1 Washington Headquarters Services Facilities Services Directorate The Pentagon Electric Upgrade (Substation No. 2) Concept Design Synopsis September 4, 2014 Prepared for Consultations with VA SHPO, ACHP, CFA, NCPC Revised September 4, 2014
2 Table of Contents Project Information Page 1 Reason for Action Page 1 Narrative Description of the Project Page 1 Development Area and Construction Page 2 Project Execution Page 2 Project Schedule Page 3 Floodplain Management Page 3 Environmental Assessment Page 3 Transportation Impact Page 3 Candidate Project Locations Page 4 Aerial View of Proposed Locations Page 5 Location 1 Page 6 Location 2 Page 7 Location 3 Page 8 Architectural Design Page 9 Key Plan Page 10 Facility Site Plan Page 10 Initial Design Page 11 Proposed Design Page 12 North Elevation of Proposed Design Page 13 Aerial View of Proposed Design Page 14 Pentagon Electric Upgrade: Concept Design Synopsis (Revised September 4, 2014)
3 Project Information Job Title: Issuing Agency: End Users: Pentagon Electric Upgrade Washington Headquarters Services Washington Headquarters Services Dominion Virginia Power Agency Project Manager Contact Information Point of Contact: Ben Borns, Project Manager Construction Management WHS Facilities Services Directorate 300 Boundary Channel Drive Arlington, VA Phone: Mobile: Reason for Action: Department of Defense studies have examined the Pentagon Reservation s electrical systems and recommended a strategic plan to enhance these systems to support specific Pentagon mission. These studies determined that the existing electrical system does not provide the level of reliability needed for the Pentagon Reservation and recommended a second power distribution source (substation) to improve power availability and reliability on the Pentagon Reservation under normal and emergency conditions. Narrative Description of the Project: This project will provide a second electrical utility power distribution source for the Pentagon Reservation. The facility will be designed in accordance with the Department of Defense Unified Facilities Criteria, the Washington Headquarters Services Building Code including the Virginia Uniform Statewide Building Code and the International Building Code, National Fire Protection Association Life Safety Code and National Electrical Code. Pentagon Electric Upgrade: Concept Design Synopsis (Revised September 4, 2014) Page 1 of 14
4 Development Area and Construction: This project will construct a new 9,000 square foot substation enclosure adjacent to Corridor 8 Pedestrian Bridge and is set, partially, in a grassy hill inside the North Secure Parking Lot zone. To accommodate major electrical equipment, the substation enclosure will be approximately 45 feet deep, 196 feet wide, and 26 feet high. The substation enclosure will house 69,000 Volt utility supply feeders, a 25 megawatt (MW) transformer, 13,000 Volt switchgear, and electrical service distribution to the Pentagon and ancillary facilities on the Pentagon Reservation. Supporting work includes excavation, site utilities (rerouting existing and installing new), replacement of existing pavements, sidewalks, and curbs and gutters disturbed by construction of the substation; and site improvements to include greening and blending with surrounding architecture. Project Execution: The project will be executed in two parts. Part 1 will be accomplished through Design-Build effort. The Design-Build Contractor will design and install the (1) medium and high voltage substation enclosure facility, (2) 69,000 Volt isolation switchgear, (3) 69,000 Volt transformer, (4) 13,800 Volt switchgear, (5) 13,800 Volt underground ducts to the 13.8 kv switchgear, and (6) downstream distribution to the Pentagon Reservation. Part 2 will be accomplished by Dominion Virginia Power (DVP), the local electrical utility provider. DVP will design and install the 69,000 Volt transmission lines and the 69,000 Volt switchgear. Pentagon Electric Upgrade: Concept Design Synopsis (Revised September 4, 2014) Page 2 of 14
5 Project Schedule: 1. Conceptual design is currently ongoing, and is rapidly advancing. Candidate project locations (3 each) and respective site constraints are addressed on pages 4, 5, 6, 7 and Electrical equipment design is complete to overcome long lead procurement. 3. Pre-construction Activity scheduled for September 2014: Foundation design will be sufficiently advanced mid August 2014 for the construction mobilization, site surveys, and additional geotechnical explorations. 4. Construction Start: Fall Projected Construction Completion: Summer Floodplain Management and Wetlands Protection: The critical infrastructure project is not located in 100 or 500 Year FEMA Flood Zones. The Pentagon Coastal Resource Protection Area is not affected by the project. National Environmental Policy Act (NEPA) and Section 106 Status: The 2014 Pentagon Reservation Master Plan Environmental Assessment public review took place (Aug. 01-Aug ) and the Pentagon Electric Upgrade project was included in the Pentagon Reservation Master Plan Environmental Assessment. The Department of Defense anticipates concluding the Pentagon Master Plan NEPA process late September Due to project schedule and funding limitations, the project is currently going through a separate and parallel Section 106 consultation from the Pentagon Master Plan, which is under ongoing Section 106 Consultation. Transportation Impact: Temporary minimal impact will exist only at North Secure Parking past the vehicular bridge crossing the relocated Rt Impact will cease upon construction completion. Pentagon Electric Upgrade: Concept Design Synopsis (Revised September 4, 2014) Page 3 of 14
