FIRE ALARMS SYSTEMS - UCL GENERAL INSTALLATION EMPLOYERS & REQUIREMENTS DESIGN GUIDANCE

Size: px
Start display at page:

Download "FIRE ALARMS SYSTEMS - UCL GENERAL INSTALLATION EMPLOYERS & REQUIREMENTS DESIGN GUIDANCE"

Transcription

1 Fire Safety Technical Guide Contents FIRE ALARMS SYSTEMS - UCL GENERAL INSTALLATION EMPLOYERS & REQUIREMENTS DESIGN GUIDANCE (Student Hals of Residences - Sleeping Accommodation) 1.0. Introduction General Fire Alarm & Device Design Standards General Requirements & Design Standards Fire Alarm Panels & Electrical Supplies Manual Call Points (MCPs) Sounders (Sound Pressure Requirements) Beam Detectors Facilities for Hearing Impaired People Fire Resistant Cabling Marking and Indicating of Fire Alarm Devices Ceilings, Ducts & Voids Door Hold Open, Fire Dampers & Other Automatically Released Equipment Provision of Audible & Visual Warning at Internal Building Boundaries Access Control Devices Connected to Fire Alarm Systems Mechanical & Electrical, Air Handling & Smoke Control Equipment Cause & Effect Matrix Fire Alarm System Passive Fire Protection Fire Brigade Communications General Commissioning Requirements Sleeping Risk Equipment Overview INTRODUCTION 1.1. UCL strives to improve its standards, designers, installers and maintenance companies must be able to demonstrate their competence to design, install and commission the system, e.g. by certification to BAFE SP203, LPS1014 or other relevant standard and have ISO9001 Quality Management System compliance or equivalent, will be acceptable to undertake works on our estate. Date Last Amended: Dec 15 (Rev 4) 1.

2 1.2. The following information will be of assistance to Design Consultants, Project Managers and Contractors employed by UCL or its agents. It is to be regarded as a general statement of requirements and is in addition to any British Standard Recommendation or other instructions received from the Local Fire or Building Control Other Related Technical Notes: UCL student halls of residence fire detection and alarm system commission of software cause and effect confirmation of room testing schedule = TN055A; Specification for smoke alarms in UCL owned domestic flats, apartments, dwellings and similar accommodation = TN055B; (c). UCL student halls of residence fire safety design and refurbishment strategy = = TN050; 2.0. GENERAL FIRE ALARM & DEVICE DESIGN STANDARDS 2.1. New fire detection and alarm system provided in UCL properties must use standard equipment and open protocols to ensure communality of systems, efficient maintenance, control of software and engineering access. No other fire alarm panels or systems will be acceptable unless written permission through the UCL Chief Engineer / UCL Fire Safety Manager is sought first Loop Capacity - loops should be designed so that the numbers of devices on the loop is limited so that there is some (approx.) 20% spare capacity - e.g. maximum loop capacity = 126 devices - then the actual loop device numbers should be no more than 105 devices as a general rule Fire Detection - residential and sleeping accommodation must generally be designed to meet a minimum of BS Life Risk 2 (L2) provision of Automatic Fire Detection Where Apollo Discovery Multi-Sensing heads are used; they will need to be programmed to meet the local conditions by changing the ratio of heat to smoke detection. Generally (as rule of thumb guidance only), Apollo discovery multi-sensing heads have five settings (check the latest specification by Apollo for accuracy before instructing): Mode 1 - the most sensitive setting using both heat & smoke monitoring and reacting at around less than 3% obscuration of the optical head, Mode 2 - optical sensing setting only, that reacts at less than 3% obscuration of the optical head, Mode 3 - medium sensitivity setting, which uses both heat & smoke monitoring and reacts at less than 3% obscuration of the optical head, Date Last Amended: Dec 15 (Rev 4) 2.

3 Mode 4 - least sensitive setting using both heat & smoke monitoring and reacting at around 5% obscuration of the optical head - use this setting in all laboratories and periphery kitchen areas, Mode 5 - heat sensing setting only, 3.0. GENERAL REQUIREMENTS & DESIGN STANDARDS 3.1. All fire alarm systems in UCL premises are to be designed to comply with the latest edition of BS Fire detection and fire alarm systems for buildings - Code of practice for design, installation, commissioning and maintenance of systems in non-domestic premises; and other relevant parts of BS5839 series, as necessary Unwanted alarms - the London Fire Brigade and other local Fire require all possible measures to be taken to reduce the instances of unwanted fire alarm activations and calls to the fire authority. Electrical Service Engineers are to take considerable care to ensure that their fire alarm design reduces unwanted fire alarms through thoughtful consideration and understanding of room / space function where detection is provided. This will help substantially to reduce the potential for unwanted alarms through positioning of detection to avoid activation from on-suite showers etc. 3.3 Halls of Residence Fire Alarm Design Principle Given the prominence of unwanted fire alarms in halls of residence, and in view of London Fire Brigade s policy of charging for attendance, the configuration of each fire alarm in halls of residence will be subject to review by UCL. UCL requires that initial detection will warn local occupants. This may be just within that room, or within every room in the surrounding corridor, decided on a case-by-case basis. Control and indicating equipment that supports such flexible configurations is therefore required Unwanted Alarm & Design Principles - in all new installations or upgrade of fire alarm systems within UCL residences, the general design principle shall be: smoke detector activation in a bedroom will trigger the sounder in the room only or each room within that particular corridor (subject to risk assessment based on building construction) to act as a local warning (similar to Domestic BS : Smoke Alarm). This will generate a pre-fire alarm signal and warning at the master panel, but not a global fire alarm activation or occupant evacuation, unless: (1). the sensor detects heat gain as well as smoke obscuration; (2). a second detector activates; (3). if a Manual Call Point is activated; Date Last Amended: Dec 15 (Rev 4) 3.

4 (c.). UCL Fire Technical Note -TN055 fire alarm panel is to self-cancel room or rooms off that corridor (subject to site-specific configuration) fire pre-alarm, if the condition does not progress into full fire activation mode automatically after suitable time out delay (5 minutes). Cause & Effect of detector heads used in this fire alarm strategy must follow the following principals: (1). Heat detector (either RofR or fixed type) on activation, is to cause full fire evacuation of occupants. (2). Smoke detectors located in corridors stair enclosures forming part of the Means of Escape (other than Apollo Discovery Multi-Sensing combination type) on activation, is to cause full fire evacuation of occupants. (3). Apollo Discovery Multi-Sensing smoke detectors installed in student bedrooms on activation: (i). local alarm mode indicates pre-alarm on master panel warning sounder in room (or rooms throughout that corridor depending on risk assessment) only, for approx. 5 minutes; if no change in conditions, then the fire alarm system is to reset automatically; (ii). (iii). (iv). local alarm mode on change of room conditions such as increasing levels of obscuration or heat is detected at combination head, system to change mode and cause full fire evacuation of occupants immediately; No change to the local room conditions - local alarm activates in room (and surrounding rooms if necessary under design risk assessment) only and pre alarm at main fire panel; any change of local room conditions - full fire evacuation of occupants immediately Cluster Flat Design Principals - provided with least sensitive setting using heat & smoke monitoring and reacting to approximately 5% obscuration of the optical head to be used & programmed in the following way: Apollo Discovery Multi-Sensor - detector heads to be used in all bedrooms in sleeping accommodation: (1). Detectors are to be programmed on installation for operations at MODE 4 ( student setting ) for all cluster bedrooms and areas such as corridors outside of showers or kitchens that may be effected by cooking products or steam from bathrooms etc.; Date Last Amended: Dec 15 (Rev 4) 4.

