Performance of Fiber Reinforced Concrete Beams with and without Stirrups
|
|
- Roderick Kennedy
- 7 years ago
- Views:
Transcription
1 Volume 4, Issue 1, 2012 Performance of Fiber Reinforced Concrete Beams with and without Stirrups Travis Hockenberry, Structural Engineer, WorleyParsons Group Maria M. Lopez, Associate Professor, Dept. of Civil and Env. Engineering, Penn State University, Abstract The use of Fiber Reinforced Concrete (FRC) in non-structural applications such as slabs on grade and pavements has become widely accepted by the design and construction industries. Structural use of FRC, however, has not received a similar acceptance rate in spite of the large research effort conducted in the past 50 years. This study evaluates the performance of fiber reinforced concrete beams with and without steel stirrups. In particular, the interaction between conventional stirrups and hooked steel fiber reinforcement as well as the size effect of the specimens tested is investigated. Experimental results are compared to the new ACI provisions for FRC use. Keywords: concrete, shear, size effect, steel fiber, stirrups Introduction The addition of short fibers to concrete or cement-based matrices enhances the structural performance of these composite materials. Enhanced properties include shear strength, tensile strength, compressive strength, toughness, ductility, and durability among others [1]. Fiber reinforcement has been shown to be effective as shear reinforcement when used to supplement or replace conventional steel stirrups in reinforced concrete (RC) beams [2]. The use of Fiber Reinforced Concrete (FRC) could allow for greater spacing between conventional stirrups thus alleviating reinforcement congestion; it could also eliminate the need for conventional stirrups in areas where minimum reinforcement is needed. The American Concrete Institute, in its 2008 Building Code Requirements for Structural Concrete [3], accepts hooked steel fibers as a reinforcing material for structural concrete. Even though its use is limited to shear reinforcement in beams subjected to small service loads, its inclusion in a building code requirement document opens the door for the acceptance of FRC as a structural material. This paper presents results of an experimental study aimed at evaluating key factors that affect the shear strength of hooked steel FRC beams with and without stirrups. In particular, the interaction between conventional stirrups and hooked steel fiber reinforcement as well as the size effect of the specimen tested are investigated. The results from the experimental study are then compared with the new ACI design provisions regarding FRC use. Experimental Study A total of 27 concrete specimens were fabricated and tested at the Civil Infrastructure Testing and Evaluation laboratory at Penn State University. These specimens had variations in geometry, fiber volume fraction, fiber geometry, and stirrup spacing. Table 1 shows the matrix of the specimens details. Four different sizes of specimens were investigated; specimen heights were (A) mm, (B) mm, (C) mm, and (D) mm respectively. All beam specimens had a constant width equal to 254 mm. The shear span-to-depth ratio was kept constant (2.5) for all beams. These beams are considered as short beams, where the shear capacity controls their behavior [4]. Conventional reinforcement consisted of longitudinal steel rebar (metric notation shown in Table 1) and double leg steel stirrups. The longitudinal reinforcement ratio, ρ, was selected as 1.0% for all specimen sizes. Stirrups, when used, were spaced at d/2, 2/3d and d (effective depth). Hooked steel fibers with two different aspect ratios (L/D) were used (80, 65) with a tensile strength of 1100 MPa (data provided by manufacturer). Two different fiber volume fractions (V f) were also evaluated (0.5% and 1%). Details of specimen fabrication can be found in [5]. Specimen Identification The specimen identification scheme consists of a 5-part code, α-β-γ-δ-ε, where α = specimen size A, B, C or D β = NF for no fiber; F for fiber γ = 0.5 for 0.5% fiber volume fraction; 1.0 for 1%V f δ = 65 for fiber aspect ratio (L/D=65); 80 for L/D=80 1
2 ε = NS for no stirrups; S for stirrups Three specimens were tested for each set of conditions investigated as listed below. Table 1. Matrix of tested specimens Size Specimen Identification d (mm) Flexural Reinforcement Area 1 Transverse Spacing Fiber volume fraction V f (%) Fiber L/D A A-F NS 457 B B-NF-NS 229 B B-NF-S 229 B B-F S 229 B B-F S 229 B B-F S 229 B B-F S 229 C C-F NS 152 D D-F NS 76 1 Note: METRIC bar sizes are listed (M) 3#22M bars (1161 mm 2 ) 3#13M bars (387 mm 2 ) 3#10M bars (213 mm 2 ) No No - d/2 = /3d = d = /3d = d = mm No No Test Setup Beam specimens were tested by applying a single concentrated load from a hydraulic actuator at midspan under displacement control (three-point bending configuration, as shown in Figure 1) at a rate of 0.3 mm/min. A self-reacting frame was used to contain the reaction beam. Load-displacement data from the actuator was recorded, along with additional midspan specimen deformation data from two LVDTs. Strain gages were placed in the longitudinal rebar as well as stirrups, strain data was also continuously monitored during testing. Load, displacement and deformation were recorded at a rate of 5 Hz. Load, P Hinge Support Beam Specimen Roller Support LVDT Reaction Beam Figure 1. Three-point bending test set-up In addition to the flexure tests, compressive and split tensile tests were conducted following ASTM guidelines. The concrete mixture with no fibers (control specimens) had an average compressive strength of 29 MPa and a tensile strength of 2.58 MPa. Compressive strengths for the fiber reinforced 2
