On-load tap-changer OILTAP R

Size: px
Start display at page:

Download "On-load tap-changer OILTAP R"

Transcription

1 Technical Data TD 115

2 2 TD 115/02

3 Table of Contents Table of Contents 1 General Summary of the technical data Survey Technical Data Rated through-current (I u ), rated step voltage (U i ) and step capacity (P StN ) Contact life Rated withstand voltages of the internal insulation Appendix dimensional and installation drawings NOTE These technical data are intended for the calculator and designer of the transformer. These type-specific data are only valid in connection with the information contained in the general section (TD 61) since this section contains important information on such subjects as potential connection, leakage inductance, current division, and so on. Dimensional drawings and connection diagrams are subject to change without prior notice. Drawings submitted during bidding and ordering are always binding. Since the on-load tap-changer is delivered to the specifications of the transformer manufacturer, the transformer manufacturer is responsible for selecting the correct properties of the on-load tap-changer so that the requirements of the transformer are met. TD 115/02 3

4 1 General 1 General 1.1 Summary of the technical data On-load tap-changer R III 1200 Y R I 1201 R I 2002 R I ) R I 3003 Number of poles and application 3 (neutral point) Max. rated through current I um (in A) Rated short-time withstand current (in ka) Rated short-circuit duration (in s) Rated peak withstand current (in ka) Max. rated step voltage U im (in V) 1) Step capacity (P StN ) ) ) ) 6000 (in kva) Rated frequency (in Hz) 50 to 60 Operating positions Without change-over selector: max. of 18 With change-over selector: max. of 35 Rated insulation level Highest voltage for ) ) equipment U m (in kv) 5) Highest operating voltage U b ) (phase-phase) on diverter switch (in kv) Rated lightning impulse with stand voltage (in kv, 1.2 I 50) Rated switching impulse withstand voltage (in kv) AC withstand voltage (in kv, 50 Hz, 1 min.) Rated withstand voltages of see table 3 internal insulation Oil compartment Pressure-proof up to 0.3 bar continuous difference pressure (test pressure 0.6 bar), head and cover of the on-load tap-changer are vacuum-proof. Oil suction pipe Installed as standard (for details, see BA 18) Temperature range The on-load tap-changer OILTAP R can be operated in the rated load range with oil temperatures of -25 C to +105 C. Table 1 a 4 TD 115/02

5 1 General On-load tap-changer R III 1200 Y R I 1201 R I 2002 R I 2402 R I 3003 Weight (in kg) ca. without change ) over selector with change- 595 (770 4) ) 410 (500 4) ) 505 (640 4) ) 505 (640 4) ) 595 (780 4) ) over selector Displacement volume (in dm 3 ) ca kv 289 (367 4) ) 274 (353 4) ) 280 (360 4) ) 280 (360 4) ) 286 (367 4) ) 123 kv 314 (392 4) ) 299 (376 4) ) 305 (384 4) ) 305 (384 4) ) 311 (392 4) ) 170 kv 334 (412 4) ) 319 (396 4) ) 325 (404 4) ) 325 (404 4) ) 331 (412 4) ) 245 kv 354 (432 4) ) 339 (416 4) ) 345 (424 4) ) 345 (424 4) ) 351 (432 4) ) 300 kv 369 (446 4) ) 374 (453 4) ) 374 (453 4) ) 380 (461 4) ) Oil filling quantity V S and minimum volume DV 6) of the diverter switch oil compartment 72.5 kv kv kv kv kv 240 Table 1 b Notes for tables 1a and 1b: 1) The maximum rated step voltage may be exceeded by 10% due to overexcitation of the transformer if the step capacity is limited to its rated value. 2) Higher step capacities available as special design 3) Forced current division by two parallel winding branches required 4) Applies to tap selector size E 5) In accordance with VDE 0111, part 1: R.m.s. value of the phase-phase voltage for which a piece of equipment is rated for its insulation 6) Minimum volume of oil conservator for oil temperature ϑ = 30 C C: DV = 0,1 V S + 4 (dm 3 ) 7) On request 8) Oil filter unit 0F 100 (combi-filter) required, U bst > 300 kv on request 9) Rated withstand voltages comply with IEC 60214: 1989; unrestricted tests possible up to 1050 kv or 460 kv, 50 Hz, 1 min. TD 115/02 5

6 1 General 1.2 Survey E_01 Fig. 1a Survey of the on-load tap-changer designs (no. of poles, change-over selector, and installation lengths) 6 TD 115/02

7 1 General E_02 Fig. 1b Survey of the on-load tap-changer designs (no. of poles, change-over selector, and installation lengths) TD 115/02 7

8 1 General Survey of the basic connection diagrams (figures 2a, 2b, 2c) with designation of the tap selector contact terminals in accordance with MR standards. This contact terminal designation corresponds to the specifications in the on-load tap-changer dimensional drawings. Fig. 2a excerpt from E_1 8 TD 115/02

9 1 General Fig. 2b D_2 TD 115/02 9

10 1 General Fig. 2c D_3 10 TD 115/02

11 1 General Examples of connection diagrams (contact designation in acc. w. MR standards) Fig. 3 Example: On-load tap-changer R III 1200 Y C/D, basic connection diagram W TD 115/02 11

12 1 General Fig. 4 Example: On-load tap-changer R III 1200 Y E, basic connection diagram G 12 TD 115/02

13 1 General Fig. 5 Example: On-load tap-changer R I 2002 C/D, basic connection diagram W TD 115/02 13

14 1 General Fig. 6 Example: On-load tap-changer R I 3003 C/D, basic connection diagram W 14 TD 115/02

15 2 Technical Data 2 Technical Data 2.1 Rated through-current (I u ), rated step voltage (U i ) and step capacity (P StN ) On-loadtap-changer R I 2003 R III 1200 Y R I 1201 R I 2002 (Special design) R I ) R I 3003 I u (A) U i (V) P StN (kva) Table 2 Rated through-currents (I u ), related rated step voltages (U i ) and step capacities (P StN ), at highest and lowest rated step voltage of the step capacity curve (see fig. 7 and fig. 8) 1) Note: R I 2402 with forced current division by two parallel winding branches Fig. 7 Step capacities (rated step voltages U i, rated throughcurrents I u ) for on-load tap-changer R III 1200 Y, R I 1201, R I E CAUTION: Only applies to network service. When used for industrial transformers, please contact us. TD 115/02 15

16 2 Technical Data E Fig. 8 Step capacities (rated step voltages U i, rated through-currents I u ) for on-load tap-changer R I 2002, R I 2003 (= special design), R I 2402, R I Note: 1) R I 2402 with forced current division by two parallel winding branches. CAUTION: Only applies to network service. When used for industrial transformers, please contact us. 16 TD 115/02

17 2 Technical Data 2.2 Contact life The mean expected contact life of the arcing diverter switch contacts can be estimated based on the relative load (I u / I um ) as shown in figure 9. Since actual contact life in individual cases depends on many influencing factors while in service, only estimations can be given (not applicable to constant current service). The inspection regulations must be observed. Fig. 9 Expected mean contact life under average load n Number of operations I u Rated through-current I um Max. rated through-current KHW TD 115/02 17

