Paralleling Switchgear
|
|
|
- Terence Holmes
- 10 years ago
- Views:
Transcription
1 Paralleling Switchgear By Maurice D Mello, P.Eng. Systems Engineer, GE Consumer & Industrial, Canada What is Paralleling? Paralleling is the operation in which multiple power sources, usually two or more generators, are synchronized and then connected to a common bus. Some applications require two or more generators to be paralleled with the Utility. The frequency, voltage, phase angle and phase rotation of all the sources must match within prescribed limits before they can be paralleled. Paralleling multiple sources provides increased reliability, flexibility in load management, uninterruptible maintenance and cost savings during peak rate incentive periods. Multiple generators paralleled to a common bus better serve critical loads. The first generator that reaches the preset operating parameters will power the critical loads with the remaining generators synchronizing and then picking up the lower priority loads. Load management schemes are easier to manage when load demands match the individual generator capacities. It is easy to take one generator off line for maintenance and let the others pick up the slack, especially if a N+1 configuration was adopted. Generators run at their highest efficiency when near full load. Lightly loaded generators are prone to wet stacking where the temperature at which the engine runs is not high enough to efficiently burn all the fuel, resulting in un-burnt fuel being deposited in the exhaust system. What is Paralleling Switchgear? Paralleling Switchgear (PSG) is a combination of protection, metering, control and switching elements acting as an integrated system to control the distribution of power for the following systems; Emergency Systems. Legally required standby Systems. Critical Operation Power Systems (COPS). Optional Standby Systems (emergency transfer and load management systems). In the first three types of systems, all generators start on a utility power failure. As there is no Utility circuit in the Paralleling Switchgear, an Engine Start signal must be sent from the Utility switchgear to the Paralleling Switchgear. The first generator that reaches close to the rated voltage and frequency is connected to a dead bus without having to wait to synchronize and should normally be sized to provide at least power to the critical and life safety loads. For emergency systems this must occur within 10 seconds. A signal is sent to the transfer switch to transfer load to emergency power. The other generators can be synchronized to provide power to the lower priority loads. This must happen within 60 seconds. On return of utility power, most loads will open transition while others may close transition (max 100 msec) to utility power. This would require synchronizing of the two sources of power. Such systems typically consist of Paralleling Switchgear and automatic transfer switches (Fig 1). Paralleling Switchgear by Maurice D Mello 1 September 2008
2 Fig 1: Emergency/Standby/COPS The last type of system is normally a Parallel with Utility systems (also referred to as infinite bus systems). They are the most complex as they require not only the generators to be synchronized between themselves, but the generators must be synchronized with the utility. The generators and utility could be connected together for a short duration (momentary closed, less than 100 msec) or a somewhat longer duration (soft load/unload) or a sustained duration (maintained parallel with the utility, Cogen system). On receipt of an engine start signal, all engines start and the first generator that reaches near rated voltage and frequency is connected to the dead emergency bus. The utility circuit breaker would be opened and the generator main circuit breaker would close feeding the highest priority loads. Other generators would synchronize and connect to the emergency bus and the load management program would add more loads on the system. The master PLC will now receive demand load and on-line generator capacity information. Based on a preset minimum reserve capacity, it would adjust the number of generators to match the demand load or adjust the loads to match the on-line generating capacity. When the utility voltage returns, the generators would be synchronized with the utility and the loads would be gradually transferred back to the utility. When the generators are unloaded, the generator main circuit breaker and the generator circuit breakers are opened and the generators are allowed to run through the cool down period before being shut down. Such systems typically consist of Paralleling Switchgear and transfer switches for fine control of load management (Fig 2). Fig 2: Parallel with Utility Paralleling Switchgear by Maurice D Mello 2 September 2008
3 Parallel with Utility systems are brought on line even when the Utility voltage is available. It is called Peak Shaving and is done to avoid the high cost of peak demand charges. The system monitors the utility power usage and when Peak Demand Threshold is approached, they could do either of the following; On-Line Peak Shave the generators supply the excess power demand above the Peak Demand Threshold. The generators could have a wet stacking problem if the excess kw requirement is low as compared to the generator capacity. Non-critical loads could be shed to prevent this or the generators could be run at full capacity and the excess generated power could be provided back to the utility. Off-Line Peak Shave the generators supply all the power demand once the demand exceeds the Peak Demand Threshold. This method ensures that the generators are running at near full load. If the generating capacity is less than the load demand, the generators are run at full load and the balance demand is supplied by the utility. System testing is a very important requirement for emergency/standby systems. No-load testing is done, where the generators are started, synchronized and connected to the emergency bus without taking on load. This test will not have any effect on the load fed from the utility and can be scheduled to occur at regular intervals (Engine Exercise setting). On-load testing is done where the load is gradually transferred from the utility to the generators, run for a period of time and then transferred back to the utility. Some systems may have load banks for testing the generators and the system controls without impacting the load. Load banks are sometimes used to load the generators when the plant loads are not enough to prevent wet stacking. Prime Power systems are in a category by themselves as they are always on and are the only system supplying power to the site (also referred to as isolated