3 concrete mixtures fluctuated slightly depending on the fiber content, but in all cases exceeded the control specimens with a maximum increase of 8%. The split tensile strength of these mixtures, in contrast, was shown to increase dramatically with the addition of fiber. Increases of between 40% and 95% were found. Table 2 presents the material properties of all concrete mixtures at the time the beam specimens were tested (average of 3 specimens is reported). The batch identification scheme follows the first 4 letters code used for specimen identification (α-β-γ-δ) described previously. Table 2. Material properties of the concrete mixtures investigated Concrete mixture description Compressive strength f c (MPa) Split Tensile strength f t (MPa) B-NF B-F B-F B-F B-F C-F NS D-F NS A-F Failure Modes All beam specimens failed as expected, by propagation of a major shear crack that extended from one of the supports to the point load. Figure 2 shows typical crack patterns observed on all specimens. The dotted line corresponds to the primary failure crack. It can be seen that for the specimens with fibers, there was a greater distribution of cracks throughout the span. In the case of the specimens with 1% fiber volume fraction and stirrups, the major crack progressed from a flexural crack to a flexural-shear crack. During the testing of these specimens, it was noted that specimens with fibers had a more ductile failure mode than control specimens. Overall, it was important to confirm that all beams had shear failures so the true shear contribution of fibers and stirrups could be evaluated. Effect of Fiber Volume Fraction Figure 3 shows representative curves of the load-deflection behavior of all the size B specimens. It can be observed that the peak load and corresponding midspan deflection increases with an increase in the fiber content. It can also be seen that for the same volume fraction as the fiber aspect ratio (L/D) increases, the peak load also increases although its effect appears to be less significant. For the specimens with 1%V f, peak loads are similar for both aspect ratios. 3
4 (a) B-NF-NS specimen (b) B-NF-S specimen (c) B-F S specimen (d) B-F S specimen (e) B-F S specimen (f) B-F S specimen (g) D-F NS specimen (h) C-F NS specimen (i) A-F NS specimen Figure 2. Crack patterns of tested beams 4
5 Figure 3. Load-midspan deflection curves for Size B specimens Combined Effect of Fibers and Stirrup Spacing Because the size B beam specimens had different fiber volume fraction and stirrup spacing, it is important to note that their combined effect is what is reflected in the curves shown in Figure 3. From a design point of view, it is important to note that the shear capacity of the control specimen NF-S (no fibers and stirrups at d/2) was achieved and exceeded by the specimens with combinations of fibers and larger stirrup spacing. Figure 4 shows this combined effect. All size B specimens are represented in this Figure. It is interesting to observe that for specimens with 1%Vf and a stirrup spacing of d this increasing trend slows down indicating the possibility of a practical limit on how much stirrup spacing can be increased even with an increasing fiber volume fraction. There is certainly an interaction between these two parameters. More importantly, these results indicate the possibility that an FRC beam specimen with no stirrups could have the same shear capacity as a control beam specimen (no fibers and with stirrups). Size Effect In order to evaluate the influence of the specimen geometry on the shear capacity of fiber reinforced beams, three series (A, C, D) of specimens with different effective depths were tested. All specimens had a 1% fiber volume fraction, L/D = 80 and no stirrups. All had the same shear span-depth ratio (2.5). Figure 5 shows the influence of the effective depth on the shear strength of the FRC beams. It can be observed that the ultimate shear stress of the specimen decreases as the effective depth increases. The ultimate shear stress v u is calculated as the ratio between the peak load and the effective cross section of the specimen (bxd). The percentage decrease from one size to the next is 41.3% from size D to size C and 11.5% from size C to size A. Although size B specimens (B-F S) have the additional effect of the stirrups (spaced at d), these results are included as an additional reference point. It can be inferred that these B specimens agree well with the trend shown by the other specimen sizes. This indicates that there is a size effect present in FRC beams with and without stirrups. Contrary to some previous studies, the ductile behavior on the structural response of these tested specimens does not seem to diminish the size effect in the shear performance of FRC beams. 5
6 180 Shear Failure Load (kn) Control Series Spacing=114.3 mm (4.5 in), d/2 No Stirrups Spacing=152.4 mm (6 in), 2/3d Spacing=228.6 mm (9 in), d Control L/D=80 L/D= Fiber Volume Fraction (%) Figure 4. Effect of fiber volume fraction and stirrup spacing in the beam shear capacity ACI Shear Design Provisions The American Concrete Institute, in its 2008 Building Code requirements for Structural Concrete [3], accepts discontinuous deformed steel fibers as acceptable reinforcement for shear under specific conditions. Only hooked steel fibers with aspect ratios (L/D) between 50 and 100 are accepted. Fiber dosage is limited to no less than 100 lb/cubic yard; deformation characteristics are defined based on ASTM C1609 test procedure. The 1%Vf fiber reinforced concrete mixture used in this study meets these criteria. ACI shear provisions limit the use of FRC in beams subjected to small shear loads. The new shear design provision is intended for beams with design load values smaller than the expected shear capacity of the concrete cross section. In previous editions of the building code requirements, if this difference is less than 50%, these beams would be required to have some minimum shear reinforcement. In the 2008 building code edition, beams made of fiber reinforced concrete meeting the specifications shown above, are allowed. Results shown in Figure 5 indicated that the shear capacity provided by these FRC beams is larger than the limit set by ACI (shown as a dotted line) by at least 1.5 times. It must be pointed out, however, that larger size of specimens, allowed under ACI provisions, could have lower shear capacities than the ones reported in this study. 6