6 Candidate Project Locations: A great deal of thought went into massing, locating, and structurally configuring this mission critical facility on Pentagon Reservation to best serve the Pentagon under normal and emergency conditions. Only Location 1 is outside the FEMA 500 Year Flood Zone. Locations 2 and 3 are within the FEMA 500 Year Flood Zone. Location 1: Is set inside the steep long hilly section along the River Terrace access road leading to executive parking at River Terrace. (See Page 6.) This is the most desired location for the new mission critical electrical facility as determined by comprehensive analysis of site constraints ranging from structural (interference with existing spread footings and pile foundations) to interference and varied debts and sizes of major underground utilities. Location 1 is set in fully secured area controlled by the Pentagon Force Protection Agency (PFPA). Location 1 has the least number of such interferences when compared with Locations 2 and 3. The initial decision was to align the substation enclosure with the Pentagon. WHS recently departed from this idea after mapping a 3,000-SF underground vault (built in the forties) which protrudes into the substation s footprint and hereby prevents us from rotating the building to make it parallel with the Pentagon. Location 2: Is set inside a curved hill adjacent to, and following the alignment of, the structured North Parking Pedestrian Ramp that connects to the Pentagon s Corridor 8 Bridge/Entrance. (See page 7.) Location 2 is not constructible due to the size of the new electrical substation and severe structural conflicts with the pedestrian ramp s foundation system and nearby underground utilities running parallel to the proposed facility footprint. Moving the facility away from the pedestrian ramp into the parking zone to avoid structural conflicts with the pedestrian ramp foundation system would create a severe conflict with major underground utilities inside the parking zone. The substation s pile foundation would end up directly over major utilities which is technically not permissible due to constraining their accessibility and maintaining mandated horizontal and vertical clearances. Location 3: Is set inside the abandoned Child Development Center (CDC). (See page 8.) Based on the UFC and PFPArefined Design Basis Threat (DBT) for this type of facility, and its close proximity to the rerouted Rt. 110, Location 3 poses high security threat to the new facility. Secondly, bringing in the pressurized 69,000 Volt and 13,800 Volt lines is virtually impossible through the maze of major underground utilities and do so over such a long distance, especially on a diagonal. Pentagon Electric Upgrade: Concept Design Synopsis (Revised September 4, 2014) Page 4 of 14
7 Aerial View of Candidate Locations 1, 2, and 3 Pentagon Electric Upgrade: Concept Design Synopsis (Revised September 4, 2014) Page 5 of 14
8 Architectural Design The initial design did not capture the character of the historic Pentagon and its surroundings. Its simplistic design is in direct contrast with the iconic image of the Pentagon, overwhelming the entire site with its prevalent industrial appearance. (See Page 11.) Revised Design: Upon WHS/ECM s consultations with VA SHPO, ACHP, CFA, and NCPC, ECM evaluated the input provided by all four agencies and revised the initial design to the extent our budgetary, structural, governing safety and security criteria allow. The Pentagon is a designated National Historic Landmark. The project is located on the boundary between Zone 3A and Zone 4 of the Pentagon Reservation Exterior Standards Manual. The primary purpose of the manual is to provide clarity as to how to preserve the Pentagon historic elements protected by the National Historic Preservation Act and its implementing regulations. Substantial effort went into the architectural redesign of the facility. Due to budgetary restrictions, the Zone 4 standards were followed, with cast-in place concrete selected for the exterior walls finish with a color complimenting the Pentagon limestone and historic concrete elements of the Corridor 8 Bridge. EAD s architect relocated all employee entrances to both sides of the building and articulated the painted metal double doors with rail and stile details to improve the appearance of the front elevation and add Pentagon building details. He also articulated the façade with base, cornice and column reveals and added door trim and keystones to the painted metal rollup doors. This gives the facility a balanced and understated architectural appearance and a departure from the initial strong industrial concept. (See Page 12.) The enclosure roof will be a slate gray fiberglass (3 X 1 X 1 ) grid which will screen the enclosed substation equipment from the Pentagon offices above. Pentagon Electric Upgrade: Concept Design Synopsis (Revised September 4, 2014) Page 9 of 14
9 Initial Design Artist Rendering Pentagon Electric Upgrade: Concept Design Synopsis (Revised September 4, 2014) Page 11 of 14
10 Proposed Design Artist Rendering Pentagon Electric Upgrade: Concept Design Synopsis (Revised September 4, 2014) Page 12 of 14
11 North Elevation of Proposed Design SUBSTATION No. 2 SUBSTATION No. 2 Pentagon Electric Upgrade: Concept Design Synopsis (Revised September 4, 2014) Page 13 of 14
12 Aerial View of Proposed Design Pentagon Electric Upgrade: Concept Design Synopsis (Revised September 4, 2014) Page 14 of 14
PART II SCHEDULE. Scope of Services. Special Terms and Conditions. Virginia Railway Express
PART II SCHEDULE SECTION TITLE D E Scope of Services Special Terms and Conditions 11 SECTION D SCOPE OF SERVICES D.1 OVERVIEW A. The selected firm is referred to herein as either the Consultant or the
More informationAlternatives Presentation Meeting Middlebury WCRS(23)
Alternatives Presentation Meeting Middlebury WCRS(23) Main Street (VT 30/TH 2 Bridge 102) and Merchants Row (TH 8 Bridge 2) over Vermont Railway June 4, 2013 Twilight Hall Auditorium, Middlebury College
More informationThe total estimated PFC revenue for the application is $266,900,000. The estimated charge effective date for this application is December 1, 2016.