18 2 Technical Data 2.3 Rated withstand voltages of the internal insulation Fig. 10 shows diagrams of the voltage stress present on the tap winding of the three primary basic connections of threepole on-load tap-changers and single-pole on-load tap-changers. When selecting the on-load tap-changer, a check must be made to determine whether the highest stress on the tap selector does not exceed the related rated withstand voltages. Without change-over selector With reversing switch With coarse tap selector in (+) - position With coarse tap selector in (-) - position M CAUTION Adhere to the maximum rated lightning impulse withstand voltage stress on a0 in mid-position. a0 = Between preselected and selected tapping on the diverter switch a1 = Between tap selector contacts of the winding of one tap position (connected or not) a = Between beginning and end of a tapped winding and, with coarse tap winding, between beginning and end of a coarse tap winding. Note for coarse tapping arrangement in (-) -position of the change-over selector: When stressed with impulse voltage, the permissible withstand voltage a must be adhered to between the end of a coarse tap winding connected with the K tap selector contact and the tap selector contact at the end of the tapped winding of the same phase. b = Between the tap selector contacts of different phases and between change-over selector contacts of different phases, which are connected with the beginning/end of a tapped winding or with a tap selector contact. f = Between diverter switch terminal and ground Additional for coarse tapping arrangement in (+) - position of the change-over selector: c1 = From one (-) -change-over selector contact to terminal of the same phase. c2 = Between (-) -change-over selector contacts of different phases Fig. 10 Rated withstand voltages 18 TD 115/02

19 2 Technical Data Insulation Tap selector size C Tap selector size D 1) Tap selector size E distances kv 1.2I50 kv, 50 Hz, 1 min kv 1.2I50 kv, 50 Hz, 1 min kv 1.2I50 kv, 50 Hz, 1 min a0 U b 72.5 kv: 140 kv 1.2I50; 30 kv, 50 Hz, 1 min / U b >72.5 kv: 80 kv 1.2I50; 3 x U St a a ) b 3) ) c ) c Table 3 Note: Rated withstand voltages (in kv) of the internal insulation of the tap selector 1) Tap selectors in accordance with basic connection diagrams W, W, W are designed as W, W, W. Tap selectors in accordance with basic connection diagrams W and W are not possible. 2) Higher values up to 550 kv on request 3) Omitted for on-load tap-changers R I 1201, R I 2002/2402, R I 3003 The tap selector size (ID letters C, D, E) characterizes the internal insulation of the tap selector whose rated withstand voltages must be adjusted to the requirements of the transformer winding. The permissible maximum service voltage along the individual tap selector paths is half the AC withstand voltages listed in table 3. TD 115/02 19

20 3 Appendix 3 Appendix Dimensional drawings III 1200 Y, tap selector size C/D, E , I 1201, tap selector size C/D, E , I 2002, tap selector size C/D, E , I 2402, tap selector size C/D, E , I 3003, tap selector size C/D, E , Tap selector and change-over selector terminal contacts, tap selector size E Installation drawings Tap selector size C/D Tap selector size E Additional drawings On-load tap-changer head On-load tap-changer cover with mounting flange for pressure relief valve Versions of the on-load tap-changer head, swiveling range of gear unit Special design for installation in bell-type tanks Horizontal drive shaft, tap selector size C/D, E , Jumpers for parallel connection of tap selector terminal contacts for on-load tap-changer OILTAP R I 2002, R I 3003, selector size C/D, E , Tap selector bottom, shielding, tap selector size C/D Tap selector bottom, tap selector size E Tie-in resistors, tap selector size C/D , Potential switch, tap selector size C/D, E , Additional drawings for on-load tap-changer TD 115/02

21 E R III C/D, dimension drawing TD 115/02 21

22 E R III E, dimension drawing 22 TD 115/02

23 E R I C/D, dimension drawing TD 115/02 23

24 E R I E, dimension drawing 24 TD 115/02

25 E R I C/D, dimension drawing TD 115/02 25

26 E R I E, dimension drawing 26 TD 115/02

27 E R I C/D, with forced current division with two parallel winding branches, dimension drawing TD 115/02 27

28 E R I E, with forced current division with two parallel winding branches, dimension drawing 28 TD 115/02

29 E R I C/D, dimension drawing TD 115/02 29

30 E R I E, dimension drawing 30 TD 115/02

31 E Tap selector size E, tap selector and change-over selector terminal contacts TD 115/02 31

32 E Tap selector size C/D, installation drawing 32 TD 115/02

33 E Tap selector size E, installation drawing TD 115/02 33

34 893899AE On-load tap-changer OILTAP MS, M, R, RM On-load tap-changer head, centric drive 34 TD 115/02

35 E On-load tap-changer OILTAP MS, M, R, RM With flange for pressure relief valve TD 115/02 35

36 E Versions of the on-load tap-changer head, swiveling range and drive direction of the gear unit 36 TD 115/02

37 E On-load tap-changer OILTAP MS, M, R, RM Special design for installation in bell-type tank O-Ring ,7 Lifting device Suction pipe Drilling hole in sectional plane Transformer cover O-Ring Level traverse Guiding ring with U m = 170 kv, 245 kv, 300 kv Supporting flange Level traverse Z = Guiding pin Drive side of the tap selector TD 115/02 37

38 E On-load tap-changer OILTAP MS, M, R, RM Horizontal drive shaft (limit dimensions) Tap selector size C/D, centric drive 38 TD 115/02

39 E Horizontal drive shaft (limit dimensions) Tap selector size E, centric drive TD 115/02 39

40 E R I 2002, R I 3003, tap selector size C/D Jumpers for parallel connection of tap selector terminal contacts 40 TD 115/02

41 E R I 2002, R I 3003, tap selector size E Jumpers for parallel connection of tap selector terminal contacts TD 115/02 41

42 E On-load tap-changeroiltap R Tap selector size C/D, tap selector bottom shown with the lowest parts connected to the voltage, standard design without grading ring, special design with grading ring 42 TD 115/02

43 E Tap selector size E, tap selector bottom shows lowest parts connected to voltage TD 115/02 43

44 E Tap selector size C/D, principal arrangement of potential switch and tie-in resistors 44 TD 115/02

45 M Tie-in resistor cylinder R I to WP, tap selector size C/D, U m = 72.5 kv to 300 kv, 2 x 14 to 2 x 18 resistors TD 115/02 45

46 M Tie-in resistor cylinder R I to WP, tap selector size C/D, U m = 72.5 kv to 300 kv, 2 x 3, 2 x 5, to 2 x 13 resistors 46 TD 115/02

47 M Tie-in resistor cylinder R I to WP, tap selector size C/D, U m = 72.5 kv to 300 kv, 2 x 4, 2 x 6 to 2 x 12 resistors TD 115/02 47

48 M Tie-in resistor cylinder R I to WP, tap selector size C/D, U m = 72.5 kv to 300 kv, 3 to 26 resistors 48 TD 115/02

49 M Tie-in resistor cylinder R I to WR, tap selector size C/D, U m = 72.5 kv to 300 kv, 2 x 14 to 2 x 18 resistors TD 115/02 49

50 M Tie-in resistor cylinder R I to WR, tap selector size C/D, U m = 72.5 kv to 300 kv, 2 x 3, 2 x 5, to 2 x 13 resistors 50 TD 115/02

