Split and Multi Split air conditioners Service information

Size: px
Start display at page:

Download "Split and Multi Split air conditioners Service information"

Transcription

1 Split and Multi Split air conditioners Service information Programming LG wired controllers 2 New type 2 Old type 7 Fault codes 9 Wall units (single split) 9 Universal split and multi split 10 Detailed explanation of fault codes 12 Thermistor calibration figures 27 Testing the diodes in the inverter circuit 29 Last update: 14/1/

2 Programming LG wired controllers 1. New type PQRCUSA0 The new controller is model number PQRCUSA0.The same model is used for split and multi splits and for VRF. There is a built-in receiver which responds to an infra red controller when used in ducted units. Updated 29/3/10-2 -

3 User functions Setting the time Press the time button (13) for about 4 seconds until the display flashes Use the arrow keys to navigate around the sections and to set each item (hour, minutes, am/pm, day of week) Press OK/CLEAR (14) to confirm. Child lock The Child Lock is used to prevent unauthorised changes to the controller settings. The controller does not respond to any button, until the lock is released Repeat pressing the FUNCTION SETTING button (7) until the child lock sign appears Press OK/CLEAR button (14) to confirm. CL will appear on the display Repeat the operation to release the child lock Vane angle control Repeat pressing the FUNCTION SETTING button (7) until the vane angle control sign appears The display would show a pair of numbers, for example example The number to the left (2 in this example) is the vane number to be controlled. The number on the right (P1 in this example) is the vane angle. Use the keys to get the left number to flash. Use the up/down keys to select the vane number to be adjusted. The choice is 1,2,3,4 or All Use the left/right arrow keys to get the right hand number to flash. Then use the up/down keys to select the required angle. P1 directs the air closest to the ceiling; P6 provides the steepest downwards flow. Press OK/CLEAR (14) to confirm Press ESC to leave the programming mode (the controller would automatically leave the programming mode if left for 25 seconds) - 3 -

4 Engineer functions The following functions can be programmed No. Function Function Value Code 1 Test run 18 minutes, 01 01:Set cooling, high fan speed, 2 Address setting to FF : Address 3 ESP value for ducted units 03 01:Very low 02:Low 03: Medium 04:High 05:Very high 4 Room temperature thermistor 04 01:Remote controller sensor 02:Return air sensor 03:Both sensors 5 Ceiling height adjustment 05 01: Medium 02:Low 03:High 04:Very high 7 Two controllers on one indoor unit one must be master, one slave 07 00:Slave 01:Master 9 Dry contact 09 00:Off 01:On 12 Centigrade to Fahrenheit 12 00:Centigrade 01: to Fahrenheit Group control No programming required on controller. See Product Sheet 98 for dip switch settings on indoor unit PCB The engineer functions are accessed by pressing the FUNCTION SETTING button for about 4 seconds, until the following appears on the display instead of the time-of-day: Once you are in the programming mode, the function number advances each time you press the FUNCTION SETTING key. Repeat pressing this key until you reach the function code you need to set. When you have selected the function code, use the up/down arrow keys to obtain the required selection within that function code. Example: ceiling height adjustment (function 05) for medium ceiling height (selection 03) should display 05:03 Press the OK/CLEAR (14) to confirm the selection Then continue programming, or press the ESC button (8) to leave the programming mode (The programming mode exits automatically in any case after 25 seconds)

5 7-Day Timer Setting (Technical sheet 107) Press the timer setting button (13) once, towards the bottom right side you ll see flashing. Repeat pressing (3 times) until is flashing. Scroll across to the required day that you wish to set using the (15). Press down (15). You can now see the number 1 flashing. Each controller can be set to operate up to two time run periods each day. ie, Number Number signifies period one, 2 signifies period two. Press to scroll to between each period. To set the on/off time press once to select the hour on time and again to select the minute on time. The up down buttons will adjust the time. Note that a hyphen appears on the right side of the 4 digit time. Now set the off time by pressing once. The hour time will now flash and the hyphen appears on the left side of the 4 digit time to signify the off time. Adjust the hour and minute time accordingly using the buttons. Press once to return back to the time run period selection. Press to scroll to the next time run period and press to exit back to the day selection and set the next day. To exit out completely press escape (8). To save settings press ok/clear (14). Once fully out of the 7 day timer menu press escape once to show the current time on the display. A line will appear under any day that has a set run time. You can set a day not to run by using the holiday feature. This is ideal for operation Monday to Friday only. To set a holiday escape completely out from the weekly reservation settings and press the timer setting button once, towards the bottom right side you ll see flashing. Repeat pressing button (4 times), you will now see flashing. Scroll across to the required day using the buttons, press the button to select. A line replaces that specific day to signify holiday set. Press button again to unselect. Press escape to exit out

6 2. Older wired controller The wired remote controller has the following main functions: Mode selection Mainly heating, cooling, and auto changeover at a specified temperature. Temperature selection The display shows the set temperature. Pressing the button with the house symbol displays the actual room temperature. The display reverts back to room temperature after a few seconds. Fan speed High, medium and low or automatic. On some model the fan speed may reduce when the set temperature is reached and the compressor is off. In the heating mode, the fan operates only when the indoor coil is warm. Timer A seven day timer is built-in Child lock This is used to lock the controller at a set position to prevent unauthorised tampering. To lock, press Timer and Min buttons together for about 3 sec till CL shows To unlock, press Timer and Min together for about 3 sec till CL disappears When locked, CL appears for a few seconds each time any button is pressed, but the controller does not respond. Swing The louvers may me set to either stay in one position, or swing Vane angle control (cassettes) This permanently sets the angle of the vanes when the swing function is not in use. Each pair of vanes is adjusted separately. Press right arrow + Swing for 3 sec till PO is displayed (the default position) Keep pressing the swing button to change the angle between P0 and P5. Press Right arrow + swing to complete and set. This sets the angle on one pair of louvers. For the other pair, repeat the above using the left arrow key instead of the right arrow. Test mode In this mode the unit operates continuously for 18 minutes, ignoring the room thermostat. Press house button + hour button for 3 second, till display shows LO. The test may be stopped early using the on/off button. Alternative room thermostats There are two alternative room thermostats. The installer can select the return air thermostat, the controller thermostat, or a combination of both. A switch is provided at the back of the controller for this purpose. Top position remote controller Mid position indoor unit Lower position both - 6 -

7 Fault codes Wall units (single split) A summary of the fault codes is given in the table below, but they are described in greater detail in the pages that follow. Error Code C1 or CH1 C2 or CH2 C4 0r CH4 C5 or CH5 C6 or CH6 Flashing Lights Fault 1 Indoor temperature sensor open or closed circuit 2 Indoor temperature sensor open or closed circuit 4 Heat sink temperature sensor open or closed circuit 5 Communication between indoor and outdoor units 6 Excessive current at inverter DC power circuit (can be indoor pipe outlet sensor, or outdoor condenser sensor on some models) C7 or CH7 C8 or CH8 C9 or CH9 CA Discharge temp more than C 2. Faulty discharge thermistor Display Indoor Outdoor O Indoor operation ON O O ON O O ON O O OFF O O SHUT DOWN 7 Excessive compressor current O O SHUT DOWN 8 Indoor fan not rotating O OFF 9 Outdoor fan not rotating O O OFF O O ON CC EEPROM error O ON CD Inverter module error O ON CE O ON Po Lo System in Power Mode not a fault System in test mode not a fault O O Notes: On models with an alpha-numeric display the error codes are as per the left hand column above. On other models the fault is determined by counting the number of flashes on one or two led s. There is an interval of three seconds between repeats of the flashing sequence

8 Universal units including multi-split If there is a fault on any LG Universal unit, a two digit number will appear on the remote controllers led display. If the unit does not have a remote controller the fault will be displayed using the LED's on the front of the indoor unit. Tens Units Units Digit (Red) Tens Digit (Green) The Units digit of the fault code is shown by the power led which has the following symbol by it. This is usually Red, but on a few models it is Green. The Tens digit will be displayed by one other led, usually the Sleep or Filter lamp. Error Indicator: The function provides self-diagnosis and displays an error code if there is any trouble. Error codes are displayed on the Indoor unit s Wired Remote as CH**, and/or Fascia Display. In addition, the code is indicated via LED s on the outdoor unit control board. If more than two troubles occur simultaneously, the lower number of error code is displayed first. After an error occurs, if error is released, error LED is also released simultaneously. Indoor Unit Faults: Error code Contents Case of error Indoor Status 01 Air sensor (open/short) Open / Short circuit Off 02 Inlet pipe sensor Open / Short circuit Off 03 Communication(Indoor Wired R/Control) 04 Drain pump / Float switch Communication Poorly Float switch Open circuit (High level water alarm) 05 Communication(Indoor Outdoor) Communication Poorly Off 06 Outlet pipe sensor Open / Short circuit Off 07 Different operation mode Indoor units set in different operation modes Off 09 Checksum Error Defective PCB or EEPROM Connections Off 10 BLDC Motor Fan Lock (Indoor) Fan Motor or PCB Defective Off HL Hard Lock (Controlled by External Source) Controlled by Dry Contact or Central Controller Off CL Child Lock Function selected Not an error, press Timer & Min buttons simultaneously for 3 seconds to toggle On/Off On Po Jet Cool Mode selected Not an error, press Jet Cool button to toggle On/Off On Off Off - 8 -

