1 Bulletin No.SRM/2000 Series SCR & SAB Seismic Restraints Seismic Braces for Piping, Ductwork, Conduit, and Equipment
2 VMC Seismic cable restraints (SCR) and single arm braces (SAB) are an excellent means to restrain suspended equipment, piping, duct and electrical cable trays during an earthquake. With isolated systems, seismic cables are required. The cables are installed slightly slack so as to avoid short-circuiting the isolation system. The VMC seismic cable restraints come in kit form to minimize labor cost for the contractor. Each pre-packaged kit contains all of the necessary hardware for proper installation and positive attachment to the building structure. Our cables are factory swaged on one end to eliminate extra installation time. Seismic cable kits are made from 7 x 19 aircraft cable and are available in 1/8",1/4", and 3/8" sizes. Non-isolated systems can utilize our single arm brace. Our SAB series brackets allow for positive seismic attachment of all suspended systems. The bracket design accepts field-supplied unistrut or steel angle and allows for a full range of motion in all directions for ease of installation. The SAB-1 is designed for steel attachment, and the SAB-2 is utilized when concrete is the anchoring medium. Both the VMC Series SCR and Series SAB strictly comply with all requirements of the national building codes and the International Building Code (IBC 2000). 1. W = Weight at Center of Gravity 2. fp = Horizontal force by code = "g" x W 3. P Cable = fp = Force on cable or brace Cos45 Throughout this brochure, you will find graphs and charts which are to be used as guidelines only. Many different installation configurations are possible which may effect the performance of the restraints used. As a basic rule of thumb, the force acting on the seismic cable restraint or single arm brace can be broken down into a static analysis for selection purposes. Looking at suspended pipe, duct, cable tray or equipment, you will notice that the seismic restraint is positioned at an angle of approximately 45 up from the point of support. To determine the approximate seismic load imparted on the restraint: 1. Determine weight of the equipment, pipe, or duct to be restrained. 2. Multiply the weight by the seismic acceleration specified by code to determine horizontal seismic force. 3. Solve for force on seismic cable or brace by dividing the horizontal seismic force by Cos45. 2
3 Type SCR Seismic Cable Restraints Each Kit consists of: 2 - lengths of cable - swaged one end -11 ft. long or 20 ft. long, 7 x 19 Galvanized Aircraft Cable, 1/8", 1/4", 3/8" dia. 2 - concrete angle brackets 4 - shackles 2 - thimbles 4 - U-bolts 2 - clevis angles Seismic Load Table Wire Recommended Max. Equipment Mimimum Recommended Rope Dia. Working Load Weight Concrete Anchor (2) in. lbs..5g 1g Dia. (in.) Embedment Cable Spacing Guide -.5 "G" Cable Size and Spacing Pipe Size 1/8" 1/4" 3/8" T* - L* T* - L* T* - L* ft ft ft ft ft ft ft ft ft ft ft ft ft ft ft ft ft ft ft ft ft ft ft ft ft ft ft ft ft ft ft ft ft. 12 N/A ft t. 14 N/A ft ft. 16 N/A ft ft. 18 N/A ft ft. *T = *L = Cable Spacing Guide - 1 "G" Cable Size and Spacing Pipe Size 1/8" 1/4" 3/8" T* - L* T* - L* T* - L* ft ft ft ft ft ft ft ft ft ft ft ft ft ft ft ft ft ft ft ft ft ft ft ft ft ft ft. 8 N/A ft ft. 10 N/A ft ft. 12 N/A ft ft. 14 N/A ft ft. 16 N/A ft ft. 18 N/A N/A ft. *T = *L = Project: Architect: Acoustician Contractor: Project No. Date: Drawing No. VIBRATION MOUNTINGS & CONTROLS, INC. An Aeroflex, Inc. Company 113 Main St. Box 270, Bloomingdale, NJ Toll Free: LOW-VIBE Tel: 973/ Fax: 973/ TYPE "SCR " SEISMIC RESTRAINTS 3
4 Single Arm Brace Type SAB SAB-1 for equipment and steel structure attachment SAB-2 for concrete anchorage 9 16" holes for 1 2" bolt 13 16" hole for 3 4" bolt 9 16" hole (1 2" concrete anchors) 2 places 8" 6" 9 16" holes for 1 2" bolt (6 places) 2 3 4" 4" 1 1 2" 4" 1 1 2" 2 3 4" Single Arm Brace Spacing Guide -.5 "G" Pipe Size Spacing T - L ft ft ft ft ft ft ft ft ft ft ft ft ft ft ft. *T = *L = Single Arm Brace Spacing Guide - 1 "G" Pipe Size Spacing T - L ft ft ft ft ft ft ft ft ft ft ft ft ft ft. 18 N/A *T = *L = SAB brackets have been designed to accept field-supplied unistrut or steel angle as the rigid brace. Two brackets are required per brace. Model SAB-1 is used at the equipment, pipe, or duct and at the building structure when attaching to steel. When bolting the brace into concrete building structure, SAB-2 must be utilized. (SAB-1 at equipment, SAB-2 at structure). Project: Architect: Acoustician Contractor: Project No. Date: Drawing No. VIBRATION MOUNTINGS & CONTROLS, INC. An Aeroflex, Inc. Company 113 Main St. Box 270, Bloomingdale, NJ Toll Free: LOW-VIBE Tel: 973/ Fax: 973/ TYPE "SAB" SEISMIC RESTRAINTS 4
