Chapter (2) Circuit Breakers

Size: px
Start display at page:

Download "Chapter (2) Circuit Breakers"

Transcription

1 Chapter (2) Circuit Breakers 2.1 Introduction A circuit breaker is required to perform the following three duties: 1. It must be capable of opening the faulty circuit and breaking the fault current. 2. It must be capable of being closed on to a fault 3. Must be capable of carrying fault current for a short time while another breaker is clearing the fault. Depending on the above duties circuit breaker has three ratings breaking capacity, making capacity and short time capacity. 10

2 BREAKING CAPACITY It is current that a circuit breaker is capable of breaking at a given recovery voltage under specified conditions. The breaking capacity is always stated at the r.m.s value of fault current at the instant of contact separation. When a fault occurs there is considerable asymmetry in the fault current due to presence of d.c component. The d.c component dies away rapidly. The contacts are separated at DD as shown in fig5 11

3 12

4 At this point, fault current has x = max value of a.c component y = d.c component Therefore Symmetrical breaking current = r.m.s value of a.c component = x / [2] 1/2 Asymmetrical breaking current = r.m.s value of a.c component =[[x / [2] 1/2 ]^ 2 + y^ 2 ] Breaking capacity is expressed in MVA by taking into account the rated breaking current and rated service voltage. Thus if I is the rated breaking current in amperes and V is rated service line voltage in volts, then for a three phase circuit breaking capacity = 3 * V * I * 10 6 MVA 13

5 MAKING CAPACITY The capacity of a breaker to make current depends upon its ability to withstand and close successfully against the effects of electromagnetic forces. These forces are proportional to the square of maximum instantaneous current on closing. So making capacity is stated in terms of a peak value of current. The peak value of current during the first cycle of current wave after the closure of circuit breaker is known as making capacity. To find making capacity multiply symmetrical breaking current by root 2 to convert from r.m.s to peak and then by 1.8 to include the doubling effect of maximum asymmetry. Making capacity = 2.55 * symmetrical breaking capacity. 14

6 SHORT TIME RATING It is the period for which the circuit breaker is able to carry fault current while remaining closed. The fault on the system of very temporary nature persist for 1 or 2 sec after which the fault will be cleared, so the breaker should not be tripped in such situations. This means the circuit breakers should be able to carry high current safely for some specified period while remaining closed. i.e they should have short time rating. It depends on its ability to withstand electromagnetic force effects and temperature rise. 15

7 2.2 Trip circuit of circuit breakers Consider a simplified circuit of a typical relay as shown in the Fig. 1 usually the relay circuit is a three phase circuit and the contact circuit of relays is very much complicated. The Fig. 1 shows a single phase simplified circuit to explain the basic action of a relay. Let part A is the circuit to be protected. The current transformer C.T. is connected with its primary in series with the line to be protected. The secondary of C.T. is connected in series with the relay coil. The relay contacts are the part of a trip circuit of a circuit breaker. The trip circuit consists of a trip coil and a battery, in addition to relay 16 contacts. The trip circuit can operate on a.c. or d.c.

8 If the fault occurs as shown in the Fig. 1, Then current through the line connected to A increases to a very high value. The current transformer senses this current. Accordingly its secondary current increases which is nothing but the current through a relay coil. Thus the relay contacts get closed mechanically under the influence of such a high fault current. Thus the trip circuit of a circuit breaker gets closed and current starts flowing from battery, through trip coil, in a trip circuit. Thus the trip coil of a circuit breaker gets energized. This activates the circuit breaker opening mechanism, making the circuit breaker open. This isolates the faulty part from rest of the healthy system. 17

9 Prof. Dr. Sayed A. Ward 18 Fig.1 typical C.Bs and Substations relay circuit 4th year elec. Power Eng.

10 2.3 Tripping Schemes in Circuit Breaker Two schemes are very popularly used for tripping in circuit breakers which are: 1. Relay with make type contact 2. Relay with break time contact The relay with make type contact requires auxiliary d.c. supply with its operation. while the relay with break type contact uses the energy from the main supply source for its operation. Let us see the details of these two types of schemes. 19

11 2.3.1 Relays With Make Type Contact The schematic diagram representing the arrangement of various elements in a relay with make type contact is shown in the Fig.2. A separate supply is necessary for the relay operation. The relays are connected in star while the relay contacts are connected in parallel. The entire relay contact unit is connected in series with the auxiliary switch, trip coil and the battery. Relay contacts are open in normal position. 20

12 Fig. 2 Relay with make type contact 21

13 Operation : When the fault occurs, the current through relay coils increases to a very high value. Due to this, the normally open relay contacts C 1, C 2 and C 3 get closed. This activates the trip coil of a circuit breaker. The auxiliary switch is initially closed along with the circuit breaker. So when contacts C 1, C 2 and C 3 are closed, the current flows through trip coil of circuit breaker. This activates the trip coil which opens the circuit breaker. As auxiliary switch is mechanically coupled with the circuit breaker, it also gets opened. This interrupts the current through trip coil. Thus supply to fault part gets interrupted and trip coil also gets de-energized. This brings the relay contacts back to normal position. 22

14 Due to auxiliary switch, arcing across relay contacts gets avoided. As relay contacts are normally open and they 'make' the circuit to open the circuit breaker hence called make type contact relay. 23

15 2.3.2 Relay With Break Type Contact The schematic arrangement of various elements in a relay with break type contact is shown in the Fig. 3. This type of relay does not require external battery supply for the tripping. The current transformers (C.T.s) or potential transformer (P.T.s) are used to derive the energy required for the relay from the main supply source. The relay using C.T.s to derive operating energy from the supply is shown in the Fig

16 Fig.3 Relay with break type contact (using C.T.s) 25

17 In this scheme, the relay coil and trip coil of each are connected in series. The three phases are then connected in star. Under normal working, the relay contacts C 1, C 2 and C 3 are closed. The energy for relay coils is derived from supply using C.T.s. The trip coils of circuit breaker are deenergized under normal condition. When the fault occurs, heavy current flows through relay coils due to which relay contacts C 1, C 2 and C 3 break. Thus current flows through trip coils of circuit breaker due to which circuit breaker gets open. 26

18 The Fig. 4 shows the break type contact relay using P.T. to derive energy to keep relay coils energized. 27

19 Fig.4 Relay with break type contact (using P.T.) 28

20 In this type, in addition to normal trip coils of circuit breaker, an additional undervoltage trip coil is used. All the relay contacts are in series with the undervoltage trip coil. Through potential transformer, for normal voltage, the undervoltage trip coil is kept energized. When the voltage becomes less than the normal value, the magnetic effect produced by undervoltage trip coil reduced which is responsible for the opening of the circuit breaker. When fault occurs, the normal trip coils of circuit breaker comes into the picture and are responsible for the opening of the circuit breaker. 29

21 In both the above types of tripping circuit (using C.T. Or P.T.), relay contacts 'break' to cause the circuit breaker operation hence the relay is called break type contact relay. 30

22 2.4.Classification of Circuit Breakers Circuit breakers can be arbitrarily classified using criteria such as, 1. intended voltage application, 2. Location of installation (i.e. outdoor, indoor), 3. Their external design characteristics, or perhaps the most important, method and medium used for the current interruption. This is shown in Fig

23 Fig.5 Classification of Circuit Breakers 32

24 2.4.1 Classification by Voltage The classification of circuit breakers by its intended application voltage, is normally as given in Fig Classification by Location Switchgears, based on where they are located are classified as, indoor and outdoor types (Fig.6) Medium and low voltage switchgears, and high voltage Gas Insulated Switchgears (GIS) are mostly categorised as Indoor switchgears, whereas the switchgears which have air as an external insulating medium, i.e. Air Insulated Switchgear (AIS), are categorised as Outdoor Switchgears. These are shown in Fig

