DC INVERTER MULTI-SYSTEM AIR CONDITIONER

Size: px
Start display at page:

Download "DC INVERTER MULTI-SYSTEM AIR CONDITIONER"

Transcription

1 TECHNICAL & SERVICE MANUAL OUTDOOR UNIT : CM97 CM7 CM7 FILE NO. Destination: North America DC INVERTER MULTI-SYSTEM AIR CONDITIONER Capacity at 0V 9,700 BTU/h,00 BTU/h 0,600 BTU/h Outdoor Model No. CM97 CM7 CM7 Product Code No CM97 < Applicable Indoor Units > Wall mounted type KMS077 KMS097 KMS7 KMS87 KMS7 NOTE CM7 For details about the combination, refer to "Unit Combination Table" in the Appendix of this manual. CM7 IMPORTANT These air conditioners employ new refrigerant R0A. Pay special attention when servicing the unit. REFERENCE NO. SM

2 Important! Please Read Before Starting This air conditioning system meets strict safety and operating standards. As the installer or service person, it is an important part of your job to install or service the system so it operates safely and efficiently. For safe installation and trouble-free operation, you must: Carefully read this instruction booklet before beginning. Follow each installation or repair step exactly as shown. Observe all local, state, and national electrical codes. Pay close attention to all warning and caution notices given in this manual. WARNING CAUTION SPECIAL PRECAUTIONS WARNING When Wiring This symbol refers to a hazard or unsafe practice which can result in severe personal injury or death. This symbol refers to a hazard or unsafe practice which can result in personal injury or product or property damage. If Necessary, Get Help These instructions are all you need for most installation sites and maintenance conditions. If you require help for a special problem, contact our sales/service outlet or your certified dealer for additional instructions. In Case of Improper Installation The manufacturer shall in no way be responsible for improper installation or maintenance service, including failure to follow the instructions in this document. ELECTRICAL SHOCK CAN CAUSE SEVERE PERSONAL INJURY OR DEATH. ONLY A QUALIFIED, EXPERIENCED ELECTRICIAN SHOULD ATTEMPT TO WIRE THIS SYSTEM. Do not supply power to the unit until all wiring and tubing are completed or reconnected and checked. Highly dangerous electrical voltages are used in this system. Carefully refer to the wiring diagram and these instructions when wiring. Improper connections and inadequate grounding can cause accidental injury or death. Ground the unit following local electrical codes. Connect all wiring tightly. Loose wiring may cause overheating at connection points and a possible fire hazard. When Transporting Be careful when picking up and moving the indoor and outdoor units. Get a partner to help, and bend your knees when lifting to reduce strain on your back. Sharp edges or thin aluminum fins on the air conditioner can cut your fingers. When Installing In a Ceiling or Wall Make sure the ceiling/wall is strong enough to hold the unit s weight. It may be necessary to construct a strong wood or metal frame to provide added support. In a Room Properly insulate any tubing run inside a room to prevent "sweating" that can cause dripping and water damage to walls and floors. In Moist or Uneven Locations Use a raised concrete pad or concrete blocks to provide a solid, level foundation for the outdoor unit. This prevents water damage and abnormal vibration. In an Area with High Winds Securely anchor the outdoor unit down with bolts and a metal frame. Provide a suitable air baffle. In a Snowy Area (for Heat Pump-type Systems) Install the outdoor unit on a raised platform that is higher than drifting snow. Provide snow vents. When Connecting Refrigerant Tubing Use the flare method for connecting tubing. Apply refrigerant lubricant to the matching surfaces of the flare and union tubes before connecting them, then tighten the nut with a torque wrench for a leak-free connection. Check carefully for leaks before starting the test run. When Servicing Turn the power off at the main power box (mains) before opening the unit to check or repair electrical parts and wiring. Keep your fingers and clothing away from any moving parts. Clean up the site after you finish, remembering to check that no metal scraps or bits of wiring have been left inside the unit being serviced. Others CAUTION Ventilate any enclosed areas when installing or testing the refrigeration system. Escaped refrigerant gas, on contact with fire or heat, can produce dangerously toxic gas. Confirm upon completing installation that no refrigerant gas is leaking. If escaped gas comes in contact with a stove, gas water heater, electric room heater or other heat source, it can produce dangerously toxic gas.

3 Table of Contents APPLICABLE INDOOR UNITS.... OPERATING RANGE... Page. SPECIFICATIONS -. Unit Specifications Major Component Specifications... Other Component Specifications.... DIMENSIONAL DATA.... REFRIGERANT FLOW DIAGRAM -. Refrigerant Flow Diagram.... PERFORMANCE DATA -. Temperature Charts Cooling Capacity ELECTRICAL DATA 6-. Electric Wiring Diagrams FUNCTIONS 7-. Explanation of Functions Protective Functions TROUBLESHOOTING 8-. Precautions before Performing Inspection or Repair Trouble Diagnosis by Error Monitop Lamps Checking the Outdoor System Trouble Diagnosis of Each Part Trouble Diagnosis of Fan Motor REFRIGERANT R0A: SPECIAL PRECAUTIONS WHEN SERVICING UNIT 9-. Characteristics of New Refrigerant R0A Checklist before Servicing Tools Specifically for R0A Tubing Installation Procedures In Case of Compressor Malfunction In Case Refrigerant is Leaking Charging Additional Refrigerant Retro-Fitting Existing Systems APPENDIX A INSTALLATION INSTRUCTIONS... APPENDIX B UNIT COMBINATION TABLES A- A-

4 APPLICABLE INDOOR UNITS Multi-Outdoor Unit Indoor Unit KMS077 KMS097 KMS7 KMS87 KMS7 -Room CM97 YES YES YES YES NO -Room CM7 YES YES YES YES YES -Room CM7 YES YES YES YES YES NOTE The table lists the wall-mounted type of indoor units as representative models.

5 . OPERATING RANGE Cooling Temperature Indoor Air Intake Temp. Outdoor Air Intake Temp. Maximum 9 F D.B. / 7 F W.B. F D.B. Minimum 67 F D.B. / 7 F W.B. 67 F D.B.

6 . SPECIFICATIONS -. Unit Specifications Outdoor Unit CM97 Indoor Unit KMS097 Type Number of Connectable Indoor Units Number of Operatable Indoor Units Voltage Rating -Room Multi Outdoor Unit 0V Single-Phase 60Hz < 0V > Performance Total Capacity Sensible Capacity Latent Capacity Air Circulation (High) BTU/h kw BTU/h BTU/h ft /min (m /h) 9, Cooling ( 9,800 to 9,700 ) (.90 to.80 ) 6,800,900,707 (,900) Electrical Rating Available Voltage Range V 87 to Running Amperes Power Input A W 7.0,70 Power Factor % 98 SEER BTU/W Compressor Locked Rotor Amperes A.0 Fuse or Circuit Breaker Capacity A 0 Features (Outdoor Unit) Control Microprocessor Fan Speeds Auto (Hi, Me, Lo) Compressor Refrigerant / Amount charged at shipment Ib. (g) DC Twin Rotary (Inverter) R0A / 6.7 (,800) Refrigerant Control Electric Expansion Valve Operation Sound (High) Cool db-a 0 Refrigerant Tubing Connections Flare Type Max. allowable tubing length per unit ft. (m) 8 () Refrigerant Narrow tube inch (mm) / (6.) Tube Diameter Wide tube inch (mm) /8 (9.) Dimensions & Weight (Outdoor Unit) Unit Dimensions Package Dimensions Weight Height Width Depth Height Width Depth Shipping Volume Net Shipping inch (mm) inch (mm) Ib. (kg) Ib. (kg) cu.ft (m ) Cooling 9-/8-7/6-9/ ( ) -7/ 0-/8 6-/ (860,0 ) (6.0) (67.0) (0.6) DATA SUBJECT TO CHANGE WITHOUT NOTICE. Remarks:. The Values shown in performance section and electrical rating section above are based on the following unit combination. For other combination unit, please refer to the "Unit Combination Tables" in this manual. Indoor Unit : KMS097 units Outdoor Unit : CM97 unit. Rating conditions are: Cooling : Indoor air temp. 80 F D.B./ 67 F W.B. Outdoor air temp. 9 F D.B./ 7 F W.B. 6

7 Outdoor Unit CM97 Indoor Unit KMS097 Type Number of Connectable Indoor Units Number of Operatable Indoor Units Voltage Rating -Room Multi Outdoor Unit 08V Single-Phase 60Hz < 08V > Performance Total Capacity Sensible Capacity Latent Capacity Air Circulation (High) BTU/h kw BTU/h BTU/h ft /min (m /h) 9, Cooling ( 9,800 to 9,700 ) (.90 to.80 ) 6,800,900,707 (,900) Electrical Rating Available Voltage Range V 87 to Running Amperes Power Input A W 7.7,70 Power Factor % 98 SEER BTU/W Compressor Locked Rotor Amperes A.0 Fuse or Circuit Breaker Capacity A 0 Features (Outdoor Unit) Control Microprocessor Fan Speeds Auto (Hi, Me, Lo) Compressor Refrigerant / Amount charged at shipment Ib. (g) DC Twin Rotary (Inverter) R0A / 6.7 (,800) Refrigerant Control Electric Expansion Valve Operation Sound (High) Cool db-a 0 Refrigerant Tubing Connections Flare Type Max. allowable tubing length per unit ft. (m) 8 () Refrigerant Narrow tube inch (mm) / (6.) Tube Diameter Wide tube inch (mm) /8 (9.) Dimensions & Weight (Outdoor Unit) Unit Dimensions Package Dimensions Weight Height Width Depth Height Width Depth Shipping Volume Net Shipping inch (mm) inch (mm) Ib. (kg) Ib. (kg) cu.ft (m ) Cooling 9-/8-7/6-9/ ( ) -7/ 0-/8 6-/ (860,0 ) (6.0) (67.0) (0.6) DATA SUBJECT TO CHANGE WITHOUT NOTICE. Remarks:. The Values shown in performance section and electrical rating section above are based on the following unit combination. For other combination unit, please refer to the "Unit Combination Tables" in this manual. Indoor Unit : KMS097 units Outdoor Unit : CM97 unit. Rating conditions are: Cooling : Indoor air temp. 80 F D.B./ 67 F W.B. Outdoor air temp. 9 F D.B./ 7 F W.B. 7

8 Outdoor Unit CM7 Indoor Unit KMS097 Type Number of Connectable Indoor Units Number of Operatable Indoor Units Voltage Rating -Room Multi Outdoor Unit 0V Single-Phase 60Hz < 0V > Performance Total Capacity Sensible Capacity Latent Capacity Air Circulation (High) BTU/h kw BTU/h BTU/h ft /min (m /h), Cooling ( 9,800 to,00 ) (.90 to 7.0 ),00,000,707 (,900) Electrical Rating Available Voltage Range V 87 to Running Amperes Power Input A W.,60 Power Factor % 98 SEER BTU/W Compressor Locked Rotor Amperes A.0 Fuse or Circuit Breaker Capacity A 0 Features (Outdoor Unit) Control Microprocessor Fan Speeds Auto (Hi, Me, Lo) Compressor Refrigerant / Amount charged at shipment Ib. (g) DC Twin Rotary (Inverter) R0A / 6.7 (,800) Refrigerant Control Electric Expansion Valve Operation Sound (High) Cool db-a 0 Refrigerant Tubing Connections Flare Type Max. allowable tubing length per unit ft. (m) 8 () Refrigerant Narrow tube inch (mm) Tube Diameter Wide tube inch (mm) Dimensions & Weight (Outdoor Unit) Unit Dimensions Package Dimensions Weight Height Width Depth Height Width Depth Shipping Volume Net Shipping inch (mm) inch (mm) Ib. (kg) Ib. (kg) cu.ft (m ) Cooling / (6.) /8 (9.) + / (.7) 9-/8-7/6-9/ ( ) -7/ 0-/8 6-/ (860,0 ) (6.0) (67.0) (0.6) DATA SUBJECT TO CHANGE WITHOUT NOTICE. Remarks:. The Values shown in performance section and electrical rating section above are based on the following unit combination. For other combination unit, please refer to the "Unit Combination Tables" in this manual. Indoor Unit : KMS097 units Outdoor Unit : CM7 unit. Rating conditions are: Cooling : Indoor air temp. 80 F D.B./ 67 F W.B. Outdoor air temp. 9 F D.B./ 7 F W.B. 8

9 Outdoor Unit CM7 Indoor Unit KMS097 Type Number of Connectable Indoor Units Number of Operatable Indoor Units Voltage Rating -Room Multi Outdoor Unit 08V Single-Phase 60Hz < 08V > Performance Total Capacity Sensible Capacity Latent Capacity Air Circulation (High) BTU/h kw BTU/h BTU/h ft /min (m /h), Cooling ( 9,800 to,00 ) (.90 to 7.0 ) 0,600,800,707 (,900) Electrical Rating Available Voltage Range V 87 to Running Amperes Power Input A W.,60 Power Factor % 98 SEER BTU/W Compressor Locked Rotor Amperes A.0 Fuse or Circuit Breaker Capacity A 0 Features (Outdoor Unit) Control Microprocessor Fan Speeds Auto (Hi, Me, Lo) Compressor Refrigerant / Amount charged at shipment Ib. (g) DC Twin Rotary (Inverter) R0A / 6.7 (,800) Refrigerant Control Electric Expansion Valve Operation Sound (High) Cool db-a 0 Refrigerant Tubing Connections Flare Type Max. allowable tubing length per unit ft. (m) 8 () Refrigerant Narrow tube inch (mm) Tube Diameter Wide tube inch (mm) Dimensions & Weight (Outdoor Unit) Unit Dimensions Package Dimensions Weight Height Width Depth Height Width Depth Shipping Volume Net Shipping inch (mm) inch (mm) Ib. (kg) Ib. (kg) cu.ft (m ) Cooling / (6.) /8 (9.) + / (.7) 9-/8-7/6-9/ ( ) -7/ 0-/8 6-/ (860,0 ) (6.0) (67.0) (0.6) DATA SUBJECT TO CHANGE WITHOUT NOTICE. Remarks:. The Values shown in performance section and electrical rating section above are based on the following unit combination. For other combination unit, please refer to the "Unit Combination Tables" in this manual. Indoor Unit : KMS097 units Outdoor Unit : CM7 unit. Rating conditions are: Cooling : Indoor air temp. 80 F D.B./ 67 F W.B. Outdoor air temp. 9 F D.B./ 7 F W.B. 9

