Fire Protection Program Of Chashma Nuclear Power Generating Station Pakistan Atomic Energy Commission 5/28/2015 1
|
|
- Magdalene Whitehead
- 8 years ago
- Views:
Transcription
1 Fire Protection Program Of Chashma Nuclear Power Generating Station Pakistan Atomic Energy Commission 5/28/2015 1
2 Nuclear Power in Pakistan Nuclear Power Plants Capacity (MWe) Year of Commissioning In Operation KANUPP (PHWR) 137/ CHASNUPP-1 (PWR) CHASNUPP-2 (PWR) Under-construction CHASNUPP-3 (PWR) CHASNUPP-4 (PWR) /28/2015 2
3 IRAN Location of NPPs TAJIKISTAN CHINA C1/C2/C3/C4 KANUPP 5/28/2015 3
4 Plants Design / Specifications of CNPGS Reactor Type Rated Thermal Power Gross Electrical Output Net Electrical Output PWR, 2 Loop MW th 325 MWe 300 MWe Operating Pressure Operating Temperature 15.2 MPa o C Net Efficiency ~34 % 4
5 Elements of Fire Protection Program Design Codes and Standards Principles of Fire Protection Fire protection policy Fire Fighting Strategy Manual Fire Fighting Fire Prevention plan IAEA Expert Review Missions Fire Events Review at CNPGS On-going Issues Improvement plan 5/28/2015 5
6 Principles of Fire Protection Defense in Depth criteria will ensure throughout plant lifetime following objectives: Preventing fires from starting Detecting and Extinguishing quickly those fires which do starts, thus limiting the damage Preventing the spread of fires which have not been extinguished, thus minimizing their effects on essential plant functions Ensuring that fire will not prevent the performance of necessary plant safe shut down functions and will not significantly increase radioactive release to the environment 5/28/2015 7
7 Fire Protection Policy Protection of Structures, Systems & Components Fire prevention Use of non combustible material in construction and non combustible /fire resistant equipments / cables Transient Combustible Control Control of Ignition Source Fire Detection Provision of State of the Art Plant Fire Detection and Alarm system Fire fighting Systems A combination of Auto Actuated and Manual Fire Fighting Systems 5/28/2015 8
8 Fire Protection Policy Preventing the Spread of Fire 03 hours & 1.5 hours fire resistance rating fire compartment Redundant trains of safety systems Spatial separation of safety equipment Fire retardant Class 1E Electrical cables and Equipment Fire dampers in HVAC Ducts Implementation of Fire Barrier penetration seals Procedure Smoke Exhaust system for important plant areas (MCR, 6 kv panel rooms) 5/28/2015 9
9 Fire Fighting Strategy Fire Water Suppression systems includes: Four 50% capacity fire water supply pumps Two 100% Fire Water Pools Independent pneumatic pressurizer pumps & tanks Pressurized fire water main supplies to Spray & Sprinkler System, pre-action deluge system and fire hydrants Auto actuated Deluge valve protect cable shafts, cable spreading areas, Charging pumps, lube oil tanks, Turbine Generator bearings and main transformers. Fixed CO 2 fire extinguishing system protect Emergency Diesel Generators and Auxiliary feed water Diesel Driven Pumps & tanks in Nuclear Auxiliary building Fixed foam system protect Diesel fuel oil tanks at EDG building 5/28/
10 Manual Fire Fighting Fire hydrants covers all areas inside and outside the plant buildings More than 1400 portable fire extinguishers at about 400 fire points Plant operation staff trained in fire fighting serve as first responder to fire in plant Plant on-site Fire Brigade is equipped with 4 Fire Tenders, more than 40 professional fire fighting staff and equipment Perform Round the Clock shift duty Equipment in Fire Tenders - hose pipes, Multi-jet Nozzles, Special Safety Shoes, Fire Resistant Suits, Fire Helmets, Emergency Communication equipment, Flash Lights, Self Contained Breathing Apparatus, CO filters, Full Face Masks, Fire Extinguishers etc. 5/28/
11 Fire Prevention Plan Conduct of Transient Combustible Control inspection every month Control of ignition sources through administrative procedures Control of Hot work through work permit /fire watch Conduct of Fire drills regularly to verify the preparedness of operator and fire fighting staff Imparted training in fire fighting to other plant personnel Close collaboration with off site fire brigade 5/28/
12 Fire Prevention plan Emergency plans are available for the proper response to all potential site fires, particularly nuclear safety-related areas and equipment. Plans contains safety-related areas and equipment layout, fire hazards, fire protection equipment and fire detector type and location Respond to fire alarms Notification to emergency response teams (e.g., onsite fire brigade, off-site fire department) Coordination with operations and security personnel Fire-fighting techniques Response to potential radiological hazards. 5/28/
13 IAEA Fire Protection Mission to C-1 IAEA Pre OSART Review Mission of Chashma NPP Unit-1 was conducted in 1999 and recommended Review Mission on Fire Protection. IAEA Experts Review Mission on Fire Protection of Chashma NPP Unit-1 was conducted from 8 to 12 Nov 1999 prior to initial core loading. Overall fire protection program in the light of FSAR and FHA was reviewed. 12 Recommendations and 17 Observations were recommended in the mission final report Mission s recommendations and observations were implemented in due time and made the fire protection requirements at par with FSAR and FHA 5/28/
14 IAEA Fire Training Follow-up Mission IAEA Experts Fire Training Mission from 11 to 14 April 2000 was conducted at Chashma NPP Unit participants from Operation, Maintenance, Health Physics & Technical Divisions participated. Various plant fire protection procedures were developed as result of the training mission. 5/28/
