DELAWARE STATE FIRE MARSHAL FIRE ALARM SYSTEM CERTIFICATE OF INSTALLATION
|
|
- Todd Reynolds
- 1 years ago
- Views:
Transcription
1 Phone System Owner Phone System Engineered by: of Record Drawings: of System Manuals: of Test Reports: System Installer 1. GENERAL INFORMATION Phone Delaware License No: Certificate Holder No. System Supplier Phone Delaware License No: Certificate Holder No. 2. CERTIFICATION OF SYSTEM INSTALLATION: Fill out after installation is complete and wiring has been checked for opens, shorts, ground faults and improper branching, but prior to conducting operational acceptance tests). The installer certifies that the installation was inspected by on Installer: and that it is in strict accordance with the approved plans and specifications, and that the system installation fully complies with the installation requirements of: Signed: Page 1 of 5
2 3. CERTIFICATION OF SYSTEM OPERATION: The installer certifies that all operational features and functions of the system were tested and inspected by on and that all were found to be operating property in strict accordance with the approved plans and specifications, and acknowledges that all components of the system are in service and that the system installation fully complies with the operational requirements. Installer: Signed: Operational testing of the system witnessed and accepted by the Authority Having Jurisdiction. Signed: 4. TYPE OF SYSTEM OR SERVICE Central Station Service. (, location and telephone number of the Central Station) Local alarm system. If alarm is transmitted to location(s) off premise list where received: Auxiliary alarm system. Indicate type of connection: Local energy, Shunt, Parallel, and telephone number of receipt of signals: Remote Station Service., and telephone number of receipt of signals: Proprietary alarm system. If alarms are retransmitted to Public Fire Service Communications Center or Central Station, indicate name, location and telephone number of the organization receiving the alarm: Indicate how the alarm is retransmitted: Emergency Voice/Alarm Service. of voice/alarm channels: Single, Multiple (specify): Speaker zones wired Dual Path, Single Path. If single path, is installation wiring enclosed in a 2-hour rated enclosure? Yes (specify) No Page 2 of 5
3 5. ALARM INITIATING DEVICES AND CIRCUITS and style (see NFPA 72, Table 3-5.1) of initiating circuits connected to the system: Types and quantities of alarm initiating devices installed: Manual Stations, Noncoded, Coded, Heat Detectors, Fixed, Rate of Rise, Smoke Detectors, Ion, Photo, Duct Detectors, Ion, Photo, Sprinkler Water Flow Switches, Fire Fighters Phones, Jacks, 6. ALARM NOTIFICATION APPLIANCES AND CIRCUITS and style (see NFPA 72, Table 3-7.1) of notification appliance circuits connected to the system: Types and quantities of alarm notification appliances installed: Bell, Type/Size Horn, Type Chimes, Type/Size Speakers, Type/Size Remote Annunciators, Type Fire Fighters Phones, Jacks, Indicate whether visual signals are combined with audible or, mounted separately. Measured alarm sound pressure level is dba, measured equivalent (average) ambient sound pressure level is dba. Area in which measurement was taken: Time of Day Measurement Device Utilized: 7. SUPERVISORY SIGNAL INITIATING DEVICES AND CIRCUITS: and style (see NFPA 72, Table 3-5.1) of supervisory circuits: Sprinkler Control Valve, Type Building Temperature, Type Site Water Temperature, Type/Size Site Water Supply Level, Type Electric Fire Pump: Fire Pump Power, Fire Pump Running, Engine Driven Fire Pump: Selector in Auto. Position, Engine or Control Panel Trouble, Fire Pump Running, Page 3 of 5
4 Engine Driven Generator: Selector in Auto. Position, Control Panel Trouble, Transfer Switch, Engine Running, Other Supervisory Function(s) (specify) 8. SIGNALING LINE CIRCUITS: and style (see NFPA 72, Table 3-6.1) of signaling line circuits connected to system: 9. SYSTEM POWER SUPPLIES: A. Primary (Main) Power: Nominal Voltage Amps Over Current Protection: Type Amps Is primary power provided by a dedicated branch circuit from the protected property s light and power service? Yes No (explain) Is the circuit disconnecting means labeled FIRE ALARM CIRCUIT CONTROL, and is it locked out? Yes No (explain) B. Secondary (Standby) Power: Storage Battery: Amp-Hour rating Calculated standby capacity to operate system in standby for 24 hours, 60 hours, Other Engine driven generator dedicated to fire alarm system: of fuel storage C. Emergency or Standby System used as a backup to Primary Power Supply, instead of using a Secondary Power Supply: Emergency system described in NFPA 70, Article 700. Legally Required Standby System described in NFPA 70, Article 701. Optional Standby System described in NFPA 70, Article 702, which also meets the performance requirements of Article 700 or KNOWN SYSTEM DEVIATIONS FROM THE REFERENCED CODES, REGULATIONS AND STANDARDS None As Follows (describe fully) 11. SYSTEM ACCEPTANCE: (use additional sheets if necessary) A. The Certificate Holder verifies that on all operational features and functions of the system control Equipment were operationally testing and inspected by and that the control equipment was found to be operating property in strict accordance with the approved plans and Specifications and that the system control equipment fully complies with the operational requirements of: Certificate Holder: Signed: Page 4 of 5
