Technical service manual 2009
|
|
|
- Imogen Tate
- 10 years ago
- Views:
Transcription
1 MULTI SPLIT TYPE, HEAT PUMP AIR CONDITIONERS Technical service manual 2009 KSIM MULTI ZONE SERIES R410A DC Inverter multi Series Models KSIM20912-H216 KSIM30912-H216 KSIM40912-H216
2 CONTENT 1. Product features 2. Dimensions 3. Refrigeration cycle diagram 4. Operation limits 5. Indoor unit combination 6. Wiring diagram 7. Electric control functions 8. Troubleshooting Annex 1 Characteristic of temp. sensor Annex 2 Reference data
3 1. Product features Indoor unit Operation by remote controller Sensing by room temperature Room temperature sensor. Pipe temperature sensor. Room temperature control Maintain the room temperature in accordance w ith the setting temperature. Anti-freezing control in cooling Prevent the water being frozen on evaporator by sensing the evaporator pipe temperature in cooling mode Time Delay Safety control Restarting is for approx. 3 minutes.. Indoor fan speed control high, med, low, breeze. Two-direction air vane The unit will decide the louver direction according to operation mode. Tele Remote control (Optional) Sleep mode auto control The fan is turn to low speed (cooling/heating). The unit will be turn off at the seventh hour. Independent dehumidification The function is usually used in rainy days in springtime or damp areas. Air flow Direction control The louver can be set at the desired position or swing up and down automatically Auto mode The mode can be change by the room temperature. Temp. Compensation Self-diag. function Anti-cold function Prevent the cold wind at the beginning of unit start. Auto defrost Auto-restart function When the power supply is interrupted and then restore, the air conditioners automatically restore the previous function setting. Flexible wiring connection
4 Outdoor unit Power relay control The unit has 3 mins delay between continuously ON/OFF operations. Low noise air flow system Bird tail propeller fan makes the outdoor unit run more quietly. Hydrophilic aluminum fin The hydrophilic fin can improve the heating efficiency at operation mode. 4 way valve control It is only operated in the heating operation mode except defrosting operation. Anti-rust cabinet Made from electrolytic zinc steel sheet and anti-rust coated components. Valve protection cover It protects the valves and prevents water from dripping. Discharge pipe temperature protect Driving heating at -15
5 2 Dimensions 2.1 KSIM MULTIZONE Series Indoor unit 9K&12K Mode Dimension W H D 9K K Outdoor unit KSIM20912-H216, KSIM30912-H216
6 b) KSIM40912-H216 3 Refrigeration Cycle Diagram 3.1 Refrigeration circuit drawing of inverter quadplex type
7 3.2 Refrigeration circuit drawing of inverter trinary type Exhaust temp. sensor Axial flow fan Main Capillary Auxiliary Capillary Capillary A Capillary B EXV A EXV B Filter A Liquid valve A Liquid valve B 4-way valve Condenser Coil temp. sensor Check Valve Capillary C Filter B EXV C Filter C Liquid valve C flow fan Cross Evaporator Indoor pipe out temp. seneor A Gas valve A Compressor Indoor pipe out temp. seneor B Gas valve B Indoor pipe out temp. seneor C Gas valve C Outdoor Unit Indoor Unit 3.3 Refrigeration circuit drawing of inverter binary type
8 4-way valve Exhaust temp. sensor Axial flow fan Condenser Coil temp. sensor Main Capillary Auxiliary Capillary Check Valve Capillary A Capillary B EXVA EXVB Filter A Filter B Liquid valve A Liquid valve B Cross flow fan Evaporator Indoor pipe out temp. seneor A Gas valve A Compressor Indoor pipe out temp. seneor B Gas valve B Outdoor Unit 4 Temperature Operation range Indoor Unit Cooling mode Heating mode Dry mode Indoor temperature Outdoor temperature Indoor temperature Outdoor temperature Indoor temperature Outdoor temperature Indoor units combination 5.1 Indoor unit combination for KSIM20912-H216 One unit Two unit Indoor unit combination for KSIM30912-H216 One unit Two unit Three unit Indoor unit combination for KSIM40912-H216 One unit Two unit Three unit Four unit
9 6. Wiring Diagram 6.1 Indoor unit (9k/12k)
10 6.2 Outdoor unit (2 ZONE) 6.3 Outdoor unit (3 ZONE)
11 6.4 Outdoor unit (4 ZONE)
12 7 Electronic control function 7.1 Electric Control working environment Input voltage: 175~253V Input power frequency:50hz Indoor fan normal working amp. is less than 1A Outdoor fan. rmal working amp. is less than 1.5A Four-way valve normal working amp. is less than 1A Swing motor: DC12V. 7.2 Icon explanation on indoor display board. OPERRATION indicator This indicator flashes after power is on and illuminates when the unit is in operation. AUTO indicator This indicator illuminates when the air conditioner is in AUTO operation. TIMER indicator This indicator illuminates when TIMER is set ON/OFF. IONIZER (CLEAN AIR) indication lamp Lights up when CLEAN AIR feature is activated and Ionizer can generate abundant anions to fill the room with refreshing and natural air. PRE-DEF. indicator This indicator illuminates when the air conditioner starts defrosting automatically or when the warm air control feature is activated in heating mode. TURBO indication lamp Lights up when select TURBO function on cooling operation or on heating operation. FREQUENCY indicator This indicator appears only when the compressor is in operation and indicates the current operating frequency. TEMPERATURE indicator Usually it displays the temperature settings. When change the setting temperature, this indicator begins to flash, and stops 20 seconds later. It displays the room temperature when the air conditioner is in FAN only operation. When the unit stops operation, it returns to
13 original factory settings. The temperature indicator area will display SC when the self clean function is started. It also displays the malfunction code or protection code. FAN SPEED indication lamp Displays the selected fan speed: AUTO (nothing) and three fan speed levels: LOW, MED and HIGH. LED display control function. Pressing LED display button on remote controller will turn off all displays on indoor unit, while pressing once again, all displays will resume. 7.3 Outdoor unit s digital display tube There is a digital display tube in outdoor PCB Digital display tube display function In standby, The LED displays, In compressor operation, the LED display the frequency, In defrosting mode, The LED displays the frequency or df each other for 2 seconds, In compressor pre-heating, The LED displays In protection or malfunction, the LED displays error code or protection code. 7.4 Outdoor unit point check function There is a check switch in outdoor PCB. Push the switch SW1 to check the states of unit when the unit is running. The digital display tube will display the follow procedure when push SW1 each time: Display Remark 1 Indoor unit capacity demand code 2 Outdoor unit running mode code Off:0, Cooling:1, Heating:2 3 Amendatory capacity demand code 4 Outdoor unit fan motor state Off:0, Low speed:1, High speed:2 5 Evaporator outlet temp. for 1# indoor unit Actual data 6 Evaporator outlet temp. for 2# indoor unit Actual data 7 Evaporator outlet temp. for 3# indoor unit Actual data 8 Evaporator outlet temp. for 4# indoor unit Actual data 9 Condenser pipe temp. Actual data 10 Ambient temp. Actual data 11 Compressor discharge temp. Actual data 12 Inverter current Actual data 13 EXV open angle for 1# indoor unit Actual data 8 14 EXV open angle for 2# indoor unit Actual data 8 15 EXV open angle for 3# indoor unit Actual data 8 16 EXV open angle for 4# indoor unit Actual data 8 17 Outdoor unit DC Voltage AD *472/255=Actual Voltage 18 Indoor unit number The indoor unit can communicate with outdoor unit well. 19 The last error or protection code 00 means no malfunction