15 IAEA OSART Mission IAEA OSART Review Mission on Unit-1 was conducted in 2004 Mission gave 3 recommendations on Fire protection program Resolution of issues were verified during OSART follow-up mission in FHA was reviewed and validated during PSR conducted in /28/
16 Fire Events Review at CNPGS # Description Causes Corrective Action 1. Plant was in Mode B after fuel loading. On , under-water lights were switched ON to perform some work. These lights were left ON inadvertently. On water from spent fuel pool was transferred to FTC for some requirement. When water level decreased below set point, level switches of under-water lights switched off their respective lights except one due to malfunction of its level switch. A short circuit in the underwater light resulted in damage of the power cable insulation which resulted in the burning of 10 under water light cables, 07 floating switches cable, 03 under water light controllers, under water light camera cable. Direct Cause: Malfunction of the water level switch (controller) of an under water light and power supply circuit breaker. Root Cause: In-adequate work control and non existence of a procedure defining responsibilities of the operators /work Group for operation of underwater lights. Contributory Causes: In-adequate procedure for draining water from the spent fuel pools. Use of a single circuit breaker for two underwater lights. Incorporated instruction in the relevant procedure for the circuit breakers of all under water lights are to be switched off prior to start of draining water from the pools. Modified existing power supply circuit for the underwater lights so that each light has its own breaker of 6 Amps instead of a common 16 Amps for two. 5/28/
17 Fire Events Review at CNPGS # Description Causes Corrective Action 2. On , smoke alarm received in MCR from room NA 004. On surveillance by operator smoke / burning smell was observed from Incoming Breaker-B of MCC Panel. 3. On , Plant was at mode 4A. SRC heating and pressurization was in progress with RCP-B in operation. Operator observed smoke coming from near pump body. Fire alarms also gave fire alarm. MCR was informed and pump was stopped Loose joint of terminal of one phase of a power supply bus to the breaker caused heating of insulating material. No real fire develop. Soaked oil in insulation material ignited due to high temperature of SRC line i.e. 192ºC Terminal joints were replaced and were properly tightened. Pump was stopped. Fire was extinguished using portable fire extinguishers. Insulation was removed and leakage of oil was fixed. 5/28/
18 Fire Events Review at CNPGS # Description Causes Corrective Action On when plant was operating at full load smoke alarm annunciated in MCR from IPB (Insulated Phase Bus Bar) area at +8.0 m, underneath Main Generator at turbine building. Whereas after checking the area smoke and sparking was observed from carbon brushes of Main Generator. GCB was manually opened and reactor was manually tripped Direct Cause Smoke due to sparking from carbon brushes Contributory Causes Choking of the slanted ventilating holes of slip ring. Choking of ventilation ducts of carbon brush assembly. Root Cause Design inadequacy preventing effective monitoring of carbon brushes. - Replaced and repaired damaged parts. - Adjusted gaps between the slip rings and carbon brushes holders in the range of 1.5 mm to 3.5 mm as per vendor advice. - Cleaned ventilating holes of slip rings and inlet / outlet ventilation duct of carbon bushes assembly. - Marked the individual carbon brush holders in the carbon brush rigging. - Installed smoke detectors in generator cubical 5/28/
19 On Going Issues Obsolete electronic of Plant Fire Detection and Alarm System Maintenance issue of pneumatic fire detection piping net of Main, Auxiliary and Step down transformers Non availability of power supply to Fire alarm control panel under LOP / draining of back up battery. 5/28/
20 Improvement Plan of Fire Detection System Unit-1 Components and software of plant Fire Detection and alarm system are being upgraded in progress Transformer s pneumatic detection is being replaced with Automatic flame detectors will be done in RFO-10 To provide connection from emergency power supply to fire alarm control panels in MCR modification is under review Air sampling fire detectors are being installed inside electrical cabinets in NI will be done in RFO-10 5/28/
21 Any Question Please 5/28/
FIRE-FIGHTING DESIGN BRIEF REPORT
P a g e 1 SECTION 04 (Doc.No.A/DBR 001) FIRE-FIGHTING DESIGN BRIEF REPORT P a g e 2 1.0 SCOPE 2.0 STANDARDS AND CODES 3.0 TYPES OF SYSTEM PROPOSED 4.0 FIRE HYDRANT SYSTEM 5.0 AUTOMATIC SPRINKLER SYSTEM
More informationFACILITY FIRE PREVENTION AND EMERGENCY PREPAREDNESS INSPECTION CHECKLIST
FACILITY FIRE PREVENTION AND EMERGENCY PREPAREDNESS INSPECTION CHECKLIST Date of Inspection: Conducted by: Location: Reviewed by: Date of Review: Comments or additional corrective action taken as a result
More informationTrace Electric Trace Fire Protection
ELECTRIC AL FIRE PROTECTION ACTIVE IN THE FOLLOWING AREAS: Multi-Unit Residential Apartment Buildings Industrial Commercial Institutional & Long Term Care Facilities Trace Electric Trace Fire Protection
More informationFire Alarm System Standpipes Sprinkler Systems Fire Drills Commercial Cooking Hood and more
FIRE PROTECTION SYSTEMS Fire protection systems, measures and equipment are all related to the safety of the occupants and the protection of the property. As part of a building design and its intended
More informationLiberty Mutual Insurance RISK ENGINEERING PROCEDURE. REP 07 Incident Planning For external use
Liberty Mutual Insurance RISK ENGINEERING PROCEDURE REP 07 Incident Planning For external use Risk Engineering Procedure Incident Planning CONTENTS Page PURPOSE... 3 BACKGROUND... 4 INCIDENT PLANNING PREPARATION...
