loads directly associated with the turbo-generator operation and the station bus supply auxiliaries and loads associated with station services. 415V System The 415V NPS supplies power to non-safety related equipment which is either associated with the turbo-generator or required for station services. Generally all 415V switchboards associated with power generation or station services will be radially fed and their power sources derived from the 3.3kV NPS. The system consists of two tiers of switchgear types ie. Load centres and motor control centres. Load centres incorporate a 3.3kVl433V Class 'C' AN transformer fed by a motor switching device/circuit breaker on a 3.3kV unit or station switchboard of the same separation group. III. EMERGENCY POWER SUPPLY SYSTEMS The Emergency power supply systems (EPS) are divided into four separation groups or trains and provide power to all equipment required to ensure the safety of the Reactor. To ensure that these systems meet their safety functional requirements detailed safety criteria must be satisfied. The following Safety Design Bases include both general and those specific to the EPS. Safetv Design Bases The EPS is designed and qualified to adequately survive external hazards such as lightning, earthquakes, high winds and floods with consideration given to extremes of ambient temperature. The postulated internal hazard such as fire, internal missiles or pipe break coincident with loss of grid sufficient equipment in the EES will remain. Functional to allow a safe shutdown of the Reactor. The separation segregation and isolation criteria for plant and cabling are applied to preserve the independence of redundant essential equipment. The EPS is divided into four similar trains. Each train is capable of supplying its connected loads independently of the other three trains. All auxiliaries and Services required for continued operation of a train are derived from that same train of the EES. The EES will operate when power supplies are available from either on-site or off-site (grid) power sources. Each EES train has its own associated and independent essential diesel generator. Connections from the Main Power Systems are made through qualified devices designed to isolate these connections when necessary [4]. 110V DC Electrical System The function of the llov DC Electrical System is to provide battery backed power, control and switching supplies to the essential switchgear and control equipments. This includes supplies to DC driven Heating, Ventilating and Cooling (HVAC) plant for the essential switchgear, reactor protection equipment and control gear rooms located in the control building. The 11OV DC comprises four trains of equipment, each having a battery, charger, switch board and associated distribution fuse boards for each of the primary and secondary systems within a train. The 110V DC system is normally energised at all times from the 415V system. 11OV AC Essential Uninterruptible Power Supply System The function of the 11OV AC Essential Uninterruptible Power Supply (UPS) System is to provide battery backed single phase instrumentation supplies to control cubicles and other essential equipment. The 11OV AC Essential UPS System comprises four trains of equipment each having a single phase inverter, charger, static switch unit, battery, switchboard and associated distribution fuseboards for each of the primary and secondary systems within a train. Essential UPS System is normally energised at all times from the 415V system. Generally, all electrical plant is located in dedicated rooms with controlled environmental conditions. The Main Electrical Power System..The function of the llov AC Uninterruptible Power Supply (UPS) System is to provide battery backed single phase instrumentation supplies to the control cubicles associated with the data processing system and all other equipment requiring a non-essential UPS.The 11OV AC UPS System comprises two trains of equipment each having a single phase inverter, charger, static switch unit, battery, switchboard and associated distribution fuse boards.. 48V DC Power System The function of the 48V DC Power System is to provide battery backed power for remote control relays for the main station switchgear. The system is significant to safety in that it is used to support restoration of off-site supplies to the system 250V DC System The principal function of the 250V DC Main is to provide battery backed power for the main turbo-generators DC driven plant. These are installed to prevent mechanical damage to the main turbine in the event of loss of normal AC supplies coincident with a turbine trip.. The 250V DC system comprises two trains of equipment each having two batteries, two chargers, two switchboards and associated distribution fuse boards. The system is normally energised at all times from the 415V plant protection boards with the chargers float charging the batteries. IV. DESIGNING PARAMETERS The electrical systems are required to perform reliably and their parameters to remain within defined tolerances during all

3 steady state operating conditions. The frequency excursions which have been addressed within the design are as follows [3]: The Voltage limits will be permitted to exceed the nominal +_ 6% limit under transient conditions. The tolerances, both during steady state and transient conditions, are a significant factor in the design and specification of the mechanical systems and plant. The voltage profile for the voltage levels at the load terminals are given in Table 2 [3] The electrical systems design is to be verified by a series of calculations/studies to demonstrate that their performance is satisfactory under all credible conditions of operation. The studies will include the following: 50 Hz Nominal frequency Hz Full station output to be maintained Hz Output may be reduced with frequency, although Frequencies in the range Hz will not exceed 15 minutes duration Hz System load flow Steady state voltage profile Fault levels Frequencies in this range will not exceed 15 minutes duration Hz These frequencies will not persist for more than 1 minute. Table 2. Voltage Profile for the AC Power System Voltage Levels Nomi nal ge V Volta Up per (%) Stea dy Stat e (%) Motor starting studies Fault recovery studies Transi ent EES (%) 11KV +6-5 N/A K V Transient MPS (%) The System Fault Levels are given in table 3 below.[3] Fault level (MVA) e) k) Table 3. System Fault Levels 11kV 3.3kV 415VLC 415V 900(Mak 750(Brea MCC The Equipment Parameters are given in table 4 below.[3] The Main Power Systems Plant Parameters are given in table 5 [4] Main Power Systems Plant Parameters(Per Train) System Battery Charger/UPS 110V DC 1200 A hr 200A 48V DC (Control Building) 48V House) Table 4 11kV 3.3kV 415 V Interrupt ing Device Continuous Short Circuit Largest Connected Motor Vacu um Circuit er DC(Turbine 800 A hr 2 250A 400 A hr A 250V DC A hr A 110V UPS(Turbine House) Break Vacuu m Circuit Breake r/motor switch Device 3150A 2500A/450 A 121kA/3 9.4kA 7300 kw 40kA/11k A W 1130k LC con tactor 324A 43kA 166 kw 800 A hr 150 KVA 110V UPS(TSC) 400 A hr 50 KVA 415V MCC conta ctor 47A 43kA 22k W