Public Notice of Application for Authority to Impose and Use Passenger Facility Charges (PFCs) at EWR, LGA, JFK and SWF and Amendment to Approved PFC Applications at EWR, LGA, and JFK The Port Authority
More informationPresentation: Proposed Plan Amendments
Epstein s Rehabilitation Plan Presentation: Proposed Plan Amendments MORRISTOWN REDEVELOPMENT ENTITY March 14, 2013 Epstein s Rehabilitation Plan Presentation Part 1: Morristown Planning Division Neighborhood
More informationCONSOLIDATED EDISON CO. OF NEW YORK, INC. 4 IRVING PLACE NEW YORK, NY 10003 DISTRIBUTION ENGINEERING DEPARTMENT SUBSTATION & EQUIPMENT SECTION
CONSOLIDATED EDISON CO. OF NEW YORK, INC. 4 IRVING PLACE NEW YORK, NY 10003 DISTRIBUTION ENGINEERING DEPARTMENT SUBSTATION & EQUIPMENT SECTION SPECIFICATION EO-5023 REVISION 3 MARCH 2003 REQUIREMENTS FOR
More informationSCHEMATIC AND PROJECT BUDGET APPROVAL EAST CAMPUS NURSING EDUCATION AND CLASSROOM
Shepherd University Board of Governors June 9, 2005 Agenda Item No. 9 SCHEMATIC AND PROJECT BUDGET APPROVAL EAST CAMPUS NURSING EDUCATION AND CLASSROOM In 1994 construction began on the Byrd Science and
More informationNational Archives and Record Administration
National Archives and Record Administration Installation of Self-Closing Flood Barriers and Loading Dock Turntable Removal and Structural Slab Repairs ! 2010 Baltimore Washington Chapter Outstanding Repair
More informationCity of Colleyville Community Development Department. Site/Landscape Plan Application Packet
City of Colleyville Community Development Department Site/Landscape Plan Application Packet Development Application Fees City of Colleyville 100 Main Street Colleyville TX 76034 817.503.1050 Zoning Zoning
More informationDoes your new building
Does your new building need electricity? To save you time and money, talk to us early about your power supply. Our equipment will occupy ground space on your property. You need to consider the size and
More informationENCROACHMENTS INTO THE PUBLIC RIGHT-OF-WAY
CHAPTER 32 ENCROACHMENTS INTO THE PUBLIC RIGHT-OF-WAY SECTION BC 3201 GENERAL 3201.1 Scope. The provisions of this chapter shall govern the encroachment of structures into the public right-of-way. 3201.1.1
More informationElectrical. This section applies to the design and installation of building power distribution systems.
Basis of Design This section applies to the design and installation of building power distribution systems. Design Criteria This section contains the architectural, structural and mechanical provisions
More informationIndustrial Suburban District Regulations City of St. Petersburg City Code Chapter 16, Land Development Regulations
16.20.110 - Industrial Suburban District ( IS ) Figure REFERENCE Typical Buildings in the IS District Figure REFERENCE Site Plan of a typical development in the IS District Sections: 16.20.110.1 Composition
More information3.1 Historical Considerations
3. Recommended Scope of Bridge improvements 3.1 Historical Considerations In the fall of 2000, an outside consultant, Fraser Design, suggested that the existing 4 th St. Bridge is potentially eligible
More informationExecutive Director s Recommendation Commission Meeting: March 5, 2015
Executive Director s Recommendation Commission Meeting: March 5, 2015 PROJECT Curseen-Morris Processing and Distribution Center Parking Lot 900 Brentwood Avenue NE Washington, DC SUBMITTED BY United States
More informationEXISTING MASONRY WALL TO REMAIN (TYP.). EXISTING PARTITION TO REMAIN PROVIDE 3'-3" W. X 8'-0"H. NEW PELLA WINDOWS AS INDICATED ON PLANS. (TYP.
