KOLMA and IHDA Indoor type Cable Current Transformers Catalogue ABB Power Distribution ABB Transmit 1 KKOLMA 1 GB
|
|
- Randolf Johnston
- 7 years ago
- Views:
Transcription
1 KOLMA and IHDA Indoor type Cable Current Transformers Catalogue ABB Power Distribution ABB Transmit 1 KKOLMA 1 GB
2 KOLMA and IHDA Indoor Type Cable Current Transformers Index Description... 3 Technical data and ordering information Cable Current Transformers type KOLMA... 4 How to select the correct residual current transformers... 4 Technical data... 4 Installation... 5 Number of turns and terminal markings... 5 Current rations and rated burdens for accuracy class 10 P Ordering data... 6 Current transformers type IHDA... 7 Selection table... 7 Technical data... 7 Special current transformers KOKM and KOKU Accessories Ordering data Overall dimensions KOLMA, KOLA IHDA ABB Transmit KOLMA 1 GB
3 KOLMA and IHDA Indoor Type Cable Current Transformers Description Transformers, KOLMA_ and KOLA_ are suitable for the measurement of the sum of three-phase currents in a 3-phase cable. Under normal operating conditions this sum is zero. In the event of an earth-fault the sum of the currents is equal to the earthfault current and a corresponding current flows in the secondary. IHDA 05 current transformers are suitable for measuring of phase currents in low voltage switchgear. An uninsulated busbar or low voltage cable serves as the primary conductor. These transformers are used together with static earth-fault relays. The cable current transformers can generally be used when measuring the residual current e.g. to prewarn of, or locate an earth-fault. ABB Transmit 3 KKOLMA 1 GB
4 Cable Current Transformers type KOLMA Technical data and ordering information How to select the correct residual current transformers The transformer for an earth-fault relay is selected according to dimension of the window, and construction of the transformer. For types KOLMA 06 A1, and KOLMA 06 D1, the number of turns used in the secondary winding is selected according to the relay setting value, and the earth-fault current or the required current ratio. In addition correct functioning of the earthfault protection relays for KOLMA 06 A1 and KOLMA 06 D1 is easy to test by means of the test winding (terminals P1x - P2x) of the transformer. The test winding is rated for 6 A max. continuous current. Table 1. Selection of residual current transformers Type Window diam. Construction Weight mm kg KOLMA 06 A1 90 Ring core, multi-tap secondary 7.0 KOLMA 06 A2 58 Ring core 2.9 KOLMA 06 B2 100 Ring core 5.4 KOLMA 06 D1 180 Ring core, multi-cap secondary 11.5 KOLMA 06 D2 180 Ring core 11.4 KOLA 06 B2 100 Split ring core 6.0 KOLA 06 D2 180 Split ring core 11.0 Technical data The primary winding of indoor type cable current transformers is either a cable or a busbar, which is insulated for the application voltage. The secondary winding and ring shaped iron core is cast in resin which has good electrical and mechanical properties Cable current transformers, types KOLMA_ Rated voltage 0.72 kv (1) Insulation test voltage 50 Hz 1 min 3 kv (IEC 185) Frequency 50 Hz (60 Hz) Rated thermal current 1.2 x I pn Short-time withstand current I th 1 s 60 x I pn (2) Peak withstnad current I dyn 2.5 x I th Secondary terminals For 6 mm 2 conductor Operating temperature range o C (1) The insulation level of the primary conductor determines the maximum operating voltage. (2) KOLA 06 B2 is type tested for 10 ka 3 s. 4 ABB Transmit KOLMA 1 GB
5 Cable Current Transformers type KOLMA Technical data and ordering information Installation The KOLMA-types must be installed before the cables and cable terminations are connected. INST With the KOLA 06 B2 and KOLA 06 D2 -types, the ring core can be opened and thus the transformer can be installed eventhough the cable is already connected. The two halves of the ring core are tightened together with four screws which also guide the halves to the correct position. The secondary winding is distributed over both halves of the core. The two sections of the winding are connected together with two connecting pieces. Cable current transformers are fastened either by means of the fixing base or by the nuts cast into the transformer frame. When installing the transformer, the effect of the current in the metal armour or in the protective conductor must be eliminated. In case the metal armour or the protective conductor is drawn through the transformer, the earthing conductor must be drawn back through the transformer for earthing. The earthing conductor between the cable termination box and the transformer, must not be connected to conductive structures, and the metal cable termination box must be insulated from the supporting structures. On a multi-ratio transformer the unconnected secondary winding terminals and test winding must not be short circuited. Number of turns and terminal markings KOLMA 06 A1 KOLMA 06 D1 KOLMA 06 A2 KOLMA 06 B2 KOLMA 06 D2 KOLA 06 B2 KOLA 06 D2 KOLMA ABB Transmit 5 KKOLMA 1 GB
