TYPE TEST CERTIFICATE OF SHORT-CIRCUIT PERFORMANCE. A three-phase outdoor oil-immersed distribution transformer

Size: px
Start display at page:

Download "TYPE TEST CERTIFICATE OF SHORT-CIRCUIT PERFORMANCE. A three-phase outdoor oil-immersed distribution transformer"

Transcription

1 TYPE TEST CERTIFICATE OF SHORT-CIRCUIT PERFORMANCE APPARATUS A three-phase outdoor oil-immersed distribution transformer DESIGNATION 1000 kva SERIAL No Rated power Rated voltage Connection symbol Rated frequency 1000 kva 11 kv ± 2 x 2,5% / 433 V Dyn11 50 Hz MANUFACTURER TESTED FOR United Transformers Electric Co., Riyadh, Saudi Arabia United Transformers Electric Co., Riyadh, Saudi Arabia TESTED BY KEMA HIGH-POWER LABORATORY and HIGH-VOLTAGE LABORATORY Utrechtseweg AR Arnhem - The Netherlands DATE(S) OF TESTS 15 to 29 October 2008 The apparatus, constructed in accordance with the description, drawings and photographs incorporated in this Certificate, has been subjected to the series of proving tests in accordance with IEC This Type Test Certificate has been issued by KEMA following exclusively the STL Guides. The results are shown in the record of Proving Tests and the oscillograms attached hereto. The values obtained and the general performance are considered to comply with the above Standard with respect to the dynamic ability to withstand short-circuits. This Certificate applies only to the apparatus tested. The responsibility for conformity of any apparatus having the same designations with that tested rests with the Manufacturer. This Certificate consists of 40 sheets in total. This Certificate falls under the scope of the accreditation certificates L 020 and L 218 of the Dutch Council for Accreditation. See information sheet (page 2). Copyright: Only integral reproduction of this Certificate is permitted without written permission from KEMA. Electronic copies in e.g. PDF-format or scanned version of this Certificate may be available and have the status for information only. The sealed and bound version of the Certificate is the only valid version. KEMA Nederland B.V. P.G.A. Bus KEMA T&D Testing Services Managing Director Version: F Arnhem, 17 December 2008

2 INFORMATION SHEET Page 2 1 Certificate A Certificate contains a record of a series of type tests carried out strictly in accordance with a recognized standard. The equipment tested has fulfilled the requirements of this standard and the relevant ratings assigned by the manufacturer are endorsed by KEMA. The Certificate is applicable only to the equipment tested. KEMA is responsible for the validity and the contents of the Certificate. The responsibility for conformity of any apparatus having the same designation as the one tested rests with the manufacturer. The Certificate contains the essential drawings and a description of the equipment tested. Detailed rules are given in KEMA's Certification procedure. 2 Report of Performance A Report of Performance contains a record of one or more tests which have been carried out according to the client's instructions. These tests are not necessarily in accordance with a recognized standard. The test results do not verify ratings of the test object. KEMA issues three types of Reports of Performance: 2.1 The tests have been carried out strictly in accordance with. The apparatus has complied with the relevant requirements. This sentence will appear on the front page of a Report of Performance if the tests have been performed in accordance with a recognized standard, but the series of tests does not completely fulfil the requirements for a Certificate of Compliance (for example, if the number of test duties is not a complete series of type tests). The Report contains verified drawings and a description of the equipment tested. Detailed rules are given in KEMA's Certification procedure. The condition of the test object after the tests is assessed and recorded in the Report. 2.2 The tests have been carried out in accordance with the client's instructions. Test procedure and test parameters were based on... This sentence will appear on the front page of a Report of Performance if the number of tests, the test procedure and the test parameters are based on a recognized standard and related to the ratings assigned by the manufacturer. If the apparatus does not pass the tests such behaviour will be mentioned on the front sheet. Verification of the drawings (if submitted) and assessment of the condition after the tests is only done on the client's request. 2.3 The tests have been carried out according to the client's instructions. This sentence will appear on the front page of a Report of Performance if the tests, test procedure and/or test parameters are not in accordance with a recognized standard. 3 Standards When reference is made to a standard, and the date of issue is not stated, this applies to the latest issue, including amendments which have been officially published prior to the date of the tests. 4 Official and uncontrolled test documents The official test documents of KEMA High-Power Laboratory are issued in bound form. Uncontrolled copies may be provided as loose sheets or as a digital file for convenience of reproduction by the client. The copyright has to be respected at all times. 5 Accuracy of measurement In the table of test results the measured quantities are given in three digits. This method of presentation does not indicate an accuracy. The guaranteed uncertainty in the figures mentioned, taking into account the total measuring system, is less than 5%, unless mentioned otherwise. 6 Qualified by RvA (Dutch Council for Accreditation) KEMA High-Power Laboratory and High-Voltage Laboratory have been entered in the RvA-register for laboratories under resp. Nrs. L 020 and L 218 for the testing services as defined in the Field of Accreditation. The accreditation is carried out in accordance with ISO/IEC Version: M4 1

3 TABLE OF CONTENTS Page 3 TABLE OF CONTENTS: INFORMATION SHEET...2 IDENTIFICATION OF THE APPARATUS TESTED...4 Ratings assigned by the manufacturer...4 Description of apparatus tested...4 List of drawings...4 GENERAL INFORMATION...5 The tests were witnessed by...5 The tests were observed by...5 The transformer was inspected by...5 LEGEND...6 SUMMARY OF TESTS...7 REACTANCE MEASUREMENT OVERVIEW...9 DUTY: Routine tests before short-circuit tests...10 Tests DUTY: Short-circuit tests...15 Test circuit...16 Calculation sheet short-circuit current...17 Photograph before test...18 Tests to 6019, 6021 to 6023, 6025 to CONDITION AFTER TEST...28 Photograph after test...29 DUTY: Routine tests after short-circuit tests...30 Tests INSPECTION / CONCLUSION...35 Photographs during inspection...36 DRAWINGS...39 Version: G1 1

4 IDENTIFICATION OF THE APPARATUS TESTED Page 4 RATINGS/CHARACTERISTICS ASSIGNED BY THE MANUFACTURER Voltage 11 kv ± 2 x 2,5% / 433 V Power 1000 kva Current 52,5 / 1333 A Short-circuit impedance 5,67 % X Connection symbol Dyn11 Cooling method ONAN Frequency 50 Hz X Category I Apparent system power 500 MVA X = This rating has been proved by the tests of this Certificate. DESCRIPTION OF APPARATUS TESTED A three-phase outdoor oil-immersed distribution transformer LIST OF DRAWINGS The manufacturer has guaranteed that the equipment submitted for tests has been manufactured in accordance with the following drawings. KEMA has verified that these drawings adequately represent the equipment tested. The following drawings have been included in this Certificate: P11 Rev. B P Rev. 0 The following drawings are only listed for reference and are kept in KEMA s files: U11 Rev E Rev U12 Rev. A P Rev. A U81 Rev D00 Rev P11 Rev. A P Rev. B P Rev. A P Rev P Rev. A P Rev. A P Rev P Rev P Rev P Rev. A G Version: 1

5 GENERAL INFORMATION Page 5 THE TESTS WERE WITNESSED BY Name Abdul Hafeez, S. Company United Transformers Electric Co., Riyadh, Saudi Arabia THE TESTS WERE OBSERVED BY Name Bannink, H. Company KEMA High-Power Laboratory, Arnhem, The Netherlands Koevoets, R.C.A.M. Gruntjes, R.J.B. KEMA High-Voltage Laboratory, Arnhem, The Netherlands THE TRANSFORMER WAS INSPECTED BY Name Dobbe, N. Company KEMA High-Power Laboratory, Arnhem, The Netherlands Version: G3 1

6 LEGEND Page 6 PHASE INDICATIONS If more than one phase is recorded on oscillogram, the phases are indicated by the digits 1, 2 and 3. These phases 1, 2 and 3 correspond to the phase values in the columns of the accompanying table, respectively from left to right. EXPLANATION OF THE LETTER SYMBOLS AND ABBREVIATIONS ON THE OSCILLOGRAMS pu I1pri I1sec I2pri I2sec I3pri I3sec Itank U1S U2S U3S Uprot Per unit (the reference length of one unit is represented by the black bar on the oscillogram) Primary current transformer Secondary current transformer Primary current transformer Secondary current transformer Primary current transformer Secondary current transformer Tank current test object Supply voltage Supply voltage Supply voltage Protection signal Version: G4 1