bus system). They would consist of a Paralleling Switchgear but no transfer switches. What are the building blocks of Paralleling Switchgear? Paralleling Switchgear consists of breaker compartments and control compartments. These can be integrated into one line-up or separately installed. The latter is preferred in order to lower the arc flash hazard risk category (HRC). System operators spend most of their time near control compartments, which can be installed outside the arc flash boundary of the breaker compartments. Irrespective of the layout of the switchgear the following are the basic breaker compartment requirements for parallel with utility application; Utility Breaker Compartment breaker directly fed from utility source. Generator Breaker Compartment breaker directly fed from generator source. Tie Breaker Compartment breaker in-between similar source breakers. These could be utility tie or generator tie (optional). Generator Main Breaker Compartment breaker that ties the generator bus to the utility bus and is used for transfer control between the two sources. Feeder/Distribution Breaker Compartment breakers directly feeding loads or transfer switches. For Emergency, Standby and Prime Power applications there are no Utility and Generator Main breaker compartments. The following are the basic control compartments; Paralleling Switchgear by Maurice D Mello 3 September 2008
4 Master/System Control Compartment used for controlling the paralleling of generators, generator optimization, load add/shed, system status annunciation, user HMI and local transfer control. One required per system. Generator Control Compartment used for starting and stopping of generators, control of voltage, speed and output and provide annunciation of engine and generator status, alarms and shutdowns. One required per generator. Utility Control Compartment used for loading control between utility source and generator source, power management and providing transfer device status. One required per utility source. Mimic Panel used normally when needed to display system one line status when using a black and white OIP (Operator Interface Panel). This function is incorporated in the ACS (Automatic Control System), which is normally a 15 color touch screen HMI. Fig 3 shows a single line diagram of a Parallel to Utility system with two generators (Cogen application) Fig 3: Typical One Line Diagram Fig 4 shows how this single line diagram would be configured into an integrated switchgear lineup. Fig 4: Switchgear Layout for same SLD Paralleling Switchgear can be low voltage or medium voltage. They can be of switchboard construction, metal-enclosed construction or metal-clad construction. The applicable standards will depend on voltage and type of construction. Paralleling Switchgear by Maurice D Mello 4 September 2008
5 For low voltage PSG; UL891 For Dead-Front Switchboards. UL1558 and ANSI/IEEE C For Metal-Enclosed LV Power Circuit Breaker Switchgear. For medium voltage PSG; ANSI/IEEE C For Metal-Clad and Station Type Cubicle Switchgear. The equivalent Canadian standard for all the above is CSA C22.2 No. 31. What are the components of Paralleling Switchgear? Protection - The protection requirements for Paralleling Switchgear are dependent on the size of the generators and the required level of reliability of the system. Low voltage circuit breakers have built-in trip units and therefore provide all the protection for feeder circuits. Utility and generator circuits require more protection than what low voltage circuit breakers can provide. They have to be provided with separate protective relays. Special selectivity considerations are required when applying LV circuit breakers in conjunction with protective relays, to generator and utility circuits. Generators would normally require the following protective functions as indicated by ANSI device numbers 25, 27, 32, 40, 46, 49, 50P, 50/51G, 51V, 59, 67G, 81O/U and 87G. 67G is also available for directional ground alarm. Recommended protection relay that meets all the above functions (except 25) is the GE Multilin SR489 Generator Protection System Relay. For combined generator transformer protection, a GE Multilin G30 relay is ideally suited. Large generators may require the GE Multilin G60 relay for proper protection. Utility circuits normally require the following protective functions 25, 27, 32, 47, 50/51P, 50/51G, 59, 67 and 81O/U. Recommended protection relay that meets all the above functions is the GE Multilin SR750 Feeder Protection System Relay. For high speed inter-tripping and communication, utility circuits may require a GE Multilin F60 relay. For feeder circuits in MV systems, the minimum requirement is 50/51P and 50/51G. The GE Multilin SR735 or MIFII provides all these functions. If metering is required on the feeders, a SR750 can be used. A GE Multilin F35 relay also provides protection and metering for up to 5 feeders in one relay. Load Management Load add/shed is controlled by the master PLC and is very important for the efficient operation of the engine-generators. Loads are divided into blocks by the number of generators in parallel and are also given sub-priorities. Loads are added/shed by pre-assigned priorities based on the available on-line capacity. Block shedding is done if a generator fails. Sub-priority load add/shed is done to prevent light loading of the generator. Block and priority settings are done through the ACS. Certain metered values are required for load management watts, watt demand, watt-hour and engine run time. SR489 and SR750 provide these metered values via analog signal and/or communication. For precise load management, a GE Multilin PQMII meter may be needed to provide metered values with higher accuracy. Loss of voltage and changes to frequency are captured by the SR750 and SR489 and are used by the Master PLC to transfer/re-transfer, add or shed loads. Engine run time information is used to even the usage of all generators. Generators can be sequentially or randomly loaded and unloaded based on this usage information. Paralleling Switchgear by Maurice D Mello 5 September 2008
