Application of Four-Pole Circuit Breakers within Data Centers

Size: px
Start display at page:

Download "Application of Four-Pole Circuit Breakers within Data Centers"

Transcription

1 Application of Four-Pole Circuit Breakers within Data Centers December 2013/AT324 by Frank Waterer, Fellow Engineer, Schneider Electric Engineering Services Make the most of your energy SM Revision #1 12/13

2 Summary Abstract... p 3 IEC lexicon (vs) North American Nomenclature... p 4 Brief Introduction of the Four Wire Electrical System... p 5 Origins of Four-Pole Circuit Breakers... p 6 Radial Circuit Breaker Applications in North America... p 7 The use of MDGF Protection Systems versus Four-Pole Circuit Breakers... p 9 The use of four-pole circuit breakers as UPS and generator circuit breakers with HRG systems... p 10 White paper on data centers 2

3 Abstract Since the introduction of the four pole circuit breaker in the 1950s, there has been ambiguity as to the appropriate applications for its utilization. Of particular interest is the use of four pole circuit breakers in multiple source power distribution systems such as service entrance rated equipment, optional stand-by generators, and uninterruptable power system (UPS) units where some of the three phase power systems are resistively grounded. This paper provides a brief history on the origins of three phase, four wire systems and the use of four pole circuit breakers within data centers today. Also discussed are the applications for using four pole circuit breakers with power distribution systems in lieu of the installation of Modified Differential Ground Fault (MDGF) Protection Systems. Get connected to power White paper on data centers 3

4 IEC lexicon (vs) North American Nomenclature Below is a short list of notable abbreviations and their definitions that are commonly used in countries that follow the mandates of the International Electrotechnical Commission (IEC) and the equivalent term in North America. Closed Coupled: The connection of two or more electrical power sources together in a synchronized manner. (North America: closed transition) Earth: Connected directly to the planet Earth or through a selected resistance where soil resistivity is measured and maintained. (North America: ground) Line: The energized conductor relative to the earth or another line. (North America: line of phase) Non - Coupled: The prevention and restriction of connecting two or more electrical power sources together. (North America: open transition or make before break) PEN: Protected Earth Neutral (USA within NPFA documents: the grounded conductor or neutral) RCD: Residual Current Device [USA: ground fault circuit interrupter (GFCI) or a ground fault relay (GFR)] RCCB: Residual Current Circuit Breaker. Also known in other IEC countries in Eastern Europe and India as an Earth Leakage Circuit Breaker or ELCB. (USA: circuit breaker with an integral ground fault protective function) RE: Resistively Earthed. [USA: low resistive grounded (LRG) system or a high resistive grounded (HRG) system. A resistively earthed or ground system is one in which a resistor with a specific resistance is intentionally installed in series between the Xo terminal of the supplying transformer and earth.] SCPD: Short-Circuit Protection Devices (circuit breakers or fuses) STD: Short Time Delay protection (protection against short-circuit over currents by circuit breaker with rapid trip release) White paper on data centers 4

5 Brief Introduction of the Four Wire Electrical System Beginning in the late 1950 s and continuing through the 1960 s, in response to a growing energy and raw materials shortages and energy supply issues, the manufacturing and industrial base within the United States began a slow and steady conversion from 3Ø, 3W, ungrounded DELTA, systems to 3Ø, 4W, solidly grounded, WYE systems. The use of three separate single phase transformers were replaced with a design in which all of the three phase windings are enclosed within a single transformer tank. This was a dramatic savings in materials and real estate. Commercial and industrial lighting systems in the United States rapidly changed from 120V to 277V. The operating voltage for industrial motors changed from 220/230V to 440/460V. The use of higher utilization voltages resulted in the use of less copper. Smaller conductors and smaller conduits equated to significant savings in material and labor cost. Eventually all commercial and industrial utilization equipment within the United States were converted to a power distribution systems supplied with a 3Ø, 4W, solidly grounded, WYE, 480Y/277V, 60Hz. The reconfigured transformers and systems provided power for both motors and facility lighting. In Canada, the voltage for the 3Ø, 4W configured systems were converted to 600Y/347V, 60Hz. Similar voltage system conversions had already begun in Europe and some other IEC countries years before for the same economic and raw material reasons. In the United Kingdom, the voltage for the 3Ø, 4W configured systems were 415Y/240V, 50Hz. In Europe, North Africa, and some Middle Eastern countries, the 3Ø, 4W configured systems were 380Y/220V, 50Hz. See Figure 1 below. Presently in the European Union, the utilization voltages are being converted to a 3Ø, 4W, 400Y/230V, 50Hz for standardization purposes. Figure 1 Three Phase, Four Wire, Solidly Earthed/Grounded WYE White paper on data centers 5

6 Origins of Four-Pole Circuit Breakers In IEC countries, the use of 3Ø, 4W configured voltage systems are not limited to commercial and industrial power equipment. The respective voltage and current between a line-to-protected earth neutral is utilized to supply residential housing, shops, small stores, and clinics with a 240V or 220V single line (or phase) electrical service. In IEC countries, two-pole circuit breakers have been utilized for decades in single line or phase applications and with RCDs to open the line conductor as well as the PEN or protected earth neutral conductor during a faulted condition or as a result of the detection of leakage currents in order to completely isolate the supply from the load for safety concerns. The use of four pole circuit breakers originated in Europe after the installation and use of 3Ø, 4W, solidly grounded, WYE configured power systems became widely common. The use of four pole circuit breakers in Europe was deemed a logical technological evolution with the two-pole circuit breakers utilized in single phase application and RCDs to open the line conductor as well as the PEN for same safety concerns. The initial use of four pole circuit breakers in IEC countries were on low ampacity control and power circuits and in applications requiring a RCCB or ELCB. RCCB or ELCB that interrupted all energized phase conductors and the PEN were employed in IEC countries where the traditional molded case circuit breakers or fuses (SCPD and STD) did not detect leakage currents dangerous to humans and livestock or that could result in fire hazards if not detected and interrupted. It has been historically common in IEC countries to provide complete mechanical isolation of the PEN from the electrical current source after any faulted condition or when isolation from the PEN is desirable for maintenance or repairs to existing electrical power circuits. As the power distribution system grew in ampacity in IEC countries due to power demands, the size of four pole circuit breakers also increased in ampacity and application. When two source power systems in commercial applications began to be installed in IEC countries to provide an alternate source of electrical power during abnormal or emergency conditions, the use of four pole circuit breakers were the applicable technological means of choice to avoid any circulating current between two separate electrical power source and a common load. The use of four pole circuit breakers in a non-coupled or open transition application also provided a means to avoid nuisance tripping of RCCB or ELCB (ground fault circuit breakers or ground fault relays) due to inadequate sensing and relaying of current imbalances caused by single phase loads. White paper on data centers 6