9 Outdoor Unit Faults can also be read from the outdoor unit PCB using the flashing LED s as below: Error code Contents LED01G (Red) LED02G (Green) 21 IPM Fault (Compressor Over current) 2 times 1 time Case of Error Compressor malfunction, IPM Fault Outdoor Status 22 CT 2 (Max. Current) 2 times 2 times Current is 14A Off 23 DC Link Low Volt. 2 times 3 times DC Link volt. Is 140V Off 24 Low / High Pressure 2 times 4 times Low / High press switch OPEN Off 25 AC Low / AC High Volts. 2 times 5 times Abnormal AC volt. Input. Off 26 DC Compressor Position 2 times 6 times Off 27 PSC Fault (Reactor) 2 times 7 times Off 28 DC Link High Volts 2 times 8 times Off Off 29 COMP Over Current 2 times 9 times Inverter Compressor input current is over 30A 32 Discharge Pipe Temp. High (INV) 3 times 2 times D-Pipe Temp (Inv.) >105 C Off 33 Discharge Pipe Temp. High (Cons.) 3 times 3 times D-Pipe Temp (Const) >105 C Off 39 Communication Error 3 times 9 times Communication Error Between PFC and INV PCB s 40 CT Circuit 4 times CT Circuit malfunction Off 41 D-Pipe sensor INV. (Open/Short) 4 times 1 time Open / Short circuit. Off 44 Air sensor (Open/Short) 4 times 4 times Open / Short circuit Off 45 Cond. Pipe Sensor (Open/Short) 4 times 5 times Open / Short circuit Off 46 Suction Pipe Sensor (Open/Short) 4 times 6 times Open / Short circuit Off 47 D-pipe Sensor Cons. (Open/Short) 4 times 7 times Open / Short circuit Off 48 D-Pipe & Air Sensor (Open) 4 times 8 times Dual Sensor unplugged Off 51 Over Capacity 5 times 1 times Over Load Combination Off Communication Error (Main micom Sub micom) Communication Error (Indoor Outdoor) Outdoor 3-Phase Power Supply Reverse Phase / Missing Phase 5 times 2 times Poor/Loss of Communication Off 5 times 3 times Poor/Loss of Communication Off 5 times 4 times Incorrect Wiring Off 60 EEPROM Check Sum 6 times Check Sum Mis-Match Off 61 Cond. Pipe Sensor Temp. High 6 times 1 time Cond. Temp. High Off 62 Heat Sink Sensor Temp. High 6 times 2 times Heat Sink Temp. High Off 63 Cond. Pipe Sensor Temp. Low 6 times 3 times Cond. Temp. Low Off 65 Heat Sink Sensor (Open/Short) 6 times 5 times Open / Short circuit Off 67 Outdoor BLDC Fan Lock 6 times 7 times Fan Motor/Circuit Problem Off 73 PFC Fault Error (S/W) 7 times 3 times Inverter PCB input current is over 48A (Peak) for 2ms Off 105 Comms. Error (Main board Fan board) 6 times 5 times Poor/Loss of Communication Off [The codes are explained in detail on the following pages] Off Off Off - 9 -

10 Fault Code 01 Is a fault with the Indoor unit return air Thermistor Unplug the Thermistor from the PCB and Check its resistance check against this graph: Resistance of Air thermistor Resistance k Ohms Temperature Alternatively the sensor can be tested while still connected to the PCB measure the DC voltage across the resistor and check it against the graph below. 3.5 Voltage across Air thermistor Volts DC Temperature

11 Fault Code 02 Is a problem with the Indoor unit coil inlet Thermistor Unplug the Thermistor from the indoor PCB and Check its resistance against this graph: Coil thermistor resistance k Ohms 20 Resistance k Ohms Temperature Alternatively the sensor can be tested while still connected to the PCB measure the DC voltage across the resistor and check it against the graph below. 4.0 Voltage across coil thermistor Volts DC Temp

12 Fault Code 03 Indicates a wiring error between the remote controller and the fan coil, this is most common in group control applications where more than 1 fan coil is connected to a single remote controller. Firstly check the wiring has been done correctly see below Next check the switch in the back of the remote controller, it has to be set to Group or GR1 for group control, the Factory setting is Single or SG, after setting the switch reset the power for 2 minutes. If the fault does not clear, check the Voltage of the remote controller cable. The Red cable is 12 Vdc The Brown or Black cable is Ground or 0 Vdc The Yellow is signal (Comms.) Test Voltage across the Brown/ Black cable and the Red, this should be 12 Vdc Voltage from Yellow to Brown/Black this should be fluctuating between 8 12 Vdc

13 Fault Code 04 Fault code CH04 indicates that the float switch of the fan coil has risen. On fan coils without a drain pump it indicates that the jumper (blue plug with 30mm of blue wire) in terminal CN FLOAT is missing. If the fan coil is running and the float rises it will take 3 1/2 minutes for the fault to show on the controller, this is to give the unit time to pump excess water away. Once the float falls, (or the jumper is put back into the board) it will not be possible to clear the fault for 40 seconds. It is considered good practice to reset the power to clear this fault code. Fault Code 05 These error codes indicate a communication fault between the indoor and outdoor units; it appears approximately 5 minutes after powering up the system. The communication between the units is a fluctuating DC voltage commonly called a serial signal, it can be easily lost if the wiring is not done correctly. If there is a communication error fault CH05 will appear on the Wired Remote within 5 mins. of powering up the system. Testing First check for any isolator or switches on the interconnecting cable and ensure both the Comms and Neutral are un-switched. Then confirm connections are correct and secure at both the Indoor and Outdoor units. Check if any other devices are connected on the interconnecting cable, remove such equipment, and connect them elsewhere. Open the outdoor unit to reveal the Main PCB and identify the Green and Red LED s on that board. The Green LED should be lit steadily if power is present, the Red LED should be doing one of the following:- 1. If the outdoor unit receives communications from the indoor unit, the Red LED should be flickering. 2. If the Red LED glows steadily without flickering, then no communication is being received from the indoor unit. Check the interconnecting cables for any short or open circuits, not forgetting the connecting cables between the terminal rail and PCB on both Indoor & Outdoor units. Repair wiring, or replace the Indoor PCB as necessary. 3. If the Red LED does not light at all, then the fault is with the outdoor PCB, or connections to it. Confirm that the Outdoor PCB is receiving power (Green LED lit). Repair wiring, or replace the Outdoor PCB as necessary. 4. If Condition 3 above applies please check the following and repair/replace as required. Failure to do so may result in the new PCB becoming damaged. a. Check PCB Control Fuse, if blown, identify cause and rectify. b. Check Fan Motor(s). i. AC Motors for Short Circuits or Down to Earth. ii. BLDC Motors (See Product Technical Update - Sheet 83). c. Reversing Valve Coil, for Short Circuit or Down to Earth. d. Reactor, for Open Circuit. e. Electronic Expansion Valve Down to Earth (See Product Technical Update - Sheet 96). f. Compressor, for Short Circuit or Down to Earth. Additional Tests: Set your meter to DC Volts, Test between terminals 2 and 3 of the outdoor unit and wiring terminals, you should see 0-75 Vdc, it will be fluctuating rapidly. If this signal voltage is not present disconnect the wire from terminal 3 of the inter unit cabling, and test terminal 3 Voltage again. If Voltage is still not present, the outdoor PCB must be faulty. If this signal voltage is detected leaving the outdoor unit, reconnect wire 3 and check what is being received at the indoor unit. Disconnect wire 3 from the indoor terminal block and check the DC Voltage between this wire and terminal 2. It should be the same as what you saw at the outdoor unit, if not your wiring is at fault. With the wire still disconnected, check between terminals 2 & 3. You should see a relatively steady voltage in the range of Vdc (Negative). Any significant difference would indicate a faulty Indoor PCB. Important: Comms Errors are also created on Universal Synchro Systems when they are not configured/commissioned correctly. Please follow the correct Synchro Commissioning Procedures

14 Fault Code 06 Is a problem with the Indoor unit coil outlet Thermistor Unplug the Thermistor from the indoor PCB and Check its resistance against this graph: Coil thermistor resistance k Ohms 20 Resistance k Ohms Temperature Alternatively the sensor can be tested while still connected to the PCB measure the DC voltage across the resistor and check it against the graph below. 4.0 Voltage across coil thermistor Volts DC Temp

15 Fault Code 07 On Multi split systems, the first unit switched on is the cool heat master, the master tells the condensing unit what to do. If the condenser is in heating and any slave is set to cooling a CH07 fault code will appear. Likewise if the condenser is in cooling and any slave is set to heating a CH07 fault code will appear. If the master is switched off the next longest running unit becomes the master. To clear the fault turn off the unit at the remote controller, turn it back on again and change the mode Fault Code 09 Check for loose connections or dry joints where EEPROM connects on Main PCB, repair if possible, if not replace PCB. Fault Code 10 Indoor Fan Motor problem, See Fault Code 67 for Troubleshooting help. Fault Code 21 This fault is caused by an over current in the inverters DC power circuit. If the DC part of the circuit exceeds 14 Amps fault code 21 will be displayed. This is caused by either the inverter PCB being faulty or compressor being short circuit or down to earth. Disconnect the electrical connections to the compressor and check the resistance of the compressor windings, measure from U to V, V to W and W to U the values should be between 0.25 and 5 Ohms each. The next test is to measure the resistance of the compressor windings to earth. Using a Megger (High Voltage Meter) measure the resistance from any of the 3 compressor terminals to an Earth point (pipe work). The value should exceed 2 M Ohms. If the compressors fail these tests it will need replacing. If the compressor is OK you will need to check the inverter output voltages. Please see section on Inverter testing at end. Fault Code 22 This fault is caused by a Compressor over-current see code 21 Please see section on Inverter testing at the end. Fault Code 23 This fault indicates a fault in the DC part of the inverter circuit; it means that the Dc Voltage to the inverter is below 140 V Dc, it should be 370 V for single phase machines and 600 V dc for three phase machines. The