6 Engine Control - There are two major engine/generator controls that are required by the Paralleling Switchgear for proper functioning: An Engine Governor Controller, controls the speed and output of the engine. Most major engine manufacturers have their own matched engine governor controller and prefer to mount it near the engine in the control cabinet. In these cases, the PLCs in the Paralleling Switchgear would only provide the enable signal and the engine governor controller would control the engine-generator. A Voltage Regulator, controls the voltage and the reactive power of the generator. They are most often mounted near the generator in the terminal box. Lastly, there is a need to have an automatic synchronizer to send control signals to the voltage regulator and engine governor controller to bring the generator into synchronism with the generator bus. This device is normally mounted in the Paralleling Switchgear and is shared between generators. Synchronizing switches are used to connect the synchronizing equipment to the correct line and load bus. Master Control - PLCs are the heart of the Paralleling Switchgear (Fig 5). In order to ensure reliability, the Paralleling Switchgear will have one PLC (GE Fanuc 90/30) per generator and one for the Master Control (GE Fanuc 90/70 or 90/30). All protective, metering, control and display devices are connected to the PLCs and the PLCs are daisy chained to each other. The Master PLC controls the transfer switches for load add/shed. The generator PLCs communicate with the engine/generator s controllers via specific gateways. If reliability needs to be enhanced, redundant Master PLC can be employed. Alternatively, complete manual control could be employed as backup for the PLC. Critical start/stop, alarm and shutdown signals can be hardwired to meet the requirements of NFPA 110. On master PLC failure, the generator PLC will Fig 5: Typical PLC Architecture provide the generator start signals, automatically synchronize all generators and connect the first priority loads. The lower priority loads will have to be connected manually. Paralleling Switchgear by Maurice D Mello 6 September 2008
7 HMI - A master HMI is provided on all Paralleling Switchgear. This can be a simple 5 black and white OIP or a 12, 15, 17, 19 or 42 high resolution, touch screen color ACS (Fig 6). Front views, single line diagrams and various other information and control screens can be incorporated in the ACS. OIPs may need a separate mimic panel to complete the visual display of the overall system. ACS will incorporate the mimic and provides the interface for control, option settings (time delays, transition mode selections etc), soft switching and load management. Advanced diagnostics such as fault monitoring, alarming, shutdown, event recording and trending can be done on the local ACS or even remotely. Some users prefer to have discrete meters such as ammeters, voltmeters, wattmeters etc. This option is normally selected with the OIP option. The ACS can provide this same information either in tabular format or as digitized analog meters on the screen. As the ACS is only an input device, failure of this device will not effect the switchgear operation. Redundant ACS or remote ACS can be provided as an option. Fig 6: ACS with Typical Screens Annunciators, (2x9 windows) can be provided for users that appreciate the standard annunciator displays or the ACS can have screens that depict the discrete annunciators and replicate the operation. 24VDC is provided to the Paralleling Switchgear from the best starting battery available and is controlled by an automatic 24VDC Control Voltage Sensor system. This system ensures a stable 24VDC supply. Fig 7: GE Paralleling Switchgear Conclusion - Paralleling Switchgear can be built as simple as possible with minimal control or as complex as possible with complete control, load management and redundancy. At the lower Paralleling Switchgear by Maurice D Mello 7 September 2008
8 end, hardwired relays are used but at the higher end, complete digital control is adopted. Redundancy is achieved by having hot synched PLCs in lieu of hardwired switches and meters. The trend is towards Digital Control as it can handle complex algorithms that enable multiple scenarios for load management and redundancy. It provides flexibility for system upgrades and enhancements. It also permits operational modifications to be done outside the equipment and then uploaded after complete testing. Digital controls have extensive diagnostics that can enhance reliability. Reference: Energy Commander TM Paralleling Switchgear- Application Guide. GE Consumer & Industrial, Power Quality TB Paralleling Switchgear by Maurice D Mello 8 September 2008
Suitable for Emergency, Peak and Prime Power System Applications. Low Voltage Automatic Transfer Switch Systems
Suitable for Emergency, Peak and Prime Power System Applications Low Voltage Automatic Transfer Switch Systems THE POWER AUTHORITY THE POWER AUTHORITY ASCO s experience and commitment to excellence in
SWITCHGEAR. EGP Switchgear
SWITCHEA EP Switchgear Cat generator set paralleling switchgear has been designed to integrate with Cat EMCP3 generator set controls. Now you can get greater efficiency, reliability and dependability all
FFI. Advances in Medium and Low Voltage Power Distribution ESS Metron Expo and Technical Seminars. Presented By: Greg Pelster & Robert Schmid
Advances in Medium and Low Voltage Power Distribution ESS Metron Expo and Technical Seminars Presented By: Greg Pelster & Robert Schmid FFI Ferrie, Franzmann Industries LOW VOLTAGE SWITCHGEAR & LOW VOLTAGE
PowerCommand Paralleling System Digital MasterControl
PowerCommand Paralleling System Digital MasterControl Description The PowerCommand Digital MasterControl is a systemlevel controller designed to interface directly with Cummins Power Generation PowerCommand
Gas Genset Controls. Genset Control Panel (GCP2) with PCS (PowerCommand Supervisor) Features. Description
Gas Genset Controls Genset Control Panel (GCP2) with PCS (PowerCommand Supervisor) Description The Cummins Power Genset Control Panel (GCP2) is an integrated monitoring and control system for the Cummins
Minimizing Impact of Electric Utility Outages with Backup Generation
Minimizing Impact of Electric Utility Outages with Backup Generation Introduction of the Speaker Michael Dempsey, PE Senior Electrical Engineer Carter & Burgess, Inc. Energy & Power Solutions Facility
TURBOtech srl. SED-635 Digital Excitation System. Industrial Electronics Sector FEATURES
SED-635 Digital Excitation System SED-635 is a complete excitation system capable of adapting to control synchronous generators of any size. The integration of the TOUCH SCREEN operator interface and a
QUESTIONS and ANSWERS RFB 745-15-9894, Metal Clad Switchgear and Power Control Room
QUESTIONS and ANSWERS RFB 745-15-9894, Metal Clad Switchgear and Power Control Room 1) When you click on the UTHSCSA Drawing the site takes you to the E-1 drawing no other. Will there be other drawings
Federal Wage System Job Grading Standards for Electric Power Controlling, 5407. Table of Contents
Federal Wage System Job Grading Standards for Electric Power Controlling, 5407 Table of Contents WORK COVERED... 2 WORK NOT COVERED...2 TITLES... 2 GRADE LEVELS... 2 SPECIAL ADDITIONAL RESPONSIBILITIES...