7 Radial Circuit Breaker Applications in North America The 3Ø, 4W, solidly grounded, WYE, 480Y/277V and 600Y/347V power distribution system used in North America are not utilized to supply electrical power to residential housing, shops, small stores, and clinics as are the 3Ø, 4W systems in IEC countries. Also, two-pole circuit breakers and two pole RCDs are not installed in single phase 277V and 347V applications to open the neutral conductor associated with a feeder or branch circuit in North America. In North America a three-pole circuit breaker has been the standard for an over current protective device in three phase power circuits since molded case circuit breakers were first developed and introduced into the electrical market in the USA in See Figure 2 below. In North America, the neutral conductor within electrical power equipment has traditionally been installed as a solidly connected conductor and is not automatically opened to mechanically separate the grounded conductor or neutral in the service rated equipment or any distribution equipment from the source of electrical power as part of any electrical protective function. Instead a mechanical means is provided in the electrical service rated equipment, pursuant Underwriter s Laboratory (UL) requirements, to physically separate the grounded conductor or neutral associated with all loads from the source of electrical power if necessary. This mechanical means is identified as the neutral disconnect link. See Figure 2 below. The intended purpose of a neutral disconnect link is to provide a mechanical means to completely separate an electrical service from its electrical supply provided by a local electrical utility, electrical co-operative, or electrical energy provider. If a neutral circuit connection still remained between Xo terminal of the supplying transformer and the neutral terminal within the service entrance equipment after the opening of the associated main circuit breaker, then connected loads would still remain actually connected to the supplying system via the respective neutral or associated grounded conductor(s). By operating and opening the main circuit breaker or fused disconnect within the service entrance equipment, as well as mechanically disconnecting and removing the neutral disconnect link, all electrical loads can be completely isolated and electrically separated from its electrical supply. Also, when an integral ground fault protective function is required or specified on a three phase, four wire, solidly grounded, WYE power circuit, then a separate neutral sensor is installed to monitor imbalanced current flow in the neutral conductor in order to provide effective ground fault protection along with a Main Bonding Jumper. See Figure 2 below. White paper on data centers 7

8 Figure 2 Typical Example of a Three-Pole Circuit Breaker with Integral Ground Fault Protection White paper on data centers 8

9 The use of MDGF Protection Systems versus Four-Pole Circuit Breakers There are specific benefits of installing four pole circuit breakers in multiple ended power distribution systems. During the past decades there have been numerous attempts to avoid the challenges, complexities, and cost associated with the design and installation of complex MDGF Protection Systems by the use of four-pole circuit breakers in switchboard and switchgear construction where there are two or more sources of electrical power. In some applications the use of four-pole circuit breakers can be a direct substitute for a well engineered and effectively commissioned MDGF Protection System. However, there are specific benefits of installing and utilizing four-pole circuit breakers in lieu of designing and installing a MDGF Protection System. The benefits for installing four pole circuit breakers in multiple ended power distribution systems are listed below. No MDGF Protection System is required if the Service Entrance Equipment is constructed in a Main-Main or in a Main-Tie-Main style configuration in which all four-pole circuit breakers are only operated in an open transition operation. No two electrical power sources can ever be interconnected in any closed transition operation at any time. In effect, the power distribution system will always be operating as a radial power distribution system with only one electrical power source at any given time for any and all connected electrical loads. The use of four-pole circuit breakers removes the necessity and cost to a project for a complex MDGF Protection System along with complex interconnection wiring between individual sections or between remote line ups of switchboards or switchgear. The use of four-pole circuit breakers in an open transition will prevent circulating current between the neutral bus and the ground bus within the interior of the switchboard or switchgear Service Entrance Equipment. The use of four-pole circuit breakers enhances the switching operations when employed with power systems with multiple generators by limiting the dielectric stresses on the insulation of components and equipment connected to power distribution systems that can result from switching transient. However, the installation of four-pole circuit breakers cannot not be utilized in every configured multiple ended power distribution systems to avoid the necessary use of a MDGF Protection System. Below is list of common issues and limitations. Four-pole circuit breakers can NOT be employed as a solution to avoid the installation of a MDGF Protection System if these circuit breakers are ever employed in continuous paralleled or closed transition operations. Inherent selectivity between Mains and Ties can no longer exist without allowing a space in the TCC curves for the insertion of one or more tie circuit breakers. Consequently, selective coordination can be compromised resulting in circuit breakers being subjected to the forces of greater I2T energy under a phaseto-ground fault. White paper on data centers 9

10 The use of four-pole circuit breakers as UPS and generator circuit breakers with HRG systems HRG systems can be installed with the intended purpose of dramatically reducing the current flow to ground on the three phase, four wire output windings of a UPS Unit, paralleled UPS Units, a single generator, or paralleled generators for a limited period of time during a phase-to-ground fault condition. However, where any UPS Units or generators contain a HRG System there must not be any interconnection of the service entrance neutral conductor with the neutral associated with the Xo output windings of any UPS Unit or generators containing a HRG System. This would result in the unintended consequences of the HRG for the UPS Unit(s) and generators functioning as a HRG for the service entrance system. Also, if the output windings of the multiple UPS Units or generators are paralleled together, they must not have a respective interconnected common neutral bus if each UPS Unit or generator has an individual HRG connected in series between its respective Xo terminal and ground. The use of four pole circuit breakers for UPS Unit(s) or generators with HRG Systems can be beneficial to completely isolate the outputs of UPS Unit(s) or generators from upstream service entrance equipment supplied by a utility or customer provided power class transformer with secondary winding configured as 3Ø, 4W, solidly grounded, WYE. White paper on data centers 10

11 Schneider Electric USA, Inc S. Roselle Road Palatine, IL Tel: Fax: Document Number AT324 This document has been printed on recycled paper January 2013 sf 2013 Schneider Electric Industries SAS, All Rights Reserved.