7 SUMMARY: Short-circuit tests Page 7 Test no Tap position C kv 6,63 6,64 6,67 6,48 6,53 6,55 Voltage, phase value, beginning B kv 6,67 6,70 6,72 6,51 6,57 6,58 A kv 6,57 6,61 6,64 6,44 6,50 6,50 C kv 6,61 6,63 6,65 6,47 6,51 6,51 Voltage, phase value, end B kv 6,65 6,67 6,70 6,49 6,54 6,54 A kv 6,57 6,60 6,63 6,41 6,47 6,47 C A Current HV-winding, peak value B A A A C A Current HV-winding, phase value, beginning B A A A C A Current HV-winding, phase value, end B A A A C A Current HV-winding, phase value, average B A A A C ka 48,7-48,5 48,5 40,8-40,9 40,7 Current LV-winding, peak value B ka -36,1 35,7-36,9-49,1 49,1-49,6 A ka -42,2 42,1-41,5 37,0-37,5 38,1 C ka 20,7 20,7 20,8 21,3 21,5 21,5 Current LV-winding, phase value, beginning B ka 21,4 21,4 21,5 22,1 22,3 22,3 A ka 20,6 20,6 20,7 21,5 21,7 21,7 C ka 20,5 20,6 20,6 21,3 21,4 21,5 Current LV-winding, phase value, end B ka 21,2 21,3 21,4 22,0 22,1 22,1 A ka 20,6 20,7 20,7 21,4 21,5 21,5 C ka 20,6 20,7 20,7 21,3 21,4 21,5 Current LV-winding, phase value, average B ka 21,3 21,4 21,4 22,1 22,2 22,2 A ka 20,6 20,6 20,7 21,4 21,6 21,6 Current duration s 0,510 0,509 0,514 0,505 0,506 0,501 C Ω 16,59 16,65 16,68 14,95 14,99 14,99 Reactance after test B Ω 16,71 16,78 16,81 15,02 15,05 15,05 A Ω 16,62 16,65 16,68 14,89 14,92 14,92 REMARKS No visible disturbance. Reactances measured between resp. A-C, B-C, A-B. No visible disturbance. Reactances measured between resp. A-C, B-C, A-B. No visible disturbance. Reactances measured between resp. A-C, B-C, A-B. No visible disturbance. Reactances measured between resp. A-C, B-C, A-B. No visible disturbance. Reactances measured between resp. A-C, B-C, A-B. No visible disturbance. Reactances measured between resp. A-C, B-C, A-B. Version: 1

8 SUMMARY: Short-circuit tests Page 8 SUMMARY (continued) Test no Tap position C kv 5,95 5,96 5,96 Voltage, phase value, beginning B kv 6,00 6,00 6,00 A kv 5,92 5,92 5,91 C kv 5,95 5,94 5,94 Voltage, phase value, end B kv 5,98 5,99 5,99 A kv 5,91 5,91 5,92 C A Current HV-winding, peak value B A A A C A Current HV-winding, phase value, beginning B A A A C A Current HV-winding, phase value, end B A A A C A Current HV-winding, phase value, average B A A A C ka 39,1-39,1 39,5 Current LV-winding, peak value B ka 42,5-42,5 42,1 A ka -51,2 50,6-50,8 C ka 21,3 21,3 21,3 Current LV-winding, phase value, beginning B ka 21,8 21,8 21,9 A ka 21,3 21,2 21,3 C ka 21,2 21,2 21,3 Current LV-winding, phase value, end B ka 21,9 21,9 21,9 A ka 21,2 21,2 21,2 C ka 21,3 21,3 21,3 Current LV-winding, phase value, average B ka 21,8 21,8 21,8 A ka 21,3 21,2 21,3 Current duration s 0,510 0,500 0,513 C Ω 13,10 13,13 13,13 Reactance after test B Ω 13,16 13,16 13,16 A Ω 13,10 13,13 13,13 REMARKS No visible disturbance. Reactances measured between resp. A-C, B-C, A-B. No visible disturbance. Reactances measured between resp. A-C, B-C, A-B. No visible disturbance. Reactances measured between resp. A-C, B-C, A-B. Version: 1

9 REACTANCE MEASUREMENT OVERVIEW Page 9 Test number Measured between the phases Tap position 1 Reactance Calculated per leg Change per leg Ω Ω % A-C B-C A-B C B A C B A Before tests 16,52 16,43 16,37 24,91 24,63 24, AT ,59 16,71 16,62 24,80 25,18 24,90-0,4 2,2 1,9 AT ,65 16,78 16,65 24,91 25,29 24,91 0,0 2,7 1,9 AT ,68 16,81 16,68 24,96 25,34 24,96 0,2 2,9 2,1 After tests 16,87 16,90 16,87 25,29 25,38 25,29 1,5 3,1 3,5 Test number Measured between the phases Tap position 3 Reactance Calculated per leg Change per leg Ω Ω % A-C B-C A-B C B A C B A Before tests 14,55 14,64 14,58 21,76 22,04 21, AT ,95 15,02 14,89 22,43 22,62 22,24 3,1 2,6 1,8 AT ,99 15,05 14,92 22,48 22,67 22,29 3,3 2,9 2,0 AT ,99 15,05 14,92 22,48 22,67 22,29 3,3 2,9 2,0 After tests 15,05 15,08 15,02 22,57 22,67 22,48 3,8 2,8 2,9 Test number Measured between the phases Tap position 5 Reactance Calculated per leg Change per leg Ω Ω % A-C B-C A-B C B A C B A Before tests 12,69 12,79 12,75 18,96 19,24 19, AT ,10 13,16 13,10 19,62 19,81 19,62 3,5 2,9 2,5 AT ,13 13,16 13,13 19,68 19,78 19,68 3,8 2,8 2,8 AT ,13 13,16 13,13 19,68 19,78 19,68 3,8 2,8 2,8 After tests 13,13 13,16 13,13 19,68 19,78 19,68 3,8 2,8 2,8 MAXIMUM DEVIATION The maximum deviation in reactance per leg was 3,8%. The maximum deviation allowed in accordance with the IEC is 7,5%. Version: M2 D1 1

10 DUTY: Routine tests before short-circuit tests Page 10 Standard and date Standard IEC , clause Test date Transformer in same condition. Environmental conditions Ambient temperature 21 C Ambient air pressure 1013 hpa Temperature of test object 20,6 C Humidity 12 g/m 3 MEASUREMENT OF WINDING RESISTANCE DC-winding resistances at 20,6 C HV winding (Ω) LV winding (mω) Terminals Tap position Terminals A8-B8 1,106 1,047 0,989 a2-b2 1,364 A8-C8 1,107 1,048 0,990 a2-c2 1,383 B8-C8 1,105 1,046 0,989 b2-c2 1,363 Average 1,106 1,047 0,989 Average 1,370 Requirements None. Result The results are used for further calculations and are for information only. Version: M4 1

11 Routine tests before short-circuit tests Page 11 MEASUREMENT OF VOLTAGE RATIO AND CHECK OF PHASE DISPLACEMENT Ratio for Dyn11 Tap position Declared ratio 46,20 44,00 41,80 Phase 1 46,23 44,02 41,81 Phase 2 46,23 44,02 41,81 Phase 3 46,23 44,02 41,81 Average 46,23 44,02 41,81 Deviation from declared ratio (%) -0,06-0,04-0,02 Requirements None. Result The results are used for further calculations and are for information only. Version: 1

12 Routine tests before short-circuit tests Page 12 MEASUREMENT OF SHORT-CIRCUIT IMPEDANCE AND LOAD LOSS Load loss and characteristics at θ ref of 75 C Tap position Load-losses (W) R K (Ω) 1,39 1,28 1,18 U R (%) 1,04 1,06 1,08 X K (Ω) 8,12 7,23 6,30 U X (%) 6,08 5,97 5,77 Z K (Ω) 8,23 7,34 6,41 U K (%) 6,17 6,07 5,87 Requirements None. Results The results are used for further calculations and are for information only. Version: 1

13 Routine tests before short-circuit tests Page 13 MEASUREMENT OF NO-LOAD LOSS AND CURRENT No-load losses and currents in tap position 3 Terminal U rms U mean I I/I n x 100 P P o (V) (V) (A) (%) (W) (W) a2 436,5 433,6 4,12 0, b2 434,3 433,3 3,40 0, c2 435,1 432,8 4,28 0, Average 435,3 433,2 3,93 0,29 Total Note: The no-load losses are calculated with the formula U P0 = P 1 + U U mean mean RMS Requirements None. Results The results are used for further calculations and are for information only. Version: 1

14 Routine tests before short-circuit tests Page 14 DIELECTRIC ROUTINE TESTS Separate source AC withstand voltage test (applied voltage test) Tap position Winding Applied voltage Duration Frequency 3 (kv) (min) (Hz) HV LV Requirements No collapse of the test voltage shall occur. Result The tests are passed. INDUCED AC VOLTAGE TESTS (ACSD) Tap position Winding Induced voltage phase-to-phase Duration Frequency (V) (min) (Hz) 3 LV Requirements No collapse of the test voltage shall occur. Result The test is passed. Version: 1

15 DUTY: Short-circuit tests Page 15 TEST NUMBERS CONDITION BEFORE TESTS Transformer in same condition. Supply to HV winding by means of flexible connections. LV winding short-circuited by means of shunts and earthed. Tank earthed via an earth fault current indicating CT. Version: M4 D1 1