6 Cable current transformers type KOLMA Current rations and rated burdens Technical data and ordering information Table 2. Current ratios and rated burdens for accuracy class 10 P 10 Design data. Types KOLMA 06 A1 and KOLMA 06 D1 Current ratio Secondary terminals Burden / VA Type A KOLMA 06 A1 KOLMA 06 D1 50/1 S4 - S /1 S3 - S /1 S1 - S /1 S1 - S /5 S1 - S /5 S2 - S /5 S1 - S /5 S4 - S /5 S3 - S /5 S1 - S /5 S3 - S /5 S1 - S Table 3. Current ratios and rated burdens for accuracy class 10 P 10 Design data. Types KOLMA 06 A2, KOLMA 06 B2, KOLMA 06 D2 and KOLA 06 B2 Type Current ratio Secondary terminals Burden A VA Openable residual current transformers, type KOLA 06 B2 complete with fixing base KOLMA-ZK 1 and terminal cover KOK-ZAX 14. KOLMA 06 A2 100/1 S1 - S2 2.0 KOLMA 06 B2 100/1 S1 - S2 2.5 KOLMA 06 D2 100/1 S1 - S2 2.0 KOLA 06 B2 100/1 S1 - S2 2.0 KOLA 06 D2 100/1 S1 - S2 2.0 Ordering data quantity type Accessores shall be ordered separately. 6 ABB Transmit KOLMA 1 GB
7 Current transformers type IHDA 05 Technical data and ordering information Current transformer series IHDA 05 for measuring of phase currents IHDA 05 current transformers are suitable for measuring of phase currents in low voltage switchgear. An uninsulated busbar or low voltage cable serves as the primary conductor. Series IHDA 05 current transformers can also be used for measuring the phase current at voltages even higher than 0.72 kv, if the insulation of the high voltage primary conductor fulfils the respective standards for the operating voltage. Selection of current transformers Transformer selection is made according to tables 4 and 5. Ordering On order please mention quantity, type and class. Example: 3 pcs IHDA 05 B1-150/1, class 3 Technical data Rated voltage 0.72 kv (1) Insulation test voltage 50 Hz 1 min 3 kv (IEC 185) Frequency 50 Hz (60 Hz) Rated thermal current 1.2 x I pn Short-time withstand current I th 1 s 60 x I pn (2) Peak withstnad current I dyn 2.5 x I th Secondary terminals For 6 mm 2 conductor Operating temperature range o C (1) The insulation level of the primary conductor determines the maximum operating voltage. ABB Transmit 7 KKOLMA 1 GB
8 Current transformers type IHDA 05 Technical data and ordering information Table 4. Selection of current transformers. Secondary current I sn = 1 A Rated frequency 50 Hz Performance values according to IEC 185 < < F s = F a = Instrument security factor Accuracy limit factor Type Window Prim. Burden (VA) Weight diam. curr. Class and Fs or Fa IHDA mm A 0.5 Fs 1 Fs 3 Fs 10P Fa kg 05A1 100/ A1 150/ A1 200/ A1 300/ A1 400/ A1 500/ A1 600/ B1 100/ B1 150/ B1 200/ B1 300/ B1 400/ B1 500/ B1 600/ B1 800/ C1 400/ C1 500/ C1 600/ C1 800/ C1 1000/ D1 600/ D1 800/ D1 1000/ D1 1200/ D1 1500/ D1 1600/ E1 1500/ E1 1600/ E1 2000/ Cable current transformers with one secondary winding, typ IHDA_ ABB Transmit KOLMA 1 GB
9 Current transformers type IHDA 05 Technical data and ordering information Table 5. Selection of current transformers. Secondary current I sn = 5 A Rated frequency 50 Hz Performance values according to IEC 185 < < F s = F a = Instrument security factor Accuracy limit factor Type Window Prim. Burden (VA) Weight diam. curr. Class and Fs or Fa IHDA mm A 0.5 Fs 1 Fs 3 Fs 10P Fa kg 05A1 100/ A1 150/ A1 200/ A1 300/ A1 400/ A1 500/ A1 600/ B1 100/ B1 150/ B1 200/ B1 300/ B1 400/ B1 500/ B1 600/ B1 800/ B1 1000/ B1 1200/ C1 400/ C1 500/ C1 600/ C1 800/ C1 1000/ C1 1200/ C1-1500/ C1-1600/ D1 600/ D1 800/ D1 1000/ D1 1200/ D1 1500/ D1 1600/ E1 1500/ E1 1600/ E1 2000/ E1 2400/ E1 2500/ E1 3000/ ABB Transmit 9 KKOLMA 1 GB
10 Special current transformers Technical data and ordering information Special current transformers KOKM 06_ and KOKU 06_ Special indoor type current transformer type KOKM 06 J2. Window size 300 x 500. Examples of some special transformer. Left: KOKM 06 for indoor use. Right: KOKU 06 for outdoor use. We also manufacture current transformers cast in epoxy resin, to meet special demands, both for outdoor and indoor use. Enquires for these special transformers should mention the following data: 1. Quantity 2. Current ratio I pn /I sn (A) 3. Burden (VA) 4. Accuracy class 5. Window dimension (mm) 6. Other limiting data such as instrument security factor, dimensions of transformer, fixing of transformer (fixing base) etc. 7. Indoor or outdoor use Maximum service voltage for these transformers is 0.6 kv. The insulation of the primary conductor determines the highest permissible system voltage. 10 ABB Transmit KOLMA 1 GB
