Real-Time Energy Consumption Measurements in Data Centers. ASHRAE TC9.9 and The Green Grid
|
|
- Mariah Fletcher
- 8 years ago
- Views:
Transcription
1 Real-Time Energy Consumption Measurements in Data Centers ASHRAE TC9.9 and The Green Grid
2 First printing released at the ASHRAE Winter Annual Meeting, Jan 23 27, 2010 ASHRAE/TGG Real Time Energy Consumption Measurements in Data Centers. Atlanta: American Society of Heating, Refrigerating and Air Conditioning Engineers, Inc.; coauthored by The Green Grid, Beaverton, Oregon. 2
3 PURPOSE OF THE BOOK Gartner, IDC, Forrester and other analysts continue to rank Power & Cooling (energy efficiency) as the #1 concern of data center owners/operators TGG s PUE is becoming the proxy for data center energy efficiency The PUE cannot be reasonably determined if energy consumption in the data center cannot be measured EPA reports an average PUE of 2.04 (2009 data) The book is designed to Provide an overview of the state of energy consumption measurements in the data center Educate the data center owner/operator with respect to making real-time energy consumption measurements in the data center Demonstrate how to consolidate the energy consumption data into a single energy efficiency value, e.g., PUE Provide guidance with respect to determining energy efficiency in mixeduse facilities 3
4 TABLE OF CONTENTS 4 PART 1 BASICS Chapter 1 Introduction Chapter 2 How, What, & Where to Measure Chapter 3 Measurement Devices Chapter 4 Measurement Collection Systems Architecture and Software PART 2 COOLING SYSTEMS Air Measurements Chapter 5 Air Handler Units Chapter 6 Computer Room Units PART 3 COOLING SYSTEMS Hydronic Measurements Chapter 7 Pumps Chapter 8 Cooling Towers Chapter 9 Chillers Chapter 10 Heat Exchangers
5 TABLE OF CONTENTS PART 4 POWER SYSTEMS MEASUREMENTS Chapter 11 Introduction to Critical Power Distribution Chapter 12 Upstream Critical Power Distribution Chapter 13 Uninterruptible Power Supply Chapter 14 Computer Room Transformer and Power Distribution Unit PART 5 IT SYSTEMS MEASUREMENTS Chapter 15 Compute and Storage Systems Chapter 16 Networking Systems Appendix A Pumps Appendix B Chillers Appendix C Mixed-Use Facilities Appendix D Uninterruptible Power Supply Appendix E Onsite Power Generation and CCHP in Data Center Applications 5
6 KEY CONTRIBUTORS 6
7 KEY CONTRIBUTORS 7
8 PART 1 BASICS 8
9 MEASUREMENT DEVICES (Chapter 3) John Bean (APC), presenter 9
10 Part 1 Chapter 3 Sensors 3.1 Overview There are numerous attributes within the data center that require measurements Temperature Pressure Flow Rates Voltage Current Humidity Sensors come in a variety of connectivity styles: direct, analog (0 10vdc / 4 20ma) and serial communication (ModBus, BacNet, etc ) Introduce Terms: Span, Resolution, Accuracy 10
11 Part 1 Chapter 3 Sensors 3.2 Accuracy What may appear to be small inaccuracies frequently may be compounded to give very misleading data Example: Chiller with design temperature difference of 10 F Return chilled water sensor reading 1 F low Supply chilled water sensor reading 1 F high Combined error of 2 F Chiller reported capacity error of 20% 11
12 Part 1 Chapter 3 Sensors 3.3 Temperature There are several types of temperature sensors available Thermocouple dissimilar metals that produce a voltage the corresponds to junction temperature. Accuracy ± 1 to 5%. Care must be used when using hookup wire to avoid new dissimilar junctions with voltage potentials that could bias reading accuracy Thermistors semiconductor devices whose resistance varies in response to temperature change, typically are constructed of polymer or ceramic. Accuracy ± 0.1 to 2% RTD Resistance Temperature Detector, typically are wire wound or thin film devices whose resistance changes in response to an increase in temperature. Accuracy ± 0.01 to 1%. Are available in three and four wire version to compensate for lead wire resistance error All types may use a local transmitter to convert weak signal to more robust signal (0 10vdc or 4 20ma) to allow longer runs of wiring to measurement device 12
13 Part 1 Chapter 3 Sensors 3.4 Pressure There are several types of pressure sensors available Bourdon Tube Strain Gauge Compound (vacuum and positive pressure) Absolute Pressure Gauge Pressure Need to ensure wetted surface material is compatible with fluid to be measured All types may use a local transmitter to convert weak signal to more robust signal (0 10vdc or 4 20ma) to allow longer runs of wiring to measurement device 13
14 Part 1 Chapter 3 Sensors 3.5 Flow Liquid There are several types of liquid flow sensors available Paddle Wheel Turbine Wheel Shedding Vortices Venturi Ultrasonic Coriolis Variable Area Need to assure wetted surface material is compatible with fluid to be measured All types may use a local transmitter to convert weak signal to more robust signal (0 10vdc or 4 20ma) to allow longer runs of wiring to measurement device 14
15 Part 1 Chapter 3 Sensors 3.6 Flow Gas There are several types of gas flow sensors available Pitot Tube Hot Wire Anemometer Flow Nozzle Cup Anemometer All types may use a local transmitter to convert weak signal to more robust signal (0 10vdc or 4 20ma) to allow longer runs of wiring to measurement device 15
16 Part 1 Chapter 3 Sensors 3.7 Current There are several types of current sensors available Split Core Solid Core Resistor (voltage drop) Clamp-On Split Core Extra loops of conductor thru core act as current multiplier for current transformers All types may use a local transmitter to convert weak signal to more robust signal (0 10vdc or 4 20ma) to allow longer runs of wiring to measurement device 16