Atlanta Chapter IEEE Industry Applications Society

Atlanta Chapter IEEE Industry Applications Society Atlanta Chapter IEEE Industry Applications Society Electrical Equipment Room Design Considerations presented at the Sheraton Buckhead Hotel Atlanta, Georgia November 20, 2006 Outline 1. Definitions 2.

More information

HAZARDS, INCLUDING SHOCK, ARC FLASH AND FIRE

HAZARDS, INCLUDING SHOCK, ARC FLASH AND FIRE Appendix B-2 - Electrical Safety In Design Final Report TECHNOLOGIES THAT REDUCE LIKELIHOOD OF INJURY FROM ELECTRICAL HAZARDS, INCLUDING SHOCK, ARC FLASH AND FIRE The following are technologies that reduce

More information

Unified requirements for systems with voltages above 1 kv up to 15 kv

Unified requirements for systems with voltages above 1 kv up to 15 kv (1991) (Rev.1 May 2001) (Rev.2 July 2003) (Rev.3 Feb 2015) Unified requirements for systems with voltages above 1 kv up to 15 kv 1. General 1.1 Field of application The following requirements apply to

More information

Reverse-feed applications for circuit breakers

Reverse-feed applications for circuit breakers Technical Publication PU01200001E Contents Description Page Intoduction.......................................................................... 2 breaker classifications..........................................................

More information

Extend the Life of Existing Switchgear

Extend the Life of Existing Switchgear Extend the Life of Existing Switchgear January 2011/1910DB1002 by Hal Theobald, Product Manager Schneider Electric USA, Inc. Make the most of your energy SM Summary Introduction... p 3 Maintenance Requirements...

More information

415V DISTRIBUTION FOR GREEN DATA CENTERS

415V DISTRIBUTION FOR GREEN DATA CENTERS White Paper: HMRP-WP001-A5 June 5, 2012 415V DISTRIBUTION FOR GREEN DATA CENTERS Prepared by: Anthony (Tony) Hoevenaars, P. Eng President and CEO Mirus International Inc. Copyright 2012 Mirus International

More information

System Grounding and Ground-Fault Protection Methods for UPS-Supplied Power Systems

System Grounding and Ground-Fault Protection Methods for UPS-Supplied Power Systems System Grounding and Ground-Fault Protection Methods for -Supplied Power Systems Bill Brown, P.E., Square D Critical Power Competency Center 1. INTRODUCTION The use of solid grounding for -supplied power

More information

Arc Terminator Active Arc-Resistant Switchgear

Arc Terminator Active Arc-Resistant Switchgear Arc Terminator Active Arc-Resistant Switchgear Increasing safety and productivity by extinguishing internal arcing faults within the switchgear. The Square D Arc Terminator from Schneider Electric offers

More information

OPTIMIZING POWER SYSTEM PROTECTION FOR MODERN DATA CENTERS

OPTIMIZING POWER SYSTEM PROTECTION FOR MODERN DATA CENTERS OPTIMIZING POWER SYSTEM PROTECTION FOR MODERN DATA CENTERS Data center power systems are constructed with a premium on reliability at a significant cost. The return on this investment is realized if it

More information

> Executive summary. The Role of Isolation Transformers in Data Center UPS Systems. White Paper 98 Revision 0. Contents.

> Executive summary. The Role of Isolation Transformers in Data Center UPS Systems. White Paper 98 Revision 0. Contents. The Role of Isolation Transformers in Data Center UPS Systems White Paper 98 Revision 0 by Neil Rasmussen > Executive summary Most modern UPS systems do not include the internal s that were present in

More information

415V DISTRIBUTION FOR GREEN DATA CENTERS

415V DISTRIBUTION FOR GREEN DATA CENTERS White Paper: HMRP-WP001-A1 October 1, 2010 415V DISTRIBUTION FOR GREEN DATA CENTERS Prepared by: Anthony (Tony) Hoevenaars, P. Eng President and CEO Mirus International Inc. Copyright 2005 Mirus International

More information

Fundamentals of Power

Fundamentals of Power Fundamentals of Power Fundamentals of Power 2008 American Power Conversion Corporation. All rights reserved. All trademarks provided are the property of their respective owners. Learning Objectives At

More information

Fortune Oregon Data Center Increases Reliability with a High Resistance Grounding System

Fortune Oregon Data Center Increases Reliability with a High Resistance Grounding System Fortune Oregon Data Center Increases Reliability with a High Resistance Grounding System Cory David Smith, Project Manager, ECOM Engineering Inc., and David Lawrence Smith, Principal, ECOM Engineering

More information

Electrical Grounding. Appendix C

Electrical Grounding. Appendix C Appendix C Electrical Grounding Low-Voltage Equipment Grounding The most frequently cited Office of Safety and Health Administration (OSHA) electrical violation is improper occupational grounding of equipment

More information

Siemens STEP 2000 Course Basics of Electrical Products

Siemens STEP 2000 Course Basics of Electrical Products Siemens STEP 2000 Course Basics of Electrical Products It's easy to get in STEP! Download any course. Hint: Make sure you download all parts for each course and the test answer form. Complete each chapter

More information

Short Circuit Current Calculations

Short Circuit Current Calculations Introduction Several sections of the National Electrical Code relate to proper overcurrent protection. Safe and reliable application of overcurrent protective devices based on these sections mandate that

More information

What are the basic electrical safety issues and remedies in solar photovoltaic installations?