14 20 The Compressor s running frequency 29 Check point over Frequency of compressor: Display Stand by Frequency of compressor (Hz) Running mode: Display Corresponding mode 0 Off 1 Cooling mode 2 Heating mode 7.4.3Number of indoor unit Display Number of indoor unit Outdoor ambient temp: Display Corresponding temp. Display Corresponding Corresponding Display temp. temp
15 ~ ~ ~ ~ ~ ~ ~ Current of outdoor unit Display Corresponding mode A A A A A A A A A A A A A A opening degree of electronic expansion valve: Opening degree equals the display data times opening degree of electronic expansion valve: Opening degree equals the display data times 8
16 opening degree of electronic expansion valve: Opening degree equals the display data times Protection minutes delay at restart for compressor Discharge temperature protection of compressor, compressor stops when the temp. of discharge is more than 115 and last out 10 s. compressor runs when the temp. of discharge is less than When AC voltage 80V, Outdoor Unit stops operation and Outdoor LED displays E5,. When AC voltage 100V, Outdoor Unit resumes operation Inverter module Protection, Inverter module Protection itself has a protection function against current, voltage and temperature, and Indoor LED displays P Sensor protection at open circuit and breaking disconnection Fan Speed is out of control. When Indoor Fan Speed is too high(higher than High Fan+300RPM)or too low(lower than 400RPM), the unit stops and Indoor LED displays E3, and can t return to normal operation automatically Cross Zero signal error warning. For If there is no Cross Zero signals in 4 minutes, the unit stops and Indoor LED displays E2, and can t return to normal operation automatically Current protection: when the current is more than X A, the compressor stops. and Outdoor LED diaplays P3 for 30 seconds, and the unit will restart after 3 minutes. (X is 12.5A for 18K 1x2 unit, is 14.5A for 27K 1x3 unit and is 20A for 36K 1x4 unit. ) Outdoor condenser high temperature protection: Under cooling mode, if T3>65 for 3 seconds, the compressor will stop. When T3<52, the protection is not valid. And the unit will restart after 3 minutes Pressure protection (just be available for 36K 1x4 unit): If low pressure is lower 21Psig, the compressor will stop and when low pressure is higher than 44Psig, the compressor will restart. If high pressure is higher than 630Psig, the compressor will stop and when high pressure is lower than 460Psig, the compressor will restart Compressor pre-heating function: When the outdoor temperature is lower than 3 and the compressor stops operation, the compressor enters into pre-heating condition. When outdoor temp. is more than 5 or user operate it, pre-heating condition will finish Fan-only mode Fan speed is high/mid/low/ Auto 7.7 Cooling mode Indoor fan keeps running, fan speed can be set in high/mid/low/ Auto: 7.7.2Auto fan at cooling mode: (T=Indoor Temp.-Setting Temp.) Room temp. up Condition T<1.5 Indoor fan speed 1.5<T<3.5 Mid. T>3.5 High Room temp. down T> 3 High Low
17 1<T<3 T<1 Mid. Low 7.7.3Anti-freezing control to indoor evaporator at cooling mode( T: evaporator temp. ) Evaporator Temp. Compressor T< 4 Off T > 8 On 7.8 Dehumidifying mode 7.8.1the indoor fan is fixed in low speed 7.8.2Low room temperature protection: When room temperature decreases to below 10, indoor fan stop, when room temperature restores to over 12, indoor fan start At dehumidifying mode, the anti-freezing function of the indoor heat exchanger is the same as that of cooling mode. 7.9Heating mode 7.9.1Indoor Fan actions at heating mode Indoor Fan can be set at HIGH/MID/LOW/AUTO by using a remote controller, but Anti-cold wind function prevails. Anti-cold wind control function at heating mode Condition Indoor fan speed T= Indoor exchanger temp. Indoor exchanger temp. T<34 Off up 34<T<37 Breeze 37<T<44 Low speed T> 44 Setting fan speed Indoor exchanger temp. T> 38 Setting fan speed down 33<T<38 Low speed 24<T<33 Breeze T<24 Off 7.9.2Auto wind at heating mode Condition T=Indoor Temp.-Setting Temp. Room temp. up T< <T<2.5 T>2.5 Room temp. down T< <T<2.0 T>2.0 Indoor fan speed High Mid. Low High Mid. Low
18 7.9.3Indoor evaporator high-temperature protection at heating mode Condition Compressor T= Indoor exchanger temp. T>63 Off T<48 On. Defrosting operation (Available for heating only) 7.10 Defrost Defrosting condition: The temperature of outdoor heat exchanger remains consecutively lower than -2 c for more than 40 minutes, Ending condition of defrosting If one of following conditions is satisfied, end the defrost and turn into heating mode: a. The defrost time has reached to 10 minutes. b. When the temperature of outdoor heat exchanger rises up to 15 C Defrosting Actions: a. Compressor runs. b. 4 way valve switches off, c. Outdoor fan switches off d. Indoor fan running according to anti-cold wind function in heating mode. 7.11Automatic operation mode The air conditioner automatically selects one of the following operation modes: cooling, heating or fan only according to the temp. difference between room temp. (TA) and set temp. (TS). The temp. can be adjusted between C by remote controller. TA TS Operation mode TA TS>1 Cooling -1 TA-TS +1 Fan-only TA-TS<-1 Heating 7.12Manual switch Mode changes when push this button. Cooing mode Auto mode Unit off Cooing mode At Cooing mode, after 30 minutes cooling operation whose fan speed is set as low, the A/C operates with a setting temp. of At auto mode, the A/C operates with a set temp. of Timer Function The maximum length of timer is 24 hours Timer on: the A/C will be automatically on at the set time Timer off: the A/C will be automatically off at the set time Timer on/off function: if Timer on & Timer off functions have been set at the same time, the A/C will act on which the timer achieves earlier..
