1 Interested in conducting your own webinar?
2 Improving Efficiencies by Integrating Data Center Systems August 30 th, 2012
3 Audio Abstract Presenter Info Slides Handouts Group Chat Q & A Live Twitter Feed Help Survey Archive Add to your favorites
4 Improving Efficiencies by Integrating Data Center Systems August 30 th, 2012
5 Architectural Effects on Efficiencies Raised floor and room air tightness Humidity control vapor barrier Ceilings as return air plenums Raised floor as supply air plenums Containment coordination, tightness Large areas required to reduce static pressure and accommodate ducts and louvers
6
7 Controls Pressurization Contamination Smoke, Pollen, Diesel Temperature reset on cooling equipment to control Humidity. Select controls based on type of air management
8 Electrical High voltage distribution 208, 230, 277V High efficiency equipment (or Eco mode UPS) Take heat producing equipment out of computer room Let Electrical and UPS rooms operate at higher temperatures Lighting control
9 Mechanical Raise Computer room temperatures to ASHRAE recommendations/allowable limits Increase allowable humidity levels consider cost to add humidity Raise chilled water temperatures Use VSD pumps and fans to reduce power Use redundant equipment to increase efficiencies
10 Mechanical High efficiency economizer systems Air Water Refrigerant Adiabatic cooling systems Right size cooling system operation ASHRAE code requirements Typical DX type units may not meet minimum efficiencies
11 Mechanical PUE varies by system and geography Fan power is a big influence
12 Key Factors for PUE System Location Operating Conditions
13 P U E Hi gh Lo w
14 Mechanical Hot/Cold aisle containment systems Similar operational costs Different control strategies How to keep hot and cold air separated Doors at end of aisles Barriers from cabinets to ceiling Duct from cabinet to ceiling Consider temperature in room OSHA limits on heat exposure
15
16 OSHA Technical Manual SECTION III: CHAPTER 4 HEAT STRESS TABLE III:4-2. PERMISSIBLE HEAT EXPOSURE THRESHOLD LIMIT VALUE Work Load* Work/rest regimen Light Moderate Heavy Continuous work 30.0 C (86 F) 26.7 C (80 F) 25.0 C (77 F) 75% Work, 25% rest, each hour 30.6 C (87 F) 28.0 C (82 F) 25.9 C (78 F) 50% Work, 50% rest, each hour 31.4 C (89 F) 29.4 C (85 F) 27.9 C (82 F) 25% Work, 75% rest, each hour 32.2 C (90 F) 31.1 C (88 F) 30.0 C (86 F) *Values are in C and F, WBGT. These TLV's are based on the assumption that nearly all acclimatized, fully clothed workers with adequate water and salt intake should be able to function effectively under the given working conditions without exceeding a deep body temperature of 38 C (100.4 F). They are also based on the assumption that the WBGT of the resting place is the same or very close to that of the workplace. Where the WBGT of the work area is different from that of the rest area, a time-weighted average should be used (consult the ACGIH Threshold Limit Values for Chemical Substances and Physical Agents and Biological Exposure Indices (1992). These TLV's apply to physically fit and acclimatized individuals wearing light summer clothing. If heavier clothing that impedes sweat or has a higher insulation value is required, the permissible heat exposure TLV's in Table III:4-2 must be reduced by the corrections shown in Table III:4-3. Average Web Bulb Globe Temperature (WBGT) For indoor and outdoor conditions with no solar load, WBGT is calculated as: WBGT = 0.7NWB + 0.3GT WBGT = Wet Bulb Globe Temperature Index NWB = Nature Wet-Bulb Temperature DB = Dry-Bulb Temperature GT = Globe Temperature
17 Monitoring and Modeling for the Future M+W U.S., Inc. A Company of the M+W Group August 30, 2012
18 Datacenter Infrastructure Management (DCIM) DCeP - Datacenter Energy Productivity Datacenter Predictive Modeling (DCPM) Information Technology Infrastructure Management (ITIM) Building Management Systems (BMS) Network Management Systems (NMS) The ability to manage, monitor, control and forecast the performance of a data center now and into the future 18 M+W U.S., Inc. Corporate Overview
19 19 M+W U.S., Inc. Corporate Overview
20 Integrating the facilities into a large homogeneous network is the driving force in today s environments. 20 M+W U.S., Inc. Corporate Overview
21 Distributed Controller EPMS BMS Security EPMS BMS Asset Management Facility Planning Change Management 21 M+W U.S., Inc. Corporate Overview
22 DCPM Tools: CFD Modeling EPMS Systems BMS Systems LSS Systems Carbon Footprint Assessment Network Management Systems Capacity Planning Tools 22 M+W U.S., Inc. Corporate Overview
23 Goals for opendcim The number one goal for opendcim is to eliminate the excuse for anybody to ever track their data center inventory using a spreadsheet or word processing document again. We've all been there in the past, which is what drove us developers to create this project. Provide complete physical inventory (asset tracking) of the data center Support for Multiple Rooms (Data Centers) Management of the three key elements of capacity management - space, power, and cooling Basic contact management and integration into existing business directory via UserID Fault Tolerance Tracking - run a power outage simulation to see what would be affected as each source goes down Computation of Center of Gravity for each cabinet Template management for devices, with ability to override per device Optional tracking of cable connections within each cabinet, and for each switch device Archival functions for equipment sent to salvage/disposal Integration with intelligent power strips and UPS devices - APC, Geist Manufacturing, Liebert, and Server Technologies. Easy to update with OIDs for other manufacturers Open Architecture - All built on a MySQL database for easy report building, or export to other applications 23 M+W U.S., Inc. Corporate Overview