17 Part 1 Chapter 3 Sensors 3.8 Voltage There are several types of voltage sensors available Potential Transformer (high & medium voltage) Voltage Divider Voltage Transducer 17
18 Part 1 Chapter 3 Sensors 3.8 Power Monitor Typically use both current and voltage sensor and have necessary processing means to determine power in real time. Other common metrics from power meters may include KVA (apparent power) KVAR (reactive power) Power Factor Individual Leg Currents Individual Leg Voltages May or may not be revenue grade Typically may have local display along with serial communication interface to BMS or SCADA System 18
19 MEASUREMENT COLLECTION SYSTEMS Architecture and Software (Chapter 4) Kenneth Uhlman, Ph.D, P.E., presenter 19
20 Topics Business Questions Measurement Levels Scalable Hardware / Software Architecture 20
21 Business Questions Does this data metering and monitoring strategy support the organization s sustainability objectives? Will this project support current and future regulatory requirements domestically and abroad? Is there executive sponsorship to fund and support the project? How will this project be funded? What is the ROI and risks? Who currently pays the energy bills (IT or Facilities)? Is there a plan to charge back energy (and carbon) to the end users? Technology is not the limiting factor, but rather organizational structure and behavior 21
22 Measurement Levels Minimum Best State-of Item Practical Practical the-art Linked IT / Facility Business Goals Metrics Measure and log metrics Online data acquisition? Monitoring Separate views (IT & Facilities) Linked IT/Facility dashboards Linked Business / IT / Facility dashboards 22 Proactive Strategies Server managing servers Auto-discovery of IT / Facility devices Proactive IT/Facility Proactive IT/Facility/Smart Grid
23 Typical Data Center Meters Many data centers have plenty of meters for each sub-system Typically installed for capacity or component health, not enterprise efficiency FACILITY HEALTH CAPACITY EFFICIENCY May be able to aggregate and recast data to measure and log efficiency Solutions at various price points to meet business objectives M M M M M M M M M M M M M M M M M M M M M M M M M Data Center Meters M IT M Facilities M Utilities 23
24 Enterprise Energy Dashboard While a single-pane of glass may be an ultimate goal, there are many tactical activities for improvement The cost for enterprise views continues to decrease with the proliferation of networks and web-based equipment and gateways Initiate program with existing metering data where available 24
25 Sensing Hierarchy IT and Facilities equipment have different constraints bu are implemented similarly The application dictates realtime monitoring acquisition rates from seconds, minutes days, weeks or months - IT Applications -Networks - Power or cooling systems 25
26 Collecting Data Center Telemetry in an Enterprise Sites may be internal or external, domestic or international Network security is crucial Typically many vendors and vintages of Power, Building Automation, HVAC, Security, IT, etc. Local and central storage of data and acquisition rates 26
27 Managed server monitored by a manager server Proactive management of servers enables IT to match optimal energy rates, facility capacities and carbon footprint Virtualization enables IT loads to be shifted globally Facility systems must be linked to process 27
28 Data Collector Software Architecture Is the heart of a linked system Secure and customized screens for: - Executives -IT - Facilities Proactively optimize IT, Facilities and Utilities to meet the organization s business objectives 28
29 PART 2 COOLING SYSTEMS Air Measurements 29
30 AIR HANDLERS (Chapter 5) COMPUTER ROOM UNITS (Chapter 6) Daryn Cline (Evapco), presenter 30
31 Part 2 Cooling Systems Air Measurements Chapter 5 Air Handlers 5.1 Overview 5.2 Measurement Levels Chapter 6 Computer Room Units 6.1 Overview 6.2 Measurement Levels 31
32 Part 2 Cooling Systems- Air Measurements Chapter 5 Air Handlers 5.1 Overview 32
33 Part 2 Cooling Systems Air Measurements Chapter 5 Air Handlers 5.2 Measurement Levels 33
34 Part 2 Cooling Systems Air Measurements Chapter 6 Computer Room Units 6.1 Overview CRAC Computer Room Air Conditioners Direct Expansion (DX) Chilled Water Dual Source -Chilled Water Primary, DX Backup Downflow -raised floor Upflow -free discharge or ducted Ceiling units Environmental Control Humidity Control RH, Dew point Sensible Heat 34
35 Chapter 6 Computer Room Units M =Measuring Points for Power Consumption 35
36 Chapter 6 Computer Room Units 36
37 PART 3 COOLING SYSTEMS Hydronic Measurements 37
38 PUMPS (Chapter 7) COOLING TOWERS (Chapter 8) CHILLERS (Chapter 9) HEAT EXCHANGERS (Chapter 10) Daryn Cline (Evapco), presenter 38
39 Part 3 Cooling Systems Hydronic Measurements Chapter 7 Pumps 7.1 Overview 7.2 Measurement Levels-Electrical 7.3 Measurement Levels-Fluid Chapter 8 Cooling Towers 8.1 Overview 8.2 Measurement Levels Chapter 9 Chillers 9.1 Overview 9.2 Measurement Levels Chapter 10 Heat Exchangers 10.1 Overview 10.2 Measurement Levels 39
40 Part 3 Cooling Systems Hydronic Measurements Chapter 7 Pumps 7.1 Overview 40
41 Part 3 Cooling Systems Hydronic Measurements Chapter 7 Pumps 7.2 Measurement Levels-Electrical 41
42 Part 3 Cooling Systems Hydronic Measurements Chapter 7 Pumps 7.2 Measurement Levels-Electrical 42
43 Part 3 Cooling Systems Hydronic Measurements Chapter 7 Pumps 7.3 Measurement Levels-Fluid 43
44 Part 3 Cooling Systems Hydronic Measurements Chapter 8 Cooling Towers 8.1 Overview-Open Counter and Cross Flow Cooling Towers 8.1 Overview-Closed Counter and Combined Flow Circuit Cooling Towers 44