4 Figure 1: Normal Power System & Emergency Power system of a Nuclear Generating Station

5 The Emergency power Systems Plant Parameters are given in table 6 [4] Emergency Electrical Systems Plant Parameters(Per Train) System Battery Charger/U PS 110V DC (Primary) 600 A hr 160A 110V (Secondary) DC 600 A hr 160A 48V DC(Primary) 1200 A hr A 48V DC(Secondary) A hr 2 40 A 110V UPS(Primary) 900 A hr 50 KVA 110V UPS(Secondary) 800 A hr 50 KVA V. CONCLUSION This paper covers the designing of the electrical power system of a nuclear power plant. The efforts made to design the system are only indicative. In actual practice lot of considerations to be taken to design the electrical systems. The type of nuclear plant also very essential, But this design is generalized for all types of nuclear plants. The most important factor in designing is economic considerations naturally plays a significant role in the nuclear power generating station. REFERENCES [1] K Raja,N Theivarajan Emergency Power Supply System of a Nuclear Power Plant-Modelling and Simulation Studies of Diesel Generators and Load Pickup on Emergency Transfer International Conference on Electrical Energy Systems (ICEES 2011), 3-5 Jan [2] M Prasad, N Theivarajan Normal Power Supply System of a Nuclear Power Plant-Modeling and Simulation Studies for Fast Bus Transfer International Conference on Electrical Energy Systems (ICEES 2011), 3-5 Jan [3] N Stenstrom, The design of the AC electrical power systems IEEE Electrical and Control Aspects of the Sizewell B PWR,International Conference on Date:14-15 Sep [4] B Wheeler, Design of the DC and UPS electrical power systems IEEE Electrical and Control Aspects of the Sizewell B PWR,International Conference on Date:14-15 Sep [5] K.E.Yeager,J.R.Willis, Modelling of Emergency Diesel- Generators in an 800 MW Nuclear Power Plant, IEEETrans on Energy Conversion,Vol.8, No.3,September1993. [6] Modern Power Station Practice, Third edition, is incorporating Modern Power System Practice, British Electricity International London, Volume D, Electrical systems & Equipment, [7] IEEE Std , Criteria for Class 1E Power Systems for Nuclear Power Generating Stations. [8] IEEE Std , Qualification of Class 1E Lead Storage Batteries for Nuclear Power Generating Stations. [9] IEEE Std , Recommended Practice for the Design of DC Auxiliary Power Systems for Generating Stations. [10] IEEE Design Guide for Electric Power Service Systems for Generating Stations, IEEE Std [11] IEEE Std , Qualification of Class 1E Static Battery Chargers and Inverters for Nuclear Power Generating Stations. [12] IEEE std 387. Criteria for diesel generator units applied as stand by power supplies for Nuclear Power Generating station

ANCILLARY EQUIPMENT AND ELECTRICAL EQUIPMENT Power Supply Systems and Electrical Equipment for Desalination Plants - Y.M. Hamud and A.H.

ANCILLARY EQUIPMENT AND ELECTRICAL EQUIPMENT Power Supply Systems and Electrical Equipment for Desalination Plants - Y.M. Hamud and A.H. POWER SUPPLY SYSTEMS AND ELECTRICAL EQUIPMENT FOR DESALINATION PLANTS Y.M. Hamud and A.H. Anwar Abu Dhabi Water and Electricity Authority, Abu Dhabi, UAE Keywords : Electrical System, Network for Desalination,

More information

Generic PCSR Sub-chapter 15.4 : Electrical Equipment

Generic PCSR Sub-chapter 15.4 : Electrical Equipment Form10/00 Document ID : GA91-9101-0101-15004 Document Number : EE-GDA-C284 Revision Number : A Generic Design Assessment Generic PCSR Sub-chapter 15.4 : Electrical Equipment Hitachi-GE Nuclear Energy,

More information

C.I.8.2 Offsite Power System. C.I.8.2.1 Description

C.I.8.2 Offsite Power System. C.I.8.2.1 Description C.I.8 Electric Power The electric power system is the source of power for station auxiliaries during normal operation, and for the reactor protection system and ESF during abnormal and accident conditions.

More information

Nuclear Power Plant Electrical Power Supply System Requirements

Nuclear Power Plant Electrical Power Supply System Requirements 1 Nuclear Power Plant Electrical Power Supply System Requirements Željko Jurković, Krško NPP, zeljko.jurkovic@nek.si Abstract Various regulations and standards require from electrical power system of the

More information

Tour of new eircom Data Centre Blanchardstown by Dervan Engineering Consultants 11 th March 2015

Tour of new eircom Data Centre Blanchardstown by Dervan Engineering Consultants 11 th March 2015 Tour of new eircom Data Centre Blanchardstown by Dervan Engineering Consultants 11 th March 2015 Presentation Outline Mechanical Overview Chillers and Pumps Pipework and Ancillaries In Row Cooling Units

More information

Cahier technique no. 196

Cahier technique no. 196 Collection Technique... Cahier technique no. 196 Integration of local power generation in industrial sites and commercial buildings T. Hazel "Cahiers Techniques" is a collection of documents intended for

More information

Unified requirements for systems with voltages above 1 kv up to 15 kv

Unified requirements for systems with voltages above 1 kv up to 15 kv (1991) (Rev.1 May 2001) (Rev.2 July 2003) (Rev.3 Feb 2015) Unified requirements for systems with voltages above 1 kv up to 15 kv 1. General 1.1 Field of application The following requirements apply to

More information

Totally Integrated Power SIESTORAGE. The modular energy storage system for a reliable power supply. www.siemens.com/siestorage

Totally Integrated Power SIESTORAGE. The modular energy storage system for a reliable power supply. www.siemens.com/siestorage Totally Integrated Power SIESTORAGE The modular energy storage system for a reliable power supply www.siemens.com/siestorage Totally Integrated Power (TIP) We bring power to the point. Our products, systems,