24 Server Room Environmental Monitoring: Temperature IT equipment Ambient Outside Humidity Airflow / Pressurization Air Quality (Internal and external) Smoke Water Leakage Energy Flow / Power Failure / Usage Security 24 M+W U.S., Inc. Corporate Overview
25 Top 10 Questions being asked of datacenter managers: 1. Are we effectively measuring power utilization in our data center(s) today? 2. What's our overall efficiency rating (PUE, DCIE, and CADE), and how does that compare to the industry norm? 3. Are we able to accurately determine which equipment is being utilized the least and/or is the least efficient? 4. Can we determine energy consumption by application, transaction, or department, and does it make sense to allocate those costs accordingly? 5. How much is this year's technology refresh cycle expected to improve overall data center efficiency and capacity? 6. What gains did we realize (or do we expect to realize) from consolidation and virtualization of server and storage resources? 7. Can we optimize those gains with "what-if" analyses of all available options or through other measures? 8. Where are we most likely to experience a serious limitation, and are we at risk of having a data center exceed its available capacity? 9. How can we minimize energy consumption (and costs) in our data center(s)? 10. What will be the return on investment for improving overall efficiency in our data center(s)? 25 M+W U.S., Inc. Corporate Overview
26 Demands and Constraints placed upon Datacenter Operators 26 M+W U.S., Inc. Corporate Overview
27 Benchmarking: Power Utilization Effectiveness (PUE) Green Grid Data Center Infrastructure Efficiency (DCiE) Green Grid Water Usage Effectiveness (WUE) Green Grid Carbon Usage Effectiveness (CUE) Green Grid Corporate Average Data Center Efficiency (CADE) Dynamic Power Optimization (DPO) Data Center Fixed to Variable Energy Ratio Matrix (DC-FVER) IT Metrics - SPECPower IT Metrics - Energy Star Datacenter Power Performance per Energy (DPPE) GreenIT Carbon Reduction Commitment (CRC) 27 M+W U.S., Inc. Corporate Overview
28 28 M+W U.S., Inc. Corporate Overview
29 29 M+W U.S., Inc. Corporate Overview
30 Losses in the electrical system occur at every form of transformation and over the distance in cabling VAC distribution and Electrical Power Monitoring Systems (EPMS) are designed to monitor and minimize losses where ever possible. 30 M+W U.S., Inc. Corporate Overview
31 In the recent past, the datacenter industry has responded favorably to cries from environmentalist to search for ways to improve their efficiencies. The benchmarks created have allowed the industry to better understand the waste that was generated by over designed and poorly managed datacenters. These same benchmarks are now being used to better understand the actual infrastructure required to better support the business need. 31 M+W U.S., Inc. Corporate Overview
32 With the use a well developed set of DCIM tools, the datacenter manager will be able to commission the facility to function as designed and then recheck that facility yearly to be sure the operating parameters do not deviate from the optimal criteria developed for the facility It s critical to be sure that when the facility is measured yearly that the facilities baseline never changes. 32 M+W U.S., Inc. Corporate Overview
33 33 M+W U.S., Inc. Corporate Overview
34 This Matrix shows that strong DCPM Tools enable the datacenter owner to better plan for capital expenditures rather than basing decisions on the DCiE benchmark. Tools allow the owner a glimps of how his facility will operate under the new conditions before implementing the change. 34 M+W U.S., Inc. Corporate Overview
35 35 M+W U.S., Inc. Corporate Overview
36 36 M+W U.S., Inc. Corporate Overview
37 The approach in building a modern Datacenter Match to Business Demands Be cognizant of the total costs of the facility Understand the effective and economic lifetime of the building systems Monolithic Tier X Datacenter s are out Modular split Tier built in modular fashion are in With the rising costs of energy and increasing pressure on organizations to be more "green," implementing a DCIM and/or DPO solution is inevitable. Monitor, control and benchmark 37 M+W U.S., Inc. Corporate Overview
38 Type your question in the box and hit submit
39
Excool Indirect Adiabatic and Evaporative Data Centre Cooling. World s Leading Indirect Adiabatic and Evaporative Data Centre Cooling
Excool Indirect Adiabatic and Evaporative Data Centre Cooling World s Leading Indirect Adiabatic and Evaporative Data Centre Cooling Indirect Adiabatic and Evaporative Data Centre Cooling Solutions by
More informationDealing with Thermal Issues in Data Center Universal Aisle Containment
Dealing with Thermal Issues in Data Center Universal Aisle Containment Daniele Tordin BICSI RCDD Technical System Engineer - Panduit Europe Daniele.Tordin@Panduit.com AGENDA Business Drivers Challenges
More informationEnergy Efficiency and Availability Management in Consolidated Data Centers
Energy Efficiency and Availability Management in Consolidated Data Centers Abstract The Federal Data Center Consolidation Initiative (FDCCI) was driven by the recognition that growth in the number of Federal
More informationManaging Power Usage with Energy Efficiency Metrics: The Available Me...