10 Outdoor Unit CM7 Indoor Unit KMS097 Type Number of Connectable Indoor Units Number of Operatable Indoor Units Voltage Rating -Room Multi Outdoor Unit 0V Single-Phase 60Hz < 0V > Performance Total Capacity Sensible Capacity Latent Capacity Air Circulation (High) BTU/h kw BTU/h BTU/h ft /min (m /h) 0, Cooling ( 9,800 to 0,600 ) (.90 to 9.00 ),800,800,9 (,00) Electrical Rating Available Voltage Range V 87 to Running Amperes Power Input A W.,800 Power Factor % 99 SEER BTU/W 6 Compressor Locked Rotor Amperes A 7.0 Fuse or Circuit Breaker Capacity A 0 Features (Outdoor Unit) Control Microprocessor Fan Speeds Auto (Hi, Me, Lo) Compressor Refrigerant / Amount charged at shipment Ib. (g) DC Twin Rotary (Inverter) R0A / 8.8 (,800) Refrigerant Control Electric Expansion Valve Operation Sound (High) Cool db-a Refrigerant Tubing Connections Flare Type Max. allowable tubing length per unit ft. (m) 00 (0.) Refrigerant Narrow tube inch (mm) Tube Diameter Wide tube inch (mm) Dimensions & Weight (Outdoor Unit) Unit Dimensions Package Dimensions Weight Height Width Depth Height Width Depth Shipping Volume Net Shipping inch (mm) inch (mm) Ib. (kg) Ib. (kg) cu.ft (m ) Cooling / (6.) /8 (9.) + / (.7) -/ -7/6-9/ ( ) 9-/ 0-/8 6-/ (,00,0 ) (79.0) (8.0) (0.) DATA SUBJECT TO CHANGE WITHOUT NOTICE. Remarks:. The Values shown in performance section and electrical rating section above are based on the following unit combination. For other combination unit, please refer to the "Unit Combination Tables" in this manual. Indoor Unit : KMS097 units Outdoor Unit : CM7 unit. Rating conditions are: Cooling : Indoor air temp. 80 F D.B./ 67 F W.B. Outdoor air temp. 9 F D.B./ 7 F W.B. 0

11 Outdoor Unit CM7 Indoor Unit KMS097 Type Number of Connectable Indoor Units Number of Operatable Indoor Units Voltage Rating -Room Multi Outdoor Unit 08V Single-Phase 60Hz < 08V > Performance Total Capacity Sensible Capacity Latent Capacity Air Circulation (High) BTU/h kw BTU/h BTU/h ft /min (m /h) 8, Cooling ( 9,800 to 8,600 ) (.90 to 8.0 ),00,00,9 (,00) Electrical Rating Available Voltage Range V 87 to Running Amperes Power Input A W.6,800 Power Factor % 99 SEER BTU/W 6 Compressor Locked Rotor Amperes A 7.0 Fuse or Circuit Breaker Capacity A 0 Features (Outdoor Unit) Control Microprocessor Fan Speeds Auto (Hi, Me, Lo) Compressor Refrigerant / Amount charged at shipment Ib. (g) DC Twin Rotary (Inverter) R0A / 8.8 (,800) Refrigerant Control Electric Expansion Valve Operation Sound (High) Cool db-a Refrigerant Tubing Connections Flare Type Max. allowable tubing length per unit ft. (m) 00 (0.) Refrigerant Narrow tube inch (mm) Tube Diameter Wide tube inch (mm) Dimensions & Weight (Outdoor Unit) Unit Dimensions Package Dimensions Weight Height Width Depth Height Width Depth Shipping Volume Net Shipping inch (mm) inch (mm) Ib. (kg) Ib. (kg) cu.ft (m ) Cooling / (6.) /8 (9.) + / (.7) -/ -7/6-9/ ( ) 9-/ 0-/8 6-/ (,00,0 ) (79.0) (8.0) (0.) DATA SUBJECT TO CHANGE WITHOUT NOTICE. Remarks:. The Values shown in performance section and electrical rating section above are based on the following unit combination. For other combination unit, please refer to the "Unit Combination Tables" in this manual. Indoor Unit : KMS097 units Outdoor Unit : CM7 unit. Rating conditions are: Cooling : Indoor air temp. 80 F D.B./ 67 F W.B. Outdoor air temp. 9 F D.B./ 7 F W.B.

12 -. Major Component Specifications --. Outdoor Unit Outdoor Unit CM97 Control PCB Part No. Controls Control Circuit Fuse Compressor Type Compressor Model / Nominal Output Compressor Oil... Amount Pints (cc) Coil Resistance (Ambient Temp. 68 F (0 C)) Ohm Safety Device CT (Peak current cut-off control) Compressor Discharge Temp. Control Operation cut-off control in abnormal ambient Temp. Overload Relay Model Operation Temp. Run Capacitor Crankcase Heater Micro F VAC CB-CM97 Microprocessor 0V A DC Twin Rotary (Hermetic) KD0XAB /,700W FV0S....9 (900) U - V : 0.70 V - W : W - U : 0.76 Yes Yes Yes CS-7LN Open : 9 F ( C), Close : F (00 C) Fan Type Q'ty... Dia. inch (mm) Propeller... D8-/8 (D60) Fan Motor Type Model... Q'ty No. of Poles Rough Measure RPM (Cool) Nominal Output Coil Resistance (Ambient Temp. 68 F (0 C)) Safety Device Type Over-Current Protection Over-Heat Protection Run Capacitor W Ohm Micro F VAC DC Motor SIC-7FW-D Internal Controller Yes Yes - - Heat Exchanger Coil Coil Rows Fins per inch Aluminum Plate Fin / Copper Tube 8. Face Area ft (m ) 6.0 (0.9) External Finish Acrylic baked-on enamel finish DATA SUBJECT TO CHANGE WITHOUT NOTICE.

13 Outdoor Unit CM7 Control PCB Part No. Controls Control Circuit Fuse Compressor Type Compressor Model / Nominal Output Compressor Oil... Amount Pints (cc) Coil Resistance (Ambient Temp. 68 F (0 C)) Ohm Safety Device CT (Peak current cut-off control) Compressor Discharge Temp. Control Operation cut-off control in abnormal ambient Temp. Overload Relay Model Operation Temp. Run Capacitor Crankcase Heater Micro F VAC CB-CM7 Microprocessor 0V A DC Twin Rotary (Hermetic) KD0XAB /,700W FV0S....9 (900) U - V : 0.70 V - W : W - U : 0.76 Yes Yes Yes CS-7LN Open : 9 F ( C), Close : F (00 C) Fan Type Q'ty... Dia. inch (mm) Propeller... D8-/8 (D60) Fan Motor Type Model... Q'ty No. of Poles Rough Measure RPM (Cool) Nominal Output Coil Resistance (Ambient Temp. 68 F (0 C)) Safety Device Type Over-Current Protection Over-Heat Protection Run Capacitor W Ohm Micro F VAC DC Motor SIC-7FW-D Internal Controller Yes Yes - - Heat Exchanger Coil Coil Rows Fins per inch Aluminum Plate Fin / Copper Tube 8. Face Area ft (m ) 6.0 (0.9) External Finish Acrylic baked-on enamel finish DATA SUBJECT TO CHANGE WITHOUT NOTICE.

14 Outdoor Unit CM7 Control PCB Part No. Controls Control Circuit Fuse Compressor Type Compressor Model / Nominal Output Compressor Oil... Amount Pints (cc) Coil Resistance (Ambient Temp. 68 F (0 C)) Ohm Safety Device CT (Peak current cut-off control) Compressor Discharge Temp. Control Operation cut-off control in abnormal ambient Temp. Overload Relay Model Operation Temp. Run Capacitor Crankcase Heater Micro F VAC CB-CM7 Microprocessor 0V A DC Twin Rotary (Hermetic) JD0XAB /,000W FV0S.... (,00) U - V : 0. V - W : 0. W - U : 0. Yes Yes Yes CS-7LN Open : 9 F ( C), Close : F (00 C) Fan Type Q'ty... Dia. inch (mm) Propeller... D8-/8 (D60) Fan Motor Type Model... Q'ty No. of Poles Rough Measure RPM (Cool) Nominal Output Coil Resistance (Ambient Temp. 68 F (0 C)) Safety Device Type Over-Current Protection Over-Heat Protection Run Capacitor W Ohm Micro F VAC DC Motor SIC-7FW-D Internal Controller Yes Yes - - Heat Exchanger Coil Coil Rows Fins per inch Aluminum Plate Fin / Copper Tube 8. Face Area ft (m ) 7.7 (0.7) External Finish Acrylic baked-on enamel finish DATA SUBJECT TO CHANGE WITHOUT NOTICE.

15 -. Other Component Specifications Sensor Name Model No. of sensor Quantity of Sensor CM97 CM7 CM7 Outdoor air temp sensor TKS9B Outdoor heat exchanger sensor TKS9B AW / AN sensor TKS9B / / / BW / BN sensor TKS9B / / / CW / CN sensor TKS9B / / / DW / DN sensor TKS9B 0 / / 0 Resistance (k ohm) (-0)(-)(-0) (-) (0) () (0) () (0) Temperature F ( C) Sensor Name Model No. of sensor Quantity of Sensor CM97 CM7 CM7 Compressor temp sensor TKS9B Resistance (k ohm) (0) (0) (0) (0) (0) (0) (60) (70) (80) (90) Temperature F ( C)

16 . DIMENSIONAL DATA Outdoor Unit CM97 -/6 -/ -/8-7/ ID:/ -ID:/6 / -7/6(900) Wide tube service valve dia./8" (9.) Narrow tube service valve dia./" (6.) / -9/ -7/ -/ -7/6 -/6 -/ 9-/8(70) -9/(0) -9/ -7/ -/6 -/6 -/ -/ -/6 Unit: inch(mm) 6

17 Outdoor Unit CM7 -/6 -/ -/8-7/ ID:/ -ID:/6 / -9/(0) -9/ -7/ -7/6(900) -/6 Wide tube service valve dia./8" (9.) Narrow tube service valve dia./" (6.) / 9-/8(70) -9/ -7/ -/ -/ Wide tube service valve dia./" (.70) -/6 -/ -/ -7/6 -/6 -/ -/ -/6 -/ Unit: inch(mm) 7

18 Outdoor Unit CM7 -/6 -/ -/8-7/ ID:/ -ID:/6 / -7/6(900) Wide tube service valve dia./8" (9.) Narrow tube service valve dia./" (6.) Wide tube service valve dia./" (.70) / -9/ -7/8 -/ -/ -7/6 -/6 -/ -/ -9/(0) -9/ -7/ -/(890) -/6 -/6 -/ -/ -/6 -/ Unit: inch(mm) 8

19 . REFRIGERANT FLOW DIAGRAM -. Refrigerant Flow Diagram Outdoor Unit CM97 Indoor unit Outdoor unit Wide tube O.D./8" O.D./8" O.D./8" Service valve on wide tube CW BW AW Header Sub accumulator Main accumulator High pressure switch H.P. Compressor Narrow tube O.D./" O.D./" O.D./" Service valve on narrow tube CN BN AN Strainer Electric expansion valve M M M Header Heat exchanger Cooling cycle Insulation of Refrigerant Tubing IMPORTANT Because capillary tubing is used in the outdoor unit, both the wide and narrow tubes of this air conditioner become cold. To prevent heat loss and wet floors due to dripping of condensation, both tubes must be well insulated with a proper insulation material. The thickness of the insulation should be a min./6"(8 mm). Thickness: Min./6"(8 mm) Insulation Thickness: Min./6"(8 mm) CAUTION After a tube has been insulated, never try to bend it into a narrow curve because it can cause the tube to break or crack. Wide tube Narrow tube 9

20 Outdoor Unit CM7 Indoor unit Outdoor unit Wide tube O.D./8" O.D./8" O.D./8" O.D./" Service valve on wide tube DW CW BW AW Header Sub accumulator Main accumulator High pressure switch H.P. Compressor Narrow tube O.D./" O.D./" O.D./" O.D./" Service valve on narrow tube DN CN BN AN Strainer Electric expansion valve M M M M Header Heat exchanger Cooling cycle Insulation of Refrigerant Tubing IMPORTANT Because capillary tubing is used in the outdoor unit, both the wide and narrow tubes of this air conditioner become cold. To prevent heat loss and wet floors due to dripping of condensation, both tubes must be well insulated with a proper insulation material. The thickness of the insulation should be a min./6"(8 mm). Thickness: Min./6"(8 mm) Insulation Thickness: Min./6"(8 mm) CAUTION After a tube has been insulated, never try to bend it into a narrow curve because it can cause the tube to break or crack. Wide tube Narrow tube 0