5 B. The System Owner accepts the system as installed and acknowledges that the System fully performs to the System Owner s complete satisfaction. Further, the System Owner acknowledges receiving an Office of State Fire Marshal memorandum titled System Owners Responsibility for Testing, Inspection and Maintenance of Fire Alarm Signaling Systems. System Owner: Signed: C. The Authority Having Jurisdiction (AHJ) accepts the system as installed and acknowledges that the System fully performs to the AHJ s complete satisfaction. AHJ: Signed: AHJ not present for final testing/inspection. F:\Tech Services Dover\Quality Assurance\QAP process\qap2001\ forms\fass Installation Certificate Page 5 of 5
FIRE ALARM SYSTEM RECORD OF COMPLETION
FUNDAMENTALS OF FIRE ALARM SYSTEMS 72 33 FIRE ALARM SYSTEM RECORD OF COMPLETION To be completed by the system installation contractor at the time of system acceptance and approval. 1. PROTECTED PROPERTY
FIRE ALARM SYSTEM RECORD OF COMPLETION
FIRE ALARM SYSTEM RECORD OF COMPLETION To be completed by the system installation contractor at the time of system acceptance and approval. 1. Protected Property Information Name of property: Description
INSTRUCTIONS FOR BUILDINGS WITH FIRE PROTECTION EQUIPMENT
INSTRUCTIONS FOR BUILDINGS WITH FIRE PROTECTION EQUIPMENT FIRE EXTINGUISHERS,SPRINKLER SYSTEMS AND FIRE ALARMS Attachment #1 Inspection of Fire Extinguishers Fire Extinguishers must be tested according
INSTRUCTIONS FOR BUILDINGS WITH FIRE PROTECTION EQUIPMENT
INSTRUCTIONS FOR BUILDINGS WITH FIRE PROTECTION EQUIPMENT FIRE EXTINGUISHERS,SPRINKLER SYSTEMS AND FIRE ALARMS Attachment #1 Inspection of Fire Extinguishers Fire Extinguishers must be tested according
FIRE ALARM AND EMERGENCY COMMUNICATION SYSTEM RECORD OF COMPLETION
FIRE ALARM AND EMERGENCY COMMUNICATION SYSTEM RECORD OF COMPLETION To be completed by the system installation contractor at the time of system acceptance and approval. It shall be permitted to modify this
Fire Alarm System Description Worksheet
UL LLC 333 Pfingsten Road, Northbrook, IL 60062-2096 Phone: (877) UL HELPS, Fax: (847) 407-1001 SN: Fire Alarm System Description Worksheet PROTECTED PROPERTY Name: Address: City: State: Zip Code: Representative
CITY OF PHILADELPHIA DEPARTMENT OF LICENSES AND INSPECTIONS ANNUAL CERTIFICATION FOR FIRE ALARM SYSTEMS
CITY OF PHILADELPHIA DEPARTMENT OF LICENSES AND INSPECTIONS ANNUAL CERTIFICATION FOR FIRE ALARM SYSTEMS PROPERTY ADDRESS (BRT Address Required) TESTING CONTRACTOR (Name and Address) License No. ANNUAL
Module 4, Lesson 12 Fire Alarm Systems
Student Manual Module 4, Lesson 12 Fire Alarm Systems Performance Objectives At the conclusion of this lesson, you will be able to: Identify the components and functions of a fire alarm system and determine
TAMARAC FIRE RESCUE INSTRUCTIONS FOR FIRE ALARM PRE-SUBMITTAL CHECKLIST
TAMARAC FIRE RESCUE INSTRUCTIONS FOR FIRE ALARM PRE-SUBMITTAL CHECKLIST In order to provide a comprehensive plan review in a timely manner, and to insure the design and installation of fire alarm systems
EXHIBIT A SCOPE OF WORK
EXHIBIT A SCOPE OF WORK 1. (Contractor) shall provide fire alarm system maintenance/repair/testing services as described herein to the California Department of Veterans Affairs (hereinafter CDVA, CalVet,
NATIONAL FIRE ALARM AND SIGNALING CODE
GAP.11.1.1.0 A Publication of Global Asset Protection Services LLC NATIONAL FIRE ALARM AND SIGNALING CODE INTRODUCTION National Fire Protection Association (NFPA) documents describe a level of fire protection
INSPECTION AND TESTING FORM
INSPECTION AND TESTING FORM SERVICE ORGANIZATION PROPERTY NAME (USER) DATE: 08-04-15 TIME: 8:00 Name: Siemens Industries Inc. Name: Kcvtcs Madisonville Tech, School Bldg. Address: 2700 Stanley Gault Pkwy
FIRE ALARM AND EMERGENCY COMMUNICATION SYSTEM INSPECTION AND TESTING FORM
FIRE ALARM AND EMERGENCY COMMUNICATION SYSTEM INSPECTION AND TESTING FORM To be completed by the system inspector or tester at the time of the inspection or test. It shall be permitted to modify this form
Michael Catalano 24 Nassau Avenue, Islip NY 11751 Phone (631) 224-5477 Chief Fire Marshal fireprevention@islipny.gov Fax (631) 224-5458
OFFICE OF THE FIRE MARSHAL BUREAU OF FIRE PREVENTION Michael Catalano, Phone Chief Fire Marshal fireprevention@islipny.gov Fax To whom it may concern: Enclosed please find the NFPA 72 forms needed for
AETNA FIRE ALARM SERVICE CO., INC.