11 Accessories Ordering data Ordering data for accessories - quantity - type Table 6. Selection of accessories for KOLMA_ and KOLA_ Description of accessory Type Suitable for use together with transformer Fixing base KOLMA-ZK 1 KOLMA 06 A1 Fixing base KOLMA-ZK 1 KOLMA 06 A2 Fixing base KOLMA-ZK 1 KOLMA 06 B2 Fixing base KOLMA-ZK 1 KOLA 06 B2 Fixing base KOLMA-ZK 2 KOLMA 06 D1 Fixing base KOLMA-ZK 2 KOLMA 06 D2 Fixing base KOLMA-ZK 2 KOLA 06 D2 Secondary terminal cover KOK-ZAX 14 KOLMA 06 A2 Secondary terminal cover KOK-ZAX 14 KOLMA 06 B2 Secondary terminal cover KOK-ZAX 14 KOLA 06 B2 Secondary terminal cover KOK-ZAX 14 KOLA 06 D2 Table 7. Selection of accessories for IHDA_ Type Description Suitable for IHDA current transformer KOK-ZAX 12 Fixing base (1) A1 KOK-ZAX 13 Fixing base (1) B1...E1 KOK-ZAX 14 Secondary terminal cover (2) B1...E1 (1) The fixing base shall be fixed to the bottom inserts of the current transformer by means of screws equipped with spring washers which are included in the package. The fixing base can be mounted either in line with the current transformer of transversely. (2) The secondary terminal cover shall be mounted on the secondary terminals of the current transformer. The cover includes a bushing sleeve. There are two alternative holes for the outgoing wiring. The cover is sealable. ABB Transmit 11 KKOLMA 1 GB
12 KOLMA Overall dimensions KOLMA 06 A1 KOLMA 06 A2, B2 06A2 06A1 Type A B C D KOLMA 06 A B KOLMA 06 D1, D2 06D1 12 ABB Transmit KOLMA 1 GB
13 KOLA Overall dimensions KOLA 06 B2 KOLA 06 D2 06D2 06B2 ABB Transmit 13 KKOLMA 1 GB
14 IHDA Overall dimensions IHDA 05 A1 IHDA 05 B1, C1, D1, E1 IHDA A1 IHDAB1 Type Dims./mm IHDA A B C D 05 B C D E ABB Transmit KOLMA 1 GB
15 IHDA Overall dimensions Base for IHDA 05 A1 Type KOK-ZAX 12 Base for IHDA 05 B1, C1, D1, E1 Type KOK-ZAX 13 05B1 05A1 ABB Transmit 15 KKOLMA 1 GB
16 IHDA Overall dimensions Terminal cover for IHDA 05 B1, C1, D1 and E1. Sealable. KOK-ZAX 14 KOKZAX IHDA.TBL Type IHDA 05 B1 05 C1 05 D1 05 E1 Dim. H mm ABB Transmit KOLMA 1 GB
17 ABB Transmit 17 KKOLMA 1 GB
18 ABB Transmit Oy MV Systems Division P.O.Box 613, FIN Vaasa, Finland Tel: Fax: Catalogue KOLMA 1 GB 94-11/97-03 Ykkös-Offset Oy 3000, ABB Transmit KOLMA 1 GB
PPS-PPQ-BT-PIAS RESIN INSULATORS FOR OIL INSULATED ELECTRICAL MACHINES
PPS-PPQ-BT-PIAS RESIN INSULATORS FOR OIL INSULATED ELECTRICAL MACHINES BUSHING WITH PLUG CONNECTION WITH OUTER CONE PPS CHARACTERISTICS The PPS bushing can be used as a fixed section for the entry of medium
More informationMedium-voltage transformers
Medium-voltage transformers We make energy measurable and take care of your future www.mbs-ag.com Page 2 E-Mail: info@mbs-ag.com Web: www.mbs-ag.com Contents Current transformers Technical characteristics
More informationTape Wound, Split Core and Ebony Current Transformers
Tape Wound, Split Core and Ebony Current Transformers Current Transformers Contents Page Tape Wound Measuring and Protection Current Transformers 2 6 Split Core Current Transformers 7 9 3-in-1 Current
More informationTape Wound, Split Core and Ebony Current Transformers
Tape Wound, Split Core and Ebony Current Transformers Table of contents Tape Wound Measuring and Protection Current Transformers 2 MR Series Measuring Range 3 PR Series Protection Range 4 Class PX Current
More informationLow Voltage Products. Switches Automatic Transfer Switches
Low Voltage Products Switches Automatic Transfer Switches Growing importance of a secure power supply Standby power is an integral part of many industrial and domestic electrical systems. High energy prices,
More informationVoltage Regulator SPAU 341 C. Product Guide
Issued: July 1998 Status: Updated Version: D/25.04.2006 Data subject to change without notice Features Comprehensive voltage regulation for power transformers with on-load tapchangers in distribution substations
More informationLOW VOLTAGE RING TYPE MEASURING CURRENT TRANSFORMERS
Specification for LOW VOLTAGE RING TYPE MEASURING CURRENT TRANSFORMERS CEYLON ELECTRICITY BOARD SRI LANKA Specification for LOW VOLTAGE RING TYPE MEASURING CURRENT TRANSFORMERS CEB Standard 027: 1998 CEYLON
More informationLOW-VOLTAGE CURRENT TRANSFORMERS
LOWVOLTAGE CURRENT TRANSFORMERS 5 A Power network meters ND0 and ND type. N4Z and N5Z Tel: (+48 68) 45 75 39; 45 75 305; 45 75 3; 45 75 368; email: export@lumel.com.pl ul. Słubicka 657 Zielona Góra CONTENTS
More informationMEDIUM VOLTAGE CE-BF SWITCHBOARDS. UP TO 40.5 kv. CE - BF - C - en - REV.00 2012.4
CE - BF - C - en - REV.00 2012.4 APPLICATION CE-BF Switchbords up to 40.5 kv are designed for use in public and industrial distribution system up to 40,5KV for the operation and protection of lines, transformers,
More informationVario-Series Accessories
Accessories and spare parts for GMW analogue panel meters and controllers Current Transformers pages 2-9 Shunt Resistors 10-11 Voltage Dividers 12 Power supply for indicator/controllers 13 Blanking Plates
More informationMeasurement devices Accessories for analogue and digital instruments
Accessories for analogue and digital instruments 1 2CSC96F0001 Current transformers Used to transform primary currents (max. 6000 A) into.../5 A and.../1 A low secondary currents indirectly supplying power
More informationEnhanced Quality with a Touch of Style
Rudolf Current Transformer Enhanced Quality with a Touch of Style Current Transformer Enhanced Quality with a Touch of Style New Products Rudolf launched our new encapsulated current transformer. Portraying
More informationkeep your measure under control
INSTRUMENTACIÓN INDUSTRIAL ZURC, S.A. keep your measure under control CURRENT For measuring instruments. Mounted in selfexinguishing, plastic, strengthened cases. Isolation voltage V Made as per UNEEN