51 M Tie-in resistor cylinder R I to WR, tap selector size C/D, U m = 72.5 kv to 300 kv, 2 x 4, 2 x 6, to 2 x 12 resistors TD 115/02 51

52 M Tie-in resistor cylinder R I to WR, tap selector size C/D, U m = 72.5 kv to 300 kv, 3 to 26 resistors 52 TD 115/02

53 M Tie-in resistor cylinder R III 1200 WP, tap selector size C/D, U m = 72.5 kv to 245 kv, 3 x 2 to 3 x 7 resistors TD 115/02 53

54 M Tie-in resistor cylinder R III 1200 WP, tap selector size C/D, U m = 72.5 kv to 245 kv, 3 x 8 to 3 x 10 resistors 54 TD 115/02

55 M Tie-in resistor cylinder R III 1200 WR, tap selector size C/D, U m = 72.5 kv to 245 kv, 3 x 2 to 3 x 8 resistors TD 115/02 55

56 M Tie-in resistor cylinder R III 1200 WR, tap selector size C/D, U m = 72.5 kv to 245 kv, 3 x 9 to 3 x 11 resistors 56 TD 115/02

57 M Potential switch R III 1200 WS, R I to WS, tap selector size C/D, U m = 72.5 kv to 300 kv TD 115/02 57

58 M Potential switch R III 1200 WS, R I to WS, tap selector size E, U m = 72.5 kv to 300 kv 58 TD 115/02

59 E Additional drawings for on-load tap-changer Basic connection diagrams Tap selector and change-over selector terminal contacts, tap selector size E Tap selector bottom, shielding, tap selector size C/D Tap selector bottom, tap selector size E Versions of the on-load tap-changer head Horizontal drive shaft, tap selector size C/D Horizontal drive shaft, tap selector size E Installation drawing, tap selector size C/D Installation drawing, tap selector size E On-load tap-changer head TD 115/02 59

60 Maschinenfabrik Reinhausen GmbH Phone Falkensteinstrasse 8 Fax Regensburg, Germany sales@reinhausen.com Please note: The data in our publications may differ from the data of the devices delivered. We reserve the right to make changes without notice. TD 115/02 en 0903/1000 F Printed in Germany

The On-Load Tap-Changer for Maximum Switching Frequency More Switching Operations without Needing Maintenance.

The On-Load Tap-Changer for Maximum Switching Frequency More Switching Operations without Needing Maintenance. The On-Load Tap-Changer for Maximum Switching Frequency More Switching Operations without Needing Maintenance. new and even more cost effective. Today s on-load tap-changers for regulating transformers

More information

DS 600. A contact free flux gate based current measurement sensor 600A rms

DS 600. A contact free flux gate based current measurement sensor 600A rms DS 600 A contact free flux gate based current measurement sensor 600A rms DS 600 is member of the small housing sensor family. The family includes a 200A and a 600A version. 600A rms - 900A peak Maximum

More information

Pluggable interface relays CR-P Pcb relays

Pluggable interface relays CR-P Pcb relays 2CDC 293 034 F0004 1 2 4 3 Features 9 different supply s: DC versions: 12 V, 24 V, 48 V, 110 V AC versions: 24 V, 48 V, 110 V, 120 V, 230 V Output contacts: 1 c/o (16 A) or 2 c/o (8 A) Cadmium-free contact

More information

REVIEWED BY CAPITAL PROJECTS MANAGER (DAN REDDY) GENERAL MANAGER EQUIPMENT ENGINEERING & ASSET MANAGEMENT (HAMILTON NXUMALO)

REVIEWED BY CAPITAL PROJECTS MANAGER (DAN REDDY) GENERAL MANAGER EQUIPMENT ENGINEERING & ASSET MANAGEMENT (HAMILTON NXUMALO) SA Port Operations DOCUMENT TYPE: REFERENCE EEAM-Q-014 (ORIGINAL SPECIFICATION HE8.2.3 Ver5) REVISION 0 SPECIFICATION TITLE: SPECIFICATION FOR ELECTRICAL MOTORS AND GENERATORS PAGE 0 of 07 COMPILED BY

More information

Electronic timer CT-VBS.17+18 OFF-delayed without auxiliary voltage, for DC contactors Data sheet

Electronic timer CT-VBS.17+18 OFF-delayed without auxiliary voltage, for DC contactors Data sheet Characteristics Single-function OFF-delay timer for DC contactors, without auxiliary voltage Width.5 mm CDC 5 6 F3 Approvals A culus E CCC CT-VBS a Circuit diagram b Marker label Marks a CE b C-Tick Order

More information

OLI. Oil level indicator

OLI. Oil level indicator OLI Oil level indicator Oil level indicator Unexpected or accidental oil leakages may occur randomly along transformer s lifetime. Clear indication of oil level inside transformer tank and on load tap

More information

High-Voltage Circuit-Breakers 3AP1/2 72.5 kv up to 550 kv. Power Transmission and Distribution

High-Voltage Circuit-Breakers 3AP1/2 72.5 kv up to 550 kv. Power Transmission and Distribution High-Voltage Circuit-Breakers AP/ 7.5 kv up to 550 kv Power Transmission and Distribution The AP/ High-Voltage Circuit-Breakers Now Applicable for 550 kv Decades of our experience in high-voltage switching

More information

1ZSE 2750-105 en, Rev. 8. Transformer bushings, type GOE and GOE(2) Technical guide

1ZSE 2750-105 en, Rev. 8. Transformer bushings, type GOE and GOE(2) Technical guide 1ZSE 2750-105 en, Rev. 8 Transformer bushings, type GOE and GOE(2) Technical guide Original instruction The information provided in this document is intended to be general and does not cover all possible

More information

UniGear ZS1. Medium voltage, arc proof, air insulated switchgear for primary distribution

UniGear ZS1. Medium voltage, arc proof, air insulated switchgear for primary distribution UniGear ZS1 Medium voltage, arc proof, air insulated switchgear for primary distribution UniGear ZS1: an innovative solution for all installation requirements ABB UniGear is medium voltage metal-clad,

More information

3/2- and 2/2-way cartridge valve type BVE

3/2- and 2/2-way cartridge valve type BVE 3/2- and 2/2-way cartridge valve type BVE for any flow direction, zero leakage, all ports pressure resistant Flow Q max = 70 lpm Perm. pressure p max = 400 bar Additional valves with same function: ' Type

More information

Tool Turrets and Tool Discs

Tool Turrets and Tool Discs Our other products Automatic Tool Changer Chucking Cylinders Tool Discs Indexing Tables Tool Turrets and Tool Discs Pragati Automation Pvt. Ltd. 1, IV Phase, 11th Cross, Peenya Industrial Area Bangalore

More information

Lightning Arresters P30027 18 KVA P30038 10 KVA. Description & Installation

Lightning Arresters P30027 18 KVA P30038 10 KVA. Description & Installation Lightning Arresters P30027 18 KVA P30038 10 KVA Description & Installation Printed in USA 09/11 TO330 Rev. B Table of Contents Page 1.0 SCOPE 2 2.0 PRODUCT OVERVIEW 2 2.1 Intended Uses 2 2.2 Lightning

More information

THE OLTC AS AN "OIL ISOLATED SYSTEM" IN THE TRANSFORMER & OIL ANALYSIS IN OLTC. I Hr. Dr. Hurm, Hr. Dr. Schübel I 26.06.2014 I