What are the basic electrical safety issues and remedies in solar photovoltaic installations? What are the basic electrical safety issues and remedies in solar photovoltaic installations? Presented by: Behzad Eghtesady City of Los Angeles Department of Building and Safety Topics Covered Photovoltaic

More information

Proper Application of 415V Systems in North American Data Centers. A White Paper from the Experts in Business-Critical Continuity

Proper Application of 415V Systems in North American Data Centers. A White Paper from the Experts in Business-Critical Continuity Proper Application of 415V Systems in North American Data Centers A White Paper from the Experts in Business-Critical Continuity Introduction Increasing pressure to reduce operating expenses and be more

More information

PREFACE. Your comments or suggestions are welcome and appreciated. They should be sent to:

PREFACE. Your comments or suggestions are welcome and appreciated. They should be sent to: PREFACE UL developed the Dead-Front Switchboard Marking Guide for code authorities, electric utilities, contractors, installers, users, designers, and other interested parties to aid in understanding deadfront

More information

ASK THE EXPERTS. Resistance Grounding Q&A. with industry experts

ASK THE EXPERTS. Resistance Grounding Q&A. with industry experts ASK THE EXPERTS Resistance Grounding Q&A with industry experts system grounding system grounding system grounding system grounding system grounding System Grounding Definition and Different Types What

More information

Rule 5.500 Fast Track Analysis for National Life Insurance Co.

Rule 5.500 Fast Track Analysis for National Life Insurance Co. Rule 5.500 Fast Track Analysis for National Life Insurance Co. For a 500 kw Solar array to be located at 155 Northfield Street in Montpelier, Vermont Green Mountain Power Pam Allen Date: 5/31/13 SECTION

More information

Submit shop drawings for equipment provided under this section Shop drawings shall indicate:

Submit shop drawings for equipment provided under this section Shop drawings shall indicate: Section 16435 - SWITCHBOARDS Introduction Part 1 - General Reference The work under this section is subject to requirements of the Contract Documents including the General Conditions, Supplementary Conditions,

More information

Corner-Grounded Delta (Grounded B Phase) Systems

Corner-Grounded Delta (Grounded B Phase) Systems Data Bulletin 2700DB0202R03/12 09/2012 Replaces 2700DB0202R2/09 dated 02/2009 Corner-Grounded Delta (Grounded B Phase) Systems Class 2700 Retain for future use. Introduction Corner-grounded delta systems

More information

Mission Critical Data Center Systems

Mission Critical Data Center Systems Mission Critical Systems Mission Critical/ Electrical Distribution Systems Data center electrical distribution designs are rapidly evolving, driven by needs such as increasing power densities, energy efficiency,

More information

IRRIGATION PUMPING Table of Contents - Section 900

IRRIGATION PUMPING Table of Contents - Section 900 IRRIGATION PUMPING Table of Contents - Section 900 PARAGRAPH 900.1 GENERAL 1 900.2 METERING REQUIREMENTS 1 900.3 CUSTOMER S CONTROL EQUIPMENT 2 900.4 SERVICE CONDUCTOR REQUIREMENTS 2 900.5 RECOMMENDATIONS

More information

Top Commercial / Residential Electrical Requirements *

Top Commercial / Residential Electrical Requirements * Department of Community Development Building Division 4800 West 92 nd Avenue Westminster, Colorado 80031 For Information call (303) 658-2075 Fax (303) 706-3922 www.westminsterpermits.com Top Commercial

More information

Fault Characteristics in Electrical Equipment

Fault Characteristics in Electrical Equipment 1. Introduction Proper design and installation of electrical equipment minimizes the chance of electrical faults. Faults occur when the insulation system is compromised and current is allowed to flow through

More information

BASIC NEC CODE RULES AND DESIGN PRACTICE

BASIC NEC CODE RULES AND DESIGN PRACTICE BASIC NEC CODE RULES AND DESIGN PRACTICE Wire Ampacity and Size Circuit Breaker Size 1. Maximum loading for any branch circuit is 80% of rating of circuit for ampacity of wire for any load. NEC 220-2,

More information

FIT TIER 2 Application

FIT TIER 2 Application FIT TIER 2 Application Application Information The below information Auto-Fills from your registration information: Building Permit Application Date: Project Completion Date: Name: Address: City: State:

More information

Title 20 PUBLIC SERVICE COMMISSION. Subtitle 50 SERVICE SUPPLIED BY ELECTRIC COMPANIES. Chapter 02 Engineering

Title 20 PUBLIC SERVICE COMMISSION. Subtitle 50 SERVICE SUPPLIED BY ELECTRIC COMPANIES. Chapter 02 Engineering Title 20 PUBLIC SERVICE COMMISSION Subtitle 50 SERVICE SUPPLIED BY ELECTRIC COMPANIES Chapter 02 Engineering Authority: Public Utility Companies Article, 2-121, 5-101 and 5-303, Annotated Code of Maryland.

More information

The Application of Circuit Breakers to Reduce Downtime in Datacentres

The Application of Circuit Breakers to Reduce Downtime in Datacentres The Application of Circuit Breakers to Reduce Downtime in Datacentres Tim Campbell BEng MIET. Marketing Manager, Terasaki Electric (Europe) Ltd. Abstract Circuit breakers fulfil several functions in the

More information

Residual Current Circuit Breaker

Residual Current Circuit Breaker Introduction Residual Current Circuit Breaker / ELCB The Fault current overloads and short circuits can be detected by circuit breakers like MCB s MCCB s & HRC Fuses etc. But, Circuit breakers don t detect

More information

Three-phase AC circuits

Three-phase AC circuits Three-phase AC circuits This worksheet and all related files are licensed under the Creative Commons Attribution License, version 1.0. To view a copy of this license, visit http://creativecommons.org/licenses/by/1.0/,

More information

ARC FLASH CALCULATIONS & LABELING REQUIREMENTS

ARC FLASH CALCULATIONS & LABELING REQUIREMENTS ARC FLASH CALCULATIONS & LABELING REQUIREMENTS Presented by: Edmund Elizalde EYP Mission Critical Facilities, Inc. Slides by: Lonnie Lindell SKM Systems Analysis, Inc. 1 Agenda NEC 110.16 NFPA 70E IEEE

More information

12 SOLAR PHOTOVOLTAIC POWER SUPPLY SYSTEMS by John Ware. PV modules are current-limiting

12 SOLAR PHOTOVOLTAIC POWER SUPPLY SYSTEMS by John Ware. PV modules are current-limiting 12 SOLAR PHOTOVOLTAIC POWER by John Ware IT IS PLANNED for BS 7671:2008 to include a new Section 712 providing additional requirements for safety applicable to solar photovoltaic (pv) power supply systems.