45 Part 3 Cooling Systems Hydronic Measurements Chapter 8 Cooling Towers 8.2 Measurement Levels 45
46 Part 3 Cooling Systems Hydronic Measurements Chapter 8 Cooling Towers 8.2 Measurement Levels Minimum Practical Measurement-True RMS Power Best Practical Measurement-Current Transducers Best Practical Measurement-State-of-the-Art 46
47 Part 3 Cooling Systems Hydronic Measurements Chapter 9 Chillers 9.1 Overview 47
48 Part 3 Cooling Systems Hydronic Measurements 9.2 Measurement Levels 48
49 PART 4 POWER SYSTEMS MEASUREMENTS 49
50 INTRODUCTION TO CRITICAL POWER DISTRIBUTION (Chapter 11) UPSTREAM CRITICAL POWER DISTRIBUTION (Chapter 12) UNINTERRUPTIBLE POWER SUPPLY (Chapter 13) COMPUTER ROOM TRANSFORMER & POWER DISTRIBUTION UNIT (Chapter 14) Steve McCluer (Schneider/APC), presenter 50
51 Chapter 11 - Critical Power Distribution Critical Power vs. Essential Power Focus is on the Critical Power Path Can be several meandering paths Supports those loads with zero tolerance for unplanned downtime Mostly (but not entirely) in the IT Equipment Room Essential Power Path can tolerate a brief disruption Highly precise meters are typically required for power quality and forensic analysis, overkill for routine efficiency studies. Part 4 describes a data center rated somewhere between 200 kw and 5000 kw 51
52 Generator Utility Switchgear & Transformers ATS Distribution Switchgear UPS Mechanical Switchboard Distribution Switchgear Distribution Switchgear PDU RPDU 52 IT Loads Mechanical Loads Critical Path Essential Path Non-Critical Loads Non-Data Center Loads Other Loads Path
53 Ch 12 Upstream Critical Power Distribution Service Entrance Metering Typically highly precise revenue grade Typically includes kw & kvar May be difficult to separate IT loads Automatic Transfer Switch (ATS) Typically less precise May capture variances between sources Primary Electrical Distribution Switchgear May or may not be available for each circuit Ideal place to capture power into IT equipment room 53
54 54
55 Chapter 13 Uninterruptible Power Supply (UPS) Centralized UPS Measured outside of IT Equipment Room Output of UPS may be ideal place to capture IT room critical power consumption Distributed UPS Measured close to the IT loads in the IT Room May be multiple UPSs May be highest power consumption in the critical power path Possible to capture power going to zones or rows Metering can be at power module &/or at the system level UPS room Distributed UPS 55
56 UPS Metering 56
57 CHAPTER 14 COMPUTER ROOM TRANSFORMER & POWER DISTRIBUTION UNIT (PDU) Transformers can appear in many places in the power path Efficiency lost at every conversion Typically no metering i.e., measurements taken by hand-held instruments PDUs With transformer, typically meter output May be best place to aggregate actual IT equipment energy consumption Without transformer, metering may be optional 57
58 58
59 PDU Figure 14.3 Power Flow Through a Power Distribution Unit 59
60 Rack-mounted PDU (RPDU) Measurements taken inside the equipment rack or cabinet Generally impractical for aggregating equipment power consumption Good for equipment measurement May be multiple units in one rack powering the same equipment Typically have lower accuracy than upstream devices Many levels of metering options 60
61 Appendix D - UPS Overview of UPS types Redundancy and availability Challenges for power measurement on multiple paths Rules of thumb for minimum practical level of UPS instrumentation Example for quick estimation of PUE / DCIE inside the computer room Sample case study: PUE and DCIE determination for the critical power path within the data center (Partial PUE) 61
62 PART 5 IT SYSTEMS MEASUREMENTS
63 COMPUTER AND STORAGE SYSTEMS (Chapter 15) NETWORKING SYSTEMS (Chapter 16) Mike Patterson, Ph.D., P.E. (Intel), presenter
64 Motivation IT equipment power is the denominator in the PUE Calculation Overview Workload Characteristics Issues Measurements Minimum Measurement Best Practical State of the Art 64
65 Power thru the IT gear (Server, Stor, & Comms) Room Rack rack power strip or PDU a PSU CPU, etc.. PDU Server b Measurement location (a) can give aggregate power (b) best location if actual data is avaiable 65
66 Process for Measurement IT Equipment Inventory Age & self reporting capability Location; remote storage, etc Data Center Workloads Power draw can have unexpected patterns; power vs. energy considerations Enterprise, HPC, Financial, Internet, , etc Time of day, weekly variations, batch processes Server to server variation due to workload 66
67 Issues and challenges Different organizations, different systems Different protocols IT Facility IPMI -BACnet DCMI -Modbus ASH -other Where is it brought together? Management console, spreadsheet, or back of an envelope? Redundant Power Supplies Must measure all feeds and attribute accordingly Power over Ethernet (POE) 67
68 68 Chapter 16 Network; essentially the same, see the book for details
69 Minimum Practical Measurements Equipment nameplate Better than doing nothing, but just barely See Green Grid White Paper #23, Proper Sizing of IT Power and Cooling Loads PDU Output Can give actual rack-level power (sometimes energy) Not always tracked on-line Single server/network/storage measured value Actual portable power meter Workload, timeframe, scalability questions 69
70 Best Practical Measurement Rack or row level PDU output Rack power aggregate No visibility to individual servers or workloads Easily tracked/trended in BMS system Majority of PDUs have this capability Ignores line losses This is a reasonable assumption 70