Switchgear and Metal-Enclosed Bus
Section 18 Switchgear and Metal-Enclosed Bus 180. SWITCHGEAR ASSEMBLIES 180A. General Requirements for All Switchgear. This rule covers general requirements for all switchgear. Examples of switchgear found
LTR Series Uninterruptible Power Systems 700 VA - 2.1 KVA. General Specification
08/17/12 Rev2 LTR Series General Specification 700 VA to 2.1 KVA 1.0 General LTR Series Uninterruptible Power Systems 700 VA - 2.1 KVA General Specification This specification describes the features and
Pow-R-Con Multi Function Control
37264 Pow-R-Con Multi Function Control Product Specification Product Specification 37264 Product Information DYNA Power Controls Pow-R-Con TM GENERAL The Barber-Colman Pow-R-Con TM represents an integrated
PMCS. Integrated Energy Management Solution. Unlock the Full Potential of Power Networks Through Integration. Complete Solution. Informed Decisions
PMCS Integrated Energy Management Solution Unlock the Full Potential of Power Networks Through Integration Power Management Control System (PMCS) is a highly customizable, fully integrated end-to-end Energy
Arc Terminator Active Arc-Resistant Switchgear
Arc Terminator Active Arc-Resistant Switchgear Increasing safety and productivity by extinguishing internal arcing faults within the switchgear. The Square D Arc Terminator from Schneider Electric offers
Inverter / Charger Installation General Operations and AC and DC Connections
Inverter / Charger Installation General Operations and AC and DC Connections The Inverter is just one piece. Sometimes, a tendency is to mount the inverter and batteries, and make it work It is better
30-120 3 Phase Modular Finally the benefits of Modular ups are for all
MUST 30-120 3 Phase Modular UPS Finally the benefits of Modular ups are for all MUST 30-120 MUST means Modular UPS System Three-phase MUST 30-120 is an uninterruptible power supply with double conversion
AUTOMATIC TRANSFER SWITCH. Changeover Type from 250A to 2500A
AUTOMATIC TRANSFER SWITCH Changeover Type from 250A to 2500A Table of Contents Preamble 1.1 Theoretical base 1.2 Selection the size of automatic transfer switch 1.3 Automatic transfer switch components
SWITCHGEAR SOLUTIONS FOR MISSION CRITICAL APPLICATIONS. Presented by SAI Advanced Power Solutions
SWITCHGEAR SOLUTIONS FOR MISSION CRITICAL APPLICATIONS POWER DISTRIBUTION RACKS IN A MISSION CRITICAL SYSTEM MODULES IN A MISSION CRITICAL SYSTEM UPS Convertor Main Inverter Load Battery BPC UPS & BATTERY
reliable company...caterpillar
The markets most reliable technology... from the industryʼs most reliable company...caterpillar Caterpillar switchgear with PowerLynx technology has been designed to integrate hand-inglove with Caterpillar
SOLARCARE SERIES PRODUCT AND APPLICATION GUIDE
SOLARCARE SERIES PRODUCT AND APPLICATION GUIDE for solar energy management LEATEC Delivering Solutions for Energy Management SOLAR ENERGY DATA CENTER BUILDING 4 to8 String Monitoring with 0.% Accuracy
NFPA 70E 2012 Rolls Out New Electrical Safety Requirements Affecting Data Centers
NFPA 70E 2012 Rolls Out New Electrical Safety Requirements Affecting Data Centers A market position paper from the experts in Business-Critical Continuity TM Executive Summary Electrocutions are the fourth
A Comparison of Contemporary Electrical Distribution Equipment Standards. San Francisco IEEE Industry Applications Society May 26, 2009
A Comparison of Contemporary Electrical Distribution Equipment Standards San Francisco IEEE Industry Applications Society May 26, 2009 What are Standards? Clearly defined performance characteristics Based
Circuit Breakers and Switchgear. Thomas Greer Director of Engineering TLG Services
Circuit Breakers and Switchgear Thomas Greer Director of Engineering TLG Services Presentation Outline Switchgear Definition Overcurrent Protection Devices Circuit Breaker Trip Curves and Coordination
INTRODUCTION TO SYNCHRONIZING AUTOMATIC SYNCHRONIZING CONSIDERATIONS AND APPLICATIONS
INTRODUCTION TO SYNCHRONIZING AUTOMATIC SYNCHRONIZING CONSIDERATIONS AND APPLICATIONS INTRODUCTION It is the intention of this presentation to provide an explanation of the automatic synchronizing process,
HYDRO-ELECTRIC POWER PLANTS
HYDRO-ELECTRIC POWER PLANTS SOLINA MYCZKOWCE ROŻNÓW Supervisory and control systems for Hydro-Electric Power Plants R E L I A B L E S O L U T I O N S O F A U T O M A T I O N S Y S T E M S Doc. No. ENPN007
Increased power protection with parallel UPS configurations
Increased power protection with parallel UPS configurations Making the selection between Centralized Bypass and Distributed Bypass systems Janne Paananen Application Engineer, Large Systems Group Eaton
Guidelines for ATS selection: How to choose the right transfer solution for your power application.