21 Outdoor Unit CM7 Indoor unit Outdoor unit Wide tube O.D./8" O.D./8" O.D./" O.D./" Service valve on wide tube DW CW BW AW Header Sub accumulator Main accumulator High pressure switch H.P. Compressor Narrow tube O.D./" O.D./" O.D./" O.D./" Service valve on narrow tube DN CN BN AN Strainer Electric expansion valve M M M M Header Heat exchanger Cooling cycle Insulation of Refrigerant Tubing IMPORTANT Because capillary tubing is used in the outdoor unit, both the wide and narrow tubes of this air conditioner become cold. To prevent heat loss and wet floors due to dripping of condensation, both tubes must be well insulated with a proper insulation material. The thickness of the insulation should be a min./6"(8 mm). Thickness: Min./6"(8 mm) Insulation Thickness: Min./6"(8 mm) CAUTION After a tube has been insulated, never try to bend it into a narrow curve because it can cause the tube to break or crack. Wide tube Narrow tube

22 . PERFORMANCE DATA -. Temperature Charts --. Temperature Charts (CM97) Outdoor Unit CM97 Indoor Unit KMS077 Cooling Characteristics (RH : 6%, Indoor fan speed : High fan) (0V, 60Hz) () Low pressure performance chart Low pressure at wide tube service valve psig (MPaG) 88 (.) 7 (.) 60 (.) 6 (.0) 77 () Lo fan Hi fan HH fan 86 (0) Indoor air temp. 86 F (0 C) 80 F (7 C) 7 F ( C) 9 () Outdoor air temperature F ( C) () Operating current performance chart 0 (0) Lo fan Hi fan HH fan Operating current (A) Indoor air temp. 86 F (0 C) 80 F (7 C) 7 F ( C) 77 () 86 (0) 9 () Outdoor air temperature F ( C) () Indoor discharge air performance chart 0 (0) Indoor discharge air temperature F ( C) 68.0(0) 6.(8) 60.8(6) 7.().6() 0.0(0) 6.( 8) 77 () Lo fan Hi fan HH fan 86 (0) Indoor air temp. 86 F (0 C) 9 () Outdoor air temperature F ( C) 80 F (7 C) 7 F ( C) 0 (0) NOTE This performance chart shows operation of a single wall-mounted indoor unit. The performance chart will vary depending on the indoor unit type. Check each performance value in test-run mode. Electrical performance values represent a combined indoor/outdoor value. (In this case, be sure to stop all the indoor units where performance is not being checked.) The performance is for a tubing length of.6t (7.m). If the tubing length is different, the performance chart will vary.

23 Outdoor Unit CM97 Indoor Unit KMS097 Cooling Characteristics (RH : 6%, Indoor fan speed : High fan) (0V, 60Hz) () Low pressure performance chart Low pressure at wide tube service valve psig (MPaG) 88 (.) 7 (.) 60 (.) Lo fan Hi fan Indoor air temp. 86 F (0 C) 80 F (7 C) 7 F ( C) HH fan 6 (.0) 77 () 86 (0) 9 () Outdoor air temperature F ( C) 0 (0) () Operating current performance chart 6 Lo fan Hi fan HH fan Operating current (A) Indoor air temp. 86 F (0 C) 80 F (7 C) 7 F ( C) 77 () 86 (0) 9 () Outdoor air temperature F ( C) 0 (0) () Indoor discharge air performance chart Indoor discharge air temperature F ( C) 68.0(0) 6.(8) 60.8(6) 7.().6() 0.0(0) 6.( 8) 77 () Lo fan 86 (0) Outdoor air temperature F ( C) NOTE This performance chart shows operation of a single wall-mounted indoor unit. The performance chart will vary depending on the indoor unit type. Check each performance value in test-run mode. Electrical performance values represent a combined indoor/outdoor value. (In this case, be sure to stop all the indoor units where performance is not being checked.) The performance is for a tubing length of.6ft (7.m). If the tubing length is different, the performance chart will vary. Hi fan Indoor air temp. 86 F (0 C) 9 () 80 F (7 C) 7 F ( C) HH fan 0 (0)

24 Outdoor Unit CM97 Indoor Unit KMS7 Cooling Characteristics (RH : 6%, Indoor fan speed : High fan) (0V, 60Hz) () Low pressure performance chart Low pressure at wide tube service valve psig (MPaG) 7 (.) 60 (.) 6 (.0) (0.9) 77 () Lo fan 86 (0) Hi fan Indoor air temp. 86 F (0 C) 80 F (7 C) 7 F ( C) 9 () Outdoor air temperature F ( C) HH fan 0 (0) () Operating current performance chart 6 Lo fan Hi fan HH fan Operating current (A) Indoor air temp. 86 F (0 C) 80 F (7 C) 7 F ( C) 77 () 86 (0) 9 () Outdoor air temperature F ( C) 0 (0) () Indoor discharge air performance chart Indoor discharge air temperature F ( C) 68.0(0) 6.(8) 60.8(6) 7.().6() 0.0(0) 6.( 8) 77 () Lo fan 86 (0) Outdoor air temperature F ( C) NOTE This performance chart shows operation of a single wall-mounted indoor unit. The performance chart will vary depending on the indoor unit type. Check each performance value in test-run mode. Electrical performance values represent a combined indoor/outdoor value. (In this case, be sure to stop all the indoor units where performance is not being checked.) The performance is for a tubing length of.6ft (7.m). If the tubing length is different, the performance chart will vary. Hi fan Indoor air temp. 86 F (0 C) 80 F (7 C) 7 F ( C) 9 () HH fan 0 (0)

25 Outdoor Unit CM97 Indoor Unit KMS87 Cooling Characteristics (RH : 6%, Indoor fan speed : High fan) (0V, 60Hz) () Low pressure performance chart Low pressure at wide tube service valve psig (MPaG) 7 (.) 60 (.) 6 (.0) Lo fan Hi fan Indoor air temp. 86 F (0 C) 80 F (7 C) 7 F ( C) HH fan (0.9) 77 () 86 (0) 9 () Outdoor air temperature F ( C) 0 (0) () Operating current performance chart 8 Lo fan Hi fan HH fan Operating current (A) 7 6 Indoor air temp. 86 F (0 C) 80 F (7 C) 7 F ( C) 77 () 86 (0) 9 () Outdoor air temperature F ( C) 0 (0) () Indoor discharge air performance chart Indoor discharge air temperature F ( C) 68.0(0) 6.(8) 60.8(6) 7.().6() 0.0(0) 6.( 8) 77 () Lo fan 86 (0) Hi fan Indoor air temp. 86 F (0 C) 80 F (7 C) 7 F ( C) 9 () Outdoor air temperature F ( C) HH fan 0 (0) NOTE This performance chart shows operation of a single wall-mounted indoor unit. The performance chart will vary depending on the indoor unit type. Check each performance value in test-run mode. Electrical performance values represent a combined indoor/outdoor value. (In this case, be sure to stop all the indoor units where performance is not being checked.) The performance is for a tubing length of.6ft (7.m). If the tubing length is different, the performance chart will vary.

26 --. Temperature Charts (CM7) Outdoor Unit CM7 Indoor Unit KMS077 Cooling Characteristics (RH : 6%, Indoor fan speed : High fan) (0V, 60Hz) () Low pressure performance chart Low pressure at wide tube service valve psig (MPaG) 88 (.) 7 (.) 60 (.) 6 (.0) 77 () Lo fan Hi fan HH fan 86 (0) Indoor air temp. 86 F (0 C) 9 () Outdoor air temperature F ( C) 80 F (7 C) 7 F ( C) () Operating current performance chart 0 (0) Lo fan Hi fan HH fan Operating current (A) Indoor air temp. 86 F (0 C) 80 F (7 C) 7 F ( C) 77 () 86 (0) 9 () Outdoor air temperature F ( C) () Indoor discharge air performance chart 0 (0) Indoor discharge air temperature F ( C) 68.0(0) 6.(8) 60.8(6) 7.().6() 0.0(0) 6.( 8) 77 () Lo fan Hi fan HH fan 86 (0) Indoor air temp. 86 F (0 C) 9 () Outdoor air temperature F ( C) 80 F (7 C) 7 F ( C) 0 (0) NOTE This performance chart shows operation of a single wall-mounted indoor unit. The performance chart will vary depending on the indoor unit type. Check each performance value in test-run mode. Electrical performance values represent a combined indoor/outdoor value. (In this case, be sure to stop all the indoor units where performance is not being checked.) The performance is for a tubing length of.6t (7.m). If the tubing length is different, the performance chart will vary. 6

27 Outdoor Unit CM7 Indoor Unit KMS097 Cooling Characteristics (RH : 6%, Indoor fan speed : High fan) (0V, 60Hz) () Low pressure performance chart Low pressure at wide tube service valve psig (MPaG) 88 (.) 7 (.) 60 (.) 6 (.0) 77 () Lo fan 86 (0) Hi fan Indoor air temp. 86 F (0 C) 80 F (7 C) 7 F ( C) 9 () Outdoor air temperature F ( C) HH fan 0 (0) () Operating current performance chart 6 Lo fan Hi fan HH fan Operating current (A) Indoor air temp. 86 F (0 C) 80 F (7 C) 7 F ( C) 77 () 86 (0) 9 () Outdoor air temperature F ( C) 0 (0) () Indoor discharge air performance chart Indoor discharge air temperature F ( C) 68.0(0) 6.(8) 60.8(6) 7.().6() 0.0(0) 6.( 8) 77 () Lo fan 86 (0) Outdoor air temperature F ( C) NOTE This performance chart shows operation of a single wall-mounted indoor unit. The performance chart will vary depending on the indoor unit type. Check each performance value in test-run mode. Electrical performance values represent a combined indoor/outdoor value. (In this case, be sure to stop all the indoor units where performance is not being checked.) The performance is for a tubing length of.6ft (7.m). If the tubing length is different, the performance chart will vary. 7 Hi fan Indoor air temp. 86 F (0 C) 9 () 80 F (7 C) 7 F ( C) HH fan 0 (0)

28 Outdoor Unit CM7 Indoor Unit KMS7 Cooling Characteristics (RH : 6%, Indoor fan speed : High fan) (0V, 60Hz) () Low pressure performance chart Low pressure at wide tube service valve psig (MPaG) 7 (.) 60 (.) 6 (.0) (0.9) 77 () Lo fan 86 (0) Hi fan Indoor air temp. 86 F (0 C) 80 F (7 C) 7 F ( C) 9 () Outdoor air temperature F ( C) HH fan 0 (0) () Operating current performance chart 6 Lo fan Hi fan HH fan Operating current (A) Indoor air temp. 86 F (0 C) 80 F (7 C) 7 F ( C) 77 () 86 (0) 9 () Outdoor air temperature F ( C) 0 (0) () Indoor discharge air performance chart Indoor discharge air temperature F ( C) 68.0(0) 6.(8) 60.8(6) 7.().6() 0.0(0) 6.( 8) 77 () Lo fan 86 (0) Outdoor air temperature F ( C) NOTE This performance chart shows operation of a single wall-mounted indoor unit. The performance chart will vary depending on the indoor unit type. Check each performance value in test-run mode. Electrical performance values represent a combined indoor/outdoor value. (In this case, be sure to stop all the indoor units where performance is not being checked.) The performance is for a tubing length of.6ft (7.m). If the tubing length is different, the performance chart will vary. Hi fan Indoor air temp. 86 F (0 C) 8 80 F (7 C) 7 F ( C) 9 () HH fan 0 (0)

29 Outdoor Unit CM7 Indoor Unit KMS87 Cooling Characteristics (RH : 6%, Indoor fan speed : High fan) (0V, 60Hz) () Low pressure performance chart Low pressure at wide tube service valve psig (MPaG) 7 (.) 60 (.) 6 (.0) Lo fan Hi fan Indoor air temp. 86 F (0 C) 80 F (7 C) 7 F ( C) HH fan (0.9) 77 () 86 (0) 9 () Outdoor air temperature F ( C) 0 (0) () Operating current performance chart 8 Lo fan Hi fan HH fan Operating current (A) 7 6 Indoor air temp. 86 F (0 C) 80 F (7 C) 7 F ( C) 77 () 86 (0) 9 () Outdoor air temperature F ( C) 0 (0) () Indoor discharge air performance chart Indoor discharge air temperature F ( C) 68.0(0) 6.(8) 60.8(6) 7.().6() 0.0(0) 6.( 8) 77 () Lo fan 86 (0) Hi fan Indoor air temp. 86 F (0 C) 80 F (7 C) 7 F ( C) 9 () Outdoor air temperature F ( C) HH fan 0 (0) NOTE This performance chart shows operation of a single wall-mounted indoor unit. The performance chart will vary depending on the indoor unit type. Check each performance value in test-run mode. Electrical performance values represent a combined indoor/outdoor value. (In this case, be sure to stop all the indoor units where performance is not being checked.) The performance is for a tubing length of.6ft (7.m). If the tubing length is different, the performance chart will vary. 9