1 of 5 9/1/2011 1:19 PM AUG 2011 Managing Power Usage with Energy Efficiency Metrics: The Available Metrics and How to Use Them Rate this item (1 Vote) font size Data centers consume an enormous amount
More informationHeat Recovery from Data Centres Conference Designing Energy Efficient Data Centres
What factors determine the energy efficiency of a data centre? Where is the energy used? Local Climate Data Hall Temperatures Chiller / DX Energy Condenser / Dry Cooler / Cooling Tower Energy Pump Energy
More informationGuideline for Water and Energy Considerations During Federal Data Center Consolidations
Guideline for Water and Energy Considerations During Federal Data Center Consolidations Prepared for the U.S. Department of Energy Federal Energy Management Program By Lawrence Berkeley National Laboratory
More informationEngineers Ireland Cost of Data Centre Operation/Ownership. 14 th March, 2013 Robert Bath Digital Realty
Engineers Ireland Cost of Data Centre Operation/Ownership 14 th March, 2013 Robert Bath Digital Realty Total Cost of Operation (TCO) Rental TCO - 10 Year Lease Term Power Cooling Connectivity Costs 26%
More informationData Center Infrastructure Management: ERP for the Data Center Manager
Data Center Infrastructure Management: ERP for the Data Center Manager 1 2 Topics What s DCIM & the ERP Analogy Why DCIM How DCIM Works How DCIM Helps 3 DCIM by Definition DCIM is a system that collects
More informationData Center Technology: Physical Infrastructure
Data Center Technology: Physical Infrastructure IT Trends Affecting New Technologies and Energy Efficiency Imperatives in the Data Center Hisham Elzahhar Regional Enterprise & System Manager, Schneider
More informationManaging Data Centre Heat Issues
Managing Data Centre Heat Issues Victor Banuelos Field Applications Engineer Chatsworth Products, Inc. 2010 Managing Data Centre Heat Issues Thermal trends in the data centre Hot Aisle / Cold Aisle design
More informationProtecting Yourself from. Heat Stress
Fast Facts Heat stress, from exertion or hot environments, places workers at risk for illnesses such as heat stroke, heat exhaustion, or heat cramps. Heat Stroke A condition that occurs when the body becomes
More informationDataCenter 2020: first results for energy-optimization at existing data centers
DataCenter : first results for energy-optimization at existing data centers July Powered by WHITE PAPER: DataCenter DataCenter : first results for energy-optimization at existing data centers Introduction
More informationSpecialty Environment Design Mission Critical Facilities
Brian M. Medina PE Associate Brett M. Griffin PE, LEED AP Vice President Environmental Systems Design, Inc. Mission Critical Facilities Specialty Environment Design Mission Critical Facilities March 25,
More informationGreen Data Centre Design
Green Data Centre Design A Holistic Approach Stantec Consulting Ltd. Aleks Milojkovic, P.Eng., RCDD, LEED AP Tommy Chiu, EIT, RCDD, LEED AP STANDARDS ENERGY EQUIPMENT MATERIALS EXAMPLES CONCLUSION STANDARDS
More informationAIRAH Presentation April 30 th 2014
Data Centre Cooling Strategies The Changing Landscape.. AIRAH Presentation April 30 th 2014 More Connections. More Devices. High Expectations 2 State of the Data Center, Emerson Network Power Redefining
More informationData Center Facility Basics
Data Center Facility Basics Ofer Lior, Spring 2015 Challenges in Modern Data Centers Management, Spring 2015 1 Information provided in these slides is for educational purposes only Challenges in Modern
More information7 Best Practices for Increasing Efficiency, Availability and Capacity. XXXX XXXXXXXX Liebert North America
7 Best Practices for Increasing Efficiency, Availability and Capacity XXXX XXXXXXXX Liebert North America Emerson Network Power: The global leader in enabling Business-Critical Continuity Automatic Transfer
More informationMeasuring Power in your Data Center: The Roadmap to your PUE and Carbon Footprint
Measuring Power in your Data Center: The Roadmap to your PUE and Carbon Footprint Energy usage in the data center Electricity Transformer/ UPS Air 10% Movement 12% Cooling 25% Lighting, etc. 3% IT Equipment
More informationAnalysis of data centre cooling energy efficiency
Analysis of data centre cooling energy efficiency An analysis of the distribution of energy overheads in the data centre and the relationship between economiser hours and chiller efficiency Liam Newcombe
More informationEnergy Efficiency Best Practice Guide Data Centre and IT Facilities