7 8000 Shear Stress, vu (kpa) A mm C mm B mm D mm 254 mm 254 mm 254 mm 254 mm ACI Shear Capacity Limit for FRC Type D Type C Type A Type B Effective Depth, d (mm) Conclusions Figure 5. Size Effect on FRC Beams with 1% V f This study evaluates key factors that affect the shear strength of hooked steel fiber reinforced concrete beams with and without steel stirrups. The following conclusions are drawn: All beam specimens failed in shear thus proving that the true contribution of fibers and stirrups was assessed by the experimental program. As expected, an increase in the fiber volume fraction ratio was shown to increase the shear capacity of each specimen tested. It was also observed that for the same volume fraction, as the fiber aspect ratio (L/D) increases, the shear capacity also increased, however its effect was less significant. The shear capacity of the control specimens (no fibers and stirrups at d/2) was achieved and exceeded by the specimens with combinations of fibers and larger stirrup spacing. It was inferred that this increasing trend may reach a plateau due to the possibility of a practical limit on how much stirrup spacing can be increased even with an increasing fiber volume fraction. It is very likely that a properly designed FRC beam with no stirrups can have the same shear capacity as a control specimen. The four different sizes of specimen tested showed that there is a size effect present in FRC beams with and without stirrups. All FRC beams tested had a shear capacity at least 1.5 times larger than the limit set by ACI building code provisions. It must be pointed out, however, that larger size of specimens, allowed under these ACI provisions, could have lower shear capacities than the ones reported in this study. References 1. ACI Committee 544. State-of-the-Art Report on Fiber Reinforced Concrete. American Concrete Institute, Detroit, MI (Reapproved 2002). 2. Lim, D. H. and Oh, B. H. Experimental and Theoretical Investigation on the Shear of Steel Fiber Reinforced Concrete Beams, Engineering Structures, Vol. 21, ACI Committee 318. Building Code Requirements for Structural Concrete (ACI ) and Commentary, an ACI Standard. American Concrete Institute, Detroit, MI., January MacGregor, J.G. and Wight, J.K. Reinforced Concrete: Mechanics and Design, New Jersey: Pearson Prentice Hall, Hockenberry, T. Evaluation of Shear Capacity of hooked Steel Fiber Reinforced Concrete Beams with Stirrups, M.S Thesis. The Pennsylvania State University, August
Numerical modelling of shear connection between concrete slab and sheeting deck
7th fib International PhD Symposium in Civil Engineering 2008 September 10-13, Universität Stuttgart, Germany Numerical modelling of shear connection between concrete slab and sheeting deck Noémi Seres
More informationAssistant Professor of Civil Engineering, University of Texas at Arlington
FRC Performance Comparison: Direct Tensile Test, Beam Type Bending Test, and Round Panel Test Shih Ho Chao (Presenting Author) Assistant Professor of Civil Engineering, University of Texas at Arlington
More informationANALYSIS FOR BEHAVIOR AND ULTIMATE STRENGTH OF CONCRETE CORBELS WITH HYBRID REINFORCEMENT
International Journal of Civil Engineering and Technology (IJCIET) Volume 6, Issue 10, Oct 2015, pp. 25-35 Article ID: IJCIET_06_10_003 Available online at http://www.iaeme.com/ijciet/issues.asp?jtype=ijciet&vtype=6&itype=10
More informationIn-situ Load Testing to Evaluate New Repair Techniques
In-situ Load Testing to Evaluate New Repair Techniques W.J. Gold 1 and A. Nanni 2 1 Assistant Research Engineer, Univ. of Missouri Rolla, Dept. of Civil Engineering 2 V&M Jones Professor, Univ. of Missouri
More informationADVANTAGES OF STEEL FIBRE REINFORCED CONCRETE IN INDUSTRIAL FLOORS
ADVANTAGES OF STEEL FIBRE REINFORCED CONCRETE IN INDUSTRIAL FLOORS Murugesan M 1, Dashrath Rajpurohit 2 1 Assistant General Manager, Civil & Structural, Larsen & Toubro Technology Services, Tamilnadu,
More informationUSE OF CFRP LAMINATES FOR STRENGTHENING OF REINFORCED CONCRETE CORBELS
International Journal of Civil Engineering and Technology (IJCIET) Volume 6, Issue 11, Nov 2015, pp. 11-20, Article ID: IJCIET_06_11_002 Available online at http://www.iaeme.com/ijciet/issues.asp?jtype=ijciet&vtype=6&itype=11
More informationDEVELOPMENT OF A NEW TEST FOR DETERMINATION OF TENSILE STRENGTH OF CONCRETE BLOCKS
1 th Canadian Masonry Symposium Vancouver, British Columbia, June -5, 013 DEVELOPMENT OF A NEW TEST FOR DETERMINATION OF TENSILE STRENGTH OF CONCRETE BLOCKS Vladimir G. Haach 1, Graça Vasconcelos and Paulo
More informationDraft Table of Contents. Building Code Requirements for Structural Concrete and Commentary ACI 318-14
Draft Table of Contents Building Code Requirements for Structural Concrete and Commentary ACI 318-14 BUILDING CODE REQUIREMENTS FOR STRUCTURAL CONCRETE (ACI 318 14) Chapter 1 General 1.1 Scope of ACI 318
More informationIMPROVING THE STRUT AND TIE METHOD BY INCLUDING THE CONCRETE SOFTENING EFFECT
International Journal of Civil Engineering and Technology (IJCIET) Volume 7, Issue 2, March-April 2016, pp. 117 127, Article ID: IJCIET_07_02_009 Available online at http://www.iaeme.com/ijciet/issues.asp?jtype=ijciet&vtype=7&itype=2
More informationBehavior of High-Strength Concrete Rectangular Columns
Seventh International Congress on Advances in Civil Engineering, October11-13, 26 Yildiz TechnicalUniversity, Istanbul, Turkey Behavior of High-Strength Concrete Rectangular Columns S. Kim, H. C. Mertol,
More informationHow To Make A Steel Beam
Resistenza a taglio di travi in calcestruzzo fibrorinforzato Università degli Studi di Brescia giovanni.plizzari@unibs.it Milano June 17 th, 2015 Outlines Shear Action Factor affecting the shear strength
More informationTHE EFFECT OF STIRRUPS AND HOOKED STEEL FIBERS INSTEAD ON MOMENT-ROTATION CAPACITY OF BEAM-COLUMN CONNECTIONS
THE EFFECT OF STIRRUPS AND HOOKED STEEL FIBERS INSTEAD ON MOMENT-ROTATION CAPACITY OF BEAM-COLUMN CONNECTIONS Assist. Prof. Dr. S. KamilAkın 1, Assist. Prof. Dr. Nail Kara 1, 1 Department of Civil Engineering,
More informationDetailing of Reinforcment in Concrete Structures
Chapter 8 Detailing of Reinforcment in Concrete Structures 8.1 Scope Provisions of Sec. 8.1 and 8.2 of Chapter 8 shall apply for detailing of reinforcement in reinforced concrete members, in general. For