30 Outdoor Unit CM7 Indoor Unit KMS7 Cooling Characteristics (RH : 6%, Indoor fan speed : High fan) (0V, 60Hz) () Low pressure performance chart Low pressure at wide tube service valve psig (MPaG) 7 (.) 60 (.) 6 (.0) Lo fan Hi fan HH fan Indoor air temp. 86 F (0 C) 80 F (7 C) 7 F ( C) (0.9) 77 () 86 (0) 9 () Outdoor air temperature F ( C) 0 (0) () Operating current performance chart Operating current (A) 9 Lo fan 8 7 HH fan Hi fan Indoor air temp. 86 F (0 C) 80 F (7 C) 7 F ( C) 6 77 () 86 (0) 9 () Outdoor air temperature F ( C) 0 (0) () Indoor discharge air performance chart Indoor discharge air temperature F ( C) 68.0(0) 6.(8) 60.8(6) 7.().6() 0.0(0) 6.( 8) 77 () Lo fan 86 (0) Outdoor air temperature F ( C) NOTE This performance chart shows operation of a single wall-mounted indoor unit. The performance chart will vary depending on the indoor unit type. Check each performance value in test-run mode. Electrical performance values represent a combined indoor/outdoor value. (In this case, be sure to stop all the indoor units where performance is not being checked.) The performance is for a tubing length of.6ft (7.m). If the tubing length is different, the performance chart will vary. 0 Hi fan Indoor air temp. 86 F (0 C) 80 F (7 C) 7 F ( C) 9 () HH fan 0 (0)

31 --. Temperature Charts (CM7) Outdoor Unit CM7 Indoor Unit KMS077 Cooling Characteristics (RH : 6%, Indoor fan speed : High fan) (0V, 60Hz) () Low pressure performance chart Low pressure at wide tube service valve psig (MPaG) 7 (.) 6 (.0) 8 (0.8) 90 (0.6) 77 () Lo fan Hi fan Hi fan HH fan 86 (0) Indoor air temp. 86 F (0 C) 9 () Outdoor air temperature F ( C) 80 F (7 C) 7 F ( C) 0 (0) () Operating current performance chart Lo fan Hi fan Hi fan HH fan Operating current (A) Indoor air temp. 86 F (0 C) 80 F (7 C) 7 F ( C) 77 () 86 (0) 9 () Outdoor air temperature F ( C) 0 (0) () Indoor discharge air performance chart Indoor discharge air temperature F ( C) 68.0(0) 6.(8) 60.8(6) 7.().6() 0.0(0) 6.( 8) 77 () Lo fan Hi fan Hi fan HH fan 86 (0) Outdoor air temperature F ( C) NOTE This performance chart shows operation of a single wall-mounted indoor unit. The performance chart will vary depending on the indoor unit type. Check each performance value in test-run mode. Electrical performance values represent a combined indoor/outdoor value. (In this case, be sure to stop all the indoor units where performance is not being checked.) The performance is for a tubing length of.6ft (7.m). If the tubing length is different, the performance chart will vary. Indoor air temp. 86 F (0 C) 9 () 80 F (7 C) 7 F ( C) 0 (0)

32 Outdoor Unit CM7 Indoor Unit KMS097 Cooling Characteristics (RH : 6%, Indoor fan speed : High fan) (0V, 60Hz) () Low pressure performance chart Low pressure at wide tube service valve psig (MPaG) 7 (.) 6 (.0) 8 (0.8) 90 (0.6) 77 () Lo fan Hi fan Hi fan HH fan 86 (0) Indoor air temp. 86 F (0 C) 80 F (7 C) 7 F ( C) 9 () Outdoor air temperature F ( C) 0 (0) () Operating current performance chart Lo fan Hi fan Hi fan HH fan Operating current (A) Indoor air temp. 86 F (0 C) 80 F (7 C) 7 F ( C) 77 () 86 (0) 9 () Outdoor air temperature F ( C) 0 (0) () Indoor discharge air performance chart Indoor discharge air temperature F ( C) 68.0(0) 6.(8) 60.8(6) 7.().6() 0.0(0) 6.( 8) 77 () Lo fan Hi fan Hi fan HH fan 86 (0) Indoor air temp. 86 F (0 C) 80 F (7 C) 7 F ( C) 9 () Outdoor air temperature F ( C) 0 (0) NOTE This performance chart shows operation of a single wall-mounted indoor unit. The performance chart will vary depending on the indoor unit type. Check each performance value in test-run mode. Electrical performance values represent a combined indoor/outdoor value. (In this case, be sure to stop all the indoor units where performance is not being checked.) The performance is for a tubing length of.6ft (7.m). If the tubing length is different, the performance chart will vary.

33 Outdoor Unit CM7 Indoor Unit KMS7 Cooling Characteristics (RH : 6%, Indoor fan speed : High fan) (0V, 60Hz) () Low pressure performance chart Low pressure at wide tube service valve psig (MPaG) 7 (.) 6 (.0) 8 (0.8) Lo fan Hi fan Hi fan HH fan Indoor air temp. 86 F (0 C) 80 F (7 C) 7 F ( C) 90 (0.6) 77 () 86 (0) 9 () Outdoor air temperature F ( C) 0 (0) () Operating current performance chart 6 Lo fan Hi fan Hi fan HH fan Operating current (A) Indoor air temp. 86 F (0 C) 80 F (7 C) 7 F ( C) 77 () 86 (0) 9 () Outdoor air temperature F ( C) () Indoor discharge air performance chart 0 (0) Indoor discharge air temperature F ( C) 68.0(0) 6.(8) 60.8(6) 7.().6() 0.0(0) 6.( 8) 77 () Lo fan Hi fan Hi fan HH fan 86 (0) Outdoor air temperature F ( C) NOTE This performance chart shows operation of a single wall-mounted indoor unit. The performance chart will vary depending on the indoor unit type. Check each performance value in test-run mode. Electrical performance values represent a combined indoor/outdoor value. (In this case, be sure to stop all the indoor units where performance is not being checked.) The performance is for a tubing length of.6ft (7.m). If the tubing length is different, the performance chart will vary. Indoor air temp. 86 F (0 C) 9 () 80 F (7 C) 7 F ( C) 0 (0)

34 Outdoor Unit CM7 Indoor Unit KMS87 Cooling Characteristics (RH : 6%, Indoor fan speed : High fan) (0V, 60Hz) () Low pressure performance chart Low pressure at wide tube service valve psig (MPaG) 7 (.) 6 (.0) 8 (0.8) Indoor air temp. 86 F (0 C) 80 F (7 C) 7 F ( C) Lo fan Hi fan 90 (0.6) 77 () 86 (0) 9 () Outdoor air temperature F ( C) 0 (0) () Operating current performance chart 9 Lo fan Hi fan Operating current (A) F (7 C) Indoor air temp. 86 F (0 C) 7 F ( C) 77 () 86 (0) 9 () Outdoor air temperature F ( C) 0 (0) () Indoor discharge air performance chart Indoor discharge air temperature F ( C) 68.0(0) 6.(8) 60.8(6) 7.().6() 0.0(0) 6.( 8) 77 () 86 (0) Lo fan Indoor air temp. 86 F (0 C) 9 () Outdoor air temperature F ( C) 80 F (7 C) 7 F ( C) Hi fan 0 (0) NOTE This performance chart shows operation of a single wall-mounted indoor unit. The performance chart will vary depending on the indoor unit type. Check each performance value in test-run mode. Electrical performance values represent a combined indoor/outdoor value. (In this case, be sure to stop all the indoor units where performance is not being checked.) The performance is for a tubing length of.6ft (7.m). If the tubing length is different, the performance chart will vary.

35 Outdoor Unit CM7 Indoor Unit KMS7 Cooling Characteristics (RH : 6%, Indoor fan speed : High fan) (0V, 60Hz) () Low pressure performance chart Low pressure at wide tube service valve psig (MPaG) 7 (.) 6 (.0) 8 (0.8) 90 (0.6) 77 () 86 (0) Lo fan Indoor air temp. 86 F (0 C) 80 F (7 C) 7 F ( C) 9 () Outdoor air temperature F ( C) Hi fan 0 (0) () Operating current performance chart Operating current (A) 0 9 Lo fan Indoor air temp. 86 F (0 C) 80 F (7 C) 7 F ( C) Hi fan 8 77 () 86 (0) 9 () Outdoor air temperature F ( C) 0 (0) () Indoor discharge air performance chart Indoor discharge air temperature F ( C) 68.0(0) 6.(8) 60.8(6) 7.().6() 0.0(0) 6.( 8) 77 () 86 (0) Outdoor air temperature F ( C) NOTE This performance chart shows operation of a single wall-mounted indoor unit. The performance chart will vary depending on the indoor unit type. Check each performance value in test-run mode. Electrical performance values represent a combined indoor/outdoor value. (In this case, be sure to stop all the indoor units where performance is not being checked.) The performance is for a tubing length of.6ft (7.m). If the tubing length is different, the performance chart will vary. Lo fan Indoor air temp. 86 F (0 C) 9 () 80 F (7 C) 7 F ( C) Hi fan 0 (0)

36 -. Cooling Capacity Outdoor Unit CM97 Indoor Unit KMS097 Outdoor Unit CM7 Indoor Unit KMS097 Outdoor Unit CM7 Indoor Unit KMS Cooling capacity ratio (%) () 68 (0) 77 () 86 (0) 9 () 0 (0) () (0) Outdoor temperature F D.B. ( C D.B.) NOTE Rating conditions: Indoor air temperature Outdoor air temperature 80 F (6.7 C) D.B. / 67 F (9. C)W.B. 9 F ( C) D.B. 6

37 6. ELECTRICAL DATA 6-. Electric Wiring Diagrams Outdoor Unit CM97 WARNING To avoid electrical shock hazard, be sure to disconnect power before checking, servicing and/or cleaning any electrical parts. REACTANCE COMPRESSOR THERMISTOR COIL/OUTDOOR AW THERMISTOR AN THERMISTOR A-TH (P)CONNECTOR FERRITE CORE (7P)CONNECTOR BW THERMISTOR BN THERMISTOR B-TH HIGH PRESSURE SWITCH CW THERMISTOR CN THERMISTOR (P)CONNECTOR (P)CONNECTOR RED COIL THERMISTOR OUTDOOR THERMISTOR (P)CONNECTOR COMPRESSOR MOTOR FAN MOTOR OVERLOAD RELAY(OLR) CONTROLLER SICOM KS KS KS0 W CN0 CN0 EXPANSION BOARD C-TH CN0 MV W SICOM SI-C W U W W W W L L E E A SI-A MV0 SI-B MV0 MAGNETIC COIL W ACIN W ACIN COMP GRN/ GRN/ W W W V W 6 RELAY TERMINAL PLATE GND TERMINAL PLATE W W L L POWER SUPPLY FERRITE CORE RED GND BLU C INDDOR UNIT B INDDOR UNIT TO INDDOR UNIT A INDDOR UNIT MV GRY RED ORG GRY RED ORG MV MAGNETIC COIL RED BLU RED BLU FM S/U C/W CM 6 6 R/V RED BLU RED BLU RED BLU BRN ORG MV MAGNETIC COIL RED BLU BRN ORG GRY RED ORG FM BRN BLU RED (PNK) BLU RED (PNK) 8FA

38 Outdoor Unit CM7 WARNING To avoid electrical shock hazard, be sure to disconnect power before checking, servicing and/or cleaning any electrical parts. REACTANCE COMPRESSOR THERMISTOR AW THERMISTOR AN THERMISTOR COIL/OUTDOOR A-TH (7P)CONNECTOR (P)CONNECTOR FERRITE CORE BW THERMISTOR BN THERMISTOR B-TH HIGH PRESSURE SWITCH CW THERMISTOR CN THERMISTOR MAGNETIC COIL (P)CONNECTOR (P)CONNECTOR RED COIL THERMISTOR OUTDOOR THERMISTOR (P)CONNECTOR COMPRESSOR MOTOR FAN MOTOR OVERLOAD RELAY(OLR) CONTROLLER SICOM KS KS KS0 W CN0 CN0 EXPANSION BOARD D-TH C-TH MV W CN0 SICOM MV SI-D SI-C W W U W W W W L L E E A SI-A MV0 SI-B MV0 MAGNETIC COIL W ACIN W ACIN COMP GRN/ W W W V W 6 RELAY TERMINAL PLATE GND TERMINAL PLATE W W L L POWER SUPPLY FERRITE CORE RED GND BLU D INDDOR UNIT C INDDOR B INDDOR UNIT UNIT TO INDDOR UNIT A INDDOR UNIT MV GRY RED ORG GRY RED ORG MV MAGNETIC COIL RED BLU RED BLU FM S/U C/W CM R/V RED BLU RED BLU RED BLU BRN ORG MV MAGNETIC COIL RED BLU BRN ORG DW THERMISTOR DN THERMISTOR GRY RED ORG FM 6 6 GRY RED ORG MV BRN GRY BLU RED (PNK) BLU RED (PNK) GRN/ 8FA