Power topic #7012 Technical information from Cummins Power Generation Inc. Guidelines for ATS selection: How to choose the right transfer solution for your power application. > White Paper By Gary Olson,
Critical-Power Automatic Transfer Systems Design and Application
Critical-Power Automatic Transfer Systems Design and Application Bill Brown, P.E., Jay Guditis, Square D Critical Power Competency Center 1. INTRODUCTION An important requirement of mission-critical electric
Switchgear Application Issues for Mission Critical Power Systems, Part One
Switchgear pplication Issues for Mission Critical Power Systems, Part One BSTRCT With the advent of high reliability data centers and telecommunication facilities, designers of commercial power face new
Reducing Energy Costs with Peak Shaving in Industrial Environments
Reducing Energy Costs with Peak Shaving in Industrial Environments Speaker : Phillip Yeung Asia Pacific Business Development Power Monitoring & Control Seminar 70SE01 1 Summary I. Introduction II. Monitoring
UNIVERSITY OF WASHINGTON Facilities Services Design Guide. Electrical. Switchboards. Basis of Design. Design Evaluation
Basis of Design This section applies to the design relating to low voltage switchboards. Design Criteria UW Class N1 facilities main switchboards shall be rear accessible. The main, tie and feeder breakers
Process Alarm Solutions
Process Alarm Solutions Reliable Supervision and Control www.selco.com SELCO flexible alarm panels for supervision and control SELCO provides efficient and reliable solutions for alarm monitoring of electrical
ELECTRICAL ENGINEERING DESIGN CRITERIA APPENDIX F
ELECTRICAL ENGINEERING DESIGN CRITERIA APPENDIX F TABLE OF CONTENTS Appendix F - Electrical Engineering Design Criteria F.1 Introduction...F-1 F.2 Codes and Standards...F-1 F.3 Switchyard and Transformers...F-1
OPTIMIZING POWER SYSTEM PROTECTION FOR MODERN DATA CENTERS
OPTIMIZING POWER SYSTEM PROTECTION FOR MODERN DATA CENTERS Data center power systems are constructed with a premium on reliability at a significant cost. The return on this investment is realized if it
Transfer Equipment Controls
Control Types Manual Transfer Switches Nonautomatic Transfer Switches Automatic Transfer Switches The type of control system for the transfer switch will vary depending on the type of switching equipment
TDMS Test & Data Management Software
Test & Data Management Software TDMS protective relays energy meters transducers power quality CT-VT-PT transformers ground grid circuit breakers batteries surge arresters The Integrated Testing Solution
REMOTE MONITORING AND CONTROL OF THE KAKKONDA GEOTHERMAL POWER PLANTS
REMOTE MONITORING AND CONTROL OF THE KAKKONDA GEOTHERMAL POWER PLANTS Shinji Nishikawa 1, Toshiyuki Takahashi 1, Takeshi Koi 1, and Katsuyoshi Yamada 2 1 Toshiba Corporation Power Systems & Services Company,
DORMA MODEL PS-406BB POWER SUPPLY INSTALLATION INSTRUCTIONS
Features: INSTALLATION Install in accordance with NFPA 70. DORMA MODEL PS-406BB POWER SUPPLY INSTALLATION INSTRUCTIONS Up to 1.95 Amps Load Capacity Class 2 Rated Outputs Overload, Over Voltage, and Short
Safety Requirements Specification Guideline
Safety Requirements Specification Comments on this report are gratefully received by Johan Hedberg at SP Swedish National Testing and Research Institute mailto:[email protected] -1- Summary Safety Requirement
Product Description Full Voltage Starting Electric Fire Pump Controllers FTA1000
Product Description Full Voltage Starting Electric Fire Pump Controllers FTA1000 Description Firetrol FTA1000 Full Voltage Fire Pump Controllers are intended for use with electric motor driven fi re pumps
Short Form Catalogue. Alarm Systems. Reliable Supervision and Control
Short Form Catalogue Alarm Systems Reliable Supervision and Control Alarm Monitors and Indicators The SELCO product range includes a number of alarm monitors and indicator panels for use in numerous applications.