71 State-of-the Art Measurement On-line server power consumption New Energy Star for Servers requires this! Challenge is integrating server manageability protocols with BMS systems IPMI, DCMI, ASH, Vendor-specific Extensive server data available CPU utilization Front panel temperature sensors On-line network and storage power consumption Somewhat behind Server; Energy Star on the horizon Capabilities vary on self reporting Wireless remote sensors Wide range of data capture 71
72 Thank you for attending 2010 For more information, visit 72
7 Best Practices for Increasing Efficiency, Availability and Capacity. XXXX XXXXXXXX Liebert North America
7 Best Practices for Increasing Efficiency, Availability and Capacity XXXX XXXXXXXX Liebert North America Emerson Network Power: The global leader in enabling Business-Critical Continuity Automatic Transfer
More informationMeasuring Power in your Data Center: The Roadmap to your PUE and Carbon Footprint
Measuring Power in your Data Center: The Roadmap to your PUE and Carbon Footprint Energy usage in the data center Electricity Transformer/ UPS Air 10% Movement 12% Cooling 25% Lighting, etc. 3% IT Equipment
More informationscalable data centre energy management solution
scalable data centre energy management solution scalable data centre energy management solution EcoMeasure - Scalable Data Centre Energy Management & Efficiency Measurement Solution by Workspace Technology
More informationData Center Infrastructure Management: ERP for the Data Center Manager
Data Center Infrastructure Management: ERP for the Data Center Manager 1 2 Topics What s DCIM & the ERP Analogy Why DCIM How DCIM Works How DCIM Helps 3 DCIM by Definition DCIM is a system that collects
More informationAbSTRACT INTRODUCTION background
february 20, 2007 GREEN GRID METRICS: Describing Datacenter Power Efficiency Technical Committee White Paper white paper 1 Abstract The Green Grid is an association of IT professionals seeking to dramatically
More informationData Center Metering and Resource Guide. Version 1.1. July 30th, 2015. Rod Mahdavi and Steve Greenberg. Lawrence Berkeley National Laboratory
Data Center Metering and Resource Guide Version 1.1 July 30th, 2015 Rod Mahdavi and Steve Greenberg Lawrence Berkeley National Laboratory Note to users: Please submit comments and suggestions to Steve
More informationIncreasing Data Center Efficiency through Metering and Monitoring Power Usage
White Paper Intel Information Technology Computer Manufacturing Data Center Efficiency Increasing Data Center Efficiency through Metering and Monitoring Power Usage To increase data center energy efficiency
More informationManaging Cooling Capacity & Redundancy In Data Centers Today
Managing Cooling Capacity & Redundancy In Data Centers Today About AdaptivCOOL 15+ Years Thermal & Airflow Expertise Global Presence U.S., India, Japan, China Standards & Compliances: ISO 9001:2008 RoHS
More informationConvergence of Complexity
Convergence of Complexity Optimize Existing Data Center Space Measure And Allocate Energy Cost Plan for new data centers or additional capacity How to make your Data Center Last Longer, Gartner, December
More informationTHE GREEN GRID DATA CENTER POWER EFFICIENCY METRICS: PUE AND DCiE
THE GREEN GRID DATA CENTER POWER EFFICIENCY METRICS: PUE AND DCiE 2007 The Green Grid. All rights reserved. No part of this publication may be used, reproduced, photocopied, transmitted, or stored in any
More informationImprove competiveness of IDC and enterprise data centers with DCIM
Improve competiveness of IDC and enterprise data centers with DCIM This paper studies the implementation of modern DCIM systems for data centers to improve operational competitiveness with ATEN's DCIM
More informationServer Technology, Inc.
Server Technology, Inc. Cabinet Power Monitoring, Management & Control Within the Data Center White Paper STI-100-011 2010-Sept-27 by Calvin Nicholson, Senior Director Software and Strategic Alliances,
More informationRecommendations for Measuring and Reporting Overall Data Center Efficiency
Recommendations for Measuring and Reporting Overall Data Center Efficiency Version 2 Measuring PUE for Data Centers 17 May 2011 Table of Contents 1 Introduction... 1 1.1 Purpose Recommendations for Measuring
More informationSystem integration oriented data center. planning. In terms of ATEN's eco Sensors DCIM solution
System integration oriented data center planning In terms of ATEN's eco Sensors DCIM solution 1. Introduction The reliability of an enterprise data center servicing either external or internal clients
More informationData Center Industry Leaders Reach Agreement on Guiding Principles for Energy Efficiency Metrics
On January 13, 2010, 7x24 Exchange Chairman Robert Cassiliano and Vice President David Schirmacher met in Washington, DC with representatives from the EPA, the DOE and 7 leading industry organizations
More informationIT Cost Savings Audit. Information Technology Report. Prepared for XYZ Inc. November 2009
IT Cost Savings Audit Information Technology Report Prepared for XYZ Inc. November 2009 Executive Summary This information technology report presents the technology audit resulting from the activities
More informationMetrics for Data Centre Efficiency
Technology Paper 004 Metrics for Data Centre Efficiency Workspace Technology Limited Technology House, PO BOX 11578, Sutton Coldfield West Midlands B72 1ZB Telephone: 0121 354 4894 Facsimile: 0121 354
More informationOverview of Green Energy Strategies and Techniques for Modern Data Centers
Overview of Green Energy Strategies and Techniques for Modern Data Centers Introduction Data centers ensure the operation of critical business IT equipment including servers, networking and storage devices.
