21 st Century Facilities
|
|
- Bryan Lamb
- 8 years ago
- Views:
Transcription
1 Electrical Testing
2 21 st Century Facilities Facility Owners face tough challenges 24 X 7 reliability needed Non linear loads cause harmonics VFD Computers Switching transients disrupt operations Less customer support from Utilities Pressure to hold energy costs down Compressed schedules for expanding facilities Effect of EMF on computers and equipment How to expand facilities to meet customer needs cost effectively Harsh environments
3 Formula For Successful Facilities Facility Planning and Scheduling Engineering Design Quality Installation Acceptance Testing Regular and Complete Maintenance Preventative Maintenance Testing
4 Testing for All Phases of Facility Improvements Load analysis for facility improvements Trouble shooting and correction of problems Acceptance Testing for New Projects Switchboards and/or Switchgear Circuit Breakers Preventative Maintenance Forensic Testing
5 Testing Load Analysis Measuring existing loads with portable test equipment 120V to 480V, Amps Recorded values Volts - Power Factor Amps - KVA KW - KVAR Measure harmonic distortion THD - Voltage & Current Individual harmonics Measure loads for emergency generator sizing Motor starting studies
6 CURRENT Trend Monitoring Trend Plot For Device: 3 Phase Current IAvg IA :50 AM 11:00 AM 11:10 AM 11:20 AM 11:30 AM 11:40 AM 11:50 AM 11/5/01 10:50:00 AM to 11/5/01 11:50:00 AM IB IC
7 Testing Acceptance Testing Equipment Acceptance Testing Medium Voltage Transformers Switchgear Cables PFC Air Switches SF6 Circuit Breakers Below 600V Switchboards and Switchgear Motor Control Centers Generator Load Testing
8 Acceptance Testing Cont d. Short Circuit and Coordination Studies Short Circuit Study verifies overcurrent protective devices meet requirement for interrupting available fault current. Coordination Study graphically shows how overcurrent protective devices coordinate to have the CB closest to the fault open. Ground Resistance Testing 3 Point Fall of Potential Method Ground Fault Interruption Testing Required by NEC
9 Transformer Testing Oil Filled Transformers On Line, no shutdown Excellent analytical technique developed by IEEE to evaluate condition of transformer IEEE/ANSI C57 Distribution, Power and Regulating Transformers. C is the Standard for Interpretation. NFPA 70B Section Oil Tests Section Dissolved Gas Analysis
10 Transformer Testing Cont. d Mineral Oil is complex hydrocarbon molecular compound At normal conditions it is very stable Heat, corona and arcing break molecule down to sub elements (combustible gases) (H 2, CH 4, etc.) Analysis of dissolved combustible gases gives the condition of the transformer. Trending of gases is very helpful in the analysis. DGA is one of the best ways to monitor the condition of the transformer and help the Owner plan repairs or replacements.
11 Infrared Thermography Scan Heat is the enemy for electrical equipment Heat breaks down electrical insulation 10 C Rule = ½ life Infrared thermography scanning Looks at thermal image of switchgear, busbars, connections, cables, etc. Hot spots and irregularities are discovered by trained technicians Problem areas can be corrected before they cause shutdowns or cause fires. Scanning Saves Equipment Technician scanning is much faster that tightening all bolts. Cannot see some circuit breaker problems without IR. Early detection and correction = preventative maintenance.
12 Infrared Thermography Scan F SP02 SP F 100 Spot 1 Temperature Spot 2 Temperature Spot 1 Rise over Spot 2 Ambient Temperature F 93.9 F F 68.0 F
13 Circuit Breaker Testing Contact Resistance Results vary with size and construction of circuit breaker less than 100 microhms for medium voltage Contact resistance exposes problems not detectable with IR when there is little load current. Insulation Resistance Phase to ground Phase to phase Functionality Tests Close, Open Trip Kirk key interlocks, etc.
14 Circuit Breaker Testing Cont d. Overcurrent Trip Point Calibration and Testing Secondary Injection Testing Electronic CB test sets for accurate testing Square D Cutler Hammer GE Siemens New Circuit Breakers with on-board secondary injection testing Cutler Hammer 1150 Trip Unit
15 Medium Voltage (> 600 Volts) Cable Testing New Cables Insulation resistance testing using hi pot at manufacturer s recommended values NETA use Table 10.6 of Acceptance Testing Specs. Leakage current should be <10 micro Amps for new cables. Existing Cables Watch out! Be careful what voltage you use on old cables. Conservative approach RMS X Square Root of 2 = Peak voltage Use peak value as DC value
16 Relay Testing Relays are typically used on medium voltage systems Older electro mechanical style relays (typical single phase) Newer models microprocessor based, 1 Phase + 3 Phase Incorporate metering and relay tripping. Programmable on site Fault analysis logging for retrieval Short Circuit and Coordination Studies At least 50% of facilities are not coordinated Poor maintenance Poor installation
17 Power Quality - Today s Perspective The quality of power 30 years ago was not much of an issue Linear Devices Today many devices disrupt and corrupt the quality of the power Utility Side Voltage Sags Impulses Transient Disturbances Loss of One Phase Over voltage
18 Power Quality Today s Perspective Customer Side Switch mode power supplies (non-linear device) Harmonic Distortion Overloaded neutrals Transformer heating SCR (non-linear device) Loose wiring Large motor starting
19 PQ Testing Power Quality Analyzer 3 phase microprocessor based analyzer that samples the voltage waveform 128 times per second. We set thresholds for voltages. By exceeding the thresholds, the machine is activated to record the events as they occur. Harmonic testing and analysis Measure voltage and current THD Analyze individual harmonic values Engineering investigation of problem and surrounding power distribution system by power quality engineer.