19 7.14Sleep mode It is available at cooling, heating or auto mode Cooling: The set temperature rise 1 per hour. Two hours later, the set temperature will maintain as a constant and the fan speed is kept at low speed Heating: The set temperature decrease 1 per hour. Two hours later, the set temperature will maintain as a constant and the air circulation is kept at low speed (Cold air proof function takes precedence over all) Auto: The Sleep Mode running function operates in accordance with selected running mode by auto mode After 7 hours, unit cancels this mode automatically, and the unit turns off Auto restart function In case of a sudden power failure, this function automatically sets the unit to previous settings before the power failure when power returns Mode conflict The indoor units can not work cooling mode and heating at same time. Heating mode has a priority Definition Cooling mode Heating Mode Fan Off Cooling mode Yes Heating Mode Yes Yes Fan Yes Off : mode conflict; Yes: Mode conflict Unit action In case of one Indoor unit working in cooling mode or fan mode, and another indoor unit is set to heating mode, the indoor unit working in cooling mode or fan mode will change to stand by. The outdoor unit will work in heating mode. In case of one Indoor unit working in heating mode, and another indoor unit is set to cooling mode or fan mode, the indoor unit setting to cooling mode or fan mode will change to stand by. 8.Troubleshooting 8.1 Safety Because of there are capacitors in PCB and relative circuit in outdoor unit, even shut down the power supply, electricity power still are kept in capacitors, do not forget to discharge the electricity power in capacitor. The value of resistance is about 1500 ohms to 2000 ohms
20 Resistance The voltage in P3 and P4 in outdoor PCB is high voltage about 310V The voltage in P6 in outdoor PCB is high voltage about 310V 8.2 Troubleshooting for indoor unit Display E0 E1 E2 E3 E5 E6 P0 P1 P2 P3 P4 EEPROM error Communication error between indoor and outdoor unit Zero-crossing examination error Fan speed beyond control Outdoor units temp. sensor or connector of temp. sensor is defective Indoor units temp. sensor or connector of temp. sensor is defective Inverter module protection Outdoor voltage too low protection Compressor discharge temp. protection Outdoor temp. too low protection Compressor driving protection 8.3 LED error code display for outdoor unit Display E0 E1 EEPROM error 1 Indoor units pipe temp. sensor or connector of pipe temp. sensor is defective
21 E2 E3 E6 E4 E5 E7 P0 P1 P2 P3 P4 P5 P6 P7 PF 2 Indoor units pipe temp. sensor or connector of pipe temp. sensor is defective 3 Indoor units pipe temp. sensor or connector of pipe temp. sensor is defective 4 Indoor units pipe temp. sensor or connector of pipe temp. sensor is defective Outdoor temp. sensor or connector of temp. sensor is defective Compressor volt protection Communication error between outdoor IC and DSP Compressor discharge temp. protection High pressure protection (just for 36K 1x4 units.) Low pressure protection (just for 36K 1x4 units.) Compressor current protection Inverter module protection Outdoor temp. too low protection Condenser high-temperature protection Compressor driving protection PFC protection 8.4 Troubleshooting Indoor unit trouble shooting Indoor unit display E0 EEPROM error Circuit or software error on indoor Replace indoor PCB Indoor unit display E1 outdoor communication error
22 Disconnect the power supply, after 1 minute, connect the power supply, turn on the unit with remote controller Does the unit work normally? NO Check the wiring between indoor and outdoor unit. Is the connection of L, N, S and GND good? Is the GND connection on outdoor PCB good? NO Reconnect and retest again Yes Is the LED4(red) on outdoor PCB bright and LED1(yellow) blinking? Yes Replace indoor PCB and repower on. Is the failure cleared? The power supply for outdoor PCB is fail. Check the wiring on outdoor PCB comparing with wiring plate. Is the connection good? Yes Correct the connection. Replace outdoor e-box. Indoor unit display E2 Zero-crossing examination error Is power supply and connection of connectors good? NO Be sure the power supply is good and correct the connection Indoor PCB is defective. Replace the indoor PCB. Indoor unit display E3 Fan speed beyond control
23 Is the indoor fan motor connector and connection good? NO Repair the connector and reconnect Is voltage being applied to the fan motor? (rang 90v-160v between mid pin and N on CN1 Indoor PCB is defective. Replace the indoor PCB. NO Replace the indoor fan motor Indoor unit display E5 Outdoor units temp. sensor or connector of temp. sensor is defective Is the outdoor temperature sensor connector and connection good? NO Repair the connector and reconnect Replace the sensor and check if E5 display again? Replace outdoor e-box Indoor unit display E6 Indoor units temp. sensor or connector of temp. sensor is defective Is the indoor temperature and evaporator sensor connector and connection good? NO Repair the connector and reconnect Replace the sensor and check if E6 display again? Replace the.indoor PCB Indoor unit display P0 Inverter module protection
24 Is voltage normal? Is all connection good? NO NO Revise the power and retest. Revise the power and retest. Is the wiring to compressor right? Check the moduler if some components blow out or be failure? Repair or replace the moduler. Is it breakdown between P-N, P-V, P-W, N-V,N-W or V-W of inverter moduler? Replace the moduler. Check the compressor. Indoor unit display P1 Outdoor voltage protection Is the power supply good? NO Be sure the power supply is normal when using the units Replace the outdoor e-box. Indoor unit display P2 Compressor top protection against temperature
25 Does compressor operate? NO Is the connection good? NO Reconnect and retest. Is refrigerant circulation volume normal? NO Is protector normal? NO Replace the protector. Charge refrigerant Check the outdoor main PCB. Is there some problem? Is abnormality the same after gas charging? Replace the outdoor PCB. NO Check refrigerant system (such as clogging of capillary, etc) Indoor unit display P3 Compressor current protection The trouble shooting is same with one of outdoor unit P3 protection Outdoor unit trouble shooting Outdoor unit display E0 EEPROM error Circuit or software error on indoor Replace indoor PCB Outdoor unit display E1 1 Indoor units pipe temp. sensor or connector of pipe temp. sensor is defective
26 Is connection to connector of pipe temp. sensor good? Yes Check the resistance of the temp. sensor according to Annex 1 Repair connector Replace the sensor Outdoor unit display E2 2 Indoor units pipe temp. sensor or connector of pipe temp. sensor is defective Is connection to connector of pipe temp. sensor good? Yes Check the resistance of the temp. sensor according to Annex 1 Repair connector Replace the sensor Outdoor unit display E3 3 Indoor units pipe temp. sensor or connector of pipe temp. sensor is defective Is connection to connector of pipe temp. sensor good? Yes Check the resistance of the temp. sensor according to Annex 1 Repair connector Replace the sensor Outdoor unit display E6 4 Indoor units pipe temp. sensor or connector of pipe temp. sensor is defective
27 Is connection to connector of pipe temp. sensor good? Yes Check the resistance of the temp. sensor according to Annex 1 Repair connector Replace the sensor Outdoor unit display E4 Outdoor units temp. sensor or connector of temp. sensor is defective Is connection to connector of pipe temp. sensor good? Yes Check the resistance of the temp. sensor according to Annex 1 Repair connector Replace the sensor Outdoor unit display E5 Compressor volt protection Check the voltage of power supply, if the voltage is about 220V, turn off the power supply to indoor unit and turn it on again after 1 minute Does the trouble occur again? Yes Check the voltage of secondary of T3 transformer in outdoor power board, is this voltage 12-14V(AC) Replace the outdoor power board
28 Outdoor unit display E7 outdoor units communication protection Is the LED in outdoor main PCB light? Yes Check the signal wires between outdoor PCBs, is it connected good. 1.Is the +5 voltage in outdoor main board? Power Board: CN4, Red wire and yellow (GND) Outdoor main PCB: CZ1 2.Is the +3.3v voltage in outdoor main board? Power Board: CN1, Purple wire and yellow (GND) Inverter module defective. Rectifier circuit is bad connection or defective when the voltage in outdoor is abnormal. D and N: 310V(DC); Yes Check the IC6, IC7 (at Outdoor power PCB) rmally: Input voltage: <5V, changeable Output voltage:<5v, changeable Outdoor power PCB is defective.
29 Outdoor unit display P0 Compressor top protection against temperature Off: 105c; On: 90c The trouble shooting is same with the one of indoor unit P2 protection. Outdoor unit display P3 Compressor current protection Check the resistance of compressor, normally U and V is 1 ohm U and W is 1 ohm V and W is 1ohm The compressor is defective Turn one indoor unit only, Does the compressor start after 3 minutes? Yes Does the trouble occur again after compressor running some time? The compressor is defective Yes Check the refrigerant circulation volume and pressure If refrigerant circulation volume and pressure is OK, change the outdoor main PCB. Outdoor unit display P4 Compressor drive malfunctiondrive protection arose
30 Are the U,V,W connected to compressor and inverter module right? Yes Replace the outdoor power board Repair connector If the problem comes to again, check wingding resistance of inverter compressor, is it 1 ohm? Replace inverter compressor Outdoor unit display P4(LED flashes for nine times) Compressor drive malfunctionmodule protection arose Are the U,V,W connected to compressor and inverter module right? Yes Replace the module to see if it is normal Repair connector Replace the outdoor power board If the problem comes to again, check wingding resistance of inverter compressor, is it right? Replace inverter compressor
31 Outdoor unit display P6 Condenser high-temperature protection When outdoor pipe temp. is more than 65 C, the unit will stop, and unit runs again when outdoor pipe temp. less than 52 C. Is the outdoor pipe temp. more than 65 C? Is the outdoor pipe temp sensor right according to the annex 1 Yes Replace the outdoor main board Replace the outdoor pipe temp sensor
32 Annex 1 Characteristic of temp. sensor Temp. Resistance KΩ Temp. Resistance KΩ Temp. Resistance KΩ
33 Annex 2 1. Reference voltage data: a) Rectifier : Input : V(AC), output :310V(DC) b) Inverter module: U,V, W 3ph. Result U-V U-W V-W P-N V(AC) V(AC) V(AC) DC 310V c) Photo-couple PC817, PC851: Control side <+5V, AC side :< 24V(AC) d) S terminal and N: changeable from 0-24V 2. Check the Diode Bridge component ( In wiring diagram, rectifier) Remark: If this part is abnormal, the LED will not light. ~ + - ~ Multi-meter Result Forward Resistance + _ Infinite Infinite ~ ~500 ohm Infinite ~ + - ~ ~500 ohm Infinite ~ Backward Resistance
34 7909 N.W. 54th Street, Miami, FL USA Phone: +1 (305) Fax: + 1 (305) [email protected]
SERVICE MANUAL. Room Air Conditioner Multi Split type Outdoor unit /R410A DC Inverter/
SERVICE MANUAL Room Air Conditioner Multi Split type Outdoor unit /R410A DC Inverter/ FS2MI-147HFD FS2MI-187HFD FS3MI-217HFD FS3MI-277HFD FS4MI-277HFD FS4MI-367HFD FS5MI-367HFD NOTE: Before servicing the
TAS-18MVHN/O TAS-27MVHN/O TAS-36MVHN/O
SERVICE MANUAL AIRCONDITIONER DC INVERTER MULTI TYPE TAS-18MVHN/O TAS-27MVHN/O TAS-36MVHN/O DC MULTI OUTDOOR UNITS CONTENTS 1. General information of Outdoor Units... 3 2. Dimensions... 4 3. Wiring Diagram...
