1 IMPERIAL COLLEGE FIRE ALARMS DETECTION SYSTEMS EQUIPMENT REVISION 1 FIRE ALARMS AND DETECTION SYSTEMS EQUIPMENT Revision Log REV. COMMENTS REVISED BY DATE CHECKED APPROVED 1 First Issue NDY Notes 1 Amendments to this specification are struck out and new added in italics 2 Distribution as per Document Issue Sheet.

2 Contents Introduction Category Guidance Notes Historical Review Bench Marking Standard Details Performance Criteria Standard Performance Specification For Fire Alarms Detection Systems Equipment Standard Performance Specification for Fire Alarm and Detection Systems Components and Supplier Information Market Overview and Suitability Characteristics Supplier and Installer Review & Recommendations Contractors Suppliers Proposed Strategy for Procurement Memorandum of Understanding

3 Introduction This document has been prepared with the aim of achieving consistency in quality, appearance and standards and to give guidance in the selection and specification of products. It is not intended that these documents be used as substitutes for fully detailed project specifications. Consultants/Contractors shall develop their project specific documentation in line with these documents. Where deviation from this document is proposed written approval of this departure shall be approved jointly by the Imperial College Estates Engineering Manager and Building Services Manager. This document is to be updated during Summer 2005 hence any agreed deviations should be sent to the document editor (as noted on the cover sheet of this document) for consideration and inclusion within the next revision. The end beneficiary will be Imperial College, its staff and students. This information is classed as work in progress.. Any comments and contributions will be welcome.

4 Category Standard Performance Specifications included in this Category Elements Included Within Category Elements in Category Control Panels Smoke Detectors Call Points Input/Output Units Sounders Beacons Magnetic Door Retainers Plant Override Switch Performance Standards Developed by team Reasons for team not developing standard

5 Guidance Notes Historical Review Information to be sourced and loaded during Phase 2 Summer 2005

6 Bench Marking Information to be sourced and loaded during Phase 2 Summer 2005

7 Standard Details Information to be sourced and loaded during Phase 2 Summer 2005

8 Performance Criteria Performance Standards Selection Guide The performance of the Fire Alarm Equipment is in accordance with the requirements of the Imperial College Chief Fire Officer and the Estates Engineering Manager to align with the long-term fire alarm systems strategy of Imperial College London. Key requirements of this strategy are The need for College fire safety personnel to instantly understand the status of a panel in an emergency situation The ability to network the Fire Alarm Equipment in the longer term Additional College requirements include: Compliance with regulatory requirements Multi Protocol Modular concept Simple, robust design Intuitive to use Easy to maintain Low cost to maintain & hold spares Easy to expand Easy to install Easy to configure It is also recognised that the existing older fire alarm equipment within the College campuses has exceeded its life span and has become difficult and costly to maintain. The above requirements led the College to identify appropriate manufacturers four years ago in 2000 and, following price comparisons, select single sources on all core elements. These sources have been detailed in the draft Technical Policy Statements F12 Fire Alarms & Detection Systems Equipment Schedule that is attached. The equipment performance standard required by Imperial College London is implicitly defined in the suppliers and ranges described in draft Technical Policy Statement F12. Note that this is an uncontrolled copy. The latest version is obtainable via the College s internet site as described in the Imperial College London Project Management Procedures.

9 Standard Performance Specification for Fire Alarms Detection Systems Equipment The relevant specification criteria which follow include. F12 Fire Alarm & Detection Systems Equipment Schedule Associated Imperial College London Technical Policy Statements & other design standards which can be found elsewhere include: F 1 F 2 F 3 F 4 F 5 Fire Alarm / Ventilation Interface. Fire Alarm / Access Control Interface. Fire Alarm Levels Automatic Detection. Automatic Fire Detection In Academic Buildings. Fire Alarm. F 13 Fire Alarms Detection and Cabling System. The Technical Policy Statement F 13 Fire Alarms Detection and Cabling System was created as a result of this standardisation programme.

10 Standard Performance Specification for Fire Alarm and Detection Systems Fire Alarm Control and Indicating Panels Addressable Panels shall be selected from the Morley ZX5e range, complete with internal power supply unit and Yasa battery. All panels to be selected to operate using devices from the Apollo Discovery protocol. Conventional Panels shall be selected from the Morley M1/M2/M4/EM8 range complete with internal power supply unit and Yasa battery. All panels to be selected to operate using devices from the Apollo Series 60 range. Devices For Use in Addressable Systems Point Detectors Point detection devices shall be selected from the Apollo XP 95 range. Prior to selecting devices, the designer shall consult with the College Chief Fire Officer and Estates Engineering Manager with regard to the possible application of Discovery devices from within the XP95 range. Manual Call Points Manual call points shall be selected from the Apollo XP 95 range. Input/Output Units Input/Output units shall be selected from the Apollo XP 95 range. Devices for Use In Conventional Systems Point Detectors Point detection devices shall be selected from the Apollo Series 60 range. Manual Call Points Manual call points shall be selected from the Morley WR range.

11 Relay Units Relay units shall be selected from the Morley range. Beam Detectors Beam detectors shall be selected from the Morley detection range complete with associated power supply unit. Sounders Voice Enhanced Voice enhanced sounders shall be selected from the Vimpex Voice Enhanced range, complete with associated control equipment. Bells Bells shall be selected from the Fulleon electronic range. Beacons Beacons shall be selected from the Fulleon Xenon range complete with a red lens. Magnetic Door Retainers Magnetic door retainers shall be selected from the Vimpex 24 volt range, complete with associated power supply unit. Plant Override Test Switch Key operated plant override test switches shall be selected from the Haes System switch range. Manual Break Glass Override Switch (Magnetically retained secure doors) Manual break glass override switches shall be coloured green, and shall release the associated door by operating a clear plastic element. Switches shall be as Fulleon CKM/TO/P/G. Speech Dialler Speech diallers shall be fitted to all fire alarm systems in buildings remote from the South Kensington Campus. Speech diallers shall be as Vimpex range.