20 Main Switchboard Voltage Sag Model V RMS Sag Disturbance Three Phase Wye 340.0A Vc Ic 175.0V 170.0A 0.0V 0.00ns M SWBD 0.0A 5.83 ms/div ms 11/22/01 07:57:32.98 AM Channel Y1 Y2 Delta Voltage Channel Y1 Y2 Delta Current Time X1 X2 Delta
21 Main SWBD Voltage Sag on Phase C-N Model V Impulse Disturbance Three Phase Wye 640.0A Vc 0.0V 0.0A V 0.00ns M SWBD A 2.50 ms/div 50.00ms 11/22/01 07:57:32.98 AM
22 Main SWBD Utility Capacitor Switching Transient Phase B-N Model V Impulse Disturbance Three Phase Wye 2.1KA Vb 0.0V 0.0A V 0.00ns M SWBD -2.1KA 2.50 ms/div 50.00ms 12/03/01 09:48:07.93 AM
23 Time X1 X2 Delta Utility Capacitor Switching Transient Phase B-N Model V Impulse Disturbance Three Phase Wye 2.3KA Vb 0.0V 0.0A V 0.00ns M SWBD -2.3KA 2.50 ms/div 50.00ms 12/03/01 11:43:11.90 AM Channel Y1 Y2 Delta Voltage Channel Y1 Y2 Delta
24 Panel NEH1 Power Source Switching Transient Phase A-N Model V Impulse Disturbance Three Phase Wye 575.0A Va 0.0V 0.0A V 0.00ns Pnl NEH A 2.50 ms/div 50.00ms 01/03/02 02:00:54.74 PM
25 Panel NEH1 Power Source Switching Phase B-N Model V Impulse Disturbance Three Phase Wye 570.0A Vb 0.0V 0.0A V 0.00ns Pnl NEH A 2.50 ms/div 50.00ms 01/03/02 02:48:29.37 PM
26 Harmonic Distortion Voltage Waveform Model V Snapshot Waveform Three Phase Wye 50.0A Va 0.0V 0.0A V -50.0A 0.00ns ms PDU PnlD us/div 01/17/02 01:06:45.97 PM 1.0% 0.5% 0.0% 60Hz 2940Hz Distortion: thd=1.41% Odd=1.36%
27 Harmonic Distortion - Current Model V Snapshot Waveform Three Phase Wye 50.0A Ia 0.0V 0.0A V -50.0A 0.00ns ms PDU PnlD us/div 01/17/02 01:06:45.97 PM 32.0% 16.0% 0.0% 60Hz 2940Hz Distortion: thd=42.34% Odd=42.19%
28 How Do You Spot PQ Problems? Variable speed drives trip off line more than usual. Computer data errors that cannot be explained by hardware or software Lights flicker (not in a storm). Equipment power supplies have burned or damaged boards. Transformers overheating. Circuit breaker nuisance tripping. Motors overheating or failing easily. Voltages vary significantly from loose wiring. Computer screens wave or are disrupted.
29 Power Quality and Facility Maintenance Are Related Loose connections are one of the leading power quality problems Lack of coordination of overcurrent protection devices can cause blackouts that could have been avoided. Coordination Study Short Circuit Study Preventative Maintenance Infrared thermography scan looks for hot spots Transformer Testing Oil Quality Dissolved Gas Analysis Cable Testing Test Circuit Breakers Switchgear Maintenance
30 Conclusion Facilities today face tough problems: Harsh environments Power Quality Problems Need for 24/7 Reliability Compressed schedules A successful 21 st Century Facility needs four solid legs to stand on: Engineering Design Quality Installation Maintenance Testing
31 Conclusion Cont d. Excellent resources and standards from IEEE, NETA and NFPA for Testing and Maintenance A proper test is worth a thousand opinions. The right test equipment and experience will aid the Design Engineer in ensuring success for the Customer. Call IETC at for a quote today!