Service manual. The voltage in P3 and P4 in outdoor PCB is high voltage about 310V The voltage in P5 and P6 in outdoor PCB is high voltage about 310V
Resistance The voltage in P3 and P4 in outdoor PCB is high voltage about 310V The voltage in P5 and P6 in outdoor PCB is high voltage about 310V 9.2 Troubleshooting for indoor unit E0 E1 E2 E3 E5 E6 P0
13. Troubleshooting. Indoor unit s LED indication of Corona DC inverter unit. Indoor unit s LED indication of Alfa DC inverter unit
Troubleshooting 13. Troubleshooting Indoor unit s LED indication of Corona DC inverter unit MCAC-HTSM-2007-11 E0 E1 E2 E3 E5 E6 P0 P1 P2 P3 P5 EEPROM error outdoor communication error Zero-crossing examination
Technical service manual
GD Midea Refrigeration Equipment Co.,Ltd ODMI-A-1202 MULTI SPLIT TYPE, HEAT PUMP AIR CONDITIONERS Technical service manual R410A Multi DC inverter 220~240V-1Ph-50Hz Outdoor units Models M2OC-14HRDN1 M2OC-14HRDN1-Q
SERVICE INSTRUCTION R410A. WALL MOUNTEDtype INVERTER SPLIT TYPE ROOM AIR CONDITIONER. Models Indoor unit Outdoor unit
SERVICE INSTRUCTION SPLIT TYPE ROOM AIR CONDITIONER WALL MOUNTEDtype INVERTER Models Indoor unit Outdoor unit ASYG07LECA ASYG09LECA ASYG12LECA ASYG14LECA AOYG07LEC AOYG09LEC AOYG12LEC AOYG14LEC R410A CONTENTS
10.1 Indoor Unit Error Display
10.1 Indoor Unit Error Display Display E0 E1 E2 E3 E5 E6 P0 P1 P2 P4 LED STATUS EEPROM parameter error Indoor / outdoor units communication protection Zero-crossing signal error Fan speed out of control
14. Troubleshooting Guide
14. Guide 14.1 Refrigeration Cycle System In order to diagnose malfunctions, ensure the air conditioner is free from electrical problems before inspecting the refrigeration cycle. Such problems include
SERVICE MANUAL. Room Air Conditioner Multi Split Wall-Mounted Type Indoor. FSAI-Pro-91AE2 FSAI-Pro-121AE2 FSAIF-Pro-181AE2
SERVICE MANUAL Room Air Conditioner Multi Split Wall-Mounted Type Indoor FSAI-Pro-91AE2 FSAI-Pro-121AE2 FSAIF-Pro-181AE2 NOTE: Before servicing the unit, please read this at first. Always contact with
SERVICE INSTRUCTION R410A. WALL MOUNTEDtype SPLIT TYPE ROOM AIR CONDITIONER INVERTER. Models Indoor unit Outdoor unit AOU 9RLFW AOU12RLFW AOU15RLS
SERVICE INSTRUCTION SPLIT TYPE ROOM AIR CONDITIONER WALL MOUNTEDtype INVERTER Models Indoor unit Outdoor unit ASU 9RLF ASURLF ASU5RLS AOU 9RLFW AOURLFW AOU5RLS R40A CONTENTS. DESCRIPTION OF EACH CONTROL
CONTENTS 1. IMPORTANT NOTICE 2 2. TECHNICAL SPECIFICATION 3 3. OPERATION DETAILS 4 4. WIRING DIAGRAM 11 5. EXPLOSION VIEW 12 6.
TCL WALL MOUNTED SPLIT-TYPE AIR CONDITIONERS SERVICE MANUAL No.TE051220 Models TAC-09CHSA/GI TAC-12CHSA/GI CONTENTS 1. IMPORTANT NOTICE 2 2. TECHNICAL SPECIFICATION 3 3. OPERATION DETAILS 4 4. WIRING DIAGRAM
SERVICE INSTRUCTION R410A. SPLIT TYPE ROOM AIR CONDITIONER Universal Floor / Ceiling Duct / Cassette Wall Mounted / Floor type INVERTER MULTI
SERVICE INSTRUCTION SPLIT TYPE ROOM AIR CONDITIONER Universal Floor / Ceiling Duct / Cassette Wall Mounted / Floor type INVERTER MULTI R410A Models Indoor unit Outdoor unit AB*14LBAJ AB*18LBAJ AB*F14LAT
Failure code manual. content
Failure code manual content 一 wall split AC series 2 二 floor standing AC series. 4 三 portable AC series.. 5 四 dehumidifer 6 五 DC inverter single split series...7 六 DC inverter multi-split series 10 1 一
Service manual. Website: www.andico.com.au CAUTION - BEFORE SERVICING THE UNIT, READ THE SAFETY - PRECAUTIONS IN THIS MANUAL.