More informationELEKTROTEHNI KO PODJETJE Leskoπkova cesta 12, 1000 Ljubljana, SLOVENIA
MRO Modularne Razdelilne Omare d.o.o. ELEKTROTEHNI KO PODJETJE Leskoπkova cesta 2, 000 Ljubljana, LOVENIA MC GENERAL When to use? MC - modular switchgear cabinets are type-tested, factory built switchgears,
More informationCurrent transformers (CT) & Shunts
Current transformers (CT) & Shunts Genreal overview LV CURRENT TRANSFORMERS Product selection guide Standard industrial transformers?????? TCR - TCRO range NEW 9 9 9 Current summation JVM 0 9 TCR usbar
More information0.84" x 2.00" Z-TRAUQ INC. Tel.: (450)226-6997 Fax: (450)226-5837 z-trauq@qc.aira.com SPLIT CORE CURRENT TRANSFORMER MODEL 1SP.
SPLIT CORE CURRENT MODEL 1SP 0.84" x 2.00" PAGE No 3-2 REV 18DEC00 UL 1015 LEAD WIRE, STANDARD LENGTH IS 36 E DIMENSIONS A = 0.84 MIN B = 2.00 MIN C = 3.31 MAX D = 3.09 MAX E = 0.61 MAX F = 0 MAX F C B
More informationPressure monitoring equipment for oil-sf 6. bushings, type GOEK
Pressure monitoring equipment for oil-sf 6 bushings, type GOEK Installation and maintenance guide 5693 827-6 en, Rev. 3, 2002-01-30 This document must not be copied without our written permission, and
More information1ZSC000563-AAC en, Rev. 7. Resin impregnated paper bushing, oil to air, type GSB Technical guide
1ZSC000563-AAC en, Rev. 7 Resin impregnated paper bushing, oil to air, type GSB Technical guide Original instruction The information provided in this document is intended to be general and does not cover
More informationMedium voltage product. Instrument transformers for indoor applications Product overview
Medium voltage product Instrument transformers for indoor applications Product overview 02 Contents Introduction Current transformers Supporting type 6 TPU, TPE 7 KOFA, IHBF 10 Dummy Bus type 8 KOKS 12,
More information1ZSE 2750-105 en, Rev. 8. Transformer bushings, type GOE and GOE(2) Technical guide
1ZSE 2750-105 en, Rev. 8 Transformer bushings, type GOE and GOE(2) Technical guide Original instruction The information provided in this document is intended to be general and does not cover all possible
More informationQuick Connect. quick - simple - efficient. www.g-mw.de
Quick Connect quick - simple - efficient www.g-mw.de Phone: +49 9103 7129-0 Fax: +49 9103 7129-207 Innovative connection technology to plug three single-phase current transformers to multifunctional power
More informationCirculating Current Relay. Type IRXm
Circulating Current Relay Type IRXm ABB a global technology leader ABB is a global leader in Power and Automation technologies that enable utility and industry customers to improve performance while lowering
More informationCapacitor Protection Relay SPAJ 160 C. Product Guide
Issued: April 1999 Status: Updated Version: C/19.04.2006 Data subject to change without notice Features One-, two- and three-phase overload stage with definite time characteristic One-, two- and three-phase
More information3.1.1 Full Type Tests & Routine Tests according to Clause 8 2 & 8 3. 4.0 Instructions For Installation, Operation & Maintenance
SPECIFICATION FOR LOW VOLTAGE SWITCHBOARD SEN I N D E X Description 10 STANDARD TECHNICAL REQUIREMENTS 11 Standards 12 General Operating Conditions 13 General Description Of Switchboard 131 Structure 132
More informationDead Tank Circuit Breaker 72PM40-C Proven reliability through common platforms
Dead Tank Circuit Breaker 72PM40-C Proven reliability through common platforms ABB innovations for changing demands ABB (www.abb.com) is a leader in power and automation technologies that enables utility
More informationCurrent & Instrument Transformers
Reliable & Accurate Inputs for Measuring & Protection Equipment Current & Instrument Transformers Type MKE11 Inside the Catalogue Range Specifications Ordering Code Delivering Value to You M-Kris Electric
More informationType: EASY719 DC RC Article No.: 274119. Ordering information Relay outputs Quantity 6 Power supply V DC 24 V DC. Description
Type: EASY719 DC RC Article.: 274119 Ordering information Relay outputs Quantity 6 Power supply V DC 24 V DC Description 12 digital inputs (4 inputs available as analog inputs) 6 relay outputs LCD display
More informationOur brand POWER DYNAMIC PASSION COMMITMENT CREATIVITY. A strong brand for strong products: 8PU Premium. MV Energy
Our brand A strong brand for strong products: The ENERGOLINE brand represents our product portfolio of INDUSTRIAL SWITCHGEAR SYSTEMS. Our products are characterized by a high degree of safety, flexibility
More informationProduct presentation. PPMV Instrument transformers. Milos Dvorak Product manager CZELS. ABB s.r.o. -1
Product presentation Milos Dvorak Product manager CZELS PPMV Instrument transformers ABB s.r.o. -1 General information General information Instrument transformers Current transformers Current transformers
More informationHow To Choose A Transformer
Consider open loop MV network as an example source 1 source 2 NC NC NC or NO main MV switchboard A B Detail design of substation NC NC NC NO NC NC switchboard 1 switchboard 2 switchboard 3 MV MV MV LV