Line to Ground Voltage Monitoring on Ungrounded and Impedance Grounded Power Systems
Line to Ground Voltage Monitoring on Ungrounded and Impedance Grounded Power Systems by Reza Tajali, P.E. Square D Company, Power Systems Engineering Group 295 Tech Park Drive LaVergne, Tennessee 37086
More informationMV, HV AND EHV SWITCHGEAR TESTING & COMMISSIONING
Training Title MV, HV AND EHV SWITCHGEAR TESTING & COMMISSIONING Training Duration 5 days Training Date MV, HV and EHV Switchgear Testing & Commissioning 5 20 24 Apr $3,750 Dubai, UAE In any of the 5 star
More informationENGINEERING REPORT. XYZ Corporation 100 Anyplace Drive Chicago, Illinois 60613
ENGINEERING REPORT XYZ Corporation 100 Anyplace Drive Chicago, Illinois 60613 PERFORMED BY: MIDWEST ELECTRICAL CONSULTANTS, INC 18055 UPLAND DRIVE TINLEY PARK, ILLINOIS 60487 (708) 444-0001 fax: 444-0003
More informationUnderstanding Arc Flash
Understanding Arc Flash Presented by Eddie F. Jones, PE 1 2 3 4 5 Five to 10 arc flash explosions occur in electric equipment every day in the United States. This number does not include cases in which
More informationPMCS. Integrated Energy Management Solution. Unlock the Full Potential of Power Networks Through Integration. Complete Solution. Informed Decisions
PMCS Integrated Energy Management Solution Unlock the Full Potential of Power Networks Through Integration Power Management Control System (PMCS) is a highly customizable, fully integrated end-to-end Energy
More informationPart 1 System Modeling & Studies for Existing Systems
Part 1 System Modeling & Studies for Existing Systems Operation Technology, Inc. Copyright 2009 Result of rapid release of energy due to an arcing fault between two conductors. Bus voltages > 208V Temperatures
More informationEnhance Power Equipment Reliability with Predictive Maintenance Technologies
Enhance Power Equipment Reliability with Predictive Maintenance Technologies November 2012/1910DB1208 by S. Frank Waterer, Electrical Engineerinig, Fellow Schneider Electric USA, Inc. Make the most of
More informationArc Flash Energy Mitigation Techniques
Arc Flash Energy Mitigation Techniques When short circuits occur on an electrical distribution system, an arc flash event usually forms. These arc flash events can cause dangerous and potentially fatal
More informationEmergency Power System Services Industrial UPS, Batteries, Chargers, Inverters and Static Switches
Emergency Power System Services Industrial UPS, Batteries, Chargers, Inverters and Static Switches Downtime Is Not An Option The industrial uninterruptible power supply (UPS) is the foundation of your
More informationFundamentals of Power
Fundamentals of Power Fundamentals of Power 2008 American Power Conversion Corporation. All rights reserved. All trademarks provided are the property of their respective owners. Learning Objectives At
More informationIntroduction. Harmonics and IEEE 519 Page 1 of 19
Introduction In an ideal power system, the voltage supplied to customer equipment, and the resulting load current are perfect sine waves. In practice, however, conditions are never ideal, so these waveforms
More informationThe Importance of the X/R Ratio in Low-Voltage Short Circuit Studies
The Importance of the X/R Ratio in Low-Voltage Short Circuit Studies DATE: November 17, 1999 REVISION: AUTHOR: John Merrell Introduction In some short circuit studies, the X/R ratio is ignored when comparing
More informationPower System Harmonics
Pacific Gas and Electric Company Power System Harmonics What are power system harmonics? Ideally, voltage and current waveforms are perfect sinusoids. However, because of the increased popularity of electronic
More informationUFES Active protection for switchgear
Active protection for switchgear ABB AG Oberhausener Strasse 4047 Ratingen, Germany Phone: +49 0-0 Fax: +49 0-7 77 Note: We reserve the right to make technical changes or modify the contents of this document
More informationUNIVERSITY OF WASHINGTON Facilities Services Design Guide. Electrical. Switchboards. Basis of Design. Design Evaluation
Basis of Design This section applies to the design relating to low voltage switchboards. Design Criteria UW Class N1 facilities main switchboards shall be rear accessible. The main, tie and feeder breakers
More informationElectrical Network Management System
Electrical Network Management System Optimisation of the electrical network Measure to understand Understand to control Control to optimise Cost of power and fluids Power quality Power availability 2 Improvement
More informationArc Flash Hazards. Electrical Hazards. Dan Neeser Field Application Engineer DanRNeeser@Eaton.com. Electrical Hazards 2/18/2015. Shock.
Arc Flash Hazards Dan Neeser Field Application Engineer DanRNeeser@Eaton.com Electrical Hazards Electrical Hazards Shock Arc Flash Arc Blast 2 1 Arcing Fault Basics 35,000 F Radiant Heat & UV Speed of
More informationPower Quality Standards for Electric Service
Power Quality Standards for Electric Service Effective June 1, 2008 A transition period will exist from June 1 through December 31, 2008 in which installations may be approved and connected as long as
More informationSelecting Current Transformers Part 1 By Darrell G. Broussard, P.E.