More information

Standards in Marine Power Systems. APEC 2014 Session IS2.1 Power Electronic Standards Roger Dougal University of South Carolina Columbia, SC 29208

Standards in Marine Power Systems. APEC 2014 Session IS2.1 Power Electronic Standards Roger Dougal University of South Carolina Columbia, SC 29208 Standards in Marine Power Systems APEC 2014 Session IS2.1 Power Electronic Standards Roger Dougal University of South Carolina Columbia, SC 29208 Need is Driven by Electrification Oasis of the Seas DDG

More information

For a phase-to-phase voltage between 100 V and 1000 V. The standard ratings are: 400 V - 690 V - 1000 V (at 50 Hz)

For a phase-to-phase voltage between 100 V and 1000 V. The standard ratings are: 400 V - 690 V - 1000 V (at 50 Hz) 24 1. NETWORK CONFIGURATIONS definition Standard IEC 38 defines voltage ratings as follows: - Low voltage () For a phase-to-phase voltage between 100 V and 1000 V. The standard ratings are: 400 V - 690

More information

Fukushima Daini Nuclear Power Station: Progress Status Based on the Recovery Plan (As of the End of April 2013)

Fukushima Daini Nuclear Power Station: Progress Status Based on the Recovery Plan (As of the End of April 2013) Attachment 1 Progress milestone dates are defined as follows: : The date when an equipment is removed power station: The date when an equipment is carried into the relevant building within the premises

More information

Chapter 1. Network Structures

Chapter 1. Network Structures Chapter 1 Network Structures Definition Standard IEC 60038 defines voltage ratings as follows: Low voltage (): for a phase-to-phase voltage of between 100 V and 1,000 V, the standard ratings are: 400 V

More information

UNITED STATES NUCLEAR REGULATORY COMMISSION OFFICE OF NUCLEAR REACTOR REGULATION OFFICE OF NEW REACTORS WASHINGTON, DC 20555-0001.

UNITED STATES NUCLEAR REGULATORY COMMISSION OFFICE OF NUCLEAR REACTOR REGULATION OFFICE OF NEW REACTORS WASHINGTON, DC 20555-0001. OMB Control No.: 3150-0012 ML12074A115 UNITED STATES NUCLEAR REGULATORY COMMISSION OFFICE OF NUCLEAR REACTOR REGULATION OFFICE OF NEW REACTORS WASHINGTON, DC 20555-0001 July 27, 2012 NRC BULLETIN 2012-01:

More information

Power Plant Electrical Distribution Systems

Power Plant Electrical Distribution Systems PDH Course E184 Power Plant Electrical Distribution Systems Gary W Castleberry, PE 2008 PDH Center 2410 Dakota Lakes Drive Herndon, VA 20171-2995 Phone: 703-478-6833 Fax: 703-481-9535 www.pdhcenter.com

More information

How To Choose A Transformer

How To Choose A Transformer Consider open loop MV network as an example source 1 source 2 NC NC NC or NO main MV switchboard A B Detail design of substation NC NC NC NO NC NC switchboard 1 switchboard 2 switchboard 3 MV MV MV LV

More information

DRAFT REGULATORY GUIDE DG-1154 (Proposed Revision 2 of Regulatory Guide 1.128, dated October 1978)

DRAFT REGULATORY GUIDE DG-1154 (Proposed Revision 2 of Regulatory Guide 1.128, dated October 1978) U.S. NUCLEAR REGULATORY COMMISSION October 2006 OFFICE OF NUCLEAR REGULATORY RESEARCH Division 1 DRAFT REGULATORY GUIDE Contact: W.S. Raughley (301) 415-7577 DRAFT REGULATORY GUIDE DG-1154 (Proposed Revision

More information

Office for Nuclear Regulation

Office for Nuclear Regulation ONR GUIDE Essential Services Document Type: Nuclear Safety Technical Assessment Guide Unique Document ID and Revision No: Date Issued: May 2013 Review Date: May 2016 Approved by: D Senior Director Regulatory

More information

Switchgear and Metal-Enclosed Bus

Switchgear and Metal-Enclosed Bus Section 18 Switchgear and Metal-Enclosed Bus 180. SWITCHGEAR ASSEMBLIES 180A. General Requirements for All Switchgear. This rule covers general requirements for all switchgear. Examples of switchgear found

More information

Electric Power Distribution Systems Operations

Electric Power Distribution Systems Operations Naval Facilities Engineering Command 200 Stovall Street Alexandria, Virginia 22332-2300 Electric Power Distribution Systems Operations NAVFAC MO-201 April 1990 SN 0525-LP-320-1900 FOREWORD This manual

More information

Emergency Power System Services Industrial UPS, Batteries, Chargers, Inverters and Static Switches

Emergency Power System Services Industrial UPS, Batteries, Chargers, Inverters and Static Switches Emergency Power System Services Industrial UPS, Batteries, Chargers, Inverters and Static Switches Downtime Is Not An Option The industrial uninterruptible power supply (UPS) is the foundation of your

More information

CONSULTATION PAPER FOR PROPOSED MODIFICATIONS TO THE TRANSMISSION CODE

CONSULTATION PAPER FOR PROPOSED MODIFICATIONS TO THE TRANSMISSION CODE CONSULTATION PAPER FOR PROPOSED MODIFICATIONS TO THE TRANSMISSION CODE Closing date for submission of representations: 30 th Sep 2014, 5 pm 18 AUG 2014 ENERGY MARKET AUTHORITY 991G Alexandra Road #01-29

More information

ELECTRICAL ENGINEERING DESIGN CRITERIA APPENDIX F

ELECTRICAL ENGINEERING DESIGN CRITERIA APPENDIX F ELECTRICAL ENGINEERING DESIGN CRITERIA APPENDIX F TABLE OF CONTENTS Appendix F - Electrical Engineering Design Criteria F.1 Introduction...F-1 F.2 Codes and Standards...F-1 F.3 Switchyard and Transformers...F-1

