Fire Protection Program Of Chashma Nuclear Power Generating Station Pakistan Atomic Energy Commission 5/28/2015 1

Size: px
Start display at page:

Download "Fire Protection Program Of Chashma Nuclear Power Generating Station Pakistan Atomic Energy Commission 5/28/2015 1"

Transcription

1 Fire Protection Program Of Chashma Nuclear Power Generating Station Pakistan Atomic Energy Commission 5/28/2015 1

2 Nuclear Power in Pakistan Nuclear Power Plants Capacity (MWe) Year of Commissioning In Operation KANUPP (PHWR) 137/ CHASNUPP-1 (PWR) CHASNUPP-2 (PWR) Under-construction CHASNUPP-3 (PWR) CHASNUPP-4 (PWR) /28/2015 2

3 IRAN Location of NPPs TAJIKISTAN CHINA C1/C2/C3/C4 KANUPP 5/28/2015 3

4 Plants Design / Specifications of CNPGS Reactor Type Rated Thermal Power Gross Electrical Output Net Electrical Output PWR, 2 Loop MW th 325 MWe 300 MWe Operating Pressure Operating Temperature 15.2 MPa o C Net Efficiency ~34 % 4

5 Elements of Fire Protection Program Design Codes and Standards Principles of Fire Protection Fire protection policy Fire Fighting Strategy Manual Fire Fighting Fire Prevention plan IAEA Expert Review Missions Fire Events Review at CNPGS On-going Issues Improvement plan 5/28/2015 5

6 Principles of Fire Protection Defense in Depth criteria will ensure throughout plant lifetime following objectives: Preventing fires from starting Detecting and Extinguishing quickly those fires which do starts, thus limiting the damage Preventing the spread of fires which have not been extinguished, thus minimizing their effects on essential plant functions Ensuring that fire will not prevent the performance of necessary plant safe shut down functions and will not significantly increase radioactive release to the environment 5/28/2015 7

7 Fire Protection Policy Protection of Structures, Systems & Components Fire prevention Use of non combustible material in construction and non combustible /fire resistant equipments / cables Transient Combustible Control Control of Ignition Source Fire Detection Provision of State of the Art Plant Fire Detection and Alarm system Fire fighting Systems A combination of Auto Actuated and Manual Fire Fighting Systems 5/28/2015 8

8 Fire Protection Policy Preventing the Spread of Fire 03 hours & 1.5 hours fire resistance rating fire compartment Redundant trains of safety systems Spatial separation of safety equipment Fire retardant Class 1E Electrical cables and Equipment Fire dampers in HVAC Ducts Implementation of Fire Barrier penetration seals Procedure Smoke Exhaust system for important plant areas (MCR, 6 kv panel rooms) 5/28/2015 9

9 Fire Fighting Strategy Fire Water Suppression systems includes: Four 50% capacity fire water supply pumps Two 100% Fire Water Pools Independent pneumatic pressurizer pumps & tanks Pressurized fire water main supplies to Spray & Sprinkler System, pre-action deluge system and fire hydrants Auto actuated Deluge valve protect cable shafts, cable spreading areas, Charging pumps, lube oil tanks, Turbine Generator bearings and main transformers. Fixed CO 2 fire extinguishing system protect Emergency Diesel Generators and Auxiliary feed water Diesel Driven Pumps & tanks in Nuclear Auxiliary building Fixed foam system protect Diesel fuel oil tanks at EDG building 5/28/

10 Manual Fire Fighting Fire hydrants covers all areas inside and outside the plant buildings More than 1400 portable fire extinguishers at about 400 fire points Plant operation staff trained in fire fighting serve as first responder to fire in plant Plant on-site Fire Brigade is equipped with 4 Fire Tenders, more than 40 professional fire fighting staff and equipment Perform Round the Clock shift duty Equipment in Fire Tenders - hose pipes, Multi-jet Nozzles, Special Safety Shoes, Fire Resistant Suits, Fire Helmets, Emergency Communication equipment, Flash Lights, Self Contained Breathing Apparatus, CO filters, Full Face Masks, Fire Extinguishers etc. 5/28/

11 Fire Prevention Plan Conduct of Transient Combustible Control inspection every month Control of ignition sources through administrative procedures Control of Hot work through work permit /fire watch Conduct of Fire drills regularly to verify the preparedness of operator and fire fighting staff Imparted training in fire fighting to other plant personnel Close collaboration with off site fire brigade 5/28/

12 Fire Prevention plan Emergency plans are available for the proper response to all potential site fires, particularly nuclear safety-related areas and equipment. Plans contains safety-related areas and equipment layout, fire hazards, fire protection equipment and fire detector type and location Respond to fire alarms Notification to emergency response teams (e.g., onsite fire brigade, off-site fire department) Coordination with operations and security personnel Fire-fighting techniques Response to potential radiological hazards. 5/28/

13 IAEA Fire Protection Mission to C-1 IAEA Pre OSART Review Mission of Chashma NPP Unit-1 was conducted in 1999 and recommended Review Mission on Fire Protection. IAEA Experts Review Mission on Fire Protection of Chashma NPP Unit-1 was conducted from 8 to 12 Nov 1999 prior to initial core loading. Overall fire protection program in the light of FSAR and FHA was reviewed. 12 Recommendations and 17 Observations were recommended in the mission final report Mission s recommendations and observations were implemented in due time and made the fire protection requirements at par with FSAR and FHA 5/28/

14 IAEA Fire Training Follow-up Mission IAEA Experts Fire Training Mission from 11 to 14 April 2000 was conducted at Chashma NPP Unit participants from Operation, Maintenance, Health Physics & Technical Divisions participated. Various plant fire protection procedures were developed as result of the training mission. 5/28/

15 IAEA OSART Mission IAEA OSART Review Mission on Unit-1 was conducted in 2004 Mission gave 3 recommendations on Fire protection program Resolution of issues were verified during OSART follow-up mission in FHA was reviewed and validated during PSR conducted in /28/