More information1.054/1.541 Mechanics and Design of Concrete Structures (3-0-9) Outline 1 Introduction / Design Criteria for Reinforced Concrete Structures
Prof. Oral Buyukozturk Massachusetts Institute of Technology Outline 1 1.054/1.541 Mechanics and Design of Concrete Structures (3-0-9) Outline 1 Introduction / Design Criteria for Reinforced Concrete Structures
More informationModern Codes for Design of Concrete Concrete Structures Presentation Outline
Modern Codes for Design of Concrete Structures James K. Wight F.E. Richart, Jr. Professor of Civil Eng. University of Michigan Presentation Outline Current Codes Where did they come from? What is their
More informationSP-276 5 FRC PERFORMANCE COMPARISON: UNIAXIAL DIRECT TENSILE TEST, THIRD-POINT BENDING TEST, AND ROUND PANEL TEST
SP-276 5 FRC PERFORMANCE COMPARISON: UNIAXIAL DIRECT TENSILE TEST, THIRD-POINT BENDING TEST, AND ROUND PANEL TEST Shih-Ho Chao, Jae-Sung Cho, Netra B. Karki, Dipti R. Sahoo, and Nur Yazdani Synopsis: The
More informationHardened Concrete. Lecture No. 14
Hardened Concrete Lecture No. 14 Strength of Concrete Strength of concrete is commonly considered its most valuable property, although in many practical cases, other characteristics, such as durability
More informationDesign of Fibre Reinforced Concrete Beams and Slabs
Design of Fibre Reinforced Concrete Beams and Slabs Master of Science Thesis in the Master s Programme Structural Engineering and Building Performance Design AMMAR ABID, KENNETH B. FRANZÉN Department of
More informationSEISMIC DESIGN. Various building codes consider the following categories for the analysis and design for earthquake loading:
SEISMIC DESIGN Various building codes consider the following categories for the analysis and design for earthquake loading: 1. Seismic Performance Category (SPC), varies from A to E, depending on how the
More informationINFLUENCE OF STEEL FIBERS AS ADMIX IN NORMAL CONCRETE MIX
International Journal of Civil Engineering and Technology (IJCIET) Volume 7, Issue 1, Jan-Feb 2016, pp. 93-103, Article ID: IJCIET_07_01_008 Available online at http://www.iaeme.com/ijciet/issues.asp?jtype=ijciet&vtype=7&itype=1
More informationAPE T CFRP Aslan 500
Carbon Fiber Reinforced Polymer (CFRP) Tape is used for structural strengthening of concrete, masonry or timber elements using the technique known as Near Surface Mount or NSM strengthening. Use of CFRP
More informationOverview of Topics. Stress-Strain Behavior in Concrete. Elastic Behavior. Non-Linear Inelastic Behavior. Stress Distribution.
Stress-Strain Behavior in Concrete Overview of Topics EARLY AGE CONCRETE Plastic shrinkage shrinkage strain associated with early moisture loss Thermal shrinkage shrinkage strain associated with cooling
More informationBEHAVIOR OF SHORT CONCRETE COLUMNS REINFORCED BY CFRP BARS AND SUBJECTED TO ECCENTRIC LOAD
International Journal of Civil Engineering and Technology (IJCIET) Volume 6, Issue 10, Oct 2015, pp. 15-24 Article ID: IJCIET_06_10_002 Available online at http://www.iaeme.com/ijciet/issues.asp?jtype=ijciet&vtype=6&itype=10
More informationThe following sketches show the plans of the two cases of one-way slabs. The spanning direction in each case is shown by the double headed arrow.
9.2 One-way Slabs This section covers the following topics. Introduction Analysis and Design 9.2.1 Introduction Slabs are an important structural component where prestressing is applied. With increase
More informationDESIGN OF SLABS. 3) Based on support or boundary condition: Simply supported, Cantilever slab,
DESIGN OF SLABS Dr. G. P. Chandradhara Professor of Civil Engineering S. J. College of Engineering Mysore 1. GENERAL A slab is a flat two dimensional planar structural element having thickness small compared
More informationSEISMIC UPGRADE OF OAK STREET BRIDGE WITH GFRP
13 th World Conference on Earthquake Engineering Vancouver, B.C., Canada August 1-6, 2004 Paper No. 3279 SEISMIC UPGRADE OF OAK STREET BRIDGE WITH GFRP Yuming DING 1, Bruce HAMERSLEY 2 SUMMARY Vancouver
More information16. Beam-and-Slab Design
ENDP311 Structural Concrete Design 16. Beam-and-Slab Design Beam-and-Slab System How does the slab work? L- beams and T- beams Holding beam and slab together University of Western Australia School of Civil
More informationDeflection Calculation of RC Beams: Finite Element Software Versus Design Code Methods
Deflection Calculation of RC Beams: Finite Element Software Versus Design Code Methods G. Kaklauskas, Vilnius Gediminas Technical University, 1223 Vilnius, Lithuania (gintaris.kaklauskas@st.vtu.lt) V.
More informationbi directional loading). Prototype ten story
NEESR SG: Behavior, Analysis and Design of Complex Wall Systems The laboratory testing presented here was conducted as part of a larger effort that employed laboratory testing and numerical simulation
More informationTHEORETICAL BEHAVIOR OF COMPOSITE CONSTRUCTION PRECAST REACTIVE POWDER RC GIRDER AND ORDINARY RC DECK SLAB
International Journal of Civil Engineering and Technology (IJCIET) Volume 6, Issue 12, Dec 215, pp. 8-21, Article ID: IJCIET_6_12_2 Available online at http://www.iaeme.com/ijciet/issues.asp?jtype=ijciet&vtype=6&itype=12
More informationTechnical Notes 3B - Brick Masonry Section Properties May 1993
Technical Notes 3B - Brick Masonry Section Properties May 1993 Abstract: This Technical Notes is a design aid for the Building Code Requirements for Masonry Structures (ACI 530/ASCE 5/TMS 402-92) and Specifications
More informationLARGE SCALE TENSILE TESTS OF HIGH PERFORMANCE FIBER REINFORCED CEMENT COMPOSITES
LARGE SCALE TENSILE TESTS OF HIGH PERFORMANCE FIBER REINFORCED CEMENT COMPOSITES Shih-Ho Chao (1), Wen-Cheng Liao (2), Thanasak Wongtanakitcharoen (3), and Antoine E. Naaman (4) (1) Post-Doctoral Research
More informationNumerical Analysis of the Moving Formwork Bracket Stress during Construction of a Curved Continuous Box Girder Bridge with Variable Width
Modern Applied Science; Vol. 9, No. 6; 2015 ISSN 1913-1844 E-ISSN 1913-1852 Published by Canadian Center of Science and Education Numerical Analysis of the Moving Formwork Bracket Stress during Construction
More informationResearch on the meaning of reinforcement ductility for a behavior of double-spans reinforced concrete beam.