By Darrell G. Broussard, P.E. Introduction: As engineers, we are aware that electrical power systems have grown. How much have they grown? When was the last time you specified a 2400-volt system, a 4160-volt
More informationNeutral Currents in Three Phase Wye Systems
POWER SYSTEMS ENGINEERING DATA PUBLISHED BY SQUARE D, OSHKOSH, WISCONSIN Subject: Neutral Currents in Three Phase Wye Systems by Robert Arthur Square D Company Oshkosh, Wisconsin (414) 46-80 and R. A.
More informationThe Facts About Harmonics and Power Factor. Power Quality: Harmonics & Power Factor Correction
The Facts About Harmonics and Power Factor Power Quality: Harmonics & Power Factor Correction 1 Agenda I. Harmonic Basics II. Harmonic Mitigation Methods III. Active Harmonic Filters IV. Applications V.
More informationFusible Disconnect Switch
Circuit Breakers Circuit breakers are used in panelboards and switchboards to provide circuit protection and provide a means of energizing and de-energizing a circuit. Siemens Sentron molded case circuit
More informationMotor Protection Voltage Unbalance and Single-Phasing
Motor Protection Voltage Unbalance and Single-Phasing Cooper Bussmann contributes the following information, which is an excerpt from their 190-page handbook SPD Selecting Protective Devices Based on the
More informationCONSULTANT REPORT. Behavior of Two Capstone 30kW Microturbines Operating in Parallel with Impedance Between Them CALIFORNIA ENERGY COMMISSION
CALIFORNIA ENERGY COMMISSION Behavior of Two Capstone 3kW Microturbines Operating in Parallel with Impedance Between Them CONSULTANT REPORT MARCH 2 CEC-2-2 Arnold Schwarzenegger, Governor CALIFORNIA ENERGY
More informationOPTIMIZING POWER SYSTEM PROTECTION FOR MODERN DATA CENTERS
OPTIMIZING POWER SYSTEM PROTECTION FOR MODERN DATA CENTERS Data center power systems are constructed with a premium on reliability at a significant cost. The return on this investment is realized if it
More informationPredictive Maintenance
PART ONE of a predictive maintenance series Predictive Maintenance Overview Predictive maintenance programs come in all shapes and sizes, depending on a facility s size, equipment, regulations, and productivity
More informationCircuit Breakers and Switchgear. Thomas Greer Director of Engineering TLG Services
Circuit Breakers and Switchgear Thomas Greer Director of Engineering TLG Services Presentation Outline Switchgear Definition Overcurrent Protection Devices Circuit Breaker Trip Curves and Coordination
More informationPrimary and Secondary Electrical Distribution Systems
Primary and Secondary Electrical Distribution Systems Critical Facilities Round Table 12th Quarterly Membership Meeting June 2, 2006 David D. Roybal. P.E. Eaton Electrical Cutler-Hammer Products Utility
More informationProduct Data Bulletin
Product Data Bulletin Power System Harmonics Causes and Effects of Variable Frequency Drives Relative to the IEEE 519-1992 Standard Raleigh, NC, U.S.A. INTRODUCTION This document describes power system
More informationLTR Series Uninterruptible Power Systems 700 VA - 2.1 KVA. General Specification
08/17/12 Rev2 LTR Series General Specification 700 VA to 2.1 KVA 1.0 General LTR Series Uninterruptible Power Systems 700 VA - 2.1 KVA General Specification This specification describes the features and
More informationGUIDE TO LV SWITCHGEAR & FORMS OF SEPARATION
GUIDE TO LV SWITCHGEAR & FORMS OF SEPARATION CONTENTS INDEX...PAGE # PRODUCT EXAMPLES Mobile Battery Charging Unit... 3 PRODUCT EXAMPLES Form 4 Type 5 PDU - C/W Isolating Transformer... 3 PRODUCT EXAMPLES
More informationDATA CENTER UNIQUE CHARACTERISTICS AND THE ROLE OF MEDIUM VOLTAGE VACUUM CIRCUIT BREAKERS
DATA CENTER UNIQUE CHARACTERISTICS AND THE ROLE OF MEDIUM VOLTAGE VACUUM CIRCUIT BREAKERS ABSTRACT Data Centers are a critical part of the world economic systems. Billions of electronic transactions happen
More informationARC FLASH CALCULATIONS & LABELING REQUIREMENTS
ARC FLASH CALCULATIONS & LABELING REQUIREMENTS Presented by: Edmund Elizalde EYP Mission Critical Facilities, Inc. Slides by: Lonnie Lindell SKM Systems Analysis, Inc. 1 Agenda NEC 110.16 NFPA 70E IEEE
More information7-41 POWER FACTOR CORRECTION
POWER FTOR CORRECTION INTRODUCTION Modern electronic equipment can create noise that will cause problems with other equipment on the same supply system. To reduce system disturbances it is therefore essential
More informationTransfer Equipment Controls
Control Types Manual Transfer Switches Nonautomatic Transfer Switches Automatic Transfer Switches The type of control system for the transfer switch will vary depending on the type of switching equipment
More informationSurvey of Harmonics Measurements in Electrical Distribution System of a Technical Institution