More information

Switchgear and Metal-Enclosed Bus

Switchgear and Metal-Enclosed Bus Section 18 Switchgear and Metal-Enclosed Bus 180. SWITCHGEAR ASSEMBLIES 180A. General Requirements for All Switchgear. This rule covers general requirements for all switchgear. Examples of switchgear found

More information

Effective: September 10, 2006 Vermont Attachment 1 to Rule 5.500 Public Service Board Page 1 of 6

Effective: September 10, 2006 Vermont Attachment 1 to Rule 5.500 Public Service Board Page 1 of 6 Public Service Board Page 1 of 6 STANDARD APPLICATION FOR INTERCONNECTION OF GENERATION RESOURCES IN PARALLEL TO THE ELECTRIC SYSTEM OF: (Interconnecting Utility) Preamble and Instructions: An owner of

More information

Primary and Secondary Electrical Distribution Systems

Primary and Secondary Electrical Distribution Systems Primary and Secondary Electrical Distribution Systems Critical Facilities Round Table 12th Quarterly Membership Meeting June 2, 2006 David D. Roybal. P.E. Eaton Electrical Cutler-Hammer Products Utility

More information

Arc Fault Circuit Interrupters Frequently Asked Questions

Arc Fault Circuit Interrupters Frequently Asked Questions Contents My AFCI is tripping! What do I do? What is the difference between branch feeder and combination type Arc Fault Circuit Interrupters? What is new with the 2008 NEC versus the 2005 NEC with respect

More information

Switchgear Application Issues for Mission Critical Power Systems, Part One

Switchgear Application Issues for Mission Critical Power Systems, Part One Switchgear pplication Issues for Mission Critical Power Systems, Part One BSTRCT With the advent of high reliability data centers and telecommunication facilities, designers of commercial power face new

More information

FFI. Advances in Medium and Low Voltage Power Distribution ESS Metron Expo and Technical Seminars. Presented By: Greg Pelster & Robert Schmid

FFI. Advances in Medium and Low Voltage Power Distribution ESS Metron Expo and Technical Seminars. Presented By: Greg Pelster & Robert Schmid Advances in Medium and Low Voltage Power Distribution ESS Metron Expo and Technical Seminars Presented By: Greg Pelster & Robert Schmid FFI Ferrie, Franzmann Industries LOW VOLTAGE SWITCHGEAR & LOW VOLTAGE

More information

Hyperlinks are Inactive

Hyperlinks are Inactive Prepared by: NIB/EOB PLANNING GUIDE FOR SINGLE CUSTOMER SUBSTATIONS SERVED FROM TRANSMISSION LINES 05503 Department: Electric T&D Section: T&D Engineering and Technical Support Approved by: G.O. Duru (GOD)

More information

Services. Three Phase Service

Services. Three Phase Service Services Primary Service vs Secondary Service Overhead vs Underground Common Service Types Three Phase Wye Closed Open Delta Corner Grounded Center Tapped Open Single Phase Three Phase Service Wye Delta

More information

How To Test A Power Switch On A Power Supply

How To Test A Power Switch On A Power Supply transfer switches Soft load Innovative, reliable, integrated solution Built with years of experience Powered with innovation Delivered with reliability A history of experience, innovation and reliability

More information

Qualitative Analysis of Power Distribution Configurations for Data Centers

Qualitative Analysis of Power Distribution Configurations for Data Centers Qualitative Analysis of Power Distribution Configurations for Data Centers White Paper #4 2007 The Green Grid. All rights reserved. No part of this publication may be used, reproduced, photocopied, transmitted,

More information

CONSTRUCTION STANDARD ELECTRIC OPERATIONS ORGANIZATION

CONSTRUCTION STANDARD ELECTRIC OPERATIONS ORGANIZATION Page 1 of 11 ****This Standard Supercedes BECo CS2.13-2.3 & ComElectric OH Construction Manual, System Grounding Section, drawings CGND, GRDSUM, and C2**** 1.0 Bill of Materials GROUNDING AND BONDING POLE-MOUNTED

More information

LIMITING SHORT-CIRCUIT CURRENTS IN MEDIUM-VOLTAGE APPLICATIONS

LIMITING SHORT-CIRCUIT CURRENTS IN MEDIUM-VOLTAGE APPLICATIONS LIMITING SHORT-CIRCUIT CURRENTS IN MEDIUM-VOLTAGE APPLICATIONS Terence Hazel Senior Member IEEE Schneider Electric 38050 Grenoble France Abstract The power requirements for large industrial sites is increasing.

More information

Integrating SPDs in Switchgear & Switchboards Causes More Problems than it Solves

Integrating SPDs in Switchgear & Switchboards Causes More Problems than it Solves Integrating SPDs in Switchgear & Switchboards Causes More Problems than it Solves White Paper July 2010 Integrating surge protective devices (SPD) into distribution equipment (i.e. switchgear, switchboards,

More information

Earth Fault Detection Basics in Theory

Earth Fault Detection Basics in Theory Earth Fault Detection Basics in Theory Author: Dipl.-Ing. Ingo Kühnen Woodward Power Solutions Krefelder Weg 47 47906 Kempen, Germany Kempen, 16.04.2010 Earth_Fault_Detection_20100416.doc page 1 1. Star

More information

A Comparison of Contemporary Electrical Distribution Equipment Standards. San Francisco IEEE Industry Applications Society May 26, 2009

A Comparison of Contemporary Electrical Distribution Equipment Standards. San Francisco IEEE Industry Applications Society May 26, 2009 A Comparison of Contemporary Electrical Distribution Equipment Standards San Francisco IEEE Industry Applications Society May 26, 2009 What are Standards? Clearly defined performance characteristics Based

More information

Ground Fault Protection

Ground Fault Protection Technical collection Ground Fault Protection Low voltage expert guides n 2 Contents The role of "Ground Fault Protection".. Safety and availability.2. Safety and installation standards.2.. The IEC 60

More information

The complete range of consumer switchboards and switchgear

The complete range of consumer switchboards and switchgear Power Distribution The complete range of consumer switchboards and switchgear www.nhp.com.au/mod6 The MOD6 range of consumer switchboards and switchgear is specifically designed for domestic and commercial

More information

The following components are common to most cubicles; this example is an ABB HK cubicle.