12 Vibrating Pillows Where vibrating pillows are required to alert sleeping occupants with a hearing disability, these shall be as agreed with ICL fire officer. NOTE. The contents of this Technical Policy Statement shall be treated as confidential and shall not be disclosed to any suppliers of fire alarm equipment or their agents.

13 Component and Supplier Information Imperial College London has commenced an initiative to introduce supply chain management on all future capital projects undertaken throughout its property portfolio. This section details the work undertaken to date and provides guidance of proposed components and suppliers as at July 2004 (although the lists and names are not exhaustive). Components were selected following a review of the College s indicative capital spend plan over the next two years. Category Teams made up from the College s Framework partners were responsible for then taking these forward into Standard Specifications and also formulating Purchasing Strategies to best buy the components appropriately in the market place. All specifications, components and proposed suppliers should align with the latest needs of the Estates Department and be formally signed off at each appropriate stage by the College to ensure that they are technically compliant and compatible with the College s requirements and internal purchasing policies. Market Overview & Suitability Characteristics Elements Included Within Category Elements in Category Purchasing Strategy developed by team Control Panels Smoke Detectors Call Points Input/Output Units Sounders Beacons Magnetic Door Retainers Plant Override Switch Reasons for team not developing purchasing strategy

14 Market Evaluation The Technical Policy Statement, F12 Fire Alarm & Detection Systems Equipment Schedule, identifies appropriate manufacturers to obtain single source elements. These are: Morley Apollo Vimpex Fulleon Haes The College has stipulated that future installations use Morley control equipment with Apollo protocol. Other advantages in choosing the above manufacturers were their good quality, user friendliness, guaranteed replacement parts and that software update are readily available. Morley and Apollo are both part of global companies and are considered as leaders within the fire alarm industry. In addition the control panels manufactured by Morley can be maintained and configured by any recognized fire alarm company unlike other manufacturers that require specialist software programming. Imperial College London requires that its main and M&E contractors comply with their aim to standardize the fire alarm and detection systems equipment. Historically Elecro Ltd has been used by the College s main and M&E contractors as their preferred fire alarm installer on the College Estate. Hence Elecro Ltd has installed all such equipment over the last 3 to 4 years (excluding the Tanaka, Faculty Building and Pembridge Building) and have therefore developed knowledge of existing and new fire alarm systems throughout the College campuses. On behalf of the College, Elecro Ltd agreed preferential equipment rates with the selected manufacturers in Yr and these prices have remained unchanged since then. It is believed that due to the limited annual spend of the College on fire alarm equipment then substantial discounts will not be achieved.

15 Supplier and Installer Review & Recommendations Potential Suppliers/Installers The following list may become the preferred suppliers: Morley Apollo Vimpex Fulleon Haes The Morley fire alarm panel can be expanded making it both simple & cost effective. Final networking of all Morley fire alarm systems will enable the systems to be monitored for one central location making identification of fire/fault location much easier. Networking of the Morley Systems will enable the Chief Fire Officer to be aware of the systems undergoing maintenance or modification and thus facilitate Health & Safety issues.

16 Contractors As detailed in previous page Elecro Ltd are the preferred installation contractor.

17 Suppliers The College has stipulated that future installations use Morley control equipment with Apollo protocol. Proposed Strategy for Procurement Key Recommendations Component prices agreed by the suppliers with Elecro Ltd are to be made available to both other potential Fire Alarm and Detection Systems installers and to the appropriate maintenance contractors. These prices will be the base level that other potential installers will be required to match. Where manufacturer prices agreed with Elecro Ltd prove high in comparison to other installers then action is to be taken by Elecro Ltd to try and renegotiate prices appropriately. Elecro Ltd to procure Fire Alarm and Detection Systems for Imperial College London projects on behalf of other contractors and /or maintenance providers when requested. Carry out continued maintaining of the suppliers and a performance appraisal at project completions to ensure value for money.

18 Memorandum of Understanding A Memorandum of Understanding or Partnering Charter may be established with the suppliers and installers and key issues to be included should be;- The pre-agreed schedule detailing product types, delivery period and price. Method of inspection and sign off on delivery. Key person within each organization to be the point of contact for all Imperial College works. Protection during delivery. Establish agreed response times for dealing with defects. After sales service and advice. Response times in submitting prices from receipt of enquiry. Minimum delivery period for materials. Base rates, fixed price period and pre-agreed RPI increase. Warranty period Pre-agreed discounts for the following year s prices if supply exceeds expectations.

FIRE ALARMS SYSTEMS - UCL GENERAL INSTALLATION EMPLOYERS & REQUIREMENTS DESIGN GUIDANCE

FIRE ALARMS SYSTEMS - UCL GENERAL INSTALLATION EMPLOYERS & REQUIREMENTS DESIGN GUIDANCE Fire Safety Technical Guide Contents FIRE ALARMS SYSTEMS - UCL GENERAL INSTALLATION EMPLOYERS & REQUIREMENTS DESIGN GUIDANCE (Student Hals of Residences - Sleeping Accommodation) 1.0. Introduction... 1

More information

BELMONT FIRE DEPARTMENT FIRE ALARM SYSTEM REQUIREMENTS BFD-OFM-10-011

BELMONT FIRE DEPARTMENT FIRE ALARM SYSTEM REQUIREMENTS BFD-OFM-10-011 Fire Alarm System plan(s) MUST be reviewed and approved by the Belmont Fire Department prior to the start of construction. The design and any changes must be fully compliant with NFPA 1, NFPA 101, NFPA

More information

For the Design, Installation, Commissioning & Maintenance of Fixed Gaseous Fire Suppression Systems

For the Design, Installation, Commissioning & Maintenance of Fixed Gaseous Fire Suppression Systems BAFE Scheme: SP203-3 Version 1: July 2008 Amendment No: 1 Fire Protection Industry Scheme, Reference SP203 Part 3 For the Design, Installation, Commissioning & Maintenance of Fixed Gaseous Fire Suppression