More information

Inverter / Charger Installation General Operations and AC and DC Connections

Inverter / Charger Installation General Operations and AC and DC Connections Inverter / Charger Installation General Operations and AC and DC Connections The Inverter is just one piece. Sometimes, a tendency is to mount the inverter and batteries, and make it work It is better

More information

Engineering innovation

Engineering innovation Eaton's Electrical Engineering Services & Systems Solutions Focus Seamless Solutions for Reliable, Efficient and Safe Power Systems Engineering innovation Progressive solutions for today s power systems

More information

ENERGY NETWORKS ASSOCIATION. Electricity Industry EMF Measurement Protocol for High Field Areas

ENERGY NETWORKS ASSOCIATION. Electricity Industry EMF Measurement Protocol for High Field Areas ENERGY NETWORKS ASSOCIATION Electricity Industry EMF Measurement Protocol for High Field Areas Contents 1 Introduction 1.1 Background 1.2 High Field Areas 2 High Field Area - Generation Businesses 2.1

More information

Arc Flash Mitigation. Remote Racking and Switching for Arc Flash danger mitigation in distribution class switchgear.

Arc Flash Mitigation. Remote Racking and Switching for Arc Flash danger mitigation in distribution class switchgear. Arc Flash Mitigation Remote Racking and Switching for Arc Flash danger mitigation in distribution class switchgear. Distance is Safety We will discuss through examples of actual occurrences and possible

More information

Product brochure Multi Functional Switchgear PASS M00 72.5 kv Flexible and compact switchgear solutions for windfarms

Product brochure Multi Functional Switchgear PASS M00 72.5 kv Flexible and compact switchgear solutions for windfarms Product brochure Multi Functional Switchgear PASS M00 72.5 kv Flexible and compact switchgear solutions for windfarms The future of Wind Farms As offshore wind farms move towards deploying higher capacity

More information

This is a Master s degree level apprenticeship which includes academic learning combined workplace learning and training.

This is a Master s degree level apprenticeship which includes academic learning combined workplace learning and training. Power Engineer Degree Apprenticeship The UK s energy sector is integral to the prosperity and stability of the UK economy as a whole, delivering an absolutely fundamental service for all its citizens.

More information

Rule 5.500 Fast Track Analysis for National Life Insurance Co.

Rule 5.500 Fast Track Analysis for National Life Insurance Co. Rule 5.500 Fast Track Analysis for National Life Insurance Co. For a 500 kw Solar array to be located at 155 Northfield Street in Montpelier, Vermont Green Mountain Power Pam Allen Date: 5/31/13 SECTION

More information

Part 1 System Modeling & Studies for Existing Systems

Part 1 System Modeling & Studies for Existing Systems Part 1 System Modeling & Studies for Existing Systems Operation Technology, Inc. Copyright 2009 Result of rapid release of energy due to an arcing fault between two conductors. Bus voltages > 208V Temperatures

More information

Fire Protection Program Of Chashma Nuclear Power Generating Station Pakistan Atomic Energy Commission 5/28/2015 1

Fire Protection Program Of Chashma Nuclear Power Generating Station Pakistan Atomic Energy Commission 5/28/2015 1 Fire Protection Program Of Chashma Nuclear Power Generating Station Pakistan Atomic Energy Commission 5/28/2015 1 Nuclear Power in Pakistan Nuclear Power Plants Capacity (MWe) Year of Commissioning In

More information

SWITCHGEAR SOLUTIONS FOR MISSION CRITICAL APPLICATIONS. Presented by SAI Advanced Power Solutions

SWITCHGEAR SOLUTIONS FOR MISSION CRITICAL APPLICATIONS. Presented by SAI Advanced Power Solutions SWITCHGEAR SOLUTIONS FOR MISSION CRITICAL APPLICATIONS POWER DISTRIBUTION RACKS IN A MISSION CRITICAL SYSTEM MODULES IN A MISSION CRITICAL SYSTEM UPS Convertor Main Inverter Load Battery BPC UPS & BATTERY

More information

Electric Power in Airplane. Student: Maja Knezev Course ELEN 615, 31 st August 2006

Electric Power in Airplane. Student: Maja Knezev Course ELEN 615, 31 st August 2006 Electric Power in Airplane Student: Maja Knezev Course ELEN 615, 31 st August 2006 Power sources on aircraft engine driven AC generators, auxiliary power units (APUs), external power and ram air turbines.

More information

Best Practices, Benefits and Economics of Load Testing IEEE PES Fort Worth, TX Chapter July 16, 2013

Best Practices, Benefits and Economics of Load Testing IEEE PES Fort Worth, TX Chapter July 16, 2013 Best Practices, Benefits and Economics of Load Testing IEEE PES Fort Worth, TX Chapter July 16, 2013 Mark Siira ComRent International 1 8/1/2013 Agenda Introduction Overview of Load Bank Testing Benefits

More information

EMTP STUDIES PERFORMED TO INSERT LONG AC CABLES IN THE FRENCH GRID

EMTP STUDIES PERFORMED TO INSERT LONG AC CABLES IN THE FRENCH GRID Tension (kv) Impedance (Ohms) EMTP STUDIES PERFORMED TO INSERT LONG AC CABLES IN THE FRENCH GRID frequency (Hz) Simon DESCHANVRES Yannick VERNAY RTE, CNER, Substations Department t (ms) EMTP-RV Users Group

More information

NPCC Regional Reliability Reference Directory # 8 System Restoration

NPCC Regional Reliability Reference Directory # 8 System Restoration NPCC Regional Reliability Reference Directory # 8 Task Force on Coordination of Operations Revision Review Record: October 21, 2008 Adopted by the Members of the Northeast Power Coordinating Council, Inc.