16 Fire Events Review at CNPGS # Description Causes Corrective Action 1. Plant was in Mode B after fuel loading. On , under-water lights were switched ON to perform some work. These lights were left ON inadvertently. On water from spent fuel pool was transferred to FTC for some requirement. When water level decreased below set point, level switches of under-water lights switched off their respective lights except one due to malfunction of its level switch. A short circuit in the underwater light resulted in damage of the power cable insulation which resulted in the burning of 10 under water light cables, 07 floating switches cable, 03 under water light controllers, under water light camera cable. Direct Cause: Malfunction of the water level switch (controller) of an under water light and power supply circuit breaker. Root Cause: In-adequate work control and non existence of a procedure defining responsibilities of the operators /work Group for operation of underwater lights. Contributory Causes: In-adequate procedure for draining water from the spent fuel pools. Use of a single circuit breaker for two underwater lights. Incorporated instruction in the relevant procedure for the circuit breakers of all under water lights are to be switched off prior to start of draining water from the pools. Modified existing power supply circuit for the underwater lights so that each light has its own breaker of 6 Amps instead of a common 16 Amps for two. 5/28/

17 Fire Events Review at CNPGS # Description Causes Corrective Action 2. On , smoke alarm received in MCR from room NA 004. On surveillance by operator smoke / burning smell was observed from Incoming Breaker-B of MCC Panel. 3. On , Plant was at mode 4A. SRC heating and pressurization was in progress with RCP-B in operation. Operator observed smoke coming from near pump body. Fire alarms also gave fire alarm. MCR was informed and pump was stopped Loose joint of terminal of one phase of a power supply bus to the breaker caused heating of insulating material. No real fire develop. Soaked oil in insulation material ignited due to high temperature of SRC line i.e. 192ºC Terminal joints were replaced and were properly tightened. Pump was stopped. Fire was extinguished using portable fire extinguishers. Insulation was removed and leakage of oil was fixed. 5/28/

18 Fire Events Review at CNPGS # Description Causes Corrective Action On when plant was operating at full load smoke alarm annunciated in MCR from IPB (Insulated Phase Bus Bar) area at +8.0 m, underneath Main Generator at turbine building. Whereas after checking the area smoke and sparking was observed from carbon brushes of Main Generator. GCB was manually opened and reactor was manually tripped Direct Cause Smoke due to sparking from carbon brushes Contributory Causes Choking of the slanted ventilating holes of slip ring. Choking of ventilation ducts of carbon brush assembly. Root Cause Design inadequacy preventing effective monitoring of carbon brushes. - Replaced and repaired damaged parts. - Adjusted gaps between the slip rings and carbon brushes holders in the range of 1.5 mm to 3.5 mm as per vendor advice. - Cleaned ventilating holes of slip rings and inlet / outlet ventilation duct of carbon bushes assembly. - Marked the individual carbon brush holders in the carbon brush rigging. - Installed smoke detectors in generator cubical 5/28/

19 On Going Issues Obsolete electronic of Plant Fire Detection and Alarm System Maintenance issue of pneumatic fire detection piping net of Main, Auxiliary and Step down transformers Non availability of power supply to Fire alarm control panel under LOP / draining of back up battery. 5/28/

20 Improvement Plan of Fire Detection System Unit-1 Components and software of plant Fire Detection and alarm system are being upgraded in progress Transformer s pneumatic detection is being replaced with Automatic flame detectors will be done in RFO-10 To provide connection from emergency power supply to fire alarm control panels in MCR modification is under review Air sampling fire detectors are being installed inside electrical cabinets in NI will be done in RFO-10 5/28/

21 Any Question Please 5/28/

FIRE-FIGHTING DESIGN BRIEF REPORT

FIRE-FIGHTING DESIGN BRIEF REPORT P a g e 1 SECTION 04 (Doc.No.A/DBR 001) FIRE-FIGHTING DESIGN BRIEF REPORT P a g e 2 1.0 SCOPE 2.0 STANDARDS AND CODES 3.0 TYPES OF SYSTEM PROPOSED 4.0 FIRE HYDRANT SYSTEM 5.0 AUTOMATIC SPRINKLER SYSTEM

More information

FACILITY FIRE PREVENTION AND EMERGENCY PREPAREDNESS INSPECTION CHECKLIST

FACILITY FIRE PREVENTION AND EMERGENCY PREPAREDNESS INSPECTION CHECKLIST FACILITY FIRE PREVENTION AND EMERGENCY PREPAREDNESS INSPECTION CHECKLIST Date of Inspection: Conducted by: Location: Reviewed by: Date of Review: Comments or additional corrective action taken as a result

More information

Trace Electric Trace Fire Protection

Trace Electric Trace Fire Protection ELECTRIC AL FIRE PROTECTION ACTIVE IN THE FOLLOWING AREAS: Multi-Unit Residential Apartment Buildings Industrial Commercial Institutional & Long Term Care Facilities Trace Electric Trace Fire Protection

More information

Fire Alarm System Standpipes Sprinkler Systems Fire Drills Commercial Cooking Hood and more

Fire Alarm System Standpipes Sprinkler Systems Fire Drills Commercial Cooking Hood and more FIRE PROTECTION SYSTEMS Fire protection systems, measures and equipment are all related to the safety of the occupants and the protection of the property. As part of a building design and its intended

More information

Liberty Mutual Insurance RISK ENGINEERING PROCEDURE. REP 07 Incident Planning For external use

Liberty Mutual Insurance RISK ENGINEERING PROCEDURE. REP 07 Incident Planning For external use Liberty Mutual Insurance RISK ENGINEERING PROCEDURE REP 07 Incident Planning For external use Risk Engineering Procedure Incident Planning CONTENTS Page PURPOSE... 3 BACKGROUND... 4 INCIDENT PLANNING PREPARATION...