5 (2). Programmed on installation for operations at MODE 4 for areas such as cluster flat corridors, that may be affected by cooking products from kitchens or rooms etc.; (c). Apollo heat detection to be used in kitchens - provide Rate of Rise heat detectors; Manual Call Points (MCP) - are to be provided so that there is a shorter distance for occupants in a real fire situation to operate a call point, as follows: (1). Cluster Flats (containing six rooms with kitchen unit etc., with access to a main corridor) - provide a MCP complete with security covers to prevent accidental use to be provided at the cluster flat exit on to main corridor. (2). Grouped Cluster Rooms (containing rooms with kitchen unit etc., formed around a central corridor) - then additional MCPs complete with security covers to prevent accidental use, located where cluster flat groups stop and a new cluster group starts requiring additional MCPs and with shorter travel distances Studio Flats - Design Principals: Studio Flats - due to unwanted alarm issues will be provided with smoke detection and control unit to comply BS5839-6; see UCL Fire Safety Technical Note TN055B. An Apollo rate of rise heat detector will be provided in all studio flats positioned with the flat within 500mm in from the entrance door. (1). all studio flat bedrooms (care on positioning standalone smoke detector in room - away from cooker, showers & steam), (c). Manual Call Points - position additional MCPs so that studio flat occupants travel no more than 15m in any direction, to operate a unit FIRE ALARM PANELS & ELECTRICAL SUPPLIES 4.1. The fire detection system shall be designed, installed and commissioned in accordance with, and all elements shall meet the requirements of BS , BS EN 54 Parts 1, 2 & 4 and other relevant Codes of Practice. The Fire Alarm Control Panel shall be independently certified as complying with requirements of EN54-2&4. The Independent approvals body shall be either British Standards Institute (BSI) or Loss Prevention Council Board (LPCB) 429C The panel must be capable and compatible of using and switching between all modes of Apollo Discovery detection heads, using alarm confirmation Date Last Amended: Dec 15 (Rev 4) 5.

6 facilities. In addition, have pier-to-pier networking and IP gateway facilities. Furthermore, they must have adjustable time to alarm and be programmable to meet the local conditions The following fire alarm panel manufactures MUST be used (adjoining building FA panel types and other consideration may need to be taken into account in the choice of panels) but Advance at present panels can provide desired approach at Para 3.0.: Advanced Electronic Ltd - Mx Range (see: Electrical Supplies & Batteries - UCL requires standby batteries for fire alarm systems to last for 60 hours not for the minimum specified by the British Standard of 24 hours. Where standby generator provide then this may dropped for standard 24-hour battery backup Main Electrical Supply to Fire Alarm Panels - any new fire alarm system will require a dedicated 240v ac supply in accordance with the latest editions of BS 7671 & BS This circuit is to be installed using fire resistant cable and terminated into a double pole, isolating spur with key switch as defined in BS Main Electrical Isolation to Fire Alarm Panels - means should be provided for double pole isolation of the mains supply to all parts of the system; the isolation facilities should be suitably sited, near the equipment served, for use by maintenance technicians without the need for access to remote parts of the building. It should be possible to lock the facilities in both the normal and isolate positions to prevent unauthorised use. It should be possible to lock the facilities in both the normal and isolate positions to prevent unauthorised use UCL requires a Fire Safety Isolator Switch (available from to be provided which is a secure method for safely isolating the mains voltage supply to fire systems in accordance with BS 5839: Part 1. The 'Fire Safety Isolation' switch can only be isolated by an authorised person, by means of a keylock switch - the key is removable in both ON/OFF positions, The fuse cannot be removed without taking the cover off & when in the off position the FUSE is disconnected from the supply, A neon indicator is provided to indicate mains present at the switched output, Technical Specification: Date Last Amended: Dec 15 (Rev 4) 6.

7 o Working Voltage : 250AV o Switch Contact Rating : Double Pole - 250V AC 4Amp o o o o FUSE Rating : Max - 6A Fast (20mm) supplied Enclosure Material : RoHS Compliant FR ABS Weight : 175g Switch Surge Rating : 80Amp o Key Number : 901 o Housing Size: Single Gang : W.86 x L.86 x H.56.5mm 5.0. MANUAL CALL POINTS (MCPs) 5.1. The following Manual Call Points (MCPs) should be used for all systems: Apollo MCPs suitable for product range being installed (see: KAC MCPs Alarm Company Ltd (see: In student halls circulation spaces, common rooms, bars of UCL Student s Union occupancy and vulnerable places - Anti-Tamper security covers are to be fitted to each call point, supplied by: Apollo - transparent Hinged Cover for use with XP95 and Discovery Manual Call Points (Apollo Ref: /179); KAC Ltd - as above under 'accessories' (KAC Ref: PS200 Plain Hinged Cover); 5.3 All instances of anti-tamper covers on manual call points are to be recorded as a Variation in accordance with the recommendations of BS by the company installing the covers / main fire alarm contractor SOUNDERS (SOUND PRESSURE REQUIREMENTS) 6.1. Sleeping Accommodation - loop driven Intelligent sounders compatible with Apollo protocol and detectors are to be used to ensure devices can be programmed using unwanted fire alarm strategy as per Para 3.0 above. Date Last Amended: Dec 15 (Rev 4) 7.

8 6.2. The following standard sounders may be used: UCL Fire Technical Note -TN055 Apollo - loop driven sounders at should have a defaulted setting of 90+dB(A) Fulleon - further information can be found at: General Note on Sound Levels (Sleeping Accommodation) - UCL require an average sound pressure level in all areas of 85 db(a) (not 75 db(a) as specified in the BS ), particularly at the bed head. Where sound pressure levels fall below this standard, additional sounders MUST be installed or other means used, to raise the sound pressure levels. Often the BS minimum sounder levels are not adequate for this task; furthermore, fire doors can reduce sounder levels by up to 40 db(a) when closed further reducing overall sounder levels. It is expected that each room in a halls of residence will be supplied with a sounder within the room to achieve a suitable warning of fire. Note - Consultants and contractors are to ensure that contingency funds from the project are available at pre-contract, to ensure that additional sounders can be installed at commissioning should the sound pressure coverage fall below acceptable levels any particular area. Where sound levels fall below this standard, additional sounders MUST be installed or other means used, to raise the sound levels At the commissioning of the system (regardless of the size of installation), a sound pressure check MUST be carried out with sound pressure levels being recorded on a log sheet. The log is to be submitted with the Commissioning Certificate ; short falls are to be addressed through addition of extra sounders within the area Visual Alarms - meeting BS EN to be provided (visual flashing Red strobe lights or new LED Technology) in the following locations: Disabled Refuges - where disabled or hearing impaired persons may use facilities (such as WCs) and in Disabled Refuges to allow communications with other by users, Find the Panel - to identify and locate the main fire alarm panel particularly in property with identical frontage, or where the panel location is not obvious or in the normal location of the main entrance area, 7.0. BEAM DETECTORS 7.1. Where there is a requirement for covering large open spaces then Open Area Smoke Imaging Detection (OSID) by xtralis Ltd beam detectors should be considered. These beam detectors use two wavelengths to distinguish between particle size and solid intruding objects, thus helping to reduce unwanted alarms. Moreover, one unit because of its design, cover much Date Last Amended: Dec 15 (Rev 4) 8.

9 more area with multipoint viewing from a single beam detector head reducing the need for point detection. Further information can be found at FACILITIES FOR HEARING IMPAIRED PEOPLE 8.1. UCL has a specific policy and procedures for accommodating people with disabilities - please discus with UCL Fire Safety Manager prior to design. UCL will not accept blanket coverage of a building with supplementary visual alarms (LED) as per guidance in BS Hearing Impaired requirements connected to the fire alarm may need to be supplied - Please see - UCL Fire Safety Technical Note (TN) Visual Alarms - visual alarms are to be provided (visual flashing Red strobe lights or new LED Technology) where disabled or hearing impaired persons may use facilities (such as WCs or common rooms etc.), 8.4. Deaf Message Service (DMS) - for Deaf messaging within student Halls provide a DMS system which deaf or hard of hearing person enters the residence, they will see clear signage asking them to text a location code to the DMS number. Once a connection text has been sent, the person will be connected to DMS for that location. After 12 months they will receive a text asking them to reconnect, connection text costs the same as a standard SMS text FIRE RESISTANT CABLING 9.1. Fire cables used in the installation of fire alarm systems meeting the latest edition of BS / BS 6387 / BS 7629 in design, construction and installation All cables shall be coloured Red, unless there is overriding aesthetic reasons for White to be used. Special attention is to be paid to the terminating of cables to ensure that earth faults are eliminated The following cables should be used in all instances: FP 200 Gold or cabling that is equal and approved; MIC cabling is required where routes provide mission critical signals or pass through a high risk or vulnerable areas (as required under BS ); 9.4. Fixing - all fire alarm cabling is to be fixed to the structure of the building, fixed in a cable tray or cable management system only using metal ties. No other fixing is acceptable. Date Last Amended: Dec 15 (Rev 4) 9.

10 10.0. MARKING AND INDICATING OF FIRE ALARM DEVICES UCL Fire Technical Note -TN Labelling - all fire alarm devices are to be permanently marked or using suitable adhesive labels, to indicate the device Zone and Address number Identification - where remote or hidden detectors / devices are placed in voids, ducts or above ceilings, a suitable LED repeater indicator is to be provided in a logical and adjacent location. All LED indicators are to be clearly marked specifying type of device, address number and remote device location CEILINGS, DUCTS & VOIDS Ceiling Voids (Enclosed & Down Stands - see BS 5839:1 2013/Para 22(d)(2)) where an enclosed or down stand void area is greater than 800mm, but there is no risk (e.g. electrical equipment etc.) it may be considered as 'low risk', then it is reasonable not to provide AFD in these spaces. This should be recorded as a variation on the relevant system certificate. However, where there is an obvious risk such as significant electrical equipment (other than light units) or air handling units / chillers / void passes over other rooms or compartments, then the void should be provided with appropriate automatic fire detection as any electrical / equipment fire may not be detected at it initial stages. Clarification may be sought for the UCL fire safety manger Detectors in Voids & Ducts - any void where detection is provided MUST be fully accessible and not obstructed for maintenance purposes. This means that ceiling tiles or access panels must be available directly below the detector to allow maintenance and a testing pole to be used, which requires a clear vertical path from below to be maintained Identification of Hidden Devices - see Para 10.2 above DOOR HOLD OPEN, FIRE DAMPERS & OTHER AUTOMATICALLY RELEASED EQUIPMENT These items should adhere to the terms of latest edition of BS It should be noted that 'door holders' are generally not acceptable on any fire door that leads directly onto a protected stair (to be discussed with the UCL fire safety manager) Electromagnetic door release switches are to be positioned in a clear and accessible location, to prevent damage to fixings by doors being pulled close against the magnetic holders. See UCL fire safety technical note TN016. Date Last Amended: Dec 15 (Rev 4) 10.

11 13.0. PROVISION OF AUDIBLE & VISUAL WARNING AT INTERNAL BUILDING BOUNDARIES CONNECTED TO THE FIRE ALARM SYSTEM Where the Means of Escape (MoE) routes access and egress passes through a building boundary, it is necessary to provide Visual and Audible Warning signs connected to the fire alarm systems and it will be necessary to interface with the fire alarm system to meet UCL, local fire and District Surveyor Authority requirements. See UCL fire safety technical note TN ACCESS CONTROL DEVICES CONNECTED TO FIRE ALARM SYSTEMS Where security Access Control Systems are to be installed in a building, it will be necessary to interface with the fire alarm system to meet UCL, local fire and District Surveyor requirements. See UCL fire safety technical note TN001 & TN MECHANICAL & ELECTRICAL, AIR HANDLING & SMOKE CONTROL EQUIPMENT Where mechanical & electrical systems and smoke control measures are provided and connected to the fire alarm system, please see UCL Fire Safety Technical Notes TN038 & TN039 for general requirements CAUSE & EFFECT MATRIX FIRE ALARM SYSTEM Designers are to provide a cause and effect chart for all new systems - see UCL fire safety technical note TN PASSIVE FIRE PROTECTION Passive Fire Protection - in all cases, Building Service Engineers and Contractors must provide appropriate passive fire protection for all works. Contingency sums to be provide to ensure that all new works are covered and additionally any failures of passive fire protection identified during the works is made good and reinstated as necessary (See UCL Fire Safety Technical Note 066) FIRE BRIGADE COMMUNICATIONS Generally, UCL fire alarm panels are to alert the fire brigade via in all cases where practicable using UCL Gallagher system and relayed to the UCL Security Control Room when a: Fire Signal is generated by the fire panel; Date Last Amended: Dec 15 (Rev 4) 11.

12 Pre-Alarm and Fault is generated by the fire panel; UCL Fire Technical Note -TN Monitoring Centre - signals are to terminate at the UCL Security Control Room on the Main Campus, which acts as a 24-hour monitoring service for the UCL estate The UCL Access Systems Manager can be contacted on and should be consulted on all signals requiring to be monitored by the Security Control Room, including security / lift alarms, as well as fire alarm signals General Commissioning Requirements Design, Installation Commissioning and UCL Acceptance Certificates The provision of the appropriate design, installation and commissioning certificates containing information based on the Model Certificates provided in BS : Annex H, to be provided by the appropriate parties. Copies of the certificates are to be issued as following: (c). (d). All original certificate(s) to be placed in the Operational & Maintenance (O&M) Manuals; a copy of each certificate to be issued to the UCL Estates Head of Engineering or his representative; a copy of each certificate to be issued the UCL fire safety manager for building s fire certificate and fire strategy documents; any additional copies required by an authorised person; Design Certificate - is to be provided in all cases by the Design Consultant on completion of the design stage of the fire alarm Installation Certificate - is to be provided in all cases by the Contractor installing the fire alarm system, on completion of the installation stage Commissioning Certificate - is to be provided in all cases by Commissioning Engineers (generally UCL Fire Alarm Maintenance provider) on completion of the testing & commissioning stage of the fire alarm Acceptance Certificate (UCL) - this is to be completed and issued the by Project / Design Consultant; and witnessed by a Nominated UCL Person on behalf of the Director of UCL Estates Only on completion of the Acceptance Certificate witnessed by a UCL Nominated Person may: a new system, become the primary Warning in Case of Fire for the building; Date Last Amended: Dec 15 (Rev 4) 12.

13 UCL Fire Technical Note -TN055 where the fire alarm system has been replaced / upgraded etc may the old system be switched off and decommissioned. The new system may then become the primary Warning in Case of Fire for the building Where an addressable fire alarm system is provided, the programming of the device address must be carefully considered to ensure that its location matches the local, generic or room numbers to prevent confusion by staff, contractors or the Fire Brigade in locating the device Drawing and Zone Chart information is to be supplied as part of the commissioning of the fire alarm system as follows: Clear fire alarm zone information in A4 Word format, is to be provided in a suitable clip frame position adjacent to the fire alarm panel. This is to provide quick reference to incident location. As Installed Drawings are to be provided on hard copy A1 sheets and in electronic AutoCAD Version format scale of 1:50, 1:100 or 1:200 as appropriate Fire Zone Representation - adjacent to the indicating equipment, the following shall be supplied to the UCL Fire Safety Manager as part of the commissioning of the fire alarm system as follows: (c). Clear fire alarm zone information in A4 Word format, is to be provided in a suitable clip frame position adjacent to the fire alarm panel. This is to provide quick reference to incident location. As Installed Drawings are to be provided on hard copy A1 sheets and in electronic AutoCAD Version format scale of 1:50, 1:100 or 1:200 as appropriate. a diagrammatic representation with a correctly orientated plan of the premises should be displayed showing at least the building entrances, the main circulation areas and the division into zones Installation testing of Bedroom Cause & Affect - is to be undertaken by all commissioning and witnessing engineers. Guidance on test required and outcomes provided at TN055A. TN055A is a general guide only, to achieving the cause & affect desired but engineers should ensure that panel and device manufacture s testing, commissioning tests and instructions, British Standards and/or other relevant instructions guidance or requirements are also complied with. Date Last Amended: Dec 15 (Rev 4) 13.

14 20.0. Sleeping Risk Equipment Overview General equipment overview required by UCL for new and existing fire alarm systems on upgrading refurbishment etc (where practical): Items / Devices Details Protocols & Remarks Fire Panels Manual Call Points Smoke Detectors Heat Detectors Multi-Sensing Detectors C-TEC - XFP Range Apollo or KAC Type to Suite Apollo Range - Type to Suite Apollo Range - Type to Suite Apollo Discovery Range Open Protocol / Apollo / Addressable Open Protocol / Apollo / Addressable Open Protocol / Apollo / Addressable Open Protocol / Apollo / Addressable Open Protocol / Apollo / Addressable Bells 8 / 10 To suite Open Protocol / Addressable Sounders Apollo / Fulleon Range - Type to Suite Open Protocol / Addressable Voice Sounders Vimpex Firecryer Open Protocol / Addressable End Beam Detectors Building Interface Cables Visual Indicators Deaf & Hearing Impaired Warning Systems Open Area Smoke Imaging Detection (OSID) by xtralis Philip Payne 2784 Range FP 200 Gold (or equivalent) MIC (where required by BS5839-1) Do not blanket cover for DDA - separate arrangements at UCL Deaf Message Service (DMS) or similar texting system Special purchase arrangments Open Protocol / Addressable ( Fire Alarm Activated Do not Enter illuminated signs Red unless aesthetic consideration required Red LED indicators fitted to sounder units Alarmscom Ltd Discuss with UCL Fire Safety Manager Date Last Amended: Dec 15 (Rev 4) 14.

FIRE ALARMS SYSTEMS - UCL GENERAL INSTALLATION DESIGN GUIDANCE & EMPLOYERS REQUIREMENTS

FIRE ALARMS SYSTEMS - UCL GENERAL INSTALLATION DESIGN GUIDANCE & EMPLOYERS REQUIREMENTS Fire Safety Technical Guide FIRE ALARMS SYSTEMS - UCL GENERAL INSTALLATION DESIGN GUIDANCE & EMPLOYERS REQUIREMENTS (All Buildings Except Sleeping Accommodation) Contents: 1.0 Introduction... 1 2.0. UCL

More information

Fire. The Fire Installers Mate. A guide to fire alarm systems design

Fire. The Fire Installers Mate. A guide to fire alarm systems design Fire The Fire Installers Mate A guide to fire alarm systems design BS 5839 Part 1:2002 A guide to BS 5839 Part 1:2002 Disclaimer This booklet is not intended to be a comprehensive guide to all aspects

More information

AVAILABLE TO DOWNLOAD ON THE APOLLO APP. Fire Alarm Systems Design. a guide to BS5839

AVAILABLE TO DOWNLOAD ON THE APOLLO APP. Fire Alarm Systems Design. a guide to BS5839 AVAILABLE TO DOWNLOAD ON THE APOLLO APP a guide to Fire Alarm Systems Design BS5839 Part1:2013 The Regulatory Reform (Fire Safety) Order (FSO) became law on 1 October 2006 Legally you must comply! What

More information

FIRE DETECTION AND ALARM SYSTEMS

FIRE DETECTION AND ALARM SYSTEMS HMO Information Sheet No 1 FIRE DETECTION AND ALARM SYSTEMS 1. Introduction When a property is in multiple occupation, the risk of fire breaking out is greater than in an ordinary single family home. Some

More information

Fire Alarm Systems Technical Note 1 - Installation and Design Guidance (Ref: QM_OHSD_FS008)

Fire Alarm Systems Technical Note 1 - Installation and Design Guidance (Ref: QM_OHSD_FS008) Occupational Health and Safety Directorate Fire Alarm Systems Technical Note 1 - Installation and Design Guidance (Ref: QM_OHSD_FS008) QM_OHSD_FS008_Fire Alarm Systems-Technical Note 1- Installation and

More information

Fire Alarm system Installation Guide

Fire Alarm system Installation Guide Fire Alarm system Installation Guide Fire Alarm System Categories Systems designed for Protection of Property only, fall into two classifications P1 or P2. but a manual system is also needed, then this

More information

AVAILABLE TO DOWNLOAD ON THE APOLLO APP. Pocket guide to. Fire Alarm Systems Design BS 5839-1. Standard

AVAILABLE TO DOWNLOAD ON THE APOLLO APP. Pocket guide to. Fire Alarm Systems Design BS 5839-1. Standard Pocket guide to Fire Alarm Systems Design BS 5839-1 Standard AVAILABLE TO DOWNLOAD ON THE APOLLO APP The Regulatory Reform (Fire Safety) Order (FSO) became law on 1 October 2006 Legally you must comply!

More information

BS5839 Part 1:2002 Overview

BS5839 Part 1:2002 Overview BS5839 Part 1:2002 Overview 1 Contents Introduction So why is the current standard being revised? The brief for the new standard Changes to structure of current Standard Enhanced certification of Fire

More information

Fire precautions in dwellings. Private sector housing Providing homes building communities

Fire precautions in dwellings. Private sector housing Providing homes building communities Fire precautions in dwellings Private sector housing Providing homes building communities Version 3 Published by Norwich City Council August 2011 Contents Page Introduction 1 2 Types of dwellings (A) Shared

More information

AlarmSense 2-wire detection and alarm system. Product Guide

AlarmSense 2-wire detection and alarm system. Product Guide AlarmSense 2-wire detection and alarm system Product Guide Contents What is AlarmSense? 2 The purpose of AlarmSense 4 How AlarmSense works 4 Alarmsense Features 5 Detector removal monitoring 5 Priority/non-priority

More information

Application Guide HMOs

Application Guide HMOs Application Guide HMOs 2 Aims of this guide 3 What is AlarmSense? 3 What is an HMO 3 Fire Protection for an HMO 3 Approved Document B 4 Mandatory Licensing 4 BS 5839 4 Categories of System 6 Application

More information

I.S. 3218 :2013 Fire Detection & Alarm Systems

I.S. 3218 :2013 Fire Detection & Alarm Systems I.S. 3218 :2013 Fire Detection & Alarm Systems Overview of significant changes 26 th March 2014 FPS Ltd Today s Programme Commencement Transition Competence & Qualifications System Certification System

More information

I.S. 3218 :2013 Fire Detection & Alarm Systems

I.S. 3218 :2013 Fire Detection & Alarm Systems I.S. 3218 :2013 Fire Detection & Alarm Systems Overview of significant changes 26 th March 2014 FPS Ltd Today s Programme Commencement Transition Competence & Qualifications System Certification System

More information

FIRE ALARMS AND DETECTION SYSTEMS EQUIPMENT

FIRE ALARMS AND DETECTION SYSTEMS EQUIPMENT IMPERIAL COLLEGE FIRE ALARMS DETECTION SYSTEMS EQUIPMENT REVISION 1 FIRE ALARMS AND DETECTION SYSTEMS EQUIPMENT Revision Log REV. COMMENTS REVISED BY DATE CHECKED APPROVED 1 First Issue NDY 18.03.05 Notes

More information

Fire detection equipment

Fire detection equipment PRODUCT CATALOG Fire detection equipment www.apollo-fire.com Apollo Fire Detectors is one of the world s largest manufacturers of fire detectors, modules and notification devices. Established in 1980,

More information

Standard the the Raising

Standard the the Raising Raising the Standard Introduction to BS 5839-1:2013 An Overview of the BS 5839 1:2013 for professionals who are responsible for the provision of fire detection and alarm systems for buildings Agenda Introduction

More information

GENERAL FIRE SAFETY TERMS & DEFINITIONS

GENERAL FIRE SAFETY TERMS & DEFINITIONS UCL Fire Technical Note - TN006 Fire Safety Technical Guide GENERAL FIRE SAFETY TERMS & DEFINITIONS Reference: BS4422-2005 Fire Safety Vocabulary - for further information and definitions BS EN ISO 13943-2000:

More information

USER MANUAL, MAINTENANCE GUIDE & LOG BOOK

USER MANUAL, MAINTENANCE GUIDE & LOG BOOK Software Versions: PANEL 1.52 & LOOP CARD 2.0 ONE TO FOUR LOOPS ANALOGUE ADDRESSABLE FIRE ALARM PANEL USER MANUAL, MAINTENANCE GUIDE & LOG BOOK #Doc No. GLT.MAN-135 TABLE OF CONTENTS WHAT TO DO IF THE

More information

section one guide to design, installation,commissioning and maintenance of fire systems in non domestic premises Consultant s Guide

section one guide to design, installation,commissioning and maintenance of fire systems in non domestic premises Consultant s Guide section one Consultant s Guide section one section one contents About this manual Purpose Readership Electronic Format Acknowledgments 1 3 4 4 Section One: Guide to Design of Fire Systems 1. 1.1 1.1.1

More information

UCL FIRE RISK ASSESSMENT POLICY& ARRANGEMENTS

UCL FIRE RISK ASSESSMENT POLICY& ARRANGEMENTS Fire Safety Technical Guide UCL FIRE RISK ASSESSMENT POLICY& ARRANGEMENTS 1.0. BACKGROUND 1.1. The Regulatory Reform (Fire Safety) Order (known Fire Safety Order) applies to England and Wales (Northern

More information

Analogue addressable devices

Analogue addressable devices Discovery Analogue addressable devices from Channel Safety Systems Discovery Analogue addressable devices Discovery is a range of high-specification, intelligent fire detectors that are developed to meet

More information

Call reduction guidance for false alarm/ unwanted fire signals

Call reduction guidance for false alarm/ unwanted fire signals Call reduction guidance for false alarm/ unwanted fire signals Acting to Protect & Save Introduction Devon & Somerset Fire & Rescue Service attend in excess of 20,000 incidents each year, approximately

More information

UPP Residential Services Fire Risk Assessment

UPP Residential Services Fire Risk Assessment UPP Residential Services Fire Risk Assessment TS11151-R02-DRAFT1 15 August 2011 for: Keynes College University Road Canterbury Kent Recommended latest review date 14 August 2011 Executive summary This

More information

Building Control. Householder Guidance Leaflet No. 29. Fire detection in dwellings

Building Control. Householder Guidance Leaflet No. 29. Fire detection in dwellings Building Control Householder Guidance Leaflet No. 29 Fire detection in dwellings This leaflet is one of a series produced by the Hertfordshire Building Control Technical Forum GUIDANCE NOTE FOR HOME OWNERS

More information

Consultants Guide Issue 1 : 2012

Consultants Guide Issue 1 : 2012 Consultants Guide Issue 1 : 2012 FireClass Hillcrest Business Park Cinderbank Dudley West Midlands DY2 9AP United Kingdom Tel. +44(0)1384 453985 www.fireclass.co.uk fireclasssales@tycoint.com part one

More information

Consultant s Guide for Designing Fire Detection & Alarm Systems

Consultant s Guide for Designing Fire Detection & Alarm Systems Consultant s Guide for Designing Fire Detection & Alarm Systems part one contents About this manual Purpose Readership Electronic Format Acknowledgments 1 3 4 4 Part One: Guide to Design of Fire Systems

More information

Proposed changes to the Acceptable Solution for Building Code clause F7 (Warning Systems) Proposed amended Acceptable Solution for Warning Systems

Proposed changes to the Acceptable Solution for Building Code clause F7 (Warning Systems) Proposed amended Acceptable Solution for Warning Systems Proposed changes to the Acceptable Solution for Building Code clause F7 (Warning Systems) Appendix A Proposed amended Acceptable Solution for Warning Systems s in the grey boxes form part of the proposed

More information

MINERVA MX MX Virtual Multi-Sensor Detectors

MINERVA MX MX Virtual Multi-Sensor Detectors DATASHEET MINERVA MX MX Virtual Multi-Sensor Detectors Over 20 fire detection modes Tyco MX FASTLOGIC Expert algorithms MX HPO detection Algorithms Up to 250 detectors per loop Optional bi-directional

More information

www.ealarm.com.my P/N 5-051-371-00 Rev D

www.ealarm.com.my P/N 5-051-371-00 Rev D System 236 System 236i P/N 5-051-371-00 Rev D Thank you for purchasing this C&K alarm system Your system is one of the most powerful and advanced alarm systems on the market today, designed to provide

More information

(68.52) X. June 2000 Supercedes February 2000. xenex CONVENTIONAL FIRE DETECTION & ALARM SYSTEM. we look @ business differently

(68.52) X. June 2000 Supercedes February 2000. xenex CONVENTIONAL FIRE DETECTION & ALARM SYSTEM. we look @ business differently (68.52) X June 2000 Supercedes February 2000 xenex CONVENTIONAL FIRE DETECTION & ALARM SYSTEM.... we look @ business differently XENEX SYSTEM ARCHITECTURE Note: This schematic is for guidance only please

More information

NC State University Design and Construction Guidelines Division 26 Fire Alarm Systems

NC State University Design and Construction Guidelines Division 26 Fire Alarm Systems NC State University Design and Construction Guidelines Division 26 Fire Alarm Systems 1.0 Purpose A. The following guideline provides the minimum standards and requirements for fire alarm systems. 2.0

More information

BUILDING CONTROL GUIDANCE SHEET SMOKE ALARMS IN STANDARD DWELLINGS Last updated 16/12/2010

BUILDING CONTROL GUIDANCE SHEET SMOKE ALARMS IN STANDARD DWELLINGS Last updated 16/12/2010 Building Control Charnwood Borough Council Southfield Road Loughborough LE11 2TN BUILDING CONTROL GUIDANCE SHEET SMOKE ALARMS IN STANDARD DWELLINGS Last updated 16/12/2010 Page 1 of 7 PURPOSE: This Guidance

More information

Conventional Fire Detection and Extinguishant Control System Specification

Conventional Fire Detection and Extinguishant Control System Specification Conventional Fire Detection and Extinguishant Control System Specification Page 1 of 9 Scope Furnish a complete 24VDC Conventional, electrically supervised, combined fire detection and extinguishant release

More information

FIRE ALARM SYSTEM TECHNICAL SPECIFICATIONS Page 1 of 10

FIRE ALARM SYSTEM TECHNICAL SPECIFICATIONS Page 1 of 10 TECHNICAL SPECIFICATIONS Page 1 of 10 FIRE DETECTION AND ALARM SYSTEM Scope Furnish a complete 24V DC conventional, electrically supervised, zone annunciated, fire detection and alarm system as specified

More information

TS510 & TS500. Installation & User Guide. Compatible Equipment

TS510 & TS500. Installation & User Guide. Compatible Equipment Installation & User Guide Compatible Equipment TS510 REM - Remote Keypad 9040 - Loudspeaker DC54/58 - Digital Communicator SD1+ - Speech Dialler 496525 Issue A 1 of 10 TS510 and TS500 Overview Introduction

More information

welcome to our world fire alarm systems - series 600 www.staticsystems.co.uk

welcome to our world fire alarm systems - series 600 www.staticsystems.co.uk Static Systems Group PLC Heath Mill Road, Wombourne Staffordshire WV5 8AN. United Kingdom. Tel: +44 (0) 1902 895551 Fax: +44 (0) 1902 324969 www.staticsystems.co.uk welcome to our world In line with our

More information

Fire Standards & Regulations Are you confused?

Fire Standards & Regulations Are you confused? Fire Standards & Regulations Are you confused? Regulatory Reform (Fire Safety) Order Local Licensing Requirements BS 5839-6: 2013 Building Regulations Document B LACORS Fire Safety Guidance Fire Alarm

More information

Using your LED Plus keypad

Using your LED Plus keypad Using your LED Plus keypad System 238 System 2316 System 238i System 2316i Part Number 5-051-372-00 Rev B Thank you for purchasing this C&K alarm system Your system is one of the most powerful and advanced

More information

Bold items are particular to the City of Euless

Bold items are particular to the City of Euless EULESS FIRE DEPARTMENT FIRE MARSHAL S OFFICE INFORMATION LINE: Revised 2/12 Fire Chief Wes Rhodes Fire Marshal Paul Smith EFD-FMO 3-2 2009 International Fire & Building Code as Amended NFPA Standards Adopted

More information

conventional system operation

conventional system operation conventional system operation detection line operation Conventional detection systems normally operate on a 24VDC line. In the standby condition, the detectors will draw a low current, typically less than

More information

CFP 2/4/8 ZONE CONVENTIONAL FIRE ALARM CONTROL PANEL. user manual & log book. Approved Document No. DFU7001020 Rev 1

CFP 2/4/8 ZONE CONVENTIONAL FIRE ALARM CONTROL PANEL. user manual & log book. Approved Document No. DFU7001020 Rev 1 CFP 2/4/8 ZONE CONVENTIONAL FIRE ALARM CONTROL PANEL user manual & log book Approved Document No. DFU7001020 Rev 1 CONTENTS Safety...3 Important information regarding the safe use of this fire alarm panel

More information

EDA-Z5008 & Z5020. Radio Fire Alarm System. User Manual

EDA-Z5008 & Z5020. Radio Fire Alarm System. User Manual EDA-Z5008 & Z5020 Radio Fire Alarm System User Manual Electro-Detectors Ltd. Electro House, Edinburgh Way Harlow, Essex, CM20 2EG UK Tel: 01279 635668. Fax 01279 450185 Email: eda@electrodetectors.co.uk

More information

9452/9453 Installation and User Guide

9452/9453 Installation and User Guide 9452/9453 Installation and User Guide Compatible Equipment 9425 Remote Keypad 9040 Internal Sounder 660 Speech Communicator 8440 4-Channel Minicom 496330 Issue 1 1 of 10 9452/3 Introduction The 9452 and

More information

Fire Detection Systems

Fire Detection Systems Fire Detection Systems contents conventional fire alarm systems 4 intelligent fire alarm systems 9 detector application guide 15 conventional fire alarm systems principle of operation A conventional fire

More information

Fire Safety Requirements for Child Care Centre

Fire Safety Requirements for Child Care Centre Fire Safety Requirements for Child Care Centre A. Restrictions on Location Child care centre shall not be located : - (a) (b) in any premises designed for residential use; in any industrial building, warehouses,

More information

London Borough of Barnet. Fire Safety in Houses in Multiple Occupation. A Guide to Landlords

London Borough of Barnet. Fire Safety in Houses in Multiple Occupation. A Guide to Landlords London Borough of Barnet Fire Safety in Houses in Multiple Occupation A Guide to Landlords March 2016 Contents Introduction p.3 Summary of main requirements p.3 Fire Safety Precautions p.4 Protecting the

More information

CHANGES IN NFPA 72 NATIONAL FIRE ALARM CODE 1999 2002

CHANGES IN NFPA 72 NATIONAL FIRE ALARM CODE 1999 2002 CHANGES IN NFPA 72 NATIONAL FIRE ALARM CODE 1999 2002 Three new chapters were added. What was chapter 1 in 1999 was reorganized into chapters 1 (Fundamentals), 2 (Referenced Publications), and 3 (Definitions).

More information

ISLE OF MAN FIRE & RESCUE SERVICE FIRE PRECAUTIONS LOGBOOK. Website www.iomfire.com

ISLE OF MAN FIRE & RESCUE SERVICE FIRE PRECAUTIONS LOGBOOK. Website www.iomfire.com ISLE OF MAN FIRE & RESCUE SERVICE FIRE PRECAUTIONS LOGBOOK Website www.iomfire.com ADDRESS OF PREMISES FIRE CERTIFICATE No. (where applicable).. LOCATION OF LOG BOOK. CONTENTS OF LOG BOOK Useful telephone

More information

DELAWARE STATE FIRE MARSHAL FIRE ALARM SYSTEM CERTIFICATE OF INSTALLATION

DELAWARE STATE FIRE MARSHAL FIRE ALARM SYSTEM CERTIFICATE OF INSTALLATION Phone System Owner Phone System Engineered by: of Record Drawings: of System Manuals: of Test Reports: System Installer 1. GENERAL INFORMATION Phone Delaware License No: Certificate Holder No. System Supplier

More information

DOMESTIC SMOKE ALARMS

DOMESTIC SMOKE ALARMS SOUTH AUSTRALIAN METROPOLITAN FIRE SERVICE HOME FIRE SAFETY INFORMATION For further advice contact the Community Safety Department South Australian Metropolitan Fire Service on 8204 3611 DOMESTIC SMOKE

More information

Guidance for Responsible Persons on False Alarm Management of Fire Detection and Alarm Systems

Guidance for Responsible Persons on False Alarm Management of Fire Detection and Alarm Systems Thames House, 29 Thames Street Kingston upon Thames, Surrey, KT1 1PH Phone: +44 (0) 8549 5855 Website: www.fia.uk.com Guidance for Responsible Persons on False Alarm Management of Fire Detection and Alarm

More information

Users Guide to Keypad Functions

Users Guide to Keypad Functions Users Guide to Keypad Functions MANUAL NO. 700-175-01J ISSUED JAN 2002 VERSION 1.41 Summary of Operation A rm/ disarm [#] + [USER CODE] Quick Quick Quick Panic Fire Medical Away Arm Stay Arm Stay Arm &

More information

XFP NETWORKABLE ANALOGUE ADDRESSABLE FIRE ALARM CONTROL PANEL. user manual and log book. Approved Document No. DFU2000510 Rev 1

XFP NETWORKABLE ANALOGUE ADDRESSABLE FIRE ALARM CONTROL PANEL. user manual and log book. Approved Document No. DFU2000510 Rev 1 XFP NETWORKABLE ANALOGUE ADDRESSABLE FIRE ALARM CONTROL PANEL user manual and log book Approved Document No. DFU2000510 Rev 1 CONTENTS Important safety notes...3 Introduction...4 Fire alarm systems - an

More information

FIRE ALARM SYSTEM TECHNICAL SPECIFICATIONS Page 1 of 19

FIRE ALARM SYSTEM TECHNICAL SPECIFICATIONS Page 1 of 19 TECHNICAL SPECIFICATIONS Page 1 of 19 FIRE DETECTION AND ALARM SYSTEM Scope Furnish a complete 24V DC analogue addressable, electrically supervised, zone annunciated, fire detection and alarm system as

More information

For use by landlords of small premises Premises Address

For use by landlords of small premises Premises Address fire risk assessment For use by landlords of small premises Premises Address FIRE RISK ASSESSMENT for use by landlords of small premises Person having control of the premises: Name of landlord (if different):

More information

720r Addendum: Siting the 720r

720r Addendum: Siting the 720r 720r Addendum: Siting the 720r UK 1 Cooper Security Limited 2013 Every effort has been made to ensure that the contents of this leaflet are correct. However, neither the authors nor Cooper Security Limited

More information

IDS. Users Guide to Keypad Functions S E C U R I T Y MANUAL NO. 700-171-01B ISSUED AUG 2002 VERSION 1.18

IDS. Users Guide to Keypad Functions S E C U R I T Y MANUAL NO. 700-171-01B ISSUED AUG 2002 VERSION 1.18 INHEP DIGITAL IDS S E C U R I T Y Users Guide to Keypad Functions MANUAL NO. 700-171-01B ISSUED AUG 2002 VERSION 1.18 Summary of Operation A rm/ disarm [#] + [USER CODE] Quick Quick Quick Away Arm Stay

More information

25 Years of Manufacturing Excellence INFINITY. The Intelligent 2 Wire Fire Detection System for Professionals

25 Years of Manufacturing Excellence INFINITY. The Intelligent 2 Wire Fire Detection System for Professionals INFINITY The Intelligent 2 Wire Fire Detection System for Professionals Infinity ID 2 The intelligent 2 wire fire detection system for professionals In a nutshell Zeta Alarm Systems is proud to introduce

More information

Sound Engineering for 60 Years EmerCall Disabled Refuge and Fire Telephone System

Sound Engineering for 60 Years EmerCall Disabled Refuge and Fire Telephone System EmerCall Disabled Refuge and Fire Telephone System Slide 1 Audix EmerCall Fully Compliant to BS5839 Part 9 Slide 2 Audix EmerCall One System for Fire phones and Disabled persons See BS5839 Part 9 Forward,

More information

500r+ Installation and User Guide

500r+ Installation and User Guide 500r+ Installation and User Guide Compatible Equipment 502rUK-50 Watch/Pendant PA. 509rUK-50 Smoke Detector 515rUK-00 10 metre passive infra red movement detector. 525rUK-00 Remote Set/Unset (Full and

More information

NetworX Series. NX- 4/8 Code Pad. User Manual (Australian Version)

NetworX Series. NX- 4/8 Code Pad. User Manual (Australian Version) NetworX Series NX- 4/8 Code Pad User Manual (Australian Version) Table Of Contents Code Pad Diagram... Inside Front Glossary of Terms...2 Understanding the Code Pad lights...3 Code Pad Tones...4 Fully

More information

SECURIT 800L+ CONTROL PANEL

SECURIT 800L+ CONTROL PANEL USER MANUAL SECURIT 800L+ CONTROL PANEL COMPANY PROFILE IntelliSense have been successfully making security products for over 20 years and lead the security industry throughout the world with many innovative

More information

SECTION 13850 DETECTION AND ALARM

SECTION 13850 DETECTION AND ALARM SECTION 13850 DETECTION AND ALARM PART 1 GENERAL 1.01 SUMMARY A. Section Includes 1. Control Panel 2 Associated Equipment B. Products Installed But Not Supplied Under This Section 1. Section 16140 - Wiring

More information

FIRE ALARMS. IN DWELLINGS By John Ware FIRE ALARMS

FIRE ALARMS. IN DWELLINGS By John Ware FIRE ALARMS 1 FIRE ALARMS IN DWELLINGS By John Ware IN THE UK around 80% of all fire deaths and injuries occur in dwellings, a total of 450 to 500 deaths and 14,000 injuries per annum, according to BS 5839-6: 2004.

More information

Your responsibilities if you have an automatic fire alarm. A handy guide for owners and responsible persons

Your responsibilities if you have an automatic fire alarm. A handy guide for owners and responsible persons Your responsibilities if you have an automatic fire alarm A handy guide for owners and responsible persons Kent Fire and Rescue Service Contents Your responsibilities if you have an automatic fire alarm

More information

City of Bettendorf Fire Alarm System Requirements

City of Bettendorf Fire Alarm System Requirements City of Bettendorf Fire Alarm System Requirements Section 907 of the 2009 Edition of the International Fire Code (IFC) and Section 10-7-3 of the Municipal Code provide fire alarm requirements. IFC Section

More information

BARDIC. 4 & 8 Zone Fire Panels Zircon range. Data, installation, operation and maintenance. by Honeywell

BARDIC. 4 & 8 Zone Fire Panels Zircon range. Data, installation, operation and maintenance. by Honeywell Data, installation, operation and maintenance 4 & 8 Zone Fire Panels Zircon range BARDIC by Honeywell LED flashing LED Continuous FAULT DISABLE/TEST Power General Fault Sounder Fault/ Disable System Fault

More information

CONTENTS. GST102A/104A/108A/116A Conventional Fire Alarm Control Panel Installation and Operation Manual

CONTENTS. GST102A/104A/108A/116A Conventional Fire Alarm Control Panel Installation and Operation Manual CONTENTS Installation Precautions... 1 EN 54 Information... 2 Chapter 1 Product Overview... 3 1.1 Features... 3 1.2 Technical Specifications... 3 1.2.1 Operating Voltage... 3 1.2.2 Batteries... 4 1.2.3

More information

PLAN REVIEW GUIDE FOR FIRE ALARM

PLAN REVIEW GUIDE FOR FIRE ALARM PLAN REVIEW GUIDE FOR FIRE ALARM PROJECT NAME: PERMIT # PROJECT ADDRESS: CONTACT PERSON: PHONE Fire alarm system installation information shall be provided on the appropriate architectural and electrical

More information

FURNITURE & FURNISHINGS - FIRE SAFETY STANDARDS

FURNITURE & FURNISHINGS - FIRE SAFETY STANDARDS Fire Safety Technical Guide FURNITURE & FURNISHINGS - FIRE SAFETY STANDARDS 1.0. Introduction 1.1. Furniture and furnishings may significantly increase fire spread in rooms and those circulation spaces,

More information

1.0 APPOINTMENTS 2.0 FIRE RISK ASSESSMENTS

1.0 APPOINTMENTS 2.0 FIRE RISK ASSESSMENTS Fire Risk assessment 1.0 APPOINTMENTS 1.1 Responsible Person. In compliance with the Regulatory Reform (Fire Safety) Order 2005 (FSO) the School s Head, Mrs J M Miles is appointed as the Responsible Person

More information

FIRE SAFETY SIGNAGE - UCL FIRE SAFETY STANDARD

FIRE SAFETY SIGNAGE - UCL FIRE SAFETY STANDARD Fire Safety Technical Guide FIRE SAFETY SIGNAGE - UCL FIRE SAFETY STANDARD Fire Safety Signage - what you need to know: Prohibited or Check First! Local purchase of fire safety signs - departmental staff,

More information

Risk Management Guidelines

Risk Management Guidelines Automatic Fire Alarm (AFA) Automatic Fire Detection (AFD) Introduction AFD can be described as being the means or equipment used to raise an alarm, whilst AFA is actually the action of the alarm itself.

More information

Manual for Fire Suppression & Methane Detection System

Manual for Fire Suppression & Methane Detection System Manual for Fire Suppression & Methane Detection System Fogmaker North America Post address: 150 Gordon Dr Exton, PA 19341 Delivery address: 150 Gordon Dr Exton, PA 19341 Tel: 610-265-3610 Fax: 610-265-8327

More information

HARDWIRED CONTROL PANELS

HARDWIRED CONTROL PANELS USER GUIDE 9651 HARDWIRED CONTROL PANELS Contents 1. Introduction...3 The Alarm System...3 The Keypad...3 About This Guide...5 2. Everyday Operation...6 How Do I Know if the System is Working?...6 Setting

More information

EMERGENCY LIGHTING - UCL GENERAL DESIGN GUIDANCE

EMERGENCY LIGHTING - UCL GENERAL DESIGN GUIDANCE Fire Safety Technical Guide EMERGENCY LIGHTING - UCL GENERAL DESIGN GUIDANCE Reference: A. British Standard 5266-1 Emergency Lighting - Code of Practice for the emergency lighting of premises; B. BS 5266-7

More information

CLARK COUNTY FIRE DEPARTMENT Fire Hazard & Prevention Services

CLARK COUNTY FIRE DEPARTMENT Fire Hazard & Prevention Services CLARK COUNTY FIRE DEPARTMENT Fire Hazard & Prevention Services 575 E. Flamingo Road, Las Vegas, NV 89119 (702) 455-7316 FAX (702) 455-7347 105.8a-6.1 TITLE: FIRE ALARM SYSTEM REQUIREMENTS SCOPE: This guideline

More information

Fire Safety Policy. Fire Safety Policy: May 2011 Page 1 of 6. Version 1. Scope:

Fire Safety Policy. Fire Safety Policy: May 2011 Page 1 of 6. Version 1. Scope: Version 1 Fire Safety Policy Scope: Effective Date: Review Date: Signed Off by: Author: Policy Owned by: This policy applies to Hackney Homes Ltd working on behalf of the London Borough of Hackney July

More information

FIRST ALERT INSTRUCTION MANUAL FOR FA 270 KEYPADS SECURITY SYSTEM

FIRST ALERT INSTRUCTION MANUAL FOR FA 270 KEYPADS SECURITY SYSTEM FIRST ALERT INSTRUCTION MANUAL FOR FA 270 KEYPADS SECURITY SYSTEM Page 0 Table of Contents Introduction 1 System Basics.. 1 Burglary Protection.. 1 Fire Protection.. 1 Security Codes. 1 Zones and Partitions

More information

FLORIDA ATLANTIC UNIVERSITY FIRE ALARM SYSTEM INSTALLATION MANUAL

FLORIDA ATLANTIC UNIVERSITY FIRE ALARM SYSTEM INSTALLATION MANUAL FLORIDA ATLANTIC UNIVERSITY FIRE ALARM SYSTEM INSTALLATION MANUAL January, 2003 Environmental Health and Safety Florida Atlantic University 777 Glades Rd. Boca Raton, FL 33431 Phone: 561-297-3129 Fax:

More information

Reducing the Risk of Fire Through Telecare Commissioning Standards. London Fire Brigade

Reducing the Risk of Fire Through Telecare Commissioning Standards. London Fire Brigade Reducing the Risk of Fire Through Telecare Commissioning Standards London Fire Brigade Sheltered Accommodation Irene - Surrey Coroner s Court 9 th May 2014 HM Coroner Richard Travers highlighted the delay

More information

ACTIVE 5 ENGINEERING MANUAL

ACTIVE 5 ENGINEERING MANUAL ACTIVE 5 ENGINEERING MANUAL C & K Systems Ltd C031-066 Issue 3 THE ACTIVE 5 INSTALLATION MANUAL. Date: Feb 1997 INTRODUCTION. The Active 5 is a microprocessor controlled intruder alarm panel. It features

More information

HAM841K ALARM CONTROL PANEL FOR COMMERCIAL AND RESIDENTIAL SECURITY SYSTEMS

HAM841K ALARM CONTROL PANEL FOR COMMERCIAL AND RESIDENTIAL SECURITY SYSTEMS ALARM CONTROL PANEL FOR COMMERCIAL AND RESIDENTIAL SECURITY SYSTEMS USER MANUAL USER MANUAL ALARM CONTROL PANEL FOR COMMERCIAL AND RESIDENTIAL SECURITY SYSTEMS INTRODUCTION The (HA-841K) is a complete

More information

TAMARAC FIRE RESCUE INSTRUCTIONS FOR FIRE ALARM PRE-SUBMITTAL CHECKLIST

TAMARAC FIRE RESCUE INSTRUCTIONS FOR FIRE ALARM PRE-SUBMITTAL CHECKLIST TAMARAC FIRE RESCUE INSTRUCTIONS FOR FIRE ALARM PRE-SUBMITTAL CHECKLIST In order to provide a comprehensive plan review in a timely manner, and to insure the design and installation of fire alarm systems

More information

BURGLAR ALARM SYSTEMS BURGLAR ALARM SYSTEMS BURGLAR ALARM SYSTEM EURO ALARM WIRELESS BURGLAR ALARM SYSTEM OASIS

BURGLAR ALARM SYSTEMS BURGLAR ALARM SYSTEMS BURGLAR ALARM SYSTEM EURO ALARM WIRELESS BURGLAR ALARM SYSTEM OASIS BURGLAR ALARM SYSTEMS BURGLAR ALARM SYSTEMS BURGLAR ALARM SYSTEM EURO ALARM WIRELESS BURGLAR ALARM SYSTEM OASIS BURGLAR ALARM SYSTEM EURO ALARM Six zones with the following connection capabilities: One

More information

Quantec Wiring Instructions

Quantec Wiring Instructions Approved Document No. DNUQ777 Rev Quantec Wiring Instructions GENERAL Quantec can be compared to a very sophisticated analogue addressable fire alarm system where the integrity of the wiring is of paramount

More information

VR8. User Guide Intruder Alarm System

VR8. User Guide Intruder Alarm System VR8 EN User Guide Intruder Alarm System VR8 User Guide Notices EN 2 Copyright Notice Unless otherwise indicated, this publication is the copyright of Bosch Security Systems Pty Ltd ( Bosch ). All rights

More information

SECTION 16721 FIRE ALARM AND DETECTION SYSTEM

SECTION 16721 FIRE ALARM AND DETECTION SYSTEM 1. GENERAL 1.1. Related Documents: 1.2. Scope: 1.1.1. The general provisions of the Contract, including General and Supplementary Conditions and General Requirements apply to the work specified in this

More information

Commercial Fire Alarm Systems How can a Fire Alarm system help protect your business from the threat of fire?

Commercial Fire Alarm Systems How can a Fire Alarm system help protect your business from the threat of fire? Commercial Fire Alarm Systems How can a Fire Alarm system help protect your business from the threat of fire? How do Fire and Smoke Alarms actually work, from the different types of controls to positioning

More information

PRODUCT WARRANTY. Page 20

PRODUCT WARRANTY. Page 20 PRODUCT WARRANTY Manufactured equipment is warranted to be free from defects in material and workmanship for a period of twelve (12) months from date of manufacture as indicated by the date stamp and/or

More information

UCL ESTATES SECURITY DEPARTMENT. CCTV, Intruder Alarm & Alarm Monitoring. Specification Guidance Document

UCL ESTATES SECURITY DEPARTMENT. CCTV, Intruder Alarm & Alarm Monitoring. Specification Guidance Document UCL ESTATES SECURITY DEPARTMENT CCTV, Intruder Alarm & Alarm Monitoring Specification Guidance Document CCTV UCL has an extensive Pelco Endura CCTV system comprising of in excess of 500 cameras, a number

More information

CBD-233. Fire Alarm and Detection Systems

CBD-233. Fire Alarm and Detection Systems Page 1 of 5 CBD-233. Fire Alarm and Detection Systems Originally published August 1984. R.H.L. McEwen Fire alarm systems are normally required by building codes. In the case of new buildings, this is usually

More information

FIRE ALARM SYSTEM. A. Shop drawings shall be submitted as follows: 1. Manufacturer's published literature. for aspproval.

FIRE ALARM SYSTEM. A. Shop drawings shall be submitted as follows: 1. Manufacturer's published literature. for aspproval. Polk School District Specifications for the New Fire Alarm in the Existing Building Eastside Elementary School FIRE ALARM SYSTEM 1.01 SUBMITTALS A. Shop drawings shall be submitted as follows: 1. Manufacturer's

More information

Guidance on loft conversions in two-storey houses

Guidance on loft conversions in two-storey houses Guidance on loft conversions in two-storey houses Technical guidance for building control surveyors, designers and installers 01 Guidance on loft conversions in two-storey houses Technical guidance for

More information

Guide to Fire Alarm Systems

Guide to Fire Alarm Systems Guide to Fire Alarm Systems Guide to Fire Alarm Systems INDEX Introduction Page 2 When is a Fire Alarm System Required Page 2 The Fire Precautions Act 1971 & Fire Precautions (Workplace) Regulations 1997Page

More information

Fire Alarm Systems Care and Maintenance

Fire Alarm Systems Care and Maintenance April 2011 Country of Origin: United Kingdom Fire Alarm Systems Care and Maintenance Introduction A fire alarm installation is designed to provide early warning of a fire condition. To ensure that the

More information

Northern Ireland Housing Executive: HMO Fire Safety Guide

Northern Ireland Housing Executive: HMO Fire Safety Guide Northern Ireland Housing Executive: HMO Fire Safety Guide Contents Equality Statement 5 Houses in Multiple Occupation (HMOs) means of escape in case of fire and other fire precautions 6 1.0 Introduction

More information

Overview of Fire Alarm Systems and Maintenance

Overview of Fire Alarm Systems and Maintenance Overview of Fire Alarm Systems and Maintenance By Mr. David Goh Vice President Fire Safety Managers Association Convener of Working Group for CP 10 : 2005 Er. Matthew Kwek Committee Member Fire Safety

More information

FIRE DETECTION AND ALARM

FIRE DETECTION AND ALARM Scope Provide a fire alarm system, or expand the existing system, as required by Code, the requirements in the Special Instructions to Designers (SID) of the Design Guidelines, and/or as noted in the Program

More information

USER INSTRUCTIONS CONTENTS

USER INSTRUCTIONS CONTENTS CONTENTS Full Set [1]...2 Part Set [2]...2 Night Set [3]...3 Unsetting...3 Unsetting after or during an alarm...3 Testing the system [5]...3 Isolating zones [6]...4 Reprogramming codes [8]...4 Chime facility

More information