THE OLTC AS AN OIL ISOLATED SYSTEM IN THE TRANSFORMER & OIL ANALYSIS IN OLTC. I Hr. Dr. Hurm, Hr. Dr. Schübel I 26.06.2014 I THE OLTC AS AN "OIL ISOLATED SYSTEM" IN THE TRANSFORMER & OIL ANALYSIS IN OLTC MR Hr. Dr. Hurm, MESSKO Hr. Dr. Schübel 26.06.2014 Seite 1 von 39 Table of contents Part 1: 1. Introduction: working principle

More information

3/2-way Solenoid Valve, direct-acting, NC or NO

3/2-way Solenoid Valve, direct-acting, NC or NO 3/2-way Solenoid Valve, direct-acting, NC or NO Electrical connection cable plug, Form A With or without manual override as standard Threaded port and sub-base s Impulse optional Type 6014 can be combined

More information

Power transformers. Special transformers Railway

Power transformers. Special transformers Railway Power transformers Special transformers Railway A leader in railway systems Our compact and low-weight transformers fully comply with the customer s specifications. The products are developed together

More information

ALTERNATIVE METHODS FOR INTERNAL ARC TESTS ON 12 KV AND 24 KV METAL-ENCLOSED SWITCHGEARS WITH COMPACT RMU

ALTERNATIVE METHODS FOR INTERNAL ARC TESTS ON 12 KV AND 24 KV METAL-ENCLOSED SWITCHGEARS WITH COMPACT RMU ALTERNATIVE METHODS FOR INTERNAL ARC TESTS ON 12 KV AND 24 KV METAL-ENCLOSED SWITCHGEARS WITH COMPACT RMU George CURCANU, Constantin ILINCA, Ilie SBORA ICMET Craiova, Romania, Calea Bucuresti 144, phone:

More information

Magnetic and Hydraulic-Magnetic Circuit Breaker 8340-G2...

Magnetic and Hydraulic-Magnetic Circuit Breaker 8340-G2... Magnetic and Hydraulic-Magnetic Circuit Breaker 840-G2... Description Single, two and three pole magnetic circuit breakers with trip-free mechanism and push/pull on/off manual actuation. A choice of fast

More information

5SV Residual Current Protective Devices

5SV Residual Current Protective Devices s Siemens AG 2013 SENTRON 5SV Residual Current Protective Devices New portfolio for reliable personnel, material and fire protection Safe protection against residual currents Residual current protective

More information

RY2 miniature industrial relays

RY2 miniature industrial relays 6 RY2 Relays of general application For plug-in sockets, 35 mm rail mount acc. to PN-EN 60715 or on panel mounting Flat insert connectors - faston x 0,5 mm Recognitions, certifications, directives: RoHS,

More information

Mounting Instructions. Torque Transducer. A0329 3.2 en

Mounting Instructions. Torque Transducer. A0329 3.2 en Mounting Instructions Torque Transducer T5 T5 Contents 3 Page Safety instructions.............................................. 4 1 Measuring characteristics..................................... 7 2 Mounting.....................................................

More information

Emergency stop As an emergency switching off/emergency stop device. Standards According to IEC/EN 60204-1, VDE 0113 Part 1

Emergency stop As an emergency switching off/emergency stop device. Standards According to IEC/EN 60204-1, VDE 0113 Part 1 MainswitchSurfacemounting Partno. P3-63/I4/SVB Articleno. 207343 CatalogNo. SP3-063-I4CRQ IP65 Deliveryprogramme Product range Switch-disconnectors Basic function Main switches Maintenance switches Manual

More information

1ZSC000563-AAC en, Rev. 7. Resin impregnated paper bushing, oil to air, type GSB Technical guide

1ZSC000563-AAC en, Rev. 7. Resin impregnated paper bushing, oil to air, type GSB Technical guide 1ZSC000563-AAC en, Rev. 7 Resin impregnated paper bushing, oil to air, type GSB Technical guide Original instruction The information provided in this document is intended to be general and does not cover

More information

High-Voltage Compact Switchgear 3AP1 DTC for 145 kv and 245 kv

High-Voltage Compact Switchgear 3AP1 DTC for 145 kv and 245 kv High-Voltage Compact Switchgear AP1 DTC for 1 kv and kv Answers for energy. The AP1 DTC Complying with our Customers demands Experience you can rely on - at anytime, anywhere Decades of experience in high-voltage

More information

Pressure monitoring equipment for oil-sf 6. bushings, type GOEK

Pressure monitoring equipment for oil-sf 6. bushings, type GOEK Pressure monitoring equipment for oil-sf 6 bushings, type GOEK Installation and maintenance guide 5693 827-6 en, Rev. 3, 2002-01-30 This document must not be copied without our written permission, and

More information

PM734F - Technical Data Sheet Winding 28

PM734F - Technical Data Sheet Winding 28 - Technical Data Sheet Winding 28 SPECIFICATIONS & OPTIONS STANDARDS STAMFORD AC generators are designed to meet the performance requirements of IEC EN 60034-1. Other international standards, including

More information

40 Series - Miniature PCB/Plug-in relays 8-10 - 16 A. Features 40.31 40.51 40.52

40 Series - Miniature PCB/Plug-in relays 8-10 - 16 A. Features 40.31 40.51 40.52 Features 40.31 40.51 40.52 1 & 2 Pole relay range 40.31-1 Pole 10 A (3.5 mm pin pitch) 40.51-1 Pole 10 A (5 mm pin pitch) 40.52-2 Pole 8 A (5 mm pin pitch) PCB mount - direct or via PCB socket 35 mm rail

More information

Transformer Bushings for GIS

Transformer Bushings for GIS Transformer Bushings for GIS Oil to SF6 Connections GARIP RTKG 725-55 kv SQS certified ISO 91 / ISO 141 Bushings RIP - Technology for SF6 / Oil - Bushings In modern metal enclosed switchgear SF6 -gas is

More information

Aluminum Electrolytic Capacitors Axial Miniature, Long-Life

Aluminum Electrolytic Capacitors Axial Miniature, Long-Life Aluminum Electrolytic Capacitors Axial Miniature, Long-Life 38 AML 0 ASM smaller dimensions Fig. QUICK REFERENCE DATA DESCRIPTION Nominal case sizes (Ø D x L in mm) 6.3 x.7 to 0 x 5 VALUE 0 x 30 to x 38

More information

Step Voltage Regulators

Step Voltage Regulators Step Voltage Regulators Don Wareham Field Application Engineer Today s Agenda Introduction Voltage Regulator theory Voltage Regulator application considerations Installation and proper bypassing Wrap-up/questions

More information

In addition to the basic models, it is also possible for the units to be outfitted with add-ons.