More information

FIRE ALARMS SYSTEMS - UCL GENERAL INSTALLATION DESIGN GUIDANCE & EMPLOYERS REQUIREMENTS

FIRE ALARMS SYSTEMS - UCL GENERAL INSTALLATION DESIGN GUIDANCE & EMPLOYERS REQUIREMENTS Fire Safety Technical Guide FIRE ALARMS SYSTEMS - UCL GENERAL INSTALLATION DESIGN GUIDANCE & EMPLOYERS REQUIREMENTS (All Buildings Except Sleeping Accommodation) Contents: 1.0 Introduction... 1 2.0. UCL

More information

How To Comply With The Loss Prevention Certification Board

How To Comply With The Loss Prevention Certification Board Loss Prevention Standard LPS 1014: Issue 5.3 This Loss Prevention Standard is the property of BRE Global Ltd. and is made publicly available for information purposes only. Its use for testing, assessment,

More information

Conventional Fire Detection and Extinguishant Control System Specification

Conventional Fire Detection and Extinguishant Control System Specification Conventional Fire Detection and Extinguishant Control System Specification Page 1 of 9 Scope Furnish a complete 24VDC Conventional, electrically supervised, combined fire detection and extinguishant release

More information

astec Integrated Alarm System USER GUIDE

astec Integrated Alarm System USER GUIDE astec Integrated Alarm System USER GUIDE 020008599 CONTENTS Full Set, Part Set and Disarm 3 Instant Full Set 3 Part Set with exit time 4 Bell Test 4 Bypassing zones 4 Switch Lights on/off 4 Bypass (24

More information

EDA-Z5008 & Z5020. Radio Fire Alarm System. User Manual

EDA-Z5008 & Z5020. Radio Fire Alarm System. User Manual EDA-Z5008 & Z5020 Radio Fire Alarm System User Manual Electro-Detectors Ltd. Electro House, Edinburgh Way Harlow, Essex, CM20 2EG UK Tel: 01279 635668. Fax 01279 450185 Email: eda@electrodetectors.co.uk

More information

FIRE ALARM PANEL & SYSTEM OPERATION ID50 SYSTEM. The Fire Alarm System can be activated in the following ways :~

FIRE ALARM PANEL & SYSTEM OPERATION ID50 SYSTEM. The Fire Alarm System can be activated in the following ways :~ ID50 SYSTEM The Fire Alarm System can be activated in the following ways :~ 1. By breaking the glass in a Manual Alarm Call Point 2. By a rise in temperature activating an Automatic Heat Detector 3. By

More information

Electronics Ltd. Presenting. Power, Intelligence... with a sense of feeling

Electronics Ltd. Presenting. Power, Intelligence... with a sense of feeling Electronics Ltd Presenting Power, Intelligence... with a sense of feeling By Appointment to Her Majesty The Queen Supplier of Fire Detection Equipment Kentec Electronics Ltd. Dartford Plug in slots K772

More information

Fire detection equipment

Fire detection equipment PRODUCT CATALOG Fire detection equipment www.apollo-fire.com Apollo Fire Detectors is one of the world s largest manufacturers of fire detectors, modules and notification devices. Established in 1980,

More information

AlarmSense 2-wire detection and alarm system. Product Guide

AlarmSense 2-wire detection and alarm system. Product Guide AlarmSense 2-wire detection and alarm system Product Guide Contents What is AlarmSense? 2 The purpose of AlarmSense 4 How AlarmSense works 4 Alarmsense Features 5 Detector removal monitoring 5 Priority/non-priority

More information

NC State University Design and Construction Guidelines Division 26 Fire Alarm Systems

NC State University Design and Construction Guidelines Division 26 Fire Alarm Systems NC State University Design and Construction Guidelines Division 26 Fire Alarm Systems 1.0 Purpose A. The following guideline provides the minimum standards and requirements for fire alarm systems. 2.0

More information

Security Systems Intrusion Alarm

Security Systems Intrusion Alarm Dufferin-Peel Catholic District School Board STANDARD TEXT GUIDELINE FOR Security Systems for SECONDARY AND ELEMENTARY SCHOOLS Prepared by the Plant Department With Assistance from Vision Dynamics Formatted

More information

FIRE ALARM AND DETECTION SYSTEMS SECTION 16721

FIRE ALARM AND DETECTION SYSTEMS SECTION 16721 PART 1 - GENERAL 1.01 WORK INCLUDED FIRE ALARM AND DETECTION SYSTEMS SECTION 16721 A. Provide a complete fully addressable, power limited, fire detection and evacuation system. The system shall be connected

More information

FIRE DETECTION AND ALARM SYSTEMS

FIRE DETECTION AND ALARM SYSTEMS HMO Information Sheet No 1 FIRE DETECTION AND ALARM SYSTEMS 1. Introduction When a property is in multiple occupation, the risk of fire breaking out is greater than in an ordinary single family home. Some

More information

I.S. 3218 :2013 Fire Detection & Alarm Systems

I.S. 3218 :2013 Fire Detection & Alarm Systems I.S. 3218 :2013 Fire Detection & Alarm Systems Overview of significant changes 26 th March 2014 FPS Ltd Today s Programme Commencement Transition Competence & Qualifications System Certification System

More information

Fire Safety Policy. Fire Safety Policy: May 2011 Page 1 of 6. Version 1. Scope:

Fire Safety Policy. Fire Safety Policy: May 2011 Page 1 of 6. Version 1. Scope: Version 1 Fire Safety Policy Scope: Effective Date: Review Date: Signed Off by: Author: Policy Owned by: This policy applies to Hackney Homes Ltd working on behalf of the London Borough of Hackney July

More information

Fire. The Fire Installers Mate. A guide to fire alarm systems design

Fire. The Fire Installers Mate. A guide to fire alarm systems design Fire The Fire Installers Mate A guide to fire alarm systems design BS 5839 Part 1:2002 A guide to BS 5839 Part 1:2002 Disclaimer This booklet is not intended to be a comprehensive guide to all aspects

More information

Fire Alarm Systems Care and Maintenance

Fire Alarm Systems Care and Maintenance April 2011 Country of Origin: United Kingdom Fire Alarm Systems Care and Maintenance Introduction A fire alarm installation is designed to provide early warning of a fire condition. To ensure that the