The following components are common to most cubicles; this example is an ABB HK cubicle. 4.0 CIRCUIT BREAKER CUBICLE Learning Objectives The circuit breaker cubicle is the component of the switchgear that holds the circuit breaker, and the controls and cabling for the distribution system.

More information

Circuit Breakers and Switchgear. Thomas Greer Director of Engineering TLG Services

Circuit Breakers and Switchgear. Thomas Greer Director of Engineering TLG Services Circuit Breakers and Switchgear Thomas Greer Director of Engineering TLG Services Presentation Outline Switchgear Definition Overcurrent Protection Devices Circuit Breaker Trip Curves and Coordination

More information

Motor Protection Voltage Unbalance and Single-Phasing

Motor Protection Voltage Unbalance and Single-Phasing Motor Protection Voltage Unbalance and Single-Phasing Cooper Bussmann contributes the following information, which is an excerpt from their 190-page handbook SPD Selecting Protective Devices Based on the

More information

ESP 120 M1, ESP 208 M1, ESP 240 M1, ESP 415 M1, ESP 277 M1, ESP 480 M1 and M1R variants. Installation instructions ESP M1/M1R mains protectors

ESP 120 M1, ESP 208 M1, ESP 240 M1, ESP 415 M1, ESP 277 M1, ESP 480 M1 and M1R variants. Installation instructions ESP M1/M1R mains protectors ESP 120 M1, ESP 208 M1, ESP 240 M1, ESP 415 M1, ESP 277 M1, ESP 480 M1 and M1R variants Installation instructions Contents Key points of installation Before installation Installation Installation check

More information

ELECTRICAL ENGINEERING DESIGN CRITERIA APPENDIX F

ELECTRICAL ENGINEERING DESIGN CRITERIA APPENDIX F ELECTRICAL ENGINEERING DESIGN CRITERIA APPENDIX F TABLE OF CONTENTS Appendix F - Electrical Engineering Design Criteria F.1 Introduction...F-1 F.2 Codes and Standards...F-1 F.3 Switchyard and Transformers...F-1

More information

How to reduce exposure to arc flash hazards

How to reduce exposure to arc flash hazards GE Energy Industrial Solutions How to reduce exposure to arc flash hazards Multiple solutions for new and existing facilities imagination at work Multiple Issues Today s power system engineer must not

More information

Part 1 System Modeling & Studies for Existing Systems

Part 1 System Modeling & Studies for Existing Systems Part 1 System Modeling & Studies for Existing Systems Operation Technology, Inc. Copyright 2009 Result of rapid release of energy due to an arcing fault between two conductors. Bus voltages > 208V Temperatures

More information

How To Get A Power Line Extension

How To Get A Power Line Extension GUIDELINES FOR COMMERCIAL ELECTRIC SERVICE HOOKUP 1 Steps to Commercial Service Pay the Design Deposit Commercial Buildings: Up to 1, sq ft = $1,. 1, 5, sq ft = $2,. Over 5, sq ft = $3,. Commercial jobs

More information

Power Plant Electrical Distribution Systems

Power Plant Electrical Distribution Systems PDH Course E184 Power Plant Electrical Distribution Systems Gary W Castleberry, PE 2008 PDH Center 2410 Dakota Lakes Drive Herndon, VA 20171-2995 Phone: 703-478-6833 Fax: 703-481-9535 www.pdhcenter.com

More information

101 BASICS SERIES LEARNING MODULE 3: FUNDAMENTALS OF ELECTRICAL DISTRIBUTION. Cutler-Hammer

101 BASICS SERIES LEARNING MODULE 3: FUNDAMENTALS OF ELECTRICAL DISTRIBUTION. Cutler-Hammer 101 BASICS SERIES LEARNING MODULE 3: FUNDAMENTALS OF ELECTRICAL DISTRIBUTION Cutler-Hammer WELCOME Welcome to Module 3, Fundamentals of Electrical Distribution. If you have successfully completed Module

More information

Engineers Edge, LLC PDH & Professional Training

Engineers Edge, LLC PDH & Professional Training 510 N. Crosslane Rd. Monroe, Georgia 30656 (770) 266-6915 fax (678) 643-1758 Engineers Edge, LLC PDH & Professional Training Copyright, All Rights Reserved Engineers Edge, LLC An Introduction to Interior

More information

6.0 Electrical Installations

6.0 Electrical Installations 6.0 An electrical installation is a combination of electrical equipment installed to fulfill a specific purpose and having coordinated characteristics. In dealing with the electrical installation, it is

More information

Electronic Trip Circuit Breaker Basics Circuit Breaker Application Guide Class 0600

Electronic Trip Circuit Breaker Basics Circuit Breaker Application Guide Class 0600 Electronic Trip Circuit Breaker Basics Circuit Breaker Application Guide Class 0600 Data Bulletin 0600DB1104 03/2012 Retain for future use. Electronic Trip Circuit Breaker Basics 0600DB1104 Table of Contents

More information

Grounding of AC generators and switching the neutral in emergency and standby power systems

Grounding of AC generators and switching the neutral in emergency and standby power systems Power topic #6006 Part 2 of 2 Technical information from Cummins Power eneration rounding of AC generators and switching the neutral in emergency and standby power systems > White paper By Lawrence A.