More information

Transformer Deluge Systems

Transformer Deluge Systems Transformer Deluge Systems How Do Transformer Fires Ignite? Common causes of transformer failure: Weather-related events such as lightning Short circuits in electrical equipment The most common cause is

More information

Winnipeg Fire Department Fire Prevention Branch

Winnipeg Fire Department Fire Prevention Branch Winnipeg Fire Department Fire Prevention Branch Manitoba Fire Code Life-Safety Equipment Maintenance Requirements The Fire Prevention Branch of the Winnipeg Fire Department has prepared this document of

More information

GE LM6000 PA Package for Sale. Business Unit Industrial Gas Turbines - Packaging

GE LM6000 PA Package for Sale. Business Unit Industrial Gas Turbines - Packaging GE LM6000 PA Package for Sale Business Unit Industrial Gas Turbines - Packaging 50 Hz LM6000 PA Package Key Data Technical Characteristics Gas Turbine Technical Characteristics El. Generator Brand: GE

More information

Trouble Shooting. Pump

Trouble Shooting. Pump Trouble Shooting Pump Trouble Possible Cause Remedy Oil leaking in the area of water pump crankshaft Worn crankshaft seal, bad bearing, grooved shaft, or failure of retainer o-ring. Excessive play on crankshaft

More information

FORM FOR INSPECTION, TESTING AND MAINTENANCE OF FIRE PUMPS DIESEL

FORM FOR INSPECTION, TESTING AND MAINTENANCE OF FIRE PUMPS DIESEL Information on this form covers the minimum requirements of NFPA 25-1998 for centrifugal fire pumps. This form does not relieve the owner of the responsibility of complying with the other requirements

More information

Published in the Official State Gazette (BOE) number 166 of July 10th 2009 [1]

Published in the Official State Gazette (BOE) number 166 of July 10th 2009 [1] Nuclear Safety Council Instruction number IS-22, of July 1st 2009, on safety requirements for the management of ageing and long-term operation of nuclear power plants Published in the Official State Gazette

More information

Name Of Occupancy Date. Yes No Describe

Name Of Occupancy Date. Yes No Describe FIRE PREVENTION INSPECTION CHECKLIST For Class A Occupancy (For Assembly Buildings, Bars, Restaurants, Gyms, Churches, Arenas, Theatres or wherever people gather) Name Of Occupancy Date Physical Address

More information

Important Ontario Fire Code Information for Building Owners in the City of Windsor

Important Ontario Fire Code Information for Building Owners in the City of Windsor Important Ontario Fire Code Information for Building Owners in the City of Windsor This information is intended to be used a reference only. For a complete listing consult the Ontario Fire Code or contact

More information

Maintaining Fire Protection Systems

Maintaining Fire Protection Systems Maintaining Fire Protection Systems Fire continues to be a major threat to your business and your personal safety. Each year several thousand people are injured or killed by fires and billions of dollars

More information

Ontario Fire Code SECTION 5.13 DIP TANKS. Illustrated Commentary. Office of the Ontario Fire Marshal

Ontario Fire Code SECTION 5.13 DIP TANKS. Illustrated Commentary. Office of the Ontario Fire Marshal Ontario Fire Code SECTION 5.13 DIP TANKS Illustrated Commentary Office of the Ontario Fire Marshal Dip Tanks Illustrated Commentary 1 5.13.1. Location 5.13.1.1. Dip tank operations involving flammable

More information

Risk Engineering Guideline

Risk Engineering Guideline www.hdi.global HDI Risk Consulting Risk Engineering Guideline Impairment of fire protection systems Basic protection systems should not be impaired without adequate replace compensation with provisions.

More information

ALBERTA FIRE CODE SAFETY EQUIPMENT MAINTENANCE REQUIREMENTS

ALBERTA FIRE CODE SAFETY EQUIPMENT MAINTENANCE REQUIREMENTS ALBERTA FIRE CODE SAFETY EQUIPMENT MAINTENANCE REQUIREMENTS In this document are the fire safety equipment maintenance requirements that are found in Division B of the Alberta Fire Code (AFC 2006) for

More information

Chapter 1 Malfunction and Troubleshooting for Diesel Engine

Chapter 1 Malfunction and Troubleshooting for Diesel Engine Chapter 1 Malfunction and Troubleshooting for Diesel Engine 1. Causes and Troubleshooting for the Engine Not Being Started It is cold Machine oil is viscous Failure of fuel system Water mixed in the fuel

More information

Vehicle Fire Protection. An Ownerʼs Manual for ANSUL Fire Suppression/Detection Systems

Vehicle Fire Protection. An Ownerʼs Manual for ANSUL Fire Suppression/Detection Systems Vehicle Fire Protection An Ownerʼs Manual for ANSUL Fire Suppression/Detection Systems 002792 Off-road vehicles do have fires Statistics show that off-road vehicles burn with alarming frequency. These

More information

NRC INSPECTION MANUAL

NRC INSPECTION MANUAL NRC INSPECTION MANUAL INSPECTION PROCEDURE 88055 NMSS/FCSS PROGRAM APPLICABILITY: 2600 FIRE PROTECTION (ANNUAL) 88055-01 INSPECTION OBJECTIVES 01.01 The objectives of this procedure are to evaluate the

More information

Evaluate, Clean, and Tune Guidance

Evaluate, Clean, and Tune Guidance Evaluate, Clean, and Tune Guidance The Evaluate, Clean and Tune (ECT) process serves three essential purposes in the Weatherization Assistance Program (WAP). The first is to evaluate the existing system

More information

26 3213.13 Diesel Engine Driven Generators Page 1 of 6

26 3213.13 Diesel Engine Driven Generators Page 1 of 6 Last Update: December 8, 2014 A. Description of System Consultant s Handbook Page 1 of 6 1. Provide a diesel engine driven electric generating unit, factory assembled, tested and certified to operate at

More information

Nuclear power plant systems, structures and components and their safety classification. 1 General 3. 2 Safety classes 3. 3 Classification criteria 3

Nuclear power plant systems, structures and components and their safety classification. 1 General 3. 2 Safety classes 3. 3 Classification criteria 3 GUIDE 26 June 2000 YVL 2.1 Nuclear power plant systems, structures and components and their safety classification 1 General 3 2 Safety classes 3 3 Classification criteria 3 4 Assigning systems to safety

More information

HSE information sheet. Fire and explosion hazards in offshore gas turbines. Offshore Information Sheet No. 10/2008

HSE information sheet. Fire and explosion hazards in offshore gas turbines. Offshore Information Sheet No. 10/2008 HSE information sheet Fire and explosion hazards in offshore gas turbines Offshore Information Sheet No. 10/2008 Contents Introduction.. 2 Background of gas turbine incidents in the UK offshore sector...2

More information

Recommended Practice for Installation of Transit Vehicle Fire Protection Systems

Recommended Practice for Installation of Transit Vehicle Fire Protection Systems Recommended Practice for Installation of Transit Vehicle Fire Protection Systems Approved October 25, 2007 APTA Fire Safety Working Group Approved May 3, 2008 APTA Bus Safety Committee Approved October

More information

Factory owners must ensure the boiler is:

Factory owners must ensure the boiler is: Factory owners must ensure the boiler is: * Registered with the Boilers and Pressure Vessels Division, Labour Department * Examined by an appointed examiner and has a valid certificate of fitness * Supervised

More information

EXHIBIT A SCOPE OF WORK

EXHIBIT A SCOPE OF WORK EXHIBIT A SCOPE OF WORK 1. (Contractor) shall provide fire alarm system maintenance/repair/testing services as described herein to the California Department of Veterans Affairs (hereinafter CDVA, CalVet,

More information

Full scale tunnel fire tests of VID Fire-Kill Low Pressure Water Mist Tunnel Fire Protection System in Runehamar test tunnel, spring 2009

Full scale tunnel fire tests of VID Fire-Kill Low Pressure Water Mist Tunnel Fire Protection System in Runehamar test tunnel, spring 2009 Full scale tunnel fire tests of VID Fire-Kill Low Pressure Water Mist Tunnel Fire Protection System in Runehamar test tunnel, spring 2009 By Carsten Palle, VID Fire-Fill, www.vid.eu Presented at ISTSS

More information

ALVERNIA UNIVERSITY OSHA REGULATION: 29 CFR 1910.252 WELDING, CUTTING, AND BRAZING ( HOT WORK ) SECTION: 3600

ALVERNIA UNIVERSITY OSHA REGULATION: 29 CFR 1910.252 WELDING, CUTTING, AND BRAZING ( HOT WORK ) SECTION: 3600 OSHA REGULATION: 9 CFR 90.5 WELDING, CUTTING, AND BRAZING ( HOT WORK ) A. POLICY. This procedure follows requirements set forth in 9 CFR 90.5.. This policy applies to all Hot Work operations being done

More information

Harris Nuclear Plant (HNP) NFPA 805 Transition. NFPA 805 Monitoring Program

Harris Nuclear Plant (HNP) NFPA 805 Transition. NFPA 805 Monitoring Program Harris Nuclear Plant (HNP) NFPA 805 Transition NFPA 805 Monitoring Program Oconee / Harris NFPA 805 Pilot Observation Meeting April 14-16, 2008 Charlotte, NC Keith Began, CES/FP Review from Nov. 2007 Pilot

More information

Automatic fire-extinguishing systems for commercial cooking

Automatic fire-extinguishing systems for commercial cooking Automatic fire-extinguishing systems for commercial cooking Leading Items First Ignited in Eating and Drinking Establishment Structure Fires, 2000-2004 Annual Averages Cooking materials, incl. food and

More information

FIRE RISK ASSESSMENT IN GERMANY - PROCEDURE, DATA, RESULTS -

FIRE RISK ASSESSMENT IN GERMANY - PROCEDURE, DATA, RESULTS - International Conference Nuclear Energy in Central Europe 2000 Golf Hotel, Bled, Slovenia, September 11-14, 2000 FIRE RISK ASSESSMENT IN GERMANY - PROCEDURE, DATA, RESULTS - H.P. Berg Bundesamt für Strahlenschutz

More information

CITY OF PHILADELPHIA DEPARTMENT OF LICENSES AND INSPECTIONS ANNUAL CERTIFICATION FOR FIRE ALARM SYSTEMS

CITY OF PHILADELPHIA DEPARTMENT OF LICENSES AND INSPECTIONS ANNUAL CERTIFICATION FOR FIRE ALARM SYSTEMS CITY OF PHILADELPHIA DEPARTMENT OF LICENSES AND INSPECTIONS ANNUAL CERTIFICATION FOR FIRE ALARM SYSTEMS PROPERTY ADDRESS (BRT Address Required) TESTING CONTRACTOR (Name and Address) License No. ANNUAL

More information

(2) Various fire sections enclosed by various classes of fire divisions; (3) Arrangement of fire detectors and manual fire alarm stations;

(2) Various fire sections enclosed by various classes of fire divisions; (3) Arrangement of fire detectors and manual fire alarm stations; (1979) (Rev.1 1990) (Rev.2 1996) (Rev.3 Jan 2012) Safety features.1 Fire protection and extinction.1.1 General Fire protection arrangements and fire extinguishing systems are to be in accordance with the

More information

Program No. 1.6.1. Section Heading

Program No. 1.6.1. Section Heading ENVIRONMENTAL HEALTH AND SAFETY EHS PROGRAM MANUAL Program Title 1.0 INTRODUCTION The New York City Fire Department (FDNY) is responsible for approving and/or inspecting fire alarm systems, buildings,

More information

OROT RABIN POWER STATION UNITS 1-4. 4 x 350 MW

OROT RABIN POWER STATION UNITS 1-4. 4 x 350 MW ISRAEL ELECTRIC OROT RABIN POWER STATION UNITS 1-4 4 x 350 MW COAL BOILER CONVERSION TO LOW NO X NATURAL GAS AND COAL FIRING BY PRIMARY AND SECONDARY MEASURES INSTALLATION Replacing the Burner Management

More information

INDUSTRIAL POWER GENERATION EQUIPMENT Typhoon SGT-100 4.9 MW / 5340 KVA 50Hz 11KV Duel Fuel Power Station

INDUSTRIAL POWER GENERATION EQUIPMENT Typhoon SGT-100 4.9 MW / 5340 KVA 50Hz 11KV Duel Fuel Power Station D & S Turbine International LLC INDUSTRIAL POWER GENERATION EQUIPMENT Typhoon SGT-100 4.9 MW / 5340 KVA 50Hz 11KV Duel Fuel Power Station INDUSTRIAL POWER GENERATION EQUIPMENT Typhoon SGT-100 4.9 MW /

More information

Nuclear Power Plant Electrical Power Supply System Requirements

Nuclear Power Plant Electrical Power Supply System Requirements 1 Nuclear Power Plant Electrical Power Supply System Requirements Željko Jurković, Krško NPP, zeljko.jurkovic@nek.si Abstract Various regulations and standards require from electrical power system of the

More information

PRODUCT DATA BULLETIN

PRODUCT DATA BULLETIN PRODUCT DATA BULLETIN Unit: LM1500 Gas Turbine Generator Package Ref: DSSI unit number 83316 Summary Specifications GE-LM1500 9 MW (nominal) Natural Gas / Diesel Dual Fuel Turbine 9.36 MW Capable Capacity

More information

WASTE Application Form - Dublin Waste to Energy SECTION J ACCIDENT PREVENTION & EMERGENCY RESPONSE

WASTE Application Form - Dublin Waste to Energy SECTION J ACCIDENT PREVENTION & EMERGENCY RESPONSE SECTION J ACCIDENT PREVENTION & EMERGENCY RESPONSE Describe the existing or proposed measures, including emergency procedures, to minimise the impact on the environment of an accidental emission or spillage.