FIRE ALARM AND EMERGENCY COMMUNICATION SYSTEM INSPECTION AND TESTING FORM To be completed by the system inspector or tester at the inspection or test. It shall be permitted to modify this form as needed
FIRE ALARM SYSTEMS PERMIT APPLICATION, PLAN SUBMITTAL, DESIGN, INSTALLATION AND INSPECTION REQUIREMENTS Effective Date: January, 2011
Office of the Fire Marshal 1.0 PERMITS FIRE ALARM SYSTEMS PERMIT APPLICATION, PLAN SUBMITTAL, DESIGN, INSTALLATION AND INSPECTION REQUIREMENTS Effective Date: January, 2011 1.1 To acquire an installation
FLORIDA ATLANTIC UNIVERSITY FIRE ALARM SYSTEM INSTALLATION MANUAL
FLORIDA ATLANTIC UNIVERSITY FIRE ALARM SYSTEM INSTALLATION MANUAL January, 2003 Environmental Health and Safety Florida Atlantic University 777 Glades Rd. Boca Raton, FL 33431 Phone: 561-297-3129 Fax:
SECTION 16721 FIRE ALARM AND SMOKE DETECTION SYSTEMS
SECTION 16721 PART 1 - GENERAL 1.1 SECTION INCLUDES A. Fire Alarm Control Panels B. Manual Fire Alarm Stations C. Automatic Smoke D. Fire Alarm Notification Appliances E. Auxiliary Fire Alarm Equipment
HERNANDO COUNTY FIRE ALARM GUIDELINES
HERNANDO COUNTY FIRE ALARM GUIDELINES To be used for all commercial building fire alarm system plan review. The procedures set forth in this document are the minimum requirements necessary to ensure a
SECTION 16720 - FIRE AND SMOKE ALARM SYSTEM. City of San Diego, CWP Guidelines
PART 1 -- GENERAL 1.1 WORK OF THIS SECTION SECTION 16720 - City of San Diego, CWP Guidelines A. The WORK of this Section includes providing manual and automatic fire alarm and smoke detection systems meeting
FIRE ALARM SYSTEM SUBMITTAL CHECKLIST AND APPLICATION
PERMITS AND INSPECTIONS FIRE ALARM SYSTEM SUBMITTAL CHECKLIST AND APPLICATION 911 Assigned PROJECT LOCATION Subdivision: Lot: Blk: Sec: PROJECT New Construction Addition/Remodel Demolition Other: Number
CHANGES IN NFPA 72 NATIONAL FIRE ALARM CODE 1999 2002
CHANGES IN NFPA 72 NATIONAL FIRE ALARM CODE 1999 2002 Three new chapters were added. What was chapter 1 in 1999 was reorganized into chapters 1 (Fundamentals), 2 (Referenced Publications), and 3 (Definitions).