16 Test circuit for Short-circuit tests Page 16 TEST-CIRCUIT S01 G MB MS L PT TO U U U Ι Ι Ι Ι Ι Ι Ι U Ι G = Generator TO = Test Object U = Voltage Measurement to earth MB = Master Breaker L = Reactor Ι = Current Measurement MS = Make Switch PT = Power Transformer Supply Power MVA 500 Frequency Hz 50 Phase(s) 3 Voltage kv 11 Current ka 26,24 Impedance Ω 0,242 Power factor < 0,1 Neutral not earthed Load Short-circuit point earthed Version: C1 1 Remarks: -

17 Calculation sheet short-circuit current for Short-circuit tests Page 17 System power of : 500 MVA System voltage of: 11 kv tap position 1 Max. 3 Nom. 5 Min. tap voltage 11,55 kv 11,00 kv 10,45 kv impedance voltage % 6,17 % 6,07 % 5,87 % resistance % (75 C) 1,04 % 1,06 % 1,08 % TAP POSITION 1 Max. Supply voltage: 11,55 kv Terminal voltage: 11,55 kv Short cir. current min. value rated max. value HV current 728,9 A 809,9 A 890,8 A LV current 19,44 ka 21,60 ka 23,76 ka LV peak current 46,25 ka 48,68 ka 51,12 ka HV reactance: 8,12 Ω HV inductance: 25,84 mh TAP POSITION 3 Nom. Supply voltage: 11,00 kv Terminal voltage: 11,00 kv Short cir. current min. value rated max. value HV current 778,9 A 865,4 A 951,9 A LV current 19,79 ka 21,98 ka 24,18 ka LV peak current 46,71 ka 49,17 ka 51,63 ka HV reactance: 7,23 Ω HV inductance: 23,00 mh TAP POSITION 5 Min. Supply voltage: 10,45 kv Terminal voltage: 10,45 kv Short cir. current min. value rated max. value HV current 847,3 A 941,5 A 1035,6 A LV current 20,45 ka 22,72 ka 24,99 ka LV peak current 47,79 ka 50,31 ka 52,82 ka HV reactance: 6,30 Ω HV inductance: 20,05 mh peakfactor according to IEC = 2,24 Zsupply / Ztrafo = 3,30 % peakfactor according to X/R = 2,24 Version: M2 1

18 Photograph before test Page 18 P1-BT Version: 1

19 Short-circuit test Page 19 Uprot 20.1kV pu 6017 U1S 38.6kV pu I1pri 5.01kA pu I1sec 125kA pu U2S 38.6kV pu I2pri 5.01kA pu I2sec 125kA pu U3S 38.6kV pu I3pri 5.01kA pu I3sec 125kA pu Itank 5.01kA pu unit 1.00 s TEST NUMBER: Phase C B A Tap position 1 Voltage, phase value, beginning kv 6,63 6,67 6,57 Voltage, phase value, end kv 6,61 6,65 6,57 Current HV-winding, peak value A Current HV-winding, phase value, beginning A Current HV-winding, phase value, end A Current HV-winding, phase value, average A Current LV-winding, peak value ka 48,7-36,1-42,2 Current LV-winding, phase value, beginning ka 20,7 21,4 20,6 Current LV-winding, phase value, end ka 20,5 21,2 20,6 Current LV-winding, phase value, average ka 20,6 21,3 20,6 Current duration s 0,510 Reactance after test Ω 16,59 16,71 16,62 Remarks: No visible disturbance. Reactances measured between resp. A-C, B-C, A-B. Version: T41 1

20 Short-circuit test Page 20 Uprot 20.1kV pu 6018 U1S 38.6kV pu I1pri 5.01kA pu I1sec 125kA pu U2S 38.6kV pu I2pri 5.01kA pu I2sec 125kA pu U3S 38.6kV pu I3pri 5.01kA pu I3sec 125kA pu Itank 5.01kA pu unit 1.00 s TEST NUMBER: Phase C B A Tap position 1 Voltage, phase value, beginning kv 6,64 6,70 6,61 Voltage, phase value, end kv 6,63 6,67 6,60 Current HV-winding, peak value A Current HV-winding, phase value, beginning A Current HV-winding, phase value, end A Current HV-winding, phase value, average A Current LV-winding, peak value ka -48,5 35,7 42,1 Current LV-winding, phase value, beginning ka 20,7 21,4 20,6 Current LV-winding, phase value, end ka 20,6 21,3 20,7 Current LV-winding, phase value, average ka 20,7 21,4 20,6 Current duration s 0,509 Reactance after test Ω 16,65 16,78 16,65 Remarks: No visible disturbance. Reactances measured between resp. A-C, B-C, A-B. Version: T41 1

21 Short-circuit test Page 21 Uprot 20.1kV pu 6019 U1S 38.6kV pu I1pri 5.01kA pu I1sec 125kA pu U2S 38.6kV pu I2pri 5.01kA pu I2sec 125kA pu U3S 38.6kV pu I3pri 5.01kA pu I3sec 125kA pu Itank 5.01kA pu unit 1.00 s TEST NUMBER: Phase C B A Tap position 1 Voltage, phase value, beginning kv 6,67 6,72 6,64 Voltage, phase value, end kv 6,65 6,70 6,63 Current HV-winding, peak value A Current HV-winding, phase value, beginning A Current HV-winding, phase value, end A Current HV-winding, phase value, average A Current LV-winding, peak value ka 48,5-36,9-41,5 Current LV-winding, phase value, beginning ka 20,8 21,5 20,7 Current LV-winding, phase value, end ka 20,6 21,4 20,7 Current LV-winding, phase value, average ka 20,7 21,4 20,7 Current duration s 0,514 Reactance after test Ω 16,68 16,81 16,68 Remarks: No visible disturbance. Reactances measured between resp. A-C, B-C, A-B. Version: T41 1

22 Short-circuit test Page 22 Uprot 20.1kV pu 6021 U1S 38.6kV pu I1pri 5.01kA pu I1sec 125kA pu U2S 38.6kV pu I2pri 5.01kA pu I2sec 125kA pu U3S 38.6kV pu I3pri 5.01kA pu I3sec 125kA pu Itank 5.01kA pu unit 1.00 s TEST NUMBER: Phase C B A Tap position 3 Voltage, phase value, beginning kv 6,48 6,51 6,44 Voltage, phase value, end kv 6,47 6,49 6,41 Current HV-winding, peak value A Current HV-winding, phase value, beginning A Current HV-winding, phase value, end A Current HV-winding, phase value, average A Current LV-winding, peak value ka 40,8-49,1 37,0 Current LV-winding, phase value, beginning ka 21,3 22,1 21,5 Current LV-winding, phase value, end ka 21,3 22,0 21,4 Current LV-winding, phase value, average ka 21,3 22,1 21,4 Current duration s 0,505 Reactance after test Ω 14,95 15,02 14,89 Remarks: No visible disturbance. Reactances measured between resp. A-C, B-C, A-B. Version: T41 1

23 Short-circuit test Page 23 Uprot 20.1kV pu 6022 U1S 38.6kV pu I1pri 5.01kA pu I1sec 125kA pu U2S 38.6kV pu I2pri 5.01kA pu I2sec 125kA pu U3S 38.6kV pu I3pri 5.01kA pu I3sec 125kA pu Itank 5.01kA pu unit 1.00 s TEST NUMBER: Phase C B A Tap position 3 Voltage, phase value, beginning kv 6,53 6,57 6,50 Voltage, phase value, end kv 6,51 6,54 6,47 Current HV-winding, peak value A Current HV-winding, phase value, beginning A Current HV-winding, phase value, end A Current HV-winding, phase value, average A Current LV-winding, peak value ka -40,9 49,1-37,5 Current LV-winding, phase value, beginning ka 21,5 22,3 21,7 Current LV-winding, phase value, end ka 21,4 22,1 21,5 Current LV-winding, phase value, average ka 21,4 22,2 21,6 Current duration s 0,506 Reactance after test Ω 14,99 15,05 14,92 Remarks: No visible disturbance. Reactances measured between resp. A-C, B-C, A-B. Version: T41 1

24 Short-circuit test Page 24 Uprot 20.1kV pu 6023 U1S 38.6kV pu I1pri 5.01kA pu I1sec 125kA pu U2S 38.6kV pu I2pri 5.01kA pu I2sec 125kA pu U3S 38.6kV pu I3pri 5.01kA pu I3sec 125kA pu Itank 5.01kA pu unit 1.00 s TEST NUMBER: Phase C B A Tap position 3 Voltage, phase value, beginning kv 6,55 6,58 6,50 Voltage, phase value, end kv 6,51 6,54 6,47 Current HV-winding, peak value A Current HV-winding, phase value, beginning A Current HV-winding, phase value, end A Current HV-winding, phase value, average A Current LV-winding, peak value ka 40,7-49,6 38,1 Current LV-winding, phase value, beginning ka 21,5 22,3 21,7 Current LV-winding, phase value, end ka 21,5 22,1 21,5 Current LV-winding, phase value, average ka 21,5 22,2 21,6 Current duration s 0,501 Reactance after test Ω 14,99 15,05 14,92 Remarks: No visible disturbance. Reactances measured between resp. A-C, B-C, A-B. Version: T41 1

25 Short-circuit test Page 25 Uprot 20.1kV pu 6025 U1S 38.6kV pu I1pri 5.01kA pu I1sec 125kA pu U2S 38.6kV pu I2pri 5.01kA pu I2sec 125kA pu U3S 38.6kV pu I3pri 5.01kA pu I3sec 125kA pu Itank 5.01kA pu unit 1.00 s TEST NUMBER: Phase C B A Tap position 5 Voltage, phase value, beginning kv 5,95 6,00 5,92 Voltage, phase value, end kv 5,95 5,98 5,91 Current HV-winding, peak value A Current HV-winding, phase value, beginning A Current HV-winding, phase value, end A Current HV-winding, phase value, average A Current LV-winding, peak value ka 39,1 42,5-51,2 Current LV-winding, phase value, beginning ka 21,3 21,8 21,3 Current LV-winding, phase value, end ka 21,2 21,9 21,2 Current LV-winding, phase value, average ka 21,3 21,8 21,3 Current duration s 0,510 Reactance after test Ω 13,10 13,16 13,10 Remarks: No visible disturbance. Reactances measured between resp. A-C, B-C, A-B. Version: T41 1

26 Short-circuit test Page 26 Uprot 20.1kV pu 6026 U1S 38.6kV pu I1pri 5.01kA pu I1sec 125kA pu U2S 38.6kV pu I2pri 5.01kA pu I2sec 125kA pu U3S 38.6kV pu I3pri 5.01kA pu I3sec 125kA pu Itank 5.01kA pu unit 1.00 s TEST NUMBER: Phase C B A Tap position 5 Voltage, phase value, beginning kv 5,96 6,00 5,92 Voltage, phase value, end kv 5,94 5,99 5,91 Current HV-winding, peak value A Current HV-winding, phase value, beginning A Current HV-winding, phase value, end A Current HV-winding, phase value, average A Current LV-winding, peak value ka -39,1-42,5 50,6 Current LV-winding, phase value, beginning ka 21,3 21,8 21,2 Current LV-winding, phase value, end ka 21,2 21,9 21,2 Current LV-winding, phase value, average ka 21,3 21,8 21,2 Current duration s 0,500 Reactance after test Ω 13,13 13,16 13,13 Remarks: No visible disturbance. Reactances measured between resp. A-C, B-C, A-B. Version: T41 1

27 Short-circuit test Page 27 Uprot 20.1kV pu 6027 U1S 38.6kV pu I1pri 5.01kA pu I1sec 125kA pu U2S 38.6kV pu I2pri 5.01kA pu I2sec 125kA pu U3S 38.6kV pu I3pri 5.01kA pu I3sec 125kA pu Itank 5.01kA pu unit 1.00 s TEST NUMBER: Phase C B A Tap position 5 Voltage, phase value, beginning kv 5,96 6,00 5,91 Voltage, phase value, end kv 5,94 5,99 5,92 Current HV-winding, peak value A Current HV-winding, phase value, beginning A Current HV-winding, phase value, end A Current HV-winding, phase value, average A Current LV-winding, peak value ka 39,5 42,1-50,8 Current LV-winding, phase value, beginning ka 21,3 21,9 21,3 Current LV-winding, phase value, end ka 21,3 21,9 21,2 Current LV-winding, phase value, average ka 21,3 21,8 21,3 Current duration s 0,513 Reactance after test Ω 13,13 13,16 13,13 Remarks: No visible disturbance. Reactances measured between resp. A-C, B-C, A-B. Version: T41 1

28 CONDITION AFTER TEST Page 28 CONDITION AFTER TEST Externally no visible change. Version: D3 1

29 Photograph after test Page 29 P1-AT Version: 1

30 DUTY: Routine tests after short-circuit tests Page 30 Standard and date Standard IEC , clause Test date Transformer in same condition. Environmental conditions Ambient temperature 20 C Ambient air pressure 1004 hpa Temperature of test object 19,6 C Humidity 7 g/m 3 MEASUREMENT OF WINDING RESISTANCE DC-winding resistances at 19,6 C HV winding (Ω) LV winding (mω) Terminals Tap position Terminals A8-B8 1,096 1,039 0,981 a2-b2 1,347 A8-C8 1,098 1,040 0,982 a2-c2 1,373 B8-C8 1,096 1,039 0,981 b2-c2 1,357 Average 1,097 1,039 0,981 Average 1,359 Requirements None. Result The results are used for further calculations and are for information only. Version: M4 1

31 Routine tests after short-circuit tests Page 31 MEASUREMENT OF VOLTAGE RATIO AND CHECK OF PHASE DISPLACEMENT Ratio for Dyn11 Tap position Declared ratio 46,20 44,00 41,80 Phase 1 46,23 44,02 41,80 Phase 2 46,23 44,02 41,80 Phase 3 46,23 44,02 41,80 Average 46,23 44,02 41,80 Deviation from declared ratio (%) -0,06-0,04 0,00 Requirements None. Result The results are used for further calculations and are for information only. Version: 1

32 Routine tests after short-circuit tests Page 32 MEASUREMENT OF SHORT-CIRCUIT IMPEDANCE AND LOAD LOSS Load loss and characteristics at θ ref of 75 C Tap position Load-losses (W) R K (Ω) 1,38 1,28 1,17 U R (%) 1,03 1,06 1,08 X K (Ω) 8,34 7,44 6,49 U X (%) 6,25 6,15 5,94 Z K (Ω) 8,45 7,55 6,59 U K (%) 6,34 6,24 6,04 Requirements None. Results The results are used for further calculations and are for information only. Version: 1

33 Routine tests after short-circuit tests Page 33 MEASUREMENT OF NO-LOAD LOSS AND CURRENT No-load losses and currents in tap position 3 Terminal U rms U mean I I/I n x 100 P P o (V) (V) (A) (%) (W) (W) a2 435,2 432,7 4,18 0, b2 434,5 433,5 3,39 0, c2 435,3 432,9 4,08 0, Average 435,0 433,0 3,88 0,29 Total Note: The no-load losses are calculated with the formula U P0 = P 1 + U U mean mean RMS Requirements None. Results The results are used for further calculations and are for information only. Version: 1

34 Routine tests after short-circuit tests Page 34 DIELECTRIC ROUTINE TESTS Separate source AC withstand voltage test (applied voltage test) Tap position Winding Applied voltage Duration Frequency 5 (kv) (min) (Hz) HV LV Requirements No collapse of the test voltage shall occur. Result The tests are passed. INDUCED AC VOLTAGE TESTS (ACSD) Tap position Winding Induced voltage phase-to-phase Duration Frequency (V) (min) (Hz) 1 LV Requirements No collapse of the test voltage shall occur. Result The test is passed. Version: 1

35 INSPECTION / CONCLUSION Page 35 INSPECTION OF THE ACTIVE PART On 29 October 2008 the transformer was untanked and the active part was inspected. The out-of-tank inspection with respect to displacements, deformations of core and windings, connections and supporting structures or traces of discharges did not reveal any apparent defects. CONCLUSION The transformer complies with IEC (Ability to withstand short-circuit), subclause Version: 1

36 Photograph during inspection Page 36 P1-GE Version: 1

37 Photograph during inspection Page 37 P1-GE Version: 1

38 Photograph during inspection Page 38 P1-GE Version: 1

39 Drawing Page 39 Version: DR 1

40 Drawing Page 40 Version: DR 1

GUIDE FOR TESTING POWER TRANSFORMERS

GUIDE FOR TESTING POWER TRANSFORMERS GUIDE FOR TESTING POWER TRANSFORMERS Routine test 11/11/02 Pagina 1 di 10 INDEX Introduction... 3 1 Dielectric tests Separate-source voltage withstand test... 4 2 Induced voltage test... 5 3 Voltage ratio

More information

INTERNATIONAL STANDARD

INTERNATIONAL STANDARD INTERNATIONAL STANDARD IEC 60076-1 Edition 2.1 2000-04 Edition 2:1993 consolidated with amendment 1:1999 Power transformers Part 1: General This English-language version is derived from the original bilingual

More information

LOW VOLTAGE RING TYPE MEASURING CURRENT TRANSFORMERS

LOW VOLTAGE RING TYPE MEASURING CURRENT TRANSFORMERS Specification for LOW VOLTAGE RING TYPE MEASURING CURRENT TRANSFORMERS CEYLON ELECTRICITY BOARD SRI LANKA Specification for LOW VOLTAGE RING TYPE MEASURING CURRENT TRANSFORMERS CEB Standard 027: 1998 CEYLON

More information

INTERNATIONAL STANDARD

INTERNATIONAL STANDARD INTERNATIONAL STANDARD IEC 60076-11 First edition 2004-05 Power transformers Part 11: Dry-type transformers This English-language version is derived from the original bilingual publication by leaving out

More information

DS 600. A contact free flux gate based current measurement sensor 600A rms

DS 600. A contact free flux gate based current measurement sensor 600A rms DS 600 A contact free flux gate based current measurement sensor 600A rms DS 600 is member of the small housing sensor family. The family includes a 200A and a 600A version. 600A rms - 900A peak Maximum

More information

Power Technology Issue 104. Modeling of Two-Winding Voltage Regulating Transformers for Positive Sequence Load Flow Analysis in PSS E

Power Technology Issue 104. Modeling of Two-Winding Voltage Regulating Transformers for Positive Sequence Load Flow Analysis in PSS E SIEMENS Siemens Energy, Inc. Power Technology Issue 104 Modeling of TwoWinding Voltage Regulating Transformers for Positive Sequence Load Flow Analysis in PSS E Carlos GrandeMoran, Ph.D. Principal Consultant

More information

Testing of Power Transformers. Routine tests, Type tests and Special tests

Testing of Power Transformers. Routine tests, Type tests and Special tests Testing of Power Transformers Routine tests, Type tests and Special tests Testing of Power Transformers Routine tests, Type tests and Special tests Testing of Power Transformers Routine tests, Type tests

More information

3.1.1 Full Type Tests & Routine Tests according to Clause 8 2 & 8 3. 4.0 Instructions For Installation, Operation & Maintenance

3.1.1 Full Type Tests & Routine Tests according to Clause 8 2 & 8 3. 4.0 Instructions For Installation, Operation & Maintenance SPECIFICATION FOR LOW VOLTAGE SWITCHBOARD SEN I N D E X Description 10 STANDARD TECHNICAL REQUIREMENTS 11 Standards 12 General Operating Conditions 13 General Description Of Switchboard 131 Structure 132

More information

Power Technology Issue 106. Modeling of Three-Winding Voltage Regulating Transformers for Positive Sequence Load Flow Analysis in PSS E

Power Technology Issue 106. Modeling of Three-Winding Voltage Regulating Transformers for Positive Sequence Load Flow Analysis in PSS E SIEMENS Siemens Energy, Inc. Power Technology Issue 106 Modeling of Three-Winding Voltage Regulating Transformers for Positive Sequence Load Flow Analysis in PSS E Carlos Grande-Moran, Ph.D. Principal

More information

Transformers Energy efficient transformer solutions European Minimum Energy Performance Standard (MEPS)

Transformers Energy efficient transformer solutions European Minimum Energy Performance Standard (MEPS) Transformers Energy efficient transformer solutions European Minimum Energy Performance Standard (MEPS) 2 European MEPS for transformers The EU MEPS (European Minimum Energy Performance Standard) Transformers

More information

Presentation of the France Transfo factories

Presentation of the France Transfo factories Presentation of the France Transfo factories France Transfo's internationally recognised and highly esteemed expertise is today exported to more than 80 countries throughout the world. Over the past 15

More information

Current and voltage measuring relays

Current and voltage measuring relays Current and voltage measuring relays RXIK 1, RXEEB 1 and Page 1 Issued June 1999 Changed since July 1998 Data subject to change without notice RXIK 1 RXEEB 1 (SE980082) (SE980081) (SE970869) Features Application

More information

AMP CO Plus Insert for Cat. 6 A Applications

AMP CO Plus Insert for Cat. 6 A Applications Product Specification 108-93039 10/Mar/2011 Rev F AMP CO Plus Insert for Cat. 6 A Applications 1. SCOPE 1.1 Content This specification covers performance, tests and quality requirements for AMP* CO Plus

More information

Rules for Classification and Construction Additional Rules and Guidelines

Rules for Classification and Construction Additional Rules and Guidelines VI Rules for Classification and Construction Additional Rules and Guidelines 7 Guidelines for the Performance of Type Approvals 6 Test Requirements for Electrical Machinery Edition 1999 The following Guidelines

More information

DIMENSIONING OF CURRENT TRANSFORMERS FOR PROTECTON APPLICATION

DIMENSIONING OF CURRENT TRANSFORMERS FOR PROTECTON APPLICATION ÿþ üûúùø öõöôùóùõò CT Dimensioning DIMENSIONING OF CURRENT TRANSFORMERS FOR PROTECTON APPLICATION Application note GER3973 1 CT Dimensioning ÿþ üûúùø öõöôùóùõò GER-3973 Application note ÿþ üûúùø öõöôùóùõò

More information

Power transformers. Special transformers Railway

Power transformers. Special transformers Railway Power transformers Special transformers Railway A leader in railway systems Our compact and low-weight transformers fully comply with the customer s specifications. The products are developed together

More information

Technical Information Requirement for MV transformers and transformer for internal power supplies for SUNNY CENTRAL

Technical Information Requirement for MV transformers and transformer for internal power supplies for SUNNY CENTRAL Technical Information Requirement for MV transformers and transformer for internal power supplies for SUNNY CENTRAL SC_Trafo-TI-en-62 Version 6.2 ENGLISH Table of Contents SMA Solar Technology Table of

More information

INTERNATIONAL STANDARD

INTERNATIONAL STANDARD INTENATIONAL STANDAD IEC 60076-5 Second edition 2000-07 Power transformers Part 5: Ability to withstand short circuit This English-language version is derived from the original bilingual publication by

More information

ALTERNATIVE METHODS FOR INTERNAL ARC TESTS ON 12 KV AND 24 KV METAL-ENCLOSED SWITCHGEARS WITH COMPACT RMU

ALTERNATIVE METHODS FOR INTERNAL ARC TESTS ON 12 KV AND 24 KV METAL-ENCLOSED SWITCHGEARS WITH COMPACT RMU ALTERNATIVE METHODS FOR INTERNAL ARC TESTS ON 12 KV AND 24 KV METAL-ENCLOSED SWITCHGEARS WITH COMPACT RMU George CURCANU, Constantin ILINCA, Ilie SBORA ICMET Craiova, Romania, Calea Bucuresti 144, phone:

More information

Voltage Regulator SPAU 341 C. Product Guide

Voltage Regulator SPAU 341 C. Product Guide Issued: July 1998 Status: Updated Version: D/25.04.2006 Data subject to change without notice Features Comprehensive voltage regulation for power transformers with on-load tapchangers in distribution substations

More information

Simple Methods for Calculating Short Circuit Current Without a Computer By Dennis McKeown, PE GE Senior System Application Engineer

Simple Methods for Calculating Short Circuit Current Without a Computer By Dennis McKeown, PE GE Senior System Application Engineer Simple Methods for Calculating Short Circuit Current Without a Computer By Dennis McKeown, PE GE Senior System Application Engineer A Short Circuit analysis is used to determine the magnitude of short

More information

Short Circuit Current Calculations

Short Circuit Current Calculations Introduction Several sections of the National Electrical Code relate to proper overcurrent protection. Safe and reliable application of overcurrent protective devices based on these sections mandate that

More information

Transformers. Special transformers Reactors products

Transformers. Special transformers Reactors products Transformers Special transformers Reactors products Reactors Custom designed, custom built ABB Oy Transformers has extensive experience and numerous references from different reactor applications, having

More information

Measurement, Modeling and Simulation of Capacitor Bank Switching Transients

Measurement, Modeling and Simulation of Capacitor Bank Switching Transients Measurement, Modeling and Simulation of Capacitor Bank Switching Transients Mirza Softić*, Amir Tokić**, Ivo Uglešić*** *Kreka - Dubrave e, Dubrave, Bosnia and Herzegovina (e-mail: softic_mirza@yahoo.com).

More information

Three-phase monitoring relay CM-PFE

Three-phase monitoring relay CM-PFE Data sheet Three-phase monitoring relay CM-PFE The CM-PFE is a three-phase monitoring relay that monitors the phase parameter phase sequence and phase failure in three-phase mains. 2CDC 251 005 S0012 Characteristics

More information

Magnetic and Hydraulic-Magnetic Circuit Breaker 8340-G2...

Magnetic and Hydraulic-Magnetic Circuit Breaker 8340-G2... Magnetic and Hydraulic-Magnetic Circuit Breaker 840-G2... Description Single, two and three pole magnetic circuit breakers with trip-free mechanism and push/pull on/off manual actuation. A choice of fast

More information

INTERNATIONAL STANDARD

INTERNATIONAL STANDARD INTENATIONAL STANDAD IEC 60076-1 Edition 2.1 2000-04 Edition 2:1993 consolidated with amendment 1:1999 Power transformers Part 1: General This English-language version is derived from the original bilingual

More information

INTERNATIONAL STANDARD

INTERNATIONAL STANDARD INTERNATIONAL STANDARD IEC 60071-2 Third edition 1996-12 Insulation co-ordination Part 2: Application guide This English-language version is derived from the original bilingual publication by leaving out

More information

Together we create reliable products, thus ensuring development of power industry of continents.

Together we create reliable products, thus ensuring development of power industry of continents. PRODUCT CATALOGUE Together we create reliable products, thus ensuring development of power industry of continents. By continuous improvement we transform our knowledge, energy and experience of the generations

More information

T 3000. Substation Maintenance and Commissioning Test Equipment

T 3000. Substation Maintenance and Commissioning Test Equipment T 3000 Substation Maintenance and Commissioning Test Equipment Multi function system for testing substation equipment such as: current, voltage and power transformers, all type of protection relays, energy

More information

Transformer Design & Design Parameters

Transformer Design & Design Parameters Transformer Design & Design Parameters - Ronnie Minhaz, P.Eng. Power Transmission + Distribution GENERATION TRANSMISSION SUB-TRANSMISSION DISTRIBUTION DISTRIBUTED POWER 115/10 or 20 kv 500/230 230/13.8

More information

Requirements for Offshore Grid Connections. in the. Grid of TenneT TSO GmbH

Requirements for Offshore Grid Connections. in the. Grid of TenneT TSO GmbH Requirements for Offshore Grid Connections in the Grid of TenneT TSO GmbH Bernecker Straße 70, 95448 Bayreuth Updated: 21 December 2012 1/10 Requirements for Offshore Grid Connections in the Grid of TenneT

More information

Table of Contents. TransformerIQ FAQs 1

Table of Contents. TransformerIQ FAQs 1 [12/12] FAQs Table of Contents FAQ 1. What size transformer will TransformerIQ monitor?... 2 FAQ 2. Are there different TransformerIQ versions?... 2 FAQ 3. How are the units powered?... 2 FAQ 4. What is

More information

DUAL%CHANNEL BROADBAND%LINEAR%AMPLIFIER Model&A800D

DUAL%CHANNEL BROADBAND%LINEAR%AMPLIFIER Model&A800D ELECTRONICS AB DUAL%CHANNEL BROADBAND%LINEAR%AMPLIFIER Model&A800D & HIGH&VOLTAGE& FIXED&GAIN& BROADBAND & 800Vpp&60mA& 100x& DC&to&ca&200&kHz & LOW&OUTPUT&IMPEDANCE& HIGH&SLEW&RATE &

More information

HIGH VOLTAGE LABORATORY INSTYTUT ENERGETYKI

HIGH VOLTAGE LABORATORY INSTYTUT ENERGETYKI HIGH VOLTAGE LABORATORY INSTYTUT ENERGETYKI POLAND 01-330 WARSZAWA, ul. Mory 8, tel. (+48 22) 836-80-48, fax (+48 22) 836-80-48 e-mail: ewn@ien.com.pl EWN/70/E/11-1 APPENDIX 4 APPENDIX 4 for test report

More information

Unified requirements for systems with voltages above 1 kv up to 15 kv

Unified requirements for systems with voltages above 1 kv up to 15 kv (1991) (Rev.1 May 2001) (Rev.2 July 2003) (Rev.3 Feb 2015) Unified requirements for systems with voltages above 1 kv up to 15 kv 1. General 1.1 Field of application The following requirements apply to

More information

The standards mentioned in this document

The standards mentioned in this document The standards mentioned in this document Where can you order IEC publications? Central Offices of the International Electrotechnical Commission 1, rue de Varembé Geneva - Switzerland. The documentation

More information

IEC 1000-4-2 ESD Immunity and Transient Current Capability for the SP72X Series Protection Arrays

IEC 1000-4-2 ESD Immunity and Transient Current Capability for the SP72X Series Protection Arrays IEC 00-4-2 ESD Immunity and Transient Current Capability for the SP72X Series Protection Arrays Application Note July 1999 AN9612.2 Author: Wayne Austin The SP720, SP721, SP723, and SP724 are protection

More information

Guidance for upgrading to GB4943.1-2011 (IEC 60950-1: 2005, MOD)

Guidance for upgrading to GB4943.1-2011 (IEC 60950-1: 2005, MOD) Guidance for upgrading to GB4943.1-2011 (IEC 60950-1: 2005, MOD) Note: This guidance document is a translation of official Chinese document which is issued by CQC (China Quality Certification Center) on

More information

Instrument Transformers Application Guide

Instrument Transformers Application Guide Instrument Transformers Application Guide Edited by ABB AB High Voltage Products Department: Marketing & Sales Text: Knut Sjövall, ABB Layout, 3D and images: Mats Findell, ABB SE-771 80 LUDVIKA, Sweden

More information

Discussion on Class I & II Terminology. IEEE PES Transformers Committee Fall Meeting 2011 Boston, MA

Discussion on Class I & II Terminology. IEEE PES Transformers Committee Fall Meeting 2011 Boston, MA Discussion on Class I & II Terminology IEEE PES Transformers Committee Fall Meeting 2011 Boston, MA What is Class I & II? C57.12.00 2010 is the only document we have that defined these terms. 5.10 Insulation

More information

ELECTRICAL INSULATION TESTING OF HV EQUIPMENT UP TO 33kV

ELECTRICAL INSULATION TESTING OF HV EQUIPMENT UP TO 33kV 1. SCOPE This document details PowerSystems requirements for electrical testing of HV Equipment up to and including 33kV. 2. ISSUE RECORD This is a Reference document. The current version of Controlled

More information

SURGE PROTECTIVE DEVICES

SURGE PROTECTIVE DEVICES SURGE PROTECTIVE DEVICES 1. INTRODUCTION In order to ensure safety of people, protection of equipment and, to a certain extent, continuity of supply, insulation co-ordination aims at reducing the likelihood

More information

The Importance of the X/R Ratio in Low-Voltage Short Circuit Studies

The Importance of the X/R Ratio in Low-Voltage Short Circuit Studies The Importance of the X/R Ratio in Low-Voltage Short Circuit Studies DATE: November 17, 1999 REVISION: AUTHOR: John Merrell Introduction In some short circuit studies, the X/R ratio is ignored when comparing

More information

Electricity and Magnetism, Georgia, GEOSTM (Georgian National Agency for Standards and Metrology)

Electricity and Magnetism, Georgia, GEOSTM (Georgian National Agency for Standards and Metrology) single references 1 1.018 V Temperature (23 ± 3) C 6 µv 2 95% No 1 single references 10 10 V Temperature (23 ± 3) C 25 µv 2 95% No 2 low ranges DMM > 0.01 10 V Temperature (23 ± 3) C 2E-06U + 3E-06 to

More information

THE PER-UNIT SYSTEM. (2) The per-unit values for various components lie within a narrow range regardless of the equipment rating.

THE PER-UNIT SYSTEM. (2) The per-unit values for various components lie within a narrow range regardless of the equipment rating. THE PER-UNIT SYSTEM An interconnected power system typically consists of many different voltage levels given a system containing several transformers and/or rotating machines. The per-unit system simplifies

More information

How To Choose A Transformer

How To Choose A Transformer Consider open loop MV network as an example source 1 source 2 NC NC NC or NO main MV switchboard A B Detail design of substation NC NC NC NO NC NC switchboard 1 switchboard 2 switchboard 3 MV MV MV LV

More information

CAPACITOR BANK TESTING SWP

CAPACITOR BANK TESTING SWP 1. PURPOSE AND SCOPE The purpose of this Standard Work Practice (SWP) is to standardise and prescribe the method for testing Capacitor Banks including capacitors, tuning reactors and inrush limiting reactors.

More information

HSP GmbH Zum Handwerkerhof 2 90530 Wendelstein Tel. 09129 / 2852-0 Fax: 09129 / 2852-11 Web: www.hsshsp.de EMAIL: HSP@hsshsp.de NTG-3000.

HSP GmbH Zum Handwerkerhof 2 90530 Wendelstein Tel. 09129 / 2852-0 Fax: 09129 / 2852-11 Web: www.hsshsp.de EMAIL: HSP@hsshsp.de NTG-3000. NTG-3000 Transducer Data Sheet Document Version 2.8 Page 1 of 10 Versions / Revisions: Document Creation Author Description version date 2.0 2012-07-25 P. Compensis First official version 2.1 2012-08-24

More information

AUTOMATIC TRANSFER SWITCH. Changeover Type from 250A to 2500A

AUTOMATIC TRANSFER SWITCH. Changeover Type from 250A to 2500A AUTOMATIC TRANSFER SWITCH Changeover Type from 250A to 2500A Table of Contents Preamble 1.1 Theoretical base 1.2 Selection the size of automatic transfer switch 1.3 Automatic transfer switch components

More information

High-Voltage Compact Switchgear 3AP1 DTC for 145 kv and 245 kv

High-Voltage Compact Switchgear 3AP1 DTC for 145 kv and 245 kv High-Voltage Compact Switchgear AP1 DTC for 1 kv and kv Answers for energy. The AP1 DTC Complying with our Customers demands Experience you can rely on - at anytime, anywhere Decades of experience in high-voltage

More information

EEL303: Power Engineering I - Tutorial 4

EEL303: Power Engineering I - Tutorial 4 1. Determine the voltage at the generating station and the efficiency of the following system (Figure 1): Both transformers have ratio of 2kV/11kV. The resistance on LV side of both Figure 1: transformers

More information

EARTHING SYSTEM CALCULATION

EARTHING SYSTEM CALCULATION BAZIAN STEAL FACTORY S/S 132/11kV, 1x30/40MVA EARTHING SYSTEM CALCULATION Kurdistan Region Sulaimani May 2011 Bazian Steal Factory S/S 132/11kV, 1x30/40 MVA Contents: 1. Introduction... 3 2. List of references

More information

PRE COMMISSIONING TESTS ON EQUIPMENT AT 33/11 KV SUB STATIONS

PRE COMMISSIONING TESTS ON EQUIPMENT AT 33/11 KV SUB STATIONS PRE COMMISSIONING TESTS ON EQUIPMENT AT 33/11 KV SUB STATIONS TESTS ON TRANSFORMERS 1. IR Values a) For 33/11 KV Power Transformer 2500 V megger is to be need. b) Power Transformer neutral Earthing is

More information

2. A conductor of length 2m moves at 4m/s at 30 to a uniform magnetic field of 0.1T. Which one of the following gives the e.m.f. generated?

2. A conductor of length 2m moves at 4m/s at 30 to a uniform magnetic field of 0.1T. Which one of the following gives the e.m.f. generated? Extra Questions - 2 1. A straight length of wire moves through a uniform magnetic field. The e.m.f. produced across the ends of the wire will be maximum if it moves: a) along the lines of magnetic flux

More information

Step Voltage Regulators

Step Voltage Regulators Step Voltage Regulators Don Wareham Field Application Engineer Today s Agenda Introduction Voltage Regulator theory Voltage Regulator application considerations Installation and proper bypassing Wrap-up/questions

More information

ANCILLARY EQUIPMENT AND ELECTRICAL EQUIPMENT Power Supply Systems and Electrical Equipment for Desalination Plants - Y.M. Hamud and A.H.

ANCILLARY EQUIPMENT AND ELECTRICAL EQUIPMENT Power Supply Systems and Electrical Equipment for Desalination Plants - Y.M. Hamud and A.H. POWER SUPPLY SYSTEMS AND ELECTRICAL EQUIPMENT FOR DESALINATION PLANTS Y.M. Hamud and A.H. Anwar Abu Dhabi Water and Electricity Authority, Abu Dhabi, UAE Keywords : Electrical System, Network for Desalination,

More information

Guidelines on the Short Circuit Current Rating for Industrial Control Panels

Guidelines on the Short Circuit Current Rating for Industrial Control Panels usa.siemens.com/sccr Guidelines on the Short Circuit Current Rating for Industrial Control Panels Technical Paper for Practical Applications White Paper I October 2014 As per NEC Edition 2014, and UL508A

More information

TWENTIES WORKSHOP, EWEA 2012 Unveiling the future energy system: full scale demonstrations to reach 2020 targets. 17th April 2012

TWENTIES WORKSHOP, EWEA 2012 Unveiling the future energy system: full scale demonstrations to reach 2020 targets. 17th April 2012 TWENTIES WORKSHOP, EWEA 2012 Unveiling the future energy system: full scale demonstrations to reach 2020 targets 17th April 2012 Session 2 Technological challenges to cope with in TWENTIES field tests

More information

Arc Terminator Active Arc-Resistant Switchgear

Arc Terminator Active Arc-Resistant Switchgear Arc Terminator Active Arc-Resistant Switchgear Increasing safety and productivity by extinguishing internal arcing faults within the switchgear. The Square D Arc Terminator from Schneider Electric offers

More information

Reyrolle Protection Devices. 7PG17 - XR Intertripping, Interposing, Supervision and Special Purpose Relays. Answers for energy

Reyrolle Protection Devices. 7PG17 - XR Intertripping, Interposing, Supervision and Special Purpose Relays. Answers for energy Reyrolle Protection Devices 7PG17 - XR Intertripping, Interposing, Supervision and Special Purpose Relays. Answers for energy Siemens Protection Devices Limited 2 7PG17 XR101 & XR102 Intertripping Relay

More information

Type: EASY719 DC RC Article No.: 274119. Ordering information Relay outputs Quantity 6 Power supply V DC 24 V DC. Description

Type: EASY719 DC RC Article No.: 274119. Ordering information Relay outputs Quantity 6 Power supply V DC 24 V DC. Description Type: EASY719 DC RC Article.: 274119 Ordering information Relay outputs Quantity 6 Power supply V DC 24 V DC Description 12 digital inputs (4 inputs available as analog inputs) 6 relay outputs LCD display

More information

R.C.C.B. s two-pole LEXIC

R.C.C.B. s two-pole LEXIC 87045 LIMOGES Cedex Telephone : (+33) 05 55 06 87 87 Fax : (+ 33) 05 55 06 88 88 R.C.C.B. s two-pole LEXIC 089 06/09/10/11/12/15/16/17/18/ 27/28/29/30/35, CONTENTS PAGES 1. Electrical and mechanical characteristics...

More information

ABB 1. Three-phase monitoring relay CM-PFS. Data sheet. Features. Approvals. Marks. Order data. Order data - Accessories. Application.

ABB 1. Three-phase monitoring relay CM-PFS. Data sheet. Features. Approvals. Marks. Order data. Order data - Accessories. Application. 1SR 430 824 F9300 Features Monitoring of three-phase mains for phase sequence and failure Powered by the measuring circuit 2 c/o (SPDT) contacts 1 LED for status indication Approvals R: yellow LED - relay

More information

Current transformer selection guide

Current transformer selection guide The selection of a current transformer is a simple task. There are four phases in the selection procedure. Current transformer selection guide KEEP IN MIND efine customer requirements based on the primary

More information

How To Understand The Electrical Power Supply Of A Power Supply System

How To Understand The Electrical Power Supply Of A Power Supply System 17 Circuit diagram symbols E 18 CIRCUIT DIAGRAM SYMBOLS electrical network elements three-phase line or cable single-phase line or cable short circuit earth electrode outgoing feeder supply incoming feeder

More information

Medium-voltage transformers

Medium-voltage transformers Medium-voltage transformers We make energy measurable and take care of your future www.mbs-ag.com Page 2 E-Mail: info@mbs-ag.com Web: www.mbs-ag.com Contents Current transformers Technical characteristics

More information

Medium voltage circuit breaker

Medium voltage circuit breaker Medium voltage circuit breaker IEC 60 056 and ANSI C37-06 define on one hand the operating conditions, the rated characteristics, the design and the manufacture; and on the other hand the testing, the

More information

INTERNATIONAL STANDARD

INTERNATIONAL STANDARD INTENATIONAL STANDAD IEC 60034-1 Eleventh edition 2004-04 otating electrical machines Part 1: ating and performance This English-language version is derived from the original bilingual publication by leaving

More information

High-ohmic/high-voltage resistors

High-ohmic/high-voltage resistors FEATURES High pulse loading capability Small size. APPLICATIONS Where high resistance, high stability and high reliability at high voltage are required High humidity environment White goods Power supplies.

More information

Disturbance Recoder SPCR 8C27. Product Guide

Disturbance Recoder SPCR 8C27. Product Guide Issued: April 1999 Status: Updated Version: C/26.04.2006 Data subject to change without notice Features Versatile digital disturbance recorder module for recording various phenomena in the electric power

More information

Equipment: Power Supply, DAI, Transformer (8341), Variable resistance (8311), Variable inductance (8321), Variable capacitance (8331)

Equipment: Power Supply, DAI, Transformer (8341), Variable resistance (8311), Variable inductance (8321), Variable capacitance (8331) Lab 5: Single-phase transformer operations. Objective: to examine the design of single-phase transformers; to study the voltage and current ratios of transformers; to study the voltage regulation of the

More information

IMQ RULES. Contents. IMQ Rules - Product certification

IMQ RULES. Contents. IMQ Rules - Product certification IMQ RULES PRODUCT CERTIFICATION "ELECTRIC ENERGY METERS AND METER UNITS" PRODUCT OF NEW MANUFACTURING Contents IMQ Rules - Product certification Particular Rules for the Electric energy meters and meter

More information

RISH EM 3490 DS Dual Source Energy Meter RISH EM 3490 DS. Application : Product Features:

RISH EM 3490 DS Dual Source Energy Meter RISH EM 3490 DS. Application : Product Features: Application : RISH Master 3490 DS measures important electrical parameters of Utility (in normal mode) & Generators (in Power back up) in three phase and single phase Network & replaces the multiple analog

More information

ε: Voltage output of Signal Generator (also called the Source voltage or Applied

ε: Voltage output of Signal Generator (also called the Source voltage or Applied Experiment #10: LR & RC Circuits Frequency Response EQUIPMENT NEEDED Science Workshop Interface Power Amplifier (2) Voltage Sensor graph paper (optional) (3) Patch Cords Decade resistor, capacitor, and

More information

MAXIMUM LOAD CURRENT 1 A SN SERIES

MAXIMUM LOAD CURRENT 1 A SN SERIES SOLID STATE RELAY (I/O Module) MAXIMUM LOAD CURRENT 1 A SN SERIES RoHS compliant FEATURES I/O modules for interface between CPU and external input devices or loads Ultra slim and light weight, SIL s type

More information

High-Voltage Circuit-Breakers 3AP1/2 72.5 kv up to 550 kv. Power Transmission and Distribution

High-Voltage Circuit-Breakers 3AP1/2 72.5 kv up to 550 kv. Power Transmission and Distribution High-Voltage Circuit-Breakers AP/ 7.5 kv up to 550 kv Power Transmission and Distribution The AP/ High-Voltage Circuit-Breakers Now Applicable for 550 kv Decades of our experience in high-voltage switching

More information

7.2KV SL400 Withdrawable Vacuum Contactor-Fuse Combination Units

7.2KV SL400 Withdrawable Vacuum Contactor-Fuse Combination Units Automotive Powering business worldwide Aerospace Eaton delivers the hundreds of power distribution products that are answering the demands of today s fast changing world. We help our customers worldwide

More information

Electromagnetic Compatibility (EMC) Low-Frequency Standards. Standards on Low-Frequency Emission: IEC 61000-3-2

Electromagnetic Compatibility (EMC) Low-Frequency Standards. Standards on Low-Frequency Emission: IEC 61000-3-2 Electromagnetic Compatibility (EMC) Low-Frequency Standards Summary IEC 61000-3-2: Limits for harmonic current emissions (equipment input current 16A per phase) IEC 61000-3-4: Limitation of emission of

More information

RM17TE 183...528 V AC. Main. Product or component type. Product specific application. Relay monitored parameters 250 V DC 5 A DC

RM17TE 183...528 V AC. Main. Product or component type. Product specific application. Relay monitored parameters 250 V DC 5 A DC Characteristics multifunction control relay RM17-TE - range 183..528 V AC Complementary Reset time Maximum switching voltage Minimum switching current Maximum switching current [Us] rated supply voltage

More information

CAT AVR V2.3. Instruction Manual. Voltage regulator for generators. March 2008

CAT AVR V2.3. Instruction Manual. Voltage regulator for generators. March 2008 CAT AVR V2.3 Voltage regulator for generators March 2008 Instruction Manual Warnings WARNING The system should not be installed, operated, serviced or modified except by qualified personnel who understand

More information

Superconducting and Solid-State Electronic Fault Current Limiter Technologies The shift from demonstration projects to Business-as-Usual solutions

Superconducting and Solid-State Electronic Fault Current Limiter Technologies The shift from demonstration projects to Business-as-Usual solutions Superconducting and Solid-State Electronic Fault Current Limiter Technologies The shift from demonstration projects to Business-as-Usual solutions Dr. Detlev Kirsten & Herbert Piereder Solid State SSFCL

More information

General Validation Test Program for Wind Power Plants Connected to the Hydro-Québec Transmission System

General Validation Test Program for Wind Power Plants Connected to the Hydro-Québec Transmission System General Validation Test Program for Wind Power Plants Connected to the Hydro-Québec Transmission System Direction Planification des actifs et expertise de transport February 2011 TABLE OF CONTENTS 1. CONDUCTING

More information

High-ohmic/high-voltage resistors

High-ohmic/high-voltage resistors FEATURES These resistors meet the safety requirements of: UL1676 (range 510 kω to 11 MΩ) EN60065 BS60065 (U.K.) NFC 92-130 (France) VDE 0860 (Germany) High pulse loading capability Small size. APPLICATIONS

More information

MEDIUM VOLTAGE CE-BF SWITCHBOARDS. UP TO 40.5 kv. CE - BF - C - en - REV.00 2012.4

MEDIUM VOLTAGE CE-BF SWITCHBOARDS. UP TO 40.5 kv. CE - BF - C - en - REV.00 2012.4 CE - BF - C - en - REV.00 2012.4 APPLICATION CE-BF Switchbords up to 40.5 kv are designed for use in public and industrial distribution system up to 40,5KV for the operation and protection of lines, transformers,

More information

BASIC ELECTRONICS AC CIRCUIT ANALYSIS. December 2011

BASIC ELECTRONICS AC CIRCUIT ANALYSIS. December 2011 AM 5-202 BASIC ELECTRONICS AC CIRCUIT ANALYSIS December 2011 DISTRIBUTION RESTRICTION: Approved for Pubic Release. Distribution is unlimited. DEPARTMENT OF THE ARMY MILITARY AUXILIARY RADIO SYSTEM FORT

More information

Introduction to Paralleling of LTC Transformers by the Circulating Current Method

Introduction to Paralleling of LTC Transformers by the Circulating Current Method TAPCHANGER CONTROLS Application Note #11 Introduction to Paralleling of LTC Transformers by the Circulating Current Method 1.0 ABSTRACT This Application Note discusses the elements of paralleling load

More information

Two Position Cable-to-Board Power Connector System (Right Angle/Straight) with Coding Contacts

Two Position Cable-to-Board Power Connector System (Right Angle/Straight) with Coding Contacts Product Specification 108-19346 17 APR 2013 Rev F Two Position Cable-to-Board Power Connector System (Right Angle/Straight) with Coding Contacts 1. SCOPE 1.1. Content NOTE The product may not perform according

More information

IEC and IEEE Standards for High-Voltage Switchgear and Controlgear Present Situation and Future Evolution

IEC and IEEE Standards for High-Voltage Switchgear and Controlgear Present Situation and Future Evolution IEC and IEEE Standards for High-Voltage Switchgear and Controlgear Present Situation and Future Evolution Denis Dufournet Chairman IEC TC 17 & SC17A Fellow IEEE Senior Expert Areva T&D Mumbai, January,

More information

Product Data Bulletin

Product Data Bulletin Product Data Bulletin Power System Harmonics Causes and Effects of Variable Frequency Drives Relative to the IEEE 519-1992 Standard Raleigh, NC, U.S.A. INTRODUCTION This document describes power system

More information

SUITABILITY OF DIFFERENT TEST VOLTAGES FOR ON-SITE TESTING OF XLPE CABLE SYSTEMS

SUITABILITY OF DIFFERENT TEST VOLTAGES FOR ON-SITE TESTING OF XLPE CABLE SYSTEMS SUITABILITY OF DIFFERENT TEST VOLTAGES FOR ON-SITE TESTING OF XLPE CABLE SYSTEMS Michael Hensel HIGHVOLT Prüftechnik Dresden GmbH 2 3 Content 1 Introduction Test parameters and their significance Differences

More information

Power Meter Series 700

Power Meter Series 700 PowerLogic power-monitoring units Power Meter Series 700 Technical data sheet 2007 Functions and characteristics E90463 The PowerLogic Power Meter Series 700 offers all the measurement capabilities required

More information

2a. IEM Indoor Metal Clad Medium Voltage Switchgear 15KV 16346-1. 2a. Section 16346 INDOOR METAL CLAD MEDIUM VOLTAGE SWTICHGEAR (Std.

2a. IEM Indoor Metal Clad Medium Voltage Switchgear 15KV 16346-1. 2a. Section 16346 INDOOR METAL CLAD MEDIUM VOLTAGE SWTICHGEAR (Std. 2a. IEM Indoor Metal Clad Medium Voltage Switchgear 15KV 16346-1 2a. Section 16346 INDOOR METAL CLAD MEDIUM VOLTAGE SWTICHGEAR (Std. Relays) Part 1 General 1.1 CONDITIONS AND REQUIREMENTS: A. Refer to

More information

Power-monitoring unit PowerLogic System. Technical data sheet. Power Meter Series 800

Power-monitoring unit PowerLogic System. Technical data sheet. Power Meter Series 800 Power-monitoring unit PowerLogic System Technical data sheet 2003 Power Meter Series 800 Function and characteristics PB100313 The PowerLogic Power Meter Series 800 offers all the high-performance measurement

More information

RM4TG20 three-phase network control relay RM4-T - range 200..500 V

RM4TG20 three-phase network control relay RM4-T - range 200..500 V Characteristics three-phase network control relay RM4-T - range 200..500 V Complementary [Us] rated supply voltage Output contacts Setting accuracy of time delay Delay at power up Measuring cycle Marking

More information

Electronic timer CT-AHD.12 OFF-delayed with 1 c/o (SPDT) contact

Electronic timer CT-AHD.12 OFF-delayed with 1 c/o (SPDT) contact Data sheet Electronic timer CT-AHD.12 OFF-delayed with 1 c/o (SPDT) contact The CT-AHD.12 is an electronic time relay with OFF-delay. It is from the CT-D range. With their MDRC profile and a width of only

More information

SC Series: MIS Chip Capacitors

SC Series: MIS Chip Capacitors DATA SHEET SC Series: MIS Chip Capacitors Applications Systems requiring DC blocking or RF bypassing Fixed capacitance tuning element in filters, oscillators, and matching networks Features Readily available

More information

handbook, 2 columns handbook, halfpage 085 CS

handbook, 2 columns handbook, halfpage 085 CS FEATURES Polarized aluminium electrolytic capacitors, non-solid, self healing Extended voltage and capacitance range SMD-version, fully moulded, insulated Flexible terminals, reflow and wave solderable

More information

Technical data UNIBLOCK UBSF 180 625

Technical data UNIBLOCK UBSF 180 625 Data TECHNICL DT Technical data UNIBLOCK UBSF 80 6 Output data Type UBSF 80 UBSF 0 UBSF 00 UBSF 6 Output power 80 kv 0 kv 00 kv 6 kv Output voltage 80/77 V 0/ V 0/ V 0/ V Output current 7 8 66 80 Power

More information

Digital Pressure Measuring Instrument MDR480

Digital Pressure Measuring Instrument MDR480 Description The digital panel instrument MDR480 is designed to measure, display, and monitor pressures in industrial applications. The instrument is panel mounted with a front frame dimension of 96 mm

More information