More information

Current as of 11/10/08 1 of 1

Current as of 11/10/08 1 of 1 BEST PRACTICES STANDARDS FOR SCHOOLS UNDER CONSTRUCTION OR BEING PLANNED FOR CONSTRUCTION I. Site Layout A. School buildings shall be provided with a securable perimeter. A securable perimeter means that

More information

4.0 SPITFIRE TROUBLESHOOTING

4.0 SPITFIRE TROUBLESHOOTING 4.0 SPITFIRE TROUBLESHOOTING 1.0. Will not turn over SECTION I. ENGINE 1.1. There is a loose or corroded battery terminal. Clean and tighten the battery terminal connections. 1.2. The battery is dead.

More information

Water mist fire suppression systems. Minifog ProCon Low-pressure water mist system

Water mist fire suppression systems. Minifog ProCon Low-pressure water mist system Water mist fire suppression systems Minifog ProCon Minifog ProCon Low-pressure water mist system IRE PROTECTION Efficient even for non-enclosed equipment Minifog ProCon systems by Minimax use innovative

More information

Hot Work Permit Policy

Hot Work Permit Policy Hot Work Permit Policy Environmental Health and Safety Department 800 West Campbell Rd., SG10 Richardson, TX 75080-3021 Phone 972-883-2381/4111 Fax 972-883-6115 http://www.utdallas.edu/ehs Modified: May

More information

NMSU FIRE DEPARTMENT Commercial Kitchen Fire Suppression Worksheet

NMSU FIRE DEPARTMENT Commercial Kitchen Fire Suppression Worksheet This Commercial Kitchen Automatic Fire has been created to assure all documentation has been submitted to assist you in assuring proper plans and documentations has been submitted and reviewed by New Mexico

More information

INSPECTION, TESTING AND MAINTENANCE OF FIRE PROTECTION SYSTEMS AND EQUIPMENT

INSPECTION, TESTING AND MAINTENANCE OF FIRE PROTECTION SYSTEMS AND EQUIPMENT CITY OF SPRING LAKE PARK Code Enforcement Department 1301 81 st Avenue NE Spring Lake Park MN 55432 Business Phone 763-784-6491 Fax 763-792-7257 INSPECTION, TESTING AND MAINTENANCE OF FIRE PROTECTION SYSTEMS

More information

FIREFIGHTING AND DAMAGE CONTROL

FIREFIGHTING AND DAMAGE CONTROL FIREFIGHTING AND DAMAGE CONTROL Everyone on aboardship have another big job - to work aside from their primary duties. This big job is to look out constantly for the safety of the ship and crew. When the

More information

Other EC and LS documents may be requested by surveyors their, as needed, throughout the survey.

Other EC and LS documents may be requested by surveyors their, as needed, throughout the survey. Documentation required by the Hospital Accreditation program Life Safety (LS) and selected Environment of Care (EC) standards is presented in the following pages. These documents will be reviewed by the

More information

INSTRUCTIONS FOR BUILDINGS WITH FIRE PROTECTION EQUIPMENT

INSTRUCTIONS FOR BUILDINGS WITH FIRE PROTECTION EQUIPMENT INSTRUCTIONS FOR BUILDINGS WITH FIRE PROTECTION EQUIPMENT FIRE EXTINGUISHERS,SPRINKLER SYSTEMS AND FIRE ALARMS Attachment #1 Inspection of Fire Extinguishers Fire Extinguishers must be tested according

More information

Fire Safety Risk Assessment Checklist for Residential Care Premises

Fire Safety Risk Assessment Checklist for Residential Care Premises Checklist for Residential Care Premises Name of Premises: Address of Premises: Name of Responsible Person: What area / location does the assessment cover? Does the assessment cover the whole site YES or

More information

Fire Pump Plan Review March 2010

Fire Pump Plan Review March 2010 Fire Pump Plan Review March 2010 Date of Review: / / Permit Number: Business/Building Name: Address of Project: Designer Name: Designer s Phone: Contractor: Contractor s Phone: Occupancy Classification:

More information

Boiler & Pressure Vessel Inspection discrepancies and failures

Boiler & Pressure Vessel Inspection discrepancies and failures Boiler & Pressure Vessel Inspection discrepancies and failures Water Heaters / Pressure Vessels Pressure Vessels are inspected once every three years. This requires a test of A: safety relief devices B:

More information

Risk Assessment and Disaster Management Plan The Risk Assessment Study for the upcoming industrial area project of M/s. RIICO Ltd. has been conducted

Risk Assessment and Disaster Management Plan The Risk Assessment Study for the upcoming industrial area project of M/s. RIICO Ltd. has been conducted Risk Assessment and Disaster Management Plan The Risk Assessment Study for the upcoming industrial area project of M/s. RIICO Ltd. has been conducted by functional area expert of EIA Team. The risk assessment

More information

FIRE SAFETY MANUAL INSPECTION FORMS...48 FORM F-1 AUTOMATIC SPRINKLER SYSTEMS WEEKLY INSPECTION...48 FORM F-2 AUTOMATIC SPRINKLER SYSTEMS MONTHLY

FIRE SAFETY MANUAL INSPECTION FORMS...48 FORM F-1 AUTOMATIC SPRINKLER SYSTEMS WEEKLY INSPECTION...48 FORM F-2 AUTOMATIC SPRINKLER SYSTEMS MONTHLY FIRE SAFETY MANUAL INSPECTION FORMS...48 FORM F-1 AUTOMATIC SPRINKLER SYSTEMS WEEKLY INSPECTION...48 FORM F-2 AUTOMATIC SPRINKLER SYSTEMS MONTHLY INSPECTION...49 FORM F-3 AUTOMATIC SPRINKLER SYSTEMS QUARTERLY

More information

IEEE 1248 Guide for the Commissioning of Electrical Systems in Hydroelectric Power Plants*

IEEE 1248 Guide for the Commissioning of Electrical Systems in Hydroelectric Power Plants* IEEE 1248 Guide for the Commissioning of Electrical Systems in Hydroelectric Power Plants* John Yale P1248 Working Group Chair Hydro Plant Engineering Manager Chelan County PUD *137 pages of joyful reading!