2 Energy Efficiency Best Practice Guide Data Centre and IT Facilities Best Practice Guide Pumping Systems Contents Medium-sized data centres energy efficiency 3 1 Introduction 4 2 The business benefits
More informationChallenges In Intelligent Management Of Power And Cooling Towards Sustainable Data Centre
Challenges In Intelligent Management Of Power And Cooling Towards Sustainable Data Centre S. Luong 1*, K. Liu 2, James Robey 3 1 Technologies for Sustainable Built Environments, University of Reading,
More informationSpeaker: John Peterson Time: April 4, 2014, 9:45-10:45 a.m. Venue: Crystal 1-2. Data Center Design and Commissioning
Speaker: John Peterson Time: April 4, 2014, 9:45-10:45 a.m. Venue: Crystal 1-2 Data Center Design and Commissioning High enterprise relevancy for addressing space, power, and cooling, as well as costs
More informationDATA CENTER ASSESSMENT SERVICES
DATA CENTER ASSESSMENT SERVICES ig2 Group Inc. is a Data Center Science Company which provides solutions that can help organizations automatically optimize their Data Center performance, from assets to
More informationDataCenter 2020: hot aisle and cold aisle containment efficiencies reveal no significant differences
DataCenter 2020: hot aisle and cold aisle containment efficiencies reveal no significant differences November 2011 Powered by DataCenter 2020: hot aisle and cold aisle containment efficiencies reveal no
More informationData Centre Energy Efficiency Operating for Optimisation Robert M Pe / Sept. 20, 2012 National Energy Efficiency Conference Singapore
Data Centre Energy Efficiency Operating for Optimisation Robert M Pe / Sept. 20, 2012 National Energy Efficiency Conference Singapore Introduction Agenda Introduction Overview of Data Centres DC Operational
More informationData Centers: How Does It Affect My Building s Energy Use and What Can I Do?
Data Centers: How Does It Affect My Building s Energy Use and What Can I Do? 1 Thank you for attending today s session! Please let us know your name and/or location when you sign in We ask everyone to
More informationBenefits of. Air Flow Management. Data Center
Benefits of Passive Air Flow Management in the Data Center Learning Objectives At the end of this program, participants will be able to: Readily identify if opportunities i where networking equipment
More informationHow Does Your Data Center Measure Up? Energy Efficiency Metrics and Benchmarks for Data Center Infrastructure Systems
How Does Your Data Center Measure Up? Energy Efficiency Metrics and Benchmarks for Data Center Infrastructure Systems Paul Mathew, Ph.D., Staff Scientist Steve Greenberg, P.E., Energy Management Engineer
More informationData Center Design Guide featuring Water-Side Economizer Solutions. with Dynamic Economizer Cooling
Data Center Design Guide featuring Water-Side Economizer Solutions with Dynamic Economizer Cooling Presenter: Jason Koo, P.Eng Sr. Field Applications Engineer STULZ Air Technology Systems jkoo@stulz ats.com
More informationOptimum Climate Control For Datacenter - Case Study. T. Prabu March 17 th 2009
Optimum Climate Control For Datacenter - Case Study T. Prabu March 17 th 2009 Agenda 2 About EDEC (Emerson) Facility Data Center Details Design Considerations & Challenges Layout Design CFD Analysis Of
More informationOptimizing Network Performance through PASSIVE AIR FLOW MANAGEMENT IN THE DATA CENTER
Optimizing Network Performance through PASSIVE AIR FLOW MANAGEMENT IN THE DATA CENTER Lylette Macdonald, RCDD Legrand Ortronics BICSI Baltimore 2011 Agenda: Discuss passive thermal management at the Rack
More informationData Centre Cooling Technologies. Jon Pettitt, EMEA DataCenter Business Development Manager
Data Centre Cooling Technologies 1 Jon Pettitt, EMEA DataCenter Business Development Manager Munters Group Key facts 3.000 Employees 30 Countries Turnover of 470 M HQ in Sweden Global DC Support 25+ Data
More informationAIA Provider: Colorado Green Building Guild Provider Number: 50111120. Speaker: Geoff Overland
AIA Provider: Colorado Green Building Guild Provider Number: 50111120 Office Efficiency: Get Plugged In AIA Course Number: EW10.15.14 Speaker: Geoff Overland Credit(s) earned on completion of this course
More informationImplement Data Center Energy Saving Management with Green Data Center Environment and Energy Performance Indicators
Implement Data Center Energy Saving Management with Green Data Center Environment and Energy Performance Indicators Awareness of environmental protection issues, has many industry types focusing and pursuing