25 Prof. Dr. Sayed Fig. A. Ward 34 6 Switchgear C.Bs and Substations based on Location 4th year elec. Power Eng.

26 2.4.3 Classification by External Design Outdoor circuit breakers can be identified as either dead-tank or live-tank type of circuit breakers, from the point of view of their physical structural design (Fig. 6). 35

27 Dead Tank C.B. dead-tank circuit breakers, the switching device is located, with suitable insulator supports, inside a metallic vessel(s) at ground potential and filled with insulating medium. In dead-tank circuit breakers, the incoming and outgoing conductors are taken out through suitable insulator bushings, and low voltage type current transformers are located at the lower end of both insulator bushings, i.e. at the line side and the load side. 36

28 Live Tank C.B. In live-tank circuit breakers, the interrupter(s) is located in an insulator bushing, at a potential above ground potential. The live-tank circuit breakers are cheaper (with no current transformer), and require less mounting space. 37

29 Prof. Dr. Sayed A. Ward 38 Classification C.Bs and Substations of C.B. 4th year elec. Power Eng.

30 2.4.4 Classification by Interrupting Media The interrupting medium has been the vital factor in the evolution of circuit breakers. It dictates the overall design parameters of the breaker. The choice of air and oil, as the interrupting media, was predominant till late 70s. But today, vacuum and Sulphur hexafluoride (SF6) are the only dominant interrupting technologies, for medium and high voltage segments of circuit breaker design respectively. 39

31 2.5Techniques to extinguish the arc in C. B. Each circuit breaker will be studied thoroughly in the subsequent sections. These circuit breaker employ various technique to extinguish the arc resulting from separation of the current carrying contacts. The mode of arc extinction is:- 1. either 'high resistance interruption' 2. or 'zero-point interruption'. 40

32 2.5.1 High Resistance Interruption High Resistance Interruption: In this process the resistance of the arc is increased by lengthening and cooling it to such an extent that the system voltage is no longer able to maintain the arc and the arc gets extinguished. This technique is employed in air break circuit breakers and d.c. circuit breakers. 41

33 2.5.2 Low Resistance or Zero Point Interruption Low Resistance or Zero Point Interruption: In this process, the arc gets extinguished at natural current zero of the alternating current wave and is prevented from re-striking again by rapid build-up of dielectric strength of the contacts space. This process is employed in almost all a.c. circuit breakers. 42

34 Each leading manufacturer of circuit breaker develops two or more types of circuit breakers for every voltage class. The construction of the circuit breaker depends upon its type (arc-quenching medium), voltage rating and structural form. 43

35 Air-break circuit breaker : Utilize air at atmospheric pressure for arc extinction. Air-blast circuit breakers : Utilize high pressurecompressed air for arc extinction. They need compressed air plant. Bulk-oil and Minimum-oil circuit breaker : utilize dielectric oil ( Transformer oil ) for arc extinction. In bulk-oil circuit breakers, the contacts are separated inside a steel tank filled with dielectric oil. In minimum oil circuit breakers the contacts are separated in an insulating housing (interrupter) filled with dielectric oil. 44

36 SF6 circuit breakers : sulphur-hexa-fluoride gas is used for arc extinction. There are two types : Single pressure puffer type SF6 circuit breaker, in which the entire circuit breaker is filled with SF6 gas at single pressure ( 4 to 6 kg/cm 2 ). The pressure and gas flow required for arc extinction is obtained by piston action. Double pressure type SF6 circuit breaker in which the gas from high-pressure system is released into low pressure system over the arc during the arc quenching process. This type has been superseded by puffer type. 45

37 Vacuum circuit breaker : In vacuum circuit breaker the fixed and moving contacts are housed inside a permanently sealed vacuum interrupter. The arc is quenched as the contacts are separated in high vacuum. A brief comparison between the different types of circuit breakers is given in table 1. (see the newer post) Table 1 Comparison of circuit breakers 46

38 Type Medium Voltage. Breaking capacity Design Feature Remarks 1- Air- break circuit breaker Air at atmospheric pressure V, MVA Recently KV, 500 MVA Incorporates: Arc runners, arc splitters, magnetic coils Used for medium and low voltage, A.C., D.C., Industrial circuit breakers. Have current limiting Miniature C.B. Air at atmospheric pressure KV Small size, current limiting feature Used for low and medium voltage 2- Tank type oil circuit breaker Dielectric oil KV One tank up to 36 KV, 3 tank above 36 KV, fitted with arc control devices Getting obsolete, used up to 12 KV, 500 MVA 3- Minimum oil circuit breaker Dielectric oil KV The circuit breaking chamber is separate from supporting chamber. Small size, arc control device used Used for metal enclosed switchgear up to 36 KV. Outdoor type between 36 and 245 KV 4- Air blast circuit breaker Compressed air (20-30 kgf/cm 2 ) 245 KV, MVA up to 1100 KV, MVA, also 36 KV, 500 MVA Unit type construction, several units per pole, auxiliary compressed air system required Suitable for all EHV applications, fast openingclosing. Also for arc furnace duty 5- SF6 circuit breaker single SF6 gas (5 kgf/cm 2 ) 145 KV, 7500 MVA 245 KV, MVA 12 KV, 500 MVA 36 KV, 2000 MVA Live tank/dead tank design, single pressure type preferred Suitable for SF6 switchgear, and medium voltage switchgear. EHV circuit breaker. Maintenance free 6- Vacuum circuit breaker Vacuum Preferred for indoor switchgear rated up to 36 KV, 750 MVA Variety of designs, long life, modest maintenance Suitable for a variety of applications from 3.6 KV up to 36 KV 7- H.V.D.C circuit breaker Vacuum or SF6 500 KV DC, 15 KA/20 KA Artificial current zero by switching in capacitors Recently developed, used in HVDC systems. Installed in USA 47

39 2.6 Rated characteristic of circuit breakers The rating of a circuit breaker denote its capabilities under specified condition of use and behaviour. The following paragraphs are generally based on the recommendation of IEC-56: "High Voltage Alternating Current Circuit-Breakers" and IS-2516: " Specifications of Alternating current circuit-breaker". The capabilities of a circuit breaker of a particular type are proved by conducting type tests as per the recommendations of the standards. 48

40 2.6.1 Rated Voltage The rated voltage of a circuit-breaker corresponds to the higher system voltage for which the circuit breaker is intended. The standards values of rated voltages are given in table 2. The rated voltage is expressed in KVrms and refers to phase to phase voltage for threephase circuit. The earlier practice of specifying the rated voltage of a circuit breaker as nominal system voltage is no more followed. 49

41 Table 2 : Rated Voltage of Circuit Breaker Nominal System Voltage ( KVrms ) Rated Voltage of Circuit Breaker ( KVrms )

42 2.6.2 Rated Insulation Level of C.B. The rated insulation level of a circuit breaker refers to:- 1. The power frequency withstand voltage and 2. Impulse voltage withstand values which characterize the insulation of the circuit breaker. 51

43 Causing of Power-frequency over voltages Power-frequency over voltages are due to regulation, ferranti effect, higher tap-setting, etc. The circuit breaker should be capable of withstanding the power frequency over-voltages which are likely to occur. These capabilities are verified by conducting power frequency voltage withstand tests and impulse voltage withstand tests. The circuit breaker is subjected to impulse over-voltage due causes like lighting surge and switching surge. 52