More informationGuidance for Calculation of Efficiency (PUE) in Data Centers
Guidance for Calculation of Efficiency (PUE) in Data Centers White Paper 158 Revision 1 by Victor Avelar > Executive summary Before data center infrastructure efficiency can be benchmarked using PUE or
More informationComprehensive Data Center Energy Management Solutions
FROM INSIGHT TO EFFICIENCY: Comprehensive Data Center Energy Management Solutions Since 1995, facility managers and BAS professionals have relied on the Niagara framework to provide full convergence of
More informationSite Preparation Management Co., Ltd. March 1st 2013 By Nara Nonnapha, ATD UPTIME
Site Preparation Management Co., Ltd. March 1st 2013 By Nara Nonnapha, ATD UPTIME 2 AGENDA SESSION -1 What is Data Center? SESSION -2 Equipment and Components SESSION -3 Standard in designing Data Center
More informationArch Rock Energy Optimizer in Action Data Center
Arch Rock Energy Optimizer in Action Data Center Business Perspective Recent trends in Information Technology such as dense blade computing, server and storage virtualization, and cloud computing have
More informationEnergy Efficiency Opportunities in Federal High Performance Computing Data Centers
Energy Efficiency Opportunities in Federal High Performance Computing Data Centers Prepared for the U.S. Department of Energy Federal Energy Management Program By Lawrence Berkeley National Laboratory
More informationData Centers: Definitions, Concepts and Concerns
Data Centers: Definitions, Concepts and Concerns Arash Mousavi DCC September 2013 Agenda 1. Introduction 2. Issues in Modern Data Centers: Siemens Integrated Data Center Solutions 3. Issues in Modern Data
More informationPower & Environmental Monitoring
Data Centre Monitoring Made Easy Power & Environmental Monitoring Features & Benefits Packet Power provides the easiest, most cost effective way to capture detailed power and temperature information for
More informationMetering for today s systems
Metering for today s systems The sub-meter gathers data on the building side of the utility company meter. This allows us to break out usage so data can be collected from individual circuits, a single
More informationRecommendations for Measuring and Reporting Overall Data Center Efficiency
Recommendations for Measuring and Reporting Overall Data Center Efficiency Version 1 Measuring PUE at Dedicated Data Centers 15 July 2010 Table of Contents 1 Introduction... 1 1.1 Purpose Recommendations
More informationManaging Power Usage with Energy Efficiency Metrics: The Available Me...
1 of 5 9/1/2011 1:19 PM AUG 2011 Managing Power Usage with Energy Efficiency Metrics: The Available Metrics and How to Use Them Rate this item (1 Vote) font size Data centers consume an enormous amount
More informationUnderstanding Power Usage Effectiveness (PUE) & Data Center Infrastructure Management (DCIM)
Understanding Power Usage Effectiveness (PUE) & Data Center Infrastructure Management (DCIM) Salim Janbeh Physical Infrastructure Consultant uae-sj@panduit.com PANDUIT You Can t Manage What You Don t Measure:
More informationThe Pros and Cons of Modular Systems
The Pros and Cons of Modular Systems Kevin Brown, Vice President Global Data Center Offer Schneider Electric Schneider Electric 1 Foundational BUSINESS OVERVIEW Rev 2 Desired characteristics of pre-fabricated
More informationGuidance for Calculation of Efficiency (PUE) in Data Centers
Guidance for Calculation of Efficiency (PUE) in Data Centers White Paper 158 Revision 3 by Victor Avelar Executive summary Before data center infrastructure efficiency can be benchmarked using PUE or other
More informationCalculating Total Power Requirements for Data Centers
Calculating Total Power Requirements for Data Centers By Richard Sawyer White Paper #3 Executive Summary Part of data center planning and design is to align the power and cooling requirements of the IT
More informationServer Technology, Inc.
Server Technology, Inc. Power Efficiency Gains by Deploying 415 VAC Power Distribution in North American Data Centers White Paper STI-100-008 2009-April-07 Headquarters Server Technology, Inc. 1040 Sandhill
More informationTypes of Electrical Meters in Data Centers
Types of Electrical Meters in Data Centers White Paper 172 Revision 1 by David Kidd and Wendy Torell > Executive summary There are several different types of meters that can be designed into a data center,
More informationData Center Infrastructure Management: How to Optimize Data Center Operations
Data Center Infrastructure Management: How to Optimize Data Center Operations Khaled Nassoura, PE khaled.nassoura@raritan.com General Manager Raritan, Inc. Question of the Day Question: Would any CFO run
More informationEducation Evolution: Scalable Server Rooms George Lantouris Client Relationship Manager (Education) May 2009
Education Evolution: Scalable Server Rooms George Lantouris Client Relationship Manager (Education) May 2009 Agenda Overview - Network Critical Physical Infrastructure Cooling issues in the Server Room
More informationComprehensive Data Center Energy Management Solutions
FROM INSIGHT TO EFFICIENCY: Comprehensive Data Center Energy Management Solutions Since 1995, facility managers and BAS professionals have relied on the Niagara Framework to provide full convergence of
More informationThe Different Types of Air Conditioning Equipment for IT Environments
The Different Types of Air Conditioning Equipment for IT Environments By Tony Evans White Paper #59 Executive Summary Cooling equipment for an IT environment can be implemented in 10 basic configurations.