Research on the meaning of reinforcement ductility for a behavior of double-spans reinforced concrete beam. Prepared by: Contents list Page 1. Purpose of the research 3 2. Test models and stand description
More informationThe Strength of Concrete
Chapter The Strength of Concrete.1 The Importance of Strength.2 Strength Level Required KINDS OF STRENGTH. Compressive Strength.4 Flexural Strength.5 Tensile Strength.6 Shear, Torsion and Combined Stresses.7
More informationReinforced Concrete Design
FALL 2013 C C Reinforced Concrete Design CIVL 4135 ii 1 Chapter 1. Introduction 1.1. Reading Assignment Chapter 1 Sections 1.1 through 1.8 of text. 1.2. Introduction In the design and analysis of reinforced
More informationSEISMIC RETROFITTING TECHNIQUE USING CARBON FIBERS FOR REINFORCED CONCRETE BUILDINGS
Fracture Mechanics of Concrete Structures Proceedings FRAMCOS-3 AEDIFICA TIO Publishers, D-79104 Freiburg, Germany SEISMIC RETROFITTING TECHNIQUE USING CARBON FIBERS FOR REINFORCED CONCRETE BUILDINGS H.
More informationMethods for Seismic Retrofitting of Structures
Methods for Seismic Retrofitting of Structures Retrofitting of existing structures with insufficient seismic resistance accounts for a major portion of the total cost of hazard mitigation. Thus, it is
More informationPERFORMANCE OF SLABS REINFORCED BY PEIKKO PSB STUDS
TECHNICAL ARTICLES PERFORMANCE OF SLABS REINFORCED BY PEIKKO PSB STUDS Demonstrated by full scale tests and validated by ETA approval starting April 2013 Authors: Aurelio Muttoni (Professor), Ecole Polytechnique
More informationDetailing of Reinforcement in Concrete Structures
THE CIVIL & STRUCTURAL ENGINEERING PANEL ENGINEERS AUSTRALIA SYDNEY DIVISION 28 August 2012 Detailing of Reinforcement in Concrete Structures R.I. Gilbert Introduction: Detailing is often considered to
More informationINTRODUCTION TO BEAMS
CHAPTER Structural Steel Design LRFD Method INTRODUCTION TO BEAMS Third Edition A. J. Clark School of Engineering Department of Civil and Environmental Engineering Part II Structural Steel Design and Analysis
More informationOptimum proportions for the design of suspension bridge
Journal of Civil Engineering (IEB), 34 (1) (26) 1-14 Optimum proportions for the design of suspension bridge Tanvir Manzur and Alamgir Habib Department of Civil Engineering Bangladesh University of Engineering
More informationVisualization of the healing process on reinforced concrete beams by application of Digital Image Correlation (DIC)
Materials Characterisation VI 283 Visualization of the healing process on reinforced concrete beams by application of Digital Image Correlation (DIC) E. Tsangouri 1, K. Van Tittelboom 2, D.Van Hemelrijck
More informationObjective To conduct Charpy V-notch impact test and determine the ductile-brittle transition temperature of steels.
IMPACT TESTING Objective To conduct Charpy V-notch impact test and determine the ductile-brittle transition temperature of steels. Equipment Coolants Standard Charpy V-Notched Test specimens Impact tester
More informationSECTION 3 DESIGN OF POST TENSIONED COMPONENTS FOR FLEXURE
SECTION 3 DESIGN OF POST TENSIONED COMPONENTS FOR FLEXURE DEVELOPED BY THE PTI EDC-130 EDUCATION COMMITTEE LEAD AUTHOR: TREY HAMILTON, UNIVERSITY OF FLORIDA NOTE: MOMENT DIAGRAM CONVENTION In PT design,
More informationObjectives. Experimentally determine the yield strength, tensile strength, and modules of elasticity and ductility of given materials.