Survey of Harmonics Measurements in Electrical Distribution System of a Technical Institution Nandita Dey, Dr.A.K.Chakraborty Lecturer, Electrical Engineering Department, Tripura University Suryamaninagar
More informationRISH EM 3490 DS Dual Source Energy Meter RISH EM 3490 DS. Application : Product Features:
Application : RISH Master 3490 DS measures important electrical parameters of Utility (in normal mode) & Generators (in Power back up) in three phase and single phase Network & replaces the multiple analog
More informationSentron Series Circuit Breakers
Sentron Series Circuit Breakers Siemens Sentron Series circuit breakers are available in nine frame sizes: ED, FD, JD, LD, LMD, MD, ND, PD, and RD. Sentron Series circuit breakers have a wide range of
More informationElectrical Shore Connections / Cold Ironing
STANDARD FOR CERTIFICATION No. 2.25 Electrical Shore Connections / Cold Ironing JULY 2014 The electronic pdf version of this document found through http://www.dnv.com is the officially binding version
More informationHarmonics and Noise in Photovoltaic (PV) Inverter and the Mitigation Strategies
Soonwook Hong, Ph. D. Michael Zuercher Martinson Harmonics and Noise in Photovoltaic (PV) Inverter and the Mitigation Strategies 1. Introduction PV inverters use semiconductor devices to transform the
More informationSurvey of Harmonics Measurements in Electrical Distribution Systems
Survey of Harmonics Measurements in Electrical Distribution Systems Leon M. Tolbert, Member, IEEE Oak Ridge National Laboratory* P.O. Box 28, Bldg Oak Ridge, TN 3783-6334 Alexandria, VA 2235-3862 Phone:
More informationMETAL-CLAD AND METAL-ENCLOSED SWITCHGEAR 3.6KV~40.5KV. tgood.com. Energy. Fast.
METAL-CLAD AND METAL-ENCLOSED SWITCHGEAR 3.6KV~40.5KV tgood.com Energy. Fast. TGOOD produces over 5000 switchgear units annually for projects around the globe PRODUCT OVERVIEW Integral substation component
More informationElectrical Resistance Resistance (R)
Electrical Resistance Resistance (R) Any device in a circuit which converts electrical energy into some other form impedes the current. The device which converts electrical energy to heat energy is termed
More informationCity of Leesburg, Florida I.T. Data Center 130551 APPENDIX A TOSHIBA UPS INFORMATION
City of Leesburg, Florida I.T. Data Center 130551 APPENDIX A TOSHIBA UPS INFORMATION This Appendix A includes technical documents and specifications for the Toshiba 4200 FA 30 kva Uninterruptable Power
More informationWHAT IS INFRARED (IR) THERMOGRAPHY
WHAT IS INFRARED (IR) THERMOGRAPHY IR Thermography is the technique of producing pictures called from the invisible thermal radiation that objects emit. This is a non-contact means of identifying electrical
More informationUltrasound Condition Monitoring
Ultrasound Condition Monitoring Whitepaper Alan Bandes UE Systems, Inc. Abstract: Instruments based on airborne/structure borne ultrasound technology offer many opportunities for reducing energy waste
More informationLitigation Services & Information
Litigation Services & Information Laurence "Lo" Lehman, P.E. Lehman Engineering Company Lehman Engineering has been providing engineering, design, and consulting services for electrical power systems to
More informationChoosing the Best Solution for Reducing Arc Energy
CONVENTION SESSION HANDOUT Choosing the Best Solution for Reducing Arc Energy Terry L. Schiazza, Business Development Manager Square D / Schneider Electric SESSION #11 Independent Electrical Contractors
More informationPower Quality Issues, Impacts, and Mitigation for Industrial Customers
Power Quality Issues, Impacts, and Mitigation for Industrial Customers By Kevin Olikara, Power and Energy Management Products Rockwell Automation, Inc. Now, more than ever, electronic equipment and computing
More informationUnderstanding Power Factor, Crest Factor, and Surge Factor. White Paper #17
Understanding Power Factor, Crest Factor, and Surge Factor White Paper #17 Executive Summary This paper explains the technical terms of Power Factor, Crest Factor, and Surge Factor. The use of these terms
More informationLow Voltage Switchgear
Arc Resistant Switchgear n Insulated and isolated bus n Separation barriers and top venting n Breaker shutters 12 SWITCHGEAR Arc resistant metal-enclosed low voltage switchgear is an optional product offering
More informationEvaluating Water-Damaged Electrical Equipment
Evaluating Water-Damaged Electrical Equipment 1 USE OF THIS PUBLICATION This publication provides information on how to evaluate electrical equipment that has been exposed to water through flooding, fire
More information3) What is the difference between "Insulating", "Isolating", and "Shielded Winding" transformers?