16 fault is usually caused by the inverter charging resistor being faulty; this component is mounted on the outdoor unit PCB and cannot be replaced. Start the unit running and measure the DC Voltage supply to the inverter. This is easiest to measure at the inverter capacitors; it should be 370 V for single phase machines and 600 V dc for three phase machines See section on Inverter testing at the end. Fault Code 24 If the unit has a low or high pressure fault CH24 will display. If the LP switch goes open circuit the compressor will be stopped, on inverter units this can take up to 30 seconds. The LP Switch goes open circuit when the suction pressure falls below 0.5 bar the Hp Switch opens at 41 bar. The fault code will only occur if the pressure switch is tripped 5 times within 1 hour, this can only be reset by switching off the power to the condensing unit for 2 minutes. If your unit does not have any pressure switches it may still have a plug on the outdoor unit PCB labelled CN Press, it should have a link plugged in, and if the link is missing it must be replaced. Fault Code 25 This fault indicates a problem with the incoming power supply to the system. Measure the Voltage of the incoming supply, if it is less than 140V AC or greater than 300V AC this fault will occur. If the Power supply is correct and the fault persists replace the outdoor unit PCB. Fault Code 26 This fault indicates a problem with the positioning system of the inverter compressor, which indicates a seized compressor. Firstly check the compressor is correctly connected. Next reset the power supply to the system ensuring the power is left off for 5 minutes. Start the unit up, after a couple of minutes the compressor will try and start, you can hear a high pitched whine when it does. If the compressor does not start turning within a couple of seconds the whining will stop. The compressor will try to start 3 times then the fault will recur. Fault Code 27 This fault indicates a problem with the inverter module, see section on testing inverters. Also check reactor is connected to the PCB and check its resistance it should be well under 1 Ohm. Fault Code 28 This fault indicates a problem in the DC part of the inverter circuit; it means that the DC Voltage to the inverter is too high. Start the unit running and measure the DC Voltage supply to the inverter. This is easiest to measure at the inverter capacitors; it should be 370 V for single phase machines and 600 V dc for three phase machines. See section on Inverter testing at end. Fault Code 29 Check and correct for any: 1. Overload operation (Pipe restrictions / Restricted Airflow / EEV defect / Refrig. Overcharged) 2. Compressor damage (Insulation damage / Motor damage) 3. Input Voltage Low 4. ODU Inverter PCB assembly damage

17 Fault Code 32 Indicates that the Inverter compressor discharge temperature is high (above 105 C) this usually indicates the system has either a shortage of refrigerant or a blockage in the system. Reset the power to the unit for 2 minutes and restart it. If the compressor starts measure the compressor discharge temperature, typically it should not be more than 50 C above the ambient temperature around the condensing unit. It may take quite a long period for the compressor to overheat so don t just start the unit and run. Make sure you check the unit is operating correctly and providing adequate cooling. Fault Code 33 Indicates that the fixed speed compressor discharge temperature is high (above 105 C) this usually indicates the system has either a shortage of refrigerant or a blockage in the system. Reset the power to the unit for 2 minutes and restart it, If the compressor starts measure the compressor discharge temperature, typically it should not be than 50 C above the ambient temperature around the condensing unit. It may take quite a long period for the compressor to overheat so don t just start the unit and run. Make sure you check the unit is operating correctly and providing adequate cooling. Fault Code 39 Check and repair or replace as necessary: 1. PCB defect / Wiring defect 2. Different Micom Software Version 3. ODU Inverter PCB assembly damage Fault Code 40 This fault indicates a problem with the current drawn by the AC part of the inverter circuit. Refer to the inverter testing procedure at the end

18 Fault Code 41 This fault indicates an Inverter Compressor discharge Thermistor fault Unplug the Thermistor and Check its resistance check against this graph: Resistance of discharge pipe thermistor 250 resistance kohms temp Alternatively the sensor can be tested while still connected to the PCB measure the DC voltage across the resistor and check it against the graph below. Voltage across discharge thermistor Voltage DC Temp

19 Fault Code 44 Indicates a fault with the Outdoor unit air Thermistor Unplug the Thermistor from the PCB and Check its resistance check against this graph: Resistance of Air thermistor Resistance k Ohms Temperature Alternatively the sensor can be tested while still connected to the PCB measure the DC voltage across the resistor and check it against the graph below. 3.5 Voltage across Air thermistor Volts DC Temperature

20 Fault Code 45 Indicates a problem with the condenser coil outlet Thermistor Unplug the Thermistor from the indoor PCB and Check its resistance against this graph: Coil thermistor resistance k Ohms 20 Resistance k Ohms Temperature Alternatively the sensor can be tested while still connected to the PCB measure the DC voltage across the resistor and check it against the graph below. 4.0 Voltage across coil thermistor Volts DC Temp

21 Fault Code 46 Indicates a problem with the compressor suction Thermistor Unplug the Thermistor from the indoor PCB and Check its resistance against this graph: Coil thermistor resistance k Ohms 20 Resistance k Ohms Temperature Alternatively the sensor can be tested while still connected to the PCB measure the DC voltage across the resistor and check it against the graph below. 4.0 Voltage across coil thermistor Volts DC Temp

22 Fault Code 47 Indicates an Inverter Compressor discharge Thermistor fault Unplug the Thermistor from the PCB and Check its resistance check against this graph: Resistance of discharge pipe thermistor 250 resistance kohms temp Alternatively the sensor can be tested while still connected to the PCB measure the DC voltage across the resistor and check it against the graph below. Voltage across discharge thermistor Voltage DC Temp

23 Fault Code 48 This fault indicates that the compressor discharge sensor and the condenser air temperature sensors are both unplugged. Both these sensors are connected to a single connector on the outdoor unit PCB, plug it in and the fault will go away. Fault Code 51 This indicates that the capacity of the indoor unit / units is too great for the condensing unit. Make a note of the model number of the fan coil/coils and the condensing unit and check with the equipment supplier that the units you have installed can be connected together. Fault Code 52 This fault code indicates a communication error between the Main and Sub micom (CPU s) on the outdoor unit main PCB. Check for evidence of damage, if none found reset power, if fault reappears replace pcb. Fault Code 53, (see fault code 05) Fault Code 54 This fault normally indicates a lost phase or the phases are reversed on the power supply to 3 phase units. Check all 3 phases are available at the power terminals to the unit. You should have 415v AC across red to blue, blue to yellow and red to yellow, If this is all ok turn off the power and swap the red and yellow cores of the power supply cable over, reset the power and the unit will operate. Fault Code 60 Check the correct PCB assembly has been installed, check for dry joints, replace outdoor unit PCB if nothing is found. Fault Code 61 Indicates the outdoor unit condenser coil temperature is high above 65 C, this will usually be experienced in cooling mode and will indicate insufficient air being drawn over the coil. Check there are no blockages to the coil (carrier bags dirt etc); check the air flow is not short circuiting from the front to the back of the unit and check for Nitrogen in the system. Fault Code 62 Indicates the outdoor unit Inverter heat-sink thermistor has detected that the heat sink is overheating 85 C. This is usually caused by debris blocking the heat-sink fins or an error with the thermistor, see code

24 Fault Code 65 Is a problem with the Inverter PCB heat sink thermistor for the heat sink on the outdoor unit PCB, unplug the Thermistor from the PCB and Check its resistance against this graph: resistance of Heat sink thermistor Resistance k Ohms Temperature Alternatively the sensor can be tested while still connected to the PCB measure the DC voltage across the resistor and check it against the graph below. 3.5 Voltage across Heat Sink thermistor 3.0 Volts DC Temperature

25 Fault Code 67 This is a problem with the Outdoor Fan Motor, where rotation is not detected, and could be result of either Mechanical or Electrical failure. Check that motor is free to rotate and not seized. Check the motor is electrically sound, windings not Open or Short circuit. Check power output from PCB to fan motor. Check rotation feedback circuit. More modern units use inverter fan motors, which are powered by a DC Voltage. In reality these fan motors are AC fan motors with a small inverter-type circuit build inside. This inverter circuit is integrated with the fan motor and impossible to replace, you have to replace the entire fan motor. Similar to inverter-controlled compressors, the speed of these fan motors can be changed to whatever is needed (within certain limits). In practice the change in fan speed is not continuous but certain fixed speeds have been programmed inside the AC unit. This type of fan control can be recognized by the 5 wires coming from the fan on a connector with 7 possible connections These fan motors have 5 connections, power supply is 360VDC, and the speed is determined by a voltage ranging from 0 (0 rpm) to 5VDC (max speed) and a power supply for the internal electronics of 15VDC. These motors are easy to identify from a wiring diagram, they always show them not connected to anything as the electronics are too difficult to draw on the diagram. Detail of Hall Sensors A Hall effect sensor works like a magnetic reed switch, one end is wired to a 15 Vdc supply and the other is the feed back to the PCB. As a magnet mounted on the rotor of the motor passes the hall sensor the reed switch closes momentarily and allows the DC signal to flow through it back to the PCB. The hall sensors have a resistance so the voltage fed back to the PCB will only be approximately 12V DC. The pcb will know what speed the fan motor should be turning as it is also controlling the output of the inverter, if there is a discrepancy between the inverter output RPM and the feedback from the hall sensors a fault will occur. Usually the fan will rev very fast for a few seconds then stop this indicates hall sensor problems. Replace either Motor or Fan PCB as necessary. Fault Code 73 Check and repair or replace as necessary: 1. Overload operation (Pipe restrictions / Restricted Airflow / EEV defect / Refrig. Overcharged) 2. Compressor damage (Insulation damage / Motor damage) 3. Input Voltage abnormal 4. Power supply wiring abnormal 5. Inverter PCB assembly damage Fault Code 105 This is due to a Communication error between the Main outdoor PCB and Fan PCB. Check for Open/Short of communication line between the Main and Fan PCB s. Check communication cable plug connections. Is the communication LED on?