More information

David Payne, P.E. Associate Director February 18, 2014

David Payne, P.E. Associate Director February 18, 2014 David Payne, P.E. Associate Director February 18, 2014 Overview of Texas A&M University State's first public institution of higher education, was opened on Oct. 4, 1876 as the Agricultural and Mechanical

More information

16 West Coast Regional Plan

16 West Coast Regional Plan 16 West Coast Regional Plan 16.1 Regional overview 16.2 West Coast transmission system 16.3 West Coast demand 16.4 West Coast generation 16.5 West Coast significant maintenance work 16.6 Future West Coast

More information

UTILITIES DEPARTMENT NORTH CAMPUS DISASTER RECOVERY PLAN

UTILITIES DEPARTMENT NORTH CAMPUS DISASTER RECOVERY PLAN Page 1 of 27 UTILITIES DEPARTMENT NORTH CAMPUS DISASTER RECOVERY PLAN Page 2 of 27 Table of Contents 1. OBJECTIVE... 4 2. SCOPE... 4 3. COMMUNICATION... 4 4. LOSS OF NATURAL GAS SUPPLY... 5 5. LOSS OF

More information

DC TRANSMISSION BASED ON VOLTAGE SOURCE CONVERTERS

DC TRANSMISSION BASED ON VOLTAGE SOURCE CONVERTERS DC TRANSMISSION BASED ON VOLTAGE SOURCE CONVERTERS by Gunnar Asplund, Kjell Eriksson, Hongbo Jiang, Johan Lindberg, Rolf Pålsson, Kjell Svensson ABB Power Systems AB Sweden SUMMARY Voltage Source Converters

More information

QUESTIONS and ANSWERS RFB 745-15-9894, Metal Clad Switchgear and Power Control Room

QUESTIONS and ANSWERS RFB 745-15-9894, Metal Clad Switchgear and Power Control Room QUESTIONS and ANSWERS RFB 745-15-9894, Metal Clad Switchgear and Power Control Room 1) When you click on the UTHSCSA Drawing the site takes you to the E-1 drawing no other. Will there be other drawings

More information

CyberFortress Data Center at Innovation Park Infrastructure and Topology Guide. Innovation Park Charlotte. NC 28262. DRAFT V0.

CyberFortress Data Center at Innovation Park Infrastructure and Topology Guide. Innovation Park Charlotte. NC 28262. DRAFT V0. Innovation Park Charlotte. NC 28262 DRAFT V0.1 Page 2 CyberFortress Data Center at Innovation Park BECO South purchased Innovation Park in March 2010 and immediately launched a dramatic top-to-bottom $30M

More information

Green Energy Solutions

Green Energy Solutions Green Energy Solutions Power Electronics for Photovoltaic Inverter Systems 1 Energy Management Product Line-up Energy Management Product Line-up Power Conversion and Stabilization Frequency Converter Static

More information

Guideline for Energy Efficient Electrical systems for building. Presentation by TERI

Guideline for Energy Efficient Electrical systems for building. Presentation by TERI Guideline for Energy Efficient Electrical systems for building Presentation by TERI Objective of study The study highlights how BBMP can implement energy efficiency measures in building in co-ordination

More information

UPS Applications and VRLA Battery Sizing

UPS Applications and VRLA Battery Sizing TECHNICAL BULLETIN 41-7334 UPS Applications and VRLA Battery Sizing 41-7334/0213/CD www.cdtechno.com The uninterruptable power system (UPS) is used to protect critical equipment and processes from the

More information

Increasing safety, reliability and efficiency for today s data centers

Increasing safety, reliability and efficiency for today s data centers Increasing safety, reliability and efficiency for today s data centers Products and expertise for data center success Drawing upon vast experience in complex industries where uptime is critical, ABB provides

More information

STEP 3 ELECTRICAL SYSTEMS ASSESSMENT OF THE WESTINGHOUSE AP1000 DIVISION 6 ASSESSMENT REPORT NO. AR 09/019-P

STEP 3 ELECTRICAL SYSTEMS ASSESSMENT OF THE WESTINGHOUSE AP1000 DIVISION 6 ASSESSMENT REPORT NO. AR 09/019-P Health and Safety Executive NUCLEAR DIRECTORATE GENERIC DESIGN ASSESSMENT NEW CIVIL REACTOR BUILD STEP 3 ELECTRICAL SYSTEMS ASSESSMENT OF THE WESTINGHOUSE AP1000 DIVISION 6 ASSESSMENT REPORT NO. AR 09/019-P

More information

Scope of Restoration Plan

Scope of Restoration Plan RWG Area Restoration Review Worksheet (10/28/09) EOP-006-02 Directory 8 EOP-005 NYSRG Rule G Text Restoration Plan Requirement R1.Each Reliability Coordinator shall have a Reliability Coordinator Area

More information

Paralleling Switchgear

Paralleling Switchgear Paralleling Switchgear By Maurice D Mello, P.Eng. Systems Engineer, GE Consumer & Industrial, Canada What is Paralleling? Paralleling is the operation in which multiple power sources, usually two or more

More information

How the National Grid System Operates. Chris Gorman Lead Account Executive Syracuse

How the National Grid System Operates. Chris Gorman Lead Account Executive Syracuse How the National Grid System Operates Chris Gorman Lead Account Executive Syracuse 2 Parts of the Electric System Parts of the Electric System 1. Generating Station: Produces Electricity. 2. Transmission

More information

The following components are common to most cubicles; this example is an ABB HK cubicle.

The following components are common to most cubicles; this example is an ABB HK cubicle. 4.0 CIRCUIT BREAKER CUBICLE Learning Objectives The circuit breaker cubicle is the component of the switchgear that holds the circuit breaker, and the controls and cabling for the distribution system.

More information

Data Center Uninterrupted efficiency, guaranteed reliability and continuous modularity. ABB solutions always work.