44 During single-line to ground faults, the voltage of healthy lines to earth increases to 3 time the normal value in the system with insulated neutral. Hence higher values of insulation are recommended for circuit breaker connected in noneffectively earthed systems. The following insulations are provided in the circuit breaker : Insulation between live parts and earth for each pole external and internal. Insulation between poles. Insulation between terminals of the same pole-external and internal The design of these insulations depends upon the structural form of the circuit breaker and the rated insulation level desired. 53

45 2.6.3 Rated Frequency The standard frequency for a three pole circuit breaker is the frequency of the power system (50/60 HZ). The characteristics like normal current breaking capacity etc. are based on the rated frequency. The frequency of the current influences the circuit breaker behaviour as follows: 54

46 The temperature rise of current carrying parts and neighbouring metallic parts is influenced by eddycurrent heating. The increase in frequency results in increased eddy currents. Hence, with specified limits of the temperature rise the rated current of a circuit breaker needs de-rating for application on higher frequency. The frequency corresponds to the number of current-zeros per second. Since the breaking time of the circuit breaker is associated with the time for half cycles during the arc extinguishing process, the breaking time is influenced by the frequency of current. The breaking time increases with reducing 55 in frequency.

47 The increase in frequency influences the TRV and rate-of-rise TRV. Hence a circuit breaker designed and rated for a certain frequency cannot be recommended for other frequencies unless capabilities are proved for those frequencies. The d.c. circuit breakers generally adopt a different principle of arc extinction and have different construction than a.c. circuit breaker 56

48 2.6.4 Rated Normal Current (Rated Current) The rated normal current of a circuit breaker is the r.m.s value of the current which the circuit breaker can carry continuously and with temperature rise of the various parts within specified limits. Preferred values of rated current in A rms are 400, 630, 800, 1250, 1600, 2000, 2500, 3150, and

49 The design of contacts and other current carrying parts in the interrupter of the circuit breaker are generally based on the limits of the temperature rise. For a given cross-section of the conductor and a certain value of current, the temperature rise depends upon the conductivity of the material. Hence, high conductivity material is preferred for current carrying parts. The cross-section of the conductors should be increased for materials with lower conductivity. The use of magnetic materials in close circuits should be avoided to prevent heating due to hysteresis loss and eddy currents. The rated current of a circuit breaker is verified by 58 conducting temperature rise tests.

50 2.6.5 Rated Short Circuit Breaking Current The rated short circuit breaking current of a circuit breaker is the highest rms value of short circuit current which the circuit breaker is capable of breaking under specified conditions of transient recovery voltage and power frequency voltage. It is expressed in KArms at contact separation. 59

51 Referring to Fig. 2, the short circuit current has a certain value at the instant of contact separation, (t = T 1). The breaking current refers to value of current at the instant of the contact separation. The transient recovery voltage refers to the transient voltage appearing across the circuit breaker pole immediately after the arc interruption. 60

52 Figure 2 Oscillogram of Current and Voltage during fault clearing 61

53 The rated values of transient recovery voltage are specified for various rated voltage of circuit breakers. For specified conditions of rated TRV and rated power frequency recovery voltage, a circuit breaker has a certain limit of breaking current. This limit is determined by conducting short circuit type tests on the circuit breaker. The waveforms of short circuit current are obtained during the breaking test. The evaluation of the breaking current is explained in Fig. 3. The breaking current is expressed by two values : 62

54 Figure 3 Dimenstion of breaking current. 63

55 1. The r.m.s value of a.c. component at the instant of contact separation EE, given by (I dc / Square root of 2) 2. The percentage d.c. component at the instant of contact separation given by (I dc X100 / I Ac ) The r.m.s values of a.c. components are expressed in KA. the standard values being 8, 10, 12.5, 16, 20, 25, 31.5, 40, 45, 63, 80 and 100KA. The earlier practice was to express the rated breaking capacity of a circuit breaker in terms of MVA given as follows MVA = 3 x KV x KA Where MVA = Breaking capacity of a circuit breaker kv = Rated voltage ka = Rated breaking current 64

56 This practice of specifying the breaking capacity in terms of MVA is convenient while calculating the fault levels. However, as per the revised standards, the breaking capacity is expressed in KA for specified conditions of TRV and this method takes into account both breaking current and TRV. While selecting the circuit breaker for a particular location in the power system the fault level at that location is determined. The rated breaking current can then be selected from standard range. 65

57 2.6.6 Rated Short Circuit Making Current It may so happen that circuit breaker may close on an existing fault. In such cases the current increase to the maximum value at the peak of first current loop. The circuit breaker should be able to close without hesitation as contact touch. The circuit breaker should be able to withstand the high mechanical forces during such a closure. These capabilities are proved by carrying out making current test. The rated short circuit making current of a circuit breaker is the peak value of first current loop of short circuit current (I pk)which the circuit breaker is capable of 66 making at its rated voltage.

58 The rated short circuit making current should be least 2.5 times the r.m.s. value of a.c. component of rated breaking current. Rated making current = 1.8 x 2 x Rated short circuit breaking = 2.5 x Rated short circuit breaking current In the above equation the factor 2 convert the r.m.s value to peak value. Factor 1.8 takes into account the doubling effect of short circuit current with consideration to slight drop in current during the first quarter cycle. 67

59 Circuit Breaker Time ( total break time) Fault clearing time is the sum of "relay time" and "circuit breaker time". Circuit breaker time is also called "total break time The rapid fault clearing of extra high voltage transmission lines improves the power system stability. Hence, faster relying and fast circuit breaker are preferred for extra high voltage transmission lines, where the circuit breaker time being in order of 2.5 cycles. 68

60 Technical Data Item Unit LW (CY/CYT) LW10B- 363 (CYT) LW10 B-550 (CYT/ ABB) Rated voltage kv Rated frequency Hz 50 Rated current A 3150,4000 Rated short circuit breaking current ka 40/ Rated short line fault breaking current ka 36/ Rated out of phase breaking current ka 10/ Rated peak withstand current ka 100/ Rated short circuit making current (peak) ka 100/ Rated short time withstand current ka 40/ Rated duration of short circuit S 3 Rated line charging breaking current (r.m.s) A Breaking time of rated short circuit current times 20 Mechanical endurance times 5000/1000 Rated SF 6 gas pressure at 20 Mpa 0.4/ SF 6 gas moisture content (Ex-work) PPM 150 SF 6 gas leakage rate (per year) % 1 6 (without closing 12 (without closing 20 (without closing SF 6 gas weight (per pole) kg resistance)/10(with closing resistance)/15(with closing resistance)/25(with resistance) resistance closing resistance Circuit Breaker weight (per pole) kg 1600 (without closing resistance)/1800(with closing resistance 2530 (without closing resistance)/3180(with closing resistance 2840(without closing resistance)/3800(wit h closing resistance) Operation force for opening/closing kn 76/38 130/60 130/60 Longitudinal N Terminal load Horizontal N Vertical N

61 For distribution system, such a fast clearing is not necessary. Discrimination is obtained by "graded time lag:. Hence, slower circuit breaker, 3 to 5 cycles, are used. Total breaking time varies between ms for circuit breaker up to 12KV and ms for circuit breaker above 36KV. It is less than 60 ms for 145KV, less than 50 ms for 420 KV circuit breaker. 70

62 Fault clearing Time Remember the following time events : Fault clearing time = relay time + circuit breaker time Relay time = instant of fault to closure of trip circuit Circuit breaker time = opening time + arcing time 71