In addition to the basic models, it is also possible for the units to be outfitted with add-ons. 1-1202-EN Gear ump Units For single-line centralized lubrication systems MFE5-KW3-2 MFE5-KW6 MFE5-BW7 These units comprising the MFE Group are designed to supply the lubricant used in intermittently operated,

More information

Electronic overload relay EF19 and EF45

Electronic overload relay EF19 and EF45 Data sheet Electronic overload relay EF19 and EF45 Electronic overload relays offer reliable protection in case of overload and phase-failure. They are the alternative to thermal overload relays. Motor

More information

Lightning current simulation in the laboratory - parameters, procedures and test equipment -

Lightning current simulation in the laboratory - parameters, procedures and test equipment - Lightning current simulation in the laboratory - parameters, procedures and test equipment - Dipl.-Ing. J. Schönau, Dr.-Ing. M. Naß, CE-LAB GmbH Prof. Dr.-Ing. F. Berger, Ilmenau University of Technology

More information

produces and delivers products worldwide can provide the optimal are dedicated to supplying you with superior advice and global support.

produces and delivers products worldwide can provide the optimal are dedicated to supplying you with superior advice and global support. www.ppcinsulators.com The very Best. The very Best. That s what we deliver. ong od Insulators Only a company that develops, produces and delivers products worldwide can provide the optimal solution for

More information

Technical Information Requirement for MV transformers and transformer for internal power supplies for SUNNY CENTRAL

Technical Information Requirement for MV transformers and transformer for internal power supplies for SUNNY CENTRAL Technical Information Requirement for MV transformers and transformer for internal power supplies for SUNNY CENTRAL SC_Trafo-TI-en-62 Version 6.2 ENGLISH Table of Contents SMA Solar Technology Table of

More information

Technical data UNIBLOCK UBSF 180 625

Technical data UNIBLOCK UBSF 180 625 Data TECHNICL DT Technical data UNIBLOCK UBSF 80 6 Output data Type UBSF 80 UBSF 0 UBSF 00 UBSF 6 Output power 80 kv 0 kv 00 kv 6 kv Output voltage 80/77 V 0/ V 0/ V 0/ V Output current 7 8 66 80 Power

More information

High-ohmic/high-voltage resistors

High-ohmic/high-voltage resistors FEATURES These resistors meet the safety requirements of: UL1676 (range 510 kω to 11 MΩ) EN60065 BS60065 (U.K.) NFC 92-130 (France) VDE 0860 (Germany) High pulse loading capability Small size. APPLICATIONS

More information

Electronic overload relay EF65, EF96 and EF146

Electronic overload relay EF65, EF96 and EF146 Data sheet Electronic overload relay EF65, EF96 and EF146 Electronic overload relays offer reliable protection in case of overload and phase-failure. They are the alternative to thermal overload relays.

More information

Electronic timer CT-AHD.12 OFF-delayed with 1 c/o (SPDT) contact

Electronic timer CT-AHD.12 OFF-delayed with 1 c/o (SPDT) contact Data sheet Electronic timer CT-AHD.12 OFF-delayed with 1 c/o (SPDT) contact The CT-AHD.12 is an electronic time relay with OFF-delay. It is from the CT-D range. With their MDRC profile and a width of only

More information

2. INDUCTIVE VOLTAGE TRANSFORMERS Oil-paper insulation Gas insulation

2. INDUCTIVE VOLTAGE TRANSFORMERS Oil-paper insulation Gas insulation 2. INDUCTIVE VOLTAGE TRANSFORMERS Oil-paper insulation Gas insulation 123 kv Inductive Fingrid (Finland). 18 Instrument transformers igh voltage INTRODUCTION Inductive voltage transformers are designed

More information

Type: DILM32 10(24V50HZ) Article No.: 277247

Type: DILM32 10(24V50HZ) Article No.: 277247 Type: DILM32 10(24V50HZ) Article No.: 277247 Ordering information Rated operational current AC 3 400 V I e A 32 Max. rating for three phase motors, 50 60 Hz AC 3 230 V Max. rating for three phase motors,

More information

LOW VOLTAGE RING TYPE MEASURING CURRENT TRANSFORMERS

LOW VOLTAGE RING TYPE MEASURING CURRENT TRANSFORMERS Specification for LOW VOLTAGE RING TYPE MEASURING CURRENT TRANSFORMERS CEYLON ELECTRICITY BOARD SRI LANKA Specification for LOW VOLTAGE RING TYPE MEASURING CURRENT TRANSFORMERS CEB Standard 027: 1998 CEYLON

More information

Power Supply and Indicator Unit Type 5024-1. Fig. 1 Type 5024-1. Mounting and Operating Instructions EB 9539 EN

Power Supply and Indicator Unit Type 5024-1. Fig. 1 Type 5024-1. Mounting and Operating Instructions EB 9539 EN Power Supply and Indicator Unit Type 5024-1 Fig. 1 Type 5024-1 Mounting and Operating Instructions EB 9539 EN Edition October 2003 Application 1 Application The Type 5024-1 Power Supply and Indicator Unit

More information

MNS is Switchgear System Technical Overview

MNS is Switchgear System Technical Overview Switchgear System Technical Overview Innovative Design ABB s innovative MNS is concept combines the long term experience, energy efficiency, grid reliability and industrial productivity of the well-known

More information

Medium Voltage Products. ZN1 12 kv arc-proof air-insulated switchgear for primary distribution

Medium Voltage Products. ZN1 12 kv arc-proof air-insulated switchgear for primary distribution Medium Voltage Products ZN1 12 kv arc-proof air-insulated switchgear for primary distribution ZN1 an innovative switchgear for power distribution requirements ABB ZN1 primary distribution switchgear is

More information

QPM3 Low pressure pump for circulation of oil in hydraulic and lubricating systems

QPM3 Low pressure pump for circulation of oil in hydraulic and lubricating systems The Professional Choice in Fluid Management QPM3 Low pressure pump for circulation of oil in hydraulic and lubricating systems The Olaer Group is a global player specialising in innovative, efficient system

More information

TECHNICAL SPECIFICATION FOR PROJECTION WELDING MACHINE (Qty. 2 Nos.)

TECHNICAL SPECIFICATION FOR PROJECTION WELDING MACHINE (Qty. 2 Nos.) TECHNICAL SPECIFICATION FOR PROJECTION WELDING MACHINE (Qty. 2 Nos.) 1. Requirement: Two (02) Nos. DC Type, 3 phase, 3 wire Projection Welding Machine is required for welding of ventilation M.S. / Stainless

More information

Fig B36 Stainless Steel 'T' Type or Basket Type Strainers

Fig B36 Stainless Steel 'T' Type or Basket Type Strainers Local regulations may restrict the use of this product to below the conditions quoted. In the interests of development and improvement of the product, we reserve the right to change the specification without

More information

Type: DILM115(RAC240) Article No.: 239548 Sales text Contactor,55kW/400V,AC operated. Ordering information

Type: DILM115(RAC240) Article No.: 239548 Sales text Contactor,55kW/400V,AC operated. Ordering information Type: DILM115(RAC240) Article No.: 239548 Sales text Contactor,55kW/400V,AC operated Ordering information Connection technique Description Description Rated operational current Screw terminals 3 pole AC

More information

Medium voltage insulator

Medium voltage insulator Medium voltage insulator Line post insulators type R-ET Commercial designation LPI 24 N ET 1) LPI 24 L ET/5 1)2) LPI 24 L ET/6 1)2) LPI 38 L ET 1) esignation acc. to IEC 720 R 12,5 ET 125 N R 12,5 ET 125

More information

Aluminum Electrolytic Capacitors Power Eurodin Printed Wiring

Aluminum Electrolytic Capacitors Power Eurodin Printed Wiring Aluminum Electrolytic Capacitors Power Eurodin Printed Wiring 00/0 PEDPW Fig. QUICK REFERENCE DATA DESCRIPTION VALUE 00 0 Nominal case size (Ø D x L in mm) x 0 to 0 x 00 Rated capacitance range 0 μf to