39 Outdoor Unit CM7 WARNING To avoid electrical shock hazard, be sure to disconnect power before checking, servicing and/or cleaning any electrical parts. REACTANCE COMPRESSOR THERMISTOR AW THERMISTOR AN THERMISTOR COIL/OUTDOOR A-TH (7P)CONNECTOR (P)CONNECTOR FERRITE CORE BW THERMISTOR BN THERMISTOR B-TH HIGH PRESSURE SWITCH CW THERMISTOR CN THERMISTOR MAGNETIC COIL (P)CONNECTOR (P)CONNECTOR RED COIL THERMISTOR OUTDOOR THERMISTOR (P)CONNECTOR COMPRESSOR MOTOR FAN MOTOR OVERLOAD RELAY(OLR) CONTROLLER SICOM KS KS KS0 W CN0 CN0 EXPANSION BOARD D-TH C-TH MV W CN0 SICOM MV SI-D SI-C W W U W W W W W L L E E ACIN A W ACIN SI-A MV0 SI-B MV0 MAGNETIC COIL COMP GRN/ FERRITE CORE W W W V W 6 RELAY TERMINAL PLATE GND TERMINAL PLATE W W L L POWER SUPPLY GND BLU RED D INDDOR UNIT C INDDOR B INDDOR UNIT UNIT TO INDDOR UNIT A INDDOR UNIT MV GRY RED ORG GRY RED ORG MV MAGNETIC COIL RED BLU RED BLU FM S/U C/W CM R/V RED BLU RED BLU RED BLU BRN ORG MV MAGNETIC COIL RED BLU BRN ORG DW THERMISTOR DN THERMISTOR GRY RED ORG FM 6 6 GRY RED ORG MV BRN GRY BLU RED (PNK) BLU RED (PNK) GRN/ 8FA

40 7. FUNCTIONS 7-. Explanation of Functions NOTE The numerical values such as temperature, frequency, time and current in parentheses are an example of CM7 and the values are different from the other models. Control/conditions Unit operation Explanation INITIAL Breaker is ON. Power is supplied to the indoor and outdoor unit control circuits, however the unit remains stopped. Positioning of the outdoor unit electric expansion valve is performed. The ON/OFF operation button on the remote controller is pressed. If automatic operation mode has been selected with the remote controller, operation begins in SENSOR DRY, or COOL mode depending on the room temperature and outdoor temperature at the time operation starts. This applies in the case of automatic COOL operation. Depending on the operational mode, refer to the SENSOR DRY, or COOL item. 0

41 Control/conditions Unit operation Explanation COOL The ON/OFF operation button on the remote controller is pressed. The operation lamp illuminates. The indoor fan operates at the set fan speed. The outdoor unit stops. The outdoor unit does not operate for minutes even after the breaker is turned ON. The outdoor unit starts. The frequency is increased at the rate of 0. Hz every seconds. (Compressor and the outdoor fan start.) When the frequency reaches Hz, frequency increases are stopped for a period of seconds. (Refer to Table.) This is in order to stabilize the return of oil to the compressor. The frequency then increases. If the indoor and outdoor temperatures are high, the current peak cut-off activates, stopping any increases in frequency. The room temperature has reached the desired temperature. The indoor temperature and the desired temperature are approximately equal. Operating frequency is stabilized in order to maintain a comfortable environment. The thermostat turns OFF. The outdoor unit stops. (It does not stop if the thermostart for another indoor unit is ON.) The thermostat turns ON again. After the thermostat turns ON again, the outdoor unit will not operate for minutes, even if the room temperature increases above the desired temperature. After minutes, the outdoor unit begins operating automatically. During these minutes, a pressure balance is achieved, allowing the compressor to start more easily. Freeze prevention When the temperature of the indoor heat exchanger drops to approximately.6 F or below, the compressor turns OFF, the outdoor fan turns OFF, and the indoor fan continues operating with no changes. In order to protect against freezing, the compressor stops temporarily, until the temperature of the indoor heat exchanger has risen. Approximately minutes later, if the temperature of the indoor heat exchanger is adove 6. F, the system returns to its original conditions. Stop All indicator lamps turn OFF. The indoor and outdoor units stop. Operation is restarted within hours (only when AUTO mode is selected with the remote controller). Starts operating in the same operating mode (COOL) and with the same temperature settings as before operation was stopped. Within hours after operation was stopped, it is assumed that there has been no significant change in the indoor and outdoor temperatures, and the previous conditions (COOL) are stored. Operation starts after hours or more have passed. New operating mode is determined based on the temperature conditions at the time the ON/OFF operation button is pressed. Frequency control (Hz) Outdoor air temperature is below F. (senconds) Outdoor air temperature is F or higher. () Hz () Hz () Hz () Hz (0) seconds (60) seconds (60) seconds (80) seconds Table (60) seconds (0) seconds (0) seconds (90) seconds

42 (/f fluctuation fan) Control/conditions Unit operation Explanation SENSOR DRY The ON/OFF operation button on the remote controller is pressed. The operation lamp illuminates. The indoor fan operates at the set fan speed. The outdoor unit stops. The outdoor unit does not operate for minutes even after the breaker is turned ON. The outdoor unit starts. The frequency is increased at the rate of 0. Hz every seconds. (Compressor and the outdoor fan start.) When the frequency reaches Hz, frequency increases are stopped for a period of seconds. (Refer to Table.) This is in order to stabilize the return of oil to the compressor. The frequency then increases. If the indoor and outdoor temperatures are high, the current peak cut-off activates, stopping any increases in frequency. The room temperature reaches the desired temperature, and there is no need for further cooling. DRY operation starts DRY A operation The indoor fan changes between "Low" and "LL" (very low) over a 6-minute cycle. This is /f fluctuation fan operation. (Refer to Fig..) Operating frequency is stabilized in order to maintain a comfortable environment. Operates to effectively dehumidify the air while not excessively reducing the indoor temperature. The indoor unit operates at /f fluctuation fan operation, at a fan speed that does not cause a chilly feeling. The room temperature is 9 F or higher, and is slightly too cold. DRY B operation () The indoor fan changes between "Low" and "LL" (very low) over a 6-minute cycle. This is /f fluctuation fan operation. The compressor operates on a -minutes ON, 6-minutes OFF cycle, to prevent the room temperature from dropping too much. () After appoximately minutes, the compressor turns OFF, the outdoor fan turns OFF, and the indoor fan turns OFF. () After approximately 6 minutes, the conditions return to (). The room temperature is below 9 F. Monitoring operation begins. When monitoring operation begins, the compressor stops, and the indoor fan operates at "LL" (very low) speed. /f fluctuation fan 0 00 (Step) minute cycle Fig.

DC INVERTER MULTI-SYSTEM AIR CONDITIONER

DC INVERTER MULTI-SYSTEM AIR CONDITIONER TECHNICAL & SERVICE MANUAL OUTDOOR UNIT : AEMI0AH AEMIAHB AEMIAH AEMI0AH FILE NO. Destination: Europe DC INVERTER MULTI-SYSTEM AIR CONDITIONER Capacity.0k.k.k.0k Outdoor Model No. AEMI0AH AEMIAHB AEMIAH

More information

TECHNICAL DATA & SERVICE MANUAL SPLIT SYSTEM AIR CONDITIONER INDOOR UNIT: AW52AL AW64AL AW52AL 387030095 AW64AL 0.8180.463.0 07/05

TECHNICAL DATA & SERVICE MANUAL SPLIT SYSTEM AIR CONDITIONER INDOOR UNIT: AW52AL AW64AL AW52AL 387030095 AW64AL 0.8180.463.0 07/05 TECHNICAL DATA & SERVICE MANUAL INDOOR UNIT: AW52AL AW64AL SPLIT SYSTEM AIR CONDITIONER Model No. Product Code No. AW52AL 387030095 AW64AL 387030096 0.8180.463.0 07/05 IMPORTANT! Please read before installation

More information

DC INVERTER SPLIT SYSTEM AIR CONDITIONER

DC INVERTER SPLIT SYSTEM AIR CONDITIONER TECHNICAL & SERVICE MANUAL CSKS12NB41 & CZ18BT1U + CUKS12NK1A CSKS18NB4UW & CZ18BT1U + CUKS18NKU CSKS18NB4UW & CZ18BT1U + CUKS18NKUA DC INVERTER SPLIT SYSTEM AIR CONDITIONER Indoor Model No. Body (Panel)

More information

DC INVERTER SPLIT SYSTEM AIR CONDITIONER

DC INVERTER SPLIT SYSTEM AIR CONDITIONER TECHNICAL & SERVICE MANUAL CSKE1NB41 & CZ18BT1U + CUKE1NK1 CSKE18NB4UW & CZ18BT1U + CUKE18NKU DC INVERTER SPLIT SYSTEM AIR CONDITIONER Indoor Model No. Body (Panel) CSKE1NB41 (CZ18BT1U) CSKE18NB4UW (CZ18BT1U)

More information

DC INVERTER MULTI-SYSTEM AIR CONDITIONER

DC INVERTER MULTI-SYSTEM AIR CONDITIONER TECHNICAL & SERVICE MANUAL OUTDOOR UNIT : SAP-CMRVEH SAP-CMRV9EH SAP-CMRV9EH SAP-CMRVEH SAP-CMRVEH FILE NO. Destination: Europe Northern Europe DC INVERTER MULTI-SYSTEM AIR CONDITIONER Capacity.0k.6k.6k

More information

DC INVERTER SPLIT SYSTEM AIR CONDITIONER

DC INVERTER SPLIT SYSTEM AIR CONDITIONER AIR CONDITIONER TECHNICAL & SERVICE MANUAL CS-KS30NKU + CU-KS30NKUA CS-KS36NKU + CU-KS36NKUA DC INVERTER SPLIT SYSTEM AIR CONDITIONER Indoor Model No. CS-KS30NKU CS-KS36NKU Product Code No. 852 360 86

More information

TECHNICAL & SERVICE MANUAL SPLIT SYSTEM AIR CONDITIONER + SAP C181MA + SAP C181GA + SAP C181BA + SAP C241MA + SAP C241BA FILE NO.

TECHNICAL & SERVICE MANUAL SPLIT SYSTEM AIR CONDITIONER + SAP C181MA + SAP C181GA + SAP C181BA + SAP C241MA + SAP C241BA FILE NO. TECHNICAL & SERVICE MANUAL SAP K161GJA SAP K181GJA SAP K181MBA SAP K241GJA SAP K241MBA + SAP C161GA + SAP C161JA + SAP C181GA + SAP C181JA + SAP C181MA + SAP C181BA + SAP C241GA + SAP C241JA + SAP C241MA

More information

DC INVERTER MULTI-SYSTEM AIR CONDITIONER

DC INVERTER MULTI-SYSTEM AIR CONDITIONER AIR CONDITIONER AIR CONDITIONER TECHNICAL & SERVICE MANUAL INDOOR UNIT : CS-MKE7NKU CS-MKE9NKU CS-MKE12NKU CS-MKE18NKU CS-MKE24NKU DC INVERTER MULTI-SYSTEM AIR CONDITIONER Capacity 7,500BTU / h 9,000BTU

More information

TECHNICAL & SERVICE MANUAL WINDOW TYPE AIR CONDITIONER SA 79G SA 99G FILE NO. SA 79G SA 99G REFERENCE NO. SM700402

TECHNICAL & SERVICE MANUAL WINDOW TYPE AIR CONDITIONER SA 79G SA 99G FILE NO. SA 79G SA 99G REFERENCE NO. SM700402 TECHNICAL & SERVICE MANUAL SA 79G SA 99G FILE NO. WINDOW TYPE AIR CONDITIONER Model No. Product Code No. Destination SA-79G-A 1 851 005 18 General (50Hz) & Europe SA-99G-A 1 851 005 19 SA 79G SA 99G REFERENCE

More information

DC INVERTER SPLIT SYSTEM AIR CONDITIONER

DC INVERTER SPLIT SYSTEM AIR CONDITIONER AIR CONDITIONER TECHNICAL & SERVICE MANUAL SAP-KRV96EHDS + SAP-CRV96EHDS SAP-KRV126EHDS + SAP-CRV126EHDS FILE NO. Destination: Europe DC INVERTER SPLIT SYSTEM AIR CONDITIONER Indoor Model No. SAP-KRV96EHDS

More information

DC INVERTER SPLIT SYSTEM AIR CONDITIONER

DC INVERTER SPLIT SYSTEM AIR CONDITIONER TECHNICAL & SERVICE MANUAL CSKS1NB41 & CZ18BT1U + CUKS1NK1A CSKS18NB4UW & CZ18BT1U + CUKS18NKU CSKS18NB4UW & CZ18BT1U + CUKS18NKUA DC INVERTER SPLIT SYSTEM AIR CONDITIONER Indoor Model No. Body (Panel)

More information

HP switch LP switch Discharge thermo Comp. Surface thermo

HP switch LP switch Discharge thermo Comp. Surface thermo 1 Specifications Zubadan Model Name PUHZ-SHW80VHA PUHZ-SHW11VHA PUHZ-SHW11YHA Power supply (phase, cycle, voltage) 1φ, V, Hz 1φ, V, Hz 3φ, 0V, Hz Max. current A 9.5 35.0 13.0 Breaker size A 3 16 Outer

More information

SERVICE MANUAL SPLIT SYSTEM ROOM AIR CONDITIONER SHARP CORPORATION SHARP CORPORATION CONTENTS

SERVICE MANUAL SPLIT SYSTEM ROOM AIR CONDITIONER SHARP CORPORATION SHARP CORPORATION CONTENTS SERVICE MANUAL SPLIT SYSTEM ROOM AIR CONDITIONER INDOOR UNIT AH-129 AH-MP14 OUTDOOR UNIT AU-129 AU-MP14 CONTENTS SPECIFICATIONS...2 EXTERNAL DIMENSIONS...4 WIRING DIAGRAMS...5 ELECTRICAL PARTS...6 MICROCOMPUTER

More information

DC INVERTER SPLIT SYSTEM AIR CONDITIONER

DC INVERTER SPLIT SYSTEM AIR CONDITIONER TECHNICAL & SERVICE MANUAL SAP-KRV9AEH + SAP-CRV9AEH SAP-KRV12AEH + SAP-CRV12AEH FILE NO. Destination: Europe DC INVERTER SPLIT SYSTEM AIR CONDITIONER Indoor Model No. SAP-KRV9AEH SAP-KRV12AEH Product