26 Testing Inverters It is best to test inverters with no compressors connected especially if you expect the compressor is at fault. But if you remove the wires from the compressor and try to run the systems a fault will be displayed. The fault is caused by the inverter PCB being able to detect whether a compressor is connected or not. Most modern inverters are able to detect whether the compressor has been disconnected in only a few seconds making testing very difficult. Testing can be done in two ways: Firstly the hard way... You will need a digital multi meter with a min max function, Turn off the power Disconnect the compressor either from the PCB or at the compressor terminals. Connect your meter to two of the phases (Red to blue) set your meter to record max and min voltage Power up and Start the unit Let the inverter start and watch the Voltage rise Record the maximum Voltage The inverter will stop after a few seconds and the voltage will fall to 0 Swap the leads to measure the next two phases (Red to Yellow). Measure as before Repeat for the last two phases Blue to Yellow. The readings of maximum voltage should be the same for all 3 measurements if not the inverter is faulty, the PCB will need replacing. If the readings are equal the Inverter is healthy and the compressor will need replacing. And the easy way: You will need an LG Inverter tester, Turn off the power Disconnect the compressor lead from the compressor terminals. Connect your inverter tester to all 3 leads (polarity is not important) Power up and Start the unit Let the inverter start and watch the led s All 6 must light up and should be of equal brightness The inverter will stop after a few seconds and the led s will go out If you miss the led s (they will only light for a couple of seconds) the unit will try to start again 3 times with a 3 minute delay between each test If all 6 led s DON T light up the inverter is faulty, the PCB will need replacing. If the led s all light up the Inverter is healthy and the compressor will need replacing. 26

27 27

28 28

29 Testing the inverter circuit diodes using a diode tester Many multi-meters have a diode test facility, which can be used as shown below. This tests the diodes but does not dhow whether they are powered-up. An inverter tester does indicate that the diodes are powered. 1.3 Measures for Main Error Codes CH21 (Comp IPM Fault) IPM Check Purpose Judgment of the IPM part fault of PCB assembly. Items for checking 1. Judgment of damage of IGBT 2. Checking the soldering state How to check IPM IGBT (Diode Mode) 1. Remove the connector from PCB. 2. Set the Multi-Tester as Diode Voltage Measurement Mode. ( ) 3. Measure the voltages of P~U / P~V / P~W as shown in Fig Measure the voltages of U~Nu / V~Nu / W~Nu as shown in Fig If the measurements are significantly different from the levels shown in the figures, the IPM is deemed to be damaged Copyright 2010@LG Electronics / AC Company All Rights Reserved 25 Service Engineering Inverter Guide [Fig. 1] P W V U Nu Nv Nw ~ 0.6 V P W V U Nw Nv Nu Black Red Black Red Sequence of Measurement Measure ment Normal Standards 1 P-U 0.4V~0.6V 2 P-V 0.4V~0.6V 3 P-W 0.4V~0.6V Sequence of Measurement [Fig. 2] Measure ment Normal Standards 1 U-Nu 0.4V~0.6V 2 V-Nv 0.4V~0.6V 3 W-Nw 0.4V~0.6V 0.4 ~ 0.6 V 29

LG Air Conditioning - Universal Split Fault Codes Sheet. Universal Split Systems

LG Air Conditioning - Universal Split Fault Codes Sheet. Universal Split Systems Universal Split Systems If there is a fault on any LG Universal unit, a two digit number will appear on the remote controllers led display. If the unit does not have a remote controller the fault will

More information

LG Air Conditioning Multi F(DX) Fault Codes Sheet. Multi Split Units

LG Air Conditioning Multi F(DX) Fault Codes Sheet. Multi Split Units Multi Split Units If there is a fault on any LG Multi unit, an Error mark is indicated on the display window of the indoor unit, wired-remote controller, and LED s of outdoor unit control board. A two

More information

Indoor coil is too warm in cooling mode or too cold in heating mode. Reversing valve or coil thermistor is faulty

Indoor coil is too warm in cooling mode or too cold in heating mode. Reversing valve or coil thermistor is faulty Codes Room Air Conditioner range: Indoor unit alarm s If timer lamp flashes for 1 second on, 1 second off, this indicates pre heating on the coil during heating mode and is not an error. If timer lamp

More information

SERVICE INSTRUCTION R410A. WALL MOUNTEDtype INVERTER SPLIT TYPE ROOM AIR CONDITIONER. Models Indoor unit Outdoor unit

SERVICE INSTRUCTION R410A. WALL MOUNTEDtype INVERTER SPLIT TYPE ROOM AIR CONDITIONER. Models Indoor unit Outdoor unit SERVICE INSTRUCTION SPLIT TYPE ROOM AIR CONDITIONER WALL MOUNTEDtype INVERTER Models Indoor unit Outdoor unit ASYG07LECA ASYG09LECA ASYG12LECA ASYG14LECA AOYG07LEC AOYG09LEC AOYG12LEC AOYG14LEC R410A CONTENTS

More information

PANASONIC TROUBLE SHOOTING GUIDE

PANASONIC TROUBLE SHOOTING GUIDE A General Guide To Room Style Products Pipework Pipe sizes and lengths should be as the relevant Technical Guide Both lines should be insulated No line accessories or oil traps should be fitted In cooling

More information

SERVICE INSTRUCTION R410A. WALL MOUNTEDtype SPLIT TYPE ROOM AIR CONDITIONER INVERTER. Models Indoor unit Outdoor unit AOU 9RLFW AOU12RLFW AOU15RLS

SERVICE INSTRUCTION R410A. WALL MOUNTEDtype SPLIT TYPE ROOM AIR CONDITIONER INVERTER. Models Indoor unit Outdoor unit AOU 9RLFW AOU12RLFW AOU15RLS SERVICE INSTRUCTION SPLIT TYPE ROOM AIR CONDITIONER WALL MOUNTEDtype INVERTER Models Indoor unit Outdoor unit ASU 9RLF ASURLF ASU5RLS AOU 9RLFW AOURLFW AOU5RLS R40A CONTENTS. DESCRIPTION OF EACH CONTROL

More information

SERVICE INSTRUCTION R410A. SPLIT TYPE ROOM AIR CONDITIONER Universal Floor / Ceiling Duct / Cassette Wall Mounted / Floor type INVERTER MULTI

SERVICE INSTRUCTION R410A. SPLIT TYPE ROOM AIR CONDITIONER Universal Floor / Ceiling Duct / Cassette Wall Mounted / Floor type INVERTER MULTI SERVICE INSTRUCTION SPLIT TYPE ROOM AIR CONDITIONER Universal Floor / Ceiling Duct / Cassette Wall Mounted / Floor type INVERTER MULTI R410A Models Indoor unit Outdoor unit AB*14LBAJ AB*18LBAJ AB*F14LAT

More information

R22. K Control. Indoor Unit. Nomenclature. Compatibility PL H 3 G K H B. Unit style Heat Pump Horse Power

R22. K Control. Indoor Unit. Nomenclature. Compatibility PL H 3 G K H B. Unit style Heat Pump Horse Power R22. K Control. Indoor Unit. Nomenclature. PL H 3 G K H B Compatibility Unit style Heat Pump Horse Power Control Boost Heaters R22. K Control. Outdoor Unit. Nomenclature. PU H 3 Y K A Compatibility Outdoor

More information

14. Troubleshooting Guide

14. Troubleshooting Guide 14. Guide 14.1 Refrigeration Cycle System In order to diagnose malfunctions, ensure the air conditioner is free from electrical problems before inspecting the refrigeration cycle. Such problems include

More information

Failure code manual. content

Failure code manual. content Failure code manual content 一 wall split AC series 2 二 floor standing AC series. 4 三 portable AC series.. 5 四 dehumidifer 6 五 DC inverter single split series...7 六 DC inverter multi-split series 10 1 一

More information

SERVICE MANUAL. Room Air Conditioner Multi Split type Outdoor unit /R410A DC Inverter/

SERVICE MANUAL. Room Air Conditioner Multi Split type Outdoor unit /R410A DC Inverter/ SERVICE MANUAL Room Air Conditioner Multi Split type Outdoor unit /R410A DC Inverter/ FS2MI-147HFD FS2MI-187HFD FS3MI-217HFD FS3MI-277HFD FS4MI-277HFD FS4MI-367HFD FS5MI-367HFD NOTE: Before servicing the

More information

Si10-417_C. Pocket Manual. Service Diagnosis SPLIT & MULTI

Si10-417_C. Pocket Manual. Service Diagnosis SPLIT & MULTI Pocket Manual Service Diagnosis SPLIT & MULTI Service Diagnosis SPLIT & MULTI 1. Troubleshooting with LED...5 1.1 Indoor Unit... 5 1.2 Outdoor Unit... 10 2. Troubleshooting by Symptoms...11 2.1 Air conditioner

More information

Service manual. The voltage in P3 and P4 in outdoor PCB is high voltage about 310V The voltage in P5 and P6 in outdoor PCB is high voltage about 310V

Service manual. The voltage in P3 and P4 in outdoor PCB is high voltage about 310V The voltage in P5 and P6 in outdoor PCB is high voltage about 310V Resistance The voltage in P3 and P4 in outdoor PCB is high voltage about 310V The voltage in P5 and P6 in outdoor PCB is high voltage about 310V 9.2 Troubleshooting for indoor unit E0 E1 E2 E3 E5 E6 P0

More information

1 4. 3 4-2 ABNORMAL OPERATION. 4-2-1 Error code Display. Specifics Error Code. Subsection Error Code. Subsection and Specifics Error code target

1 4. 3 4-2 ABNORMAL OPERATION. 4-2-1 Error code Display. Specifics Error Code. Subsection Error Code. Subsection and Specifics Error code target 4-2 ABNORMAL OPERATI 4-2-1 An is represented by 3 digit characters. The first 2 digit means the subsection, and the last 1 digit means the specifics. Ex.) Indoor unit Network communication Error Subsection

More information

Technical service manual 2009

Technical service manual 2009 MULTI SPLIT TYPE, HEAT PUMP AIR CONDITIONERS Technical service manual 2009 KSIM MULTI ZONE SERIES R410A DC Inverter multi Series Models KSIM20912-H216 KSIM30912-H216 KSIM40912-H216 CONTENT 1. Product features

More information

sip Sanyo Modbus Guide Technical Specification Pinouts, Cable Connections & Wiring Issue 2: February 2009 Synapsys Solutions Ltd, all rights reserved

sip Sanyo Modbus Guide Technical Specification Pinouts, Cable Connections & Wiring Issue 2: February 2009 Synapsys Solutions Ltd, all rights reserved Sanyo Section : Section : Section : Section : Section : sip Modbus Guide Configuration Modbus Table Technical Specification Pinouts, Cable Connections & Wiring Alarm Fault Codes Issue : February 009 Section

More information

Service manual. Website: www.andico.com.au CAUTION - BEFORE SERVICING THE UNIT, READ THE SAFETY - PRECAUTIONS IN THIS MANUAL.