5 Isolated Piping Anchor Bolts by others Building Structure Concrete Angle Bracket Shackle Thimble VMC Type RSH Vibration Hanger U-bolt 7 x 19 Aircraft Cable VMC Series SRBC Seismic Rod Clamp Each Cable Kit consists of: 2 - lengths of cable - swaged one end 2 - concrete angle brackets 4 - shackles 2 - thimbles 4 - U-bolts 2 - clevis angles Clevis Angle Bracket 45 VMC Series SCR Seismic Cable Restraint Typical Brace (1 SCR Kit) Pipe Clevis (secondary pipe clamp must be used for longitudinal brace) / / Piping must be positively attached to the structure of the building in case of an earthquake. Typically, pipe is suspended on vibration isolation hangers within mechanical equipment rooms, or within 50 feet of vibrating equipment, whichever is greater. This isolated piping must also be seismically restrained to the building structure without compromising the vibration isolation (also known as "short circuiting"). A "run" of pipe must be restrained both longitudinally (in the direction of its run) and transversely (perpendicular to its run) to insure that it moves with the building and remains attached to it during an earthquake. Restraining the isolated pipe is accomplished by utilizing the VMC series SCR seismic cable restraints. Our seismic cable restraints insure positive attachment to the pipe supports, and when installed slightly slack, do not compromise the vibration isolation by short-circuiting the spring hanger. Our cable kits come with 2 lengths of cable, swaged on one end, and all of the necessary hardware for easy installation by the contractor. VMC Seismic cable restraints are a required component when restraining isolated pipe. TYPE SCR BRACING SCHEMATIC 5
6 Non-Isolated Piping SAB-2 required for concrete attachment. SAB-1 may be used for steel attachment VMC Series SRBC Seismic Rod Bracing Clamp VMC Series SAB-2 Anchor bolts by others (minimum of 2 for concrete attachment) Non-isolated threaded rod Brace (requires additional pipe clamp at clevis not shown) Brace Unistrut or angle steel (by others) VMC Series SAB-1 Clevis Hanger (pipe clamp must be used for longitudinal restraint capability) / / TYPE SAB BRACING SCHEMATIC Non-isolated piping has the same bracing requirements as isolated piping. However, piping that is rigidly supported without isolators can be seismically restrained using the VMC series SAB Single Arm Brace. Our rigid single arm brace consists of two brackets, which allow the brace a full range of motion for ease of installation. The bracing material (typically unistrut or angle steel) is contractor supplied and cut to size in the field. The brace brackets are available in two sizes and incorporate properly sized and spaced anchor bolt holes. The SAB-1 is designed for attachment to the pipe hanger and anchoring into steel. The SAB-2 incorporates two anchor bolt holes for attachment to concrete. Unlike cable restraints, which require 2 cables per brace location, the SAB series requires only one brace per transverse location and one brace per longitudinal location. An example on ordering the SAB series is as follows: brace anchored into concrete requires: 1 pc SAB-1 (for the attachment at the pipe hanger) 1 pc SAB-2 (for the attachment of the brace to the concrete ceiling) OR brace anchored into steel requires: 2 pcs SAB-1 (1 pc for attachment to the pipe hanger, 1 pc for attachment to the steel structure) 6
7 Isolated Suspended Equipment NOTE: Equipment must be positively attached to support steel VMC Type RSH Hanger VMC Series SCR (2 kits required per piece of equipment) Hanger Rods (by others) Support Steel (by others) All suspended mechanical equipment must be seismically restrained. While floor mounted equipment typically utilizes a seismically rated vibration isolator or separate snubber, no such device exists for suspended equipment. This is because suspended equipment can have any number of possible elevations. Fortunately, it is possible to seismically restrain isolated suspended equipment by using VMC Series SCR Seismic Cable Restraints. Series SCR cable restraints are required for externally isolated equipment only. Each piece of equipment requires a minimum of 4 cables, (2 SCR kits) installed slightly slack to insure continuity of the vibration isolation system. The cables are installed at 45 from the horizontal plane of the equipment, and in plan view, 45 from each corner. The diameter of the cable is determined through calculation and is based on the weight of the equipment and specified seismic force. Seismic Load Table Wire Recommended Max. Equipment Mimimum Recommended Rope Dia. Working Load Weight Concrete Anchor (2) in. lbs..5g 1g Dia. (in.) Embedment
8 Non-Isolated Suspended Equipment Threaded Rod (by others) Plan View Structural Steel (by others) VMC SAB-1 VMC SAB-2 Non-isolated or internally isolated suspended equipment can be seismically restrained utilizing the VMC Series SAB Single Arm Brace. Any internal isolation must have its own seismic capability certified by the unit manufacturer. While externally isolated suspended equipment requires a minimum of 4 cables, the SAB series brace can use as few as two braces per application. The braces are installed at 45 up from the horizontal plane of the equipment, and perpendicular to each other at either end of the equipment. Brace (unistrut by others) VMC SAB-1 Electrical Cable Trays VMC SAB-2 Cable Tray VMC SAB-2 VMC SAB-1 Brace (unistrut by others) The electrical system in a building is perhaps the most important part of the HVAC system. Should the power be interrupted due to inadequately restrained electrical systems, the HVAC system will be rendered inoperable, and the building useless. While we typically take great strides to insure that the mechanical equipment, pipe and ductwork are properly restrained, the electrical system is often overlooked. Any electrical conduit, cable trays, etc. used to supply power to the HVAC or emergency backup systems must be properly restrained using the VMC Series SAB Single Arm Brace. 8