More information

14. Troubleshooting Guide

14. Troubleshooting Guide 14. Guide 14.1 Refrigeration Cycle System In order to diagnose malfunctions, ensure the air conditioner is free from electrical problems before inspecting the refrigeration cycle. Such problems include

More information

USER S MANUAL HSC-24A

USER S MANUAL HSC-24A AIRREX AIR CONDITIONER USER S MANUAL HSC-24A Thank you for purchasing an AIRREX AIR CONDITIONER. BEFORE operation please read this user s manual carefully. Keep this manual readily available. It is ESSENTIAL

More information

technical data air conditioning systems RXS20-25-35E (single phase) FBQ-B8V1-B8V3B Split Heat Pump Condensing Units Split Sky Air

technical data air conditioning systems RXS20-25-35E (single phase) FBQ-B8V1-B8V3B Split Heat Pump Condensing Units Split Sky Air technical data RXS20-25-35E FBQ-B8V-B8V3B (single phase) Split Heat Pump Condensing Units air conditioning systems Split Sky Air Outdoor Units R-40A RXS-E2VB Split Sky Air Outdoor Units Features O u t

More information

DC INVERTER SPLIT SYSTEM AIR CONDITIONER

DC INVERTER SPLIT SYSTEM AIR CONDITIONER AIR CONDITIONER TECHNICAL & SERVICE MANUAL SAP-KRV96EH + SAP-CRV96EH SAP-KRV126EH + SAP-CRV126EH FILE NO. Destination: Europe DC INVERTER SPLIT SYSTEM AIR CONDITIONER Indoor Model No. SAP-KRV96EH SAP-KRV126EH

More information

Si10-417_C. Pocket Manual. Service Diagnosis SPLIT & MULTI

Si10-417_C. Pocket Manual. Service Diagnosis SPLIT & MULTI Pocket Manual Service Diagnosis SPLIT & MULTI Service Diagnosis SPLIT & MULTI 1. Troubleshooting with LED...5 1.1 Indoor Unit... 5 1.2 Outdoor Unit... 10 2. Troubleshooting by Symptoms...11 2.1 Air conditioner

More information

Service manual. Website: www.andico.com.au CAUTION - BEFORE SERVICING THE UNIT, READ THE SAFETY - PRECAUTIONS IN THIS MANUAL.

Service manual. Website: www.andico.com.au CAUTION - BEFORE SERVICING THE UNIT, READ THE SAFETY - PRECAUTIONS IN THIS MANUAL. Website: www.andico.com.au Service manual CAUTION - BEFORE SERVICING THE UNIT, READ THE SAFETY - PRECAUTIONS IN THIS MANUAL. - ONLY FOR AUTHORISED SERVICE PERSONNEL. MODELS: MPK1-09CR-QB8 MPK1-12ER-QB6

More information

Split-type Air-Conditioner INSTALLATION MANUAL CONTENTS FOR INSTALLER MXZ-3A30NA MXZ-4A36NA ATTENTION. English. Français. Español

Split-type Air-Conditioner INSTALLATION MANUAL CONTENTS FOR INSTALLER MXZ-3A30NA MXZ-4A36NA ATTENTION. English. Français. Español Split-type Air-Conditioner MXZ-3A30NA MXZ-4A36NA INSTALLATION MANUAL Refer to the installation manual of each indoor unit for indoor unit installation. English Français Español ATTENTION This manual mentions

More information

SERVICE MANUAL OUTDOOR UNIT. No. OBH590 REVISED EDITION-B. Models HFC

SERVICE MANUAL OUTDOOR UNIT. No. OBH590 REVISED EDITION-B. Models HFC SPLIT-TYPE AIR CONDITIONERS Revision B: MUZ-EF25/35/42/50VE - E2 and MUZ-EF25/35VEH - E2 have been added. Please void OBH590 REVISED EDITION-A. OUTDOOR UNIT SERVICE MANUAL HFC utilized R410A. OBH590 REVISED

More information

AIR-CONDITIONER SPLIT TYPE

AIR-CONDITIONER SPLIT TYPE FILE NO. A08-016 SERVICE MANUAL AIR-CONDITIONER SPLIT TYPE RAS-M10PKVP-E, RAS-M13PKVP-E, RAS-M16PKVP-E, RAS-M18PKVP-E / RAS-M10PKVP-ND, RAS-M13PKVP-ND, RAS-M16PKVP-ND, RAS-M18PKVP-ND / RAS-3M26GAV-E1,

More information

SERVICE MANUAL. Room Air Conditioner Multi Split type Outdoor unit /R410A DC Inverter/

SERVICE MANUAL. Room Air Conditioner Multi Split type Outdoor unit /R410A DC Inverter/ SERVICE MANUAL Room Air Conditioner Multi Split type Outdoor unit /R410A DC Inverter/ FS2MI-147HFD FS2MI-187HFD FS3MI-217HFD FS3MI-277HFD FS4MI-277HFD FS4MI-367HFD FS5MI-367HFD NOTE: Before servicing the

More information

Air Conditioners Technical Data

Air Conditioners Technical Data Air Conditioners Technical Data O u t d o o r U n i t E E D E N 2-0 0 RX-JV Outdoor Unit RX-JV TABLE OF CONTENTS RX-JV Features............................................................. 2 2 Specifications.......................................................

More information

Appendix - Controllers 179

Appendix - Controllers 179 Version: 200703 Appendix - Controllers 179 -3- -4- -5- -6- -7- -8- 2. Specifications 2.1 Specifications for inverter units item Model AB182ACERA Function cooling heating Capacity kw 5.01.8--5.8 5.22.0---6.2

More information

Operating Instructions Split System Air Conditioner

Operating Instructions Split System Air Conditioner Operating Instructions Split System Air Conditioner Model No. Indoor Unit Type Indoor Unit Type Nominal Capacity 26 36 F2 Low Silhouette Ducted S-26PF2U6 S-36PF2U6 Connectable outdoor unit lineup This

More information

SERVICE MANUAL MUZ-GE09NA MUZ-GE12NA MUZ-GE15NA MUZ-GE18NA MUZ-GE24NA MUY-GE09NA MUY-GE12NA MUY-GE15NA MUY-GE18NA MUY-GE24NA OUTDOOR UNIT

SERVICE MANUAL MUZ-GE09NA MUZ-GE12NA MUZ-GE15NA MUZ-GE18NA MUZ-GE24NA MUY-GE09NA MUY-GE12NA MUY-GE15NA MUY-GE18NA MUY-GE24NA OUTDOOR UNIT SPLIT-TYPE AIR CONDITIONERS Revision B: Descriptions regarding the outdoor fan motor have been corrected. Please void OBH549 REVISED EDITION-A. OUTDOOR UNIT SERVICE MANUAL HFC utilized R410A. OBH549 REVISED

More information

SERVICE MANUAL. Room Air Conditioner Multi Split Wall-Mounted Type Indoor. FSAI-Pro-91AE2 FSAI-Pro-121AE2 FSAIF-Pro-181AE2

SERVICE MANUAL. Room Air Conditioner Multi Split Wall-Mounted Type Indoor. FSAI-Pro-91AE2 FSAI-Pro-121AE2 FSAIF-Pro-181AE2 SERVICE MANUAL Room Air Conditioner Multi Split Wall-Mounted Type Indoor FSAI-Pro-91AE2 FSAI-Pro-121AE2 FSAIF-Pro-181AE2 NOTE: Before servicing the unit, please read this at first. Always contact with

More information

New Deluxe Wall Mounted Heat Pump Series EXTERIOS

New Deluxe Wall Mounted Heat Pump Series EXTERIOS New Deluxe Wall Mounted Heat Pump Series EXTERIOS May 2013 New Deluxe Wall Mounted Heat Pump Series Panasonic Adding New Air Conditioner Lineup Setting Another Mile Stone in the US Ductless Split History

More information

DC INVERTER SPLIT SYSTEM AIR CONDITIONER

DC INVERTER SPLIT SYSTEM AIR CONDITIONER AIR CONDITIONER TECHNICAL & SERVICE MANUAL SAP-KRV93EH + SAP-CRV93EH SAP-KRV123EH + SAP-CRV123EH FILE NO. Destination: Europe DC INVERTER SPLIT SYSTEM AIR CONDITIONER Indoor Model No. Product Code No.

More information

LG Air Conditioning - Universal Split Fault Codes Sheet. Universal Split Systems

LG Air Conditioning - Universal Split Fault Codes Sheet. Universal Split Systems Universal Split Systems If there is a fault on any LG Universal unit, a two digit number will appear on the remote controllers led display. If the unit does not have a remote controller the fault will

More information

Air Conditioner Water Heater - A Product of HotSpot Energy LLC

Air Conditioner Water Heater - A Product of HotSpot Energy LLC Air Conditioner Water Heater - A Product of HotSpot Energy LLC PLEASE READ THIS BEFORE YOU INSTALL THE UNIT 1. This air conditioner must be installed and/or repaired by a qualified technician. If you perform

More information

SERVICE INSTRUCTION R410A. SPLIT TYPE ROOM AIR CONDITIONER Universal Floor / Ceiling Duct / Cassette Wall Mounted / Floor type INVERTER MULTI

SERVICE INSTRUCTION R410A. SPLIT TYPE ROOM AIR CONDITIONER Universal Floor / Ceiling Duct / Cassette Wall Mounted / Floor type INVERTER MULTI SERVICE INSTRUCTION SPLIT TYPE ROOM AIR CONDITIONER Universal Floor / Ceiling Duct / Cassette Wall Mounted / Floor type INVERTER MULTI R410A Models Indoor unit Outdoor unit AB*14LBAJ AB*18LBAJ AB*F14LAT

More information

SERVICE MANUAL MUZ-GE25VA - E1 MUZ-GE25VAH - E1 MUZ-GE35VA - E1 MUZ-GE35VAH - E1 MUZ-GE42VA - E1 MUZ-GE42VAH - E1 MUZ-GE50VA - E1 MUZ-GE50VAH - E1

SERVICE MANUAL MUZ-GE25VA - E1 MUZ-GE25VAH - E1 MUZ-GE35VA - E1 MUZ-GE35VAH - E1 MUZ-GE42VA - E1 MUZ-GE42VAH - E1 MUZ-GE50VA - E1 MUZ-GE50VAH - E1 SPLIT-TYPE AIR CONDITIONERS Revision A: MUZ-GE42/50VA(H) - E1 has been added. Please void OBH516. OUTDOOR UNIT SERVICE MANUAL HFC utilized R410A. OBH516 REVISED EDITION-A Models MUZ-GE25VA - E1 MUZ-GE25VAH

More information

SERVICE MANUAL MUZ-FE09NA MUZ-FE12NA MUZ-FE18NA OUTDOOR UNIT. No. OBH543 REVISED EDITION-A. Models HFC

SERVICE MANUAL MUZ-FE09NA MUZ-FE12NA MUZ-FE18NA OUTDOOR UNIT. No. OBH543 REVISED EDITION-A. Models HFC SPLIT-TYPE AIR CONDITIONERS Revision A: MUZ-FE18NA has been added. Please void OBH543. OUTDOOR UNIT SERVICE MANUAL HFC utilized R410A. OBH543 REVISED EDITION-A Models MUZ-FE09NA MUZ-FE12NA MUZ-FE18NA Indoor

More information

SERVICE MANUAL OUTDOOR UNIT MUZ-A09NA,- 1,- U1,- U2 MUZ-A12NA,- U1 MUZ-A15NA,- U1 MUZ-A17NA,- U1 MUY-A15NA MUY-A17NA MUY-A24NA,- 1,- U1,- U2

SERVICE MANUAL OUTDOOR UNIT MUZ-A09NA,- 1,- U1,- U2 MUZ-A12NA,- U1 MUZ-A15NA,- U1 MUZ-A17NA,- U1 MUY-A15NA MUY-A17NA MUY-A24NA,- 1,- U1,- U2 SPLIT-TYPE AIR CONDITIONERS Revision E: MUZ-GA24NA and MUY-GA24NA have been added. Please void OB451 REVISED EDITION-D. OUTDOOR UNIT SERVICE MANUAL HFC utilized R410A. OB451 REVISED EDITION-E Models MUZ-A09NA,-

More information

CU-2E15LBE CU-2E18LBE CU-3E18LBE CU-4E23LBE

CU-2E15LBE CU-2E18LBE CU-3E18LBE CU-4E23LBE Order No. PHAAM1003090C3 Outdoor Unit CU-2E15LBE CU-2E18LBE CU-3E18LBE CU-4E23LBE Air Conditioner Please file and use this manual together with the service manual for Model No. CS-E7LKEW CU-E7LKE CS-E7LKEW

More information

AIR CONDITIONER INSTALLATION MANUAL

AIR CONDITIONER INSTALLATION MANUAL INSTALLATION MANUAL AIR CONDITIONER Please read this installation manual completely before installing the product. Installation work must be performed in accordance with the national wiring standards by

More information

Technical service manual 2009

Technical service manual 2009 MULTI SPLIT TYPE, HEAT PUMP AIR CONDITIONERS Technical service manual 2009 KSIM MULTI ZONE SERIES R410A DC Inverter multi Series Models KSIM20912-H216 KSIM30912-H216 KSIM40912-H216 CONTENT 1. Product features