More information

Kentec Electronics Ltd. Units 25-27 Fawkes Avenue Questor Dartford Kent DA1 1JQ England Tel: +44(0)1322 222121 Fax: +44(0)1322 291794

Kentec Electronics Ltd. Units 25-27 Fawkes Avenue Questor Dartford Kent DA1 1JQ England Tel: +44(0)1322 222121 Fax: +44(0)1322 291794 Units 25-27 Fawkes Avenue Questor Dartford Kent DA1 1JQ England Tel: +44(0)1322 222121 Fax: +44(0)1322 291794 Kentec Electronics Ltd. E-mail: sales@kentec.co.uk Web: www.kentec.co.uk Loop Explorer V6.00

More information

I.S. 3218 :2013 Fire Detection & Alarm Systems

I.S. 3218 :2013 Fire Detection & Alarm Systems I.S. 3218 :2013 Fire Detection & Alarm Systems Overview of significant changes 26 th March 2014 FPS Ltd Today s Programme Commencement Transition Competence & Qualifications System Certification System

More information

THELETTINGS SPECIALISTS

THELETTINGS SPECIALISTS Letting made easy Why choose Heywoods? If you're thinking about letting a property, let the local experts at Heywoods do everything for you. Heywoods name has been associated with property in North Staffordshire

More information

Appendix 2 Specification and Requirements Servicing and Maintenance of Fire Systems and Fire Protection Devices

Appendix 2 Specification and Requirements Servicing and Maintenance of Fire Systems and Fire Protection Devices Servicing and Maintenance of Fire Systems and Fire Protection Devices Appendix 2 Specification and Requirements... 1 Servicing and Maintenance of Fire Systems and Fire Protection Devices... 1 1. INTRODUCTION

More information

Discovery 1-4 Loop Analogue Addressable Control Panel Application Guide

Discovery 1-4 Loop Analogue Addressable Control Panel Application Guide Discovery 1-4 Loop Analogue Addressable Control Panel Application Guide Contents Page 1.0 Introduction and Typical System Illustration 2 2.0 Cabinet Specifications 4 3.0 Hardware Specifications 7 4.0 Software

More information

VOCALISER USER INSTRUCTIONS. Pyronix Ltd OCTOBER 2000. RINS113 Issue 2

VOCALISER USER INSTRUCTIONS. Pyronix Ltd OCTOBER 2000. RINS113 Issue 2 VOCALISER USER INSTRUCTIONS Pyronix Ltd OCTOBER 2000 RINS113 Issue 2 9 RECEIVING A CALL FROM THE VOCALISER A telephone call from the Vocaliser is easily recognised by the distinctive three tones heard

More information

Fire alarm bells (and associated fire detection equipment) are tested on Wednesday mornings between 0830-0845.

Fire alarm bells (and associated fire detection equipment) are tested on Wednesday mornings between 0830-0845. FIRE SAFETY PROCEDURES, ST MARY S CAMPUS MEDICAL SCHOOL BUILDING These notes supplement the Imperial College London Fire Safety Policy and Code of Practice and give details of local fire safety management

More information

CFP 2/4/8 ZONE CONVENTIONAL FIRE ALARM CONTROL PANEL. user manual & log book. Approved Document No. DFU7001020 Rev 1

CFP 2/4/8 ZONE CONVENTIONAL FIRE ALARM CONTROL PANEL. user manual & log book. Approved Document No. DFU7001020 Rev 1 CFP 2/4/8 ZONE CONVENTIONAL FIRE ALARM CONTROL PANEL user manual & log book Approved Document No. DFU7001020 Rev 1 CONTENTS Safety...3 Important information regarding the safe use of this fire alarm panel

More information

radio fire alarm system Installed with minimum disruption Provides maximum protection

radio fire alarm system Installed with minimum disruption Provides maximum protection radio fire alarm system Installed with minimum disruption Provides maximum protection Key features Fully Addressable Intuitive Menu Structure 4 Access Levels Pre-Alarm Warning Head Contaminated warning

More information

Rancho Cucamonga Fire Protection District Prevention Bureau Standard

Rancho Cucamonga Fire Protection District Prevention Bureau Standard Rancho Cucamonga Fire Protection District Prevention Bureau Standard Title: Fire Alarm and Monitoring Systems Standard # 9-3 Effective: May 2002 Number of Pages: 7 Revised: January 2014 INTENT The intent

More information

Certificate of Acceptance

Certificate of Acceptance Critical Rail Temperature Monitor 3000 Product Description Product Image The CRTM 3000 (Critical Rail Temperature Monitor) monitoring system enables people to monitor rail temperature in real time. The

More information

(68.52) X. June 2000 Supercedes February 2000. xenex CONVENTIONAL FIRE DETECTION & ALARM SYSTEM. we look @ business differently

(68.52) X. June 2000 Supercedes February 2000. xenex CONVENTIONAL FIRE DETECTION & ALARM SYSTEM. we look @ business differently (68.52) X June 2000 Supercedes February 2000 xenex CONVENTIONAL FIRE DETECTION & ALARM SYSTEM.... we look @ business differently XENEX SYSTEM ARCHITECTURE Note: This schematic is for guidance only please

More information

Always on the Lookout Perfect Protection against Burglary

Always on the Lookout Perfect Protection against Burglary Always on the Lookout Perfect Protection against Burglary Terxon wired and hybrid alarm systems One system offers all possibilities Rely on experts With a qualified specialist installation contractor on

More information

25 Years of Manufacturing Excellence. Premier Quatro Addressable Fire Alarm System. Assessed to ISO 9001: 2008

25 Years of Manufacturing Excellence. Premier Quatro Addressable Fire Alarm System. Assessed to ISO 9001: 2008 Premier Quatro Addressable Fire Alarm System Premier Quatro 4 Loop Analogue Addressable Fire Alarm Panel The Premier Quatro is the new 4 loop analogue Alarm Systems. It is available in 1, 2, 3 or 4 loop

More information

AVAILABLE TO DOWNLOAD ON THE APOLLO APP. Fire Alarm Systems Design. a guide to BS5839