More informationTransformer Deluge Systems
Transformer Deluge Systems How Do Transformer Fires Ignite? Common causes of transformer failure: Weather-related events such as lightning Short circuits in electrical equipment The most common cause is
More informationPublished in the Official State Gazette (BOE) number 166 of July 10th 2009 [1]
Nuclear Safety Council Instruction number IS-22, of July 1st 2009, on safety requirements for the management of ageing and long-term operation of nuclear power plants Published in the Official State Gazette
More informationWinnipeg Fire Department Fire Prevention Branch
Winnipeg Fire Department Fire Prevention Branch Manitoba Fire Code Life-Safety Equipment Maintenance Requirements The Fire Prevention Branch of the Winnipeg Fire Department has prepared this document of
More informationTrouble Shooting. Pump
Trouble Shooting Pump Trouble Possible Cause Remedy Oil leaking in the area of water pump crankshaft Worn crankshaft seal, bad bearing, grooved shaft, or failure of retainer o-ring. Excessive play on crankshaft
More informationName Of Occupancy Date. Yes No Describe
FIRE PREVENTION INSPECTION CHECKLIST For Class A Occupancy (For Assembly Buildings, Bars, Restaurants, Gyms, Churches, Arenas, Theatres or wherever people gather) Name Of Occupancy Date Physical Address
More informationOntario Fire Code SECTION 5.13 DIP TANKS. Illustrated Commentary. Office of the Ontario Fire Marshal
Ontario Fire Code SECTION 5.13 DIP TANKS Illustrated Commentary Office of the Ontario Fire Marshal Dip Tanks Illustrated Commentary 1 5.13.1. Location 5.13.1.1. Dip tank operations involving flammable
More informationVehicle Fire Protection. An Ownerʼs Manual for ANSUL Fire Suppression/Detection Systems
Vehicle Fire Protection An Ownerʼs Manual for ANSUL Fire Suppression/Detection Systems 002792 Off-road vehicles do have fires Statistics show that off-road vehicles burn with alarming frequency. These
More informationNRC INSPECTION MANUAL
NRC INSPECTION MANUAL INSPECTION PROCEDURE 88055 NMSS/FCSS PROGRAM APPLICABILITY: 2600 FIRE PROTECTION (ANNUAL) 88055-01 INSPECTION OBJECTIVES 01.01 The objectives of this procedure are to evaluate the
More informationImportant Ontario Fire Code Information for Building Owners in the City of Windsor
Important Ontario Fire Code Information for Building Owners in the City of Windsor This information is intended to be used a reference only. For a complete listing consult the Ontario Fire Code or contact
More informationEvaluate, Clean, and Tune Guidance
Evaluate, Clean, and Tune Guidance The Evaluate, Clean and Tune (ECT) process serves three essential purposes in the Weatherization Assistance Program (WAP). The first is to evaluate the existing system
More informationMaintaining Fire Protection Systems
Maintaining Fire Protection Systems Fire continues to be a major threat to your business and your personal safety. Each year several thousand people are injured or killed by fires and billions of dollars
More informationRisk Engineering Guideline
www.hdi.global HDI Risk Consulting Risk Engineering Guideline Impairment of fire protection systems Basic protection systems should not be impaired without adequate replace compensation with provisions.