Service manual. Website: www.andico.com.au CAUTION - BEFORE SERVICING THE UNIT, READ THE SAFETY - PRECAUTIONS IN THIS MANUAL. Website: www.andico.com.au Service manual CAUTION - BEFORE SERVICING THE UNIT, READ THE SAFETY - PRECAUTIONS IN THIS MANUAL. - ONLY FOR AUTHORISED SERVICE PERSONNEL. MODELS: MPK1-09CR-QB8 MPK1-12ER-QB6

More information

13. Troubleshooting. Indoor unit s LED indication of Corona DC inverter unit. Indoor unit s LED indication of Alfa DC inverter unit

13. Troubleshooting. Indoor unit s LED indication of Corona DC inverter unit. Indoor unit s LED indication of Alfa DC inverter unit Troubleshooting 13. Troubleshooting Indoor unit s LED indication of Corona DC inverter unit MCAC-HTSM-2007-11 E0 E1 E2 E3 E5 E6 P0 P1 P2 P3 P5 EEPROM error outdoor communication error Zero-crossing examination

More information

LG Checkpoint-codes. Versie 2.4P-M vervangt U02.3.M

LG Checkpoint-codes. Versie 2.4P-M vervangt U02.3.M LG LG Checkpoint-s Versie 2.4P-M vervangt U02.3.M BEFORE SERVICING THE UNIT, READ THE SAFETY PRECAUTIONS IN THE SERVICEMANUAL. ONLY FOR AUTHORIZED SERVICE PERSONNEL. 1 Hoofdstukindeling Single A (vloer-

More information

CONTENTS 1. IMPORTANT NOTICE 2 2. TECHNICAL SPECIFICATION 3 3. OPERATION DETAILS 4 4. WIRING DIAGRAM 11 5. EXPLOSION VIEW 12 6.

CONTENTS 1. IMPORTANT NOTICE 2 2. TECHNICAL SPECIFICATION 3 3. OPERATION DETAILS 4 4. WIRING DIAGRAM 11 5. EXPLOSION VIEW 12 6. TCL WALL MOUNTED SPLIT-TYPE AIR CONDITIONERS SERVICE MANUAL No.TE051220 Models TAC-09CHSA/GI TAC-12CHSA/GI CONTENTS 1. IMPORTANT NOTICE 2 2. TECHNICAL SPECIFICATION 3 3. OPERATION DETAILS 4 4. WIRING DIAGRAM

More information

543-0032-00, 943-0032-00. User s Manual

543-0032-00, 943-0032-00. User s Manual 543-0032-00, 943-0032-00 User s Manual 1 Comfort Alert Diagnostics Faster Service And Improved Accuracy The Comfort Alert diagnostics module is a breakthrough innovation for troubleshooting heat pump and

More information

Technical Information

Technical Information Date of last update: Oct-11 Ref: D7.8.4/1011/E Application Engineering Europe CORESENSE DIAGNOSTICS FOR STREAM REFRIGERATION COMPRESSORS CoreSense Diagnostics for Stream Refrigeration Compressors... 1

More information

USER S MANUAL HSC-24A

USER S MANUAL HSC-24A AIRREX AIR CONDITIONER USER S MANUAL HSC-24A Thank you for purchasing an AIRREX AIR CONDITIONER. BEFORE operation please read this user s manual carefully. Keep this manual readily available. It is ESSENTIAL

More information

SERVICE MANUAL SPLIT SYSTEM ROOM AIR CONDITIONER SHARP CORPORATION SHARP CORPORATION CONTENTS

SERVICE MANUAL SPLIT SYSTEM ROOM AIR CONDITIONER SHARP CORPORATION SHARP CORPORATION CONTENTS SERVICE MANUAL SPLIT SYSTEM ROOM AIR CONDITIONER INDOOR UNIT AH-129 AH-MP14 OUTDOOR UNIT AU-129 AU-MP14 CONTENTS SPECIFICATIONS...2 EXTERNAL DIMENSIONS...4 WIRING DIAGRAMS...5 ELECTRICAL PARTS...6 MICROCOMPUTER

More information

Haier Air conditioner

Haier Air conditioner For Europe Haier Air conditioner HAND in HAND HIGHER and HIGHER Page:1 For Europe HSU-09/12HVA103/R2(DB) HSU-09/12RHA103/R2(DB) Page:2 Error Codes and Description indoor and outdoor display(1) indoor Code

More information

Repair Guideline for TCL DC Inverter Air Conditioner

Repair Guideline for TCL DC Inverter Air Conditioner Repair Guideline for TCL DC Inverter Air Conditioner FLOS SERIE---V3 0 CONTENTS Ⅰ. Introduction of New control board for outdoor unit...2 1. The structure of control board... 2 2. Diagram of outdoor unit........4

More information

Technical service manual

Technical service manual GD Midea Refrigeration Equipment Co.,Ltd ODMI-A-1202 MULTI SPLIT TYPE, HEAT PUMP AIR CONDITIONERS Technical service manual R410A Multi DC inverter 220~240V-1Ph-50Hz Outdoor units Models M2OC-14HRDN1 M2OC-14HRDN1-Q

More information

SERVICE MANUAL 12VDC WALL THERMOSTAT AIR CONDITIONING SYSTEMS ROOFTOP UNITS ONLY

SERVICE MANUAL 12VDC WALL THERMOSTAT AIR CONDITIONING SYSTEMS ROOFTOP UNITS ONLY SERVICE MANUAL 12VDC WALL THERMOSTAT AIR CONDITIONING SYSTEMS ROOFTOP UNITS ONLY! WARNING - SHOCK HAZARD! TO PREVENT THE POSSIBILITY OF SEVERE PERSONAL INJURY, DEATH, OR EQUIPMENT DAMAGE DUE TO ELECTRICAL

More information

Room Air Conditioner SVC MANUAL(General)

Room Air Conditioner SVC MANUAL(General) Internal Use Only http://biz.lgservice.com Room Air Conditioner SVC MANUAL(General) MODEL : General Wall Mounted-Inverter Type CAUTION Before Servicing the unit, read the safety precautions in General

More information

Instruction manual for Firstline FCS12000CH

Instruction manual for Firstline FCS12000CH Instruction manual for Firstline FCS12000CH Contents Introduction... 2 Safety Awareness... 3 Safety Awareness... 4 Name of Parts... 5 Name of Parts... 6 Remote Controller Preparation... 7 Operation of

More information

Panasonic/Sanyo A/C Interface Modbus RTU Installation Instructions

Panasonic/Sanyo A/C Interface Modbus RTU Installation Instructions Panasonic/Sanyo A/C Interface Modbus RTU Installation Instructions Preface Safety warnings To avoid injury, or damage to the Modbus interface, read all installation and configuration instructions in this

More information

SERVICE MANUAL FOR 6535 SERIES TWO TON HIGH EFFICIENCY PACKAGED HEAT PUMPS

SERVICE MANUAL FOR 6535 SERIES TWO TON HIGH EFFICIENCY PACKAGED HEAT PUMPS SERVICE MANUAL FOR 6535 SERIES TWO TON HIGH EFFICIENCY PACKAGED HEAT PUMPS TABLE OF CONTENTS 1. Warnings...2 2. Accessibility Of Appliance...3 3. Unit Dimensions And Specifications...3 4. Unit Specifications

More information

FILE NO. SVM-07013 11. HOW TO DIAGNOSE THE TROUBLE

FILE NO. SVM-07013 11. HOW TO DIAGNOSE THE TROUBLE FILE. SVM-070. HOW TO DIAGSE THE TROUBLE The pulse motor circuits are mounted to both indoor and outdoor units. Therefore, diagnose troubles according to the trouble diagnosis procedure as described below.