More informationCalculation of the Current Transformer Accuracy Limit Factor Application Note
Calculation of the Current Transformer Application Note kansikuva_bw 1MRS 755481 Issued: 09.11.2004 Version: A/09.11.2004 Calculation of the Current Transformer Application Note Contents: 1. Scope...4
More informationInstrument Transformers Application Guide
Instrument Transformers Application Guide Edited by ABB AB High Voltage Products Department: Marketing & Sales Text: Knut Sjövall, ABB Layout, 3D and images: Mats Findell, ABB SE-771 80 LUDVIKA, Sweden
More informationUnified requirements for systems with voltages above 1 kv up to 15 kv
(1991) (Rev.1 May 2001) (Rev.2 July 2003) (Rev.3 Feb 2015) Unified requirements for systems with voltages above 1 kv up to 15 kv 1. General 1.1 Field of application The following requirements apply to
More information5SV Residual Current Protective Devices
s Siemens AG 2013 SENTRON 5SV Residual Current Protective Devices New portfolio for reliable personnel, material and fire protection Safe protection against residual currents Residual current protective
More informationEarth Fault Detection Basics in Theory
Earth Fault Detection Basics in Theory Author: Dipl.-Ing. Ingo Kühnen Woodward Power Solutions Krefelder Weg 47 47906 Kempen, Germany Kempen, 16.04.2010 Earth_Fault_Detection_20100416.doc page 1 1. Star
More informationDS 600. A contact free flux gate based current measurement sensor 600A rms
DS 600 A contact free flux gate based current measurement sensor 600A rms DS 600 is member of the small housing sensor family. The family includes a 200A and a 600A version. 600A rms - 900A peak Maximum
More informationUniGear ZS1. Medium voltage, arc proof, air insulated switchgear for primary distribution
UniGear ZS1 Medium voltage, arc proof, air insulated switchgear for primary distribution UniGear ZS1: an innovative solution for all installation requirements ABB UniGear is medium voltage metal-clad,
More informationZ-TRAUQ INC. Tel.: (450)226-6997 Fax: (450)226-5837 z-trauq@qc.aira.com
CURRENT TRANSFORMER MODEL J " x 7" PAGE No 2-2 REV 8DEC00 TERMINAL OPTION LEAD WIRE OPTION 8-2 BRASS SCREW TERMINALS (2 PLACES) SEE NOTE 9 6 9 8 6 Ø 2 9 (4 PLACES) UL 05 #6 AWG LEAD WIRE, STANDARD LENGTH
More informationAutoLink Three-Phase Sectionalizer Specifications. Scope. General. Applicable Standards. Operating principle
Scope This specification stipulates the minimum requirements for mechanically linked three-phase electronic sectionalizers, for use on outdoor medium voltage overhead lines of 15, 27, and 38 kv. Electronic
More informationCurrent transformer selection guide
The selection of a current transformer is a simple task. There are four phases in the selection procedure. Current transformer selection guide KEEP IN MIND efine customer requirements based on the primary
More informationUFES Active protection for switchgear
Active protection for switchgear ABB AG Oberhausener Strasse 4047 Ratingen, Germany Phone: +49 0-0 Fax: +49 0-7 77 Note: We reserve the right to make technical changes or modify the contents of this document
More informationLinear Luminaire for Fluorescent Lamps Series EXLUX 6001
> As wall, ceiling and pendant light fitting or side entry lamp > Version with 2 lamps: 18 W, 36 W and 58 W > Central locking > All-pole disconnection by means of an N/C switch when the lamp is opened
More informationPluggable interface relays CR-P Pcb relays
2CDC 293 034 F0004 1 2 4 3 Features 9 different supply s: DC versions: 12 V, 24 V, 48 V, 110 V AC versions: 24 V, 48 V, 110 V, 120 V, 230 V Output contacts: 1 c/o (16 A) or 2 c/o (8 A) Cadmium-free contact
More informationSocket P2RF-05-S P2RF-08-S Clip & Release Lever R99-11 nameplate for MY
Screwless Clamp Terminal Socket Screwless clamping greatly contributes to reducing wiring time. No over or under tightening of cable connection so better contact reliability is achieved. Double wiring
More informationDisturbance Recoder SPCR 8C27. Product Guide
Issued: April 1999 Status: Updated Version: C/26.04.2006 Data subject to change without notice Features Versatile digital disturbance recorder module for recording various phenomena in the electric power
More informationADS8 IP54 Direct-On-Line Starter Technical Focus. Replaces ADS7 Rated up to 9kW
ADS8 IP54 Direct-On-Line Starter Technical Focus Replaces ADS7 Rated up to 9kW New ADS8 Motor Starter The new ADS8 range of motor starters replaces the successful ADS7 range which was introduced 20 years
More informationCURRENT TRANSFORMER MODEL 546 UL1015 #16 AWG LEAD WIRE, STANDARD LENGTH IS 24" 1 X
CURRENT TRANSFORMER MODEL 546 1.10" I.D. PAGE No 1-38 REV 15DEC00 TERMINAL OPTION LEAD WIRE OPTION 1.10 0 1.20 2.55 3.00 3.47 0.18 x 0.31 SLOT ( 2 PLACES) 8-32 BRASS STUD (2 PLACES) UL1015 #16 AWG LEAD
More informationSECTION 16461 DRY-TYPE TRANSFORMERS
SECTION 16461 PART 1 - GENERAL 1.1 SECTION INCLUDES A. Furnishing and installation of and testing of cast resin dry type MV/LV distribution transformer in accordance with specifications and drawings. Any