More informationALBERTA FIRE CODE SAFETY EQUIPMENT MAINTENANCE REQUIREMENTS
ALBERTA FIRE CODE SAFETY EQUIPMENT MAINTENANCE REQUIREMENTS In this document are the fire safety equipment maintenance requirements that are found in Division B of the Alberta Fire Code (AFC 2006) for
More informationNuclear power plant systems, structures and components and their safety classification. 1 General 3. 2 Safety classes 3. 3 Classification criteria 3
GUIDE 26 June 2000 YVL 2.1 Nuclear power plant systems, structures and components and their safety classification 1 General 3 2 Safety classes 3 3 Classification criteria 3 4 Assigning systems to safety
More informationFactory owners must ensure the boiler is:
Factory owners must ensure the boiler is: * Registered with the Boilers and Pressure Vessels Division, Labour Department * Examined by an appointed examiner and has a valid certificate of fitness * Supervised
More information26 3213.13 Diesel Engine Driven Generators Page 1 of 6
Last Update: December 8, 2014 A. Description of System Consultant s Handbook Page 1 of 6 1. Provide a diesel engine driven electric generating unit, factory assembled, tested and certified to operate at
More informationEXHIBIT A SCOPE OF WORK
EXHIBIT A SCOPE OF WORK 1. (Contractor) shall provide fire alarm system maintenance/repair/testing services as described herein to the California Department of Veterans Affairs (hereinafter CDVA, CalVet,
More informationRecommended Practice for Installation of Transit Vehicle Fire Protection Systems
Recommended Practice for Installation of Transit Vehicle Fire Protection Systems Approved October 25, 2007 APTA Fire Safety Working Group Approved May 3, 2008 APTA Bus Safety Committee Approved October
More informationCITY OF PHILADELPHIA DEPARTMENT OF LICENSES AND INSPECTIONS ANNUAL CERTIFICATION FOR FIRE ALARM SYSTEMS
CITY OF PHILADELPHIA DEPARTMENT OF LICENSES AND INSPECTIONS ANNUAL CERTIFICATION FOR FIRE ALARM SYSTEMS PROPERTY ADDRESS (BRT Address Required) TESTING CONTRACTOR (Name and Address) License No. ANNUAL
More informationFIRE RISK ASSESSMENT IN GERMANY - PROCEDURE, DATA, RESULTS -
International Conference Nuclear Energy in Central Europe 2000 Golf Hotel, Bled, Slovenia, September 11-14, 2000 FIRE RISK ASSESSMENT IN GERMANY - PROCEDURE, DATA, RESULTS - H.P. Berg Bundesamt für Strahlenschutz
More informationFull scale tunnel fire tests of VID Fire-Kill Low Pressure Water Mist Tunnel Fire Protection System in Runehamar test tunnel, spring 2009
Full scale tunnel fire tests of VID Fire-Kill Low Pressure Water Mist Tunnel Fire Protection System in Runehamar test tunnel, spring 2009 By Carsten Palle, VID Fire-Fill, www.vid.eu Presented at ISTSS
More informationHarris Nuclear Plant (HNP) NFPA 805 Transition. NFPA 805 Monitoring Program
Harris Nuclear Plant (HNP) NFPA 805 Transition NFPA 805 Monitoring Program Oconee / Harris NFPA 805 Pilot Observation Meeting April 14-16, 2008 Charlotte, NC Keith Began, CES/FP Review from Nov. 2007 Pilot
More informationAutomatic fire-extinguishing systems for commercial cooking
Automatic fire-extinguishing systems for commercial cooking Leading Items First Ignited in Eating and Drinking Establishment Structure Fires, 2000-2004 Annual Averages Cooking materials, incl. food and
More information(2) Various fire sections enclosed by various classes of fire divisions; (3) Arrangement of fire detectors and manual fire alarm stations;
(1979) (Rev.1 1990) (Rev.2 1996) (Rev.3 Jan 2012) Safety features.1 Fire protection and extinction.1.1 General Fire protection arrangements and fire extinguishing systems are to be in accordance with the
More informationHSE information sheet. Fire and explosion hazards in offshore gas turbines. Offshore Information Sheet No. 10/2008
HSE information sheet Fire and explosion hazards in offshore gas turbines Offshore Information Sheet No. 10/2008 Contents Introduction.. 2 Background of gas turbine incidents in the UK offshore sector...2
More informationProgram No. 1.6.1. Section Heading
ENVIRONMENTAL HEALTH AND SAFETY EHS PROGRAM MANUAL Program Title 1.0 INTRODUCTION The New York City Fire Department (FDNY) is responsible for approving and/or inspecting fire alarm systems, buildings,
More informationNuclear Power Plant Electrical Power Supply System Requirements
1 Nuclear Power Plant Electrical Power Supply System Requirements Željko Jurković, Krško NPP, zeljko.jurkovic@nek.si Abstract Various regulations and standards require from electrical power system of the
More informationOROT RABIN POWER STATION UNITS 1-4. 4 x 350 MW
ISRAEL ELECTRIC OROT RABIN POWER STATION UNITS 1-4 4 x 350 MW COAL BOILER CONVERSION TO LOW NO X NATURAL GAS AND COAL FIRING BY PRIMARY AND SECONDARY MEASURES INSTALLATION Replacing the Burner Management
More informationINDUSTRIAL POWER GENERATION EQUIPMENT Typhoon SGT-100 4.9 MW / 5340 KVA 50Hz 11KV Duel Fuel Power Station
D & S Turbine International LLC INDUSTRIAL POWER GENERATION EQUIPMENT Typhoon SGT-100 4.9 MW / 5340 KVA 50Hz 11KV Duel Fuel Power Station INDUSTRIAL POWER GENERATION EQUIPMENT Typhoon SGT-100 4.9 MW /
More informationALVERNIA UNIVERSITY OSHA REGULATION: 29 CFR 1910.252 WELDING, CUTTING, AND BRAZING ( HOT WORK ) SECTION: 3600
OSHA REGULATION: 9 CFR 90.5 WELDING, CUTTING, AND BRAZING ( HOT WORK ) A. POLICY. This procedure follows requirements set forth in 9 CFR 90.5.. This policy applies to all Hot Work operations being done
More informationCurrent as of 11/10/08 1 of 1
BEST PRACTICES STANDARDS FOR SCHOOLS UNDER CONSTRUCTION OR BEING PLANNED FOR CONSTRUCTION I. Site Layout A. School buildings shall be provided with a securable perimeter. A securable perimeter means that
More informationNMSU FIRE DEPARTMENT Commercial Kitchen Fire Suppression Worksheet
This Commercial Kitchen Automatic Fire has been created to assure all documentation has been submitted to assist you in assuring proper plans and documentations has been submitted and reviewed by New Mexico
More informationWASTE Application Form - Dublin Waste to Energy SECTION J ACCIDENT PREVENTION & EMERGENCY RESPONSE
SECTION J ACCIDENT PREVENTION & EMERGENCY RESPONSE Describe the existing or proposed measures, including emergency procedures, to minimise the impact on the environment of an accidental emission or spillage.