EXISTING MASONRY WALL TO REMAIN N EXISTING MASONRY WALL TO REMAIN (TYP.). PROVIDE COPPER THROUGH-WALL FLASHING DN EXISTING MASONRY PARTY CHIMNEY AND WALL TO REMAIN (TYP.). EXISTING MASONRY PARTY WALL TO
More informationCh a p t e r 5. Bridges Decks and Boardwalks
05 Ch a p t e r 5 Park Structures Bridges Decks and Boardwalks Intentionally Blank Br i d g e s Chapter 5: Park Structures Pu r p o s e Bridges shall facilitate safe access across bodies of water, unstable
More informationSECTION 02100 SITE PREPARATION
SECTION 02100 SITE PREPARATION PART 1 - GENERAL 1.01 RELATED DOCUMENTS A. Drawings and General Provisions of Contract, including General Conditions and Supplementary Conditions and Division 1 through Division
More informationPreliminary Plan Application and Checklist
ALL APPLICATIONS ARE DUE AT 12:00 NOON ON THE FILING DATE Office Use Only PRELIMINARY / REVISED PRELIMINARY PLAN $300.00 Fee Paid: $ Date Paid: ALL FIELDS HIGHLIGHTED IN RED ARE REQUIRED FIELDS Case No.:
More informationEngineering Standard
Public Transport Services Engineering Standard Stations - Bicycle Facilities PART 129013 AR-PW-PM-SPE-00129013 (D073) Document Control Document Status Document Amendment Record Revision Change Description
More informationDESIGN REVIEW CHECKLIST Chapter 6 Special Consideration Design Guidelines
DESIGN REVIEW CHECKLIST Chapter 6 Special Consideration Design Guidelines A. Offices a. Office buildings should be built to the minimum required setback. b. Surface parking should be located towards the
More informationREQUIREMENTS AND SPECIFICATIONS FOR HIGH VOLTAGE CUSTOMER BUILT FACILITIES PEPCO ENGINEERING
REQUIREMENTS AND SPECIFICATIONS FOR HIGH VOLTAGE CUSTOMER BUILT FACILITIES PEPCO ENGINEERING Revised October, 2013 TABLE OF CONTENTS 1.0 INTRODUCTION... 3 2.0 REQUIRED DRAWINGS... 3 2.1 Site Plan... 3
More informationArchitectural Design Standards Example Guide DESIGN STANDARDS EXAMPLE GUIDE
Architectural Design Standards Example Guide DESIGN STANDARDS EXAMPLE GUIDE Commercial, Professional Office, and Public Facility Developments Purpose This Guide offers examples to clarify and explain the
More information28.0 Development Permit Area #2 (Neighbourhood District)
28.0 Development Permit Area #2 (Neighbourhood District) Goals and Objectives To provide a guide for infill and new development in the Neighbourhood District. To outline the nature, form and character
More informationTHE ROYAL BOROUGH OF KENSINGTON AND CHELSEA PLANNING APPLICATIONS COMMITTEE 16/06/2015
THE ROYAL BOROUGH OF KENSINGTON AND CHELSEA PLANNING APPLICATIONS COMMITTEE 16/06/2015 REPORT BY THE EXECUTIVE DIRECTOR, PLANNING AND BOROUGH DEVELOPMENT Application: /PP/15/02000 Agenda Item: N34 Address:
More informationDistribution Substation Manual (DSM) Section I - Introduction
(DSM) Section I - Introduction March 2007 Document release information Client Project name Western Power Distribution Substation Manual Document number 3463019 Document title Revision status Introduction
More informationData Center:Build-to-Suit
Data Center:Build-to-Suit A fortified 100,000 SqFt mission critical build-to-suit constructed on a secured 5 acre parcel at Innovation Park Charlotte, NC On-Site 120MW Substation Sourced from Two Independent
More informationBLOCK 400 PLANNED COMMUNITY DISTRICT
BLOCK 400 PLANNED COMMUNITY DISTRICT Newport Center December 1983 Newport Beach, California Ordinance 88-119 Adopted December 12, 1988 Amendment No. 672 Resolution No. 95-115 Adopted October 9, 1995 Amendment
More information5 ALTERNATIVE SOLUTIONS AND EVALUATION
Page 23 5 ALTERNATIVE SOLUTIONS AND EVALUATION The process used for the assessment and evaluation of the alternatives follows the procedures of the Municipal Class EA, as described below: Identify a reasonable
More informationAPPENDIX C INLETS. The application and types of storm drainage inlets are presented in detail in this Appendix.
Storm Drainage 13-C-1 APPENDIX C INLETS 1.0 Introduction The application and types of storm drainage inlets are presented in detail in this Appendix. 2.0 Inlet Locations Inlets are required at locations
More informationWholesale Data Center Suites Available Now
Wholesale Data Center Suites Available Now FROM 2,500 to 100,000 Sq Ft A secure, fortified Mission Critical data center facility located in Innovation Park, Charlotte, NC Scalable data center suites available
More informationN O W A V A I L A B L E
N O W A V A I L A B L E 5 0, 0 0 0 S F P O W E R E D S H E L L D A T A C E N T E R I I Data Center Park Catawba County, North Carolina S P E C I F I C A T I O N S Contact Doug Hollidge for more information
More informationLease Information Package
Lease Information Package Jefferson School Community Partnership, LLLP P.O. Box 19 Charlottesville, VA 22902 Contact: Jennifer Hines Arrington Project Manager Stonehaus, LLC (434) 974-7588 jarrington@stonehaus.net
More informationCITY OF YORBA LINDA P.O. BOX 87014 CALIFORNIA 92885-8714
CITY OF YORBA LINDA P.O. BOX 87014 CALIFORNIA 92885-8714 BUILDING DIVISION (714) 961-7120 Single Family Residential New Construction, Additions & Alterations Submittal Requirements Required agency approvals
More informationMANAGEMENT PLAN STONE BAY RIFLE RANGE HISTORIC DISTRICT MCB CAMP LEJEUNE
MANAGEMENT PLAN STONE BAY RIFLE RANGE HISTORIC DISTRICT MCB CAMP LEJEUNE This management plan is to be used in association with procedures outlined in Chapter of the Historic Buildings Management Handbook.