More information

SERVICE MANUAL. Room Air Conditioner Multi Split Wall-Mounted Type Indoor. FSAI-Pro-91AE2 FSAI-Pro-121AE2 FSAIF-Pro-181AE2

SERVICE MANUAL. Room Air Conditioner Multi Split Wall-Mounted Type Indoor. FSAI-Pro-91AE2 FSAI-Pro-121AE2 FSAIF-Pro-181AE2 SERVICE MANUAL Room Air Conditioner Multi Split Wall-Mounted Type Indoor FSAI-Pro-91AE2 FSAI-Pro-121AE2 FSAIF-Pro-181AE2 NOTE: Before servicing the unit, please read this at first. Always contact with

More information

Simple Self-Diagnosis by Malfunction Code

Simple Self-Diagnosis by Malfunction Code Simple Self-Diagnosis by Code After Sales Service Division (SM-TS2) Detail Division 0 Indoor Unit System Others A C E F H J L P U M 7 8 9 External device activated (unified) Protection devices activated

More information

Fan Coil EC Motor Control

Fan Coil EC Motor Control Fan Coil EC Motor Control G3 PWM BARD The Enviro-Tec Generation 3 PWM (G3 PWM) board provides a pulse-width modulated (PWM) signal to the EC motor to control fan speed. The board is factory programmed

More information

Heater and Air Conditioner, Blend Air System, Troubleshooting 83.06

Heater and Air Conditioner, Blend Air System, Troubleshooting 83.06 A/C Performance Diagnosis Problem Warm Airflow When the Air Conditioner is On, A/C Not Working, or Poor A/C Performance (dash outlet temperature is too high) Problem Warm Airflow When the Air Conditioner

More information

LG Air conditioning Company Multi V Water Ⅱ. Air Conditioning Academy

LG Air conditioning Company Multi V Water Ⅱ. Air Conditioning Academy LG Air conditioning Company Multi V Water Ⅱ Air Conditioning Academy 1.1 What is Multi V Water II? High Performance Prospect rights Water pipe Refrigerant pipe Indoor unit Beautiful Exterior Convenience

More information

Portable Air Conditioner. OWNER S MANUAL Read these instructions before use. Model: MF08CESWW. Voltage rating: 115V~60Hz Power rating : 800W

Portable Air Conditioner. OWNER S MANUAL Read these instructions before use. Model: MF08CESWW. Voltage rating: 115V~60Hz Power rating : 800W MODE ALARM Portable Air Conditioner OWNER S MANUAL Read these instructions before use 8 Model: MF08CESWW Voltage rating: 115V~60Hz Power rating : 800W Customer Support : 1-800-474-2147 For product inquiries

More information

Model: AC-S13CG x 2. Model No: AC-S13CGx2.doc Version 1.0

Model: AC-S13CG x 2. Model No: AC-S13CGx2.doc Version 1.0 Air Conditioner Service Manual 2 3 Model: AC-S13CG x 2 3 Content Technical specification.. 4 Performance curve.5 Outline & dimension of indoor unit..10 Outline & dimension of outdoor unit 11 Exploded view

More information

Section 7. Evaporator thermistor. Under-and-over pressure safety switches. Connections to the ECU

Section 7. Evaporator thermistor. Under-and-over pressure safety switches. Connections to the ECU Automatic Temperature Control Diagnosis and Repair Diagnosis of Automatic A/C Systems The most common automatic A/C system malfunctions tend to be the result of basic air conditioning problems. These problems

More information

Portable Air Conditioner

Portable Air Conditioner Portable Air Conditioner Owner's Manual Model:3 in 1 12,000 Btu/h Series 3 Please read this owner s manual carefully before operation and retain it for future reference. CONTENTS 1. SUMMARY...1 2. PORTABLE

More information

ELECTRIC CENTRAL HEATING FLOW BOILER

ELECTRIC CENTRAL HEATING FLOW BOILER ELECTRIC CENTRAL HEATING FLOW BOILER EKCO.T Used product can t be treated as general communal waste. Disassembled appliance has to be delivered to the collection point of electrical and electronic equipment

More information

INSTALLER S & OWNER S MANUAL

INSTALLER S & OWNER S MANUAL INSTALLER S & OWNER S MANUAL HVAC INSTALLER: PLEASE LEAVE MANUAL FOR HOMEOWNER DEH 3000 DEH 3000 Part No. 4028539 Dehumidifier & Ventilation System Controller P.O. Box 8680 Madison, WI 53708 TOLL-FREE

More information

INSTALLATION GUIDE. Card Reader & Controller with KIM Swipe Reader for Solitaire 850 / 950 / 850L Learnlok PK2930

INSTALLATION GUIDE. Card Reader & Controller with KIM Swipe Reader for Solitaire 850 / 950 / 850L Learnlok PK2930 INSTALLATION GUIDE Card Reader & Controller with KIM Swipe Reader for Solitaire 850 / 950 / 850L Learnlok PK2930 Card Reader and Controller Model 3.5 with KIM Swipe Reader Table of Contents 1. Features..................................

More information

A/C-HEATER SYSTEM - AUTOMATIC

A/C-HEATER SYSTEM - AUTOMATIC A/C-HEATER SYSTEM - AUTOMATIC 1995 Volvo 850 1995-96 Auto. A/C-Heater Systems Volvo 850 * PLEASE READ THIS FIRST * WARNING: To avoid injury from accidental air bag deployment, read and carefully follow

More information

its ELECTRIC POSITION for electric heat, or set the units fan control appropriately to ELECTRIC or another appropriate setting.

its ELECTRIC POSITION for electric heat, or set the units fan control appropriately to ELECTRIC or another appropriate setting. Troubleshooting Poor Temperature Regulation This page lists problems that may affect the temperature performance of your LUX thermostat with suggested resolutions. For more detailed information please

More information

*.ppt 11/2/2009 12:48 PM 1

*.ppt 11/2/2009 12:48 PM 1 Digital Compressor Controller *.ppt 11/2/2009 12:48 PM 1 Copeland Scroll Digital Controller Simple Controller That Enables OEM s To Use Digital Scrolls Relieves OEM From Developing Special Controllers

More information

Repair Guideline for SANYO New Erp. DC Inverter Air Conditioner (Published in May, 2013)

Repair Guideline for SANYO New Erp. DC Inverter Air Conditioner (Published in May, 2013) Repair Guideline for SANYO New Erp DC Inverter Air Conditioner (Published in May, 2013) Contents I. Electronic Control of DC Inverter Air Conditioner 2 1. Main parts of the electronic control of DC inverter

More information

technical data air conditioning systems RXS20-25-35E (single phase) FBQ-B8V1-B8V3B Split Heat Pump Condensing Units Split Sky Air

technical data air conditioning systems RXS20-25-35E (single phase) FBQ-B8V1-B8V3B Split Heat Pump Condensing Units Split Sky Air technical data RXS20-25-35E FBQ-B8V-B8V3B (single phase) Split Heat Pump Condensing Units air conditioning systems Split Sky Air Outdoor Units R-40A RXS-E2VB Split Sky Air Outdoor Units Features O u t

More information

NX Series Inverters. HVAC Pocket Programming Guide

NX Series Inverters. HVAC Pocket Programming Guide NX Series Inverters HVAC Pocket Programming Guide HVAC Pocket Programming Guide HVAC Pocket Programming Guide / Contents This guide provides a single reference document for the user of NXL HVAC (product

More information

SERVICE MANUAL MUZ-GE09NA MUZ-GE12NA MUZ-GE15NA MUZ-GE18NA MUZ-GE24NA MUY-GE09NA MUY-GE12NA MUY-GE15NA MUY-GE18NA MUY-GE24NA OUTDOOR UNIT

SERVICE MANUAL MUZ-GE09NA MUZ-GE12NA MUZ-GE15NA MUZ-GE18NA MUZ-GE24NA MUY-GE09NA MUY-GE12NA MUY-GE15NA MUY-GE18NA MUY-GE24NA OUTDOOR UNIT SPLIT-TYPE AIR CONDITIONERS Revision B: Descriptions regarding the outdoor fan motor have been corrected. Please void OBH549 REVISED EDITION-A. OUTDOOR UNIT SERVICE MANUAL HFC utilized R410A. OBH549 REVISED

More information

Programmable Thermostat MODEL 3312026.XXX With Dehumidify 3312024.XXX With Out Dehumidify

Programmable Thermostat MODEL 3312026.XXX With Dehumidify 3312024.XXX With Out Dehumidify Comfort Control Center 2 Thermostat Operating Instructions Programmable Thermostat MODEL 3312026.XXX With Dehumidify 3312024.XXX With Out Dehumidify TABLE OF CONTENTS About your new thermostat Features...2

More information

MAKING MODERN LIVING POSSIBLE. UniLynx Indoor User Manual. ULX 1800i ULX 3000i ULX 3600i ULX 5400i SOLAR INVERTERS

MAKING MODERN LIVING POSSIBLE. UniLynx Indoor User Manual. ULX 1800i ULX 3000i ULX 3600i ULX 5400i SOLAR INVERTERS MAKING MODERN LIVING POSSIBLE UniLynx Indoor User Manual ULX 1800i ULX 3000i ULX 3600i ULX 5400i SOLAR INVERTERS Contents Contents 1. Introduction 2 Introduction 2 2. Function Description 3 Definition

More information

Single Zone LCD Thermostat Operating Instructions

Single Zone LCD Thermostat Operating Instructions Fan Cool Furnace *Heat Pump or Heat Strip On/Off F Single Zone LCD Thermostat Operating Instructions MODEL 3313192.XXX Cool/Furnace 3313193.XXX Cool/Furnace/Heat Pump 3313194.XXX Cool/Furnace/Heat Strip

More information

TAS-18MVHN/O TAS-27MVHN/O TAS-36MVHN/O

TAS-18MVHN/O TAS-27MVHN/O TAS-36MVHN/O SERVICE MANUAL AIRCONDITIONER DC INVERTER MULTI TYPE TAS-18MVHN/O TAS-27MVHN/O TAS-36MVHN/O DC MULTI OUTDOOR UNITS CONTENTS 1. General information of Outdoor Units... 3 2. Dimensions... 4 3. Wiring Diagram...