More information

PPS-PPQ-BT-PIAS RESIN INSULATORS FOR OIL INSULATED ELECTRICAL MACHINES

PPS-PPQ-BT-PIAS RESIN INSULATORS FOR OIL INSULATED ELECTRICAL MACHINES PPS-PPQ-BT-PIAS RESIN INSULATORS FOR OIL INSULATED ELECTRICAL MACHINES BUSHING WITH PLUG CONNECTION WITH OUTER CONE PPS CHARACTERISTICS The PPS bushing can be used as a fixed section for the entry of medium

More information

WWW.SMETS-TECHNOLOGY.COM COMBI. 7 SW COMBINED. SEWER. CLEANING. TRUCK ENGLISH 01. 2013 INNOVATIONS FOR POWERFUL PERFORMANCES

WWW.SMETS-TECHNOLOGY.COM COMBI. 7 SW COMBINED. SEWER. CLEANING. TRUCK ENGLISH 01. 2013 INNOVATIONS FOR POWERFUL PERFORMANCES WWW.SMETS-TECHNOLOGY.COM COMBI. 7 SW COMBINED. SEWER. CLEANING. TRUCK ENGLISH 01. 2013 INNOVATIONS FOR POWERFUL PERFORMANCES COMBI. 7 SW COMBINED. SEWER. CLEANING. TRUCK PAGE 02 ENGLISH STATUS 01. 2013

More information

UFES Active protection for switchgear

UFES Active protection for switchgear Active protection for switchgear ABB AG Oberhausener Strasse 4047 Ratingen, Germany Phone: +49 0-0 Fax: +49 0-7 77 Note: We reserve the right to make technical changes or modify the contents of this document

More information

The complete range of consumer switchboards and switchgear

The complete range of consumer switchboards and switchgear Power Distribution The complete range of consumer switchboards and switchgear www.nhp.com.au/mod6 The MOD6 range of consumer switchboards and switchgear is specifically designed for domestic and commercial

More information

Type: DILM9 10(24VDC) Article No.: 276705

Type: DILM9 10(24VDC) Article No.: 276705 Type: DILM9 10(24VDC) Article No.: 276705 Ordering information Rated operational current AC 3 400 V I e A 9 Max. rating for three phase motors, 50 60 Hz AC 3 230 V Max. rating for three phase motors, 50

More information

www.siemens.com/energy High Voltage Circuit Breakers 3AP Type 72.5 kv to 800 kv Answers for energy.

www.siemens.com/energy High Voltage Circuit Breakers 3AP Type 72.5 kv to 800 kv Answers for energy. s www.siemens.com/energy High Voltage Circuit Breakers AP Type 7.5 kv to 800 kv Answers for energy. The AP High Voltage Circuit Breakers Available up to 800 kv Decades of our experience in high voltage

More information

Directional seated valves type VP 1

Directional seated valves type VP 1 Directional seated valves type VP 1 zero leakage, intended for general hydraulic applications and grease lubing systems Flow Q max Operation pressure p max = 15 lpm = 400 bar Individual valve Individual

More information

MEDIUM AND HIGH VOLTAGE CAPACITORS, CAPACITOR BANKS AND SYSTEMS

MEDIUM AND HIGH VOLTAGE CAPACITORS, CAPACITOR BANKS AND SYSTEMS MEDIUM AND HIGH VOLTAGE CAPACITORS, CAPACITOR BANKS AND SYSTEMS Meher Capacitors offers reliable and innovative products and solutions in the fields of Reactive Power Compensation, Power Quality and Energy

More information

Current valve. for AC 24 V pulse/pause control of electrical loads up to 30 kw

Current valve. for AC 24 V pulse/pause control of electrical loads up to 30 kw 4 937 DESIO Current valve for AC 24 V pulse/pause control of electrical loads up to 30 kw SEA45.1 Use The current valve is used for the control of electric heating elements in heating, ventilation and

More information

Basic Load Tap Changer Operation

Basic Load Tap Changer Operation Basic Load Tap Changer Operation Topics Basic Transformer Theory Differences from LTC s to DETC s LTC Definitions Transformer Nameplates Purpose of a Tap Changer How Does an LTC Work? Topics Reactance

More information

Our brand POWER DYNAMIC PASSION COMMITMENT CREATIVITY. A strong brand for strong products: 8PU Premium. MV Energy

Our brand POWER DYNAMIC PASSION COMMITMENT CREATIVITY. A strong brand for strong products: 8PU Premium. MV Energy Our brand A strong brand for strong products: The ENERGOLINE brand represents our product portfolio of INDUSTRIAL SWITCHGEAR SYSTEMS. Our products are characterized by a high degree of safety, flexibility

More information

A10VSO Nominal size 18 see RD 92712 A10VSO Nominal size 28...140 see RD 92711

A10VSO Nominal size 18 see RD 92712 A10VSO Nominal size 28...140 see RD 92711 A10VO Nominal size 18 see RD 92712 A10VO Nominal size 28...140 see RD 92711 The variable displacement axial piston pump A10VO in swashplate design was designed for hydrostatic drives in open circuits.

More information

PRODUCT GUIDE. SL Medium Voltage IEC Vacuum Contactors

PRODUCT GUIDE. SL Medium Voltage IEC Vacuum Contactors PRODUCT GUIDE SL Medium Voltage IEC Vacuum Contactors Table of Contents 1 Overview Introduction....................................................2 Features........................................................2

More information

MANTA Piston Distributor for Oil and Fluid Grease

MANTA Piston Distributor for Oil and Fluid Grease MANTA Piston Distributor for Oil and Fluid Grease Function Piston distributors meter out and distribute the oil delivered by an intermittently actuated pump. The quantities of oil for the individual lube

More information

Voltage Rated operating voltage [kv] 12 24 Rated power frequency withstand voltage [kv] 28 50 Rated lightning impulse withstand voltage [kv] 75 125

Voltage Rated operating voltage [kv] 12 24 Rated power frequency withstand voltage [kv] 28 50 Rated lightning impulse withstand voltage [kv] 75 125 Standards and Regulations IEC 62271-200 ; VDE 0671-200 ; BS EN 62271-200 Technical Data MC3-12 MC3-24 Voltage Rated operating voltage [kv] 12 24 Rated power frequency withstand voltage [kv] 28 50 Rated

More information

R.C.C.B. s two-pole LEXIC

R.C.C.B. s two-pole LEXIC 87045 LIMOGES Cedex Telephone : (+33) 05 55 06 87 87 Fax : (+ 33) 05 55 06 88 88 R.C.C.B. s two-pole LEXIC 089 06/09/10/11/12/15/16/17/18/ 27/28/29/30/35, CONTENTS PAGES 1. Electrical and mechanical characteristics...