More informationTitle: Design of a Shared Tier III+ Data Center: A Case Study with Design Alternatives and Selection Criteria
Tier 3+ 1 Title: Design of a Shared Tier III+ Data Center: A Case Study with Design Alternatives and Selection Criteria Abstract: Schoolcraft College is constructing a High Availability (HA) Data Center
More informationElectrical Systems. <Presenter>
Review Root Causes of Energy Inefficiency Roadmap to Maximize Energy Efficiency Best Practices Alternative Energy Sources Controls Take Aways Seek Professional Help. ENERGY INEFFICIENCY OF
More informationManaging Today s Data Centers Avoiding the Impending Crisis
Managing Today s Data Centers Avoiding the Impending Crisis Steven Yellen Aperture Research Institute EXECUTIVE SUMMARY Organizations are facing an impending data center management crisis. The constant
More informationData Center Commissioning: What you need to know
Data Center Commissioning: What you need to know Course # CXENERGY1511 AIA Provider # 50111116 AABC Commissioning Group CxEnergy Conference Henderson, NV April 30, 2015 Presented by: Judson H. Adams, P.E.,
More informationBCA-IDA Green Mark for Existing Data Centres Version EDC/1.0
BCA-IDA Green Mark for Existing Data Centres Version EDC/1.0 To achieve GREEN MARK Award Pre-requisite Requirement All relevant pre-requisite requirements for the specific Green Mark Rating are to be complied
More informationHow Does Your Data Center Measure Up? Energy Efficiency Metrics and Benchmarks for Data Center Infrastructure Systems
How Does Your Data Center Measure Up? Energy Efficiency Metrics and Benchmarks for Data Center Infrastructure Systems Paul Mathew, Ph.D., Staff Scientist Steve Greenberg, P.E., Energy Management Engineer
More informationAIRAH Presentation April 30 th 2014
Data Centre Cooling Strategies The Changing Landscape.. AIRAH Presentation April 30 th 2014 More Connections. More Devices. High Expectations 2 State of the Data Center, Emerson Network Power Redefining
More informationAustralian Government Data Centre Strategy 2010-2025
Australian Government Data Centre Strategy 2010-2025 Better Practice Guide: Data Centre Power June 2013 17/06/2013 4:12 PM 17/06/2013 4:12 PM Contents Contents 2 1. Introduction 3 Scope 3 Policy Framework
More informationForeseer Services. Product application guide. Table of contents
Product application guide Foreseer Services Table of contents 1.0 General.......................................... 2 1.1 What are Foreseer Software and Engineering Services.... 3 1.1.1 Foreseer Service
More informationClassification of Data Center Operations Technology (OT) Management Tools
Classification of Data Center Operations Technology (OT) Management Tools White Paper 104 Revision 0 by Kevin Brown Dennis Bouley > Executive summary Data centers today lack a formal system for classifying
More informationLegacy Data Centres Upgrading the cooling capabilities What are the options?
Legacy Data Centres Upgrading the cooling capabilities What are the options? Presentation Structure What is a Legacy Data Centre? What is CRAC cooling? ASHRAE Standards Overview Available Cooling Systems
More informationData Centre Infrastructure Assessment
Data Centre Infrastructure Assessment Prepared for: ACME INC SAMPLE REPORT Attention: Mr DC Manager This report represents a generic sample data centre audit for a generic customer by Focus Group Technologies.
More informationCase Study: Opportunities to Improve Energy Efficiency in Three Federal Data Centers
Case Study: Opportunities to Improve Energy Efficiency in Three Federal Data Centers Prepared for the U.S. Department of Energy s Federal Energy Management Program Prepared By Lawrence Berkeley National
More informationData Center Technology: Physical Infrastructure
Data Center Technology: Physical Infrastructure IT Trends Affecting New Technologies and Energy Efficiency Imperatives in the Data Center Hisham Elzahhar Regional Enterprise & System Manager, Schneider
More informationGuideline for Water and Energy Considerations During Federal Data Center Consolidations
Guideline for Water and Energy Considerations During Federal Data Center Consolidations Prepared for the U.S. Department of Energy Federal Energy Management Program By Lawrence Berkeley National Laboratory
More informationRe Engineering to a "Green" Data Center, with Measurable ROI
Re Engineering to a "Green" Data Center, with Measurable ROI Alan Mamane CEO and Founder Agenda Data Center Energy Trends Benchmarking Efficiency Systematic Approach to Improve Energy Efficiency Best Practices
More informationGHG Protocol Product Life Cycle Accounting and Reporting Standard ICT Sector Guidance. Chapter 8: 8 Guide for assessing GHG emissions of Data Centers
GHG Protocol Product Life Cycle Accounting and Reporting Standard ICT Sector Guidance Chapter : Guide for assessing GHG emissions of Data Centers DRAFT March 0 Table of Contents GHG Protocol ICT Sector
More informationMAXIMIZING YOUR DATA CENTER INFRASTRUCTURE: CENTRALIZED MANAGEMENT AND WIRE-FREE ENVIRONMENTAL MONITORING
MAXIMIZING YOUR DATA CENTER INFRASTRUCTURE: CENTRALIZED MANAGEMENT AND WIRE-FREE Chris C. Gaskins Vice President of Product Development RF Code, Inc. AUGUST 2010 Shawn Griggs Director of Product Management
More informationDOE Data Center Air-Management (AM) Tool: Data Collection Guide. Version 1.18 (November 24, 2014)
DOE Data Center Air-Management (AM) Tool: Data Collection Guide Version 1.18 (November 24, 2014) The Data Collection Guide and the Air Management Tool were developed jointly by Lawrence Berkeley National
More informationStatement Of Work Professional Services
Statement Of Work Professional Services Data Center Electrical Efficiency Assessment Data Center Electrical Efficiency Assessment Service 1.0 Executive Summary Table of Contents 1.0 Executive Summary 2.0
More informationDefining Quality. Building Comfort. Precision. Air Conditioning
Defining Quality. Building Comfort. Precision Air Conditioning Today s technology rooms require precise, stable environments in order for sensitive electronics to operate optimally. Standard comfort air