Lab 3 Tension Test Objectives Concepts Background Experimental Procedure Report Requirements Discussion Objectives Experimentally determine the yield strength, tensile strength, and modules of elasticity
More informationEXPERIMENTAL INVESTIGATION ON STRENGTH AND DURABILITY PROPERTIES OF HYBRID FIBER REINFORCED CONCRETE
EXPERIMENTAL INVESTIGATION ON STRENGTH AND DURABILITY PROPERTIES OF HYBRID FIBER REINFORCED CONCRETE SUDHEER JIROBE 1, BRIJBHUSHAN.S 2, MANEETH P D 3 1 M.Tech. Student, Department of Construction technology,
More informationChapter 5 Bridge Deck Slabs. Bridge Engineering 1
Chapter 5 Bridge Deck Slabs Bridge Engineering 1 Basic types of bridge decks In-situ reinforced concrete deck- (most common type) Pre-cast concrete deck (minimize the use of local labor) Open steel grid
More informationSTRENGTH OF CONCRETE INCORPORATING AGGREGATES RECYCLED FROM DEMOLITION WASTE
STRENGTH OF CONCRETE INCORPORATING AGGREGATES RECYCLED FROM DEMOLITION WASTE R. Kumutha and K. Vijai Department of Civil Engineering, Sethu Institute of Technology, Pulloor, Kariapatti, India E-Mail: kumuthar@yahoo.co.in,
More informationSEISMIC RETROFITTING OF STRUCTURES
SEISMIC RETROFITTING OF STRUCTURES RANJITH DISSANAYAKE DEPT. OF CIVIL ENGINEERING, FACULTY OF ENGINEERING, UNIVERSITY OF PERADENIYA, SRI LANKA ABSTRACT Many existing reinforced concrete structures in present
More informationFire-Damage or Freeze-Thaw of Strengthening Concrete Using Ultra High Performance Concrete
Fire-Damage or Freeze-Thaw of Strengthening Concrete Using Ultra High Performance Concrete Ming-Gin Lee 1,a, Yi-Shuo Huang 1,b 1 Department of Construction Engineering, Chaoyang University of Technology,Taichung
More informationTesting and appraisal of Lucobit polymer effect as an additive on asphalt mixture performance
Abstract Testing and appraisal of polymer effect as an additive on asphalt mixture performance Hamid Sabbagh mollahosseini*,golazin Yadollahi**, Ershad Amoosoltani*** *, ***Executive of Engineering and
More informationStress Strain Relationships
Stress Strain Relationships Tensile Testing One basic ingredient in the study of the mechanics of deformable bodies is the resistive properties of materials. These properties relate the stresses to the
More informationBasics of Reinforced Concrete Design
Basics of Reinforced Concrete Design Presented by: Ronald Thornton, P.E. Define several terms related to reinforced concrete design Learn the basic theory behind structural analysis and reinforced concrete
More informationSECTION 3 DESIGN OF POST- TENSIONED COMPONENTS FOR FLEXURE
SECTION 3 DESIGN OF POST- TENSIONED COMPONENTS FOR FLEXURE DEVELOPED BY THE PTI EDC-130 EDUCATION COMMITTEE LEAD AUTHOR: TREY HAMILTON, UNIVERSITY OF FLORIDA NOTE: MOMENT DIAGRAM CONVENTION In PT design,
More informationDesign, Construction, and Field-Testing of an RC Box Culvert Bridge Reinforced with GFRP Bars
Design, Construction, and Field-Testing of an RC Box Culvert Bridge Reinforced with GFRP Bars TAREK ALKHRDAJI, Ph. D. Candidate of Civil Engineering, University of Missouri-Rolla and ANTONIO NANNI, Jones
More informationNONLINEAR BEHAVIOR AND FRAGILITY ASSESSMENT OF MULTI-STORY CONFINED MASONRY WALLS UNDER CYCLIC LOADS
International Journal of Civil Engineering and Technology (IJCIET) Volume 7, Issue 1, Jan-Feb 216, pp. 113-127, Article ID: IJCIET_7_1_1 Available online at http://www.iaeme.com/ijciet/issues.asp?jtype=ijciet&vtype=7&itype=1
More informationA Comparative Analysis of Modulus of Rupture and Splitting Tensile Strength of Recycled Aggregate Concrete
American Journal of Engineering Research (AJER) e-issn : 2320-0847 p-issn : 2320-0936 Volume-03, Issue-02, pp-141-147 www.ajer.org Research Paper Open Access A Comparative Analysis of Modulus of Rupture
More informationEVALUATION OF SEISMIC RESPONSE - FACULTY OF LAND RECLAMATION AND ENVIRONMENTAL ENGINEERING -BUCHAREST
EVALUATION OF SEISMIC RESPONSE - FACULTY OF LAND RECLAMATION AND ENVIRONMENTAL ENGINEERING -BUCHAREST Abstract Camelia SLAVE University of Agronomic Sciences and Veterinary Medicine of Bucharest, 59 Marasti
More informationUniaxial Compressive Strength of Cold-formed Steel Tubular Sections with Recycled Aggregate Concrete Infill
Uniaxial Compressive Strength of Cold-formed Steel Tubular Sections with Recycled Aggregate Concrete Infill N.Umamaheswari 1, S. Arul Jayachandran 2 1 Associate Professor/Civil, SRM University, Kattankulathur,
More informationOptimising plate girder design
Optimising plate girder design NSCC29 R. Abspoel 1 1 Division of structural engineering, Delft University of Technology, Delft, The Netherlands ABSTRACT: In the design of steel plate girders a high degree
More informationSTRENGTHENING AND LOAD TESTING OF THREE BRIDGES IN BOONE COUNTY, MO
STRENGTHENING AND LOAD TESTING OF THREE BRIDGES IN BOONE COUNTY, MO S. Schiebel 1, R. Parretti 1, A. Nanni 2, and M. Huck 3 ABSTRACT Three bridges in Boone County, Missouri (Brown School Road Bridge, Coats
More information1 Barlines Rebar Detailing Standards in the Philippines
Barlines Rebar Detailing Standards in the Philippines METRIC (SI), STANDARD HOOKS AND OTHER DETAILING CRITERIAS By Amadeus (Mady) Magpile, President and CEO INTRODUCTION This is first in a series of articles
More informationSteel fibres to improve structural performance of reinforced concrete members
Steelibres to Improve Structural Performance of Reinforced Concrete Members by Prof. György L. Balázs TU Budapest and Ass. Prof. Imre Kovács UD Steel fibres to improve structural performance of reinforced
More information[BARLINES MANUAL OF STANDARD PRACTICE (PHILS)] Chapter One METRIC (SI), PNS BAR SIZES STANDARDS AND OTHER CRITERION
Chapter One METRIC (SI), PNS BAR SIZES STANDARDS AND OTHER CRITERION By Amadeus (Mady) Magpile, President and CEO INTRODUCTION This is first in a series of articles outlining the Manual of Standard Practice,
More informationChapter 8. Flexural Analysis of T-Beams
Chapter 8. Flexural Analysis of T-s 8.1. Reading Assignments Text Chapter 3.7; ACI 318, Section 8.10. 8.2. Occurrence and Configuration of T-s Common construction type.- used in conjunction with either
More informationComparison of Seismic Performance of D-region of Existing RC Structures Designed with Different Recommendations
Comparison of Seismic Performance of D-region of Existing RC Structures Designed with Different Recommendations Balthasar Novák 1, K.Ramanjaneyulu 2, Constanze Roehm 3 and Saptarshi Sasmal 4 1 Professor,
More informationRequirements for the Use of PRESSS Moment-Resisting Frame Systems
Requirements for the Use of PRESSS Moment-Resisting Frame Systems Neil M. Hawkins, Ph.D. Professor Emeritus Department of Civil Engineering University of Illinois at Urbana-Champaign Urbana, Illinois S.