FIRE ALARM APPLICATION
FIRE ALARM APPLICATION ENUMCLAW FIRE DEPARTMENT 1330 Wells St, Enumclaw, WA 98022 Phone: 360-825-5544 Fax: 360-825-9442 COMMUNITY DEVELOPMENT, BUILDING DEPARTMENT 1309 Myrtle Ave Enumclaw WA 98022 Phone:
PLAN REVIEW GUIDE FOR FIRE ALARM
PLAN REVIEW GUIDE FOR FIRE ALARM PROJECT NAME: PERMIT # PROJECT ADDRESS: CONTACT PERSON: PHONE Fire alarm system installation information shall be provided on the appropriate architectural and electrical
Finance and Administration Department 907 Billy Mitchell Blvd. P: (210) 228-1022 Fire Alarm Permit Application
PERMIT FEE: $ Finance and Administration Department 907 Billy Mitchell Blvd. P: (210) 228-1022 Fire Alarm Permit Application PAYMENT TYPE: Check Credit Card Charge to Job #: (Please complete all of the
Agenda. Agenda (continued) Fundamentals of Fire Alarm Systems
Fundamentals of Fire Alarm Systems Sponsored by UL SFPE Austin/San Antonio Chapter San Marcos, Texas 7 January 2015 Agenda Introduction and Administration Historical Context of Today s NFPA 72 Fire Alarm
Attachment 9. Trouble signals. Interfaced equipment. Primary (main) power supply
FIRE DETECTION, ALARM AND MASS NOTIFICATION SYSTEMS Inspection, testing, and maintenance of fire detection, alarm and Mass Notification systems shall be performed in accordance with the manufacturer's
FireSeeker Fire Alarm Control Panel Model FS-250 Programming Manual
FireSeeker Fire Alarm Control Panel Model FS-250 Programming Manual P/N 315-049403-1 Siemens Building Technologies Fire Safety Table Of Contents Introduction...1 The Access levels...1 User Level...1 Maintenance
Fire Alarm System Plans Submittal Guidelines For New and Existing Systems
Fire Alarm System Plans Submittal Guidelines For New and Existing Systems SCOPE The Temecula Fire Prevention Bureau (TFPB) has established the following requirements for the submittal of all fire alarms,
NC State University Design and Construction Guidelines Division 26 Fire Alarm Systems
NC State University Design and Construction Guidelines Division 26 Fire Alarm Systems 1.0 Purpose A. The following guideline provides the minimum standards and requirements for fire alarm systems. 2.0
Bold items are particular to the City of Euless
EULESS FIRE DEPARTMENT FIRE MARSHAL S OFFICE INFORMATION LINE: Revised 2/12 Fire Chief Wes Rhodes Fire Marshal Paul Smith EFD-FMO 3-2 2009 International Fire & Building Code as Amended NFPA Standards Adopted
FIRE ALARM AND DETECTION SYSTEMS SECTION 16721
PART 1 - GENERAL 1.01 WORK INCLUDED FIRE ALARM AND DETECTION SYSTEMS SECTION 16721 A. Provide a complete fully addressable, power limited, fire detection and evacuation system. The system shall be connected
NFPA 72 Inspection and Testing Requirements for Fire Alarm Systems
NFPA 72 Inspection and Testing Requirements for Fire Alarm Systems Presented by Brent Gooden, CET Specializing in Fire, Building, and Life Safety Disclaimer: The comments and opinions made during the presentation
Original Document 10/16/07 Revised 01/30/09 2 nd Revision 01-23-12 3 rd Revision- 12/18/14
North Collier Fire Control & Rescue District Greater Naples Fire Rescue District Immokalee Fire Control & Rescue District 2800 North Horseshoe Drive Naples, Florida 34104 SYSTEM REHABILITATION PLAN CHECKLIST
The Evolution of Requirements for Supervising Station Alarm Systems
The Evolution of Requirements for Supervising Station Alarm Systems Fire Marshal s Association of Colorado January 18, 2013 Warren Olsen, CFPS CBCO FSCI wolsen@firesafetyfsci.com 1 Disclaimer: The comments
Rancho Cucamonga Fire Protection District Prevention Bureau Standard
Rancho Cucamonga Fire Protection District Prevention Bureau Standard Title: Fire Alarm and Monitoring Systems Standard # 9-3 Effective: May 2002 Number of Pages: 7 Revised: January 2014 INTENT The intent
New and Existing Fire Alarm & Signaling Systems
ORANGE COUNTY FIRE AUTHORITY Planning & Development Services Section 1 Fire Authority Road, Building A, Irvine, CA 92602 714-573-6100 www.ocfa.org New and Existing Fire Alarm & Signaling Systems Guideline
Fire Alarm and Detection Systems And Central Station Monitoring Plan Submittal Guidelines
Fire Alarm and Detection Systems And Central Station Monitoring Plan Submittal Guidelines Red Oak Fire Rescue Office of the Fire Marshal 547 N. Methodist Red Oak, TX 75154 Phone: 469-218-7713 Fax: 468-218-7719
FIRE ALARM SYSTEM Plan Submittal and Inspection Requirements
FIRE ALARM SYSTEM Plan Submittal and Inspection Requirements All fire alarm systems installed within the jurisdiction of the San Mateo Fire Department shall meet all the applicable sections of the following
TECHNICAL DATA. Scan with smart phone to access Custom Zone Description Text. Viking Technical Data may be found on 24 Hour Clock
Page 1 of 8 1. DESCRIPTION The Viking VFR400 is a microprocessor based multi-hazard releasing control panel for use on preaction, deluge, Surefire and Firecycle multicycle sprinkler systems, MX-1230 Fire
Fire Alarm System Monitoring - CAN/ULC-S561-03
Fire Alarm System Monitoring - CAN/ULC-S561-03 Brian McBain ULC Regulatory Services May 4, 2011 Copyright 1995-2007 Underwriters' Laboratories of Canada. All rights reserved. No portion of this material
SECTION 16853 ZONED (DC LOOP) FIREALARM SYSTEM
SECTION 16853 ZONED (DC LOOP) FIRE-ALARM SYSTEM PART 1 - GENERAL 1.1 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General and Supplementary Conditions and Division 1
Telluride Fire Protection District Fire Alarm Systems Policy Version 03/2007
Telluride Fire Protection District Fire Alarm Systems Policy Version 03/2007 FIRE ALARM SYSTEMS POLICY TELLURIDE FIRE PROTECTION DISTRICT TABLE OF CONTENTS FIRE ALARM PROTECTION POLICY PLAN REVIEW SUBMITTAL
Module 5. Fire and Emergency Alarm System Part I- Basics
Module 5 Fire and Emergency Alarm System Part I- Basics 1 This module will describe: 1. Components and the arrangements of components in fire and emergency alarm systems. 2. How these systems work. 3.