More informationCURBING THE COST OF DATA CENTER COOLING. Charles B. Kensky, PE, LEED AP BD+C, CEA Executive Vice President Bala Consulting Engineers
CURBING THE COST OF DATA CENTER COOLING Charles B. Kensky, PE, LEED AP BD+C, CEA Executive Vice President Bala Consulting Engineers OVERVIEW Compare Cooling Strategies in Free- Standing and In-Building
More informationSolution Overview. Dan Lucas - Director of Sales Western Region Kirk Roderick - Principal SE. v1.5
Solution Overview Dan Lucas - Director of Sales Western Region Kirk Roderick - Principal SE v1.5 Agenda Introductions Rackwise & Our Customers Market News DCIM Growing Product & Technology Overview Intel
More informationEnvironmental Data Center Management and Monitoring
2013 Raritan Inc. Table of Contents Introduction Page 3 Sensor Design Considerations Page 3 Temperature and Humidity Sensors Page 4 Airflow Sensor Page 6 Differential Air Pressure Sensor Page 6 Water Sensor
More informationCooling Capacity Factor (CCF) Reveals Stranded Capacity and Data Center Cost Savings
WHITE PAPER Cooling Capacity Factor (CCF) Reveals Stranded Capacity and Data Center Cost Savings By Lars Strong, P.E., Upsite Technologies, Inc. Kenneth G. Brill, Upsite Technologies, Inc. 505.798.0200
More informationIMPROVING DATA CENTER EFFICIENCY AND CAPACITY WITH AISLE CONTAINMENT
DATA CENTER RESOURCES WHITE PAPER IMPROVING DATA CENTER EFFICIENCY AND CAPACITY WITH AISLE CONTAINMENT BY: STEVE HAMBRUCH EXECUTIVE SUMMARY Data centers have experienced explosive growth in the last decade.
More informationOffice of the Government Chief Information Officer. Green Data Centre Practices
Office of the Government Chief Information Officer Green Data Centre Practices Version : 2.0 April 2013 The Government of the Hong Kong Special Administrative Region The contents of this document remain
More informationThis 5 days training Course focuses on Best Practice Data Centre Design, Operation and Management leading to BICSI credits.
This 5 days training Course focuses on Best Practice Data Centre Design, Operation and Management leading to BICSI credits. DCD, DCOM, DCE DESIGN IMPLEMENTATION BEST PRACTICE OPERATION & MANAGEMENT DATA
More informationWhite Paper. Data Center Containment Cooling Strategies. Abstract WHITE PAPER EC9001. Geist Updated August 2010
White Paper Data Center Containment Cooling Strategies WHITE PAPER EC9001 Geist Updated August 2010 Abstract Deployment of high density IT equipment into data center infrastructure is now a common occurrence
More informationHow High Temperature Data Centers & Intel Technologies save Energy, Money, Water and Greenhouse Gas Emissions
Intel Intelligent Power Management Intel How High Temperature Data Centers & Intel Technologies save Energy, Money, Water and Greenhouse Gas Emissions Power and cooling savings through the use of Intel
More informationDatacenter Infrastructure Management (DCIM) Solution
Datacenter Infrastructure Management (DCIM) Solution Figure 1. Asset Management in 3D, Real-Time Reporting, CFD Modeling & Analysis Description Datacenter Clarity provides the tools to accurately and efficiently
More informationCarbonDecisions. The green data centre. Why becoming a green data centre makes good business sense
CarbonDecisions The green data centre Why becoming a green data centre makes good business sense Contents What is a green data centre? Why being a green data centre makes good business sense 5 steps to
More informationBuilding a data center. C R Srinivasan Tata Communications
Building a data center C R Srinivasan Tata Communications Introduction Data Center as defined by TIA 942 A building or a portion of a building whose primary function is to house a computer room and its
More informationData Center Cooling & Air Flow Management. Arnold Murphy, CDCEP, CDCAP March 3, 2015
Data Center Cooling & Air Flow Management Arnold Murphy, CDCEP, CDCAP March 3, 2015 Strategic Clean Technology Inc Focus on improving cooling and air flow management to achieve energy cost savings and
More informationServer room guide helps energy managers reduce server consumption
Server room guide helps energy managers reduce server consumption Jan Viegand Viegand Maagøe Nr. Farimagsgade 37 1364 Copenhagen K Denmark jv@viegandmaagoe.dk Keywords servers, guidelines, server rooms,
More informationRe Engineering to a "Green" Data Center, with Measurable ROI