More informationNur Yazdani, Ph.D., P.E. Professor. Lisa Spainhour, Ph.D. Associate Professor. Saif Haroon Research Assistant. FDOT Contract No. BC-386.
Florida A & M University - Florida State University College of Engineering Department of Civil & Environmental Engineering APPLICATION OF FIBER REINFORCED CONCRETE IN THE END ZONES OF PRECAST PRESTRESSED
More informationPRESTRESSED CONCRETE. Introduction REINFORCED CONCRETE CHAPTER SPRING 2004. Reinforced Concrete Design. Fifth Edition. By Dr. Ibrahim.
CHAPTER REINFORCED CONCRETE Reinforced Concrete Design A Fundamental Approach - Fifth Edition Fifth Edition PRESTRESSED CONCRETE A. J. Clark School of Engineering Department of Civil and Environmental
More informationSEISMIC RETROFITTING OF EARTHQUAKE-DAMAGED CONCRETE COLUMNS BY LATERAL PRE-TENSIONING OF FRP BELTS. K. Nasrollahzadeh Nesheli 1 and K.
Proceedings of the 8 th U.S. National Conference on Earthquake Engineering April 18-22, 26, San Francisco, California, USA Paper No. 841 SEISMIC RETROFITTING OF EARTHQUAKE-DAMAGED CONCRETE COLUMNS BY LATERAL
More informationPerformance of Existing Reinforced Concrete Columns under Bidirectional Shear & Axial Loading
Performance of Existing Reinforced Concrete Columns under Bidirectional Shear & Axial Loading Laura M. Flores University of California, San Diego REU Institution: University of California, Berkeley REU
More informationUse of Strain Gauge Rosette to Investigate Stress concentration in Isotropic and Orthotropic Plate with Circular Hole
Use of Strain Gauge Rosette to Investigate Stress concentration in Isotropic and Orthotropic Plate with Circular Hole Mr.V.G.Aradhye 1, Prof.S.S.Kulkarni 2 1 PG Scholar, Mechanical department, SKN Sinhgad
More informationFigure 5-11. Test set-up
5.5. Load Procedure A uniform load configuration was used for the load tests. An air bag, placed on the top surface of the slab, was used for this purpose, and the load was applied by gradually increasing
More informationSHEAR PERFORMANCE OF FIBER REINFORCED SELF COMPACTING CONCRETE DEEP BEAMS
International Journal of Civil Engineering and Technology (IJCIET) Volume 7, Issue 1, Jan-Feb 2016, pp. 25-46, Article ID: IJCIET_07_01_003 Available online at http://www.iaeme.com/ijciet/issues.asp?jtype=ijciet&vtype=7&itype=1
More informationField Damage Inspection and Static Load Test Analysis of Jiamusi Highway Prestressed Concrete Bridge in China
Advanced Materials Research Vols. 163-167 (2011) pp 1147-1156 Online available since 2010/Dec/06 at www.scientific.net (2011) Trans Tech Publications, Switzerland doi:10.4028/www.scientific.net/amr.163-167.1147
More informationGuidelines for the Design of Post-Tensioned Floors
Guidelines for the Design of Post-Tensioned Floors BY BIJAN O. AALAMI AND JENNIFER D. JURGENS his article presents a set of guidelines intended to T assist designers in routine post-tensioning design,
More informationDesign of Steel Structures Prof. S.R.Satish Kumar and Prof. A.R.Santha Kumar. Fig. 7.21 some of the trusses that are used in steel bridges
7.7 Truss bridges Fig. 7.21 some of the trusses that are used in steel bridges Truss Girders, lattice girders or open web girders are efficient and economical structural systems, since the members experience
More informationBEHAVIOR OF WELDED T-STUBS SUBJECTED TO TENSILE LOADS
BEHAVIOR OF WELDED T-STUBS SUBJECTED TO TENSILE LOADS R.A. Herrera 1, G. Desjouis 2, G. Gomez 2, M. Sarrazin 3 1 Assistant Professor, Dept. of Civil Engineering, University of Chile, Santiago, Chile 2
More informationMETHOD OF STATEMENT FOR STATIC LOADING TEST
Compression Test, METHOD OF STATEMENT FOR STATIC LOADING TEST Tension Test and Lateral Test According to the American Standards ASTM D1143 07, ASTM D3689 07, ASTM D3966 07 and Euro Codes EC7 Table of Contents
More informationMATERIALS AND MECHANICS OF BENDING
HAPTER Reinforced oncrete Design Fifth Edition MATERIALS AND MEHANIS OF BENDING A. J. lark School of Engineering Department of ivil and Environmental Engineering Part I oncrete Design and Analysis b FALL
More informationPCI BIG BEAM COMPETITION
PCI BIG BEAM COMPETITION Official Rules for the PCI Engineering Design Competition Academic Year 2015-16 PROGRAM The PCI Student Education Committee is inviting entries from students to participate in
More informationMETU DEPARTMENT OF METALLURGICAL AND MATERIALS ENGINEERING
METU DEPARTMENT OF METALLURGICAL AND MATERIALS ENGINEERING Met E 206 MATERIALS LABORATORY EXPERIMENT 1 Prof. Dr. Rıza GÜRBÜZ Res. Assist. Gül ÇEVİK (Room: B-306) INTRODUCTION TENSION TEST Mechanical testing
More informationSECTION 5 ANALYSIS OF CONTINUOUS SPANS DEVELOPED BY THE PTI EDC-130 EDUCATION COMMITTEE LEAD AUTHOR: BRYAN ALLRED
SECTION 5 ANALYSIS OF CONTINUOUS SPANS DEVELOPED BY THE PTI EDC-130 EDUCATION COMMITTEE LEAD AUTHOR: BRYAN ALLRED NOTE: MOMENT DIAGRAM CONVENTION In PT design, it is preferable to draw moment diagrams