More information

World Leader in HV Testing Technology

World Leader in HV Testing Technology World Leader in HV Testing Technology Cable Fault Locators w/tdr Oil/Fluid Dielectric Testers Very Low Frequency AC Technology W/TD & PD Diagnostics Portable AC Hipots ---------------------------------

More information

Series 8146/5-V37 and Series 8150/5-V37

Series 8146/5-V37 and Series 8150/5-V37 www.stahl.de > Clear assignment safe technology easy installation > Intelligent structure only one rotary actuator for frequency-controlled drives ) 20 ms leading auxiliary contact for safe motor disconnection

More information

Aluminum Electrolytic Capacitors Power Economic Printed Wiring

Aluminum Electrolytic Capacitors Power Economic Printed Wiring Aluminum Electrolytic Capacitors Power Economic Printed Wiring 0/0 PECPW 00/0 PEDPW Fig. QUICK REFERENCE DATA DESCRIPTION high ripple current 0/0 PECPW long life 0 C Nominal case size (Ø D x L in mm) Rated

More information

38 SERIES. Relay interface modules 0.1-2 - 3-5 - 6-8 - 16 A. EMR Electromechanical Relays. Common features. SSR Solid State Relays. 6.

38 SERIES. Relay interface modules 0.1-2 - 3-5 - 6-8 - 16 A. EMR Electromechanical Relays. Common features. SSR Solid State Relays. 6. 38 Relay interface modules 0.1-2 - 3-5 - 6-8 - 16 A 38 Common features Instant ejection of relay by plastic retaining clip Integral coil indication and protection circuit 6.2 mm wide EMR - DC, AC or AC/DC

More information

BOWIE PUMPS OPERATION - MAINTENANCE

BOWIE PUMPS OPERATION - MAINTENANCE BOWIE PUMPS OPERATION - MAINTENANCE PUMPING PRINCIPLE: The meshing owieeof the gears cause a slight depression, with the resulting enmeshing of the gears causing a vacuum drawing the fluid being pumped

More information

NF71E-.. / NFZ71E-.. Contactor Relays AC / DC Operated - with Screw Terminals

NF71E-.. / NFZ71E-.. Contactor Relays AC / DC Operated - with Screw Terminals Technical Datasheet 1SBC101433D0201 28/03/11 NF71E-.. / NFZ71E-.. Contactor Relays AC / DC Operated - with Screw Terminals NF(Z) contactor relays are used for switching auxiliary and control circuits.

More information

Type: DILM50(230V50HZ,240V60HZ) Article No.: 277830

Type: DILM50(230V50HZ,240V60HZ) Article No.: 277830 Type: DILM50(230V50HZ,240V60HZ) Article No.: 277830 Ordering information Rated operational current AC 3 400 V I e A 50 Max. rating for three phase motors, 50 60 Hz AC 3 230 V Max. rating for three phase

More information

HSP GmbH Zum Handwerkerhof 2 90530 Wendelstein Tel. 09129 / 2852-0 Fax: 09129 / 2852-11 Web: www.hsshsp.de EMAIL: HSP@hsshsp.de NTG-3000.

HSP GmbH Zum Handwerkerhof 2 90530 Wendelstein Tel. 09129 / 2852-0 Fax: 09129 / 2852-11 Web: www.hsshsp.de EMAIL: HSP@hsshsp.de NTG-3000. NTG-3000 Transducer Data Sheet Document Version 2.8 Page 1 of 10 Versions / Revisions: Document Creation Author Description version date 2.0 2012-07-25 P. Compensis First official version 2.1 2012-08-24

More information

NATUS NES / NES-H Draw-out Type Medium Voltage Switchgear Systems. Safe energy distribution that meets the highest industrial requirements

NATUS NES / NES-H Draw-out Type Medium Voltage Switchgear Systems. Safe energy distribution that meets the highest industrial requirements NATUS NES / NES-H Draw-out Type Medium Voltage Switchgear Systems Safe energy distribution that meets the highest industrial requirements NATUS switchgear systems your advantages minimal use of insulant

More information

Technical Description. Transistor D.C. Chopper Controller Type GS 24 S

Technical Description. Transistor D.C. Chopper Controller Type GS 24 S Technical Description Transistor D.C. Chopper Controller Type GS 24 S Table of contents 1. Getting started guide 2. General information 2.1. Characteristics 2.2. Accessories 3. Information about the Machine

More information

ELEKTROTECHNISCHE WERKE FRITZ DRIESCHER & SÖHNE GMBH D-85366 MOOSBURG TEL. +49 87 61 6 81-0 FAX +49 87 61 68 12 30

ELEKTROTECHNISCHE WERKE FRITZ DRIESCHER & SÖHNE GMBH D-85366 MOOSBURG TEL. +49 87 61 6 81-0 FAX +49 87 61 68 12 30 40 DRIESCHER - Low voltage fusedswitch-disconnector system 40 Rated current upto 445 A 40 84 40 40 ELEKTROTECHNISCHE WERKE FRITZ DRIESCHER & SÖHNE GMBH D-8566 MOOSBURG TEL. +49 87 6 6 8-0 FAX +49 87 6

More information

Achat 115MA full-range speaker. user manual

Achat 115MA full-range speaker. user manual Achat 115MA full-range speaker user manual Musikhaus Thomann Thomann GmbH Hans-Thomann-Straße 1 96138 Burgebrach Germany Telephone: +49 (0) 9546 9223-0 E-mail: info@thomann.de Internet: www.thomann.de

More information

Power Voltage Transformers for Air Insulated Substations. THE PROVEN POWER.

Power Voltage Transformers for Air Insulated Substations. THE PROVEN POWER. Power Voltage Transformers for Air Insulated Substations THE PROVEN POWER. Introduction Trench Power Voltage Transformers (Power VTs) combine the attributes of an inductive voltage transformer with the

More information

Cable Plug acc. to DIN EN 175301-803, Form A

Cable Plug acc. to DIN EN 175301-803, Form A Cable Plug acc. to DIN EN 175301-803, Form A Complete program Contact form 18 mm Also available with LED indicator Optional 4-pin version for pressure switch or impulse valves respectively Versions with

More information

Plug-in relays Mini ISO relays

Plug-in relays Mini ISO relays Powertrain Systems Chassis Systems Safety Security Body Driver Information Convenience Description Features Limiting continuous current 70 A Dimensional characteristics and the functional allocation of

More information

TYPE TEST CERTIFICATE OF SHORT-CIRCUIT PERFORMANCE. A three-phase outdoor oil-immersed distribution transformer

TYPE TEST CERTIFICATE OF SHORT-CIRCUIT PERFORMANCE. A three-phase outdoor oil-immersed distribution transformer 168-08 TYPE TEST CERTIFICATE OF SHORT-CIRCUIT PERFORMANCE APPARATUS A three-phase outdoor oil-immersed distribution transformer DESIGNATION 1000 kva SERIAL No. 1-08-112-01-0001 Rated power Rated voltage

More information

LINETRAXX VMD460-NA. Network and system protection (NS protection) for monitoring the power feed-in of power generation systems

LINETRAXX VMD460-NA. Network and system protection (NS protection) for monitoring the power feed-in of power generation systems LIETRAXX -A etwork and system protection (S protection) for monitoring the power feed-in of power generation systems TDB301021en/06.2013 LIETRAXX -A etwork and system protection (S protection) for monitoring

More information

Rotary actuator for 2 and 3-way (control) ball valves Torque 5 Nm Nominal voltage AC 100... 240 V Control: Open/close or 3-point Auxiliary switch