AVAILABLE TO DOWNLOAD ON THE APOLLO APP. Fire Alarm Systems Design. a guide to BS5839 AVAILABLE TO DOWNLOAD ON THE APOLLO APP a guide to Fire Alarm Systems Design BS5839 Part1:2013 The Regulatory Reform (Fire Safety) Order (FSO) became law on 1 October 2006 Legally you must comply! What

More information

PLAN REVIEW GUIDE FOR FIRE ALARM

PLAN REVIEW GUIDE FOR FIRE ALARM PLAN REVIEW GUIDE FOR FIRE ALARM PROJECT NAME: PERMIT # PROJECT ADDRESS: CONTACT PERSON: PHONE Fire alarm system installation information shall be provided on the appropriate architectural and electrical

More information

NJP-400A NJP-401A. Safely into a new day. Advanced modular FIRE ALARM CONTROL PANEL with additional functionality. I m on FIRE (Bruce Springsteen)

NJP-400A NJP-401A. Safely into a new day. Advanced modular FIRE ALARM CONTROL PANEL with additional functionality. I m on FIRE (Bruce Springsteen) Safely into a new day Advanced modular FIRE ALARM CONTROL PANEL with additional functionality NJP-400A NJP-401A I m on FIRE (Bruce Springsteen) EN 54-2, EN 54-4 Cert No. 1124a DESCRIPTION OP-400A, NJP-400A,

More information

Austin Independent School District Police Department Policy and Procedure Manual

Austin Independent School District Police Department Policy and Procedure Manual Policy 8.07 Austin Independent School District Police Department Policy and Procedure Manual Life Safety Systems I. POLICY The proper operations of the AISD Life Safety Systems (LSS) are essential for

More information

Control and Indicating Equipment

Control and Indicating Equipment VdS Guidelines for Fire Detection and Fire Alarm Systems VdS 2540en Control and Indicating Equipment Requirements and Test Methods VdS 2540en : 2010-12 (02) Publishing house: VdS Schadenverhütung GmbH

More information

Your responsibilities if you have an automatic fire alarm. A handy guide for owners and responsible persons

Your responsibilities if you have an automatic fire alarm. A handy guide for owners and responsible persons Your responsibilities if you have an automatic fire alarm A handy guide for owners and responsible persons Kent Fire and Rescue Service Contents Your responsibilities if you have an automatic fire alarm

More information

SECTION 13850 (28 31 00) FIRE DETECTION AND ALARM SYSTEM

SECTION 13850 (28 31 00) FIRE DETECTION AND ALARM SYSTEM SECTION 13850 (28 31 00) FIRE DETECTION AND ALARM SYSTEM ENGINEERING SPECIFICATION INTELLIGENT REPORTING FIRE DETECTION SYSTEM PART 1 GENERAL 1.1 DESCRIPTION A. This specification includes the furnishing,

More information

TS510 & TS500. Installation & User Guide. Compatible Equipment

TS510 & TS500. Installation & User Guide. Compatible Equipment Installation & User Guide Compatible Equipment TS510 REM - Remote Keypad 9040 - Loudspeaker DC54/58 - Digital Communicator SD1+ - Speech Dialler 496525 Issue A 1 of 10 TS510 and TS500 Overview Introduction

More information

Service details for Conwy Careline

Service details for Conwy Careline Service details for Conwy Careline Lifeline social alarm service Our Charter Mark award winning team of friendly and experienced Emergency Response Officers staff the control centre answering calls from

More information

DIRECTORATE OF ESTATES & FACILITIES

DIRECTORATE OF ESTATES & FACILITIES DIRECTORATE OF ESTATES & FACILITIES PROCEDURE AND INFORMATION MANUAL EPM PM4 Client Representative (University Project Manager) for Capital Projects Scope of Services Document Originated: April 2006 By:

More information

Mechanical &Electrical Services Modernisation. Presentation to The Commons & Lords Management Boards 26 th November 2008

Mechanical &Electrical Services Modernisation. Presentation to The Commons & Lords Management Boards 26 th November 2008 Mechanical &Electrical Services Modernisation Presentation to The Commons & Lords Management Boards 26 th November 2008 M&E Services Modernisation Context M&E Modernisation Overview Next Steps M&E Modernisation

More information

Fire Detection Product Range

Fire Detection Product Range Fire Detection Product Range World Leading Fire Detection Products from the NITTAN group Issue 1.0 Business Overview The Nittan Group has been at the forefront of the fire protection industry since 1954

More information

Loss Prevention Standard

Loss Prevention Standard Loss Prevention Standard : ISSUE 3.0 Requirements for the LPCB Approval and Listing of Companies Undertaking the Maintenance and Repair of Doorsets, Shutters, and Active Smoke/Fire Barriers This standard

More information

REQUEST FOR PROPOSAL FOR: Fire and Security Alarm Service and Monitoring

REQUEST FOR PROPOSAL FOR: Fire and Security Alarm Service and Monitoring MCC13-04 REQUEST FOR PROPOSAL FOR: Fire and Security Alarm Service and Monitoring Manchester Community College PURPOSE: The purpose of this REQUEST FOR PROPOSAL is to establish a contract for Manchester

More information

CB200W Water Leak Detection Panel Application Guide

CB200W Water Leak Detection Panel Application Guide Checked by: AJC Approved by: JBJ Contents CB200W Water Leak Detection Panel Application Guide 1. Cabinet Specifications... 2 2. Panel Hardware Specifications... 3 3. Panel Configuration... 4 4. Technical

More information

Engineering Innovation

Engineering Innovation Engineering Innovation In the Department of Transport and Main Roads September 2014 Foreword The Department of Transport and Main Roads role is to provide safe, functional transport infrastructure that

More information

Proposed changes to the Acceptable Solution for Building Code clause F7 (Warning Systems) Proposed amended Acceptable Solution for Warning Systems

Proposed changes to the Acceptable Solution for Building Code clause F7 (Warning Systems) Proposed amended Acceptable Solution for Warning Systems Proposed changes to the Acceptable Solution for Building Code clause F7 (Warning Systems) Appendix A Proposed amended Acceptable Solution for Warning Systems s in the grey boxes form part of the proposed