More informationSLAB DESIGN. Introduction ACI318 Code provides two design procedures for slab systems:
Reading Assignment SLAB DESIGN Chapter 9 of Text and, Chapter 13 of ACI318-02 Introduction ACI318 Code provides two design procedures for slab systems: 13.6.1 Direct Design Method (DDM) For slab systems
More informationStrain Measurement in Pavements with a Fibre Optics Sensor Enabled Geotextile
Strain Measurement in Pavements with a Fibre Optics Sensor Enabled Geotextile Olivier Artières 1, Matteo Bacchi 2, Paolo Bianchini 1, Pierre Hornych 3 and Gerrit Dortland 1 1 TenCate Geosynthetics France,
More informationStrengthening of a Bridge Using Two FRP Technologies. Paolo Casadei, Nestore Galati, Renato Parretti and Antonio Nanni
Strengthening of a Bridge Using Two FRP Technologies Paolo Casadei, Nestore Galati, Renato Parretti and Antonio Nanni Synopsis This paper reports on the use of externally bonded fiber reinforced polymers
More informationEXPERIMENTAL STUDY ON SHEAR BEHAVIOR OF REINFORCED RECYCLED AGGREGATE CONCRETE BEAMS
International Journal of Civil Engineering and Technology (IJCIET) Volume 7, Issue 2, March-April 2016, pp. 128 139, Article ID: IJCIET_07_02_010 Available online at http://www.iaeme.com/ijciet/issues.asp?jtype=ijciet&vtype=7&itype=2
More informationA STUDY ON BONDING STRENGTH OF POLYMERIC FIBERS TO CEMENTITIOUS MATRIX
CD01-006 A STUDY ON BONDING STRENGTH OF POLYMERIC FIBERS TO CEMENTITIOUS MATRIX H.R. Pakravan 1, M. Jamshidi 2, M. Latifi 3 1 M.Sc. student, Textile Engineering Department, Amirkabir University, Tehran,
More informationDeflections. Question: What are Structural Deflections?
Question: What are Structural Deflections? Answer: The deformations or movements of a structure and its components, such as beams and trusses, from their original positions. It is as important for the
More informationSeismic performance evaluation of an existing school building in Turkey
CHALLENGE JOURNAL OF STRUCTURAL MECHANICS 1 (4) (2015) 161 167 Seismic performance evaluation of an existing school building in Turkey Hüseyin Bilgin * Department of Civil Engineering, Epoka University,
More informationNUMERICAL ANALYSIS OF A HORIZONTALLY CURVED BRIDGE MODEL
10NCEE Tenth U.S. National Conference on Earthquake Engineering Frontiers of Earthquake Engineering July 21-25, 2014 Anchorage, Alaska NUMERICAL ANALYSIS OF A HORIZONTALLY CURVED BRIDGE MODEL K. Kinoshita
More informationReinforced Concrete Design Project Five Story Office Building
Reinforced Concrete Design Project Five Story Office Building Andrew Bartolini December 7, 2012 Designer 1 Partner: Shannon Warchol CE 40270: Reinforced Concrete Design Bartolini 2 Table of Contents Abstract...3
More informationEffect of Reinforcing Bar Contamination on Steel-Concrete Bond During Concrete Construction
Effect of Reinforcing Bar Contamination on Steel-Concrete Bond During Concrete Construction Lawrence H. Taber, Abdeldjelil Belarbi and David N. Richardson Synopsis: During concrete construction, form oil,
More informationREPAIR AND STRENGTHENING OF HISTORICAL CONCRETE BRIDGE OVER VENTA RIVER IN LATVIA
1 REPAIR AND STRENGTHENING OF HISTORICAL CONCRETE BRIDGE OVER VENTA RIVER IN LATVIA Verners Straupe, M.sc.eng., Rudolfs Gruberts, dipl. eng. JS Celuprojekts, Murjanu St. 7a, Riga, LV 1024, Latvia e-mail:
More informationTABLE OF CONTENTS CHAPTER NO. TITLE PAGE NO. ABSTRACT
vii TABLE OF CONTENTS CHAPTER NO. TITLE PAGE NO. ABSTRACT LIST OF TABLES LIST OF FIGURES LIST OF SYMBOLS AND ABBREVIATIONS iii xvii xix xxvii 1 INTRODUCTION 1 1.1 GENERAL 1 1.2 OBJECTIVES AND SCOPE OF
More informationCENTER FOR INFRASTRUCTURE ENGINEERING STUDIES
CENTER FOR INFRASTRUCTURE ENGINEERING STUDIES GUIDELINES FOR RAPID LOAD TESTING OF CONCRETE STRUCTURAL MEMBERS by Matthew Mettemeyer Antonio Nanni University of Missouri-Rolla CIES 99-5 Disclaimer The
More informationDesign of reinforced concrete columns. Type of columns. Failure of reinforced concrete columns. Short column. Long column
Design of reinforced concrete columns Type of columns Failure of reinforced concrete columns Short column Column fails in concrete crushed and bursting. Outward pressure break horizontal ties and bend
More informationLife-365 Service Life Prediction Model Version 2.0
Originally printed in Concrete International and posted with permission from the American Concrete Institute (www.concrete.org). Life-365 Service Life Prediction Model Version 2.0 Widely used software
More informationCH 6: Fatigue Failure Resulting from Variable Loading
CH 6: Fatigue Failure Resulting from Variable Loading Some machine elements are subjected to static loads and for such elements static failure theories are used to predict failure (yielding or fracture).
More information