SECTION 16721 FIRE ALARM AND DETECTION SYSTEMS
SECTION 16721 FIRE ALARM AND DETECTION SYSTEMS The equipment requirements of this section apply to the IUB Campus. The IUPUI Campus has a preferred vendor agreement for fire alarm systems. Contact Pat
FIRE SPRINKLER SYSTEM SUPERVISORY SERVICE User s Guide (DamarNet RAR Service)
FIRE SPRINKLER SYSTEM SUPERVISORY SERVICE User s Guide (DamarNet RAR Service) The information provided in this user guide pertains to fire suppression sprinkler system monitoring service provided over
UL Code th Edition. An Overview of the Foremost Code Updates
UL Code 864 9 th Edition An Overview of the Foremost Code Updates 9 th Edition of UL 864, ANSI/UL 864 Latest incarnation of a standard first published in 1948 Note that UL 864 is an ANSI standard. ANSI
CLARK COUNTY FIRE DEPARTMENT Fire Hazard & Prevention Services
CLARK COUNTY FIRE DEPARTMENT Fire Hazard & Prevention Services 575 E. Flamingo Road, Las Vegas, NV 89119 (702) 455-7316 FAX (702) 455-7347 105.8a-6.1 TITLE: FIRE ALARM SYSTEM REQUIREMENTS SCOPE: This guideline
SECTION 16721 FIRE ALARM AND DETECTION SYSTEM
1. GENERAL 1.1. Related Documents: 1.2. Scope: 1.1.1. The general provisions of the Contract, including General and Supplementary Conditions and General Requirements apply to the work specified in this
Understanding Fire Alarm Requirements & Inspections. Presented By Bill Conroy Technical Sales For Briscoe Protective Systems Inc
Understanding Fire Alarm Requirements & Inspections Presented By Bill Conroy Technical Sales For Briscoe Protective Systems Inc Introduction Fire Alarm Requirements are structured through a system of codes.
FVSU-33201301 REPAIR & UPGRADE FIBER OPTIC 280000-1 SECTION 280000 FIRE ALARM SYSTEM CONNECTIVITY
FVSU-33201301 REPAIR & UPGRADE FIBER OPTIC 280000-1 SECTION 280000 FIRE ALARM SYSTEM CONNECTIVITY PART 1 - GENERAL 1.1 SUMMARY A. Section Includes: 1. Fire-alarm control unit. 2. Addressable interface
City of Bettendorf Fire Alarm System Requirements
City of Bettendorf Fire Alarm System Requirements Section 907 of the 2009 Edition of the International Fire Code (IFC) and Section 10-7-3 of the Municipal Code provide fire alarm requirements. IFC Section
BASIC FIRE ALARM TRAINING
BASIC FIRE ALARM TRAINING What is a fire alarm system? Per the defini+on in NFPA 72 A system or por+on of a combina+on system that consists of components and circuits arranged to monitor and annunciate
CHAPTER. Fire Alarm Systems APPROVAL AND ACCEPTANCE. Shop Drawings
Fire Alarm Systems CHAPTER 2 The information contained in this chapter is intended to assist the registered design professional (RDP), commissioning agent, authority having jurisdiction (AHJ), and the
Fire Prevention Coffee Break Training. November 2015
Fire Prevention Coffee Break Training November 2015 Agenda Changes in the Pire Prevention Bureau FM Lund Tags FM Lund System priorities for the FD FM Lund Transmission Technologies- Phelan Questions and