Test & Data Management Software
Test & Data Management Software TDMS protective relays energy meters transducers power quality CT-VT-PT transformers ground grid circuit breakers batteries surge arresters The Integrated Testing Solution
UTILITIES DEPARTMENT NORTH CAMPUS DISASTER RECOVERY PLAN
Page 1 of 27 UTILITIES DEPARTMENT NORTH CAMPUS DISASTER RECOVERY PLAN Page 2 of 27 Table of Contents 1. OBJECTIVE... 4 2. SCOPE... 4 3. COMMUNICATION... 4 4. LOSS OF NATURAL GAS SUPPLY... 5 5. LOSS OF
AUTOMATIC TRANSFER SWITCH CONTROL UNIT OPERATOR S MANUAL
ATS-220 AUTOMATIC TRANSFER SWITCH CONTROL UNIT OPERATOR S MANUAL For Use in 208 to 240 Volts Single and 3 Phase ATS Systems With 110Volt AC or DC Control Motors and selenoids 4501 NW 27 ave Miami FL 33142
EnerVista Viewpoint Monitoring
EnerVista Viewpoint Monitoring Easy to Use Monitoring and Data Recording EnerVista Viewpoint Monitoring is an easy to setup, powerful and simple to use data monitoring and recording software application
How to reduce exposure to arc flash hazards
GE Energy Industrial Solutions How to reduce exposure to arc flash hazards Multiple solutions for new and existing facilities imagination at work Multiple Issues Today s power system engineer must not
DATA CENTER UNIQUE CHARACTERISTICS AND THE ROLE OF MEDIUM VOLTAGE VACUUM CIRCUIT BREAKERS
DATA CENTER UNIQUE CHARACTERISTICS AND THE ROLE OF MEDIUM VOLTAGE VACUUM CIRCUIT BREAKERS ABSTRACT Data Centers are a critical part of the world economic systems. Billions of electronic transactions happen
..OR How To Protect your 3-Phase Equipment Investment with 3-Phase Monitors from Time Mark...
..OR How To Protect your 3-Phase Equipment Investment with 3-Phase Monitors from Time Mark... TIME MARK CORPORATION 11440 EAST PINE STREET TULSA, OK 74116 USA tel 918 438-1220 fax 918 437-7584 www.time-mark.com
ORC TURBOGENERATOR TYPE CHP - Organic Rankine Cycle Turbogenerator fed by thermal oil, for the combined production of electric energy and heat -
Doc. : 08C00031_e Date : 10.02.2009 Page : 1 / 9 ORC TURBOGENERATOR TYPE CHP - Organic Rankine Cycle Turbogenerator fed by thermal oil, for the combined production of electric - (Preliminary) Doc. : 08C00031_e
T-016: Paralleling Application Manual
Application Engineering T-016: Paralleling Application Manual English Original Instructions 6-2014 A040W370 (Issue 4) Table of Contents 1. INTRODUCTION... 1 1.1 Overview... 1 1.2 About This Manual...
MOBILE DC POWER SYSTEMS FOR SUBSTATION APPLICATIONS
MOBILE DC POWER SYSTEMS FOR SUBSTATION APPLICATIONS Gary P. Guagliardi Director Sales & Marketing HindlePower, Inc. Easton, PA Introduction This paper explores the use of mobile DC power systems for three
Electrical Distribution Services for Mining and Metals Industries
Electrical Distribution Services for Mining and Metals Industries Solutions to help maximize plant reliability and ensure personnel safety Make the most of your energy SM Electrical Systems are Serious
Controller Automation, Model II+
Controller Automation Page 2 of 2 Automation with the RADAK II+ power controller II+ I/O Points: Inputs 5 Programmable Digital inputs 2 Dedicated digital inputs (Channel select and External SCR control
SECTION 16002C CAMPUS CENTRAL METERING SYSTEM DESIGN CRITERIA 1. General
SECTION 16002C CAMPUS CENTRAL METERING SYSTEM DESIGN CRITERIA 1. General A. Electrical usage on the Brown campus is presently monitored by a Siemens-brand, web-based central metering system, which includes
Model #: SMART2200CRMXL
Tripp Lite 1111 West 35th Street Chicago, IL 60609 USA Telephone: +(773) 869 1234 E-mail: [email protected] Model #: SMART2200CRMXL SmartPro Compact Rackmount UPS System - Precision Protection for
For a phase-to-phase voltage between 100 V and 1000 V. The standard ratings are: 400 V - 690 V - 1000 V (at 50 Hz)
24 1. NETWORK CONFIGURATIONS definition Standard IEC 38 defines voltage ratings as follows: - Low voltage () For a phase-to-phase voltage between 100 V and 1000 V. The standard ratings are: 400 V - 690
Siemens tiastar TM Motor Control Center (MCC) Siemens 2011. All rights reserved.