Fundamentals of Modern Electrical Substations Part 1: Mission of Electrical Substations and their Main Components

Fundamentals of Modern Electrical Substations Part 1: Mission of Electrical Substations and their Main Components Fundamentals of Modern Electrical Substations Part 1: Mission of Electrical Substations and their Main Components Course No: E02-010 Credit: 2 PDH Boris Shvartsberg, Ph.D., P.E., P.M.P. Continuing Education

More information

TWENTIES WORKSHOP, EWEA 2012 Unveiling the future energy system: full scale demonstrations to reach 2020 targets. 17th April 2012

TWENTIES WORKSHOP, EWEA 2012 Unveiling the future energy system: full scale demonstrations to reach 2020 targets. 17th April 2012 TWENTIES WORKSHOP, EWEA 2012 Unveiling the future energy system: full scale demonstrations to reach 2020 targets 17th April 2012 Session 2 Technological challenges to cope with in TWENTIES field tests

More information

MV, HV AND EHV SWITCHGEAR TESTING & COMMISSIONING

MV, HV AND EHV SWITCHGEAR TESTING & COMMISSIONING Training Title MV, HV AND EHV SWITCHGEAR TESTING & COMMISSIONING Training Duration 5 days Training Date MV, HV and EHV Switchgear Testing & Commissioning 5 20 24 Apr $3,750 Dubai, UAE In any of the 5 star

More information

SWITCHGEAR PROTECTION

SWITCHGEAR PROTECTION LECTURE NOTES ON SWITCHGEAR PROTECTION IV B. Tech I semester (JNTUH-R09) Mr. P SHIVAKUMAR Assistant Professor ELECTRICAL AND ELECTRONICS ENGINEERING INSTITUTE OF AERONAUTICAL ENGINEERING DUNDIGAL, HYDERABAD

More information

The Importance of the X/R Ratio in Low-Voltage Short Circuit Studies

The Importance of the X/R Ratio in Low-Voltage Short Circuit Studies The Importance of the X/R Ratio in Low-Voltage Short Circuit Studies DATE: November 17, 1999 REVISION: AUTHOR: John Merrell Introduction In some short circuit studies, the X/R ratio is ignored when comparing

More information

SF 6 Gas Insulated Switchgear Type SDF for 170 kv

SF 6 Gas Insulated Switchgear Type SDF for 170 kv Three Phase Encapsulated Type SF 6 Gas Insulated Switchgear Type SDF for 170 kv 06B1-E-0001 With Trustworthy Technology, Structure Fuji Electric as a manufacturer of comprehensive substation equipment

More information

Digital Energy ITI. Instrument Transformer Basic Technical Information and Application

Digital Energy ITI. Instrument Transformer Basic Technical Information and Application g Digital Energy ITI Instrument Transformer Basic Technical Information and Application Table of Contents DEFINITIONS AND FUNCTIONS CONSTRUCTION FEATURES MAGNETIC CIRCUITS RATING AND RATIO CURRENT TRANSFORMER

More information

Fundamentals of Power

Fundamentals of Power Fundamentals of Power Fundamentals of Power 2008 American Power Conversion Corporation. All rights reserved. All trademarks provided are the property of their respective owners. Learning Objectives At

More information

Advantages of Fixed Circuit Breaker Switchgear

Advantages of Fixed Circuit Breaker Switchgear Advantages of Fixed Circuit Breaker Switchgear by Lionel Mackay, EDF Energy, and Mike Adams, Schneider Electric Ltd Introduction The purpose of this paper is to review the advantages of fixed circuit breaker

More information

Generator Stator Protection, under/over voltage, under /over frequency and unbalanced loading. Ramandeep Kaur Aujla S.NO 250447392

Generator Stator Protection, under/over voltage, under /over frequency and unbalanced loading. Ramandeep Kaur Aujla S.NO 250447392 1 Generator Stator Protection, under/over voltage, under /over frequency and unbalanced loading By Ramandeep Kaur Aujla S.NO 250447392 ES 586b: Theory and applications of protective relays Department of

More information

Dead Tank Circuit Breaker 72PM40-C Proven reliability through common platforms

Dead Tank Circuit Breaker 72PM40-C Proven reliability through common platforms Dead Tank Circuit Breaker 72PM40-C Proven reliability through common platforms ABB innovations for changing demands ABB (www.abb.com) is a leader in power and automation technologies that enables utility

More information

The standards mentioned in this document

The standards mentioned in this document The standards mentioned in this document Where can you order IEC publications? Central Offices of the International Electrotechnical Commission 1, rue de Varembé Geneva - Switzerland. The documentation

More information

Trip circuit supervision relay. Type RXTCS

Trip circuit supervision relay. Type RXTCS Trip circuit supervision relay Type RXTCS ABB a global technology leader ABB is a global leader in Power and Automation technologies that enable utility and industry customers to improve performance while

More information

Unified requirements for systems with voltages above 1 kv up to 15 kv

Unified requirements for systems with voltages above 1 kv up to 15 kv (1991) (Rev.1 May 2001) (Rev.2 July 2003) (Rev.3 Feb 2015) Unified requirements for systems with voltages above 1 kv up to 15 kv 1. General 1.1 Field of application The following requirements apply to

More information

ELECTRICAL INSULATION TESTING OF HV EQUIPMENT UP TO 33kV

ELECTRICAL INSULATION TESTING OF HV EQUIPMENT UP TO 33kV 1. SCOPE This document details PowerSystems requirements for electrical testing of HV Equipment up to and including 33kV. 2. ISSUE RECORD This is a Reference document. The current version of Controlled

More information

High-Voltage GIS yesterday - today - tomorrow

High-Voltage GIS yesterday - today - tomorrow High-Voltage GIS yesterday - today - tomorrow Peter Glaubitz, Siemens AG, Principal Expert GIS-Technology siemens.at/future-of-energy Table of content GIS yesterday beginning and establishment of Gas-

More information

Medium Voltage Products. ZN1 12 kv arc-proof air-insulated switchgear for primary distribution

Medium Voltage Products. ZN1 12 kv arc-proof air-insulated switchgear for primary distribution Medium Voltage Products ZN1 12 kv arc-proof air-insulated switchgear for primary distribution ZN1 an innovative switchgear for power distribution requirements ABB ZN1 primary distribution switchgear is

More information

Primary and Secondary Electrical Distribution Systems

Primary and Secondary Electrical Distribution Systems Primary and Secondary Electrical Distribution Systems Critical Facilities Round Table 12th Quarterly Membership Meeting June 2, 2006 David D. Roybal. P.E. Eaton Electrical Cutler-Hammer Products Utility

More information

Best Practice Catalog Generator Switchgear

Best Practice Catalog Generator Switchgear Best Practice Catalog Generator Switchgear Revision 2.0, 8/23/2012 Prepared by MESA ASSOCIATES, INC. Chattanooga, TN 37402 and OAK RIDGE NATIONAL LABORATORY Oak Ridge, Tennessee 37831-6283 managed by UT-BATTELLE,

More information

OVERCURRENT & EARTH FAULT RELAYS. To study the protection of equipment and system by relays in conjunction with switchgear.