Website: www.andico.com.au Service manual CAUTION - BEFORE SERVICING THE UNIT, READ THE SAFETY - PRECAUTIONS IN THIS MANUAL. - ONLY FOR AUTHORISED SERVICE PERSONNEL. MODELS: MPK1-09CR-QB8 MPK1-12ER-QB6
SERVICE MANUAL SPLIT SYSTEM ROOM AIR CONDITIONER SHARP CORPORATION SHARP CORPORATION CONTENTS
SERVICE MANUAL SPLIT SYSTEM ROOM AIR CONDITIONER INDOOR UNIT AH-129 AH-MP14 OUTDOOR UNIT AU-129 AU-MP14 CONTENTS SPECIFICATIONS...2 EXTERNAL DIMENSIONS...4 WIRING DIAGRAMS...5 ELECTRICAL PARTS...6 MICROCOMPUTER
Model: AC-S13CG x 2. Model No: AC-S13CGx2.doc Version 1.0
Air Conditioner Service Manual 2 3 Model: AC-S13CG x 2 3 Content Technical specification.. 4 Performance curve.5 Outline & dimension of indoor unit..10 Outline & dimension of outdoor unit 11 Exploded view
9ASNA-A1-1202 SERVICE MANUAL SENVILLE AIRCONDITIONER DC INVERTER SPLIT WALL-MOUNTED TYPE
9ASNA-A1-1202 SERVICE MANUAL SENVILLE AIRCONDITIONER DC INVERTER SPLIT WALL-MOUNTED TYPE CONTENTS 1. Precaution... 1 1.1 Safety Precaution... 1 1.2 Warning... 1 2. Function... 6 3. Dimension... 9 3.1 Indoor
LG Air Conditioning - Universal Split Fault Codes Sheet. Universal Split Systems
Universal Split Systems If there is a fault on any LG Universal unit, a two digit number will appear on the remote controllers led display. If the unit does not have a remote controller the fault will
Indoor coil is too warm in cooling mode or too cold in heating mode. Reversing valve or coil thermistor is faulty
Codes Room Air Conditioner range: Indoor unit alarm s If timer lamp flashes for 1 second on, 1 second off, this indicates pre heating on the coil during heating mode and is not an error. If timer lamp
CONTENTS 1. IMPORTANT NOTICE 2 2. TECHNICAL SPECIFICATION 3 3. OPERATION DETAILS 4 4. ELECTRICAL SCHEMATIC DIAGRAM 13 5. EXPLOSION VIEW 16 6
TCL WALL MOUNTED SPLIT-TYPE AIR CONDITIONERS SERVICE MANUAL No.TE080528 Models KFTHP-12 KFTHP-18 KFTHP-24 CONTENTS 1. IMPORTANT NOTICE 2 2. TECHNICAL SPECIFICATION 3 3. OPERATION DETAILS 4 4. ELECTRICAL
OWNER S MANUAL VMH 09/12/18/27/36 InverterFlex
OWNER S MANUAL VMH 09/12/18/27/36 InverterFlex Version C Single, Dual, Tri or Quad Zone Ductless Mini-Split System Heat Controller, Inc. 1900 Wellworth Ave. Jackson, MI 49203 (517)787-2100 www.heatcontroller.com
Midea Commercial Air Conditioner Malfunction Handbook
Midea Commercial Air Conditioner Malfunction Handbook May 1, 2008 Customer Service Philosophy of Midea Air Conditioner Service Target: 100% Customer Satisfaction Service Standard: 100% Earnestness Service
LG Air Conditioning Multi F(DX) Fault Codes Sheet. Multi Split Units
Multi Split Units If there is a fault on any LG Multi unit, an Error mark is indicated on the display window of the indoor unit, wired-remote controller, and LED s of outdoor unit control board. A two
SERVICE MANUAL. Room Air Conditioner Split Wall-Mounted Type. FSAI-Pro-91AE2 / FSOAI-Pro-91AE2. FSAI-Pro-241AE2 / FSOAI-Pro-241AE2
SERVICE MANUAL Room Air Conditioner Split Wall-Mounted Type FSAI-Pro-91AE2 / FSOAI-Pro-91AE2 FSAI-Pro-121AE2 / FSOAI-Pro-121AE2 FSAIF-Pro-181AE2 / FSOAIF-Pro-181AE2 FSAI-Pro-241AE2 / FSOAI-Pro-241AE2 NOTE:
REMOTE CONTROL MANUAL
REMOTE CONTROL MANUAL ENGLISH CONTENT PRECAUTIONS...1-2 USING THE REMOTE CONTROL UNIT...3 OPERATION...4-9 Thank you for purchasing our Room Air Conditioner. Before using your air-conditioner, please read
RMI-1103-A SERVICE MANUAL MIDEA AIRCONDITIONER EUROPE MARKET DC INVERTER MULTI TYPE R DC INVERTER MULTI SERIES
RMI-1103-A SERVICE MANUAL MIDEA AIRCONDITIONER EUROPE MARKET DC INVERTER MULTI TYPE R DC INVERTER MULTI SERIES CONTENTS 1. Precaution... 1 1.1 Safety Precaution... 1 1.2 Warning... 1 2. Function... 6 3.
543-0032-00, 943-0032-00. User s Manual
543-0032-00, 943-0032-00 User s Manual 1 Comfort Alert Diagnostics Faster Service And Improved Accuracy The Comfort Alert diagnostics module is a breakthrough innovation for troubleshooting heat pump and
R22. K Control. Indoor Unit. Nomenclature. Compatibility PL H 3 G K H B. Unit style Heat Pump Horse Power
R22. K Control. Indoor Unit. Nomenclature. PL H 3 G K H B Compatibility Unit style Heat Pump Horse Power Control Boost Heaters R22. K Control. Outdoor Unit. Nomenclature. PU H 3 Y K A Compatibility Outdoor
Si10-417_C. Pocket Manual. Service Diagnosis SPLIT & MULTI
Pocket Manual Service Diagnosis SPLIT & MULTI Service Diagnosis SPLIT & MULTI 1. Troubleshooting with LED...5 1.1 Indoor Unit... 5 1.2 Outdoor Unit... 10 2. Troubleshooting by Symptoms...11 2.1 Air conditioner
ECO-AIR AIR CONDITIONING www.northamericanhvac.com
INDEX ACCESSORIES INSTALLATION... 3-7 LINE SETS... 3-7 GEOTHERMAL... 3-8 WIRING CABLE... 3-8 CIRCULATOR PUMPS (PRO-TECH MODEL)... 3-9 DC INVERTER SINGLE ZONE HEAT PUMP... 3-6 DC INVERTER TECHNOLOGY...
Programmable Thermostat MODEL 3312026.XXX With Dehumidify 3312024.XXX With Out Dehumidify
Comfort Control Center 2 Thermostat Operating Instructions Programmable Thermostat MODEL 3312026.XXX With Dehumidify 3312024.XXX With Out Dehumidify TABLE OF CONTENTS About your new thermostat Features...2
Haier Air conditioner
For Europe Haier Air conditioner HAND in HAND HIGHER and HIGHER Page:1 For Europe HSU-09/12HVA103/R2(DB) HSU-09/12RHA103/R2(DB) Page:2 Error Codes and Description indoor and outdoor display(1) indoor Code
PANASONIC TROUBLE SHOOTING GUIDE
A General Guide To Room Style Products Pipework Pipe sizes and lengths should be as the relevant Technical Guide Both lines should be insulated No line accessories or oil traps should be fitted In cooling
OWNER'S MANUAL R-410A Duct Free Split System Air Conditioner and Heat Pump
R-410A Duct Free Split System Air Conditioner and Heat Pump Product Family: DFS4(A/H)-System, DFC4(A/H)3-Outdoor, DFF4(A/H)H-Indoor Please read the operating instructions and safety precautions carefully
Service manual. Room air conditioner Split Wall-Mounted Type GC/CU-S05CR GC/CU-S07HR GC/CU-S09HR GC/CU-S12HR GC/CU-S18HR
Service manual Room air conditioner Split Wall-Mounted Type GC/CU-S05CR GC/CU-S07HR GC/CU-S09HR GC/CU-S12HR GC/CU-S18HR Climatic Control Corporation Wall-Mounted Split Type Content 1. Precaution 1 1.1
SERVICE MANUAL MUZ-GE09NA MUZ-GE12NA MUZ-GE15NA MUZ-GE18NA MUZ-GE24NA MUY-GE09NA MUY-GE12NA MUY-GE15NA MUY-GE18NA MUY-GE24NA OUTDOOR UNIT
SPLIT-TYPE AIR CONDITIONERS Revision B: Descriptions regarding the outdoor fan motor have been corrected. Please void OBH549 REVISED EDITION-A. OUTDOOR UNIT SERVICE MANUAL HFC utilized R410A. OBH549 REVISED
WYS SERIES SPLIT 3D DC INVERTER HEAT PUMP / AIR CONDITIONER SERVICE MANUAL
z WYS SERIES SPLIT 3D DC INVERTER HEAT PUMP / AIR CONDITIONER SERVICE MANUAL Revision A: 151110001, Content updated. Model Numbers: 17 SEER Family: WYS009AMFI17RL, WYS012AMFI17RL, WYS009GMFI17RL, WYS012GMFI17RL,
WALL MOUNTED AIR CONDITIONER SERVICE MANUAL 11M INVERTER
WALL MOUNTED AIR CONDITIONER SERVICE MANUAL 11M INVERTER This manual applies to the models: 42HVM109303 / 38HVM109303(P) 42HVM112303 / 38HVM112303(P) 42HVM118303 / 38HVM118303(P) 42HVM124303 / 38HVM124303(P)
SERVICE MANUAL 12VDC WALL THERMOSTAT AIR CONDITIONING SYSTEMS ROOFTOP UNITS ONLY
SERVICE MANUAL 12VDC WALL THERMOSTAT AIR CONDITIONING SYSTEMS ROOFTOP UNITS ONLY! WARNING - SHOCK HAZARD! TO PREVENT THE POSSIBILITY OF SEVERE PERSONAL INJURY, DEATH, OR EQUIPMENT DAMAGE DUE TO ELECTRICAL
TECHNICAL DATA & SERVICE MANUAL SPLIT SYSTEM AIR CONDITIONER INDOOR UNIT: AW52AL AW64AL AW52AL 387030095 AW64AL 0.8180.463.0 07/05
TECHNICAL DATA & SERVICE MANUAL INDOOR UNIT: AW52AL AW64AL SPLIT SYSTEM AIR CONDITIONER Model No. Product Code No. AW52AL 387030095 AW64AL 387030096 0.8180.463.0 07/05 IMPORTANT! Please read before installation
SERVICE MANUAL INDOOR UNIT
SPLIT-TYPE AIR CONDITIONERS Revision E: MSZ-GE22VAD- A1 has been added. Please void OBH531 REVISED EDITION-D. INDOOR UNIT SERVICE MANUAL. OBH531 REVISED EDITION-E Models MSZ-GE22VA - A1 MSZ-GE50VA - A1
1 4. 3 4-2 ABNORMAL OPERATION. 4-2-1 Error code Display. Specifics Error Code. Subsection Error Code. Subsection and Specifics Error code target
4-2 ABNORMAL OPERATI 4-2-1 An is represented by 3 digit characters. The first 2 digit means the subsection, and the last 1 digit means the specifics. Ex.) Indoor unit Network communication Error Subsection
Split and Multi Split air conditioners Service information
Split and Multi Split air conditioners Service information Programming LG wired controllers 2 New type 2 Old type 7 Fault codes 9 Wall units (single split) 9 Universal split and multi split 10 Detailed
USER S MANUAL HSC-24A
AIRREX AIR CONDITIONER USER S MANUAL HSC-24A Thank you for purchasing an AIRREX AIR CONDITIONER. BEFORE operation please read this user s manual carefully. Keep this manual readily available. It is ESSENTIAL
Repair Guideline for SANYO New Erp. DC Inverter Air Conditioner (Published in May, 2013)
Repair Guideline for SANYO New Erp DC Inverter Air Conditioner (Published in May, 2013) Contents I. Electronic Control of DC Inverter Air Conditioner 2 1. Main parts of the electronic control of DC inverter
Technical Service Manual. Version One
[Gree Central Air Conditioner] Technical Service Manual Ducted type unit 2.3KW-16KW Version One GREE ELECTRIC APPLIANCES.INC.OF ZHUHAI - 1 - FG Series wind pipe blowing air-conditioning unit Section One:
SERVICE MANUAL MUZ-FE09NA MUZ-FE12NA MUZ-FE18NA OUTDOOR UNIT. No. OBH543 REVISED EDITION-A. Models HFC
SPLIT-TYPE AIR CONDITIONERS Revision A: MUZ-FE18NA has been added. Please void OBH543. OUTDOOR UNIT SERVICE MANUAL HFC utilized R410A. OBH543 REVISED EDITION-A Models MUZ-FE09NA MUZ-FE12NA MUZ-FE18NA Indoor
york air-conditioning products Residential & VRF News 2015
york air-conditioning products Residential & VRF News 2015 york air-conditioning products Catalogue Content Split Systems Pag. High wall High Efficiency Inverter YWHJZH 09 to 24 K 6 High wall Inverter
Repair Guideline for TCL DC Inverter Air Conditioner
Repair Guideline for TCL DC Inverter Air Conditioner FLOS SERIE---V3 0 CONTENTS Ⅰ. Introduction of New control board for outdoor unit...2 1. The structure of control board... 2 2. Diagram of outdoor unit........4
Portable Air Conditioner
Portable Air Conditioner Owner's Manual Model:3 in 1 12,000 Btu/h Series 3 Please read this owner s manual carefully before operation and retain it for future reference. CONTENTS 1. SUMMARY...1 2. PORTABLE
SERVICE MANUAL FOR 6535 SERIES TWO TON HIGH EFFICIENCY PACKAGED HEAT PUMPS
SERVICE MANUAL FOR 6535 SERIES TWO TON HIGH EFFICIENCY PACKAGED HEAT PUMPS TABLE OF CONTENTS 1. Warnings...2 2. Accessibility Of Appliance...3 3. Unit Dimensions And Specifications...3 4. Unit Specifications
SERVICE MANUAL INDOOR UNIT
SPLIT-TYPE AIR CONDITIONERS Revision B: "How to check miswiring and serial signal error" for MUZ type has been added. The description about "Low standby power control" has been added to "TECHNICAL CHANGES".
Split Type Room Air Conditioner. KSWM units
OWNER S MANUAL Split Type Room Air Conditioner KSWM units Please read the operating instructions and safety precautions carefully and thoroughly before installing and operating your room air conditioner.
WALL MOUNTED SPLIT TYPE AIR CONDITIONER
WALL MOUNTED SPLIT TYPE AIR CONDITIONER MANUAL 8 OM-G12-ACSON CONTENTS - Operating Guide page 1 - G12 Remote Controller Indication page 2 - Indicator Lights page 4 - Installation of Aroma page 5 - Auto
DC INVERTER MULTI-SYSTEM AIR CONDITIONER
AIR CONDITIONER AIR CONDITIONER TECHNICAL & SERVICE MANUAL INDOOR UNIT : CS-MKE7NKU CS-MKE9NKU CS-MKE12NKU CS-MKE18NKU CS-MKE24NKU DC INVERTER MULTI-SYSTEM AIR CONDITIONER Capacity 7,500BTU / h 9,000BTU
Repair Guideline for TCL DC Inverter Air Conditioner
Repair Guideline for TCL DC Inverter Air Conditioner Contents I. Electrical Control of Inverter Air Conditioner 2 1. Main compositions of the electrical control of inverter air conditioner 2 2. Wiring
SERVICE MANUAL MIDEA AIRCONDITIONER DC INVERTER SPLIT WALL-MOUNTED TYPE MSV1-09HRDN1-QC2(A) MSV1-12HRDN1-QC2(A)
SERVICE MANUAL MIDEA AIRCONDITIONER DC INVERTER SPLIT WALL-MOUNTED TYPE MSV1-09HRDN1-QC2(A) MSV1-12HRDN1-QC2(A) V1.2 Oct, 2007 CONTENTS 1. Precaution... 1 1.1 Safety Precaution... 1 1.2 Warning... 1 2.
DC INVERTER SPLIT SYSTEM AIR CONDITIONER
TECHNICAL & SERVICE MANUAL SAP-KRV9AEH + SAP-CRV9AEH SAP-KRV12AEH + SAP-CRV12AEH FILE NO. Destination: Europe DC INVERTER SPLIT SYSTEM AIR CONDITIONER Indoor Model No. SAP-KRV9AEH SAP-KRV12AEH Product
CLOSE CONTROL SYSTEM. PFD series provide you with highly reliable computer room cooling system. High Reliability
PFD-P250VM-E PUHY-P250YJM-A(-BS) PUHY-P500YSJM-A(-BS) PQHY-P250YHM-A CLOSE CONTROL SYSTEM MITSUBISHI ELECTRIC s Close Control System (PFD series) is specifically designed for computer rooms, laboratories
SERVICE MANUAL OUTDOOR UNIT. No. OBH590 REVISED EDITION-B. Models HFC
SPLIT-TYPE AIR CONDITIONERS Revision B: MUZ-EF25/35/42/50VE - E2 and MUZ-EF25/35VEH - E2 have been added. Please void OBH590 REVISED EDITION-A. OUTDOOR UNIT SERVICE MANUAL HFC utilized R410A. OBH590 REVISED
Air Conditioning System
Air Conditioning System 1 Chonan Technical Service Training Center Chonan Technical Service Training Center 2 Objectives To understand the components of air conditioning system. To understand the control
VSI-1104-A SERVICE MANUAL MIDEA AIRCONDITIONER DC INVERTER SPLIT WALL-MOUNTED TYPE. Vertu SERIES
VSI-1104-A SERVICE MANUAL MIDEA AIRCONDITIONER DC INVERTER SPLIT WALL-MOUNTED TYPE Vertu SERIES CONTENTS 1. Precaution... 1 1.1 Safety Precaution... 1 1.2 Warning... 1 2. Function... 6 3. Dimension...
SERVICE MANUAL INDOOR UNIT MSZ-EF35VEW MSZ-EF22VEB - - E1 MSZ-EF25VEB E1 MSZ-EF35VEB - - E1 MSZ-EF35VEB E1 MSZ-EF35VES - E1 - E1 MSZ-EF22VEW -
SPLIT-TYPE AIR CONDITIONERS Revision A: Airflow in the Silent mode in the cooling operation has been changed. "TROUBLESHOOTING" has been corrected. Please void OBH589. INDOOR UNIT SERVICE MANUAL. OBH589
technical data air conditioning systems RXS20-25-35E (single phase) FBQ-B8V1-B8V3B Split Heat Pump Condensing Units Split Sky Air
technical data RXS20-25-35E FBQ-B8V-B8V3B (single phase) Split Heat Pump Condensing Units air conditioning systems Split Sky Air Outdoor Units R-40A RXS-E2VB Split Sky Air Outdoor Units Features O u t
Single Zone LCD Thermostat Operating Instructions
Fan Cool Furnace *Heat Pump or Heat Strip On/Off F Single Zone LCD Thermostat Operating Instructions MODEL 3313192.XXX Cool/Furnace 3313193.XXX Cool/Furnace/Heat Pump 3313194.XXX Cool/Furnace/Heat Strip
Heat Pump Water Heater IOM Manual
Heat Pump Water Heater IOM Manual Installation Operation & Maintenance This manual is intended as an aid to qualified service personnel for proper installation, operation and maintenance of the heat pump
SERVICE MANUAL MSZ-HJ25VA MSZ-HJ35VA MSZ-HJ50VA INDOOR UNIT. No. OBH647. Models. Revision A: MSZ-HJ50VA- E1 has been added.
SPLIT-TYPE AIR CONDITIONERS Revision A: MSZ-HJ50VA- E1 has been added. Please void OBH647. INDOOR UNIT SERVICE MANUAL. OBH647 REVISED EDITION-A Models MSZ-HJ25VA MSZ-HJ35VA MSZ-HJ50VA - E1 - E1 - E1 CONTENTS
A/C-HEATER SYSTEM - AUTOMATIC
A/C-HEATER SYSTEM - AUTOMATIC 1995 Volvo 850 1995-96 Auto. A/C-Heater Systems Volvo 850 * PLEASE READ THIS FIRST * WARNING: To avoid injury from accidental air bag deployment, read and carefully follow
Split Air Conditioner
Split nditioner plit itsplit ir onditioner Split Split Split Split Split User s WNER'S 'S ER'S For s: AWI/AWO-21HPR1 Delta AWI/AWO-25HPR1 Delta AWI/AWO-32HPR1 Delta AWI/AWO-53HPR1 Delta AWI/AWO-65HPR1
FILE NO. SVM-07013 11. HOW TO DIAGNOSE THE TROUBLE
FILE. SVM-070. HOW TO DIAGSE THE TROUBLE The pulse motor circuits are mounted to both indoor and outdoor units. Therefore, diagnose troubles according to the trouble diagnosis procedure as described below.
New Deluxe Wall Mounted Heat Pump Series EXTERIOS
New Deluxe Wall Mounted Heat Pump Series EXTERIOS May 2013 New Deluxe Wall Mounted Heat Pump Series Panasonic Adding New Air Conditioner Lineup Setting Another Mile Stone in the US Ductless Split History
ChapterⅠ Introduction to Products
AI RCONDI TI ONI NG SYSTEMS Model s : UMATCH I NVERTER Ser vi cemanual Ser vi cemanual ChapterⅠ Introduction to Products 1. Kinds of Products Universal outdoor unit Duct type Floor ceiling type Cassette
RAV-SM564UT-E RAV-SM804UT-E RAV-SM1104UT-E RAV-SM1404UT-E RAV-SM1604UT-E
AIR CONDITIONER (SPLIT TYPE) Owner s Manual Indoor Unit Model name: For commercial use 4-way Cassette Type RAV-SM564UT-E RAV-SM804UT-E RAV-SM1104UT-E RAV-SM1404UT-E RAV-SM1604UT-E Owner s Manual English
DUCT TYPE AIR CONDITIONER
OPERATING MANUAL OPERATING MANUAL BEDIENUNGSANLEITUNG MODE D EMPLOI MANUAL DE FUNCIONAMIENTO MANUALE DI ISTRUZIONI ΕΓΧΕΙΡΙ ΙΟ ΛΕΙΤΟΥΡΓΙΑΣ MANUAL DE INSTRUÇÕES AIR CONDITIONER DUCT TYPE English Deutsch
ALL IN ONE. Heat Pump Water Heater
ALL IN ONE Heat Pump Water Heater INSTALLATION AND OPERATION INSTRUCTIONS Please read this user s manual carefully before operate the unit. www.airtradecentre.com CONTENTS A. IMPORTANT REMARKS ------------------------------------------------------------------------------------------------
Heat Pump Product Brochure 2015/2016. Premier Series Hi-Wall Split Systems. Everyday Comfort
Heat Pump Product Brochure 2015/2016 Premier Series Hi-Wall Split Systems Everyday Comfort Everyday Innovation We design with you in mind. You ll find that Haier Heat Pump units are quiet, efficient and
Air conditioning, electrical testing
just a test. Air conditioning, electrical testing 01-253 Wire and component test using VAG1598 A test box Special tools and equipment VAG 1598 A test box and VAG 1598/11 adapter cable and VAG 1598/12 VAG1526
Split Air Conditioner
Change for Life Split Air Conditioner Owner's Manual Residential Air Conditioners MODEL: GWH09MA-A3DNXXA GWC09MA-A3DNXXA GWH12MB-A3DNXXA GWC12MB-A3DNXXA GWH09MB-D3DNXXD GWC09MB-D3DNXXD GWH12MB-D3DNXXD
Fossil fuel heating equipment
Fossil fuel heating equipment principles and troubleshooting techniques Application Note This application note was written to provide you with an understanding of the basic principles of fossil fuel heating
How To Power A Car With A Fan And A Fan (Power)
SPLIT TYPE ROO AIR CONDITIONER CEILING WALL TYPE INVERTER Indoor unit AWYZLBC AWYZLBC AWYZLBC AWYZLBC Outdoor unit AOYZLBC AOYZLBL AOYZLBC AOYZLBL CONTENTS SPECIFICATIONS................... OUTLINE AND
Technical Information
Date of last update: Oct-11 Ref: D7.8.4/1011/E Application Engineering Europe CORESENSE DIAGNOSTICS FOR STREAM REFRIGERATION COMPRESSORS CoreSense Diagnostics for Stream Refrigeration Compressors... 1
HYUNDAI SERVICE MANUAL HSH-I183NBE. Models WALL MOUNTED SPLIT-TYPE AIR CONDITIONERS. No.TE121023
HYUNDAI WALL MOUNTED SPLIT-TYPE AIR CONDITIONERS SERVICE MANUAL No.TE121023 Models HSH-I073NBE HSH-I123NBE HSH-I243NBE HSH-I093NBE HSH-I183NBE IMPORTANT NOTICE This service manual is intended for use by
SERVICE & MAINTENANCE MANUAL
SERVICE & MAINTENANCE MANUAL 2005 TABLE OF CONTENTS PAGE NO. 1. Precautions for Service & Maintenance 2 2. Split System Description 3 3. Unit Model Designation & Identification 4 4. Unit Models & Part
Gree Solar Hybrid Hi Wall Inverter Air Conditioner
Gree Solar Hybrid Hi Wall Inverter Air Conditioner Utilize the natural power of the sun to heat or cool your home. Find out more at www.greeonline.com Why Choose a Solar Hybrid Inverter? The new Gree Solar
HEAT PUMP FREQUENTLY ASKED QUESTIONS HEAT PUMP OUTDOOR UNIT ICED-UP DURING COLD WEATHER:
HEAT PUMP FREQUENTLY ASKED QUESTIONS HEAT PUMP OUTDOOR UNIT ICED-UP DURING COLD WEATHER: It is normal for a heat pump to have a build up of white frost on the outside coil during cold damp weather. The
USER INSTRUCTIONS FOR GET PORTABLE 12k BTU AIR CONDITIONER MODEL No. GPACU12HR
USER INSTRUCTIONS FOR GET PORTABLE 12k BTU AIR CONDITIONER MODEL No. GPACU12HR CONTENTS Introduction Safety Notes Identification of parts Installation instructions Operation instructions Maintenance Troubleshooting
USER S MANUAL FH052EAV1 FH070EAV1. System Air Conditioner (Cooling and Heating) ENGLISH ESPAÑOL FRANÇAIS ITALIANO PORTUGUÊS DEUTSCH E HNIKA
USER S MANUAL FH052EAV1 FH070EAV1 E HNIKA PORTUGUÊS ENGLISH ESPAÑOL ITALIANO DEUTSCH FRANÇAIS System Air Conditioner (Cooling and Heating) E S F I P D G DB98-29263A(1) Safety Precautions Register your
DC INVERTER MULTI-SYSTEM AIR CONDITIONER
TECHNICAL & SERVICE MANUAL OUTDOOR UNIT : CM97 CM7 CM7 FILE NO. Destination: North America DC INVERTER MULTI-SYSTEM AIR CONDITIONER Capacity at 0V 9,700 BTU/h,00 BTU/h 0,600 BTU/h Outdoor Model No. CM97
INSTALLATION MANUAL. Address card EKAC10B
INSTALLATION MANUAL 88 44 µchiller compact 70 64 4a 4b G G0 power supply G G0 power supply 50 5 50 5 4a 4b 5a 5b 4 5a 5b Installation manual READ THIS MANUAL ATTENTIVELY BEFORE STARTING UP THE UNIT. DO
Owner s Manual RAV-SM404MUT-E RAV-SM454MUT-E RAV-SM564MUT-E AIR CONDITIONER (SPLIT TYPE) Indoor Unit. Model name: Compact 4-way Type.
AIR CONDITIONER (SPLIT TYPE) Indoor Unit Model name: RAV-SM404MUT-E RAV-SM454MUT-E RAV-SM564MUT-E English 1 Original instruction Contents ADOPTION OF NEW REFRIGERANT This Air Conditioner uses R410A an
Portable Air Conditioner. OWNER S MANUAL Read these instructions before use. Model: MF08CESWW. Voltage rating: 115V~60Hz Power rating : 800W
MODE ALARM Portable Air Conditioner OWNER S MANUAL Read these instructions before use 8 Model: MF08CESWW Voltage rating: 115V~60Hz Power rating : 800W Customer Support : 1-800-474-2147 For product inquiries
DC INVERTER MULTI-SYSTEM AIR CONDITIONER
TECHNICAL & SERVICE MANUAL OUTDOOR UNIT : AEMI0AH AEMIAHB AEMIAH AEMI0AH FILE NO. Destination: Europe DC INVERTER MULTI-SYSTEM AIR CONDITIONER Capacity.0k.k.k.0k Outdoor Model No. AEMI0AH AEMIAHB AEMIAH
Room Air Conditioners
User Manual Room Air Conditioners R410A Split Type Y Series DC INVERTER ECO940SD ECO120SD ECO1840SD Please read this installation manual completely before installing the product. When the power cord is
PORTABLE AIR CONDITIONER
VERY IMPORTANT! MODEL: GDC-AC9RW / GDC-AC9RCS GDC-AC9RCW / GDC-AC12RW GDC-AC12RB / GDC-AC12RCB GDC-AC12RCW INSTRUCTIONS FOR USE PORTABLE AIR CONDITIONER Do not install and use your portable air conditioner
evo+ Installation, Service & Troubleshooting DUCTLESS SYSTEM
evo+ DUCTLESS SYSTEM Installation, Service & Troubleshooting Models: GWH09AB-A3DNA2B GWH12AB-A3DNA2B GWH09AB-D3DNA2D GWH12AB-D3DNA2D GWH18AB-D3DNA2D GWH24AB-D3DNA2D Table of Contents Safety Precautions
DUCTLESS MINI-SPLITS SINGLE & MULTI-ZONE HORIZONTAL AIR CONDITIONERS PORTABLE UNITS FREE MATCH COMPONENTS
DUCTLESS MINI-SPLITS SINGLE & MULTI-ZONE HORIZONTAL AIR CONDITIONERS PORTABLE UNITS FREE MATCH COMPONENTS AN EXCELLENT CHOICE IN COOLING, COMFORT AND CONVENIENCE Why choose a Mini-Split system? Installing
TECHNICAL & SERVICE MANUAL WINDOW TYPE AIR CONDITIONER SA 79G SA 99G FILE NO. SA 79G SA 99G REFERENCE NO. SM700402
TECHNICAL & SERVICE MANUAL SA 79G SA 99G FILE NO. WINDOW TYPE AIR CONDITIONER Model No. Product Code No. Destination SA-79G-A 1 851 005 18 General (50Hz) & Europe SA-99G-A 1 851 005 19 SA 79G SA 99G REFERENCE
WINDOW ROOM AIR CONDITIONER
WINDOW ROOM AIR CONDITIONER Installation and Operation Manual Electromechanical Remote Control CAPACITIES 220V - 60 HZ. 12,000; 18,000; 24000 BTU/HR 220V-240V - 50 HZ. 12,000; 18,000; 24000 BTU/HR Please
AIR CONDITIONING & HEAT PUMP SYSTEMS
AIR CDITIING & HEAT PUMP SYSTEMS SERVICE GUIDE Including outdoor unit (FDC 6 Series and 8 Series) FDT 4-Way Cassette FDEN Ceiling Suspended FDKN Wall Mounted FDR Ducted Cassette FDU Ducted - gh Static
SERVICE MANUAL REFRIGERATION
SERVICE MANUAL REFRIGERATION ELECTROLUX HOME PRODUCTS S.p.A. Publication no. Spares Operations Italy 599 36 16-90 Corso Lino Zanussi, 30 031117 I - 33080 PORCIA / PN (ITALY) ITZ/SERVICE/AA Fax +39 0434