9 Isolated Ductwork Concrete Angle Bracket Anchor Bolts (by others) Building Structure Shackle VMC Type RSH Vibration Hangers U-bolts Thimble Each Kit consists of: 2 - lengths of cable - swaged one end -11 ft. long or 20 ft. long, 7 x 19 Galvanized Aircraft Cable, 1/8", 1/4", 3/8" dia. 2 - concrete angle brackets 4 - shackles 2 - thimbles 4 - U-bolts 2 - clevis angles Duct: (6 square feet and larger requires restraint) Lower Angle Bracket / / Ductwork must be positively attached to the structure of the building in case of an earthquake. Isolated duct must be seismically restrained to the building structure without compromising the vibration isolation (also known as "short circuiting"). A "run" of duct must be restrained both longitudinally (in the direction of its run) and transversely (perpendicular to its run) to insure that it moves with the building and remains attached to it during an earthquake. Restraining the isolated duct is accomplished by utilizing the VMC series SCR seismic cable restraints. Our seismic cable restraints insure positive attachment to the ductwork, and when installed slightly slack, do not compromise the vibration isolation by short-circuiting the spring hanger. Our cable kits come with 2 lengths of cable, swaged on one end, and all of the hardware shown above for easy installation by the contractor. VMC Seismic cable restraints are a required component when restraining isolated duct. SCR BRACING SCHEMATIC 9
10 Non-Isolated Duct Work Anchor bolts (by others) Non-isolated threaded rod brace (unistrut by others) SAB-2 required for attachment to concrete. SAB-1 may be used for attachment to steel brace (unistrut by others) Duct: (6 square feet and larger requires restraint) SAB-1 / / TYPE SAB BRACING SCHEMATIC Non-isolated duct has the same bracing requirements as isolated duct. However, duct that is rigidly supported without isolators can be seismically restrained using the VMC series SAB Single Arm Brace. Our rigid single arm brace consists of two brackets, which allow the brace a full range of motion for ease of installation. The bracing material (typically unistrut or angle steel) is contractor supplied and cut to size in the field. The brace brackets are available in two sizes and incorporate properly sized and spaced anchor bolt holes. The SAB-1 is designed for attachment to the ductwork and anchoring into steel. The SAB-2 incorporates two anchor bolt holes for attachment to concrete. Unlike cable restraints, which require 2 cables per brace location, the SAB series requires only one brace per transverse location and one brace per longitudinal location. An example on ordering the SAB series is as follows: brace anchored into concrete requires: 1 pc SAB-1 (for the attachment at the duct) 1 pc SAB-2 (for the attachment of the brace to the concrete ceiling) OR brace anchored into steel requires: 2 pcs SAB-1 (1 pc for attachment to the duct, 1 pc for attachment to the steel structure) 10
11 Seismic Rod Bracing Clamp SRBC Rod Bracing Clamp Seismic forces act in all directions. Because the threaded rod is sized purely for gravity loads, it is necessary to add additional rod bracing to prevent buckling. Uplift forces can easily exceed the dead load on the rod resulting in compressive forces. If un-braced the rod can buckle and fail. With the addition of the VMC series SRBC bracing clamp, angle steel bracing can be quickly and easily added to the rod, stiffening and strengthening it. When vibration hangers are utilized, VMC recommends attaching the hanger directly to the overhead structure and adding an uplift washer under the box to prevent the spring from becoming unloaded. Clamp Sizing Table: Used with Size Angle Size Hanger Rod Sizes SRBC " x 1" x 1 4" 3 8", 1 2", 5 8" SRBC " x 1 1 2" x 1 4" 3 4", 7 8", 1", 1 1 8" Note: Three clamps are required per rod. Clamps are furnished complete with bolt and nut as illustrated. Project: Architect: Acoustician Contractor: Project No. Date: Drawing No. VIBRATION MOUNTINGS & CONTROLS, INC. An Aeroflex, Inc. Company 113 Main St. Box 270, Bloomingdale, NJ Toll Free: LOW-VIBE Tel: 973/ Fax: 973/ TYPE "SCR " SEISMIC RESTRAINTS 11
12 Vibration Mountings & Controls, Inc. An Aeroflex, Inc. Company 113 Main Street, Box 270, Bloomingdale, NJ Tel: 973/ TOLL FREE: LOW-VIBE Fax: 973/ Vibration Mountings & Controls, Inc. 5M 4/2000
KINETICS QuakeLoc Connector
MADE IN THE USA MADE IN THE USA MADE IN THE USA MADE IN THE USA QuakeLoc Seismic Cable Restraint Connector for piping, duct, electrical cable trays, and suspended equipment. MADE IN THE USA QuakeKit-P
More informationSpring-Flex Hangers Series SH/RSH
Bulletin No. SH/14 Spring-Flex Hangers Series SH/RSH Two Basic Designs Effective Isolation of Noise and Vibration Loads to 5,000 pounds Static Deflections to 5 inches Quickly and Easily Installed Color
More informationSEISMIC and WIND Restraint Products. 55-years of product innovation and manufacturing excellence
SEISMIC and WIND Restraint Products 55-years of product innovation and manufacturing excellence Why are Seismic and Wind Restraint Needed? For hospitals and healthcare facilities, the damaging effects
More informationSECTION 26 05 49 VIBRATION AND SEISMIC CONTROLS FOR ELECTRICAL SYSTEMS
SECTION 26 05 49 VIBRATION AND SEISMIC CONTROLS FOR ELECTRICAL SYSTEMS PART 1 - GENERAL 1.1 SUMMARY A. This Section includes seismic restraints and other earthquake-damage-reduction measures for electrical
More information3M Mobile SkyWalk Series Horizontal Lifeline Product Return Form
3M Mobile SkyWalk Series Horizontal Lifeline Product Return Form THIS FULLY COMPLETED DOCUMENT MUST BE INCLUDED WITH EACH RETURN SHIPMENT IN ORDER FOR CREDIT TO BE ISSUED. ALL CREDITS WILL BE ISSUED TO
More informationAccessories. KwikWire Clamps. KwikWire Clamp Working Loads* 78205140719 BKC100 1 /16" & 3 /32" 100 78205140723 BKC200 1 /8" & 3 /16" 50
KwikWire Clamps KwikWire system replaces jack chain or ATR to support lighting, ductwork, cable tray, etc. Can be quickly installed around beams - No drilling required. Ideal for sloped ceilings - can