Rotary actuator for 2 and 3-way (control) ball valves Torque 5 Nm Nominal voltage AC 100... 240 V Control: Open/close or 3-point Auxiliary switch echnical data sheet Rotary actuator LR-S Rotary actuator for and -way (control) ball valves orque 5 Nm Nominal voltage C... 4 V Control: Open/close or -point uxiliary switch echnical data Electrical data

More information

Series 30000 Hose Reels

Series 30000 Hose Reels Operating Instructions and Parts List for Series 30000 Hose Reels - MANUAL DRIVEN - - POWER DRIVEN - SAFETY PRECAUTIONS Personal injury and/or equipment damage may result if proper safety precautions are

More information

PLC-RS /21. PLC INTERFACE With PDT Relay, Universal Version. INTERFACE Data Sheet 101780_en_02. 1 Description

PLC-RS /21. PLC INTERFACE With PDT Relay, Universal Version. INTERFACE Data Sheet 101780_en_02. 1 Description PLC INERFCE With PD Relay, niversal Version INERFCE Data Sheet 780_en_02 PHOENIX CONC - 03/08 Description PLC-RS /2 relay modules, which can be used universally, comprise 6.2 mm basic terminal blocks and

More information

Application Switchgear for industrial and commercial applications. U e V AC 230/400. 48 (per pole)

Application Switchgear for industrial and commercial applications. U e V AC 230/400. 48 (per pole) Overcurrentswitch,6A,2p,D-Char,AC Partno. FAZ-D6/2 Articleno. 278777 CatalogNo. FAZ-D6/2 Similar to illustration Deliveryprogramme Basic function Miniature circuit breakers Pole 2 pole Tripping characteristic

More information

48.12. 2 pole, 8 A Safety relay. Screw terminal. 35 mm rail (EN 60715) mounting. 2 CO (DPDT) 8/15 250/400 2,000 500 0.37 8/0.65/0.

48.12. 2 pole, 8 A Safety relay. Screw terminal. 35 mm rail (EN 60715) mounting. 2 CO (DPDT) 8/15 250/400 2,000 500 0.37 8/0.65/0. 48 Series - Relay interface modules 8 A Features 48.12 2 Pole Safety relay interface modules, 15.8 mm wide 48.12-2 Pole 8 A (screw terminal) DC sensitive coils Relay with forcibly guided contacts according

More information

handbook, 2 columns handbook, halfpage 085 CS

handbook, 2 columns handbook, halfpage 085 CS FEATURES Polarized aluminium electrolytic capacitors, non-solid, self healing Extended voltage and capacitance range SMD-version, fully moulded, insulated Flexible terminals, reflow and wave solderable

More information

SF 6 Gas Insulated Switchgear Type SDF for 170 kv

SF 6 Gas Insulated Switchgear Type SDF for 170 kv Three Phase Encapsulated Type SF 6 Gas Insulated Switchgear Type SDF for 170 kv 06B1-E-0001 With Trustworthy Technology, Structure Fuji Electric as a manufacturer of comprehensive substation equipment

More information

Table of Contents. TransformerIQ FAQs 1

Table of Contents. TransformerIQ FAQs 1 [12/12] FAQs Table of Contents FAQ 1. What size transformer will TransformerIQ monitor?... 2 FAQ 2. Are there different TransformerIQ versions?... 2 FAQ 3. How are the units powered?... 2 FAQ 4. What is

More information

W DATA SHEET: RESIDUAL CURRENT CIRCUIT BREAKER 25-100A, SERIES BCF0 AND BCF6

W DATA SHEET: RESIDUAL CURRENT CIRCUIT BREAKER 25-100A, SERIES BCF0 AND BCF6 W DATA SHEET: RESIDUAL CURRENT CIRCUIT BREAKER 25-100A, SERIES BCF0 AND BCF6 W SCHRACK-INFO Any mains connection If using 4-pole. switches with 3 or 2-poles, ensure connection acc. to assembly instructions

More information

Protection from Short-circuit

Protection from Short-circuit Protection from Short-circuit Back-up Fuse-Link with ÜLA (controlled power dissipation) Test device for tripping device Special version with threat High-voltage Fuse-Link for voltage transformers (HSW)

More information

A E R Z E N E R M A S C H I N E N F A B R I K G M B H AERZEN POSITIVE DISPLACEMENT BLOWERS. for conveying of air and neutral gases for high vacuum

A E R Z E N E R M A S C H I N E N F A B R I K G M B H AERZEN POSITIVE DISPLACEMENT BLOWERS. for conveying of air and neutral gases for high vacuum AERZEN POSITIVE DISPLACEMENT BLOWERS for conveying of air and neutral gases for high vacuum A E R Z E N E R M A S C H I N E N F A B R I K G M B H G1-090 01 EN 1000 6.2005 Customers benefit due to technical

More information

PV module safety qualification according to IEC 61730:2004 EN 61730:2007

PV module safety qualification according to IEC 61730:2004 EN 61730:2007 PV module safety qualification according to IEC 61730:2004 EN 61730:2007 TÜV Rheinland Immissionsschutz und Energiesysteme GmbH Renewable Energies January 2009 Version 2009-01-22 Overview The long term

More information

MEDIUM VOLTAGE CE-BF SWITCHBOARDS. UP TO 40.5 kv. CE - BF - C - en - REV.00 2012.4

MEDIUM VOLTAGE CE-BF SWITCHBOARDS. UP TO 40.5 kv. CE - BF - C - en - REV.00 2012.4 CE - BF - C - en - REV.00 2012.4 APPLICATION CE-BF Switchbords up to 40.5 kv are designed for use in public and industrial distribution system up to 40,5KV for the operation and protection of lines, transformers,

More information

BETA Switching. Switching Devices. 5TT5 8 Insta contactors, AC technology. Overview

BETA Switching. Switching Devices. 5TT5 8 Insta contactors, AC technology. Overview BETA Switching Siemens AG 200 5TT5 Insta contactors, AC technology Overview The 5TT5 Insta contactors are equipped with an AC magnetic system and are ideal for use under harsh conditions. The auxiliary

More information

AF09-30-22-.. / AF09Z-30-22-.. 2-stack 3-pole Contactors AC / DC Operated - with Screw Terminals

AF09-30-22-.. / AF09Z-30-22-.. 2-stack 3-pole Contactors AC / DC Operated - with Screw Terminals Technical Datasheet 1SBC101403D0201 24/03/11 AF09-30-22-.. / AF09Z-30-22-.. 2-stack 3-pole Contactors AC / DC Operated - with Screw Terminals AF09(Z) contactors are used for controlling power circuits

More information

AutoLink Three-Phase Sectionalizer Specifications. Scope. General. Applicable Standards. Operating principle

AutoLink Three-Phase Sectionalizer Specifications. Scope. General. Applicable Standards. Operating principle Scope This specification stipulates the minimum requirements for mechanically linked three-phase electronic sectionalizers, for use on outdoor medium voltage overhead lines of 15, 27, and 38 kv. Electronic

More information

V - JET. Counteflow System. V-JET Counterflow System Installation and Operation Manual

V - JET. Counteflow System. V-JET Counterflow System Installation and Operation Manual V - JET Counteflow System V-JET Counterflow System Installation and Operation Manual 1. System Installation By purchasing the V - JET counterflow system you have obtained high-quality product, which will

More information