More informationUnit 1 Turbine Rotor 110 MW Replacement
Proceedings World Geothermal Congress 2015 Melbourne, Australia, 19-25 April 2015 Unit 1 Turbine Rotor 110 MW Replacement Amri Zein 1, Wahyu Mulyana 2 and Heribertus Dwiyudha 3 Star Energy Geothermal (Wayang
More informationFire Safety PROCEDURES January 2011
Fire Safety PROCEDURES January 2011 firesafety@uwo.ca Campus Phones EMERGENCY Dial 911 Fire Safety Service is the focal point for the coordinated administration of the University Fire Safety program and
More informationFire Safety Risk Assessment Checklist for Residential Care Premises
Checklist for Residential Care Premises Name of Premises: Address of Premises: Name of Responsible Person: What area / location does the assessment cover? Does the assessment cover the whole site YES or
More informationINSTRUCTIONS FOR BUILDINGS WITH FIRE PROTECTION EQUIPMENT
INSTRUCTIONS FOR BUILDINGS WITH FIRE PROTECTION EQUIPMENT FIRE EXTINGUISHERS,SPRINKLER SYSTEMS AND FIRE ALARMS Attachment #1 Inspection of Fire Extinguishers Fire Extinguishers must be tested according
More informationINSPECTION, TESTING AND MAINTENANCE OF FIRE PROTECTION SYSTEMS AND EQUIPMENT
CITY OF SPRING LAKE PARK Code Enforcement Department 1301 81 st Avenue NE Spring Lake Park MN 55432 Business Phone 763-784-6491 Fax 763-792-7257 INSPECTION, TESTING AND MAINTENANCE OF FIRE PROTECTION SYSTEMS
More informationFire Pump Plan Review March 2010
Fire Pump Plan Review March 2010 Date of Review: / / Permit Number: Business/Building Name: Address of Project: Designer Name: Designer s Phone: Contractor: Contractor s Phone: Occupancy Classification:
More informationBoiler & Pressure Vessel Inspection discrepancies and failures
Boiler & Pressure Vessel Inspection discrepancies and failures Water Heaters / Pressure Vessels Pressure Vessels are inspected once every three years. This requires a test of A: safety relief devices B:
More informationFIREFIGHTING AND DAMAGE CONTROL
FIREFIGHTING AND DAMAGE CONTROL Everyone on aboardship have another big job - to work aside from their primary duties. This big job is to look out constantly for the safety of the ship and crew. When the
More informationElements of the Russian Emergency Preparedness Program
Elements of the Russian Emergency Preparedness Program Randolph L. Sullivan, NRC National Radiological EP Conference St. Louis, Missouri March 2006 2 3 4 5 6 Volgodonsk NPP 1000 MWe VVER, a PWR Large Staff
More informationFire Alarm System Monitoring - CAN/ULC-S561-03
Fire Alarm System Monitoring - CAN/ULC-S561-03 Brian McBain ULC Regulatory Services May 4, 2011 Copyright 1995-2007 Underwriters' Laboratories of Canada. All rights reserved. No portion of this material
More informationMARKEL AMERICAN INSURANCE COMPANY POWERBOAT SELF SURVEY EVALUATION FORM
Our records reflect that a Condition and Value survey is due for your boat. A Condition and Value survey performed by a competent marine surveyor is the best way to determine if there are any defects or
More informationMISCELLANEOUS ELECTRICAL JOBS REQUIRING PERMITS
MISCELLANEOUS ELECTRICAL JOBS REQUIRING PERMITS 01. SAFETY INSPECTION of service equipment at FPL Power Source 02. Construction GFI power outlets (Temp Pole for Construction) 03. 90 day temporary power
More informationRisk Assessment and Disaster Management Plan The Risk Assessment Study for the upcoming industrial area project of M/s. RIICO Ltd. has been conducted
Risk Assessment and Disaster Management Plan The Risk Assessment Study for the upcoming industrial area project of M/s. RIICO Ltd. has been conducted by functional area expert of EIA Team. The risk assessment
More informationANNUAL FIRE PROTECTION SUMMARY INFORMATION REPORTING GUIDE Revised: May 2011
ANNUAL FIRE PROTECTION SUMMARY INFORMATION REPORTING GUIDE Revised: May 2011 Organizations responsible for maintaining property under stewardship of DOE and the Administrator, NNSA, will seek concurrence
More information1. Fire Safety Policy and Responsibilities. Consult the Employer s Fire Safety Policy and establish responsibilities of staff for fire safety.