Re Engineering to a "Green" Data Center, with Measurable ROI Alan Mamane CEO and Founder Agenda Data Center Energy Trends Benchmarking Efficiency Systematic Approach to Improve Energy Efficiency Best Practices
More informationIndirect Evaporative Cooling (IDEC) Unit for Data Centers
Indirect Evaporative Cooling (IDEC) Unit for Data Centers NORTEK AIR SOLUTIONS Cool3 IDEC UNIT INDIRECT EVAPORATIVE COOLING The new Nortek Air Solutions Cool 3 IDEC unit is a proven approach for highly
More informationThe Efficient Enterprise. Juan Carlos Londoño Data Center Projects Engineer APC by Schneider Electric
Ee The Efficient Enterprise Juan Carlos Londoño Data Center Projects Engineer APC by Schneider Electric Keystrokes Kilowatts Heat OUT Electricity IN Need for bandwidth exploding Going hyperbolic! 30,000
More informationData Center Lifecycle and Energy Efficiency
Data Center Lifecycle and Energy Efficiency Lifecycle infrastructure management, power management, thermal management, and simulation solutions enable data center modernization. White Paper October 2014
More informationSelecting Rack-Mount Power Distribution Units For High-Efficiency Data Centers
C P I P O W E R M A N A G E M E N T WHITE PAPER Selecting Rack-Mount Power Distribution Units For High-Efficiency Data Centers By Anderson Hungria Sr. Product Manager of Power, Electronics & Software Published
More informationImpact of Hot and Cold Aisle Containment on Data Center Temperature and Efficiency
Impact of Hot and Cold Aisle Containment on Data Center Temperature and Efficiency White Paper 135 Revision 4 by John Niemann, Kevin Brown, and Victor Avelar Executive summary Both hot-air and cold-air
More informationAward-Winning Innovation in Data Center Cooling Design
Award-Winning Innovation in Data Center Cooling Design Oracle s Utah Compute Facility O R A C L E W H I T E P A P E R D E C E M B E R 2 0 1 4 Table of Contents Introduction 1 Overview 2 Innovation in Energy
More informationCase Study: Innovative Energy Efficiency Approaches in NOAA s Environmental Security Computing Center in Fairmont, West Virginia
Case Study: Innovative Energy Efficiency Approaches in NOAA s Environmental Security Computing Center in Fairmont, West Virginia Prepared for the U.S. Department of Energy s Federal Energy Management Program
More informationEnergy Efficiency and Green Data Centers. Overview of Recommendations ITU-T L.1300 and ITU-T L.1310
Energy Efficiency and Green Data Centers Overview of Recommendations ITU-T L.1300 and ITU-T L.1310 Paolo Gemma Chairman of Working Party 3 of ITU-T Study Group 5 International Telecommunication Union Agenda
More informationHow High Temperature Data Centers and Intel Technologies Decrease Operating Costs
Intel Intelligent Management How High Temperature Data Centers and Intel Technologies Decrease Operating Costs and cooling savings through the use of Intel s Platforms and Intelligent Management features
More informationWhite Paper: Free Cooling and the Efficiency of your Data Centre
AIT Partnership Group Ltd White Paper: Free Cooling and the Efficiency of your Data Centre Using free cooling methods to increase environmental sustainability and reduce operational cost. Contents 1. Summary...
More informationHow High Temperature Data Centers & Intel Technologies save Energy, Money, Water and Greenhouse Gas Emissions
Intel Intelligent Power Management Intel How High Temperature Data Centers & Intel Technologies save Energy, Money, Water and Greenhouse Gas Emissions Power savings through the use of Intel s intelligent
More informationReducing the Annual Cost of a Telecommunications Data Center
Applied Math Modeling White Paper Reducing the Annual Cost of a Telecommunications Data Center By Paul Bemis and Liz Marshall, Applied Math Modeling Inc., Concord, NH March, 2011 Introduction The facilities
More informationHot-Aisle vs. Cold-Aisle Containment for Data Centers
Hot-Aisle vs. Cold-Aisle Containment for Data Centers White Paper 135 Revision 1 by John Niemann, Kevin Brown, and Victor Avelar > Executive summary Both hot-air and cold-air containment can improve the
More informationTitle: Design of a Shared Tier III+ Data Center: A Case Study with Design Alternatives and Selection Criteria
Tier 3+ 1 Title: Design of a Shared Tier III+ Data Center: A Case Study with Design Alternatives and Selection Criteria Abstract: Schoolcraft College is constructing a High Availability (HA) Data Center
More informationDirect Fresh Air Free Cooling of Data Centres
White Paper Introduction There have been many different cooling systems deployed in Data Centres in the past to maintain an acceptable environment for the equipment and for Data Centre operatives. The
More informationRACKWISE Data Center Manager
RACKWISE Data Center Manager For more information on RACKWISE Data Center Manager, visit or contact us at info@rackwise.com or (888) 818-2385 Corporate Headquarters 2365 Iron Point Road Suite 190 Folsom,
More informationDatacenter Efficiency
EXECUTIVE STRATEGY BRIEF Operating highly-efficient datacenters is imperative as more consumers and companies move to a cloud computing environment. With high energy costs and pressure to reduce carbon
More informationSolutions to Make Your Data Center Energy Effi cient
Common $en e: Solutions to Make Your Data Center Energy Effi cient Energy effi ciency is a life style. It s also common sense. In a data center, the name of the game is effi ciency and how many compute
More informationMSU EMPLOYEE GUIDELINES FOR WORKING IN HOT ENVIRONMENTS
MSU EMPLOYEE GUIDELINES FOR WORKING IN HOT ENVIRONMENTS The Office of Radiation, Chemical and Biological Safety May, 1999 I. BACKGROUND: There is currently no specific Occupational Safety and Health Administration
More informationData Centers: Definitions, Concepts and Concerns
Data Centers: Definitions, Concepts and Concerns Arash Mousavi DCC September 2013 Agenda 1. Introduction 2. Issues in Modern Data Centers: Siemens Integrated Data Center Solutions 3. Issues in Modern Data
More informationCreating Data Center Efficiencies Using Closed-Loop Design Brent Goren, Data Center Consultant
RESEARCH UNDERWRITER WHITE PAPER LEAN, CLEAN & GREEN Wright Line Creating Data Center Efficiencies Using Closed-Loop Design Brent Goren, Data Center Consultant Currently 60 percent of the cool air that
More informationThe Mission Critical Data Center Understand Complexity Improve Performance
The Mission Critical Data Center Understand Complexity Improve Performance Communications Technology Forum Fall 2013 Department / Presenter / Date 1 Rittal IT Solutions The State of the Data Center Market
More informationHow To Run A Data Center Efficiently
A White Paper from the Experts in Business-Critical Continuity TM Data Center Cooling Assessments What They Can Do for You Executive Summary Managing data centers and IT facilities is becoming increasingly
More informationTHE WORLD S MOST EFFICIENT DATA CENTER
THE WORLD S MOST EFFICIENT DATA CENTER HP POD 240a Ed Turkel Manager, WW HPC Marketing Hyperscale Business Unit 2011 Hewlett-Packard Development Company, L.P. The information contained herein is subject
More informationThe Data Center Dilemma - A Case Study
Second Place: Industrial Facilities or Processes, Existing The TCS data center makes use of white cabinets and reflective surfaces as one method to reduce power for its lights and cooling. Data Center
More informationGUIDE TO ICT SERVER ROOM ENERGY EFFICIENCY. Public Sector ICT Special Working Group
GUIDE TO ICT SERVER ROOM ENERGY EFFICIENCY Public Sector ICT Special Working Group SERVER ROOM ENERGY EFFICIENCY This guide is one of a suite of documents that aims to provide guidance on ICT energy efficiency.
More informationGreat Lakes Data Room Case Study
Great Lakes Data Room Case Study WeRackYourWorld.com Problem: During a warm summer period in 2008, Great Lakes experienced a network outage due to a switch failure in the network enclosure. After an equipment
More informationVerizon SMARTS Data Center Design Phase 1 Conceptual Study Report Ms. Leah Zabarenko Verizon Business 2606A Carsins Run Road Aberdeen, MD 21001
Verizon SMARTS Data Center Design Phase 1 Conceptual Study Report Ms. Leah Zabarenko Verizon Business 2606A Carsins Run Road Aberdeen, MD 21001 Presented by: Liberty Engineering, LLP 1609 Connecticut Avenue
More informationCooling Capacity Factor (CCF) Reveals Stranded Capacity and Data Center Cost Savings
WHITE PAPER Cooling Capacity Factor (CCF) Reveals Stranded Capacity and Data Center Cost Savings By Kenneth G. Brill, Upsite Technologies, Inc. Lars Strong, P.E., Upsite Technologies, Inc. 505.798.0200
More informationThe New Data Center Cooling Paradigm The Tiered Approach
Product Footprint - Heat Density Trends The New Data Center Cooling Paradigm The Tiered Approach Lennart Ståhl Amdahl, Cisco, Compaq, Cray, Dell, EMC, HP, IBM, Intel, Lucent, Motorola, Nokia, Nortel, Sun,
More informationDataCenter 2020. Data Center Management and Efficiency at Its Best. OpenFlow/SDN in Data Centers for Energy Conservation.
DataCenter 2020. Data Center Management and Efficiency at Its Best. OpenFlow/SDN in Data Centers for Energy Conservation. Dr. Rainer Weidmann, DC Architecture & DC Innovation Dr. Rainer Weidmann, DC Architecture
More informationSovereign. The made to measure data centre
Sovereign D ATA C O N N E C T The made to measure data centre Prime Location Within touching distance of everything that s important. 2 Your Customer-Centric Data Centre For the vast majority of organisations
More informationMinimising Data Centre Total Cost of Ownership Through Energy Efficiency Analysis
Minimising Data Centre Total Cost of Ownership Through Energy Efficiency Analysis Sophia Flucker CEng MIMechE Ing Dr Robert Tozer MSc MBA PhD CEng MCIBSE MASHRAE Operational Intelligence Ltd. info@dc-oi.com
More informationEconomizer Fundamentals: Smart Approaches to Energy-Efficient Free-Cooling for Data Centers
A White Paper from the Experts in Business-Critical Continuity TM Economizer Fundamentals: Smart Approaches to Energy-Efficient Free-Cooling for Data Centers Executive Summary The strategic business importance
More informationAutomation's Modular Containerized Datacenter Solutions
SAFE Automation's Modular Containerized Datacenter Solutions Automation's SAFE (Secure, Autonomous, Flexible, Efficient) Modular Containerized Datacenter offers a fast, flexible and efficient solution
More informationFEAR Model - Review Cell Module Block
F.E.A.R. Returns: 5 Steps Toward Data Center Efficiency Today Objectives Benefits for ITS professionals Brief review of the FEAR data center Define data center efficiency Link efficiency to the FEAR data
More informationGreen Computing: Datacentres
Green Computing: Datacentres Simin Nadjm-Tehrani Department of Computer and Information Science (IDA) Linköping University Sweden Many thanks to Jordi Cucurull For earlier versions of this course material
More informationAlan Matzka, P.E., Senior Mechanical Engineer Bradford Consulting Engineers
Information Technology and Data Centers HVAC Showcase November 26, 2013 Alan Matzka, P.E., Senior Mechanical Engineer Bradford Consulting Engineers Welcome. Today s webinar is being recorded and will be
More informationMaximize energy savings Increase life of cooling equipment More reliable for extreme cold weather conditions There are disadvantages
Objectives Increase awareness of the types of economizers currently used for data centers Provide designers/owners with an overview of the benefits and challenges associated with each type Outline some
More informationRack Hygiene. Data Center White Paper. Executive Summary
Data Center White Paper Rack Hygiene April 14, 2011 Ed Eacueo Data Center Manager Executive Summary This paper describes the concept of Rack Hygiene, which positions the rack as an airflow management device,
More informationBusiness white paper. A new approach to industrialized IT. HP Flexible Data Center
Business white paper A new approach to industrialized IT HP Flexible Data Center Table of contents 4 Introduction 4 Levels of modularity 5 What is HP Flexible DC? 5 HP Flexible DC features 6 The core-and-quadrant
More informationDatacenter Clarity LC for colocation owners and tenants. The Data Center Infrastructure Management (DCIM) solution from Siemens. siemens.
Datacenter Clarity LC for colocation owners and tenants The Data Center Infrastructure (DCIM) solution from Siemens siemens.com/dcim Increased efficiency through Datacenter Clarity LC As organizations
More informationData Centre Testing and Commissioning
Data Centre Testing and Commissioning What is Testing and Commissioning? Commissioning provides a systematic and rigorous set of tests tailored to suit the specific design. It is a process designed to
More informationOttawa Fire Services General Order Part 1
Ottawa Fire Services General Order Part 1 Classification # GO 1 SA 04.1-2003 Safety- Occupational Health and Safety Firefighter Heat Stress Management Guideline- Revised Subject Authority Date Issued:
More informationGreen Computing: Datacentres
Green Computing: Datacentres Simin Nadjm-Tehrani Department of Computer and Information Science (IDA) Linköping University Sweden Many thanks to Jordi Cucurull For earlier versions of this course material
More informationData Center 2020: Delivering high density in the Data Center; efficiently and reliably
Data Center 2020: Delivering high density in the Data Center; efficiently and reliably March 2011 Powered by Data Center 2020: Delivering high density in the Data Center; efficiently and reliably Review:
More informationData Center & IT Infrastructure Optimization. Trends & Best Practices. Mickey Iqbal - IBM Distinguished Engineer. IBM Global Technology Services
Data Center & IT Infrastructure Optimization Trends & Best Practices Mickey Iqbal - IBM Distinguished Engineer IBM Global Technology Services IT Organizations are Challenged by a Set of Operational Issues
More informationImperial College 3 March 2009 Green Data Centers: An Overview
Imperial College 3 March 2009 Green Data Centers: An Overview Updated: 26 Feb 09 LBNL s Data Center findings Benchmarking Efforts Energy Reduction Approaches Green Data Centers: An Overview 2 Scenarios
More informationData center upgrade proposal. (phase one)
Data center upgrade proposal (phase one) Executive Summary Great Lakes began a recent dialogue with a customer regarding current operations and the potential for performance improvement within the The
More informationUniversity of St Andrews. Energy Efficient Data Centre Cooling
Energy Efficient Data Centre Cooling St. Andrews and Elsewhere Richard Lumb Consultant Engineer Future-Tech Energy Efficient Data Centre Cooling There is no one single best cooling solution for all Data
More information