More information

SERVICE INSTRUCTION R410A. WALL MOUNTEDtype INVERTER SPLIT TYPE ROOM AIR CONDITIONER. Models Indoor unit Outdoor unit

SERVICE INSTRUCTION R410A. WALL MOUNTEDtype INVERTER SPLIT TYPE ROOM AIR CONDITIONER. Models Indoor unit Outdoor unit SERVICE INSTRUCTION SPLIT TYPE ROOM AIR CONDITIONER WALL MOUNTEDtype INVERTER Models Indoor unit Outdoor unit ASYG07LECA ASYG09LECA ASYG12LECA ASYG14LECA AOYG07LEC AOYG09LEC AOYG12LEC AOYG14LEC R410A CONTENTS

More information

york air-conditioning products Residential & VRF News 2015

york air-conditioning products Residential & VRF News 2015 york air-conditioning products Residential & VRF News 2015 york air-conditioning products Catalogue Content Split Systems Pag. High wall High Efficiency Inverter YWHJZH 09 to 24 K 6 High wall Inverter

More information

SERVICE INSTRUCTION R410A. WALL MOUNTEDtype SPLIT TYPE ROOM AIR CONDITIONER INVERTER. Models Indoor unit Outdoor unit AOU 9RLFW AOU12RLFW AOU15RLS

SERVICE INSTRUCTION R410A. WALL MOUNTEDtype SPLIT TYPE ROOM AIR CONDITIONER INVERTER. Models Indoor unit Outdoor unit AOU 9RLFW AOU12RLFW AOU15RLS SERVICE INSTRUCTION SPLIT TYPE ROOM AIR CONDITIONER WALL MOUNTEDtype INVERTER Models Indoor unit Outdoor unit ASU 9RLF ASURLF ASU5RLS AOU 9RLFW AOURLFW AOU5RLS R40A CONTENTS. DESCRIPTION OF EACH CONTROL

More information

SERVICE MANUAL FOR 6535 SERIES TWO TON HIGH EFFICIENCY PACKAGED HEAT PUMPS

SERVICE MANUAL FOR 6535 SERIES TWO TON HIGH EFFICIENCY PACKAGED HEAT PUMPS SERVICE MANUAL FOR 6535 SERIES TWO TON HIGH EFFICIENCY PACKAGED HEAT PUMPS TABLE OF CONTENTS 1. Warnings...2 2. Accessibility Of Appliance...3 3. Unit Dimensions And Specifications...3 4. Unit Specifications

More information

Air Conditioners. Technical Data. Wall Mounted Unit. www.daikin.eu RX-JV/GV

Air Conditioners. Technical Data. Wall Mounted Unit. www.daikin.eu RX-JV/GV Air Conditioners Technical Data Wall Mounted Unit www.daikin.eu RX-JV/GV Air Conditioners Technical Data Wall Mounted Unit www.daikin.eu RX-JV/GV TABLE OF CONTENTS RX-JV/GV 1 Features.............................................................

More information

Model: AC-S13CG x 2. Model No: AC-S13CGx2.doc Version 1.0

Model: AC-S13CG x 2. Model No: AC-S13CGx2.doc Version 1.0 Air Conditioner Service Manual 2 3 Model: AC-S13CG x 2 3 Content Technical specification.. 4 Performance curve.5 Outline & dimension of indoor unit..10 Outline & dimension of outdoor unit 11 Exploded view

More information

Failure code manual. content

Failure code manual. content Failure code manual content 一 wall split AC series 2 二 floor standing AC series. 4 三 portable AC series.. 5 四 dehumidifer 6 五 DC inverter single split series...7 六 DC inverter multi-split series 10 1 一

More information

Indoor coil is too warm in cooling mode or too cold in heating mode. Reversing valve or coil thermistor is faulty

Indoor coil is too warm in cooling mode or too cold in heating mode. Reversing valve or coil thermistor is faulty Codes Room Air Conditioner range: Indoor unit alarm s If timer lamp flashes for 1 second on, 1 second off, this indicates pre heating on the coil during heating mode and is not an error. If timer lamp

More information

MAC-120HE-01 Air-Cooled Chiller

MAC-120HE-01 Air-Cooled Chiller MAC-120HE-01 Air-Cooled Chiller 10 Ton / 120,000 BTUH Air-Cooled Chiller 208/230-1-50/60 1 HVAC Guide Specifications Air-Cooled Liquid Chiller Nominal Size: 10 Tons Multiaqua Model Number: MAC-120HE-01

More information

MULTI SPLIT SYSTEM AIR CONDITIONER

MULTI SPLIT SYSTEM AIR CONDITIONER TECHNICAL & SERVICE MANUAL AER534QC Dual System Kit :DKR8585C (Option) MULTI SPLIT SYSTEM AIR CONDITIONER Model No. Product Code No. AER534QC 387007146 Model No. Product Code No. DKR8585C 387025905 Outdoor

More information

Service Facts. WARNING: HAZARDOUS VOLTAGE - DISCONNECT POWER and DISCHARGE 4TTM3-SF-1. Split System Cooling 4TTM3018-4TTM3060

Service Facts. WARNING: HAZARDOUS VOLTAGE - DISCONNECT POWER and DISCHARGE 4TTM3-SF-1. Split System Cooling 4TTM3018-4TTM3060 4TTM3-SF-1 Service Facts Split System Cooling 4TTM3018-4TTM3060! CAUTION UNIT CONTAINS R-410A REFRIGERANT! R-410A OPERATING PRESSURE EXCEEDS THE LIMIT OF R-22. PROPER SERVICE EQUIPMENT IS REQUIRED. FAILURE

More information

CONTENTS 1. IMPORTANT NOTICE 2 2. TECHNICAL SPECIFICATION 3 3. OPERATION DETAILS 4 4. ELECTRICAL SCHEMATIC DIAGRAM 13 5. EXPLOSION VIEW 16 6

CONTENTS 1. IMPORTANT NOTICE 2 2. TECHNICAL SPECIFICATION 3 3. OPERATION DETAILS 4 4. ELECTRICAL SCHEMATIC DIAGRAM 13 5. EXPLOSION VIEW 16 6 TCL WALL MOUNTED SPLIT-TYPE AIR CONDITIONERS SERVICE MANUAL No.TE080528 Models KFTHP-12 KFTHP-18 KFTHP-24 CONTENTS 1. IMPORTANT NOTICE 2 2. TECHNICAL SPECIFICATION 3 3. OPERATION DETAILS 4 4. ELECTRICAL

More information

NewAir AC-10100E / AC-10100H Portable Air Conditioner Owner s Manual PLEASE READ AND SAVE THESE INSTRUCTIONS

NewAir AC-10100E / AC-10100H Portable Air Conditioner Owner s Manual PLEASE READ AND SAVE THESE INSTRUCTIONS NewAir AC-10100E / AC-10100H Portable Air Conditioner Owner s Manual PLEASE READ AND SAVE THESE INSTRUCTIONS ELECTRICAL SAFETY This appliance is for indoor use only. Always turn off the unit and unplug

More information

SERVICE MANUAL 12VDC WALL THERMOSTAT AIR CONDITIONING SYSTEMS ROOFTOP UNITS ONLY

SERVICE MANUAL 12VDC WALL THERMOSTAT AIR CONDITIONING SYSTEMS ROOFTOP UNITS ONLY SERVICE MANUAL 12VDC WALL THERMOSTAT AIR CONDITIONING SYSTEMS ROOFTOP UNITS ONLY! WARNING - SHOCK HAZARD! TO PREVENT THE POSSIBILITY OF SEVERE PERSONAL INJURY, DEATH, OR EQUIPMENT DAMAGE DUE TO ELECTRICAL

More information

SPLIT TYPE ROOM AIR CONDITIONER INSTALLATION INSTRUCTION SHEET

SPLIT TYPE ROOM AIR CONDITIONER INSTALLATION INSTRUCTION SHEET SPLIT TYPE ROOM AIR CONDITIONER INSTALLATION INSTRUCTION SHEET (PART NO. 97474700) For authorized service personnel only. This installation instruction sheet describes how to install the outdoor unit only.

More information

Dehumidifier Users manual. For Models: DH45S DH65S

Dehumidifier Users manual. For Models: DH45S DH65S Dehumidifier Users manual For Models: DH45S DH65S 950-0062-revD Jan. 9 2007 FORWARD The appearance of the units that you purchase might be slightly different from the ones described in the Manual, but

More information

REGULINE 600VA / 1000VA REGULATOR USER MANUAL

REGULINE 600VA / 1000VA REGULATOR USER MANUAL REGULINE 600VA / 1000VA REGULATOR USER MANUAL TUNÇMATİK REGULINE SERIES AUTOMATIC VOLTAGE REGULATOR Models: REGULINE 600VA / REGULINE 1000VA Principle of Operation Automatic Voltage Regulators regulate

More information

LG Air Conditioning Multi F(DX) Fault Codes Sheet. Multi Split Units

LG Air Conditioning Multi F(DX) Fault Codes Sheet. Multi Split Units Multi Split Units If there is a fault on any LG Multi unit, an Error mark is indicated on the display window of the indoor unit, wired-remote controller, and LED s of outdoor unit control board. A two

More information

CS-XE9EKE CU-XE9EKE CS-XE12EKE CU-XE12EKE

CS-XE9EKE CU-XE9EKE CS-XE12EKE CU-XE12EKE Order No. MAC0512111C8 Air Conditioner CS-XE9EKE CU-XE9EKE CS-XE12EKE CU-XE12EKE TABLE OF CONTENTS PAGE 1 Safety Precautions----------------------------------------------- 3 2 Specifications -----------------------------------------------------

More information

SECTION 15750 PACKAGED ROOFTOP AIR CONDITIONING UNITS

SECTION 15750 PACKAGED ROOFTOP AIR CONDITIONING UNITS SECTION 15750 PART 1 - GENERAL 1.01 DESCRIPTION A. Section includes requirements for roof mounted, self-contained units, with electric cooling, and electric or reverse refrigeration cycle (heat pump) heating

More information

CS-CE9NKE CS-CE12NKE CU-CE9NKE CU-CE12NKE TABLE OF CONTENTS WARNING

CS-CE9NKE CS-CE12NKE CU-CE9NKE CU-CE12NKE TABLE OF CONTENTS WARNING Order No: PAPAMY1207094CE Indoor Unit CS-CE9NKE CS-CE12NKE Outdoor Unit CU-CE9NKE CU-CE12NKE WARNING This service information is designed for experienced repair technicians only and is not designed for

More information

Use and Care Manual. Model CPA12KH AIR CONDITIONER

Use and Care Manual. Model CPA12KH AIR CONDITIONER Use and Care Manual Model CPA12KH AIR CONDITIONER Introduction Thank you for choosing this air conditioner to provide you and your family with all of the "Home Comfort" requirements for your home, cottage

More information

REFRIGERATED TYPE COMPRESSED AIR DRYERS INSTRUCTION MANUAL. For Sales & Service please contact:

REFRIGERATED TYPE COMPRESSED AIR DRYERS INSTRUCTION MANUAL. For Sales & Service please contact: 7610.478.16 8/99 INSTRUCTION MANUAL Models 8005, 8010, 8015 For Sales & Service please contact: CENTRAIR Air Systems & Supplies Phone: 705-722-5747 Fax: 705-722-5458 Email: sales@centrair.ca Website: www.centrair.ca

More information

SECTION 23 81 43 HEAT PUMPS

SECTION 23 81 43 HEAT PUMPS SECTION 23 81 43 HEAT PUMPS PART 1 GENERAL 1.1 SUMMARY A. Section Includes: 1. Packaged rooftop heat pumps. 1.2 REFERENCES A. American Society of Heating, Refrigerating and Air-Conditioning Engineers:

More information

Quest 105, Dry155, and 205 Dual

Quest 105, Dry155, and 205 Dual Quest 105, Dry155, and 205 Dual Read and Save These Instructions This manual is provided to acquaint you with the dehumidifier so that installation, operation and maintenance can proceed successfully.

More information

PANASONIC TROUBLE SHOOTING GUIDE

PANASONIC TROUBLE SHOOTING GUIDE A General Guide To Room Style Products Pipework Pipe sizes and lengths should be as the relevant Technical Guide Both lines should be insulated No line accessories or oil traps should be fitted In cooling

More information

Roof Top Air Conditioner INSTALLATION AND OPERATING INSTRUCTIONS

Roof Top Air Conditioner INSTALLATION AND OPERATING INSTRUCTIONS Roof Top Air Conditioner INSTALLATION AND OPERATING INSTRUCTIONS Ducted System RECORD THIS UNIT INFORMATION FOR FUTURE REFERENCE: Model Number: Serial Number: Date Purchased: This manual must be read and

More information

Oil and Coolant Circulating Heating System. Model - OCSM

Oil and Coolant Circulating Heating System. Model - OCSM Oil and Coolant Circulating Heating System Model - OCSM Installation & Operation Manual 216280-000 REV 2 Identifying Your System The HOTSTART heating system is designed to heat fluids for use in marine

More information

How To Measure Temperature On A Thermostat

How To Measure Temperature On A Thermostat Кондиционеры Mitsubishi Heavy Техническое руководство Кондиционеры настенного типа SRK20HD-S, SRK28HD-S, SRK40HD-S, SRK20CD-S, SRK28CD-S, SRK40CD-S CTENTS 1. GENERAL INFORMATI... 1 1.1 Specific features...