More information

Portable Air Conditioner. OWNER S MANUAL Read these instructions before use. Model: MM14CHCSCS

Portable Air Conditioner. OWNER S MANUAL Read these instructions before use. Model: MM14CHCSCS Portable Air Conditioner OWNER S MANUAL Read these instructions before use Model: MM14CHCSCS Voltage rating: 120V~60Hz Power rating : 1400W(Cooling) Power rating : 1350W(Heating) Customer Support : 1-800-474-21477

More information

T-100-R Installation Guide

T-100-R Installation Guide T-100-R Installation Guide Table of Contents Page 2 Overview T-100-R Z-Wave Thermostat 3-4 Installation HVAC System Setup 6 Installer Settings Menu Items 7-9 Installer Settings Summary 10-11 Wiring Standard

More information

SERVICE MANUAL INDOOR UNIT

SERVICE MANUAL INDOOR UNIT SPLIT-TYPE AIR CONDITIONERS Revision B: "How to check miswiring and serial signal error" for MUZ type has been added. The description about "Low standby power control" has been added to "TECHNICAL CHANGES".

More information

TECHNICAL SERVICE DEPARTMENT Technical Service Bulletin 1-800-432-8373. 2 Inch PowerVent LED Indicator Explanations & Troubleshooting Table

TECHNICAL SERVICE DEPARTMENT Technical Service Bulletin 1-800-432-8373. 2 Inch PowerVent LED Indicator Explanations & Troubleshooting Table New Robertshaw control valve was introduced in May 2008 as a replacement part. See last page for troubleshooting this replacement part. All voltage inputs are 120V. All electrical connectors are Molex

More information

OWNER S MANUAL VMH 09/12/18/27/36 InverterFlex

OWNER S MANUAL VMH 09/12/18/27/36 InverterFlex OWNER S MANUAL VMH 09/12/18/27/36 InverterFlex Version C Single, Dual, Tri or Quad Zone Ductless Mini-Split System Heat Controller, Inc. 1900 Wellworth Ave. Jackson, MI 49203 (517)787-2100 www.heatcontroller.com

More information

Portable Air Conditioner. OWNER S MANUAL Read these instructions before use. Model: MM14CCS. Voltage rating: 115V~60Hz Power rating : 1400W

Portable Air Conditioner. OWNER S MANUAL Read these instructions before use. Model: MM14CCS. Voltage rating: 115V~60Hz Power rating : 1400W Portable Air Conditioner OWNER S MANUAL Read these instructions before use Model: MM14CCS Customer Support : 1-800-474-2147 Voltage rating: 115V~60Hz Power rating : 1400W For product inquiries or support

More information

Installation and maintenance instructions. Danfoss Vent

Installation and maintenance instructions. Danfoss Vent Installation and maintenance instructions Danfoss Vent 1 Unit design... 2 2 Project planning and installation instructions... 3 2.1 Ventilation...3 2.2 Piping installation....3 2.3 Condensation line...4

More information

HP 5 Microprocessor Control for Mammoth Water Source Heat Pumps

HP 5 Microprocessor Control for Mammoth Water Source Heat Pumps HP 5 Microprocessor Control for Mammoth Water Source Heat Pumps Operation and Maintenance Manual Model: 71028004 Applies to: Single Circuit Water-to-Water Twin Circuit Units Without DDC Controls MAMM WHSP

More information

york air-conditioning products Residential & VRF News 2015

york air-conditioning products Residential & VRF News 2015 york air-conditioning products Residential & VRF News 2015 york air-conditioning products Catalogue Content Split Systems Pag. High wall High Efficiency Inverter YWHJZH 09 to 24 K 6 High wall Inverter

More information

Portable Air Conditioner. OWNER S MANUAL Read these instructions before use. Model: MN12CES / MN10CESWW

Portable Air Conditioner. OWNER S MANUAL Read these instructions before use. Model: MN12CES / MN10CESWW Portable Air Conditioner OWNER S MANUAL Read these instructions before use 8 Model: MN12CES / MN10CESWW Voltage rating: 120V~60Hz Power rating : 1100W (MN12CES) Power rating : 900W (MN10CESWW) Customer

More information

Panel Mounted Air Conditioners by Dantherm, Inc.

Panel Mounted Air Conditioners by Dantherm, Inc. Panel Mounted Air Conditioners by Dantherm, Inc. CS020020A/B with USACG-6 Control PRODUCT INFORMATION MANUAL AC-2 CS020020 USACG-6 Manual Rev H Page 1 of 17 Dantherm, Inc. 110 Corporate Drive, Suite K

More information

HITACHI INVERTER-DRIVEN MULTI-SPLIT SYSTEM HEAT PUMP AIR CONDITIONERS

HITACHI INVERTER-DRIVEN MULTI-SPLIT SYSTEM HEAT PUMP AIR CONDITIONERS HITACHI INVERTER-DRIVEN MULTI-SPLIT SYSTEM HEAT PUMP AIR CONDITIONERS SET FREE FSG(1)/FS3, FS5 SERIES AND SET FREE FXG/FX3 SERIES Models In-the-Ceiling Type RPI-0.8FSG1 RPI-2.5FSG1 RPI-8FSG1

More information

HVAC-32A. Operation Manual. Specifications. Digital Multistage Air Conditioning Controller with inbuilt Outside Air Economy function

HVAC-32A. Operation Manual. Specifications. Digital Multistage Air Conditioning Controller with inbuilt Outside Air Economy function Specifications Supply Voltage 240VAC @ 0.07Amps or 24VAC @ 0.380Amps Relays 240V @ 12A max (resistive) / Comp1,2,3, Aux Ht, Rv O/B) Fuses (Equipment) 15 Amps Maximum 3AG Control Range Minus 10 to 50C Control

More information

CONTENTS 1. IMPORTANT NOTICE 2 2. TECHNICAL SPECIFICATION 3 3. OPERATION DETAILS 4 4. ELECTRICAL SCHEMATIC DIAGRAM 13 5. EXPLOSION VIEW 16 6

CONTENTS 1. IMPORTANT NOTICE 2 2. TECHNICAL SPECIFICATION 3 3. OPERATION DETAILS 4 4. ELECTRICAL SCHEMATIC DIAGRAM 13 5. EXPLOSION VIEW 16 6 TCL WALL MOUNTED SPLIT-TYPE AIR CONDITIONERS SERVICE MANUAL No.TE080528 Models KFTHP-12 KFTHP-18 KFTHP-24 CONTENTS 1. IMPORTANT NOTICE 2 2. TECHNICAL SPECIFICATION 3 3. OPERATION DETAILS 4 4. ELECTRICAL

More information

SERVICE MANUAL MUZ-FE09NA MUZ-FE12NA MUZ-FE18NA OUTDOOR UNIT. No. OBH543 REVISED EDITION-A. Models HFC

SERVICE MANUAL MUZ-FE09NA MUZ-FE12NA MUZ-FE18NA OUTDOOR UNIT. No. OBH543 REVISED EDITION-A. Models HFC SPLIT-TYPE AIR CONDITIONERS Revision A: MUZ-FE18NA has been added. Please void OBH543. OUTDOOR UNIT SERVICE MANUAL HFC utilized R410A. OBH543 REVISED EDITION-A Models MUZ-FE09NA MUZ-FE12NA MUZ-FE18NA Indoor

More information

EVANS ELECTRONIC TEMPERATURE CONTROL TROUBLESHOOTING GUIDE for systems equipped with electric coolant valve and external PC board.

EVANS ELECTRONIC TEMPERATURE CONTROL TROUBLESHOOTING GUIDE for systems equipped with electric coolant valve and external PC board. EVANS ELECTRONIC TEMPERATURE CONTROL TROUBLESHOOTING GUIDE for systems equipped with electric coolant valve and external PC board. This Troubleshooting Guide covers the electric coolant valve and control

More information

DUCT TYPE AIR CONDITIONER

DUCT TYPE AIR CONDITIONER OPERATING MANUAL OPERATING MANUAL BEDIENUNGSANLEITUNG MODE D EMPLOI MANUAL DE FUNCIONAMIENTO MANUALE DI ISTRUZIONI ΕΓΧΕΙΡΙ ΙΟ ΛΕΙΤΟΥΡΓΙΑΣ MANUAL DE INSTRUÇÕES AIR CONDITIONER DUCT TYPE English Deutsch

More information

INSTALLATION & SERVICE MANUAL. Display Panel

INSTALLATION & SERVICE MANUAL. Display Panel INSTALLATION & SERVICE MANUAL Display Panel The PowerLine EMS TM is a specialized power distribution and energy management system intended to be used in recreational vehicles. The Control Module is housed

More information

Table V. Troubleshooting Checklist for Refrigeration Systems. Air or non-condensable gas in system. Inlet water warm.

Table V. Troubleshooting Checklist for Refrigeration Systems. Air or non-condensable gas in system. Inlet water warm. Table V Troubleshooting Checklist for Refrigeration Systems TROUBLE POSSIBLE CAUSE CORRECTIVE MEASURE High condensing pressure. Low condensing pressure. Air or non-condensable gas in system. Inlet water

More information

SERVICE INSTRUCTIONS

SERVICE INSTRUCTIONS SERVICE INSTRUCTIONS 18, 20,24, 26L Integrity Electronic Gas Continuous Flow Water Heater TM031 Reevvi issi ion:: B Publissheed:: Feebrruaarryy 0088 871018 871020 871024 871024-B 871024-C 871026 871026-B

More information

TABLE 1: Wiring Terminals. Connect to... 1C 1H 2C 2H 1H1C 2H1C 2H2C 3H2C

TABLE 1: Wiring Terminals. Connect to... 1C 1H 2C 2H 1H1C 2H1C 2H2C 3H2C Installation TURN OFF POWER TO THE SYSTEM AT THE MAIN POWER PANEL TO AVOID ELECTRICAL SHOCK. Installation should be carried out by an electrician or a qualified technician. 1.1 Find a Location for the

More information

USER INSTRUCTIONS FOR GET PORTABLE 12k BTU AIR CONDITIONER MODEL No. GPACU12HR

USER INSTRUCTIONS FOR GET PORTABLE 12k BTU AIR CONDITIONER MODEL No. GPACU12HR USER INSTRUCTIONS FOR GET PORTABLE 12k BTU AIR CONDITIONER MODEL No. GPACU12HR CONTENTS Introduction Safety Notes Identification of parts Installation instructions Operation instructions Maintenance Troubleshooting

More information

Table of Contents. 1 - Specifications...3. 2 - Installation...3. 3 - Wiring...5. 4 - User controls...7

Table of Contents. 1 - Specifications...3. 2 - Installation...3. 3 - Wiring...5. 4 - User controls...7 THERMOSTATS Table of Contents Page 1 - Specifications...3 1.1 - Product range...3 ARTTH001 (DSL-610)...3 ARTTH002 (DSL-700)...3 ARTTH003 (DSL-600)...3 1.2 - Technical data...3 1.3 - Power failures...3

More information

REMOTE CONTROL MANUAL

REMOTE CONTROL MANUAL REMOTE CONTROL MANUAL ENGLISH CONTENT PRECAUTIONS...1-2 USING THE REMOTE CONTROL UNIT...3 OPERATION...4-9 Thank you for purchasing our Room Air Conditioner. Before using your air-conditioner, please read

More information

MP-4000 Alarm List (Software version 2.4.3 or later)

MP-4000 Alarm List (Software version 2.4.3 or later) Service Bulletin SUBJECT: MP4000 Alarm s BULLETIN: C 100 DATE: June 19, 2013 ALARM LIST Where it is possible the alarm number is kept the same as for MP-3000. MP-3000 holds alarm number from 0 to 127.