Management Checklist 1. Fire Safety Policy and Responsibilities. Consult the Employer s Fire Safety Policy and establish responsibilities of staff for fire safety. 2. Fire Hazard and Risk Assessment. Use
More informationFLORIDA ATLANTIC UNIVERSITY FIRE ALARM SYSTEM INSTALLATION MANUAL
FLORIDA ATLANTIC UNIVERSITY FIRE ALARM SYSTEM INSTALLATION MANUAL January, 2003 Environmental Health and Safety Florida Atlantic University 777 Glades Rd. Boca Raton, FL 33431 Phone: 561-297-3129 Fax:
More information9.4 Air Conditioning, Heating, Cooling and Ventilating Systems
9.4 Air Conditioning, Heating, Cooling and Ventilating Systems 9.4.1 Control Building HVAC The Control Building (C/B) Heating, Ventilating and Air-Conditioning (HVAC) System is divided into two separate
More informationDennis Fire Department Fire Prevention Mark Dellner Fire Chief
Dennis Fire Department Fire Prevention Mark Dellner Fire Chief FIRE SAFETY INSPECTION GUIDELINES FOR COMMERCIAL PROPERTIES (MA Fire Prevention Regulations 527 CMR, MGL Chapter 148) FIRE PREVENTION CHECKLIST-
More informationElectric Fryers Instruction Manual Models: 8047D, 8048D, 8049D, 8050D, 8051D 8066, 8068, 8068FL, 8073, 8073BF and 8075
Part No. 89047 Electric Fryers Instruction Manual Models: 8047D, 8048D, 8049D, 8050D, 8051D 8066, 8068, 8068FL, 8073, 8073BF and 8075 Cincinnati, OH 45241-4807 USA ELECTRIC FRYER SAFETY PRECAUTIONS Installation
More informationSafe Operating Procedure
Safe Operating Procedure (Revised 07/09) HOT WORK PERMIT OPERATIONS (For assistance, please contact EHS at (402) 472-4925, or visit our web site at http://ehs.unl.edu/) Authority In recognition of the
More informationGeneral Fire Code Requirements Within Commercial Tenant Spaces
FIRE DEPARTMENT in cooperation with Scope: General Fire Code Requirements Within Commercial Tenant Spaces This handout is designed to assist owners, architects, contractors and others in understanding
More informationMOTOR FUEL DISPENSING SAFETY
STRATEGIC OUTCOMES PRACTICE TECHNICAL ADVISORY BULLETIN January 2010 MOTOR FUEL DISPENSING SAFETY Fire! Not an alarm anyone wants to hear, especially not when the fire is burning at a major fuel source.
More informationSIOUX HYBRID WATER HEATER
SIOUX Hybrid Water Heater for the Concrete Industry SIOUX HYBRID WATER HEATER Patent Pending Maximizing the Benefits of Coil and Direct-Fired Heating Technologies Higher Discharge Temperature True High-Efficiency
More informationENGINEERING SPECIFICATION. Engineering Specification SAPPHIRE 42 Bar
Engineering Specification SAPPHIRE 42 Bar PART 1 GENERAL 1.1 DESCRIPTION OF WORK This specification outlines the requirements for a "Total Flood" SAPPHIRE Clean Agent Fire Suppression System. The work
More informationAir Conditioner Water Heater - A Product of HotSpot Energy LLC
Air Conditioner Water Heater - A Product of HotSpot Energy LLC PLEASE READ THIS BEFORE YOU INSTALL THE UNIT 1. This air conditioner must be installed and/or repaired by a qualified technician. If you perform
More informationFIVE YEAR CERTIFICATION REPORT
GARDEN GROVE FIRE DEPARTMENT FIRE PREVENTION DIVISION FIVE YEAR CERTIFICATION REPORT Service and maintenance report of automatic fire extinguishing systems, including fire sprinklers, dry, deluge, and
More informationEFSN Training i Module 1. 90 Minutes
Introduction to Sprinklers EFSN Training i Module 1 90 Minutes Topics How sprinklers work Performance of sprinkler systems Types of Sprinkler Introduction to sprinkler systems Introduction ti to sprinkler
More informationNFPA 91 1999 Edition. 2.1.9 Fire dampers shall be permitted to be installed in exhaust systems in the following situations:
NFPA 91 1999 Edition 2.1.9 Fire dampers shall be permitted to be installed in exhaust systems in the following situations: 1) Where ducts pass through fire barriers (2) Where a collection system installed
More informationConsortiwm Awdurdodau Lleol Cymru Consortium Local Authorities Wales
Consortiwm Awdurdodau Lleol Cymru Consortium Local Authorities Wales SPECIFICATION FOR BOILER SERVICING MAINTENANCE Maintenance Module 11 March 2012 issue This document has been compiled by the Engineering
More informationLoviisa 3 unique possibility for large scale CHP generation and CO 2 reductions. Nici Bergroth, Fortum Oyj FORS-seminar 26.11.