Siemens tiastar TM Motor Control Center (MCC) Siemens 2011. All rights reserved. tiastar Arc Resistant MCCs UL Validated Testing of Arc-Resistant Motor Control Centers page 2 tiastar Arc Resistant MCCs
Low Voltage Switchgear
Arc Resistant Switchgear n Insulated and isolated bus n Separation barriers and top venting n Breaker shutters 12 SWITCHGEAR Arc resistant metal-enclosed low voltage switchgear is an optional product offering
EGCP-3 LS 8406-113 Revision L. Explanation of Software Changes Made for the EGCP-3 LS Control. Application Note 51294
EGCP-3 LS 8406-113 Revision L Explanation of Software Changes Made for the EGCP-3 LS Control Application Note 51294 WARNING DANGER OF DEATH OR PERSONAL INJURY WARNING FOLLOW INSTRUCTIONS Read this entire
Generic PCSR Sub-chapter 15.4 : Electrical Equipment
Form10/00 Document ID : GA91-9101-0101-15004 Document Number : EE-GDA-C284 Revision Number : A Generic Design Assessment Generic PCSR Sub-chapter 15.4 : Electrical Equipment Hitachi-GE Nuclear Energy,
ABB PSPS Erich Steinmann; Generator control-2013
ABB PSPS Erich Steinmann; Generator control-2013 GENERATOR CONTROL THE MODULAR SOLUTION FOR GENERATORS To make sure that power is efficiently converted into electric energy, it is necessary to supervise
Secondary Unit Substations
14 SWITCHGEAR Secondary Unit Substations Overview Siemens offers a wide variety of unit substation designs to meet customer requirements. A unit substation consists of one or more transformers mechanically
1.44 kw Programmable DC Power Supplies XLN Series
Data sheet 1.44 kw Programmable DC Power Supplies XLN Series New Family of High Density System Power Supplies The B&K Precision XLN series are compact, programmable, single-output DC power supplies, suitable
Emirates Aluminium starts up World s first fully integrated power distribution system from ABB
Reprint from Aluminium World 2009, Volume 2 Emirates Aluminium starts up World s first fully integrated power distribution system from ABB Emirates Aluminium (EMAL), a joint venture between Abu Dhabi s
SURGE PROTECTIVE DEVICES (SPDs) LOW VOLTAGE AC INTEGRATED SURGE PROTECTION FOR ELECTRICAL DISTRIBUTION SYSTEMS SECTION 16671A SECTION 16671A
SURGE PROTECTIVE DEVICES (SPDs) INTEGRATED UNITS LOW VOLTAGE AC SURGE PROTECTION FOR ELECTRICAL DISTRIBUTION SYSTEMS PART 1 GENERAL 01 02 03 SCOPE The Contractor shall furnish and install the Surge Protective
SECTION 13850 DETECTION AND ALARM
SECTION 13850 DETECTION AND ALARM PART 1 GENERAL 1.01 SUMMARY A. Section Includes 1. Control Panel 2 Associated Equipment B. Products Installed But Not Supplied Under This Section 1. Section 16140 - Wiring
POWER GENERATION. www.mtu-online.com
POWER GENERATION A TOGNUM GROUP BRAND Valid for north america Europe / Middle East / Africa / Latin America MTU Onsite Energy / 88040 Friedrichshafen / Germany / Phone + 49 7541 90 7060 / Fax + 49 7541
PT-6000 Power Tower INSTALLATION MANUAL SPECIFICATIONS
PT-6000 Power Tower INSTALLATION MANUAL 10.5 9.75 12 22.75 10.75 MAXIMUM SOIL HEIGHT: DO NOT ALLOW FILL TO EXCEED THIS LEVEL! 11.5 4 4 13 Optional PT-BASE for new installations or when previous 2000/6000
SiteRanger tm. Power quality / site monitoring. Comm/net Systems, Inc.
SiteRanger tm Comprehensive Broadband/ Enterprise site monitoring device for Headend s, Hub Sites. Power quality / site monitoring Focus on power system infrastructure Retrofit legacy devices for remote
Engineering innovation
Eaton's Electrical Engineering Services & Systems Solutions Focus Seamless Solutions for Reliable, Efficient and Safe Power Systems Engineering innovation Progressive solutions for today s power systems
Part 1 System Modeling & Studies for Existing Systems
Part 1 System Modeling & Studies for Existing Systems Operation Technology, Inc. Copyright 2009 Result of rapid release of energy due to an arcing fault between two conductors. Bus voltages > 208V Temperatures
The Power to Know. It s all about the need to know... It s not only to know, but to understand. To act. To solve issues when seconds count.
The Power to Know It s all about the need to know... Your need to know what s happening with your facility s on-site power and distribution system. That includes automatic transfer switches, generator
Electrical Network Management System
Electrical Network Management System Optimisation of the electrical network Measure to understand Understand to control Control to optimise Cost of power and fluids Power quality Power availability 2 Improvement
SmartOnline 200-240V 6kVA 4.2kW On-Line Double-Conversion UPS, Extended Run, SNMP, Webcard, 6U Rack/Tower, DB9 Serial, Hardwire
SmartOnline 200-240V 6kVA 4.2kW On-Line Double-Conversion UPS, Extended Run, SNMP, Webcard, 6U Rack/Tower, DB9 Serial, Hardwire MODEL NUMBER: SU6000RT3UHV Highlights 6000VA / 6kVA / 4200W on-line double-conversion
Local Back-up Protection for an Electric Power System
MULTILIN GER-3178 GE Power Management Local Back-up Protection for an Electric Power System LOCAL BACK UP PROTECTION FOR AN ELECTRIC POWER SYSTEM J. BERDY TABLE OF CONTENTS Transmission Line Back-Up Protection...............................................