Data Center Uninterrupted efficiency, guaranteed reliability and continuous modularity. ABB solutions always work. Data Center Uninterrupted efficiency, guaranteed reliability and continuous modularity. ABB solutions always work. Data security is first of all electrical Maximizing security while providing efficiency

More information

Current and voltage measuring relays

Current and voltage measuring relays Current and voltage measuring relays RXIK 1, RXEEB 1 and Page 1 Issued June 1999 Changed since July 1998 Data subject to change without notice RXIK 1 RXEEB 1 (SE980082) (SE980081) (SE970869) Features Application

More information

F.C. Chan General Manager, CLP Engineering Ltd., Hong Kong SAR, China

F.C. Chan General Manager, CLP Engineering Ltd., Hong Kong SAR, China ELECTRIC POWER DISTRIBUTION SYSTEMS F.C. Chan General Manager, CLP Engineering Ltd., Hong Kong SAR, China Keywords: Distribution system planning, Load characteristics, Subtransmission Lines, Distribution

More information

for Energy Storage System, New & Renewable Energy

for Energy Storage System, New & Renewable Energy PCS Total Solution for Energy Storage System, New & Renewable Energy The product competitiveness of our customers will be more upgraded with PLASPO s power conversion technology The perfect power conversion

More information

water is cooled in a secondary cooling control tasks: use of seawater. Treatment of the seawater formation of algal vegetation.

water is cooled in a secondary cooling control tasks: use of seawater. Treatment of the seawater formation of algal vegetation. for the start-up and shut-down procedures in the case of longer standstills. The diesel exhaust is fed into two turbochargers. A portion of the exhaust gases can be utilized in a waste-heat boiler producing

More information

FIT TIER 2 Application

FIT TIER 2 Application FIT TIER 2 Application Application Information The below information Auto-Fills from your registration information: Building Permit Application Date: Project Completion Date: Name: Address: City: State:

More information

ATTACHMENT F. Electric Utility Contact Information Utility Name. For Office Use Only

ATTACHMENT F. Electric Utility Contact Information Utility Name. For Office Use Only ATTACHMENT F CATEGORY 2 GENERATOR INTERCONNECTION APPLICATION FOR ALL PROJECTS WITH AGGREGATE GENERATOR OUTPUT OF MORE THAN 20 KW BUT LESS THAN OR EQUAL TO 150 KW Also Serves as Application for Category

More information

SWITCHGEAR. EGP Switchgear

SWITCHGEAR. EGP Switchgear SWITCHEA EP Switchgear Cat generator set paralleling switchgear has been designed to integrate with Cat EMCP3 generator set controls. Now you can get greater efficiency, reliability and dependability all

More information

L.S. de Carvalho, J. M de Oliveira Neto 1. INTRODUCTION IAEA-CN-164-5P01

L.S. de Carvalho, J. M de Oliveira Neto 1. INTRODUCTION IAEA-CN-164-5P01 IAEA-CN-164-5P01 Advanced Technology Application Station Blackout Core Damage Frequency Reduction The Contribution of AN AC Independent Core Residual Heat Removal System L.S. de Carvalho, J. M de Oliveira

More information

690 V is a good alternative in the process industry

690 V is a good alternative in the process industry 690 V is a good alternative in the process industry The process industry in the Nordic countries generally uses voltage of 690 V for process motors, whereas Central Europe, Great Britain and the USA usually

More information

Electrical Engineering

Electrical Engineering Electrical Engineering Trust our people. R eady is a professional engineering firm with highlyqualified electrical and controls personnel focused on providing solutions to meet your specific needs. Ready

More information

ACRELab Renewable Energy System Test and Support Laboratory

ACRELab Renewable Energy System Test and Support Laboratory Renewable Energy System Test and Support Laboratory Abstract T Spooner 1, T L Pryor 2, N Wilmot 3, G Cole 2 and C R Lloyd 3. 1. University of New South Wales 2. Murdoch University 3. Australian CRC for

More information

High-Megawatt Converter Technology Workshop for Coal-Gas Based Fuel Cell Power Plants January 24, 2007 at NIST

High-Megawatt Converter Technology Workshop for Coal-Gas Based Fuel Cell Power Plants January 24, 2007 at NIST Session 4a Enjeti 1 High-Megawatt Converter Technology Workshop for Coal-Gas Based Fuel Cell Power Plants January 24, 2007 at NIST Dr. Prasad Enjeti TI TI Professor Power Electronics Laboratory College

More information

APPLICATION NOTE USING A MODEL 3060-MS SERIES AS A REGENERATIVE AC SOURCE FOR PV INVERTER TEST APPLICATIONS. Abstract.

APPLICATION NOTE USING A MODEL 3060-MS SERIES AS A REGENERATIVE AC SOURCE FOR PV INVERTER TEST APPLICATIONS. Abstract. USING A MODEL 3060-MS SERIES AS A REGENERATIVE AC SOURCE FOR PV INVERTER TEST APPLICATIONS Abstract This application note describes the necessary procedure to use a standard Pacific Power Source Model

More information

ELECTRICAL INSULATION TESTING OF HV EQUIPMENT UP TO 33kV

ELECTRICAL INSULATION TESTING OF HV EQUIPMENT UP TO 33kV 1. SCOPE This document details PowerSystems requirements for electrical testing of HV Equipment up to and including 33kV. 2. ISSUE RECORD This is a Reference document. The current version of Controlled

More information

30 ms High Speed Transfer System (HSTS) Product Description

30 ms High Speed Transfer System (HSTS) Product Description 30 ms High Speed Transfer System (HSTS) Product Description 2 30 ms High Speed Transfer System (HSTS) Product Description Content Page 1 General 5 1.1 Description of the 30 ms high speed transfer system

More information

ENA Customer Guide to Electricity Supply

ENA Customer Guide to Electricity Supply ENA Customer Guide to Electricity Supply Energy Networks Association Limited ENA Customer Guide to Electricity Supply August 2008 DISCLAIMER This document refers to various standards, guidelines, calculations,

More information

Power products and systems. Intelligent solutions for power distribution Zone concept

Power products and systems. Intelligent solutions for power distribution Zone concept Power products and systems Intelligent solutions for power distribution Zone concept Securing continuous power supply ABB is one of the world's leading power and automation technology companies whose products,