More informationINSTALLING SEISMIC RESTRAINTS FOR MECHANICAL EQUIPMENT
VISCMA 412/August 2014 INSTALLING SEISMIC RESTRAINTS FOR MECHANICAL EQUIPMENT August 2014 Developed originally by the Vibration Isolation and Seismic Control Manufacturers Association under a cooperative
More informationSECTION 27 05 36 CABLE TRAYS FOR COMMUNICATIONS SYSTEMS
SECTION 27 05 36 CABLE TRAYS FOR COMMUNICATIONS SYSTEMS PART 1 GENERAL 1.01 DESCRIPTION A. The work covered by this section of the Specifications includes all labor necessary to perform and complete such
More informationFEDERAL EMERGENCY MANAGEMENT AGENCY FEMA 413/January 2004 INSTALLING SEISMIC RESTRAINTS FOR ELECTRICAL EQUIPMENT
FEDERAL EMERGENCY MANAGEMENT AGENCY FEMA 413/January 2004 INSTALLING SEISMIC RESTRAINTS FOR ELECTRICAL EQUIPMENT Notice: This guide was prepared by the Vibration Isolation and Seismic Control Manufacturers
More informationSeismic Assessment of Engineering Systems in Hospitals A Challenge for Operational Continuity
Seismic Assessment of Engineering Systems in Hospitals A Challenge for Operational Continuity S.R. Uma GNS Science, Lower Hutt. G.J. Beattie Building Research Association of New Zealand, Porirua. 2010
More informationSIMULATION PRE-INSTALLATION GUIDELINES CONTRACTOR REQUIREMENTS FOR ROOM PREPARATION
SIMULATION PRE-INSTALLATION GUIDELINES CONTRACTOR REQUIREMENTS FOR ROOM PREPARATION version 1.0_042011 www.foresightsports.com TABLE OF CONTENTS INTRODUCTION 1 COMPONENTS-AT-A-GLANCE 2 SPACE DIMENSIONS
More informationSEISMIC EVALUATION OF HOSPITAL PIPING SYSTEMS
13 th World Conference on Earthquake Engineering Vancouver, B.C., Canada August 1-6, 2004 Paper No. 1081 SEISMIC EVALUATION OF HOSPITAL PIPING SYSTEMS Elliott GOODWIN 1, Emmanuel MARAGAKIS 2, Ahmad ITANI
More informationModular Truck Equipment Price List March 1, 2012 800-627-9783 www.ladderracks.com
System Modular Truck Equipment Price List March 1, 2012 800-627-9783 www.ladderracks.com Christensen Manufacturing Corp., Pennington, NJ 08534 System Modular Truck Equipment Tradesman Package SPECIAL SAVE
More informationTHE DESIGN OF BUILDING SERVICES FOR EARTHQUAKE RESISTANCE
THE DESIGN OF BUILDING SERVICES FOR EARTHQUAKE RESISTANCE Graeme J BEATTIE 1 SUMMARY The design of seismic restraints for building services equipment is often a matter that is overlooked because there
More informationSECTION 15140 - PIPE HANGERS AND SUPPORTS
Part I - GENERAL 1.01 SECTION INCLUDES A. The work covered under this section consists of the furnishing of all necessary labor, supervision, materials, equipment, and services to completely execute the
More informationBolting: Attachment Of The Mudsill To The Foundation
Bolting: Attachment Of The Mudsill To The Foundation If the mudsill of a house (the pink area in the illustration at right) is not bolted, the lateral loads (back and forth motions) of an earthquake can
More informationHorizontal Cable Systems
Safety From The Top Down Suspended Access Systems and Fall Protection Overview Horizontal cable systems are generally installed as a permanent fall protection system, typically consisting of two terminating
More informationSports and High Mast Lighting Poles Phone: (866) 474-7200 Fax: (817) 924-7049
Sports and High Mast Lighting Poles 4 High Mast Lighting Poles General American LitePole offers a raising and lowering system that allows for ease of maintaining the lighting system at ground level. Ideal
More informationStandard Practice for Installation of Ceiling Suspension Systems for Acoustical Tile and Lay-in Panels in Areas Subject to Earthquake Ground Motions 1
Designation: E 580/E 580M 09a Standard Practice for Installation of Ceiling Suspension Systems for Acoustical Tile and Lay-in Panels in Areas Subject to Earthquake Ground Motions 1 This standard is issued
More information1-Way Bracket Assemblies
-Way Bracket Assemblies The Astro-Brac in its various configurations is a truly universal system for mounting signals. The Astro-Brac is designed to facilitate the mounting of any size or combination of
More informationPOWERS Controls No. 4 Pneumatic Damper Actuator
POWERS Controls No. 4 Pneumatic Damper Actuator Technical Instructions Document No. 155-032P25 AP 331-2 Actuator Assembly 331-2929 Typical Actuator Assembly 331-2904 Typical Actuator Assembly 331-3000
More informationSECTION 23 05 29 - HANGERS AND SUPPORTS FOR HVAC PIPING AND EQUIPMENT
SECTION 23 05 29 - HANGERS AND SUPPORTS FOR HVAC PIPING AND EQUIPMENT PART 1 - GENERAL 1.1 SUMMARY A. Section Includes: 1. Pipe hangers and supports. 2. Hanger rods. 3. Inserts. 4. Flashing. 5. Equipment
More informationResidential Deck Safety, Construction, and Repair
Juneau Permit Center, 4 th Floor Marine View Center, (907)586-0770 This handout is designed to help you build your deck to comply with the 2006 International Residential Building code as modified by the
More informationGuidelines for Earthquake Bracing Residential Water Heaters
Guidelines for Earthquake Bracing Residential Water Heaters Department of General Services Division of the State Architect In accordance with the Health and Safety Code Section 19215, the Division of the
More informationPolicy on Water Heater Installations Policy No. UPC 510-1-94 Effective: September 1, 1995 Revised: February 10, 1996
CITY OF SAN JOSE BUILDING DIVISION POLICY Policy on Water Heater Installations Policy No. UPC 510-1-94 Effective: September 1, 1995 Revised: February 10, 1996 All new and replacement water heaters installed
More informationCat. No. Finishes & Materials. Standard Finish: Electrogalvanized. Change suffix to SS6(C).