Integrated Power Systems for Data Centers
Integrated Power Systems for Data Centers A Commitment to Data Centers Caterpillar is committed to providing optimum value to the Data Center industry by leveraging our engineering, manufacturing, distribution,
GROUND DETECTION CIRCUITS FOR STATIONARY APPLICATIONS (IN PLAIN DOWN TO EARTH LANGUAGE)
GROUND DETECTION CIRCUITS FOR STATIONARY APPLICATIONS (IN PLAIN DOWN TO EARTH LANGUAGE) Matthew Theriault Designer Hindle Power Inc. Easton, PA SCOPE AND PURPOSE OF THE PAPER Why do we bother to monitor
The Application of Circuit Breakers to Reduce Downtime in Datacentres
The Application of Circuit Breakers to Reduce Downtime in Datacentres Tim Campbell BEng MIET. Marketing Manager, Terasaki Electric (Europe) Ltd. Abstract Circuit breakers fulfil several functions in the
Power Solutions for Data Centers Metering and protection architecture guide
Power Solutions for Data Centers Metering and protection architecture guide The purpose of this guide is to provide technical guidelines to designers and field engineers who specify metering and protection
4160: THE GREEN 480 MEDIUM VOLTAGE ELECTRICAL SYSTEMS
4160: THE GREEN 480 MEDIUM VOLTAGE ELECTRICAL SYSTEMS for DATA CENTERS Michael Mosman, PE Chief Technical Officer CCG Facilities Integration Incorporated FACILITIES INTEGRATION INCORPORATED MEDIUM VOLTAGE
Power-Zone 4 Arc Resistant Low Voltage Switchgear
Power-Zone 4 Arc Resistant Low Voltage Switchgear with ArcBlok Technology Make the most of your energy SM Workplace safety 2 I Power-Zone 4 Arc Resistant Low Voltage Switchgear Five to ten arc flash explosions
SFC-200 SERIES FIRE ALARM CONTROL PANELS. SFC-200 Series Fire Alarm Control Panels. Features. Description
SFC-200 SERIES FIRE ALARM CONTROL PANELS SFC-200 Series Fire Alarm Control Panels Description Summit s SFC-200 Series fire alarm control panels consist of six and twelve zone models which are equipped
TOSHIBA G9000 80/100/160/225 kva
CORPORATE OFFICE 13131 WEST LITTLE YORK ROAD HOUSTON, TX 77041 PHONE: (713) 466-0277 (800) 231-1412 FACSIMILE: (713) 896-5226 TOSHIBA G9000 80/100/160/225 kva GUIDE SPECIFICATION THREE PHASE UNINTERRUPTIBLE
GE Digital Energy. TLE Series UPS. 160-400 kw three phase 400 Vac. with best-in-class efficiency. gimagination at work
GE Digital Energy TLE Series UPS 160-400 kw three phase 400 Vac with best-in-class efficiency gimagination at work GE provides clean, efficient and reliable power for today s digital world with the ultra
PowerCommand 1.1 control system
PowerCommand 1.1 control system Control system description The PowerCommand control system is a microprocessor-based generator set monitoring, metering and control system designed to meet the demands of
Liebert GXT MT+ CX UPS, 1000VA - 3000VA Intelligent, Reliable UPS Protection. AC Power for Business-Critical Continuity
Liebert GXT MT+ CX UPS, 1000VA - 3000VA Intelligent, Reliable UPS Protection AC Power for Business-Critical Continuity Liebert GXT MT+ CX UPS, 1000VA -3000VA Intelligent, Reliable UPS Protection Liebert
PowerCommand 3201 digital generator set control
PowerCommand 3201 digital generator set control Description The PowerCommand 3201 Control is a microprocessorbased generator set monitoring, metering and control system. The control provides an operator
Advanced Protection of Distribution Networks with Distributed Generators
Date:- 8 10 March 2011 Venue: University of Manchester EES-UETP Course title Advanced Protection of Distribution Networks with Distributed Generators Peter Crossley Director of the Joule Centre School
Combined Cycle Control Overview
Combined Cycle Control Overview Introduction The Combined Cycle (CC) solution provides for the control and monitoring of a typical CC power plant in a cost effective, preengineered package. Basic Architecture
AEGIS DATA CENTER SERVICES POWER AND COOLING ANALYSIS SERVICE SUMMARY
AEGIS DATA CENTER SERVICES POWER AND COOLING ANALYSIS SERVICE SUMMARY The Aegis Services Power and Assessment Service provides an assessment and analysis of your data center facility and critical physical
SCADA Controlled Multi-Step Automatic Controlled Capacitor Banks & Filter Banks
SCADA Controlled Multi-Step Automatic Controlled Capacitor Banks & Filter Banks Introduction SCADA (Supervisory Controlled and Data Acquisition) controlled multi-step metalenclosed automatic capacitor
Spark-ignited generator set
Specification sheet Spark-ignited generator set 30 60 kw standby EPA emissions Description Cummins Power Generation commercial generator sets are fully integrated power generation systems providing optimum
Cahier technique no. 196
Collection Technique... Cahier technique no. 196 Integration of local power generation in industrial sites and commercial buildings T. Hazel "Cahiers Techniques" is a collection of documents intended for
*.ppt 11/2/2009 12:48 PM 1
Digital Compressor Controller *.ppt 11/2/2009 12:48 PM 1 Copeland Scroll Digital Controller Simple Controller That Enables OEM s To Use Digital Scrolls Relieves OEM From Developing Special Controllers
Bypass transfer switch mechanisms
Power topic #6013 Technical information from Cummins Power Generation transfer switch mechanisms > White paper By Gary Olson, Director, Power Systems Development This paper describes the configuration
CruzPro VAF110. AC Volts, Amps, Frequency, kw Monitor
CruzPro VAF110 AC Volts, Amps, Frequency, kw Monitor Table of Contents Introduction............................ 3 Specifications........................... 4 Installation..............................5
Defining the Needs of Modern Data Center Power Systems, Low Voltage Circuit Breaker Application
Defining the Needs of Modern Data Center Power Systems, Low Voltage Circuit Breaker Application by Reza Tajali, P.E. Square D Company ABSTRACT In modern data centers, Uninterruptible Power Supplies (UPS)
ATC-300 Automatic Transfer Switch Controller
ATC-300 Technical Data New Information Technical Data Page 2 Effective: May 2004 ATC-300 Introduction The Cutler-Hammer ATC-300 from Eaton s Electrical business is a comprehensive, multi-function, microprocessor-based