More information

General Fire Code Requirements Within Commercial Tenant Spaces

General Fire Code Requirements Within Commercial Tenant Spaces FIRE DEPARTMENT in cooperation with Scope: General Fire Code Requirements Within Commercial Tenant Spaces This handout is designed to assist owners, architects, contractors and others in understanding

More information

Fire Alarm System Monitoring - CAN/ULC-S561-03

Fire Alarm System Monitoring - CAN/ULC-S561-03 Fire Alarm System Monitoring - CAN/ULC-S561-03 Brian McBain ULC Regulatory Services May 4, 2011 Copyright 1995-2007 Underwriters' Laboratories of Canada. All rights reserved. No portion of this material

More information

Loviisa 3 unique possibility for large scale CHP generation and CO 2 reductions. Nici Bergroth, Fortum Oyj FORS-seminar 26.11.

Loviisa 3 unique possibility for large scale CHP generation and CO 2 reductions. Nici Bergroth, Fortum Oyj FORS-seminar 26.11. Loviisa 3 unique possibility for large scale CHP generation and CO 2 reductions Nici Bergroth, Fortum Oyj FORS-seminar 26.11.2009, Otaniemi Loviisa 3 CHP Basis for the Loviisa 3 CHP alternative Replacement

More information

Elements of the Russian Emergency Preparedness Program

Elements of the Russian Emergency Preparedness Program Elements of the Russian Emergency Preparedness Program Randolph L. Sullivan, NRC National Radiological EP Conference St. Louis, Missouri March 2006 2 3 4 5 6 Volgodonsk NPP 1000 MWe VVER, a PWR Large Staff

More information

Unit 1 Turbine Rotor 110 MW Replacement

Unit 1 Turbine Rotor 110 MW Replacement Proceedings World Geothermal Congress 2015 Melbourne, Australia, 19-25 April 2015 Unit 1 Turbine Rotor 110 MW Replacement Amri Zein 1, Wahyu Mulyana 2 and Heribertus Dwiyudha 3 Star Energy Geothermal (Wayang

More information

Fire Safety PROCEDURES January 2011

Fire Safety PROCEDURES January 2011 Fire Safety PROCEDURES January 2011 firesafety@uwo.ca Campus Phones EMERGENCY Dial 911 Fire Safety Service is the focal point for the coordinated administration of the University Fire Safety program and

More information

FIRE SPRINKLER DEMONSTRATION TRAILER

FIRE SPRINKLER DEMONSTRATION TRAILER IFIA FIRE SPRINKLER DEMONSTRATION TRAILER Recommendations for utilizing the fire sprinkler demonstration trailer in your fire department, business or association: INDEX: A) Picking up and towing the Trailer.

More information

ANNUAL FIRE PROTECTION SUMMARY INFORMATION REPORTING GUIDE Revised: May 2011

ANNUAL FIRE PROTECTION SUMMARY INFORMATION REPORTING GUIDE Revised: May 2011 ANNUAL FIRE PROTECTION SUMMARY INFORMATION REPORTING GUIDE Revised: May 2011 Organizations responsible for maintaining property under stewardship of DOE and the Administrator, NNSA, will seek concurrence

More information

MISCELLANEOUS ELECTRICAL JOBS REQUIRING PERMITS

MISCELLANEOUS ELECTRICAL JOBS REQUIRING PERMITS MISCELLANEOUS ELECTRICAL JOBS REQUIRING PERMITS 01. SAFETY INSPECTION of service equipment at FPL Power Source 02. Construction GFI power outlets (Temp Pole for Construction) 03. 90 day temporary power

More information

Ethanol Vehicle and Infrastructure Codes and Standards Citations

Ethanol Vehicle and Infrastructure Codes and Standards Citations Ethanol Vehicle and Infrastructure Codes and Standards Citations This document lists codes and standards typically used for U.S. ethanol vehicle and infrastructure projects. To determine which codes and

More information

Gas Turbine Training Manual

Gas Turbine Training Manual DEVICE NOMENCLATURE The following is the typical list of devices used in gas turbines. Usage of devices depends upon the specific unit configuration. It is advised to check unit specific device summary

More information

Ontario Fire Code SECTION 5.18 INDUSTRIAL OVENS FOR BAKING. Illustrated Commentary AND DRYING PROCESSES. Office of the Ontario Fire Marshal

Ontario Fire Code SECTION 5.18 INDUSTRIAL OVENS FOR BAKING. Illustrated Commentary AND DRYING PROCESSES. Office of the Ontario Fire Marshal Ontario Fire Code SECTION 5.18 INDUSTRIAL OVENS FOR BAKING AND DRYING PROCESSES Illustrated Commentary Office of the Ontario Fire Marshal Industrial Ovens Illustrated Commentary 1 5.18.1. Application

More information

1. Fire Safety Policy and Responsibilities. Consult the Employer s Fire Safety Policy and establish responsibilities of staff for fire safety.

1. Fire Safety Policy and Responsibilities. Consult the Employer s Fire Safety Policy and establish responsibilities of staff for fire safety. Management Checklist 1. Fire Safety Policy and Responsibilities. Consult the Employer s Fire Safety Policy and establish responsibilities of staff for fire safety. 2. Fire Hazard and Risk Assessment. Use

More information

FLORIDA ATLANTIC UNIVERSITY FIRE ALARM SYSTEM INSTALLATION MANUAL

FLORIDA ATLANTIC UNIVERSITY FIRE ALARM SYSTEM INSTALLATION MANUAL FLORIDA ATLANTIC UNIVERSITY FIRE ALARM SYSTEM INSTALLATION MANUAL January, 2003 Environmental Health and Safety Florida Atlantic University 777 Glades Rd. Boca Raton, FL 33431 Phone: 561-297-3129 Fax:

More information

Safe Operating Procedure

Safe Operating Procedure Safe Operating Procedure (Revised 07/09) HOT WORK PERMIT OPERATIONS (For assistance, please contact EHS at (402) 472-4925, or visit our web site at http://ehs.unl.edu/) Authority In recognition of the