More informationTakfan Machinery and Mould Co Ltd. Plug in Bushing. LV Monoblock. RMU Bushing. 4 Way CT Terminal. www.takfanmakina.com.tr
www.takfanmakina.com.tr Plug in Bushing LV Monoblock RMU Bushing 4 Way CT Terminal Solution Partner of Medium Voltage Insulation and Epoxy Casting Design *Medium voltage Switching Equipments Design *Load
More informationa Nexans company Catalogue 2014
a Nexans company Catalogue 2014 Nexans Network Solutions Div. Euromold COMPANY PRESENTATION EUROMOLD Euromold is the leading European specialised designer, manufacturer and distributor of prefabricated
More informationSF 6 Gas Insulated Switchgear Type SDF for 170 kv
Three Phase Encapsulated Type SF 6 Gas Insulated Switchgear Type SDF for 170 kv 06B1-E-0001 With Trustworthy Technology, Structure Fuji Electric as a manufacturer of comprehensive substation equipment
More informationNATUS NES / NES-H Draw-out Type Medium Voltage Switchgear Systems. Safe energy distribution that meets the highest industrial requirements
NATUS NES / NES-H Draw-out Type Medium Voltage Switchgear Systems Safe energy distribution that meets the highest industrial requirements NATUS switchgear systems your advantages minimal use of insulant
More informationPositive-guided relay outputs: 3 safety contacts (N/O), instantaneous. 1 auxiliary contact (N/C), instantaneous
Safety relay for monitoring E-STOP pushbuttons. Approvals Unit features Positive-guided relay outputs: 3 safety contacts (N/O), instantaneous 1 auxiliary contact (N/C), instantaneous Safe separation of
More informationMNS is Switchgear System Technical Overview
Switchgear System Technical Overview Innovative Design ABB s innovative MNS is concept combines the long term experience, energy efficiency, grid reliability and industrial productivity of the well-known
More informationTechnical catalog. Current sensors Voltage sensors
Technical catalog Current sensors Voltage sensors Current sensors Voltage sensors Technologies Current measuring technology 4 Voltage measuring technology 8 Voltage detection technology 10 Glossary 12
More informationRM4TG20 three-phase network control relay RM4-T - range 200..500 V
Characteristics three-phase network control relay RM4-T - range 200..500 V Complementary [Us] rated supply voltage Output contacts Setting accuracy of time delay Delay at power up Measuring cycle Marking
More informationR.C.C.B. s two-pole LEXIC
87045 LIMOGES Cedex Telephone : (+33) 05 55 06 87 87 Fax : (+ 33) 05 55 06 88 88 R.C.C.B. s two-pole LEXIC 089 06/09/10/11/12/15/16/17/18/ 27/28/29/30/35, CONTENTS PAGES 1. Electrical and mechanical characteristics...
More information2a. IEM Indoor Metal Clad Medium Voltage Switchgear 15KV 16346-1. 2a. Section 16346 INDOOR METAL CLAD MEDIUM VOLTAGE SWTICHGEAR (Std.
2a. IEM Indoor Metal Clad Medium Voltage Switchgear 15KV 16346-1 2a. Section 16346 INDOOR METAL CLAD MEDIUM VOLTAGE SWTICHGEAR (Std. Relays) Part 1 General 1.1 CONDITIONS AND REQUIREMENTS: A. Refer to
More informationABB s Disconnecting Circuit Breakers Higher substation availability and lower environmental impact
ABB s Disconnecting Circuit Breakers Higher substation availability and lower environmental impact Authors Carl Ejnar Sölver, ABB High Voltage Products Rasmus Larsson, ABB High Voltage Products 2 ABB ABB
More informationInstallation Contactors. Technical Catalogue. Type ESB. abb. ABB STOTZ-KONTAKT GmbH 1 2CDC 103002 C0201
Technical Catalogue Installation Contactors Type ESB abb ABB STOTZ-KONTAKT GmbH 1 CDC 10300 C001 ABB STOTZ-KONTAKT GmbH CDC 10300 C001 Low Voltage Products and Systems We ensure safety and comfort for
More informationElectronic overload relay EF19 and EF45
Data sheet Electronic overload relay EF19 and EF45 Electronic overload relays offer reliable protection in case of overload and phase-failure. They are the alternative to thermal overload relays. Motor
More informationMedium Voltage Products. ZN1 12 kv arc-proof air-insulated switchgear for primary distribution
Medium Voltage Products ZN1 12 kv arc-proof air-insulated switchgear for primary distribution ZN1 an innovative switchgear for power distribution requirements ABB ZN1 primary distribution switchgear is
More informationEGSTON Standard E2xFxWx 12W
General description The family of switchmode power supplies offers an unmatched degree of flexibility and performance fulfilling even the most stringent requirements. Highly flexible electrical configuration
More informationOutdoor Use Waterproof I/O Connectors (Optical / Modular / Electrical) FO-BH, FO-BC, NT5, JN2 / W Series
COMPONENTS PRODUCT INFORMATION RoHS Compliant NEW Outdoor Use Waterproof I/O Connectors (Optical / Modular / Electrical) FO-BH, FO-BC, NT5, JN2 / W Series Optical FO-BH Series (Compact Type) CONNECTOR
More informationPower Resistor for Mounting onto a Heatsink Thick Film Technology
DIMENSIONS in millimeters Power Resistor for Mounting onto a Heatsink Thick Film Technology FEATURES 800 W at 85 C bottom case temperature Wide resistance range: 0.3 to 900 k E24 series Non inductive Easy
More informationCT Current transformers Ideal for measuring. Designed to create efficiency.