More information

DIVISION 28 ELECTRONIC SAFETY AND SECURITY SECTION 28 13 00 SECURITY AND ACCESS CONTROL SYSTEM

DIVISION 28 ELECTRONIC SAFETY AND SECURITY SECTION 28 13 00 SECURITY AND ACCESS CONTROL SYSTEM DIVISION 28 ELECTRONIC SAFETY AND SECURITY PART 1 GENERAL 1.01 DESCRIPTION A. Division 28 Contractor shall extend a complete Matrix Systems Access Control System as shown on the Drawings and as specified

More information

Information & Communications Technology Network Infrastructure Group Network Infrastructure Standards July 2013

Information & Communications Technology Network Infrastructure Group Network Infrastructure Standards July 2013 Information & Communications Technology Group Standards July 2013 Version 1.3 Revision History Version Date Author Description Draft 12/03/2007 Antonio Barbosa Initial document 1 13/06/2007 Matthew Williams

More information

Certificate of Acceptance

Certificate of Acceptance Product Description Product Image < Scope of Acceptance Full Acceptance / Trial Acceptance (delete as appropriate) Network

More information

BS5839 Part 1:2002 Overview

BS5839 Part 1:2002 Overview BS5839 Part 1:2002 Overview 1 Contents Introduction So why is the current standard being revised? The brief for the new standard Changes to structure of current Standard Enhanced certification of Fire

More information

BS 7 SIS Safety Information System Green Light for Your Production

BS 7 SIS Safety Information System Green Light for Your Production BS 7 SIS Safety Information System Green Light for Your Production SIS - GreCon Safety Information System The Challenge The Solution In big industrial plants, such as wood based panel productions, there

More information

Guidance for Responsible Persons on False Alarm Management of Fire Detection and Alarm Systems

Guidance for Responsible Persons on False Alarm Management of Fire Detection and Alarm Systems Thames House, 29 Thames Street Kingston upon Thames, Surrey, KT1 1PH Phone: +44 (0) 8549 5855 Website: www.fia.uk.com Guidance for Responsible Persons on False Alarm Management of Fire Detection and Alarm

More information

What is an intruder alarm?

What is an intruder alarm? How to Plan and install an Intruder Alarm PART 1 PART 1 August 009 What is an intruder alarm? An intruder alarm system monitors and detects unauthorised entry to properties homes and businesses alike -

More information

THE UNIVERSITY OF TEXAS AT AUSTIN HANDBOOK OF OPERATING PROCEDURES SECURITY SYSTEMS ALARM POLICY

THE UNIVERSITY OF TEXAS AT AUSTIN HANDBOOK OF OPERATING PROCEDURES SECURITY SYSTEMS ALARM POLICY THE UNIVERSITY OF TEXAS AT AUSTIN HANDBOOK OF OPERATING PROCEDURES Section I. General Policy Guidelines A. Policy Statement SECURITY SYSTEMS ALARM POLICY Part 2. Campus Services Section A. General Campus

More information

Analogue addressable devices

Analogue addressable devices Discovery Analogue addressable devices from Channel Safety Systems Discovery Analogue addressable devices Discovery is a range of high-specification, intelligent fire detectors that are developed to meet

More information

COMPANY NAME. Environmental Management System Manual

COMPANY NAME. Environmental Management System Manual Revision No. : 1 Date : DD MM YYYY Prepared by : Approved by : (EMR) (Top Management) Revision History Revision Date Description Sections Affected Revised By Approved By Table of Content 0.0 Terms and

More information

SECURIT DEPARTMENT CIRCLE OFFICE 802,CHOPASNI ROAD JODHPUR-0291-2611213 (BY REGD POST) COJ/SEC/ BAC 19/05/2011. 2010

SECURIT DEPARTMENT CIRCLE OFFICE 802,CHOPASNI ROAD JODHPUR-0291-2611213 (BY REGD POST) COJ/SEC/ BAC 19/05/2011. 2010 (BY REGD POST) SECURIT DEPARTMENT CIRCLE OFFICE 802,CHOPASNI ROAD JODHPUR-0291-2611213 COJ/SEC/ BAC 19/05/2011. 2010 ----------------------------------------- -----------------------------------------

More information

Essex Fire Authority. Fleet Management. Internal Audit Report (4.12/13) 28 February 2013 FINAL. Overall Opinion

Essex Fire Authority. Fleet Management. Internal Audit Report (4.12/13) 28 February 2013 FINAL. Overall Opinion Essex Fire Authority Fleet Management Internal Audit Report (4.12/13) 28 February 2013 FINAL Overall Opinion Essex Fire Authority Fleet Management 4.12/13 CONTENTS Section Page Executive Summary 1 Action

More information

Fire Alarm System Plans Submittal Guidelines For New and Existing Systems

Fire Alarm System Plans Submittal Guidelines For New and Existing Systems Fire Alarm System Plans Submittal Guidelines For New and Existing Systems SCOPE The Temecula Fire Prevention Bureau (TFPB) has established the following requirements for the submittal of all fire alarms,

More information

Wharton Construction Ltd. Quality Manual. Kellaw Road Yarm Road Business Park Darlington DL1 4YA

Wharton Construction Ltd. Quality Manual. Kellaw Road Yarm Road Business Park Darlington DL1 4YA Quality Manual Kellaw Road Yarm Road Business Park Darlington DL1 4YA MANUAL IDENTIFICATION This document is a controlled/uncontrolled copy. Copy Number:...of... Issued to... Title... Holders of controlled

More information

UFGS-28 33 00.00 40 (February 2011) UNIFIED FACILITIES GUIDE SPECIFICATIONS

UFGS-28 33 00.00 40 (February 2011) UNIFIED FACILITIES GUIDE SPECIFICATIONS USACE / NAVFAC / AFCEC / NASA UFGS-28 33 00.00 40 (February 2014) ----------------------------------- Preparing Activity: NASA Superseding UFGS-28 33 00.00 40 (February 2011) UNIFIED FACILITIES GUIDE SPECIFICATIONS