More information

TERMS AND CONDITIONS

TERMS AND CONDITIONS Virginia Electric and Power Company TERMS AND CONDITIONS XXIV. GENERATOR INTERCONNECTION STANDARD Electric generator interconnection service includes only the ability to interconnect an electric generator

More information

Working definitions of terms: Commercial vs. Industrial UPS Systems:

Working definitions of terms: Commercial vs. Industrial UPS Systems: The Essential Differences Between Commercial & Industrial UPS Systems Page 1 of 8 Working definitions of terms: Commercial vs. Industrial UPS Systems: On-Line, Uninterruptible Power Systems (abbreviated:

More information

Effective: September 10, 2006 Vermont Attachment 1 to Rule 5.500 Public Service Board Page 1 of 6

Effective: September 10, 2006 Vermont Attachment 1 to Rule 5.500 Public Service Board Page 1 of 6 Public Service Board Page 1 of 6 STANDARD APPLICATION FOR INTERCONNECTION OF GENERATION RESOURCES IN PARALLEL TO THE ELECTRIC SYSTEM OF: (Interconnecting Utility) Preamble and Instructions: An owner of

More information

Qualitative Analysis of Power Distribution Configurations for Data Centers

Qualitative Analysis of Power Distribution Configurations for Data Centers Qualitative Analysis of Power Distribution Configurations for Data Centers White Paper #4 2007 The Green Grid. All rights reserved. No part of this publication may be used, reproduced, photocopied, transmitted,

More information

Emirates Aluminium starts up World s first fully integrated power distribution system from ABB

Emirates Aluminium starts up World s first fully integrated power distribution system from ABB Reprint from Aluminium World 2009, Volume 2 Emirates Aluminium starts up World s first fully integrated power distribution system from ABB Emirates Aluminium (EMAL), a joint venture between Abu Dhabi s

More information

LTR Series Uninterruptible Power Systems 700 VA - 2.1 KVA. General Specification

LTR Series Uninterruptible Power Systems 700 VA - 2.1 KVA. General Specification 08/17/12 Rev2 LTR Series General Specification 700 VA to 2.1 KVA 1.0 General LTR Series Uninterruptible Power Systems 700 VA - 2.1 KVA General Specification This specification describes the features and

More information

21 st Century Facilities

21 st Century Facilities Electrical Testing 21 st Century Facilities Facility Owners face tough challenges 24 X 7 reliability needed Non linear loads cause harmonics VFD Computers Switching transients disrupt operations Less customer

More information

..OR How To Protect your 3-Phase Equipment Investment with 3-Phase Monitors from Time Mark...

..OR How To Protect your 3-Phase Equipment Investment with 3-Phase Monitors from Time Mark... ..OR How To Protect your 3-Phase Equipment Investment with 3-Phase Monitors from Time Mark... TIME MARK CORPORATION 11440 EAST PINE STREET TULSA, OK 74116 USA tel 918 438-1220 fax 918 437-7584 www.time-mark.com

More information

ECE 586b Course Project Report. Auto-Reclosing

ECE 586b Course Project Report. Auto-Reclosing ECE 586b Course Project Report Auto-Reclosing Srichand Injeti May 5, 2008 Department Of Electrical and computer Engineering University Of Western Ontario, London Ontario Table of contents 1. Introduction...1

More information

Application of Four-Pole Circuit Breakers within Data Centers

Application of Four-Pole Circuit Breakers within Data Centers Application of Four-Pole Circuit Breakers within Data Centers December 2013/AT324 by Frank Waterer, Fellow Engineer, Schneider Electric Engineering Services Make the most of your energy SM Revision #1

More information

IV. Occurrence and Progress of Accidents in Fukushima Nuclear Power Stations and Other Facilities

IV. Occurrence and Progress of Accidents in Fukushima Nuclear Power Stations and Other Facilities IV. Occurrence and Progress of Accidents in Fukushima Nuclear Power Stations and Other Facilities 1. Outline of Fukushima Nuclear Power Stations (1) Fukushima Daiichi Nuclear Power Station Fukushima Daiichi

More information

Trip circuit supervision relay. Type RXTCS

Trip circuit supervision relay. Type RXTCS Trip circuit supervision relay Type RXTCS ABB a global technology leader ABB is a global leader in Power and Automation technologies that enable utility and industry customers to improve performance while

More information

AC COUPLED HYBRID SYSTEMS AND MINI GRIDS

AC COUPLED HYBRID SYSTEMS AND MINI GRIDS , Michael; Hermes, Matthias SMA Technologie AG Hannoversche Str. 1-5 34266 Niestetal GERMANY E-mail: Michael.@SMA.de E-mail: Matthias.Hermes@SMA.de 1. INTRODUCTION Distributed supply based on renewable

More information

MICROGRIDS FOR DATA CENTERS

MICROGRIDS FOR DATA CENTERS MICROGRIDS FOR DATA CENTERS Table of Contents Summary of Pareto Energy s Microgrid Business Model Understanding the Risks of On-Site Power for Critical Infrastructure The Pareto Energy GridLink Solution

More information

Medium voltage products UniSec for Smart Grid Air-insulated medium-voltage secondary distribution switchgear

Medium voltage products UniSec for Smart Grid Air-insulated medium-voltage secondary distribution switchgear Medium voltage products UniSec for Smart Grid Air-insulated medium-voltage secondary distribution switchgear Index 3 Overview 4 Standard Levels 6 Monitoring & Control 7 Measurements 8 Protection & Logic

More information

Reconstruction Support after the Great East Japan Earthquake

Reconstruction Support after the Great East Japan Earthquake Advanced Maintenance, Energy Saving, Environment Reconstruction Support after the Great East Japan Earthquake Kan Kumagai Keyword Earthquake disaster reconstruction, Temporary restoration, Reuse, Diagnosis