More information

ECE 586b Course Project Report. Auto-Reclosing

ECE 586b Course Project Report. Auto-Reclosing ECE 586b Course Project Report Auto-Reclosing Srichand Injeti May 5, 2008 Department Of Electrical and computer Engineering University Of Western Ontario, London Ontario Table of contents 1. Introduction...1

More information

METER REQUIREMENTS GENERAL REQUIREMENTS SECTION D

METER REQUIREMENTS GENERAL REQUIREMENTS SECTION D 12 - ELECTRIC SERVICE HANDBOOK SECTION D METER REQUIREMENTS This chapter gives you information on Central Lincoln s metering requirements. It's divided into three sections: General requirements This section

More information

CONTINUOUS MONITORING AND AVOIDANCE OF RESIDUAL CURRENTS IN DATA CENTRES WITH RCM White paper Revision 2

CONTINUOUS MONITORING AND AVOIDANCE OF RESIDUAL CURRENTS IN DATA CENTRES WITH RCM White paper Revision 2 IT Power Solutions CONTINUOUS MONITORING AND AVOIDANCE OF RESIDUAL CURRENTS IN DATA CENTRES WITH RCM White paper Revision 2 Thomas B. Jones 1 Introduction Operators and managers consider outages, operational

More information

Product Description Full Voltage Starting Electric Fire Pump Controllers FTA1000

Product Description Full Voltage Starting Electric Fire Pump Controllers FTA1000 Product Description Full Voltage Starting Electric Fire Pump Controllers FTA1000 Description Firetrol FTA1000 Full Voltage Fire Pump Controllers are intended for use with electric motor driven fi re pumps

More information

Three-Phase Electric Power Distribution for Computer Data Centers

Three-Phase Electric Power Distribution for Computer Data Centers Three-hase Electric ower Distribution for Computer Data Centers WHITE AER E901 Geist January 008 Summary This paper will describe the characteristics of three-phase power and outline the advantages of

More information

High-Efficiency AC Power Distribution for Data Centers

High-Efficiency AC Power Distribution for Data Centers High-Efficiency AC Power Distribution for Data Centers White Paper 128 Revision 2 by Neil Rasmussen > Executive summary The use of 240 volt power distribution for data centers saves floor space, simplifies

More information

MEDIUM VOLTAGE CE-BF SWITCHBOARDS. UP TO 40.5 kv. CE - BF - C - en - REV.00 2012.4

MEDIUM VOLTAGE CE-BF SWITCHBOARDS. UP TO 40.5 kv. CE - BF - C - en - REV.00 2012.4 CE - BF - C - en - REV.00 2012.4 APPLICATION CE-BF Switchbords up to 40.5 kv are designed for use in public and industrial distribution system up to 40,5KV for the operation and protection of lines, transformers,

More information

Arc Flash Energy Mitigation Techniques

Arc Flash Energy Mitigation Techniques Arc Flash Energy Mitigation Techniques When short circuits occur on an electrical distribution system, an arc flash event usually forms. These arc flash events can cause dangerous and potentially fatal

More information

For a phase-to-phase voltage between 100 V and 1000 V. The standard ratings are: 400 V - 690 V - 1000 V (at 50 Hz)

For a phase-to-phase voltage between 100 V and 1000 V. The standard ratings are: 400 V - 690 V - 1000 V (at 50 Hz) 24 1. NETWORK CONFIGURATIONS definition Standard IEC 38 defines voltage ratings as follows: - Low voltage () For a phase-to-phase voltage between 100 V and 1000 V. The standard ratings are: 400 V - 690

More information

A Practical Guide to Dielectric Testing

A Practical Guide to Dielectric Testing Chroma Systems Solutions, Inc. A Practical Guide to Dielectric Testing 19032 Series Electrical Safety Analyzer & 19050 Series Hipot Tester AC/DC/IR/SCAN Keywords: Dielectric tests, insulation resistance

More information

Safety By Design. Strategies for Electrical Contractors

Safety By Design. Strategies for Electrical Contractors Safety By Design Strategies for Electrical Contractors Introduction Engineering and system design significantly impact worker safety System design provides opportunity to eliminate/minimize workers exposure

More information

4.5 Transformer Connections

4.5 Transformer Connections ELECTRIC POWER SYSTEMS IN COMMERCIAL BUILDINGS IEEE Std 241-1990 5) Flat Billing Ñ Certain applications involve service to the load of a Þxed characteristic. For such loads, the supplying utility may offer

More information

MV, HV AND EHV SWITCHGEAR TESTING & COMMISSIONING

MV, HV AND EHV SWITCHGEAR TESTING & COMMISSIONING Training Title MV, HV AND EHV SWITCHGEAR TESTING & COMMISSIONING Training Duration 5 days Training Date MV, HV and EHV Switchgear Testing & Commissioning 5 20 24 Apr $3,750 Dubai, UAE In any of the 5 star

More information

Electrical safety requirements in DC distribution systems

Electrical safety requirements in DC distribution systems Electrical safety requirements in DC distribution systems PAUL J.L.AN TICHELEN, DOMINIQUE WEYEN ITO Boeretang 200, 2400 Mol BELGIUM Abstract: This paper focuses on the safety requirements for the DC bus

More information

ELECTRICAL INSPECTION BULLETIN (Effective 2000-03-01)

ELECTRICAL INSPECTION BULLETIN (Effective 2000-03-01) ELECTRICAL INSPECTION BULLETIN (Effective 2000-03-01) Rule 28-900 Standby Generator Installations Due to the increasing number of standby generator installations being established to maintain continuity

More information

Best Practices for Power Equipment Startup

Best Practices for Power Equipment Startup Frank Waterer, Fellow Engineer, Square D Engineering Services in conjunction with the Square D Critical Power Competency Center 1. Abstract In order for the electrical power distribution systems within

More information

White Paper SolarEdge Three Phase Inverter System Design and the National Electrical Code. June 2015 Revision 1.5

White Paper SolarEdge Three Phase Inverter System Design and the National Electrical Code. June 2015 Revision 1.5 White Paper SolarEdge Three Phase Inverter System Design and the National Electrical Code June 2015 Revision 1.5 Shalhevet Bar-Asher; SolarEdge Technologies, Inc. Bill Brooks, PE; Brooks Engineering LLC