More information

Security, Access Management and Key Control Policy and Procedures

Security, Access Management and Key Control Policy and Procedures 1 Policy Security, Access Management and Key Control Policy 1.1.1 The goal of the Vice President, Business Affairs and Facilities and Services is to provide a safe, comfortable, secure learning environment

More information

1.1 Terms of Reference Y P N Comments/Areas for Improvement

1.1 Terms of Reference Y P N Comments/Areas for Improvement 1 Scope of Internal Audit 1.1 Terms of Reference Y P N Comments/Areas for Improvement 1.1.1 Do Terms of Reference: a) Establish the responsibilities and objectives of IA? b) Establish the organisational

More information

SECTION 16721 FIRE ALARM AND DETECTION SYSTEMS

SECTION 16721 FIRE ALARM AND DETECTION SYSTEMS SECTION 16721 FIRE ALARM AND DETECTION SYSTEMS The equipment requirements of this section apply to the IUB Campus. The IUPUI Campus has a preferred vendor agreement for fire alarm systems. Contact Pat

More information

Personal Computer Standard. National Infrastructure Group. National Infrastructure Group, ehealth Leads, ehealth Architecture and Design.

Personal Computer Standard. National Infrastructure Group. National Infrastructure Group, ehealth Leads, ehealth Architecture and Design. Document Control Document Title Personal Computer Standard Version 1.0 Owner National Infrastructure Group Author Paul McLaren, paul.mclaren@scotland.gsi.gov.uk, 0131 244 2258 Creation date 13 th November

More information

University Design Standard. Fire Alarm Systems

University Design Standard. Fire Alarm Systems University Design Standard Fire Alarm Systems 1.0 Overview This document provides Virginia Tech s standards for the design and installation of fire alarm systems and equipment in new construction, retrofit

More information

CO2 Alarm. Operation. Application

CO2 Alarm. Operation. Application CO Alarm 100-77V AC Supply Voltage Two pre-configured alarm and control thresholds Thresholds factory set to customer requirements on dispersive infrared sensing technology Optional internal audible alarm

More information

University of Brighton School and Departmental Information Security Policy

University of Brighton School and Departmental Information Security Policy University of Brighton School and Departmental Information Security Policy This Policy establishes and states the minimum standards expected. These policies define The University of Brighton business objectives

More information

CONSULTANT PROCEDURES & DESIGN GUIDELINES 28 13 00 ACCESS CONTROL SYSTEM

CONSULTANT PROCEDURES & DESIGN GUIDELINES 28 13 00 ACCESS CONTROL SYSTEM GENERAL: To provide minimum standards for Access Control Systems. PART 1 Common Work Results for Access Control System 1.1 Owner will provide server and software for connecting control panels through the

More information

User s Information Guide R1A

User s Information Guide R1A HSC505-R Home Security Controller - User Manual Release R1a Pi HSC505 and Pi HSC505R Home Security Controller User s Information Guide R1A Page 1 QD Dynamics (Pty) Ltd reserves the right to make changes

More information

DOCUMENTED PROCEDURE MANUAL

DOCUMENTED PROCEDURE MANUAL NAPIT REGISTERED INSTALLERS DOCUMENTED PROCEDURE MANUAL CONTENTS 1. INTRODUCTION 2. DEFINITIONS 3. RESPONSIBILITY FOR QUALITY 4. DOCUMENT AND DATA CONTROL 5. CUSTOMER ENQUIRIES AND QUOTATIONS 6. CONTRACTS

More information

FIRE ALARM SYSTEM TECHNICAL SPECIFICATIONS Page 1 of 19

FIRE ALARM SYSTEM TECHNICAL SPECIFICATIONS Page 1 of 19 TECHNICAL SPECIFICATIONS Page 1 of 19 FIRE DETECTION AND ALARM SYSTEM Scope Furnish a complete 24V DC analogue addressable, electrically supervised, zone annunciated, fire detection and alarm system as

More information

Standard the the Raising

Standard the the Raising Raising the Standard Introduction to BS 5839-1:2013 An Overview of the BS 5839 1:2013 for professionals who are responsible for the provision of fire detection and alarm systems for buildings Agenda Introduction

More information

Overview of Fire Alarm Systems and Maintenance

Overview of Fire Alarm Systems and Maintenance Overview of Fire Alarm Systems and Maintenance By Mr. David Goh Vice President Fire Safety Managers Association Convener of Working Group for CP 10 : 2005 Er. Matthew Kwek Committee Member Fire Safety

More information

Solution Ultima ICP-CC488 Home security you can rely on

Solution Ultima ICP-CC488 Home security you can rely on Solution Ultima ICP-CC488 Home security you can rely on Keeping your home and family safe doesn t need to be complicated. That s why we ve made the Ultima security system so easy to use all it takes is

More information

IT Services stakeholder roles & responsibilities in Capital Projects

IT Services stakeholder roles & responsibilities in Capital Projects IT Services/Facilities Management Directorate IT Services stakeholder roles & responsibilities in Capital Projects University of Reading 2011 Page 1 of 10 Document Approval Originator Approved for Issue

More information

Simplex Fire Products Corporate Profile

Simplex Fire Products Corporate Profile Simplex Fire Products Corporate Profile Fire Detection and Evacuation Systems SHOPPING & ENTERTAINMENT CENTRES GOVERNMENT AND DEFENCE TRANSPORT INFRASTRUCTURE HOSPITAL AND HEALTHCARE EDUCATION FACILITIES

More information

Fire Alarms- Use of buildings when they are out of service

Fire Alarms- Use of buildings when they are out of service Fire Alarms- Use of buildings when they are out of service Document control information Published document name: no-alarm-gn.pdf Date issued: January 2016 Version: 4 Previous review dates: May 2014 Next

More information

NATIONAL INSTITUTE FOR CERTIFICATION IN ENGINEERING TECHNOLOGIES. Level III Content Outline

NATIONAL INSTITUTE FOR CERTIFICATION IN ENGINEERING TECHNOLOGIES. Level III Content Outline Fire Alarm Systems Level III Content Outline The skills and knowledge listed under each task are suggestive of those involved in that task, but are not intended to constitute an exhaustive listing. 3.1