Tyco Electronics Corporation Crompton Instruments 1610 Cobb International Parkway, Unit #4 Kennesaw, GA 30152 Tel. 770-425-8903 Fax. 770-423-7194 1) What is a transformer and how does it work? A transformer
More informationNew standardized approach to arc flash protection
New standardized approach to arc flash protection Samuel Dahl Juha Arvola Tero Virtala Arcteq Relays Ltd Arcteq Relays Ltd Arcteq Relays Ltd Wolffintie 36 F 11 Wolffintie 36 F 11 Wolffintie 36 F11 65200
More informationArc flash can kill. Arc flash can be considered as a short circuit through
The Official Publication of the InterNational Electrical Testing Association Spring 2007 Methods of Inspection to Determine the Presence of Potential Arc-Flash Incidents Feature Arc flash can kill. Arc
More informationSpecifying a Variable Frequency Drive s
Specifying a Variable Frequency Drive s Put on by Bruce Reeves and Jeremy Gonzales Dykman Electrical Covering the Western US For all of your VFD and Soft Start and Motor Needs How To Specify a Variable
More information4160: THE GREEN 480 MEDIUM VOLTAGE ELECTRICAL SYSTEMS
4160: THE GREEN 480 MEDIUM VOLTAGE ELECTRICAL SYSTEMS for DATA CENTERS Michael Mosman, PE Chief Technical Officer CCG Facilities Integration Incorporated FACILITIES INTEGRATION INCORPORATED MEDIUM VOLTAGE
More informationElectronic Trip Circuit Breaker Basics Circuit Breaker Application Guide Class 0600
Electronic Trip Circuit Breaker Basics Circuit Breaker Application Guide Class 0600 Data Bulletin 0600DB1104 03/2012 Retain for future use. Electronic Trip Circuit Breaker Basics 0600DB1104 Table of Contents
More informationArc Terminator Active Arc-Resistant Switchgear
Arc Terminator Active Arc-Resistant Switchgear Increasing safety and productivity by extinguishing internal arcing faults within the switchgear. The Square D Arc Terminator from Schneider Electric offers
More informationTWENTIES WORKSHOP, EWEA 2012 Unveiling the future energy system: full scale demonstrations to reach 2020 targets. 17th April 2012
TWENTIES WORKSHOP, EWEA 2012 Unveiling the future energy system: full scale demonstrations to reach 2020 targets 17th April 2012 Session 2 Technological challenges to cope with in TWENTIES field tests
More informationHarmonics in your electrical system
Harmonics in your electrical system What they are, how they can be harmful, and what to do about them Abstract Harmonic currents, generated by non-linear electronic loads, increase power system heat losses
More information7. Reactive energy compensation
593 7. Reactive energy compensation 594 7. REACTIVE ENERGY COMPENSATION Reactive energy compensation is an important element for reducing the electricity bill and improving the quality of the electrical
More informationWhy Buy HVI VLF Products?
Very Low Frequency AC Hipots AC testing of cables and electrical apparatus is now easier than ever. Since the introduction of the High Voltage, Inc. line of portable and affordable VLF hipots, there is
More informationHARMONIC DISTORTION IN THE ELECTRIC SUPPLY SYSTEM
Technical Note No.3 March 2000 HARMONIC DISTORTION IN THE ELECTRIC SUPPLY SYSTEM This Technical Note discusses harmonic distortion, its causes and adverse effects, what levels are unacceptable and how
More informationSquare D Company P. O. Box 729 Houston, Texas 77001 Business Phone: 713-222-9195
JOHN A. GRISWOLD Square D Company P. O. Box 729 Houston, Texas 77001 Business Phone: 713-222-9195 Education Deer Park High School - Deer Park, Texas 1989 Graduate Professional Certifications AVO Training
More informationSimple Methods for Calculating Short Circuit Current Without a Computer By Dennis McKeown, PE GE Senior System Application Engineer
Simple Methods for Calculating Short Circuit Current Without a Computer By Dennis McKeown, PE GE Senior System Application Engineer A Short Circuit analysis is used to determine the magnitude of short
More informationABB Fuses Competitive Advantages
GPMM Tomasz Komalski 2009 ABB Fuses Competitive Advantages May 14, 2009 Slide 1 Basic comments ABB is a global manufacturer of both current limiting and expulsion (non-current limiting) fuses for medium
More informationSafe and secure distribution of medium voltage with AX1
Safe and secure distribution of medium voltage with AX1 The intelligent switchgear AX1 is a modern, air-insulated switchgear that lies at the very front line of safety and security safety for operating
More informationArc Flash Mitigation. Remote Racking and Switching for Arc Flash danger mitigation in distribution class switchgear.