More information

AUTOMATIC CONTROL HEATING, VENTILATION AND AIR CONDITIONING SYSTEM

AUTOMATIC CONTROL HEATING, VENTILATION AND AIR CONDITIONING SYSTEM SECTION 7D AUTOMATIC CONTROL HEATING, VENTILATION AND AIR CONDITIONING SYSTEM TABLE OF CONTENTS Description and Operation... 7D- General... 7D- FATC Control... 7D- FATC Input/Output Routing Diagram...

More information

ICE AIR. Console Water Source Heat Pump (WSHP) OPERATING & MAINTENANCE MANUAL. Wo r l d C l a s s C o m f o r t. www.ice-air.com

ICE AIR. Console Water Source Heat Pump (WSHP) OPERATING & MAINTENANCE MANUAL. Wo r l d C l a s s C o m f o r t. www.ice-air.com 80 Hartford Avenue Mount Vernon New York 10553 Tel: 914-668-4700 EXT. 203 Fax: 914-668-5643 www.ice-air.com Wo r l d C l a s s C o m f o r t Console Water Source Heat Pump (WSHP) OPERATING & MAINTENANCE

More information

WALL MOUNTED SPLIT TYPE AIR CONDITIONER

WALL MOUNTED SPLIT TYPE AIR CONDITIONER WALL MOUNTED SPLIT TYPE AIR CONDITIONER MANUAL 8 OM-G12-ACSON CONTENTS - Operating Guide page 1 - G12 Remote Controller Indication page 2 - Indicator Lights page 4 - Installation of Aroma page 5 - Auto

More information

HEAT SIPHON ANSWERBOOK

HEAT SIPHON ANSWERBOOK ERROR CODES -Displayed on Player Board There are three different types of error codes displayed by the Digital Player Controller" 1 WARNING CODE - The Warning Code is displayed for the duration the error

More information

..OR How To Protect your 3-Phase Equipment Investment with 3-Phase Monitors from Time Mark...

..OR How To Protect your 3-Phase Equipment Investment with 3-Phase Monitors from Time Mark... ..OR How To Protect your 3-Phase Equipment Investment with 3-Phase Monitors from Time Mark... TIME MARK CORPORATION 11440 EAST PINE STREET TULSA, OK 74116 USA tel 918 438-1220 fax 918 437-7584 www.time-mark.com

More information

OWNER'S MANUAL R-410A Duct Free Split System Air Conditioner and Heat Pump

OWNER'S MANUAL R-410A Duct Free Split System Air Conditioner and Heat Pump R-410A Duct Free Split System Air Conditioner and Heat Pump Product Family: DFS4(A/H)-System, DFC4(A/H)3-Outdoor, DFF4(A/H)H-Indoor Please read the operating instructions and safety precautions carefully

More information

Single Zone Air Conditioner SVC MANUAL(General)

Single Zone Air Conditioner SVC MANUAL(General) Single Zone Air Conditioner SVC MANUAL(General) CAUTION Before Servicing the unit, read the safety precautions in General SVC manual. Only for authorized service personnel. 960-914-06 Air Conditioner Service

More information

10.1 Indoor Unit Error Display

10.1 Indoor Unit Error Display 10.1 Indoor Unit Error Display Display E0 E1 E2 E3 E5 E6 P0 P1 P2 P4 LED STATUS EEPROM parameter error Indoor / outdoor units communication protection Zero-crossing signal error Fan speed out of control

More information

Heating, Ventilation, Air Conditioning and Refrigeration (HVACR)

Heating, Ventilation, Air Conditioning and Refrigeration (HVACR) Heating, Ventilation, Air Conditioning and Refrigeration (HVACR) I. Demonstrate safety skills in typical HVACR work situations to NATE Core Installer Knowledge Areas for Technician Excellence for Safety

More information

SiBE12-625. D-Series / E-Series. [Applied Models] Inverter Multi : Cooling Only Inverter Multi : Heat Pump

SiBE12-625. D-Series / E-Series. [Applied Models] Inverter Multi : Cooling Only Inverter Multi : Heat Pump SiBE12-625 D-Series / E-Series [Applied Models] Inverter Multi : Cooling Only Inverter Multi : Heat Pump SUPER MULTI NX D-Series / E-Series Cooling Only Indoor Unit FTKS20D3VMW FTKS20CAVMB FDKS25CAVMB

More information

SERVICE MANUAL REFRIGERATION

SERVICE MANUAL REFRIGERATION SERVICE MANUAL REFRIGERATION ELECTROLUX HOME PRODUCTS S.p.A. Publication no. Spares Operations Italy 599 36 16-90 Corso Lino Zanussi, 30 031117 I - 33080 PORCIA / PN (ITALY) ITZ/SERVICE/AA Fax +39 0434

More information

HCS-3300/3302/3304 USB Remote Programmable Laboratory Grade Switching Mode Power Supply

HCS-3300/3302/3304 USB Remote Programmable Laboratory Grade Switching Mode Power Supply 1. INTRODUCTION HCS-3300/3302/3304 USB Remote Programmable Laboratory Grade Switching Mode Power Supply User Manual This family of efficient, upgraded SMPS with small form factor, auto cross over CV CC,

More information

SERVICE MANUAL INDOOR UNIT

SERVICE MANUAL INDOOR UNIT SPLIT-TYPE AIR CONDITIONERS Revision E: MSZ-GE22VAD- A1 has been added. Please void OBH531 REVISED EDITION-D. INDOOR UNIT SERVICE MANUAL. OBH531 REVISED EDITION-E Models MSZ-GE22VA - A1 MSZ-GE50VA - A1

More information

SERVICE MANUAL AE-X2M14LR MULITI SPLIT TYPE ROOM AIR CONDITIONERS (OUTDOOR UNIT) MODEL. No. S2038AEX2MLRT CONTENTS AEX2M14LR

SERVICE MANUAL AE-X2M14LR MULITI SPLIT TYPE ROOM AIR CONDITIONERS (OUTDOOR UNIT) MODEL. No. S2038AEX2MLRT CONTENTS AEX2M14LR TopPage AEX2M14LR SERVICE MANUAL. S2038AEX2MLRT MULITI SPLIT TYPE ROOM AIR CONDITIONERS (OUTDOOR UNIT) MODEL AE-X2M14LR In the interests of user-safety (Required by safety regulations in some countries)

More information

SECTION 4 ELECTRIC MOTORS UNIT 17: TYPES OF ELECTRIC MOTORS

SECTION 4 ELECTRIC MOTORS UNIT 17: TYPES OF ELECTRIC MOTORS SECTION 4 ELECTRIC MOTORS UNIT 17: TYPES OF ELECTRIC MOTORS UNIT OBJECTIVES After studying this unit, the reader should be able to Describe the different types of open single-phase motors used to drive

More information

4 Alarm and info. Alarm. Yes Warning. No Information No Reset alarms > No Current list > Alarm log list > Delete alarm log > No

4 Alarm and info. Alarm. Yes Warning. No Information No Reset alarms > No Current list > Alarm log list > Delete alarm log > No 6. 6.1 and info (Menu 4) NB are shown in the event of unit faults or irregular operation Check the Current list (Menu 4) for alarm messages and refer to the list of alarms given at the end of these instructions.

More information

ELECTRIC POSITION for electric heat, then confirm with Fan Test below.

ELECTRIC POSITION for electric heat, then confirm with Fan Test below. Troubleshooting Poor Temperature Regulation This page lists problems that may affect the temperature performance of your LUX thermostat with suggested resolutions. For more detailed information please

More information

HEAT HEAT COOL HEAT PUMP COOL

HEAT HEAT COOL HEAT PUMP COOL OWNER S MANUAL RESIDENTIAL THERMOSTAT P/N P374-1800 HEAT COOL HEAT PUMP Su AUTO 0I20: Pm 74 COOL HEAT 27 7-DAY MABLE DIGITAL THERMOSTAT 3 Configurable Outputs Accepts Optional Humidity Module: Control

More information

System. SERVICE MANUAL R410A MODEL : ARNU Series URNU Series

System. SERVICE MANUAL R410A MODEL : ARNU Series URNU Series Internal Use Only http://biz.lgservice.com System Indoor Unit R410A SERVICE MANUAL R410A MODEL : ARNU Series URNU Series CAUTI Before Servicing the unit, read the safety precautions in General SVC manual.

More information