More information

Request for Proposals. For a. Fire Station Alerting System

Request for Proposals. For a. Fire Station Alerting System Request for Proposals For a Fire Station Alerting System SouthCom Combined Dispatch Center 21113 Dettmering Dr., Matteson, IL. 60443 Ph: (708) 283-6631 Fax: (708) 283-6641 REQUEST FOR PROPOSALS 911 EMERGENCY

More information

CEA Base requirements for Installers of Automatic Fire Detection and Alarm Systems (AFDS), Intruder Alarm Systems (IAS) and/or CCTV-Systems

CEA Base requirements for Installers of Automatic Fire Detection and Alarm Systems (AFDS), Intruder Alarm Systems (IAS) and/or CCTV-Systems 26 Boulevard Haussmann F 75009 Paris Tél. : +33 1 44 83 11 83 Fax : +33 1 47 70 03 75 www.cea.assur.org Square de Meeûs, 29 B 1000 Bruxelles Tél. : +32 2 547 58 11 Fax : +32 2 547 58 19 www.cea.assur.org

More information

[Project Name] NZTA Contract No. [Contract Number] Schedule of Prices

[Project Name] NZTA Contract No. [Contract Number] Schedule of Prices [Project Name] NZTA Contract No. [Contract Number] Schedule of Prices Schedule of Prices SP1

More information

Application Guide HMOs

Application Guide HMOs Application Guide HMOs 2 Aims of this guide 3 What is AlarmSense? 3 What is an HMO 3 Fire Protection for an HMO 3 Approved Document B 4 Mandatory Licensing 4 BS 5839 4 Categories of System 6 Application

More information

Original Document 10/16/07 Revised 01/30/09 2 nd Revision 01-23-12 3 rd Revision- 12/18/14

Original Document 10/16/07 Revised 01/30/09 2 nd Revision 01-23-12 3 rd Revision- 12/18/14 North Collier Fire Control & Rescue District Greater Naples Fire Rescue District Immokalee Fire Control & Rescue District 2800 North Horseshoe Drive Naples, Florida 34104 SYSTEM REHABILITATION PLAN CHECKLIST

More information

SECTION 16853 ZONED (DC LOOP) FIREALARM SYSTEM

SECTION 16853 ZONED (DC LOOP) FIREALARM SYSTEM SECTION 16853 ZONED (DC LOOP) FIRE-ALARM SYSTEM PART 1 - GENERAL 1.1 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General and Supplementary Conditions and Division 1

More information

I N T E LLIGENCE WATC H. Ireland s only 24/7/365 CCTV intruder monitoring services with dedicated back up facilities

I N T E LLIGENCE WATC H. Ireland s only 24/7/365 CCTV intruder monitoring services with dedicated back up facilities I N T E LLIGENCE WATC H Ireland s only 24/7/365 CCTV intruder monitoring services with dedicated back up facilities WELCOME TO I-WATCH i-watch (Intelligence Watch) provides monitoring services for residential

More information

2 TM. Users Manual. SEC100, SEC200 USB Media Alert

2 TM. Users Manual. SEC100, SEC200 USB Media Alert 2 TM 2 TM Users Manual SEC100, SEC200 USB Media Alert Version 5.0 10/7/2014 Thank you for purchasing the Sonic-connect USB Media Alert Device, your companion to help you stay connected with today s specialized

More information

FIRE CODE INTERPRETATION

FIRE CODE INTERPRETATION FIRE CODE INTERPRETATION March 2008 ISSUE: Existing Fire Alarm Systems FCI-08-06 Page 1 of 9 The purpose of this bulletin is to identify conditions where a building fire alarm system may be subject to

More information

FIRE ALARM SYSTEM SUBMITTAL CHECKLIST AND APPLICATION

FIRE ALARM SYSTEM SUBMITTAL CHECKLIST AND APPLICATION PERMITS AND INSPECTIONS FIRE ALARM SYSTEM SUBMITTAL CHECKLIST AND APPLICATION 911 Assigned PROJECT LOCATION Subdivision: Lot: Blk: Sec: PROJECT New Construction Addition/Remodel Demolition Other: Number

More information

SECTION 13: COMMUNICATIONS CONTENTS

SECTION 13: COMMUNICATIONS CONTENTS SECTION 13: COMMUNICATIONS CONTENTS 13.1 INTRODUCTION 2 13.2 INFRASTRUCTURE FOR VOICE AND DATA NETWORKS 3 13.2.1 Building Communications Room 3 13.2.2 Floor Communications Rooms 3 13.3 DATA NETWORKS 3

More information

Residential & Commercial Alarm Systems by Gross Security, LLC

Residential & Commercial Alarm Systems by Gross Security, LLC 151 Main Street, Suite, 1, Get these great features with a landline or cellular alarm system from Gross Security, LLC Alarm system prices include installation Base system includes one hour of training

More information

DELAWARE STATE FIRE MARSHAL FIRE ALARM SYSTEM CERTIFICATE OF INSTALLATION

DELAWARE STATE FIRE MARSHAL FIRE ALARM SYSTEM CERTIFICATE OF INSTALLATION Phone System Owner Phone System Engineered by: of Record Drawings: of System Manuals: of Test Reports: System Installer 1. GENERAL INFORMATION Phone Delaware License No: Certificate Holder No. System Supplier

More information

Our after-sales support

Our after-sales support Static Systems Group is an ISO 9001 accredited company - your assurance that we are a reputable company who take quality, service and reliability seriously. Our after-sales support Yours for a life-time

More information

Security System User Guide

Security System User Guide Security System User Guide Contents 1. Introduction... 1 Controls and Displays... 3 Displays... 3 Controls:... 4 2. Everyday Operation... 5 Access to the System... 5 Entering and Leaving the Protected

More information

Invitation to Bid FIRE ALARM & DETECTION SYSTEM

Invitation to Bid FIRE ALARM & DETECTION SYSTEM Invitation to Bid FIRE ALARM & DETECTION SYSTEM Responses to an Invitation to Bid will be received by the Purchasing Supervisor, Sumner County Board of Education, 1500 Airport Road, Gallatin, TN 37066

More information