Arc Flash Mitigation Remote Racking and Switching for Arc Flash danger mitigation in distribution class switchgear. Distance is Safety We will discuss through examples of actual occurrences and possible
More informationHow To Choose A Transformer
Consider open loop MV network as an example source 1 source 2 NC NC NC or NO main MV switchboard A B Detail design of substation NC NC NC NO NC NC switchboard 1 switchboard 2 switchboard 3 MV MV MV LV
More informationProduct Description Full Voltage Starting Electric Fire Pump Controllers FTA1000
Product Description Full Voltage Starting Electric Fire Pump Controllers FTA1000 Description Firetrol FTA1000 Full Voltage Fire Pump Controllers are intended for use with electric motor driven fi re pumps
More informationThe HVAC SOLUTION DELIVERING POWER...SAVING ENERGY
The HVAC SOLUTION DELIVERING POWER...SAVING ENERGY PowerGate - Cost effective solutions for F 1 Horsepower Rating 001 1-40 HP (208V) 075 1-75 HP (480V) Input Voltage 2V 208-240V 4V 380-480V Disconnect
More informationANCILLARY EQUIPMENT AND ELECTRICAL EQUIPMENT Power Supply Systems and Electrical Equipment for Desalination Plants - Y.M. Hamud and A.H.
POWER SUPPLY SYSTEMS AND ELECTRICAL EQUIPMENT FOR DESALINATION PLANTS Y.M. Hamud and A.H. Anwar Abu Dhabi Water and Electricity Authority, Abu Dhabi, UAE Keywords : Electrical System, Network for Desalination,
More informationTest & Data Management Software
Test & Data Management Software TDMS protective relays energy meters transducers power quality CT-VT-PT transformers ground grid circuit breakers batteries surge arresters The Integrated Testing Solution
More informationHow to reduce exposure to arc flash hazards
GE Energy Industrial Solutions How to reduce exposure to arc flash hazards Multiple solutions for new and existing facilities imagination at work Multiple Issues Today s power system engineer must not
More informationABB ! CAUTION. Type COQ Negative Sequence Generator Relay. (50/60 Hertz) 41-161J. Instruction Leaflet
ABB Instruction Leaflet 41-161J Effective: May 1997 Supersedes I.L. 41-161H Dated July 1984 ( ) Denotes Change Since Previous Issue Type COQ Negative Sequence Generator Relay (50/60 Hertz)! CAUTION Before
More informationGENERATOR SELECTION. a. Three phase - 120/208V, 3 phase, 4W wye; 277/408, 3 phase, 4W wye; * 120/240V 3 phase, 4W Delta
GENERATOR SELECTION Generators must be sized to handle their load based on the continuous KW, kilowatt load, and KVA, kilovoltamp load, and the worst case starting load KW + KVA. They must be derated for
More informationSimulation of Ungrounded Shipboard Power Systems in PSpice
Simulation of Ungrounded Shipboard Power Systems in PSpice Haibo Zhang IEEE Student Member Karen L.Butler IEEE Member Power System Automation Lab Electrical Engineering Department Texas A&M University
More informationPower Quality for Information Technology System
Power Quality for Information Technology System ITS OBVIOUS THE TOLERANCE IS DIFFRENT But What isn t Tobvious? HOW MANY OF YOU HAVE : A COMPUTER AT HOME? = Computers are not screens and Keyboards COMPUTERS
More informationemployed to ensure the continuing reliability of critical systems.
4 Regulations 1989, Regulation 4, places a duty on employers to provide safe systems for their workers: Regulation 4 of the Electricity at Work Regulations 1989 Systems, work activities and protective
More informationMini Circuit Breakers, Fuse Blocks, and Electronic Circuit Protection
Technical Data Mini Circuit Breakers, Fuse Blocks, and Electronic Circuit Protection Topic Page 1489-M Miniature Circuit Breakers 2 1492-SP Supplementary Protectors 15 1492-D Circuit Breakers 27 188 Regional
More informationMEDIUM VOLTAGE. Michael Mosman, PE. CCG Facilities Integration Incorporated FACILITIES INTEGRATION INCORPORATED
MEDIUM VOLTAGE ELECTRICAL SYSTEMS for DATA CENTERS Michael Mosman, PE Chief Technical Officer CCG Facilities Integration Incorporated FACILITIES INTEGRATION INCORPORATED CCG Facilities Integration Incorporated
More informationTitelgrau belassen! Leere Vorlage
Titelgrau belassen! Leere Vorlage MAVOWATT 20 Energy Platform Energy and Power Analyzer MAVOWATT 20 The new Energy and Power Analyzer 2 Klaus-Peter Richter Product Management 10.3.2010 Page 2 Applications
More informationElectrical Systems. <Presenter>
Review Root Causes of Energy Inefficiency Roadmap to Maximize Energy Efficiency Best Practices Alternative Energy Sources Controls Take Aways Seek Professional Help. ENERGY INEFFICIENCY OF
More informationABB PSPS Erich Steinmann; Generator control-2013
ABB PSPS Erich Steinmann; Generator control-2013 GENERATOR CONTROL THE MODULAR SOLUTION FOR GENERATORS To make sure that power is efficiently converted into electric energy, it is necessary to supervise
More informationmisconceptions about arc-flash hazard assessments
misconceptions about arc-flash hazard assessments There are some common misconceptions about Arc-Flash Hazard Assessments which reduce the effectiveness of the Assessments and can increase electrical hazards.