More informationLOUISVILLE FIRE PROTECTION DISTRICT 895 West Via Appia, Louisville, Colorado 80027 303-666-8809
LOUISVILLE FIRE PROTECTION DISTRICT 895 West Via Appia, Louisville, Colorado 80027 303-666-8809 Contractor s Checklist and Installation Guide TABLE OF CONTENTS Fire Protection Narrative........... 3 Fire
More information3 Tappan Zee Bridge Rehabilitation Options
3 Tappan Zee Bridge Rehabilitation Options 3.1 Introduction This chapter describes possible options that rehabilitate and enhance the existing Tappan Zee Bridge. Four Rehabilitation Options have been developed:
More informationFriends Seminary Presentation to NYC Landmarks Preservation Commission 21 April 2015 Kliment Halsband Architects
Presentation to NYC Landmarks Preservation Commission 21 April 2015 Kliment Halsband Architects FRIENDS SEMINARY RE-DEVELOPMENT PROJECT NYC LPC SUBMISSION 16 APRIL 2015 INDEX 1 Project Description 2 Stuyvesant
More informationCITY OF VAUGHAN SCHEDULE O LOT GRADING DESIGN FOR RESIDENTIAL DEVELOPMENT
Page 1 CITY OF VAUGHAN SCHEDULE O LOT GRADING DESIGN FOR RESIDENTIAL DEVELOPMENT CIVIC CENTRE 2141 MAJOR MACKENZIE DRIVE MAPLE ONTARIO L6A 1T1 905-832-2281 Page 2 SECTION 1 - GENERAL OBJECTIVES To provide
More informationGuidelines for Fiber Optic Cable Permits
Guidelines for Fiber Optic Cable Permits NOVA District (Fairfax/Arlington) Permits www.virginiadot.org/business/fairfax-permits-main.asp Email: NOVAFairfaxPermits@VDOT.Virginia.gov 14685 Avion Parkway
More informationNORWALK LA MIRADA UNIFIED SCHOOL DISTRICT Measure S Program Construction Management Progress Report For Citizens Oversight Committee Fall Quarter 2008
NORWALK LA MIRADA UNIFIED SCHOOL DISTRICT Measure S Program Construction Management Progress Report For Citizens Oversight Committee Fall Quarter 2008 PROGRAM AND CONSTRUCTION MANAGER SEPTEMBER 30, 2008
More informationThe City of Basehor, Kansas
The City of Basehor, Kansas Residential and Miscellaneous Permits This list provides general information regarding permit requirements for various residential construction and maintenance activities. The
More informationENTRY FORM. DVASE 2013 Excellence in Structural Engineering Awards Program
ENTRY FORM DVASE 2013 Excellence in Structural Engineering Awards Program PROJECT CATEGORY (check one): Buildings under $2M Buildings Over $100M Buildings $2M-$10M Other Structures Under $5M Buildings
More informationOccupancy: Assembly (A-3) and Business -Includes offices, seminar rooms, classrooms, and café facility. Duke University Medical School
Introduction Background The Duke School of Nursing building offers a new three-story state of the art facility that has helped strengthen the quality and integrity of the School of Nursing at Duke. The
More informationElectric Engineering Division FIBER CONDUIT RULES AND REGULATIONS
Electric Engineering Division FIBER CONDUIT RULES AND REGULATIONS TABLE OF CONTENTS I. RULES AND REGULATIONS A. TABLE OF CONTENTS... 2 B. TERMS AND DEFINITIONS... 3 C. DEVELOPER S/CONTRACTOR S RESPONSIBILITIES...
More informationDesigner s NOTEBOOK DESIGN ECONOMY, PART 3
Designer s NOTEBOOK DESIGN ECONOMY, PART 3 Design Economy Article XII (Part 3) PCI s Architectural Precast Concrete Services Committee offers insight on the architectural precast manufacturing process
More informationEvanston Main Street Station TOD Plan and Study. Appendix A.1: Station Area Existing Conditions
Evanston Main Street Station TOD Plan and Study Appendix A.1: Station Area Existing Conditions EvanstonMainStreetStation TODPlanandStudy A 1 AppendixA.1: ExistingConditions Table of Contents Station Locations
More informationDESCRIPTION OF WORK:
DEPARTMENT OF PUBLIC WORKS COUNTY OF HENRICO P.O. BOX 27032 RICHMOND, VIRGINIA 23273 PERMIT NO. One (1) copy of application and four (4) copies of plans are hereby made to the Director of Public Works
More informationHow To Protect A Swimming Pool
County of Gloucester Codes Compliance Building Department Building Three P. O. Box 329 Gloucester, Virginia 23061 Building Code Guidelines Residential Swimming Pools & Spas KEEP YOUR POOL SAFE CODE REQUIREMENTS
More informationOPERATOR - FACILITY ADDRESS - DATE
. Facility Criteria (RFP).0 Location Characteristics Criteria Requirements 1 Ownership and Management: Please identify the owner(s) and managers of the property and indicate if there is on-site management.