OVERCURRENT & EARTH FAULT RELAYS. To study the protection of equipment and system by relays in conjunction with switchgear. OVERCURRENT & EARTH FAULT RELAYS Objective: To study the protection of equipment and system by relays in conjunction with switchgear. Theory: The function of a relay is to detect abnormal conditions in

More information

Type SA-1 Generator Differential Relay

Type SA-1 Generator Differential Relay ABB Automation Inc. Substation Automation and Protection Division Coral Springs, FL 33065 Instruction Leaflet 41-348.11C Effective: November 1999 Supersedes I.L. 41-348.11B, Dated August 1986 ( ) Denotes

More information

Current Limiting Protector For Systems rated 2.8-38kV and continuous currents through 5000A.

Current Limiting Protector For Systems rated 2.8-38kV and continuous currents through 5000A. Current Limiting Protector For Systems rated 2.8-38kV and continuous currents through 5000A. Arc Flash and Arc Blast reduction Network protection SCADA adaptable Indoor/outdoor application Professional

More information

Circulating Current Relay. Type IRXm

Circulating Current Relay. Type IRXm Circulating Current Relay Type IRXm ABB a global technology leader ABB is a global leader in Power and Automation technologies that enable utility and industry customers to improve performance while lowering

More information

Cahier technique no. 193

Cahier technique no. 193 Collection Technique... Cahier technique no. 193 MV breaking techniques S. Théoleyre "Cahiers Techniques" is a collection of documents intended for engineers and technicians, people in the industry who

More information

Step Voltage Regulators

Step Voltage Regulators Step Voltage Regulators Don Wareham Field Application Engineer Today s Agenda Introduction Voltage Regulator theory Voltage Regulator application considerations Installation and proper bypassing Wrap-up/questions

More information

ALTERNATIVE METHODS FOR INTERNAL ARC TESTS ON 12 KV AND 24 KV METAL-ENCLOSED SWITCHGEARS WITH COMPACT RMU

ALTERNATIVE METHODS FOR INTERNAL ARC TESTS ON 12 KV AND 24 KV METAL-ENCLOSED SWITCHGEARS WITH COMPACT RMU ALTERNATIVE METHODS FOR INTERNAL ARC TESTS ON 12 KV AND 24 KV METAL-ENCLOSED SWITCHGEARS WITH COMPACT RMU George CURCANU, Constantin ILINCA, Ilie SBORA ICMET Craiova, Romania, Calea Bucuresti 144, phone:

More information

High-Voltage Compact Switchgear 3AP1 DTC for 145 kv and 245 kv

High-Voltage Compact Switchgear 3AP1 DTC for 145 kv and 245 kv High-Voltage Compact Switchgear AP1 DTC for 1 kv and kv Answers for energy. The AP1 DTC Complying with our Customers demands Experience you can rely on - at anytime, anywhere Decades of experience in high-voltage

More information

Auxiliary Relay. Type P8n, PQ8n, PN8n

Auxiliary Relay. Type P8n, PQ8n, PN8n Auxiliary Relay Type P8n, PQ8n, PN8n ABB a global technology leader ABB is a global leader in Power and Automation technologies that enable utility and industry customers to improve performance while lowering

More information

ANCILLARY EQUIPMENT AND ELECTRICAL EQUIPMENT Power Supply Systems and Electrical Equipment for Desalination Plants - Y.M. Hamud and A.H.

ANCILLARY EQUIPMENT AND ELECTRICAL EQUIPMENT Power Supply Systems and Electrical Equipment for Desalination Plants - Y.M. Hamud and A.H. POWER SUPPLY SYSTEMS AND ELECTRICAL EQUIPMENT FOR DESALINATION PLANTS Y.M. Hamud and A.H. Anwar Abu Dhabi Water and Electricity Authority, Abu Dhabi, UAE Keywords : Electrical System, Network for Desalination,

More information

2a. IEM Indoor Metal Clad Medium Voltage Switchgear 15KV 16346-1. 2a. Section 16346 INDOOR METAL CLAD MEDIUM VOLTAGE SWTICHGEAR (Std.

2a. IEM Indoor Metal Clad Medium Voltage Switchgear 15KV 16346-1. 2a. Section 16346 INDOOR METAL CLAD MEDIUM VOLTAGE SWTICHGEAR (Std. 2a. IEM Indoor Metal Clad Medium Voltage Switchgear 15KV 16346-1 2a. Section 16346 INDOOR METAL CLAD MEDIUM VOLTAGE SWTICHGEAR (Std. Relays) Part 1 General 1.1 CONDITIONS AND REQUIREMENTS: A. Refer to

More information

DIMENSIONING OF CURRENT TRANSFORMERS FOR PROTECTON APPLICATION

DIMENSIONING OF CURRENT TRANSFORMERS FOR PROTECTON APPLICATION ÿþ üûúùø öõöôùóùõò CT Dimensioning DIMENSIONING OF CURRENT TRANSFORMERS FOR PROTECTON APPLICATION Application note GER3973 1 CT Dimensioning ÿþ üûúùø öõöôùóùõò GER-3973 Application note ÿþ üûúùø öõöôùóùõò

More information

Secondary Unit Substations

Secondary Unit Substations 14 SWITCHGEAR Secondary Unit Substations Overview Siemens offers a wide variety of unit substation designs to meet customer requirements. A unit substation consists of one or more transformers mechanically

More information

Arc Terminator Active Arc-Resistant Switchgear

Arc Terminator Active Arc-Resistant Switchgear Arc Terminator Active Arc-Resistant Switchgear Increasing safety and productivity by extinguishing internal arcing faults within the switchgear. The Square D Arc Terminator from Schneider Electric offers

More information

High-Voltage Circuit-Breakers 3AP1/2 72.5 kv up to 550 kv. Power Transmission and Distribution

High-Voltage Circuit-Breakers 3AP1/2 72.5 kv up to 550 kv. Power Transmission and Distribution High-Voltage Circuit-Breakers AP/ 7.5 kv up to 550 kv Power Transmission and Distribution The AP/ High-Voltage Circuit-Breakers Now Applicable for 550 kv Decades of our experience in high-voltage switching

More information

Selecting Current Transformers Part 1 By Darrell G. Broussard, P.E.

Selecting Current Transformers Part 1 By Darrell G. Broussard, P.E. By Darrell G. Broussard, P.E. Introduction: As engineers, we are aware that electrical power systems have grown. How much have they grown? When was the last time you specified a 2400-volt system, a 4160-volt

More information

Power transformers. Special transformers Railway

Power transformers. Special transformers Railway Power transformers Special transformers Railway A leader in railway systems Our compact and low-weight transformers fully comply with the customer s specifications. The products are developed together

More information

Current and voltage measuring relays

Current and voltage measuring relays Current and voltage measuring relays RXIK 1, RXEEB 1 and Page 1 Issued June 1999 Changed since July 1998 Data subject to change without notice RXIK 1 RXEEB 1 (SE980082) (SE980081) (SE970869) Features Application

More information

3.0 CHARACTERISTICS. AR Auxiliary Relay High Speed, High Threshold 41-759.3C

3.0 CHARACTERISTICS. AR Auxiliary Relay High Speed, High Threshold 41-759.3C 41-759.3C the magnetic core upon energizing of the switch. When the switch closes, the moving contacts bridge two stationary contacts, completing the trip circuit. Also during this operation two fingers

More information

AutoLink Three-Phase Sectionalizer Specifications. Scope. General. Applicable Standards. Operating principle

AutoLink Three-Phase Sectionalizer Specifications. Scope. General. Applicable Standards. Operating principle Scope This specification stipulates the minimum requirements for mechanically linked three-phase electronic sectionalizers, for use on outdoor medium voltage overhead lines of 15, 27, and 38 kv. Electronic

More information

INTRODUCTION TO SYSTEM PROTECTION. Hands-On Relay School 2012

INTRODUCTION TO SYSTEM PROTECTION. Hands-On Relay School 2012 INTRODUCTION TO SYSTEM PROTECTION Hands-On Relay School 2012 CONGRATULATIONS On choosing the field of system protection. It is an exciting, challenging profession. System protection has changed considerably

More information

Medium voltage circuit breaker

Medium voltage circuit breaker Medium voltage circuit breaker IEC 60 056 and ANSI C37-06 define on one hand the operating conditions, the rated characteristics, the design and the manufacture; and on the other hand the testing, the

More information

Electrical Shore Connections / Cold Ironing

Electrical Shore Connections / Cold Ironing STANDARD FOR CERTIFICATION No. 2.25 Electrical Shore Connections / Cold Ironing JULY 2014 The electronic pdf version of this document found through http://www.dnv.com is the officially binding version

More information

Fuseology. Medium Voltage Fuses. Continuous Current-Carrying Capacity. General. Interrupting Rating. Additional Rules.