More information

9.4 Air Conditioning, Heating, Cooling and Ventilating Systems

9.4 Air Conditioning, Heating, Cooling and Ventilating Systems 9.4 Air Conditioning, Heating, Cooling and Ventilating Systems 9.4.1 Control Building HVAC The Control Building (C/B) Heating, Ventilating and Air-Conditioning (HVAC) System is divided into two separate

More information

MARKEL AMERICAN INSURANCE COMPANY POWERBOAT SELF SURVEY EVALUATION FORM

MARKEL AMERICAN INSURANCE COMPANY POWERBOAT SELF SURVEY EVALUATION FORM Our records reflect that a Condition and Value survey is due for your boat. A Condition and Value survey performed by a competent marine surveyor is the best way to determine if there are any defects or

More information

OFFERED FOR IMMEDIATE SALE Complete 215MW CCGT Power Station For Relocation

OFFERED FOR IMMEDIATE SALE Complete 215MW CCGT Power Station For Relocation Tel: + 44 20 3206 1207 Email: info@indassol.com Longcroft House, 2-8 Victoria Avenue Bishopsgate, London EC2M 4NS OFFERED FOR IMMEDIATE SALE Complete 215MW CCGT Power Station For Relocation 2 x ~72MW GE

More information

Dennis Fire Department Fire Prevention Mark Dellner Fire Chief

Dennis Fire Department Fire Prevention Mark Dellner Fire Chief Dennis Fire Department Fire Prevention Mark Dellner Fire Chief FIRE SAFETY INSPECTION GUIDELINES FOR COMMERCIAL PROPERTIES (MA Fire Prevention Regulations 527 CMR, MGL Chapter 148) FIRE PREVENTION CHECKLIST-

More information

SIOUX HYBRID WATER HEATER

SIOUX HYBRID WATER HEATER SIOUX Hybrid Water Heater for the Concrete Industry SIOUX HYBRID WATER HEATER Patent Pending Maximizing the Benefits of Coil and Direct-Fired Heating Technologies Higher Discharge Temperature True High-Efficiency

More information

MOTOR FUEL DISPENSING SAFETY

MOTOR FUEL DISPENSING SAFETY STRATEGIC OUTCOMES PRACTICE TECHNICAL ADVISORY BULLETIN January 2010 MOTOR FUEL DISPENSING SAFETY Fire! Not an alarm anyone wants to hear, especially not when the fire is burning at a major fuel source.

More information

UNITED STATES NUCLEAR REGULATORY COMMISSION OFFICE OF NUCLEAR REACTOR REGULATION WASHINGTON, DC 20555-0001. June 16, 2011

UNITED STATES NUCLEAR REGULATORY COMMISSION OFFICE OF NUCLEAR REACTOR REGULATION WASHINGTON, DC 20555-0001. June 16, 2011 UNITED STATES NUCLEAR REGULATORY COMMISSION OFFICE OF NUCLEAR REACTOR REGULATION WASHINGTON, DC 20555-0001 June 16, 2011 NRC INFORMATION NOTICE 2011-12: REACTOR TRIPS RESULTING FROM WATER INTRUSION INTO

More information

Experience from fire sprinkler tests in a shuttle storage system

Experience from fire sprinkler tests in a shuttle storage system Global Research Update: High Challenge Storage Protection, May 22, 2014, London, England Experience from fire sprinkler tests in a shuttle storage system Magnus Arvidson Fire Research SP Technical Research

More information

EFSN Training i Module 1. 90 Minutes

EFSN Training i Module 1. 90 Minutes Introduction to Sprinklers EFSN Training i Module 1 90 Minutes Topics How sprinklers work Performance of sprinkler systems Types of Sprinkler Introduction to sprinkler systems Introduction ti to sprinkler

More information

TOBY DVR5 OIL CONTROL & SAFETY VALVE

TOBY DVR5 OIL CONTROL & SAFETY VALVE TOBY DVR5 OIL CONTROL & SAFETY VALVE TECHNICAL HANDBOOK Principle of Operation The Toby DVR5 Oil Control Valve is a multi function unit for maintaining a constant oil level, regulating the oil flow and

More information

FIVE YEAR CERTIFICATION REPORT

FIVE YEAR CERTIFICATION REPORT GARDEN GROVE FIRE DEPARTMENT FIRE PREVENTION DIVISION FIVE YEAR CERTIFICATION REPORT Service and maintenance report of automatic fire extinguishing systems, including fire sprinklers, dry, deluge, and

More information

Competency Framework for Marine Engineer Class 6. Competency Framework for Marine Engineer Class 6

Competency Framework for Marine Engineer Class 6. Competency Framework for Marine Engineer Class 6 Table of Contents (MEC 6)... 1 Function: Operate Vessel Machinery and Systems... 1 Diesel engines.... 1 Operational procedures.... 3 Operate and monitor a vessel s engines and auxiliary equipment.... 4

More information

Air Conditioner Water Heater - A Product of HotSpot Energy LLC

Air Conditioner Water Heater - A Product of HotSpot Energy LLC Air Conditioner Water Heater - A Product of HotSpot Energy LLC PLEASE READ THIS BEFORE YOU INSTALL THE UNIT 1. This air conditioner must be installed and/or repaired by a qualified technician. If you perform

More information

Electric Fryers Instruction Manual Models: 8047D, 8048D, 8049D, 8050D, 8051D 8066, 8068, 8068FL, 8073, 8073BF and 8075

Electric Fryers Instruction Manual Models: 8047D, 8048D, 8049D, 8050D, 8051D 8066, 8068, 8068FL, 8073, 8073BF and 8075 Part No. 89047 Electric Fryers Instruction Manual Models: 8047D, 8048D, 8049D, 8050D, 8051D 8066, 8068, 8068FL, 8073, 8073BF and 8075 Cincinnati, OH 45241-4807 USA ELECTRIC FRYER SAFETY PRECAUTIONS Installation

More information

CASE STUDY 1 COMMISSIONING A GAS FIRED STEAM BOILER

CASE STUDY 1 COMMISSIONING A GAS FIRED STEAM BOILER CASE STUDY 1 COMMISSIONING A GAS FIRED STEAM BOILER A steam boiler has been built and installed at a factory for the provision of process steam. The following lists the requirements used in the commissioning

More information

ENGINEERING SPECIFICATION. Engineering Specification SAPPHIRE 42 Bar

ENGINEERING SPECIFICATION. Engineering Specification SAPPHIRE 42 Bar Engineering Specification SAPPHIRE 42 Bar PART 1 GENERAL 1.1 DESCRIPTION OF WORK This specification outlines the requirements for a "Total Flood" SAPPHIRE Clean Agent Fire Suppression System. The work

More information

Nuclear Design Practices and the Case of Loviisa 3

Nuclear Design Practices and the Case of Loviisa 3 Nuclear Design Practices and the Case of Loviisa 3 Harri Tuomisto Fortum Power, Finland Third Nuclear Power School, 20-22 October 2010, Gdańsk, Poland 22 October 2010 Harri Tuomisto 1 Objectives The objective

More information

TYPICAL FIRE SAFETY INSPECTION VIOLATIONS

TYPICAL FIRE SAFETY INSPECTION VIOLATIONS TYPICAL FIRE SAFETY INSPECTION VIOLATIONS The following is a list of typical violations often found by inspectors and a generic solution. You can use this list to improve the safety of your facility, to

More information

MISSISSIPPI INSTITUTIONS OF HIGHER LEARNING OFFICE OF RISK MANAGEMENT ANNUAL BUILDING FIRE INSPECTION REPORT

MISSISSIPPI INSTITUTIONS OF HIGHER LEARNING OFFICE OF RISK MANAGEMENT ANNUAL BUILDING FIRE INSPECTION REPORT MISSISSIPPI INSTITUTIONS OF HIGHER LEARNING OFFICE OF RISK MANAGEMENT ANNUAL BUILDING FIRE INSPECTION REPORT Date of Inspection: University: Building: Address: Contact Person: Phone number: This inspection

More information

Inspection, Testing and Preventive Maintenance

Inspection, Testing and Preventive Maintenance Fire Protection Systems and Equipment Introduction HSB Professional Loss Control Two Crossroads Drive Bedminster, NJ 07921 1-800-472-1866 www.hsbplc.com The owners and operators of industrial plants, shopping

More information

Environment of Care Fire Safety Management Plan 2014

Environment of Care Fire Safety Management Plan 2014 Environment of Care Fire Safety Management Plan 2014 Updated 4.29.2014 PURPOSE The purpose of the Fire Safety Management Plan is to ensure that all facilities are designed, constructed, maintained, and

More information

Diesel Power Plant. - Arrangement - Equipment - Advantages & disadvantages

Diesel Power Plant. - Arrangement - Equipment - Advantages & disadvantages Diesel Power Plant - Arrangement - Equipment - Advantages & disadvantages Intake air filter Diesel Engine Fuel injection pump Filter Oil pump Storage tank Schematic arrangement of Diesel Power Plant Equipment

More information

DIESEL ENGINE DRIVEN POWER PLANTS CERTIFICATION, TESTING AND INSPECTION

DIESEL ENGINE DRIVEN POWER PLANTS CERTIFICATION, TESTING AND INSPECTION STANDARDS FOR CERTIFICATION No. 2.10 DIESEL ENGINE DRIVEN POWER PLANTS CERTIFICATION, TESTING AND INSPECTION JULY 1991 DETNORSKE VERITAS Veritasveien 1, N-1322 Høvik, Norway Tel.: +47 67 57 99 00 Fax:

More information

Copyright 2011 S&S Sprinklers All Rights Reserved. Family Honesty Integrity Spiritual Growth Fairness Teamwork

Copyright 2011 S&S Sprinklers All Rights Reserved. Family Honesty Integrity Spiritual Growth Fairness Teamwork Copyright 2011 S&S Sprinklers All Rights Reserved Family Honesty Integrity Spiritual Growth Fairness Teamwork AUTOMATIC SPRINKLERS Wet, Dry, Pre-Action & Deluge Sprinkler Systems Foam Systems Standpipes

More information

ENGINEERING SPECIFICATIONS FOR CO2 EXTINGUISHING AGENT PRE-ENGINEERED FIRE SUPPRESSION SYSTEMS

ENGINEERING SPECIFICATIONS FOR CO2 EXTINGUISHING AGENT PRE-ENGINEERED FIRE SUPPRESSION SYSTEMS ENGINEERING SPECIFICATIONS FOR CO2 EXTINGUISHING AGENT PRE-ENGINEERED FIRE SUPPRESSION SYSTEMS SECTION 1 GENERAL SPECIFICATIONS I. SCOPE This specification outlines the requirements for a pre-engineered

More information

MOBILE FIRE - RESCUE DEPARTMENT FIRE CODE ADMINISTRATION

MOBILE FIRE - RESCUE DEPARTMENT FIRE CODE ADMINISTRATION MOBILE FIRE - RESCUE DEPARTMENT FIRE CODE ADMINISTRATION Fire Pump Plan Review 2009 International Fire Code and NFPA 20 Date of Review / / BLD201 - Project Address: Project Name: Contractor s Business

More information

ESTIMATING FIRE PROTECTION WATER DEMANDS

ESTIMATING FIRE PROTECTION WATER DEMANDS GAP.14.1.1.0 A Publication of Global Asset Protection Services LLC ESTIMATING FIRE PROTECTION WATER DEMANDS INTRODUCTION What constitutes an adequate water supply has generated much discussion over the

More information

Design of electrical power system for a 1000MW nuclear power generating station

Design of electrical power system for a 1000MW nuclear power generating station Design of electrical power system for a 1000MW nuclear power generating station K Raja, K Yesunadam Dept. of Electrical & Electronics Engineering, Lingaya s Institute of Management & Technology, Vijayawada,

More information

Notes. Material 1. Appropriate Flammable Liquids

Notes. Material 1. Appropriate Flammable Liquids 29 CFR 1910.106 Flammable Materials Flammable Liquids Preparation 1. Read Applicable Background information and related Company Policy Chapter. 2. Make Copies of this Lesson Plan for Personnel 3. Make

More information

NFPA 91 1999 Edition. 2.1.9 Fire dampers shall be permitted to be installed in exhaust systems in the following situations:

NFPA 91 1999 Edition. 2.1.9 Fire dampers shall be permitted to be installed in exhaust systems in the following situations: NFPA 91 1999 Edition 2.1.9 Fire dampers shall be permitted to be installed in exhaust systems in the following situations: 1) Where ducts pass through fire barriers (2) Where a collection system installed

More information