More informationS c h n e i d e r E l e c t r i c BUSINESS IMPACT. Jack Hack Enterprise System Engineer 19 November 2015
S c h n e i d e r E l e c t r i c BUSINESS IMPACT Datacenter means business - create the bridge between IT en Facilities. Jack Hack Enterprise System Engineer 19 November 2015 1 Your ability to compete
More informationHow High Temperature Data Centers & Intel Technologies save Energy, Money, Water and Greenhouse Gas Emissions
Intel Intelligent Power Management Intel How High Temperature Data Centers & Intel Technologies save Energy, Money, Water and Greenhouse Gas Emissions Power and cooling savings through the use of Intel
More informationApplications for Infrared Thermography at Computer Centers
Applications for Infrared Thermography at Computer Centers By Eric Stockton CompuSCANIR, a division of Stockton Infrared Thermographic Services, Inc. 8472 Adams Farm Road Randleman, NC 27317 http://www.compuscanir.com/
More informationRevolutionizing Data Center Infrastructure Management
Infrastructure Management & Monitoring for Business-Critical Continuity TM Revolutionizing Data Center Infrastructure Management The Trellis Platform A Real-Time Solution to Continuous Performance Improvement
More informationThe 5th Greater Pearl River Delta Conference - Smart Management System in Building Facilities for Sustainability of Low Carbon Environment
The 5th Greater Pearl River Delta Conference - Smart Management System in Building Facilities for Sustainability of Low Carbon Environment Deployment of Advanced Technologies for Carbon Efficiency in Process
More informationTHE GREEN GRID METRICS: DATA CENTER INFRASTRUCTURE EFFICIENCY (DCIE) DETAILED ANALYSIS
WHITE PAPER #14 THE GREEN GRID METRICS: DATA CENTER INFRASTRUCTURE EFFICIENCY (DCIE) DETAILED ANALYSIS EDITOR: GARY VERDUN, DELL CONTRIBUTORS: DAN AZEVEDO, SYMANTEC HUGH BARRASS, CISCO STEPHEN BERARD,
More informationPower Distribution Units (PDUs): Power monitoring and environmental monitoring to improve uptime and capacity planning
Power Distribution Units (PDUs): Power monitoring and environmental monitoring to improve uptime and capacity planning 2009, Raritan Inc. Overview Corporate America is more dependent than ever on computing
More informationCooling Small Server Rooms Can Be. - Jim Magallanes Computer Room Uptime: www.cruptime.com Uptime Racks: www.uptimeracks.com
Cooling Small Server Rooms Can Be Inexpensive, Efficient and Easy - Jim Magallanes Computer Room Uptime: www.cruptime.com Uptime Racks: www.uptimeracks.com Server Rooms Description & Heat Problem Trends
More informationCURBING THE COST OF DATA CENTER COOLING. Charles B. Kensky, PE, LEED AP BD+C, CEA Executive Vice President Bala Consulting Engineers
CURBING THE COST OF DATA CENTER COOLING Charles B. Kensky, PE, LEED AP BD+C, CEA Executive Vice President Bala Consulting Engineers OVERVIEW Compare Cooling Strategies in Free- Standing and In-Building
More informationFEAR Model - Review Cell Module Block
F.E.A.R. Returns: 5 Steps Toward Data Center Efficiency Today Objectives Benefits for ITS professionals Brief review of the FEAR data center Define data center efficiency Link efficiency to the FEAR data
More informationGREEN GRID DATA CENTER POWER EFFICIENCY METRICS: PUE AND DCIE
WHITE PAPER #6 GREEN GRID DATA CENTER POWER EFFICIENCY METRICS: PUE AND DCIE EDITORS: CHRISTIAN BELADY, MICROSOFT CONTRIBUTORS: ANDY RAWSON, AMD JOHN PFLEUGER, DELL TAHIR CADER, SPRAYCOOL PAGE 2 ABSTRACT
More informationIntroduction to Datacenters & the Cloud
Introduction to Datacenters & the Cloud Datacenter Design Alex M. Hurd Clarkson Open Source Institute March 24, 2015 Alex M. Hurd (COSI) Introduction to Datacenters & the Cloud March 24, 2015 1 / 14 Overview
More informationThe following are general terms that we have found being used by tenants, landlords, IT Staff and consultants when discussing facility space.
The following are general terms that we have found being used by tenants, landlords, IT Staff and consultants when discussing facility space. Terminology: Telco: Dmarc: NOC: SAN: GENSET: Switch: Blade
More informationTim Sisson - Trane HVAC OVERVIEW
Tim Sisson - Trane HVAC OVERVIEW HVAC Systems System Types Acoustics Controls Modernization more than one Down to the Studs Opportunity for new System Type Renovation Possible opportunity for new System
More informationBuilding a power monitoring and management strategy Selecting the software and services needed to keep critical power systems continuously available
White Paper Markets Served Data center & IT By Arthur Mulligan Product Line Manager, Eaton U.S. Power Quality Jim Tessier Product Manager, Eaton IT Hardware and Software Building a power monitoring and
More informationInfrastructure & Cities Sector
Technical Article Infrastructure & Cities Sector Building Technologies Division Zug (Switzerland), October 18, 2011 Saving Energy in a Data Center A Leap of Faith? New guidelines from ASHRAE (American
More informationCooling Capacity Factor (CCF) Reveals Stranded Capacity and Data Center Cost Savings
WHITE PAPER Cooling Capacity Factor (CCF) Reveals Stranded Capacity and Data Center Cost Savings By Lars Strong, P.E., Upsite Technologies, Inc. Kenneth G. Brill, Upsite Technologies, Inc. 505.798.0200
More informationTHERMAL ANEMOMETRY ELECTRONICS, SOFTWARE AND ACCESSORIES
TSI and TSI logo are registered trademarks of TSI Incorporated. SmartTune is a trademark of TSI Incorporated. THERMAL ANEMOMETRY ELECTRONICS, SOFTWARE AND ACCESSORIES IFA 300 Constant Temperature Anemometry
More informationThe necessary convergence of IT and Facilities
The necessary convergence of IT and Facilities Bringing the two groups together under one unified process By Dr. Kenneth Uhlman Director of Data Center Business Development Eaton Corporation Abstract Many
More informationSECTION 16002C CAMPUS CENTRAL METERING SYSTEM DESIGN CRITERIA 1. General
SECTION 16002C CAMPUS CENTRAL METERING SYSTEM DESIGN CRITERIA 1. General A. Electrical usage on the Brown campus is presently monitored by a Siemens-brand, web-based central metering system, which includes