Fuseology. Medium Voltage Fuses. Continuous Current-Carrying Capacity. General. Interrupting Rating. Additional Rules. Fuseology Medium Voltage Fuses General Fuses above are classified under one of three classifications as defined in ANSI/IEEE C37.40. 1. General Purpose Current-Limiting Fuse: A fuse capable of interrupting

More information

MEDIUM AND HIGH VOLTAGE CAPACITORS, CAPACITOR BANKS AND SYSTEMS

MEDIUM AND HIGH VOLTAGE CAPACITORS, CAPACITOR BANKS AND SYSTEMS MEDIUM AND HIGH VOLTAGE CAPACITORS, CAPACITOR BANKS AND SYSTEMS Meher Capacitors offers reliable and innovative products and solutions in the fields of Reactive Power Compensation, Power Quality and Energy

More information

Power Quality Paper #3

Power Quality Paper #3 The Effect of Voltage Dips On Induction Motors by: M D McCulloch 1. INTRODUCTION Voltage depressions caused by faults on the system affect the performance of induction motors, in terms of the production

More information

Residual Current Circuit Breaker

Residual Current Circuit Breaker Introduction Residual Current Circuit Breaker / ELCB The Fault current overloads and short circuits can be detected by circuit breakers like MCB s MCCB s & HRC Fuses etc. But, Circuit breakers don t detect

More information

Outdoor circuit breaker GVR Recloser Hawker Siddeley Switchgear. rated voltage 15, 27 and 38 kv rated current 630 A

Outdoor circuit breaker GVR Recloser Hawker Siddeley Switchgear. rated voltage 15, 27 and 38 kv rated current 630 A Outdoor circuit breaker GVR Recloser Hawker Siddeley Switchgear rated voltage 15, 27 and 38 kv rated current 630 A Outdoor circuit breakers GVR Recloser GVR switchgear brings the reliability of modern

More information

Reyrolle Protection Devices. 7PG17 - XR Intertripping, Interposing, Supervision and Special Purpose Relays. Answers for energy

Reyrolle Protection Devices. 7PG17 - XR Intertripping, Interposing, Supervision and Special Purpose Relays. Answers for energy Reyrolle Protection Devices 7PG17 - XR Intertripping, Interposing, Supervision and Special Purpose Relays. Answers for energy Siemens Protection Devices Limited 2 7PG17 XR101 & XR102 Intertripping Relay

More information

ABB s Disconnecting Circuit Breakers Higher substation availability and lower environmental impact

ABB s Disconnecting Circuit Breakers Higher substation availability and lower environmental impact ABB s Disconnecting Circuit Breakers Higher substation availability and lower environmental impact Authors Carl Ejnar Sölver, ABB High Voltage Products Rasmus Larsson, ABB High Voltage Products 2 ABB ABB

More information

DIRECT CURRENT GENERATORS

DIRECT CURRENT GENERATORS DIRECT CURRENT GENERATORS Revision 12:50 14 Nov 05 INTRODUCTION A generator is a machine that converts mechanical energy into electrical energy by using the principle of magnetic induction. This principle

More information

Current valve. for AC 24 V pulse/pause control of electrical loads up to 30 kw

Current valve. for AC 24 V pulse/pause control of electrical loads up to 30 kw 4 937 DESIO Current valve for AC 24 V pulse/pause control of electrical loads up to 30 kw SEA45.1 Use The current valve is used for the control of electric heating elements in heating, ventilation and

More information

Fusible Disconnect Switch

Fusible Disconnect Switch Circuit Breakers Circuit breakers are used in panelboards and switchboards to provide circuit protection and provide a means of energizing and de-energizing a circuit. Siemens Sentron molded case circuit

More information

IEC and IEEE Standards for High-Voltage Switchgear and Controlgear Present Situation and Future Evolution

IEC and IEEE Standards for High-Voltage Switchgear and Controlgear Present Situation and Future Evolution IEC and IEEE Standards for High-Voltage Switchgear and Controlgear Present Situation and Future Evolution Denis Dufournet Chairman IEC TC 17 & SC17A Fellow IEEE Senior Expert Areva T&D Mumbai, January,

More information

www.siemens.com/energy High Voltage Circuit Breakers 3AP Type 72.5 kv to 800 kv Answers for energy.

www.siemens.com/energy High Voltage Circuit Breakers 3AP Type 72.5 kv to 800 kv Answers for energy. s www.siemens.com/energy High Voltage Circuit Breakers AP Type 7.5 kv to 800 kv Answers for energy. The AP High Voltage Circuit Breakers Available up to 800 kv Decades of our experience in high voltage

More information

Figure 1 - Crydom 3RHP Three-phase Hybrid Solid State Contactor. Crydom Inc.

Figure 1 - Crydom 3RHP Three-phase Hybrid Solid State Contactor. Crydom Inc. Crydom RHP Series 3 Phase Hybrid Solid State Contactor By Paul Bachman Fellow Engineer, Crydom, Inc. ABSTRACT Solid State Relays and Contactors (SSRs) have been available in one form or the other for over

More information

The complete range of consumer switchboards and switchgear

The complete range of consumer switchboards and switchgear Power Distribution The complete range of consumer switchboards and switchgear www.nhp.com.au/mod6 The MOD6 range of consumer switchboards and switchgear is specifically designed for domestic and commercial

More information

UniGear ZS1. Medium voltage, arc proof, air insulated switchgear for primary distribution

UniGear ZS1. Medium voltage, arc proof, air insulated switchgear for primary distribution UniGear ZS1 Medium voltage, arc proof, air insulated switchgear for primary distribution UniGear ZS1: an innovative solution for all installation requirements ABB UniGear is medium voltage metal-clad,

More information

Both variants can be used for measuring the positive sequence voltage Up or the negative sequence voltage Un.