CT Current transformers Ideal for measuring. Designed to create efficiency. CT Current transformers Optimize consumptions. Improve the efficiency. Energy efficiency, minimized costs and high system availability
More informationInstructions for Safe Use
Instructions for Safe Use (Certification N:o VTT 08 ATEX 029) Thank you for choosing Slam Trans portable transformer for your job site. Purpose of this manual is to provide you all the necessary safety
More informationMeasurement and Instrumentation
POWER QUALITY ENERGY PERFORMANCE Measurement and Instrumentation Transformers and shunts Transformers Overview of ranges Selection guide Info & advice Standard industrial transformers TCR TCRO ranges Adaptable
More informationCurrent valve. for AC 24 V pulse/pause control of electrical loads up to 30 kw
4 937 DESIO Current valve for AC 24 V pulse/pause control of electrical loads up to 30 kw SEA45.1 Use The current valve is used for the control of electric heating elements in heating, ventilation and
More informationElectronic overload relay EF65, EF96 and EF146
Data sheet Electronic overload relay EF65, EF96 and EF146 Electronic overload relays offer reliable protection in case of overload and phase-failure. They are the alternative to thermal overload relays.
More informationToroidal Conductivity Sensor
Instruction Sheet PN 51A-/rev.C June 2012 Toroidal Conductivity Sensor For additional information, please visit our website at www.emersonprocess.com/rosemountanalytical.com SPECIFICATIONS Wetted Materials:
More informationMedium Voltage Instrument Transformers
Medium Voltage Instrument Transformers Standard Transformers RITZ Instrument Transformers GmbH Core competency Under the trading name RITZ Instrument Transformers GmbH RITZ has been pooling its activities
More informationHow To Build A Low Voltage Capacitor Lvcp
Low Voltage Capacitor LVCP The new choice for Power Factor Correction LVCP : the new choice for Power Factor Correction The LVCP is a compact and powerful capacitor. It offers high modularity, unmatched
More informationELEKTROTECHNISCHE WERKE FRITZ DRIESCHER & SÖHNE GMBH D-85366 MOOSBURG TEL. +49 87 61 6 81-0 FAX +49 87 61 68 12 30
40 DRIESCHER - Low voltage fusedswitch-disconnector system 40 Rated current upto 445 A 40 84 40 40 ELEKTROTECHNISCHE WERKE FRITZ DRIESCHER & SÖHNE GMBH D-8566 MOOSBURG TEL. +49 87 6 6 8-0 FAX +49 87 6
More informationMetal Clad Indoor Instrument Transformer for Plug-In Systems
Metal Clad Indoor Instrument Transformer for Plug-In Systems RITZ Instrument Transformers GmbH Core competency Under the trading name RITZ Instrument Transformers GmbH RITZ has been pooling its activities
More informationThe complete range of consumer switchboards and switchgear
Power Distribution The complete range of consumer switchboards and switchgear www.nhp.com.au/mod6 The MOD6 range of consumer switchboards and switchgear is specifically designed for domestic and commercial
More information3/2-way Solenoid Valve, direct-acting, NC or NO
3/2-way Solenoid Valve, direct-acting, NC or NO Electrical connection cable plug, Form A With or without manual override as standard Threaded port and sub-base s Impulse optional Type 6014 can be combined
More informationContents. Document information
User Manual Contents Document information... 2 Introduction... 3 Warnings... 3 Manufacturer... 3 Description... Installation... Configuration... Troubleshooting...11 Technical data...12 Device Scope: PCB
More informationRemote Monitoring and REC 501 Control Unit Product Guide
Remote Monitoring and Control Unit REC 501 Product Guide Issued: May 1999 Status: Updated Version: B/06.11.2001 Data subject to change without notice Features Remote control and monitoring unit for the
More informationABB 1 NEW. Three-phase monitoring relay for grid feeding CM-UFS.1. Data sheet. Features. Approvals. Marks. Order data. Order data - Accessories
2CDC 251 014 F0t09 Features Monitoring of three-phase mains for grid feeding Type-tested in accordance with DIN V VDE V 0126-1-1: February 2006 Neutral conductor connection configurable Can also be used
More informationHigh-Voltage Compact Switchgear 3AP1 DTC for 145 kv and 245 kv
High-Voltage Compact Switchgear AP1 DTC for 1 kv and kv Answers for energy. The AP1 DTC Complying with our Customers demands Experience you can rely on - at anytime, anywhere Decades of experience in high-voltage
More informationTemperature monitoring relays CM-TCS Monitoring relays for monitoring temperatures with a PT100 sensor (2- or 3-wire connection)
Data sheet Temperature monitoring relays CM-TCS Monitoring relays for monitoring temperatures with a PT100 sensor (2- or 3-wire connection) The temperature monitoring relays CM-TCS monitor overtemperature,
More informationType: DILM115(RAC240) Article No.: 239548 Sales text Contactor,55kW/400V,AC operated. Ordering information
Type: DILM115(RAC240) Article No.: 239548 Sales text Contactor,55kW/400V,AC operated Ordering information Connection technique Description Description Rated operational current Screw terminals 3 pole AC
More informationTransformer Bushings for GIS
Transformer Bushings for GIS Oil to SF6 Connections GARIP RTKG 725-55 kv SQS certified ISO 91 / ISO 141 Bushings RIP - Technology for SF6 / Oil - Bushings In modern metal enclosed switchgear SF6 -gas is
More informationABB 1. Three-phase monitoring relay CM-PFS. Data sheet. Features. Approvals. Marks. Order data. Order data - Accessories. Application.