More informationFLOOD DAMAGE PREVENTION ORDINANCE
FLOOD DAMAGE PREVENTION ORDINANCE SECTION 1.0 STATUTORY AUTHORIZATION, FINDINGS FO FACT, PURPOSE, AND OBJECTIVES 1.1 STATUTORY AUTHORIZATION The Legislature of the State of Washington has in RCW delegated
More informationDigital Billboard Code Amendment Update City Council Economic Development Committee April 4, 2011
Digital Billboard Code Amendment Update City Council Economic Development Committee April 4, 2011 Department of Development Services Background On April 14, 2010, Clear Channel Outdoor submitted a request
More informationCITY COUNCIL PACKET MEMORANDUM
CITY COUNCIL PACKET MEMORANDUM DOCUMENT: Final Plan and Final Plat SUBJECT: City Center Lenexa The Domain at City Center CONTACT PERSON: Beccy Yocham, Director of Community Development DATE: December 3,
More informationDESIGN GUIDELINES FOR UTILITY METERS D.C. HISTORIC PRESERVATION REVIEW BOARD
DESIGN GUIDELINES FOR UTILITY METERS D.C. HISTORIC PRESERVATION REVIEW BOARD Introduction Utility meters are a necessary component for any building. When older buildings were originally provided with utility
More informationFriday, March 9, 2012 1800 Grant Street, 1st Floor conference room
Office of the Vice President for Finance 1800 Grant Street, Suite 800 Denver, Colorado 80203 (303) 860-5600 Fax: (303) 860-5640 University of Colorado Design Review Board Minutes Friday, March 9, 2012
More informationFinding of No Significant Impact
Finding of No Significant Impact PROPOSED CONSTRUCTION AND OPERATION OF OPERATIONAL READINESS TRAINING COMPLEX FORT HUNTER LIGGETT, MONTEREY COUNTY, CALIFORNIA Pursuant to the Council on Environmental
More informationEngineering Department
Engineering Department Site Plan Review Application 1025 31st St SE PO Box 5006 Minot, ND 58702 engineers@minotnd.org (701) 857-4100 Contact Information Developer/Property Owner Address City State Zip
More informationCHECKLIST FOR DC SUBMISSION - CONVENTIONAL HOUSING DEVELOPMENT WITH OPEN SPACE PROVISION
1 General NPARKS-0-DCS03 CHECKLIST FOR DC SUBMISSION - CONVENTIONAL HOUSING (a) The following plans are provided: Key and location plans of scale 1 : 10,000 or 1 : 5,000 showing access to the site from
More informationSUP07-6: Shenandoah Waste Services, LLC Special Use Permit Application for A Materials Recovery Center in a M1 (Industrial) Zoning District
SUP07-6: Special Use Permit Application for A Materials Recovery Center in a M1 (Industrial) Zoning District Location and Proposed Use The subject 33.76 acre parcel (Tax Map # 42A5 (A) 79) is located on
More informationCity of Wichita, Kansas Americans with Disabilities Act Transition Plan Main Library Address
City of Wichita, Kansas Americans with Disabilities Act Transition Plan Main Library Address July 005 Prepared by DMCG Disability Management Consulting Group L.L.C. 801 Jonquil Place Columbia, MO 650 In
More informationSAN DIEGO GAS & ELECTRIC COMPANY SOUTH BAY SUBSTATION RELOCATION PROJECT TRAFFIC MANAGEMENT PLAN SEPTEMBER 2014
SAN DIEGO GAS & ELECTRIC COMPANY SOUTH BAY SUBSTATION RELOCATION PROJECT TRAFFIC MANAGEMENT PLAN SEPTEMBER 2014 Traffic Management Plan TABLE OF CONTENTS 1 INTRODUCTION... 1 2 OBJECTIVES... 1 3 APPLICABLE
More informationD Sample Notices to Property Owners, Sample Affidavits, and Other Material
D Sample Notices to Property Owners, Sample Affidavits, and Other Material These samples are offered to illustrate specific points in the Desk Reference. States and communities should examine them carefully
More informationPROJECT COST ESTIMATE ASSUMPTIONS AND EXCLUSIONS
C PROJECT ESTIMATE ASSUMPTIONS AND EXCLUSIONS In support of the alternatives development process, preliminary cost estimates were prepared for each of the three Candidate Build Alternatives. The cost estimates
More informationBASSETT CREEK VALLEY MASTER PLAN OPEN HOUSE
BASSETT CREEK VALLEY MASTER PLAN OPEN HOUSE February 23, 2006 PROJECT INTRODUCTION Project Area 230 acres $50 million estimated market value (approximately) 50 acres parkland 100 residences (estimated)
More informationAGENCY COORDINATION AND PUBLIC INVOLVEMENT
5 AGENCY COORDINATION AND PUBLIC INVOLVEMENT 5.1 AGENCY COORDINATION As part of the planning process for the Oregon Avenue Final EA, DDOT conducted an agency coordination program. This coordination included
More informationLand Disturbance, Erosion Control and Stormwater Management Checklist. Walworth County Land Conservation Department
Land Disturbance, Erosion Control and Stormwater Management Checklist Walworth County Land Conservation Department The following checklist is designed to assist the applicant in complying with the Walworth
More informationPLANNING DIVISION STAFF REPORT February 23, 2015. Summary. Background Information PREPARED FOR THE PLAN COMMISSION. Legistar File ID # 36810
PLANNING DIVISION STAFF REPORT PREPARED FOR THE PLAN COMMISSION Project Address: Application Type: Legistar File ID # 36810 Prepared By: Summary Conditional Use Timothy M. Parks, Planning Division Report
More informationErection of replacement warehouse building and erection of two buildings in connection with builder s merchants
Plan: O 02/00708/FUL Thames Ward (A) Address: Development: Applicant: London Works, Ripple Road, Barking Erection of replacement warehouse building and erection of two buildings in connection with builder
More informationSite Development Information Worksheet for single family residential development
Site Development Information Worksheet for single family residential development Project description: Address: Owner Name: Phone No. Date Signature & phone number of Individual who Completed this Worksheet
More informationFast Track A Successful Redevelopment: The Palm Beach Outlets Story
Fast Track A Successful Redevelopment: The Palm Beach Outlets Story SPEAKERS Rick Greene, AICP City of West Palm Beach Brian Seymour, Esq. Gunster Ken Tuma, PE UDKS Josh Long, AICP Gunster Grand Opening
More informationInformational Workshop Public Meeting Kanawha Falls Bridge Project
Informational Workshop Public Meeting Kanawha Falls Project WV Department of Transportation Division of Highways in Cooperation with the Federal Highway Administration State Project S310-13-0.02 00 Federal
More informationGuidance Note on the Need for Planning Permission for the Development of Existing Houses and Flats (effective from 6 February 2012)
de Guidance Note on the Need for Planning Permission for the Development of Existing Houses and Flats (effective from 6 February 2012) Introduction The rules governing permitted development (that is, whether
More informationSchematic Design: Quality Management Phase Checklist Project Phase Checklist Series
Best Practices : Project Phase Series Contributed by Micheal J. Lough, AIA, Principal, Integral Consulting The AIA collects and disseminates Best Practices as a service to AIA members without endorsement
More informationFEMA P-936 Floodproofing Non-Residential Buildings ASFPM 2013
FEMA P-936 Floodproofing Non-Residential Buildings ASFPM 2013 1.1 Floodproofing Non-Residential Buildings Design Manual (FEMA P-936) 1. Existing non-residential buildings in riverine areas subject to shallow
More informationMEDIUM VOLTAGE. Michael Mosman, PE. CCG Facilities Integration Incorporated FACILITIES INTEGRATION INCORPORATED
MEDIUM VOLTAGE ELECTRICAL SYSTEMS for DATA CENTERS Michael Mosman, PE Chief Technical Officer CCG Facilities Integration Incorporated FACILITIES INTEGRATION INCORPORATED CCG Facilities Integration Incorporated
More informationRailyard Alternatives and I-280 Boulevard Feasibility Study. Planning Commission February 6, 2014
Railyard Alternatives and I-280 Boulevard Feasibility Study Planning Commission February 6, 2014 Problem Statement Major pieces of new infrastructure are planned including: Downtown Rail Extension (DTX)
More informationREVEWED BY: Ross Rogien B.O/P.R. ADDITIONAL REVIEW(S) REQ.-FIRE DEPT Y/N
PLAN REVIEW FOR: PROJECT NAME: OWNER: ARCH/DESIGNER: ADDRESS: Ph/Fx: Plans Dated: E-mail: Sealed By: Estimated Project Cost - $ REVEWED BY: Ross Rogien B.O/P.R. ADDITIONAL REVIEW(S) REQ.-FIRE DEPT Y/N
More informationSPECIAL USE PERMIT 22-01. JCSA Groundwater Treatment Facility Staff Report for the November 5, 2001, Planning Commission Public Hearing
SPECIAL USE PERMIT 22-01. JCSA Groundwater Treatment Facility Staff Report for the November 5, 2001, Planning Commission Public Hearing This report is prepared by the James City County Planning Division
More informationENGINEERING DESIGN GUIDELINES. for SUBDIVISIONS OR COMMERCIAL DEVELOPMENTS
ENGINEERING DESIGN GUIDELINES for SUBDIVISIONS OR COMMERCIAL DEVELOPMENTS City of Birmingham Department of Planning, Engineering and Permits Engineering Division Office of the City Engineer 2008 TABLE
More informationUDRB APPLICATION URBAN DEVELOPMENT REVIEW BOARD
UDRB APPLICATION CITY OF MIAMI VISION STATEMENT: To Be an International City that Embodies Diversity, Economic Opportunity, Effective Customer Service and a Highly Rated Quality of Life OBJECTIVE: The
More informationCERTIFICATE OF APPROPRIATENESS APPLICATION INSTRUCTIONS AND CHECK LIST
Certificate of Appropriateness Instructions and Checklist (revised 1/16) SYRACUSE LANDMARK PRESERVATION BOARD CERTIFICATE OF APPROPRIATENESS APPLICATION INSTRUCTIONS AND CHECK LIST INSTRUCTIONS: Applicants
More informationN O W A V A I L A B L E
N O W A V A I L A B L E 5 0, 0 0 0 S F P O W E R E D S H E L L D A T A C E N T E R I I Data Center Park Catawba County, North Carolina Contact Doug Hollidge for more information Email: doug@five9sdigital.com
More informationTopic 2 11/28/2012 Blocks & Street Network
TOPIC 2 Blocks & Street Network Implementation Note: 1. Some recommendations are summarized in the tables herein. For complete recommendation language, please see the. 2. Recommendations referenced in
More informationElevating Your House. Introduction CHAPTER 5
CHAPTER 5 Elevating Your House Introduction One of the most common retrofitting methods is elevating a house to a required or desired Flood Protection Elevation (FPE). When a house is properly elevated,
More informationLincoln County Floodplain Development Permit Application
Lincoln County Floodplain Development Permit Application Application # FP Use Permit Variance Appeal Date SECTION I: GENERAL PROVISIONS (APPLICANT to read and sign) 1. No work of any kind may start until
More informationSafe & Sound Bridge Terminology
Safe & Sound Bridge Terminology Abutment A retaining wall supporting the ends of a bridge, and, in general, retaining or supporting the approach embankment. Approach The part of the bridge that carries
More informationMTA UNIVERSAL STATION PEDESTRIAN BRIDGE Los Angeles, CA. Project Manual and Specification 100% PE SUBMITTAL TABLE OF CONTENTS
Los Angeles, CA Project Manual and Specification DIVISION 1 GENERAL CONDITIONS 01 01 10 STATEMENT OF WORK 01 11 00 SUMMARY OF THE WORK 01 14 05 METRO (OWNER) - DIRECTED STOPPAGES 01 20 00 PRICE AND PAYMENT
More informationMicropiles Reduce Costs and Schedule for Merchant RR Bridge Rehabilitation
Micropiles Reduce Costs and Schedule for Merchant RR Bridge Rehabilitation Jeff R. Hill, P.E. Hayward Baker Inc. 111 W. Port Plaza Drive Suite 600 St. Louis, MO 63146 314-542-3040 JRHill@HaywardBaker.com
More informationI-676 (Vine Expressway) Bridge Reconstruction Project 22 nd - 18 th Streets Philadelphia, PA. PSPE Presentation, December 3, 2015
I-676 (Vine Expressway) Bridge Reconstruction Project 22 nd - 18 th Streets Philadelphia, PA PSPE Presentation, December 3, 2015 Location Map N PROJECT LOCATION 22 nd 18 th Streets PHILADELPHIA, PA General
More informationAdopted 9/23/98 CHATTAHOOCHEE CORRIDOR PLAN. The goals of the Chattahoochee Corridor Plan (hereinafter also referred to as the Plan ) are:
CHATTAHOOCHEE CORRIDOR PLAN Adopted 9/23/98 PART 1: GOALS. POLICY. COVERAGE. A. Goals The goals of the Chattahoochee Corridor Plan (hereinafter also referred to as the Plan ) are: 1. Preservation and protection
More informationElevation Certificates. Brad Loar FEMA Region IV
Elevation Certificates Brad Loar FEMA Region IV What is the purpose of the Elevation Certificate? The Elevation Certificate is an important administrative tool of the National Flood Insurance Program (NFIP).
More informationPhoto Credit: Ryan Collerd courstesy of UCD
Photo Credit: Ryan Collerd courstesy of UCD P H I L A D E L P H I A P A R K L E T P R O G R A M guidelines program overview contact motu If you are interested in applying for a parklet, contact Ariel Ben-Amos
More informationUnderground Service Requirements and Instructions
This packet includes all FKEC underground service requirements, instructions, procedures and drawings. If you are considering underground power service please review this document in its entirety (3 page
More informationNational Science Foundation. Climate Change Adaptation Plan FY 2015 FY 2018
National Science Foundation Climate Change Adaptation Plan FY 2015 FY 2018 October 30, 2015 Policy Statement The National Science Foundation (NSF) is an independent Federal agency created by the National
More informationN O T I C E REQUEST FOR STATEMENT OF QUALIFICATIONS RFQ#1610-007 POLICE DEPARTMENT PARKING GARAGE
N O T I C E REQUEST FOR STATEMENT OF QUALIFICATIONS RFQ#1610-007 POLICE DEPARTMENT PARKING GARAGE The City of Frisco is seeking qualification statements from experienced engineering, architecture, and
More information3.11 Utilities. 3.11.1 Affected Environment. 3.11.2 Environmental Consequences
3 Affected Environment and Environmental Consequences 3.11 Utilities 3.11.1 Affected Environment Sterling Highway MP 45 60 Project Draft SEIS Cooper Landing and the surrounding area are rural and do not
More informationCERTIFICATE OF APPROVAL OF LOCATION (CAL) APPLICATION Page 2
C ITY OF N EW H AVEN, CONNECTICUT NEW HAVEN CITY PLAN COMMISSION 5 th Floor PHONE 203.946.6378 165 CHURCH STREET NEW HAVEN, CONNECTICUT 06510-2010 FAX 203.946.7815 FOR CITY USE ONLY CAL Filing Type Fee
More informationDESIGN AND ACCESS STATEMENT PLANNING APPLICATION. 25 Gilston Road, SW10 9SJ June 2015
DESIGN AND ACCESS STATEMENT PLANNING APPLICATION 25 Gilston Road, SW10 9SJ June 2015 CONTENTS 1.0 INTRODUCTION 2.0 SITE & CONTEXT 2.1 SITE CONTEXT 2.2 CONSERVATION AREA 3.0 BACKGROUND 3.1 RELEVANT PLANNING
More informationREFLEC TIONS I & II AT CIRCLEPORT
ERLANGER, KENTUCKY CL ASS A OFFICE SPACE AVAIL ABLE REFLECTIONS I & II AT CIRCLEPORT OFFERS MANY ADVANTAGES: State-of-the-art fiber optics cabling designed for New Economy as well as traditional business
More informationT5 CHARLOTTE REGION WEST DATA CENTER PARK
Additional!Sites Up to 120+ MW available to site from Duke Energy Low cost reliable power - 3.9-4.6 /kilowatt hour Dual Circuit 100 KV Grid Connector Low natural disaster risk Multiple l fiber carriers
More informationYale Arts Complex. The design results from the integration of programmatic, structural and mechanical needs. It includes
New Haven, Connecticut 1 2 Yale University s Rudolph Building formerly known as the Art and Architecture Building was designed in 1963 by the modern master and then chair of the School of Architecture,
More information