More informationPacifiCorp Original Sheet No. 476 FERC Electric Tariff, Substitute 6 th Rev Volume No. 11 APPENDIX 2 TO SGIP
PacifiCorp Original Sheet No. 476 APPENDIX 2 TO SGIP SMALL GENERATOR INTERCONNECTION REQUEST (Application Form) Transmission Provider: Designated Contact Person: Address: Telephone Number: An Interconnection
More informationEaton s Electrical Services & Systems. Technical Training Safety Training
Eaton s Electrical Services & Systems Technical Training Safety Training 2 EATON CORPORATION Eaton s Electrical Services & Systems Technical Training Safety Training Eaton conducts technical training and
More informationQUESTIONS and ANSWERS RFB 745-15-9894, Metal Clad Switchgear and Power Control Room
QUESTIONS and ANSWERS RFB 745-15-9894, Metal Clad Switchgear and Power Control Room 1) When you click on the UTHSCSA Drawing the site takes you to the E-1 drawing no other. Will there be other drawings
More informationPower Monitoring for Modern Data Centers
Power Monitoring for Modern Data Centers December 2010/AT304 by Reza Tajali, P.E. Square D Power Systems Engineering Make the most of your energy SM Revision #1 12/10 By their nature, mission critical
More informationCahier technique no. 196
Collection Technique... Cahier technique no. 196 Integration of local power generation in industrial sites and commercial buildings T. Hazel "Cahiers Techniques" is a collection of documents intended for
More information14. Troubleshooting Guide
14. Guide 14.1 Refrigeration Cycle System In order to diagnose malfunctions, ensure the air conditioner is free from electrical problems before inspecting the refrigeration cycle. Such problems include
More informationTable of Contents. TransformerIQ FAQs 1
[12/12] FAQs Table of Contents FAQ 1. What size transformer will TransformerIQ monitor?... 2 FAQ 2. Are there different TransformerIQ versions?... 2 FAQ 3. How are the units powered?... 2 FAQ 4. What is
More informationWhat are the basic electrical safety issues and remedies in solar photovoltaic installations?
What are the basic electrical safety issues and remedies in solar photovoltaic installations? Presented by: Behzad Eghtesady City of Los Angeles Department of Building and Safety Topics Covered Photovoltaic
More information3.1.1 Full Type Tests & Routine Tests according to Clause 8 2 & 8 3. 4.0 Instructions For Installation, Operation & Maintenance
SPECIFICATION FOR LOW VOLTAGE SWITCHBOARD SEN I N D E X Description 10 STANDARD TECHNICAL REQUIREMENTS 11 Standards 12 General Operating Conditions 13 General Description Of Switchboard 131 Structure 132
More informationApplication of Four-Pole Circuit Breakers within Data Centers
Application of Four-Pole Circuit Breakers within Data Centers December 2013/AT324 by Frank Waterer, Fellow Engineer, Schneider Electric Engineering Services Make the most of your energy SM Revision #1
More informationBRANDON AND CLARK INC. // SCOTT W. CLARK, P.E. ELECTRICAL CONTINUING EDUCATION ARC FLASH - NFPA 70E
BRANDON AND CLARK INC. // SCOTT W. CLARK, P.E. ELECTRICAL CONTINUING EDUCATION ARC FLASH - NFPA 70E Training is not a substitute for following corporate safety guidelines. Always refer to the latest safety
More informationFundamentals of Modern Electrical Substations Part 1: Mission of Electrical Substations and their Main Components
Fundamentals of Modern Electrical Substations Part 1: Mission of Electrical Substations and their Main Components Course No: E02-010 Credit: 2 PDH Boris Shvartsberg, Ph.D., P.E., P.M.P. Continuing Education
More informationSUBJECT: How to wire a motor starter Number: AN-MC-004 Date Issued: 2/08/2005 Revision: Original
SUBJECT: How to wire a motor starter Number: AN-MC-004 Date Issued: 2/08/2005 Revision: Original A motor starter is a combination of devices to allow an induction motor to start, run and stop according
More informationEvaluating Water-Damaged Electrical Equipment
Evaluating Water-Damaged Electrical Equipment 1 USE OF THIS PUBLICATION This publication provides information on how to evaluate electrical equipment that has been exposed to water through flooding, fire
More information