Both variants can be used for measuring the positive sequence voltage Up or the negative sequence voltage Un. Rev. - 2004-10-22 Page 1(5) General RXTBA 1 is a three-phase phase sequence voltage filter built up by resistors and capacitors. The filter is available in two voltage variants; one for rated voltage 3x110

More information

Modular Systems, PPMV, 2014 UniPack-G Glass Fiber Reinforced Polyester Compact Secondary Substation

Modular Systems, PPMV, 2014 UniPack-G Glass Fiber Reinforced Polyester Compact Secondary Substation Modular Systems, PPMV, 2014 UniPack-G Glass Fiber Reinforced Polyester Compact Secondary Substation Index News Introduction Applications & Segments Main Components Applicable Standards Technical characteristics

More information

Siemens Integrated Substation Condition Monitoring System. Circuit Breaker Monitoring

Siemens Integrated Substation Condition Monitoring System. Circuit Breaker Monitoring Siemens Integrated Substation Condition Monitoring System Circuit Breaker Monitoring System Description Introduction The Circuit Breaker Monitor [CBM] is only one example of the way that the Substation

More information

SECTION 4 ELECTRIC MOTORS UNIT 17: TYPES OF ELECTRIC MOTORS

SECTION 4 ELECTRIC MOTORS UNIT 17: TYPES OF ELECTRIC MOTORS SECTION 4 ELECTRIC MOTORS UNIT 17: TYPES OF ELECTRIC MOTORS UNIT OBJECTIVES After studying this unit, the reader should be able to Describe the different types of open single-phase motors used to drive

More information

Current Transformers Ratio / Polarity / Types

Current Transformers Ratio / Polarity / Types CT1 Current Ratio / Polarity / Types Application Current (CT s) are instrument transformers that are used to supply a reduced value of current to meters, protective relays, and other instruments. CT s

More information

Lecture - 4 Diode Rectifier Circuits

Lecture - 4 Diode Rectifier Circuits Basic Electronics (Module 1 Semiconductor Diodes) Dr. Chitralekha Mahanta Department of Electronics and Communication Engineering Indian Institute of Technology, Guwahati Lecture - 4 Diode Rectifier Circuits

More information

Electronic overload relay EF65, EF96 and EF146

Electronic overload relay EF65, EF96 and EF146 Data sheet Electronic overload relay EF65, EF96 and EF146 Electronic overload relays offer reliable protection in case of overload and phase-failure. They are the alternative to thermal overload relays.

More information

Single-phase (220...240 V) voltage monitoring: Undervoltage Overvoltage Window mode (overvoltage + undervoltage) Voltage fault memory selectable

Single-phase (220...240 V) voltage monitoring: Undervoltage Overvoltage Window mode (overvoltage + undervoltage) Voltage fault memory selectable Features 70.11 70.31 70.41 Electronic voltage monitoring relays for single and three-phase applications Multifunctional types, providing the flexibility of monitoring Undervoltage, Overvoltage, Window

More information

RM17TE 183...528 V AC. Main. Product or component type. Product specific application. Relay monitored parameters 250 V DC 5 A DC

RM17TE 183...528 V AC. Main. Product or component type. Product specific application. Relay monitored parameters 250 V DC 5 A DC Characteristics multifunction control relay RM17-TE - range 183..528 V AC Complementary Reset time Maximum switching voltage Minimum switching current Maximum switching current [Us] rated supply voltage

More information

Siemens AG Power Transmission and Distribution Medium Voltage Division Mozartstr. 31c 91052 Erlangen Germany. www.siemens.

Siemens AG Power Transmission and Distribution Medium Voltage Division Mozartstr. 31c 91052 Erlangen Germany. www.siemens. Siemens AG Power Transmission and Distribution Medium Voltage Division Mozartstr. 31c 91052 Erlangen Germany www.siemens.com/energy For questions on power transmission and distribution, please contact

More information

3) What is the difference between "Insulating", "Isolating", and "Shielded Winding" transformers?

3) What is the difference between Insulating, Isolating, and Shielded Winding transformers? Tyco Electronics Corporation Crompton Instruments 1610 Cobb International Parkway, Unit #4 Kennesaw, GA 30152 Tel. 770-425-8903 Fax. 770-423-7194 1) What is a transformer and how does it work? A transformer

More information

Table of Contents. TransformerIQ FAQs 1

Table of Contents. TransformerIQ FAQs 1 [12/12] FAQs Table of Contents FAQ 1. What size transformer will TransformerIQ monitor?... 2 FAQ 2. Are there different TransformerIQ versions?... 2 FAQ 3. How are the units powered?... 2 FAQ 4. What is

More information

ABB Fuses Competitive Advantages

ABB Fuses Competitive Advantages GPMM Tomasz Komalski 2009 ABB Fuses Competitive Advantages May 14, 2009 Slide 1 Basic comments ABB is a global manufacturer of both current limiting and expulsion (non-current limiting) fuses for medium

More information

CATHODIC PROTECTION TRANSFORMER RECTIFIER (CPTR)

CATHODIC PROTECTION TRANSFORMER RECTIFIER (CPTR) CATHODIC PROTECTION TRANSFORMER RECTIFIER (CPTR) Fig1. CPTR SMART CONTROL PRECISION CUSTOMIZED MANUAL OR AUTO SCR OR DIODE DRY TYPE SWITCH MODE DRY TYPE SCR OR DIODE OIL TYPE 1 INDEX PAGE 1. Cover 2. Index

More information

The following table shows approximate percentage wise the

The following table shows approximate percentage wise the SHORT-CIRCUIT CALCULATION INTRODUCTION Designing an electrical system is easy and simple, if only the normal operation of the network is taken into consideration. However, abnormal conditions which are

More information

Circuit Breaker LTB D with Motor Drive. Motor Drive. ABB PP/H/HV - Page 1. Ed 2006-04

Circuit Breaker LTB D with Motor Drive. Motor Drive. ABB PP/H/HV - Page 1. Ed 2006-04 Circuit Breaker LTB D with Motor Drive Motor Drive ABB PP/H/HV - Page 1 Ed 2006-04 Technology Traditional technology Traditional spring operating mechanism: Closing mechanism ABB PP/H/HV - Page 2 Tripping

More information

The Intelligent AX1 Switchgear for Medium Voltage

The Intelligent AX1 Switchgear for Medium Voltage The Intelligent AX1 Switchgear for Medium Voltage Leif Lundin, Manager of Research and Development, Division Medium Voltage and Compact Substations, ABB Distribution, Sweden Abstract The newly launched

More information

AUTOMATIC TRANSFER SWITCH. Changeover Type from 250A to 2500A

AUTOMATIC TRANSFER SWITCH. Changeover Type from 250A to 2500A AUTOMATIC TRANSFER SWITCH Changeover Type from 250A to 2500A Table of Contents Preamble 1.1 Theoretical base 1.2 Selection the size of automatic transfer switch 1.3 Automatic transfer switch components

More information

Safety technique. Emergency stop module BO 5988 safemaster

Safety technique. Emergency stop module BO 5988 safemaster Safety technique Emergency stop module BO 5988 safemaster 0221562 Function diagram Pushbutton on Mains or emergencystop () K1 According to EC Directive for machines 98/37/EG According to IEC/E 60204-1

More information

Primary-Side Transformer Protection

Primary-Side Transformer Protection Primary-Side Transformer Protection Peter J. Meyer, S&C Electric Company, Chicago, Illinois Presented at the Doble Life of a Transformer Seminar; Laguna Beach, California February 21 25, 2005 INTRODUCTION

More information

AMSC s Superconductor Cable Technologies for Electric Utilities

AMSC s Superconductor Cable Technologies for Electric Utilities International Workshop 2014 AMSC s Superconductor Cable Technologies for Electric Utilities Michael Ross, P.E. Managing Director of Superconductor Power Systems AMSC Corporate Facts Headquartered in MA,

More information

CHAPTER 5 PHOTOVOLTAIC SYSTEM DESIGN

CHAPTER 5 PHOTOVOLTAIC SYSTEM DESIGN CHAPTER 5 PHOTOVOLTAIC SYSTEM DESIGN 5.1 Introduction So far in the development of this research, the focus has been to estimate the available insolation at a particular location on the earth s surface