More informationUnleashing Stranded Power and Cooling Data
Unleashing Stranded Power and Cooling from New and Existing Data Centers An affordable, five-step approach to addressing power and cooling shortages By Dr. Kenneth Uhlman, P.E. Director of Data Center
More informationStatement Of Work. Data Center Power and Cooling Assessment. Service. Professional Services. Table of Contents. 1.0 Executive Summary
Statement Of Work Professional Services Data Center Power and Cooling Assessment Data Center Power and Cooling Assessment Service 1.0 Executive Summary Table of Contents 1.0 Executive Summary 2.0 Features
More informationAlternative data center power
Alternative data center power A quantitative TCO comparison of 400V AC and 600V AC power systems Abstract Power efficiency has become a critical focus for IT and facilities managers as they struggle to
More informationGreen Data Centre Design
Green Data Centre Design A Holistic Approach Stantec Consulting Ltd. Aleks Milojkovic, P.Eng., RCDD, LEED AP Tommy Chiu, EIT, RCDD, LEED AP STANDARDS ENERGY EQUIPMENT MATERIALS EXAMPLES CONCLUSION STANDARDS
More informationPUE : A COMPREHENSIVE EXAMINATION OF THE METRIC
WHITE PAPER #49 PUE : A COMPREHENSIVE EXAMINATION OF THE METRIC EDITORS: Victor Avelar, Schneider Electric Dan Azevedo, Disney Alan French, Emerson Network Power PAGE 2 The Green Grid Association would
More informationData Center Energy Use, Metrics and Rating Systems
Data Center Energy Use, Metrics and Rating Systems Steve Greenberg Energy Management Engineer Environmental Energy Technologies Division Lawrence Berkeley National Laboratory October 31, 2007 Today s s
More informationClassification of Data Center Infrastructure Management (DCIM) Tools
Classification of Infrastructure Management (DCIM) Tools White Paper 104 Revision 3 by Kevin Brown Dennis Bouley > Executive summary Data centers today lack a formal system for classifying infrastructure
More informationReducing Data Center Loads for a Large-Scale, Net Zero Office Building
rsed Energy Efficiency & Renewable Energy FEDERAL ENERGY MANAGEMENT PROGRAM Reducing Data Center Loads for a Large-Scale, Net Zero Office Building Energy Efficiency & Renewable Energy Executive summary
More informationRELIABLE AND FLEXIBLE POWER FOR YOUR DATA CENTRE
RELIABLE AND FLEXIBLE POWER FOR YOUR DATA CENTRE Highly efficient solutions for power distribution, management and monitoring POWER DISTRIBUTION WIRE-FREE MONITORING LEAK DETECTION Daxten provides comprehensive
More informationGreen Computing: Datacentres
Green Computing: Datacentres Simin Nadjm-Tehrani Department of Computer and Information Science (IDA) Linköping University Sweden Many thanks to Jordi Cucurull For earlier versions of this course material
More informationEnvironmental Data Center Management and Monitoring
2013 Raritan Inc. Table of Contents Introduction Page 3 Sensor Design Considerations Page 3 Temperature and Humidity Sensors Page 4 Airflow Sensor Page 6 Differential Air Pressure Sensor Page 6 Water Sensor
More informationEnergy Savings in the Data Center Starts with Power Monitoring
Energy Savings in the Data Center Starts with Power Monitoring As global competition intensifies, companies are increasingly turning to technology to help turn mountains of data into a competitive edge.
More informationAnalysis of the Brazilian Data Center Power Supplies Market
Analysis of the Brazilian Data Center Power Supplies Market IT Infrastructure Outsourcing Services Compel New Trends for this Growing Market ND27-14 September 2013 Contents Section Slide Numbers Executive
More informationRULES FOR THE SETTING UP OF SUSTAINABLE BRANCHES Summary
RULES FOR THE SETTING UP OF SUSTAINABLE BRANCHES Summary January 2013 TABLE OF CONTENTS INTRODUCTION... 3 GENERAL RECOMMENDATIONS... 3 Communication with customers in the field of environmental sustainability...
More informationElectrical Efficiency Modeling for Data Centers
Electrical Efficiency Modeling for Data Centers By Neil Rasmussen White Paper #113 Revision 1 Executive Summary Conventional models for estimating electrical efficiency of data centers are grossly inaccurate
More informationData Center Power Distribution and Capacity Planning:
Data Center Power Distribution and Capacity Planning: Understanding what you know and don t know about power usage in your data center 2009, Raritan Inc. About This Series Raritan, a leading provider of
More informationAeration Air & Digester Gas Flow Metering Using Thermal Mass Technology. HWEA 2011 Conference Craig S. Johnson
Aeration Air & Digester Gas Flow Metering Using Thermal Mass Technology HWEA 2011 Conference Craig S. Johnson Presentation Overview Introduction Aeration Air & Digester gas challenges Gas flow metering
More informationEnergy Efficiency and Green Data Centers. Overview of Recommendations ITU-T L.1300 and ITU-T L.1310
Energy Efficiency and Green Data Centers Overview of Recommendations ITU-T L.1300 and ITU-T L.1310 Paolo Gemma Chairman of Working Party 3 of ITU-T Study Group 5 International Telecommunication Union Agenda
More informationUniversity of St Andrews. Energy Efficient Data Centre Cooling
Energy Efficient Data Centre Cooling St. Andrews and Elsewhere Richard Lumb Consultant Engineer Future-Tech Energy Efficient Data Centre Cooling There is no one single best cooling solution for all Data
More informationImperial College 3 March 2009 Green Data Centers: An Overview
Imperial College 3 March 2009 Green Data Centers: An Overview Updated: 26 Feb 09 LBNL s Data Center findings Benchmarking Efforts Energy Reduction Approaches Green Data Centers: An Overview 2 Scenarios
More informationCarbonDecisions. The green data centre. Why becoming a green data centre makes good business sense
CarbonDecisions The green data centre Why becoming a green data centre makes good business sense Contents What is a green data centre? Why being a green data centre makes good business sense 5 steps to
More information