More information

Thyristor-controlled power supplies and battery chargers

Thyristor-controlled power supplies and battery chargers Thyristor-controlled power supplies and battery chargers Input voltage: 115 / 230 VAC, single phase, 50 / 60 Hz or 208 / 400 / 480 VAC, three phases, 50 / 60 Hz Output voltage: 12 / 24 / 48 / 60 / 72 /

More information

Data Center Commissioning: What you need to know

Data Center Commissioning: What you need to know Data Center Commissioning: What you need to know Course # CXENERGY1511 AIA Provider # 50111116 AABC Commissioning Group CxEnergy Conference Henderson, NV April 30, 2015 Presented by: Judson H. Adams, P.E.,

More information

Fundamentals of Modern Electrical Substations Part 1: Mission of Electrical Substations and their Main Components

Fundamentals of Modern Electrical Substations Part 1: Mission of Electrical Substations and their Main Components Fundamentals of Modern Electrical Substations Part 1: Mission of Electrical Substations and their Main Components Course No: E02-010 Credit: 2 PDH Boris Shvartsberg, Ph.D., P.E., P.M.P. Continuing Education

More information

Designed for uptime. Defining data center availability via a tier classification system

Designed for uptime. Defining data center availability via a tier classification system Defining data center availability via a tier classification system MIETEK GLIKOWSKI All systems can fail this is a simple fact that every industry must deal with. The paramount concern for the data center

More information

Requirements for Offshore Grid Connections. in the. Grid of TenneT TSO GmbH

Requirements for Offshore Grid Connections. in the. Grid of TenneT TSO GmbH Requirements for Offshore Grid Connections in the Grid of TenneT TSO GmbH Bernecker Straße 70, 95448 Bayreuth Updated: 21 December 2012 1/10 Requirements for Offshore Grid Connections in the Grid of TenneT

More information

ORC TURBOGENERATOR TYPE CHP - Organic Rankine Cycle Turbogenerator fed by thermal oil, for the combined production of electric energy and heat -

ORC TURBOGENERATOR TYPE CHP - Organic Rankine Cycle Turbogenerator fed by thermal oil, for the combined production of electric energy and heat - Doc. : 08C00031_e Date : 10.02.2009 Page : 1 / 9 ORC TURBOGENERATOR TYPE CHP - Organic Rankine Cycle Turbogenerator fed by thermal oil, for the combined production of electric - (Preliminary) Doc. : 08C00031_e

More information

Data center power dynamics within the settings of regional power grid

Data center power dynamics within the settings of regional power grid Data center power dynamics within the settings of regional power grid Gulnara Zhabelova 1, Alireza Yavarian 1, Valeriy Vyatkin 1,2 1 Department of Computer Science, Electrical and Space Engineering Lulea

More information

Modular architecture for high power UPS systems. A White Paper from the experts in Business-Critical Continuity

Modular architecture for high power UPS systems. A White Paper from the experts in Business-Critical Continuity Modular architecture for high power UPS systems A White Paper from the experts in Business-Critical Continuity Abstract Today, more than ever before, energy efficiency and cost-savings are among the top

More information

OWestinghouse. U.S. Nuclear Regulatory Commission ATTENTION: Document Control Desk Washington, D.C. 20555. February 1, 2010

OWestinghouse. U.S. Nuclear Regulatory Commission ATTENTION: Document Control Desk Washington, D.C. 20555. February 1, 2010 OWestinghouse Westinghouse Electric Company Nuclear Power Plants P.O. Box 355 Pittsburgh, Pennsylvania 1 5230-0355 USA U.S. Nuclear Regulatory Commission ATTENTION: Document Control Desk Washington, D.C.

More information

Energy-efficient data center achieves 2N reliability; MTU Onsite Energy generator sets provide critical backup

Energy-efficient data center achieves 2N reliability; MTU Onsite Energy generator sets provide critical backup Press Release Contact: Gary Mason Tognum America Inc. Phone: +1 248 560 8480 E-mail: gary.mason@tognum.com Agency contact: Robert E. Sheldon, APR Creative Communications Consultants, Inc. Phone: +1 210

More information

8. ELECTRIC POWER SUPPLY SYSTEM

8. ELECTRIC POWER SUPPLY SYSTEM 8. ELECTRIC POWER SUPPLY SYSTEM This Section provides an overview of the systems and components which serve to deliver the power generated by the plant and which assure that internal plant needs for electric

More information

Photovoltaic Solar Energy Unit EESFB

Photovoltaic Solar Energy Unit EESFB Technical Teaching Equipment Photovoltaic Solar Energy Unit EESFB Products Products range Units 5.-Energy Electronic console PROCESS DIAGRAM AND UNIT ELEMENTS ALLOCATION Worlddidac Member ISO 9000: Quality

More information

General Validation Test Program for Wind Power Plants Connected to the Hydro-Québec Transmission System

General Validation Test Program for Wind Power Plants Connected to the Hydro-Québec Transmission System General Validation Test Program for Wind Power Plants Connected to the Hydro-Québec Transmission System Direction Planification des actifs et expertise de transport February 2011 TABLE OF CONTENTS 1. CONDUCTING

More information

LIMITING SHORT-CIRCUIT CURRENTS IN MEDIUM-VOLTAGE APPLICATIONS

LIMITING SHORT-CIRCUIT CURRENTS IN MEDIUM-VOLTAGE APPLICATIONS LIMITING SHORT-CIRCUIT CURRENTS IN MEDIUM-VOLTAGE APPLICATIONS Terence Hazel Senior Member IEEE Schneider Electric 38050 Grenoble France Abstract The power requirements for large industrial sites is increasing.

More information

The design and performance of Static Var Compensators for particle accelerators

The design and performance of Static Var Compensators for particle accelerators CERN-ACC-2015-0104 Karsten.Kahle@cern.ch The design and performance of Static Var Compensators for particle accelerators Karsten Kahle, Francisco R. Blánquez, Charles-Mathieu Genton CERN, Geneva, Switzerland,

More information