More information

NewAir AC-10000E, AC-10000H Portable Air Conditioner Owner s Manual PLEASE READ AND SAVE THESE INSTRUCTIONS

NewAir AC-10000E, AC-10000H Portable Air Conditioner Owner s Manual PLEASE READ AND SAVE THESE INSTRUCTIONS NewAir AC-10000E, AC-10000H Portable Air Conditioner Owner s Manual PLEASE READ AND SAVE THESE INSTRUCTIONS BEFORE USE GENERAL SAFETY INSTRUCTIONS: ALWAYS OPERATE THE UNIT IN AN UPRIGHT POSITION AND PLACE

More information

SWIMMING POOL HEAT PUMP

SWIMMING POOL HEAT PUMP SWIMMING POOL HEAT PUMP Installation & User Manual Model HP40B HP50B HP65B Hayward Pool Products Canada, Inc. T: 1-888-238-7665 www.haywardpool.ca CONTENT I. Application 4 II. Features 4 III. Technical

More information

Air Conditioning System

Air Conditioning System Owner s Information Manual Air Conditioning ystem NOTE TO EQUIPMENT OWNER: For your convenience, please record the model and serial numbers of your new equipment in the space provided. This information,

More information

Split Type Room Air Conditioner. KSWM units

Split Type Room Air Conditioner. KSWM units OWNER S MANUAL Split Type Room Air Conditioner KSWM units Please read the operating instructions and safety precautions carefully and thoroughly before installing and operating your room air conditioner.

More information

Air Conditioner 457915 B57915 459516 B59516 540315 540316 640312 640315

Air Conditioner 457915 B57915 459516 B59516 540315 540316 640312 640315 RECORD THIS INFORMATION FOR FUTURE REFERENCE: Number Serial Number ADB Number ADB Serial Number Date Purchased USA SERVICE OFFICE Dometic Corporation 2320 Industrial Parkway Elkhart, IN 46516 CANADA Dometic

More information

Technical service manual

Technical service manual GD Midea Refrigeration Equipment Co.,Ltd ODMI-A-1202 MULTI SPLIT TYPE, HEAT PUMP AIR CONDITIONERS Technical service manual R410A Multi DC inverter 220~240V-1Ph-50Hz Outdoor units Models M2OC-14HRDN1 M2OC-14HRDN1-Q

More information

Model. Roof-Top Air Conditioner CARAVAN MODEL B3200 TYPE 3253.331 INSTALLATION & OPERATING INSTRUCTIONS B3200

Model. Roof-Top Air Conditioner CARAVAN MODEL B3200 TYPE 3253.331 INSTALLATION & OPERATING INSTRUCTIONS B3200 RECORD THIS UNIT INFORMATION FOR FUTURE REFERENCE: Model Number Serial Number Date Purchased Roof-Top Air Conditioner CARAVAN MODEL B200 TYPE 25.1 SERVICE OFFICE Dometic Corporation For Information Contact:

More information

Portable Air Conditioner

Portable Air Conditioner Portable Air Conditioner Owner's Manual Model:3 in 1 12,000 Btu/h Series 3 Please read this owner s manual carefully before operation and retain it for future reference. CONTENTS 1. SUMMARY...1 2. PORTABLE

More information

CLOSE CONTROL SYSTEM. PFD series provide you with highly reliable computer room cooling system. High Reliability

CLOSE CONTROL SYSTEM. PFD series provide you with highly reliable computer room cooling system. High Reliability PFD-P250VM-E PUHY-P250YJM-A(-BS) PUHY-P500YSJM-A(-BS) PQHY-P250YHM-A CLOSE CONTROL SYSTEM MITSUBISHI ELECTRIC s Close Control System (PFD series) is specifically designed for computer rooms, laboratories

More information

13. Troubleshooting. Indoor unit s LED indication of Corona DC inverter unit. Indoor unit s LED indication of Alfa DC inverter unit

13. Troubleshooting. Indoor unit s LED indication of Corona DC inverter unit. Indoor unit s LED indication of Alfa DC inverter unit Troubleshooting 13. Troubleshooting Indoor unit s LED indication of Corona DC inverter unit MCAC-HTSM-2007-11 E0 E1 E2 E3 E5 E6 P0 P1 P2 P3 P5 EEPROM error outdoor communication error Zero-crossing examination

More information

OWNER'S MANUAL R-410A Duct Free Split System Air Conditioner and Heat Pump

OWNER'S MANUAL R-410A Duct Free Split System Air Conditioner and Heat Pump R-410A Duct Free Split System Air Conditioner and Heat Pump Product Family: DFS4(A/H)-System, DFC4(A/H)3-Outdoor, DFF4(A/H)H-Indoor Please read the operating instructions and safety precautions carefully

More information

ECOCIAT. Domestic hot water heat recovery unit

ECOCIAT. Domestic hot water heat recovery unit Heat recovery unit Domestic hot water High energy efficiency with R410A Compact and quiet Scroll compressors Brazed-plate heat exchangers Heating Heat recovery ENVIRONMENTALLY HFC R410A PROTECTION DE FRIENDLY

More information

AIR CONDITIONER OUTDOOR UNIT

AIR CONDITIONER OUTDOOR UNIT AIR CONDITIONER OUTDOOR UNIT INSTALLATION MANUAL For authorized personnel only. MANUEL D'INSTALLATION Pour le personnel agréé uniquement. English Français MANUAL DE INSTALACIÓN Solo para personal autorizado.

More information

M SERIES REFRIGERANT COIL MODULE REFRIGERANT COILS for R-22, R-407C, R-410A

M SERIES REFRIGERANT COIL MODULE REFRIGERANT COILS for R-22, R-407C, R-410A Bulletin 20-20.2 / July 2012 M SERIES REFRIGERANT COIL MODULE REFRIGERANT COILS for R-22, R-407C, R-410A ➀ ➁ ➂ Model Number Key M 2430 C L 1 - A - ➀ Unit Type M=Modular Nominal Capacity 2430=24000 to 30000

More information

SERVICE MANUAL. Domestic Air Conditioner. Model. Feature HW-05LN03

SERVICE MANUAL. Domestic Air Conditioner. Model. Feature HW-05LN03 Domestic Air Conditioner SERVICE MANUAL Model HW-05LN03 Feature Anti-mold filter Mechanical control Easy clean filters Slide chassis 4-way airflow direction 2 cool settings, 2 fan settings Serial Number:

More information

CONTENTS 1. IMPORTANT NOTICE 2 2. TECHNICAL SPECIFICATION 3 3. OPERATION DETAILS 4 4. WIRING DIAGRAM 11 5. EXPLOSION VIEW 12 6.

CONTENTS 1. IMPORTANT NOTICE 2 2. TECHNICAL SPECIFICATION 3 3. OPERATION DETAILS 4 4. WIRING DIAGRAM 11 5. EXPLOSION VIEW 12 6. TCL WALL MOUNTED SPLIT-TYPE AIR CONDITIONERS SERVICE MANUAL No.TE051220 Models TAC-09CHSA/GI TAC-12CHSA/GI CONTENTS 1. IMPORTANT NOTICE 2 2. TECHNICAL SPECIFICATION 3 3. OPERATION DETAILS 4 4. WIRING DIAGRAM

More information

Air Conditioning & Heat Pump Products

Air Conditioning & Heat Pump Products Air Conditioning & Heat Pump Products Preliminary Revised April 06 SANYO Air Conditioners & Heat Pumps Btu/h 9,000 12,000 18,000 24,000 26,000 30,000 36,000 42,000 Type Standard Low Ambient Standard Low

More information

AquaFREE System. Technical Catalogue. Outdoor units: RAS-(3~5)HVRNE RAS-(4/5)HRNE. Indoor units: RWM-(3~5)FSN1E RWM-(3~5)FSN1E-(4.

AquaFREE System. Technical Catalogue. Outdoor units: RAS-(3~5)HVRNE RAS-(4/5)HRNE. Indoor units: RWM-(3~5)FSN1E RWM-(3~5)FSN1E-(4. AquaFREE System Technical Catalogue Outdoor units: RAS-(3~5)HVRNE RAS-(4/5)HRNE Indoor units: RWM-(3~5)FSN1E RWM-(3~5)FSN1E-(4.5/6)H(1/3) Specifications in this manual are subject to change without notice

More information

LOBOY 16 AIR CONDITIONERS

LOBOY 16 AIR CONDITIONERS INSTRUCTION MANUAL FOR: LOBOY 16 AIR CONDITIONERS McLean Midwest Corp. dba: McLean Cooling Technology 11611 Business Park Blvd. N Champlin, MN 55316 Tel: 763-323-8200 Fax: 763-576-3200 www.mcleancoolingtech.com

More information

R22. K Control. Indoor Unit. Nomenclature. Compatibility PL H 3 G K H B. Unit style Heat Pump Horse Power

R22. K Control. Indoor Unit. Nomenclature. Compatibility PL H 3 G K H B. Unit style Heat Pump Horse Power R22. K Control. Indoor Unit. Nomenclature. PL H 3 G K H B Compatibility Unit style Heat Pump Horse Power Control Boost Heaters R22. K Control. Outdoor Unit. Nomenclature. PU H 3 Y K A Compatibility Outdoor

More information

TYPE. MODEL B3200 Roof-Top Air Conditioner used with Mechanical Air Distribution Box INSTALLATION & OPERATING INSTRUCTIONS. 3253.332 Air Conditioner

TYPE. MODEL B3200 Roof-Top Air Conditioner used with Mechanical Air Distribution Box INSTALLATION & OPERATING INSTRUCTIONS. 3253.332 Air Conditioner Type 5. Installation and Operating Instructions RECORD THIS UNIT INFORMATION FOR FUTURE REFERENCE: Model Number Serial Number Date Purchased MODEL B00 Roof-Top Air Conditioner used with Mechanical Air

More information

OWNER S MANUAL VMH 09/12/18/27/36 InverterFlex

OWNER S MANUAL VMH 09/12/18/27/36 InverterFlex OWNER S MANUAL VMH 09/12/18/27/36 InverterFlex Version C Single, Dual, Tri or Quad Zone Ductless Mini-Split System Heat Controller, Inc. 1900 Wellworth Ave. Jackson, MI 49203 (517)787-2100 www.heatcontroller.com

More information

Heat Pump Water Heater IOM Manual

Heat Pump Water Heater IOM Manual Heat Pump Water Heater IOM Manual Installation Operation & Maintenance This manual is intended as an aid to qualified service personnel for proper installation, operation and maintenance of the heat pump

More information

www.inspection-for-industry.com

www.inspection-for-industry.com Quality Control Form (TEST RUNNING RECORD FOR AIR HANDLING UNIT) SUB POWER SUPPLY: MAIN POWER V, Hz, CONTROL V, Blower 1 kw, Blower 2 kw, Compressor: (1) kw (2) kw (3) kw (4) kw Heating Element: kw 1.

More information

E2 Series Electric Furnaces

E2 Series Electric Furnaces E2 Series Electric Furnaces Service Manual Table of Contents Electrical Requirements... 10 Codes, Specifications Requirements... 10 Connection Supply Service Wires... 10 Furnace Sequence of Operation...

More information

Versati Air to Water Heat Pump

Versati Air to Water Heat Pump Versati Air to Water Heat Pump VERSATI DC Inverter Multifunctional Air To Water Heat Pump Nowadays, people are increasingly focusing on heating costs as well as environmental issues. Traditional heating

More information

SWIMMING POOL HEAT PUMP Owners Manual

SWIMMING POOL HEAT PUMP Owners Manual SWIMMING POOL HEAT PUMP Owners Manual This manual refers to the 17.0kw and 21.0kw models only. The heat pump unit is sold with a 1 year warranty. In addition there is a 2 year parts warranty on the compressor

More information

Portable Air Conditioner. OWNER S MANUAL Read these instructions before use. Model: MF08CESWW. Voltage rating: 115V~60Hz Power rating : 800W

Portable Air Conditioner. OWNER S MANUAL Read these instructions before use. Model: MF08CESWW. Voltage rating: 115V~60Hz Power rating : 800W MODE ALARM Portable Air Conditioner OWNER S MANUAL Read these instructions before use 8 Model: MF08CESWW Voltage rating: 115V~60Hz Power rating : 800W Customer Support : 1-800-474-2147 For product inquiries

More information

Portable Air Conditioner. OWNER S MANUAL Read these instructions before use. Model: MM14CHCSCS

Portable Air Conditioner. OWNER S MANUAL Read these instructions before use. Model: MM14CHCSCS Portable Air Conditioner OWNER S MANUAL Read these instructions before use Model: MM14CHCSCS Voltage rating: 120V~60Hz Power rating : 1400W(Cooling) Power rating : 1350W(Heating) Customer Support : 1-800-474-21477

More information

ModPac II 1 to 5-Ton Vertical Wall Mount Air Conditioners Models AVPA12-20-24-30-36-42-48-60

ModPac II 1 to 5-Ton Vertical Wall Mount Air Conditioners Models AVPA12-20-24-30-36-42-48-60 ModPac II 1 to 5-Ton Vertical Wall Mount Air Conditioners Models AVPA12-20-24-30-36-42-48-60 General Description The Marvair ModPac II air conditioner is a vertical, wall mounted, cost effective air conditioner

More information

Heating, Ventilation, Air Conditioning and Refrigeration (HVACR)

Heating, Ventilation, Air Conditioning and Refrigeration (HVACR) Heating, Ventilation, Air Conditioning and Refrigeration (HVACR) I. Demonstrate safety skills in typical HVACR work situations to NATE Core Installer Knowledge Areas for Technician Excellence for Safety

More information