C. Conform to requirements of Americans with Disabilities Act (ADA).
SECTION 28 31 00 - FIRE ALARM AND DETECTION SYSTEMS PART 1 - GENERAL 1.1 SECTION INCLUDES A. Fire alarm and detection systems 1.2 REFERENCES A. NFPA 70 - National Electrical Code B. NFPA 72 - National
TESTING, INSPECTION, AND MAINTENANCE FREQUENCIES FOR FIRE DETECTION AND ALARM SYSTEMS
TESTING, INSPECTION, AND MAINTENANCE FREQUENCIES FOR FIRE DETECTION AND ALARM SYSTEMS The following information regarding testing frequencies for fire detection and alarm systems. All of the following
SECTION 16721 FIRE ALARM AND DETECTION SYSTEM
SECTION 16721 FIRE ALARM AND DETECTION SYSTEM PART 1 - GENERAL 1.1 RELATED DOCUMENTS: A. Drawings and general provisions of Contract, including General and Supplementary Conditions and Division-1 Specification
ICC CODE CORNER 2012 IFC Code & Commentary
907.5.2.3.3 Groups I-1 and R-1. Group I-1 and R-1 dwelling units or sleeping units in accordance with Table 907.5.2.3.3 shall be provided with a visible alarm notification appliance, activated by both
Fire Alarm System Plans Review Checklist Property location Date of Review
Fire Alarm System Plans Review Checklist Property location Date of Review 1. Is application completed in entirety? 2. Are the plans review fee submitted with the application? 3. Does floor plan include
FIRE DETECTION AND ALARM
Scope Provide a fire alarm system, or expand the existing system, as required by Code, the requirements in the Special Instructions to Designers (SID) of the Design Guidelines, and/or as noted in the Program
INSPECTION AND TESTING OF FIRE ALARM SYSTEMS
Page 1 January 2, 2009 INSPECTION AND TESTING OF FIRE ALARM SYSTEMS Introduction Early warning plays a key role in a healthcare facility s ability to safely evacuate its residents during a fire emergency.
CAN/ULC-S561-03 Installation and Services for Fire Signal Receiving Centres and Systems- Ottawa 2013
CAN/ULC-S561-03 Installation and Services for Fire Signal Receiving Centres and Systems- Ottawa 2013 Alan Cavers, Engineering Manager Underwriters Laboratories of Canada Dec. 2013 Copyright 1995-2007 Underwriters'
Protective Signaling Systems Wiring Practices Manual
Protective Signaling Systems Wiring Practices Manual Edwards Signaling Products 90 Fieldstone Court, Cheshire, CT 06410-1212 Edwards Protective Signaling System Wiring Practices INTRODUCTION The installation
DTW Works Master Specification Version 2006
Issued 2006/08/01 Section 13852 Multiplex Fire Alarm System Page 1 of 10 PART 1 GENERAL 1.1 RELATED WORK.1 Section 01330 Submittal Procedures..2 Section 01780 Closeout Procedures..3 Section 01810 Commissioning..4
University Design Standard. Fire Alarm Systems
University Design Standard Fire Alarm Systems 1.0 Overview This document provides Virginia Tech s standards for the design and installation of fire alarm systems and equipment in new construction, retrofit
SECTION 28 31 11 FIRE ALARM AND DETECTION SYSTEM
KNOXVILLE, TENNESSEE SECTION 28 31 11 PAGE 1 PART 1 - GENERAL 1.01 DESCRIPTION OF WORK SECTION 28 31 11 A. Extent of fire alarm and detection system work shall be as described in this specification, as
FIRE ALARM SYSTEM. A. Shop drawings shall be submitted as follows: 1. Manufacturer's published literature. for aspproval.
Polk School District Specifications for the New Fire Alarm in the Existing Building Eastside Elementary School FIRE ALARM SYSTEM 1.01 SUBMITTALS A. Shop drawings shall be submitted as follows: 1. Manufacturer's
Fire Alarm FAQs. Q: How many zone/circuit fire alarm panel do I need? Q: What candela strobes do I need?