1SR 430 824 F9300 Features Monitoring of three-phase mains for phase sequence and failure Powered by the measuring circuit 2 c/o (SPDT) contacts 1 LED for status indication Approvals R: yellow LED - relay
More informationRM17TE 183...528 V AC. Main. Product or component type. Product specific application. Relay monitored parameters 250 V DC 5 A DC
Characteristics multifunction control relay RM17-TE - range 183..528 V AC Complementary Reset time Maximum switching voltage Minimum switching current Maximum switching current [Us] rated supply voltage
More informationCurrent Transformers
Tyco Electronics Corporation Crompton Instruments 1610 Cobb International Parkway, Unit #4 Kennesaw, GA 30152 Tel. 770-425-8903 Fax. 770-423-7194 Current Transformers Current transformers (CT's) provide
More informationONE OF THE SMALLEST SNAP-ACTION SWITCHES IN THE WORLD. FEATURES Superminiature type, light-weight snap action switch PC board terminal type (0.
ONE OF THE SMALLEST SNAP-ACTION SWITCHES IN THE WORLD SWITCHES FEATURES Superminiature type, light-weight snap action switch PC board terminal type (0.2g) Solder terminal type with mounting holes (0.3g)
More informationMEDIUM AND HIGH VOLTAGE CAPACITORS, CAPACITOR BANKS AND SYSTEMS
MEDIUM AND HIGH VOLTAGE CAPACITORS, CAPACITOR BANKS AND SYSTEMS Meher Capacitors offers reliable and innovative products and solutions in the fields of Reactive Power Compensation, Power Quality and Energy
More informationCurrent Monitoring Kit
Current Monitoring Kit QUICK START GUIDE DO090-6 CONTENTS Issues: 1) 2.10.02 WP A4 format 2) 2.10.02 Added safety warning 3) 17.3.06 Word A5 format. S1: Removed relay modules. S2: Added MI010. S4.1: added
More informationA project to optimise quality and energy efficiency must include metering
EMDX 3 : Energy Metering A project to optimise quality and energy efficiency must include metering Metering upstream identifies the critical points and ensures optimum targeting of the actions to be taken,
More informationModular Systems, PPMV, 2014 UniPack-G Glass Fiber Reinforced Polyester Compact Secondary Substation
Modular Systems, PPMV, 2014 UniPack-G Glass Fiber Reinforced Polyester Compact Secondary Substation Index News Introduction Applications & Segments Main Components Applicable Standards Technical characteristics
More informationTerminal Boxes Series 8146
Series > Enclosures in shock-resistant glass fibre reinforced polyester resin > basic enclosure sizes various heights > Fitted according to the customer's requirements > For terminals up to max. 00 mm
More informationDirectory chapter 04
M Directory chapter 04 D-Sub Mixed subminiature D connectors New Page D-Sub mixed connector system general information................... 04.02 Contact arrangements............................................
More informationLinear Luminaire with LED Series EXLUX 6402/2
> Latest LED technology with a high luminous efficacy and a long service life > As pendant light fitting or side entry lamp > Central locking > All-pole disconnection by means of an N/C switch when the
More informationContact expansion modules
Gertebild ][Bildunterschrift Kontakterweiterungen Contact for increasing the number of available contacts Approvals Zulassungen Unit features Gertemerkmale Positive-guided relay outputs: 4 safety contacts
More informatione 2 ALPHA Medium Voltage Switchgear Data Sheet K-1.1.2 EN
e 2 ALPHA Medium Voltage Switchgear Data Sheet K-1.1.2 EN We create ideas with power! ELEKTROMETAL ENERGETYKA SA is a new Polish company providing solutions for electrical power engineering. Our services
More informationCABLE ACCESSORIES 110-220 kv
CABLE ACCESSORIES 110-220 kv Termination 110 kv Technical description Termination MKB 126 / 145 with composite type insulator uses for cable line joints with other elements of power-supply systems. Termination
More informationHEAT MONITORING AND CONTROL INSTRUMENTS FOR TRANSFORMERS MB 103 TEMPERATURE CONTROL UNIT PT 100 TEMPERATURE SENSOR
HEAT MONITORING AND CONTROL INSTRUMENTS FOR TRANSFORMERS MB 103 TEMPERATURE CONTROL UNIT PT 100 TEMPERATURE SENSOR 2 MB 103 TRANSFORMER TEMPERATURE CONTROL UNIT WITH CONTROL SIGNAL Recent approval of new
More informationNF71E-.. / NFZ71E-.. Contactor Relays AC / DC Operated - with Screw Terminals
Technical Datasheet 1SBC101433D0201 28/03/11 NF71E-.. / NFZ71E-.. Contactor Relays AC / DC Operated - with Screw Terminals NF(Z) contactor relays are used for switching auxiliary and control circuits.
More information