Superstrut Support Systems 1-5/8 in. x 1-5/8 in. Channel and Hardware Superstrut 1-5/8 in. x 1-5/8 in. - 12 Gauge Channel Type A Solid Base Punched Description Solid base -P Punched -HS Half slots Half
More informationHURRICANE MITIGATION RETROFITS FOR EXISTING SITE-BUILT SINGLE FAMILY RESIDENTIAL STRUCTURES
HURRICANE MITIGATION RETROFITS FOR EXISTING SITE-BUILT SINGLE FAMILY RESIDENTIAL STRUCTURES 101 Retrofits Required. Pursuant to Section 553.844 553.884, Florida Statutes, strengthening of existing site-built,
More informationHOW TO ESTIMATE THE COST OF T-BAR
HOW TO ESTIMATE THE COST OF T-BAR ACOUSTICAL CEILINGS MICHAEL HILL DATE WRITTEN: MAY OF 2007 The author is Michael Hill, Estimator with Kaiser Foundation Hospitals, National Facilities Services Cost Engineering
More informationShaft- Mounted Speed Reducers
Torque Arm Design Considerations for Todd R. Bobak has worked in the gear industry for 15 years. He has held positions in technical service, design and development, and quality assurance. He is a product
More informationAssembly Instructions for the InteliTrack 3000 Rail Tracking System
Assembly Instructions for the InteliTrack 3000 Rail Tracking System InteliTrack is a trademark of Sedona Solar Technology. Sedona Solar Technology 16 April 2013 1 1. Before you begin WARNING Safety equipment
More informationCable Installation Accessories. Cable Hoisting and Attachment. Snap-In Hangers. SnapStak Hangers
SnapStak Hangers New design increases stack height SnapStak hangers have become the industry standard for maximizing space utilization on crowded towers and now that utility is further expanded with the
More informationBracing Webs in Trusses that have Dissimilar Configurations
Bracing Webs in Trusses that have Dissimilar Configurations Released April 25, 2006 Issue: Truss Design Drawings (TDD) that are prepared in accordance with ANSI/TPI 1, National Design Standard for Metal
More informationSECTION 08360 SECTIONAL OVERHEAD DOORS 521 SERIES ALUMINUM SECTIONAL OVERHEAD DOORS
SECTION 08360 SECTIONAL OVERHEAD DOORS 521 SERIES ALUMINUM SECTIONAL OVERHEAD DOORS Display hidden notes to specifier by using Tools / Options / View / Hidden Text. On newer versions of Microsoft Word
More information270526-TC Grounding and Bonding for Telecommunications Systems
270526-TC Grounding and Bonding for Telecommunications Systems Part 1 - General Related Documents The following related sections of the OT standards shall also be applicable to this section. OT Engineer
More informationINSTALLATION OF A BAY WINDOW
INSTALLATION OF A BAY WINDOW Installation of a Bay Window These instructions relate to the replacement of an existing bay window or replacement of a straight window with a new bay window, in an opening
More informationGuidelines for Earthquake Bracing of Residential Water Heaters
Guidelines for Earthquake Bracing of Residential Water Heaters Department of General Services Division of the State Architect 1102 Q Street, Suite 5100 Sacramento, CA 95814 Phone: (916) 324-7099 Fax: (916)
More informationWisconsin Building Products Evaluation
Safety & Buildings Division 201 West Washington Avenue P.O. Box 2658 Madison, WI 53701-2658 Evaluation # 200813-O Wisconsin Building Products Evaluation Material Best Management Standards for Foundation
More informationArecont Vision H.264 Color or Day/Night SurroundVideo Series Installation Manual
0 P a g e H.264 Color or Day/Night SurroundVideo Installation Manual Inside the box: A. Arecont Vision SurroundVideo camera B. Mounting template C. RJ45 female to female coupler D. Hex key E. Security
More informationA Solid Foundation Solution for Homeowners. from. Our products are made with 90% Recycled Material Down. Right. Solid. GREEN.
A Solid Foundation Solution for Homeowners from Our products are made with 90% Recycled Material Down. Right. Solid. GREEN. Stop the damaging effects of foundation settling... Sinking foundations, cracked
More informationSTRUCTURAL CONCEPT FOR LIGHT GAUGE STEEL FRAME SYSTEM
Chapter 9 STRUCTURAL CONCEPT FOR LIGHT GAUGE STEEL FRAME SYSTEM 9.1 BACKGROUND Steel is widely used in the construction of multi-storey buildings. However, steel construction is seldom used and is traditionally
More informationBy SP Partners, LLC. www.rainbowatticstair.com INSTALLATION GUIDE. Prestige
By SP Partners, LLC www.rainbowatticstair.com INSTALLATION GUIDE Prestige IMPORTANT READ THIS FIRST Inspect stair for any damage prior to installation. Stair is NOT to be installed while home is under
More informationBUILT-IN DISHWASHER INSTALLATION INSTRUCTIONS
BUILT-IN DISHWASHER INSTALLATION INSTRUCTIONS PLEASE READ COMPLETE INSTRUCTIONS BEFORE YOU BEGIN LEAVE INSTALLATION INSTRUCTIONS AND USER'S GUIDE WITH OWNER ALL ELECTRIC WIRING AND PLUMBING MUST BE DONE
More informationSECTION 8 Industrial Facilities Field Investigation
SECTION 8 Industrial Facilities Field Investigation Types of Data to Be Collected and Recorded Warehouses, manufacturing facilities, energy-producing facilities, and factories should be inspected for performance
More informationCH. 2 LOADS ON BUILDINGS
CH. 2 LOADS ON BUILDINGS GRAVITY LOADS Dead loads Vertical loads due to weight of building and any permanent equipment Dead loads of structural elements cannot be readily determined b/c weight depends
More informationFIRE DAMPER APPLICATION GUIDE
FIRE AND CEILING RADIATION DAMPERS FIRE DAMPER APPLICATION GUIDE Use this application guide to help determine what type of fire damper best suits the application. Below are listed the ten Metal-Fab fire
More informationSeismic Technical Guide
Technical Document Seismic Technical Guide Hanger Wire Attachment Code Requirements 1 The International Building Code (IBC) defines the requirement for hanger wire and their supports and attachment methods.
More informationI BEAM TRACK INSTALLATION
PDQ 0/700 FESTOON SYSTEM INSTALLATION AND MAINTENANCE INSTRUCTIONS INTRODUCTION The PDQ Festoon System was designed to run on one of three sizes of I-beams: S x., S8 x 8. and S x.. System trolleys must
More informationATT-TP-76401-001. Internet Services Cabinet Supported Cable Rack Requirements
Internet Services Cabinet Supported Cable Rack Requirements This practice provides the guidelines and requirements for engineering and installing cable rack arrangements in AT&T IS equipment environments
More informationFEDERAL EMERGENCY MANAGEMENT AGENCY FEMA 412/December 2002 INSTALLING SEISMIC RESTRAINTS FOR MECHANICAL EQUIPMENT
FEDERAL EMERGENCY MANAGEMENT AGENCY FEMA 412/December 2002 INSTALLING SEISMIC RESTRAINTS FOR MECHANICAL EQUIPMENT Notice: This guide was prepared by the Vibration Isolation and Seismic Control Manufacturers
More informationONTRAC WIRE MESH CABLE TRAY SYSTEM
P R O D U C T D ATA S H E E T ONTRAC WIRE MESH CABLE TRAY SYSTEM K E Y F E AT U R E S Available in two styles: Shaped and Standard Tray Easy to use pathway solution that supports large quantities of network
More informationEarthquakes and Data Centers
7x24 Exchange Fall Symposium September 11, 2013 Hilton Bellevue Andrew W. Taylor, Ph.D., S.E., FACI Earthquake Hazards 2 September 11, 2013 1 Cascadia Earthquake Sources Figure Credit: Craig Weaver, Pacific
More informationRe-examining the Suitability of the Raised Floor for Data Center Applications
Re-examining the Suitability of the Raised Floor for Data Center Applications By Neil Rasmussen White Paper #19 Revision 1 Executive Summary The circumstances that gave rise to the development and use
More informationCity of Tucson and Pima County Arizona Building Code Appendix Chapter 72 Straw-Bale Structures
City of Tucson and Pima County Arizona Building Code Appendix Chapter 72 Straw-Bale Structures SECTION 7201 - PURPOSE The purpose of this appendix chapter is to establish minimum prescriptive standards
More informationLEGACY REPORT ER-5110. www.icc-es.org. ICC Evaluation Service, Inc. Reissued November 1, 2003. Legacy report on the 1997 Uniform Building Code
LEGACY REPORT Reissued November 1, 2003 ICC Evaluation Service, Inc. www.icc-es.org Business/Regional Office # 5360 Workman Mill Road, Whittier, California 90601 # (562) 699-0543 Regional Office # 900
More informationVibration Isolation Products. Spring Isolators. Isolation Hangers. Thrust Restraints. Flexible Connectors. Isolation Bases. Rooftop Isolation Curbs
Spring Isolators Isolation Hangers Thrust Restraints Flexible Connectors Isolation Bases Rooftop Isolation Curbs Neoprene Isolators Fiberglass Isolators Air Mounts Seismic and Wind Restraint Isolators,
More informationInstallation guide for the SafeLine type anchorage device. Tested in compliance with EN 795: 1996. No.: SE-...
Installation guide for the SafeLine type anchorage device Tested in compliance with EN 795: 1996 No.: SE-... Version: 09.10.2008 SE 67 Subject to technical alterations! Contents 1. General information
More informationCisco Aironet 2.4-GHz MIMO Wall-Mounted Omnidirectional Antenna (AIR-ANT2440NV-R)
Cisco Aironet 2.4-GHz MIMO Wall-Mounted Omnidirectional Antenna (AIR-ANT2440NV-R) This document outlines the specifications for the Cisco Aironet 2.4-GHz MIMO Wall-Mounted Omnidirectional Antenna (AIR-ANT2440NV-R)
More informationSECTION 230529 - HANGERS AND SUPPORTS FOR HVAC PIPING AND EQUIPMENT
SECTION 230529 - PART 1 - GENERAL 1.1 SUMMARY A. This Section includes the following: 1. Steel pipe hangers and supports. 2. Metal framing systems. 3. Thermal-hanger shield inserts. 4. Fastener systems.
More informationSummit Anchor Company, Inc.
Summit Anchor Company, Inc. Safety From The Top Down Roof and Wall Safety/Tie-Back Anchors Suspended Access Systems and Fall Protection Overview National Safety Standards OSHA regulations specifically
More informationCLEAR-DIVISIONS CENTERFOLD
CLEAR-DIVISIONS CENTERFOLD Introduction: The following three (3) part specification offers the Standard and Optional features for the CLEAR-DIVISIONS CENTERFOLD moveable The yellow highlighted areas in
More informationMaterials. Estimating Steel. Players. Materials. Shop Drawings. Detailing Process. Standard shapes. Fabricated members, Built-up sections
Materials Standard shapes W sections, C channels, Structural T, Angles, Pipes, Tubes, Rods and Plates Fabricated members, Built-up sections Adding plates to beam flanges, Stiffeners to beam webs Built
More informationCalvert USA, Inc. Attic Stairs
Calvert USA, Inc. Attic Stairs Instructions for installation of vertical opening access stairs Model numbers: 7035 through 7047 Calvert USA, Inc., P.O. Box 841, Solomons, MD 20688, Tel. (410) 286-1430,
More informationChapter 5 FLOOR LOADING AND WEIGHTS
Chapter 5 FLOOR LOADING AND WEIGHTS Section 1.0 Floor Loading Section 2.0 Seismic Data The CT system has a total floor load of approximately 6660 lbs (3021 kg). About 5050 lbs (2291 kg), including patient
More informationATS Overhead Table Shelf System INSTRUCTION MANUAL
ATS Overhead Table Shelf System INSTRUCTION MANUAL ATS Overhead Table Shelf System Instruction Manual Warranty Newport Corporation warrants this product to be free of defects in material and workmanship
More informationMark Cramer Inspection Services, Inc.
Mark Cramer Inspection Services, Inc. 492 Twentieth Avenue, Indian Rocks Beach, FL 34635-2970 (727) 595-4211 Fax (727) 596-7583 Certified Member #12085 American Society of Home Inspectors Construction
More informationPump Specifications 250 Series Submersible Sump / Effluent Pump 2 Solids handling
Pump Specifications 250 Series Submersible Sump / Effluent Pump 2 Solids handling 250_P1 R10/7/2015 Copyright 2015 Liberty Pumps Inc. All rights reserved. Specifications subject to change without notice.
More informationINSTALLATION INSTRUCTIONS HUSTLER 4-BTV, 5-BTV TRAP VERTICAL WARNING INSTALLATION OF THIS PRODUCT NEAR POWER LINES IS DANGEROUS
INSTALLATION INSTRUCTIONS HUSTLER 4-BTV, 5-BTV TRAP VERTICAL WARNING INSTALLATION OF THIS PRODUCT NEAR POWER LINES IS DANGEROUS FOR YOUR SAFETY, FOLLOW THE INSTALLATION DIRECTIONS GENERAL DESCRIPTION:
More informationInstallation Instructions Hustler 6-BTV Trap Vertical
Installation Instructions Hustler 6-BTV Trap Vertical ASSEMBLY 1. Check the package contents against the parts list on page 2. 2. WARNING. Installation of this product near power lines is dangerous. For
More informationCTI TECHNICAL BULLETIN Number 6: A publication of the Cable Tray Institute
CTI TECHNICAL BULLETIN Number 6: A publication of the Cable Tray Institute Circuit Integrity of Cable Tray Wiring Systems During Natural Disasters The January 17,1994 Los Angles, California earthquake
More informationCoaxial Cable Installation Accessories
Installation Instructions Bulletin 37608 Coaxial Cable Installation Accessories Hoisting Grips for Coaxial Cable and Elliptical Waveguide READ ALL WARNINGS AND INSTRUCTIONS BEFORE INSTALLATION Antenna
More informationSECTION 22 LIGHTNING PROTECTION SYSTEM
SECTION 22 LIGHTNING PROTECTION SYSTEM 22.01 SCOPE: A. These Specifications shall form a part of the Contract Documents and shall govern construction work for all buildings to be built or modified for
More informationIRRIGATION PUMPING Table of Contents - Section 900
IRRIGATION PUMPING Table of Contents - Section 900 PARAGRAPH 900.1 GENERAL 1 900.2 METERING REQUIREMENTS 1 900.3 CUSTOMER S CONTROL EQUIPMENT 2 900.4 SERVICE CONDUCTOR REQUIREMENTS 2 900.5 RECOMMENDATIONS
More information--- Jaypro Retractable Practice Cages --- Installation and Operating Instructions
--- Jaypro Retractable Practice Cages --- Installation and Operating Instructions Applicable Jaypro Part Numbers / Cage Models: BBC-700B = Ceiling Suspended Retractable Baseball Batting Cage BBC-700M =
More informationPole Guying More Complicated Than Meets the Eye. NRECA TechAdvantage 2014 Presented by Jason Settle, P.E. jason.settle@gdsassociates.
Pole Guying More Complicated Than Meets the Eye NRECA TechAdvantage 2014 Presented by Jason Settle, P.E. jason.settle@gdsassociates.com Pole Guying Strength of components NESC vs. RUS Guy Factor Grounding
More informationSELF-STEERING AXLE TABLE OF CONTENTS
SELF-STEERING AXLE TABLE OF CONTENTS Section 1 - Introduction Section 2 - Pre-Installation Check List Section 3 - Ride Height Adjustments Section 4 - Suspension Mount Section 5 - Axle Mount Section 6 -
More informationInstallation and Maintenance Manual for SPANCO Freestanding Modular Bridge Cranes & Monorails
Manual No. 103-0045 REV. 12/08 Installation and Maintenance Manual for SPANCO Freestanding Modular Bridge Cranes & Monorails ISO 9001 REGISTERED 2 TABLE OF CONTENTS Important Dimensions for Modular Bridge
More informationFacilities Development Division. The Building Department for California s Hospitals
OSHPD Special Seismic Certification Preapproval (OSP) Preapproval of Special Seismic Certification by OSHPD is a voluntary program for Equipment Manufacturers! Facilities Development Division The Building
More informationSeismic Data Requirements for Eaton UPS Equipment Installation
Seismic Data Requirements for Eaton UPS Equipment Installation 1.1 Introduction Eaton equipment represented in the following sections were subjected to seismic testing in accordance with the 2006 or 2012
More informationSECTION 08332 COILING COUNTER DOORS. Display hidden notes to specifier. (Don't know how? Click Here)
SECTION 08332 COILING COUNTER DOORS Display hidden notes to specifier. (Don't know how? Click Here) PART 1 GENERAL 1.1 SECTION INCLUDES A. Coiling Metal Counter Doors. B. Coiling Counter Fire Doors. 1.2
More informationPRESTRESSED CONCRETE POLES The Solid Alternative to Wood
Prestressed Concrete Utility Poles U-1 PRESTRESSED CONCRETE S The Solid Alternative to Wood Lonestar Prestress concrete poles were developed to meet the expanding need of a supporting structure for; street,
More informationConduit Fittings & Accessories Directional Drilling Conduit Utility Duct Telephone Duct Residential Boxes
CANTEX INC. 301 Commerce Ste 2700 Fort Worth, Texas 76102 817-215-7000 Fax: 817-215-7001 Conduit Fittings & Accessories Directional Drilling Conduit Utility Duct Telephone Duct Residential Boxes YOUR FULL
More informationCDGRD-10. Grounding. Solutions For Comm/Data Applications
CDGRD-10 Grounding Solutions For Comm/Data Applications Overview & Table of Contents Cooper B-Line s Grounding products for rack & runway provide a complete solution for grounding metal supports. The offering
More informationSECTION 11014 WINDOW WASHING SYSTEMS
SECTION 11014 WINDOW WASHING SYSTEMS PART 1 - GENERAL 1.1 SUMMARY A. Section includes, but is not limited to, design and furnishing portable davits, davit sleeves, dvit bases, four (4) removable outriggers,
More informationOVERALL CONVEYOR WIDTH STEEL ALUMINUM MODEL # PER FT. 10 FT. 5 FT. PER FT. 10 FT. 5 FT. PER FT. 10 FT. 5 FT. PER FT. 10 FT. 5 FT.
Pick Smarter. Pick Better. Pick UNEX. Skatewheel (SW) Skatewheel Gravity Conveyor is ideally suited to convey lightweight packages and where operations require portable or temporary conveyor lines such
More informationKey Considerations for Selecting Server Cabinets for Seismic Areas
Key Considerations for Selecting Server Cabinets for Seismic Areas Protect Up to 1500 of Critical Network Equipment without Sacrificing Flexibility Planning a data center in a seismically active area requires
More informationElectrical. This section applies to the design and installation of building power distribution systems.
Basis of Design This section applies to the design and installation of building power distribution systems. Design Criteria This section contains the architectural, structural and mechanical provisions
More informationPIPES AND TUBES FOR HVAC PIPING AND EQUIPMENT
PIPES AND TUBES FOR HVAC PIPING AND EQUIPMENT GENERAL INFORMATION 1.1 This section applies to piping systems for chilled water, hot water, condenser water, steam, condensate return, fuel oil, refrigerant
More informationCABLE SUPPORT SYSTEMS
CABLE SUPPORT SYSTEMS eaturing the CADDY CAT HP J-Hook System Why CADDY CAT HP? Why Choose CADDY CAT HP over tray? ast and Easy to Install Much faster installation compared to conventional cable or ladder
More informationUS 51 Ohio River Bridge Engineering and Environmental Study
US 51 Ohio River Bridge Engineering and Environmental Study ITEM NOS. 1-100.00 & 1-1140.00 Prepared by: Michael Baker Jr., Inc. 9750 Ormsby Station Rd Louisville, KY 40223 August 16, 2013 Table of Contents
More informationConnection Solutions
Connection Solutions DESIGN BUILD SYSTEM Connection Solutions for Cold formed Steel Construction Complies with; AS/NZS 4600:2005 AISI S100:2007 AS/NZ 1397 ASTM A653 DESIGN & BUILD SYSTEM FRAMECAD Construction
More informationGUIDELINES FOR UTILITY INSTALLATIONS Part 1 - Wire Lines and Communications Cables
Engineering Department SEPTEMBER, 2007 GUIDELINES FOR UTILITY INSTALLATIONS Part 1 - Wire Lines and Communications Cables General Requirements This section applies to all public and private utilities,
More informationCritical Facility Round Table
Critical Facility Round Table October 16, 2003 San Francisco Seismic Risk for Data Centers David Bonneville Senior Principal Degenkolb Engineers San Francisco, California Presentation Outline Seismic Risk
More informationThis mount uses concrete parking bumpers and a Davis tripod to create a mounting solution for nonpenetrable
NON-PENETRATING FLAT ROOF MOUNT Application Note 18 For Any Davis Weather Station Installed on a Mounting Tripod Introduction This application note describes various mounting solutions for non-penetrable
More informationMETHOD OF STATEMENT FOR STATIC LOADING TEST
Compression Test, METHOD OF STATEMENT FOR STATIC LOADING TEST Tension Test and Lateral Test According to the American Standards ASTM D1143 07, ASTM D3689 07, ASTM D3966 07 and Euro Codes EC7 Table of Contents
More informationCable Runways & Accessories
SB17U SB13AL SB17 SB17T SB117 SB17HRB SB2107 SB2101A SB17VRB SB2110A SB2129 SB2129SD SB130 SB2221 SB126 SB2118 SB119 SB2105 113 Cooper B-Line manufactures a wide variety of high quality cable pathway products
More informationPUSH-PULL CABLES CONTROL SYSTEMS
ISO 9001 CERTIFIED PUSH-PULL CABLES CONTROL SYSTEMS WESCON PRODUCTS COMPANY A subsidiary of LATSHAW ENTERPRISES, INC. WESCON'S PUSH-PULL CONTROL SYSTEMS Push-Pull Cable Ends Wescon Push-Pull Cable Assemblies
More informationThese Installation Instructions are valid for antennas in the following version:
Installation Instructions 4 ft CompactLine Antennas (with E-Mount 250 km/h) SB, SBX NMT 560-05(e) These Installation Instructions are valid for antennas in the following version: Reflector Ø 1.2 m (4 ft)
More informationIt's large enough to handle most welding job shop projects, yet small enough to make it a worth while home-workshop tool
It's large enough to handle most welding job shop projects, yet small enough to make it a worth while home-workshop tool H Craft Print Project No. 272 ERE'S a metal bender that will enable you to bend
More informationWeight Measurement Technology
Kistler-Morse (KM) introduced bolt-on weight measuring systems three decades ago. These devices featured Walter Kistler s invention, the Microcell. Over the years, many improvements were made to the Microcell
More information