Loviisa 3 unique possibility for large scale CHP generation and CO 2 reductions Nici Bergroth, Fortum Oyj FORS-seminar 26.11.2009, Otaniemi Loviisa 3 CHP Basis for the Loviisa 3 CHP alternative Replacement
More informationCompetency Framework for Marine Engineer Class 6. Competency Framework for Marine Engineer Class 6
Table of Contents (MEC 6)... 1 Function: Operate Vessel Machinery and Systems... 1 Diesel engines.... 1 Operational procedures.... 3 Operate and monitor a vessel s engines and auxiliary equipment.... 4
More informationTOBY DVR5 OIL CONTROL & SAFETY VALVE
TOBY DVR5 OIL CONTROL & SAFETY VALVE TECHNICAL HANDBOOK Principle of Operation The Toby DVR5 Oil Control Valve is a multi function unit for maintaining a constant oil level, regulating the oil flow and
More informationInspection, Testing and Preventive Maintenance
Fire Protection Systems and Equipment Introduction HSB Professional Loss Control Two Crossroads Drive Bedminster, NJ 07921 1-800-472-1866 www.hsbplc.com The owners and operators of industrial plants, shopping
More informationENGINEERING SPECIFICATIONS FOR CO2 EXTINGUISHING AGENT PRE-ENGINEERED FIRE SUPPRESSION SYSTEMS
ENGINEERING SPECIFICATIONS FOR CO2 EXTINGUISHING AGENT PRE-ENGINEERED FIRE SUPPRESSION SYSTEMS SECTION 1 GENERAL SPECIFICATIONS I. SCOPE This specification outlines the requirements for a pre-engineered
More informationEthanol Vehicle and Infrastructure Codes and Standards Citations
Ethanol Vehicle and Infrastructure Codes and Standards Citations This document lists codes and standards typically used for U.S. ethanol vehicle and infrastructure projects. To determine which codes and
More informationFIRE SPRINKLER DEMONSTRATION TRAILER
IFIA FIRE SPRINKLER DEMONSTRATION TRAILER Recommendations for utilizing the fire sprinkler demonstration trailer in your fire department, business or association: INDEX: A) Picking up and towing the Trailer.
More informationCopyright 2011 S&S Sprinklers All Rights Reserved. Family Honesty Integrity Spiritual Growth Fairness Teamwork
Copyright 2011 S&S Sprinklers All Rights Reserved Family Honesty Integrity Spiritual Growth Fairness Teamwork AUTOMATIC SPRINKLERS Wet, Dry, Pre-Action & Deluge Sprinkler Systems Foam Systems Standpipes
More informationJoin the UK Nuclear Renaissance. Procurement & Quality Process
Join the UK Nuclear Renaissance Procurement & Quality Process 1 AREVA NP UK Supplier Day, March 16th Birmingham EPR is a trademark of the AREVA Group 1 The Process: AREVA Supply Chain Strategy Didier David
More informationTYPICAL FIRE SAFETY INSPECTION VIOLATIONS
TYPICAL FIRE SAFETY INSPECTION VIOLATIONS The following is a list of typical violations often found by inspectors and a generic solution. You can use this list to improve the safety of your facility, to
More informationMOBILE FIRE - RESCUE DEPARTMENT FIRE CODE ADMINISTRATION
MOBILE FIRE - RESCUE DEPARTMENT FIRE CODE ADMINISTRATION Fire Pump Plan Review 2009 International Fire Code and NFPA 20 Date of Review / / BLD201 - Project Address: Project Name: Contractor s Business
More informationNotes. Material 1. Appropriate Flammable Liquids
29 CFR 1910.106 Flammable Materials Flammable Liquids Preparation 1. Read Applicable Background information and related Company Policy Chapter. 2. Make Copies of this Lesson Plan for Personnel 3. Make
More informationManual Document Page Issue Date TABLE OF CONTENTS
, Manual USQ #15-1163-D ESHQ 1 of 23 TABLE OF CONTENTS 1.0 PURPOSE AND SCOPE... 2 2.0 IMPLEMENTATION... 2 3.0 STANDARD... 2 3.1 Facility Management Support Requirements... 3 3.2 Fire System Discrepancy
More informationProtecting Your School from Fire and Weather Related Losses
Protecting Your School from Fire and Weather Related Losses Allianz Ireland s Leading School Insurer Protecting Schools since 1902 Our Policyi The most complete and appropriate insurance arrangement for
More informationUNITED STATES NUCLEAR REGULATORY COMMISSION OFFICE OF NUCLEAR REACTOR REGULATION WASHINGTON, DC 20555-0001. June 16, 2011
UNITED STATES NUCLEAR REGULATORY COMMISSION OFFICE OF NUCLEAR REACTOR REGULATION WASHINGTON, DC 20555-0001 June 16, 2011 NRC INFORMATION NOTICE 2011-12: REACTOR TRIPS RESULTING FROM WATER INTRUSION INTO
More informationSECTION 16721 FIRE ALARM AND DETECTION SYSTEMS
SECTION 16721 FIRE ALARM AND DETECTION SYSTEMS The equipment requirements of this section apply to the IUB Campus. The IUPUI Campus has a preferred vendor agreement for fire alarm systems. Contact Pat
More informationSL280UHV SERIES GAS FURNACE WARNING
2010 Lennox Industries Inc. Dallas, Texas, USA 506677 01 11/2010 Supersedes 506409 01 SL280UHV SERIES GAS FURNACE Litho U.S.A. FIRE OR EXPLOSION HAZARD. Failure to follow safety warnings exactly could
More informationRESIDENTIAL HEATING OIL SERVICE CONTRACT ANNUAL COST $276.00
RESIDENTIAL HEATING OIL SERVICE CONTRACT This service contract covers all routine service and maintenance of your residential oil fired furnace or boiler. In addition this contract covers all service calls
More informationOur data centres have been awarded with ISO 27001:2005 standard for security management and ISO 9001:2008 standard for business quality management.
AIMS is Malaysia and South East Asia s leading carrier neutral data centre operator and managed services provider. We provide international class data storage and ancillary services, augmented by an unrivaled
More informationCOMMERCIAL COOKING HOODS, VENTILATION & FIRE SUPPRESSION SYSTEM GUIDELINES AND PROCEDURES
COMMERCIAL COOKING HOODS, VENTILATION & FIRE SUPPRESSION SYSTEM GUIDELINES AND PROCEDURES These guidelines are to be used for ALL commercial cooking hoods, ventilation systems and related fire suppression
More informationSECTION 16720 - FIRE AND SMOKE ALARM SYSTEM. City of San Diego, CWP Guidelines
PART 1 -- GENERAL 1.1 WORK OF THIS SECTION SECTION 16720 - City of San Diego, CWP Guidelines A. The WORK of this Section includes providing manual and automatic fire alarm and smoke detection systems meeting
More informationEnvironment of Care Fire Safety Management Plan 2014
Environment of Care Fire Safety Management Plan 2014 Updated 4.29.2014 PURPOSE The purpose of the Fire Safety Management Plan is to ensure that all facilities are designed, constructed, maintained, and
More informationOur data centres have been awarded with ISO 27001:2005 standard for security management and ISO 9001:2008 standard for business quality management.
AIMS is Malaysia and South East Asia s leading carrier neutral data centre operator and managed services provider. We provide international class data storage and ancillary services, augmented by an unrivaled
More informationNuclear Design Practices and the Case of Loviisa 3
Nuclear Design Practices and the Case of Loviisa 3 Harri Tuomisto Fortum Power, Finland Third Nuclear Power School, 20-22 October 2010, Gdańsk, Poland 22 October 2010 Harri Tuomisto 1 Objectives The objective
More informationANALYSIS OF FIRE HAZARD AND SAFETY REQUIREMENTS OF A SEA VESSEL ENGINE ROOMS
Journal of KONES Powertrain and Transport, Vol. 18, No. 011 ANALYSIS OF FIRE HAZARD AND SAFETY REQUIREMENTS OF A SEA VESSEL ENGINE ROOMS Adam Charchalis, Stefan Czy Gdynia Maritime University, Faculty
More informationBRANCH SOLUTION. Automatic fire extinguishing systems for paint spraying plants. Safe for certain.
BRANCH SOLUTION Automatic fire extinguishing systems for paint spraying plants Safe for certain. ISK IDENTIFYING With the extreme high degree of automation in painting technology, the risk of fire has
More information01-3 0000-00 6810-20 AIR CONDITIONING SYSTEM 1. FFH SPECIFICATION AIR CONDITIONING SYSTEM RODIUS 2004.09
0000-00 01-3 6810-20 1. FFH SPECIFICATION 01-4 0000-00 2. SYSTEM LAYOUT AND COMPONENTS 0000-00 01-5 01-6 0000-00 3. FFH GENERAL INFORMATION The system is to increase the coolant temperature quickly by
More informationDELAWARE STATE FIRE MARSHAL FIRE ALARM SYSTEM CERTIFICATE OF INSTALLATION
Phone System Owner Phone System Engineered by: of Record Drawings: of System Manuals: of Test Reports: System Installer 1. GENERAL INFORMATION Phone Delaware License No: Certificate Holder No. System Supplier
More informationANCILLARY EQUIPMENT AND ELECTRICAL EQUIPMENT Power Supply Systems and Electrical Equipment for Desalination Plants - Y.M. Hamud and A.H.
POWER SUPPLY SYSTEMS AND ELECTRICAL EQUIPMENT FOR DESALINATION PLANTS Y.M. Hamud and A.H. Anwar Abu Dhabi Water and Electricity Authority, Abu Dhabi, UAE Keywords : Electrical System, Network for Desalination,
More informationDesign of electrical power system for a 1000MW nuclear power generating station
Design of electrical power system for a 1000MW nuclear power generating station K Raja, K Yesunadam Dept. of Electrical & Electronics Engineering, Lingaya s Institute of Management & Technology, Vijayawada,
More informationUCL FIRE RISK ASSESSMENT POLICY& ARRANGEMENTS
Fire Safety Technical Guide UCL FIRE RISK ASSESSMENT POLICY& ARRANGEMENTS 1.0. BACKGROUND 1.1. The Regulatory Reform (Fire Safety) Order (known Fire Safety Order) applies to England and Wales (Northern
More informationPLAN SUBMITTAL REQUIREMENTS FOR SPRAY BOOTHS AND SPRAYING ROOMS EXTINGUISHING SYSTEMS
January 1997 PLAN SUBMITTAL REQUIREMENTS FOR SPRAY BOOTHS AND SPRAYING ROOMS EXTINGUISHING SYSTEMS 1.0 PERMIT 1.1 After receipt of a Building Permit from the City of San Jose Building Department, submit
More informationCOMPREHENSIVE PROPERTY INSPECTIONS
COMPREHENSIVE PROPERTY INSPECTIONS Thank you for selecting CPI for your Deficiency Observation. A full home inspection was not performed on this property at the buyers request. This inspection is a limited
More information