5/2/2014 Fire Alarm FAQs Question Answer Q: How many zone/circuit fire alarm panel do I need? Q: What candela strobes do I need? A: The size of a fire alarm panel is determined by a number of factors,
OBOA 2009 Huntsville, ON Overview of ULC Standards Affecting Building Occupancy Alan Cavers Area Manager Fire & Security Systems Group
OBOA 2009 Huntsville, ON Overview of ULC Standards Affecting Building Occupancy Alan Cavers Area Manager Fire & Security Systems Group Course Title: Rev Date Agenda Introduction to Underwriters Laboratories
Fire Alarm Systems Certification
Fire Alarm Systems Certification The skills and knowledge listed under each task are suggestive of those involved in that task, but are not intended to constitute an exhaustive listing. 2.1 Submittal Preparation
SARATOGA FIRE DISTRICT EARLY WARNING FIRE ALARM SYSTEM STANDARDS AND REQUIRMENTS CONTENTS
SARATOGA FIRE DISTRICT EARLY WARNING FIRE ALARM SYSTEM STANDARDS AND REQUIRMENTS CONTENTS I. APPLICATION AND DEFINITIONS 1.01 Authorization for Standards 1.02 Application of Standards 1.03 Definitions
1.0 General. Inspection, Testing, and Maintenance 1 of 8
1.0 General 1.1 Scope This specifications covers the minimum requirements for the inspection, testing, and maintenance of the existing Notifier fire alarm systems at Bergen Community College (BCC) campus
QUARTERLY FIRE ALARM SYSTEM INSPECTION & TESTING (Health Care & Ambul)
Facility Q Quarterly Fire Alarm See the last page for instructions. Footnote indicates a specific instruction is available. NFPA 72 (1999) code ref shown in italic All items on this form must be completed.
rpsa FIRE PROTECTION ENGINEERS
R.P. SCHIFILITI ASSOCIATES, INC. P.O. Box 297 Reading, Massachusetts 01867-0497 USA 781.944.9300 Fax / Data 781.942.7500 Telephone Understanding Supervision of Fire Protection Systems by Robert P. Schifiliti,
Commercial Fire Alarm Standards July 1, 2010 Edition Page 1 of 14
City of Mercer Island Development Services Group Fire Code Review and Inspection 9611 SE 36 th Street Mercer Island, WA 98040-3732 PHONE (206) 275-7605 FAX (206) 275-7726 www.mercergov.org Commercial Fire
COMMISSIONING OF FIRE ALARM SYSTEMS
COMMISSIONING OF FIRE ALARM SYSTEMS OWNER FURNISHED The owner directly contracts an independent third party commissioning agent for this project. This Commissioning Plan has been included for reference
1. The objective of this guideline is to provide minimum standards for design and installation of fire alarm systems for the University of Missouri.
GENERAL: 1. The objective of this guideline is to provide minimum standards for design and installation of fire alarm systems for the University of Missouri. 2. Fire alarm systems are Life Safety Systems
SECTION 16721 FIRE DETECTION AND ALARM SYSTEM PART 1 - GENERAL 1.01 DESCRIPTION
SECTION 16721 FIRE DETECTION AND ALARM SYSTEM PART 1 - GENERAL 1.01 DESCRIPTION A. This section of the specifications includes the furnishing, installation, and connection of the microprocessor-controlled
INSPECTION, TESTING, AND MAINTENANCE OF FIRE ALARM AND OCCUPANT NOTIFICATION SYSTEMS
INSPECTION, TESTING, AND MAINTENANCE OF FIRE ALARM AND OCCUPANT NOTIFICATION SYSTEMS William E. Koffel, P.E., FSFPE President Koffel Associates, Inc. www.koffel.com wkoffel@koffel.com Expertly Engineering
BELMONT FIRE DEPARTMENT FIRE ALARM SYSTEM REQUIREMENTS BFD-OFM-10-011
Fire Alarm System plan(s) MUST be reviewed and approved by the Belmont Fire Department prior to the start of construction. The design and any changes must be fully compliant with NFPA 1, NFPA 101, NFPA
SPECIFICATIONS FOR THE INSTALLATION OF FIRE ALARM SYSTEMS, SPRINKLER SYSTEMS, AND MASTER BOXES IN THE POQUONNOCK BRIDGE FIRE DISTRICT
SPECIFICATIONS FOR THE INSTALLATION OF FIRE ALARM SYSTEMS, SPRINKLER SYSTEMS, AND MASTER BOXES IN THE POQUONNOCK BRIDGE FIRE DISTRICT The purpose of these specifications is to insure that there are minimum
BUREAU OF FIRE PREVENTION FIRE ALARM INSPECTION UNIT
BUREAU OF FIRE PREVENTION FIRE ALARM INSPECTION UNIT STANDARD OPERATING PROCEDURE SOP # 06-02-11 ACCEPTANCE / REACCEPTANCE TESTING OF FIRE ALARM, EMERGENCY AND AUTOMATIC EXTINGUISHING SYSTEMS A. PURPOSE
FIRE ALARM SYSTEM CHECKLIST For Addressable Systems PRIOR TO INSPECTION