More information

PRODUCT GUIDE. SL Medium Voltage IEC Vacuum Contactors

PRODUCT GUIDE. SL Medium Voltage IEC Vacuum Contactors PRODUCT GUIDE SL Medium Voltage IEC Vacuum Contactors Table of Contents 1 Overview Introduction....................................................2 Features........................................................2

More information

Line Reactors and AC Drives

Line Reactors and AC Drives Line Reactors and AC Drives Rockwell Automation Mequon Wisconsin Quite often, line and load reactors are installed on AC drives without a solid understanding of why or what the positive and negative consequences

More information

Power Plant Electrical Distribution Systems

Power Plant Electrical Distribution Systems PDH Course E184 Power Plant Electrical Distribution Systems Gary W Castleberry, PE 2008 PDH Center 2410 Dakota Lakes Drive Herndon, VA 20171-2995 Phone: 703-478-6833 Fax: 703-481-9535 www.pdhcenter.com

More information

Trade of Electrician. Three-phase Distribution Boards And Socket Circuits

Trade of Electrician. Three-phase Distribution Boards And Socket Circuits Trade of Electrician Standards Based Apprenticeship Three-phase Distribution Boards And Socket Circuits Phase 2 Module No. 2.3 Unit No. 2.3.2 COURSE NOTES Created by Charlie Walsh - Athlone TC Revision

More information

Programming Logic controllers

Programming Logic controllers Programming Logic controllers Programmable Logic Controller (PLC) is a microprocessor based system that uses programmable memory to store instructions and implement functions such as logic, sequencing,

More information

Joslyn Clark Controls, Inc.

Joslyn Clark Controls, Inc. Joslyn Clark Controls, Inc. CAPACITOR SWITCHING VACUUM CONTACTORS vs. AIR BREAK CONTACTORS APPLICATION PRECAUTIONS & CALCULATIONS TO LIMIT HIGH FREQUENCY & HIGH CURRENT 2 QUESTION: WHY IS A VACUUM CONTACTOR

More information

Electronic overload relay EF19 and EF45

Electronic overload relay EF19 and EF45 Data sheet Electronic overload relay EF19 and EF45 Electronic overload relays offer reliable protection in case of overload and phase-failure. They are the alternative to thermal overload relays. Motor

More information

Alternating Current and Direct Current

Alternating Current and Direct Current K Hinds 2012 1 Alternating Current and Direct Current Direct Current This is a Current or Voltage which has a constant polarity. That is, either a positive or negative value. K Hinds 2012 2 Alternating

More information

Enhanced Quality with a Touch of Style

Enhanced Quality with a Touch of Style Rudolf Current Transformer Enhanced Quality with a Touch of Style Current Transformer Enhanced Quality with a Touch of Style New Products Rudolf launched our new encapsulated current transformer. Portraying

More information

The electrical energy produced at the gen

The electrical energy produced at the gen 300 300 Principles of Power System CHAPTER CHAPTER 12 Distribution Systems General 12.1 Distribution System 12.2 Classification of Distribution Systems 12.3 A.C. Distribution 12.4 D.C. Distribution 12.5

More information

COMPLIANCE WEST USA A Compliance Products USA, Inc. Company www.compwest.com

COMPLIANCE WEST USA A Compliance Products USA, Inc. Company www.compwest.com AC vs. DC Dielectric Withstand Testing Abstract: Dielectric withstand testing is used to evaluate wiring insulation after it has been installed in a mobile home. As described below, if voltages are correctly

More information

The Application and Benefits of Multi-phase Auto-reclosing

The Application and Benefits of Multi-phase Auto-reclosing he Application and Benefits of Multi-phase Auto-reclosing etsuya Miyoshi*, Atsushi Kasai* Abstract - In this paper we explain the disadvantages in using single- and three-phase auto-reclosing on double

More information

Power measurement in balanced 3 phase circuits and power factor improvement. 1 Power in Single Phase Circuits. Experiment no 1

Power measurement in balanced 3 phase circuits and power factor improvement. 1 Power in Single Phase Circuits. Experiment no 1 Experiment no 1 Power measurement in balanced 3 phase circuits and power factor improvement 1 Power in Single Phase Circuits Let v = m cos(ωt) = cos(ωt) is the voltage applied to a R-L circuit and i =

More information

ABB 1. Three-phase monitoring relay CM-PFS. Data sheet. Features. Approvals. Marks. Order data. Order data - Accessories. Application.

ABB 1. Three-phase monitoring relay CM-PFS. Data sheet. Features. Approvals. Marks. Order data. Order data - Accessories. Application. 1SR 430 824 F9300 Features Monitoring of three-phase mains for phase sequence and failure Powered by the measuring circuit 2 c/o (SPDT) contacts 1 LED for status indication Approvals R: yellow LED - relay

More information

Medium Voltage (MV) & High Voltage (HV) Training Module 6. Date of the presentation

Medium Voltage (MV) & High Voltage (HV) Training Module 6. Date of the presentation Medium Voltage (MV) & High Voltage (HV) Training Module 6 Date of the presentation Electrical System Basics MV vs. HV - Definitions Differences between USA and the rest of the world IEC define a high voltage

More information

Hyperlinks are Inactive

Hyperlinks are Inactive Prepared by: NIB/EOB PLANNING GUIDE FOR SINGLE CUSTOMER SUBSTATIONS SERVED FROM TRANSMISSION LINES 05503 Department: Electric T&D Section: T&D Engineering and Technical Support Approved by: G.O. Duru (GOD)

More information

Pressure monitoring equipment for oil-sf 6. bushings, type GOEK

Pressure monitoring equipment for oil-sf 6. bushings, type GOEK Pressure monitoring equipment for oil-sf 6 bushings, type GOEK Installation and maintenance guide 5693 827-6 en, Rev. 3, 2002-01-30 This document must not be copied without our written permission, and

More information

Voltage Regulator SPAU 341 C. Product Guide

Voltage Regulator SPAU 341 C. Product Guide Issued: July 1998 Status: Updated Version: D/25.04.2006 Data subject to change without notice Features Comprehensive voltage regulation for power transformers with on-load tapchangers in distribution substations

More information

SWITCH YARD OPERATION IN THERMAL POWER PLANT(KaTPP Jhalawar Rajasthan)

SWITCH YARD OPERATION IN THERMAL POWER PLANT(KaTPP Jhalawar Rajasthan) From the SelectedWorks of Radhey Shyam Meena Winter July 12, 2012 SWITCH YARD OPERATION IN THERMAL POWER PLANT(KaTPP Jhalawar Rajasthan) RADHEY SHYAM MEENA, Er. Available at: http://works.bepress.com/radhey_meena/5/

More information

For a phase-to-phase voltage between 100 V and 1000 V. The standard ratings are: 400 V - 690 V - 1000 V (at 50 Hz)

For a phase-to-phase voltage between 100 V and 1000 V. The standard ratings are: 400 V - 690 V - 1000 V (at 50 Hz) 24 1. NETWORK CONFIGURATIONS definition Standard IEC 38 defines voltage ratings as follows: - Low voltage () For a phase-to-phase voltage between 100 V and 1000 V. The standard ratings are: 400 V - 690

More information

2. INDUCTIVE VOLTAGE TRANSFORMERS Oil-paper insulation Gas insulation

2. INDUCTIVE VOLTAGE TRANSFORMERS Oil-paper insulation Gas insulation 2. INDUCTIVE VOLTAGE TRANSFORMERS Oil-paper insulation Gas insulation 123 kv Inductive Fingrid (Finland). 18 Instrument transformers igh voltage INTRODUCTION Inductive voltage transformers are designed

More information