More information

STANDARDS AND RATINGS FOR THE APPLICATION OF MOLDED CASE, INSULATED CASE, AND POWER CIRCUIT BREAKERS

STANDARDS AND RATINGS FOR THE APPLICATION OF MOLDED CASE, INSULATED CASE, AND POWER CIRCUIT BREAKERS STANDARDS AND RATINGS FOR THE APPLICATION OF MOLDED CASE, INSULATED CASE, AND POWER CIRCUIT BREAKERS David D. Roybal, P.E. Senior Member, IEEE Cutler-Hammer, Inc. 3697 Mount Diablo Boulevard Lafayette,

More information

Power-Zone 4 Arc Resistant Low Voltage Switchgear

Power-Zone 4 Arc Resistant Low Voltage Switchgear Power-Zone 4 Arc Resistant Low Voltage Switchgear with ArcBlok Technology Make the most of your energy SM Workplace safety 2 I Power-Zone 4 Arc Resistant Low Voltage Switchgear Five to ten arc flash explosions

More information

Figure. 1 - Split Phase 240/120V circuit (180 phase shift)

Figure. 1 - Split Phase 240/120V circuit (180 phase shift) This technical note describes the option of connecting the 60Hz XW Inverter/Charger to a three-phase source by using a transformer to convert the AC source to split-phase 240/120V. INTRODUCTION: Split-phase

More information

Electrical Distribution Services for Mining and Metals Industries

Electrical Distribution Services for Mining and Metals Industries Electrical Distribution Services for Mining and Metals Industries Solutions to help maximize plant reliability and ensure personnel safety Make the most of your energy SM Electrical Systems are Serious

More information

SECTION 16999 ELECTRICAL ACCEPTANCE TESTS

SECTION 16999 ELECTRICAL ACCEPTANCE TESTS SECTION 16999 ELECTRICAL ACCEPTANCE TESTS PART 1 2. AND 3. COMBINED 1.1 SUMMARY A. Description of Systems 1. Furnish all labor, materials, test equipment, and technical supervision to perform and record

More information

Spending too much to maintain aging switchgear? Circuit breaker solutions from Square D Services.

Spending too much to maintain aging switchgear? Circuit breaker solutions from Square D Services. Spending too much to maintain aging switchgear? Circuit breaker solutions from Square D Services. Spending too much time and money on equipment maintenance? Square D Services: Your source for circuit breaker

More information

Guide to the Selection & Use of Residual Current Devices

Guide to the Selection & Use of Residual Current Devices Guide to the Selection & Use of Residual Current Devices ET214:2005 Edition 1 Electro-Technical Council of Ireland Limited Published by the Electro-Technical Council of Ireland Limited Date of Publication:

More information

UNIVERSITY OF WASHINGTON Facilities Services Design Guide. Electrical. Switchboards. Basis of Design. Design Evaluation

UNIVERSITY OF WASHINGTON Facilities Services Design Guide. Electrical. Switchboards. Basis of Design. Design Evaluation Basis of Design This section applies to the design relating to low voltage switchboards. Design Criteria UW Class N1 facilities main switchboards shall be rear accessible. The main, tie and feeder breakers

More information

Section 9: Power Distribution Equipment Bill Brown, P.E., Square D Engineering Services

Section 9: Power Distribution Equipment Bill Brown, P.E., Square D Engineering Services Section 9: Power Distribution Equipment Bill Brown, P.E., Square D Engineering Services Introduction Power Distribution Equipment is a term generally used to describe any apparatus used for the generation,

More information

Circuit Breakers Supplementary Protectors Manual Motor Controllers

Circuit Breakers Supplementary Protectors Manual Motor Controllers WHITE PAPER Circuit Breakers Supplementary Protectors Manual Motor Controllers Circuit Protection Methods Differentiating between Supplementary Protection, Branch Circuit Protection, and Self-Protected

More information

How Much Voltage Drop Is Acceptable?

How Much Voltage Drop Is Acceptable? How Much Voltage Drop Is Acceptable? Article supplied by Ideal The National Electrical Code (NEC) recommends that the combined voltage drop of the electrical system (branch circuit and feeders) not exceed

More information

Electrical Shore Connections / Cold Ironing

Electrical Shore Connections / Cold Ironing STANDARD FOR CERTIFICATION No. 2.25 Electrical Shore Connections / Cold Ironing JULY 2014 The electronic pdf version of this document found through http://www.dnv.com is the officially binding version

More information

Eaton Automatic Transfer Switches

Eaton Automatic Transfer Switches This is a photographic template your photograph should fit precisely within this rectangle. Eaton Automatic Transfer Switches Jody Grabowski Eaton ATS Product Line Sales Engineer February 1st, 2011 2008

More information

Evaluating Water-Damaged Electrical Equipment

Evaluating Water-Damaged Electrical Equipment Evaluating Water-Damaged Electrical Equipment 1 USE OF THIS PUBLICATION This publication provides information on how to evaluate electrical equipment that has been exposed to water through flooding, fire

More information

3. TYPES OF SERVICE AVAILABLE. 3.1 Scope

3. TYPES OF SERVICE AVAILABLE. 3.1 Scope 3. TYPES OF SERVICE AVAILABLE 3.1 Scope UI supplies 60 hertz, alternating current with different voltage and ampere ratings. Not all voltage and ampere ratings are available throughout the entire service

More information

UNIVERSITY OF WASHINGTON Facilities Services Design Guide. Electrical. Metering and Monitoring. Basis of Design

UNIVERSITY OF WASHINGTON Facilities Services Design Guide. Electrical. Metering and Monitoring. Basis of Design Basis of Design This section applies to the design, installation and integration of metering and monitoring equipment, including: hardware installed in the electrical service and distribution equipment,

More information

Grounding and Electrical Safety of Shore Power Supply and DC Stinger System Design

Grounding and Electrical Safety of Shore Power Supply and DC Stinger System Design Grounding and Electrical Safety of Shore Power Supply and DC Stinger System Design Dev Paul AECOM 2101 Webster Street, Suite 1900, Oakland, Ca 94612 dev.paul@aecom.com; (510) 419 6448 Abstract: To enhance

More information