Building Name/Location: Installing Company: Observation By: Date: Time: 1 Building Occupants, Authorities and Alarm Monitoring Co Have Been Notified 2 FACP Manufacturer and Panel is Approved for NCSU Campus
2007 ICC FINAL ACTION AGENDA
907.2.1.1 System initiation in Group A occupancies with an occupant load of 1,000 or more. Activation of the fire alarm in Group A occupancies with an occupant load of 1,000 or more shall initiate a signal
REGULATIONS for INSTALLATION, MAINTENANCE, and TESTING APPLICATION PACKET
REGULATIONS for INSTALLATION, MAINTENANCE, and TESTING FIRE ALARM SYSTEMS APPLICATION PACKET CITY OF NAPERVILLE 400 S EAGLE STREET NAPERVILLE, Il 60540 PHONE: 630.420.6070 FAX: 630.420.6657 Fire Alarm
rpsa FIRE PROTECTION ENGINEERS
R.P. SCHIFILITI ASSOCIATES, INC. P.O. Box 297 Reading, Massachusetts 01867-0497 USA 781.944.9300 Fax / Data 781.942.7500 Telephone Sample Fire Alarm System Calculations 1. A fire alarm manufacturer specifies
Fire Alarm Systems Permit Packet. City of Greer Fire Department
Fire Alarm Systems Permit Packet City of Greer Fire Department Updated July 2004 If you have any questions or comments regarding the information contained within; or of you need assistance interpreting
RIDER SCOPE OF WORK AND SPECIFICATIONS FIRE ALARM SYSTEM TESTING AND INSPECTION SERVICES
I. General RIDER 101 - SCOPE OF WORK AND SPECIFICATIONS FIRE ALARM SYSTEM TESTING AND INSPECTION SERVICES 1. This scope of work describes testing, inspection and maintenance services required for The University
RHODE ISLAND DIVISION OF STATE FIRE MARSHAL
RHODE ISLAND DIVISION OF STATE FIRE MARSHAL Smoke Alarm and Carbon Monoxide Brochure JOHN E. CHARTIER STATE FIRE MARSHAL 118 PARADE STREET PROVIDENCE, RI 02909 DAYS 401-462-4200 24 Hr. 401-222-2331 FAX#
Formal Interpretation NFPA 72. National Fire Alarm Code Edition
Reference: 3.3.43.19, 11.7.2 F.I. 89-1 Question: Is it the intent of the Committee that only devices which comply with the definition of a smoke detector in 3.3.43.19 meet the intent of 11.7.2? Answer:
NMSU FIRE DEPARTMENT Commercial Kitchen Fire Suppression Worksheet
This Commercial Kitchen Automatic Fire has been created to assure all documentation has been submitted to assist you in assuring proper plans and documentations has been submitted and reviewed by New Mexico
Life Safety Code Enabling References
SUPPLEMENT 4 Life Safety Code Enabling References Editor s Note: Supplement 4 provides users of NFPA 72, National Fire Alarm and Signaling Code, with a summary of requirements from NFPA 101, Life Safety
Approval Standard for Central Station Service for Fire Alarms and Protective Equipment Supervision
Approval Standard for Central Station Service for Fire Alarms and Protective Equipment Supervision Class Number 3011 April 1999 2002 FM Approvals LLC. All rights reserved. Foreword The FM Approvals certification
Invitation to Bid FIRE ALARM & DETECTION SYSTEM
Invitation to Bid FIRE ALARM & DETECTION SYSTEM Responses to an Invitation to Bid will be received by the Purchasing Supervisor, Sumner County Board of Education, 1500 Airport Road, Gallatin, TN 37066
IR F-1 EMERGENCY VOICE/ALARM COMMUNICATION SYSTEMS
IR F-1 Disciplines: Fire/Life Safety History: Revised 10-01-15 Issued 06-23-15 PURPOSE: This Interpretation of Regulations (IR) is being issued by the Division of the State Architect (DSA) to clarify when
Summary of NFPA Inspection, Test & Maintenance Requirements for Fire Alarm Systems
Daily: Power Supply public emergency alarm reporting systems-wired system-voltage test Weekly: No. 7d Control Equipment: fire alarm systems unmonitored Inspect NFPA 72 14.3.1 for alarm, supervisory and
Winnipeg Fire Department Fire Prevention Branch
Winnipeg Fire Department Fire Prevention Branch Manitoba Fire Code Life-Safety Equipment Maintenance Requirements The Fire Prevention Branch of the Winnipeg Fire Department has prepared this document of
FIRE-FIGHTING DESIGN BRIEF REPORT
P a g e 1 SECTION 04 (Doc.No.A/DBR 001) FIRE-FIGHTING DESIGN BRIEF REPORT P a g e 2 1.0 SCOPE 2.0 STANDARDS AND CODES 3.0 TYPES OF SYSTEM PROPOSED 4.0 FIRE HYDRANT SYSTEM 5.0 AUTOMATIC SPRINKLER SYSTEM
527 CMR: BOARD OF FIRE PREVENTION REGULATIONS
527 CMR 31.00: CARBON MONOXIDE ALARMS Section 31.01: Purpose and Scope 31.02: Definitions 31.03: General Installation Provisions 31.04: Specific Installation Provisions 31.05: Carbon Monoxide Protection: