White Paper: Free Cooling and the Efficiency of your Data Centre

Size: px
Start display at page:

Download "White Paper: Free Cooling and the Efficiency of your Data Centre"

Transcription

1 AIT Partnership Group Ltd White Paper: Free Cooling and the Efficiency of your Data Centre Using free cooling methods to increase environmental sustainability and reduce operational cost.

2 Contents 1. Summary Traditional Data Centre Cooling Methods Fresh Air Free Cooling Factors to Consider for Fresh Air Free Cooling... 7 Humidity... 7 Dust, Smoke and Air Borne Pollutants Adiabatic/Evaporative Cooling Maximising the Efficiency of your Data Centre... 9 References

3 1. Summary Free cooling systems can, in most cases, offer the operator large savings on their annual operational costs over more traditional air-conditioning methods. The term free cooling refers to using external ambient air and/or water in order to cool your data centre. Cost is reduced and environmental sustainability increased due to far less power being used to cool the air through an air-conditioning unit. A water side free cooling unit is slightly different in that your data centre must be sealed, much like a traditional air conditioned data centre. This prevents outside contaminants being brought into the data centre with the hot air exhausted being cooled through coils surrounded by chilled water. In many cases using a combination of these systems will allow year round use, dependent on your location. The overwhelming majority of data centres rely on air-based cooling provided by airconditioning to keep IT equipment in the server racks below the industry standard ASHRAE (American Society of Heating, Refrigerating and Air-conditioning Engineers) guideline temperature limit of 27⁰ C. In order to achieve this air temperature is closely monitored and controlled within the data centre. IT equipment running too hot will reduce its lifetime and cause early failure, while over cooling the data centre wastes energy and increases costs. The UK s climate, for the vast majority of the year, lends itself perfectly to free cooling methods. With ASHRAE standards stating that IT equipment should be cooled to between 18⁰ C and 27⁰ C, the UK s yearly average temperature of 9.7⁰ C ( provides suitable ambient temperatures almost all year round. The only time when a traditional air-conditioning system may have to be used is if external ambient temperatures are above 27⁰ C during the summer months, which remains relatively rare, or depending on external pollutants. Even then water side free cooling methods can remain very efficient up to 32⁰ C with adiabatic cooling installed. 3

4 Fig 1: Example of Water Side Free Cooling There are several other factors to consider when weighing whether to use air conditioned cooling systems over the equivalent free cooling methods. Humidity and air borne contaminants such as dust and smoke all play an important part in weighing up which option to install into your data centre. The choice of traditional approaches vs fresh air (or water side) free cooling is always a trade-off between energy saving and data centre reliability. 2. Traditional Data Centre Cooling Methods Traditional cooling methods mainly use air-conditioning units to cool the air within a data centre to within official guidelines. As with free cooling methods, there are pros and cons surrounding air conditioned units which should be considered when deciding which is best for you. Where air-conditioning is used, hot air exhausted from your data centre is cooled by the computer room air conditioning (CRAC) unit in a continuous refrigeration cycle. Pros of this method include the re-cycling of the same air limiting the introduction of contaminants from the outside environment which can harm the computer equipment. Humidity creates another problem area in data centres, with levels of 80% and above also likely to affect equipment therefore reducing the lifetime of your centre. Air-conditioning reduces humidity levels to a suitable percentage as cool air cannot hold as much moisture as warm air. Thus in certain climates and at certain times of the year, a traditional cooling facility will be more effective than an equivalent free cooling system. 4

5 In coastal areas the salt content of the air presents a typical scenario that forces traditional air conditioning solutions to be used. Ross Carver, Project Manager at AIT Partnership Group states salty sea air in coastal locations also causes reliability issues with connectors and IT equipment. In some areas it makes sense to seal the room and use air-conditioning to avoid costly downtime. Air-conditioning recycles the air contained within the data centre whereas free cooling methods will draw in large amounts of fresh (salty/damp) air which can attack your equipment and quickly cause reliability problems. Fig 2: Example of Traditional Air Conditioning System With air-conditioned cooling systems however comes a higher operational cost due to the compressive stages of refrigeration, consuming considerably more energy. This must be considered when selecting which option to take, creating a balance between the cost of energy consumed and the possible cost of downtime caused by external causes. Each of the factors mentioned above are vital in deciding which cooling method is preferable for you. In many cases a combination of both can be fitted to ensure year round efficiency and a balance between operational costs and PUE (Power Usage Effectiveness). The PUE, a ratio of power used by the IT equipment vs total data centre power, is a metric commonly used for assessing efficiency with an average rating of and more efficient data centres between Add to this environmental factors and potential ROI (Return on Investment) you can begin to decide which cooling solution makes sense for your particular situation. 5

6 3. Fresh Air Free Cooling Despite the name, fresh air free cooling isn t actually a completely free alternative to cooling your data centre. As discussed previously in this whitepaper, operational costs can be greatly reduced with free cooling methods, but only if your data centre requirements and your location are suitable. In its simplest form, a fresh air free cooling system will use a fan to draw in external ambient air into the data centre. The air is passed through filters to remove as many contaminants as possible and can then be directed through the data centre. The hot air created by the equipment rises and is extracted back out. Fig 3: Example of Fresh Air Free Cooling The use of fans means energy is required to run them efficiently. The amount of energy however is greatly reduced compared to running an air-conditioning unit. AIT Partnership Group has an innovation suite in its Reading office, cooled by external fresh air, where it tests data centre infrastructure management (DCIM) solutions. Ross Carver adds so far we haven t had any issues with fresh air free cooling and the temperature range has remained within ASHRAE guidelines. This is testament to free air cooling methods demonstrating the reliability and savings that can be made, as long as your data system requirements are suitable. 6

7 4 Factors to Consider for Fresh Air Free Cooling There are several important factors to take into consideration when choosing whether fresh air free cooling is right for you. Humidity The level of water carried by air will vary throughout the seasons as weather conditions change. When related to sustaining your data centre both air that is too humid and air that is too dry can have negative outcomes. Humid air may lead to corrosion of equipment meaning installing new equipment or changing parts more often. On the other hand air that is too dry is associated with static build up discharging, in turn damaging equipment and increasing downtime and therefore expense. For this reason a combination of cooling methods is often necessary, as air conditioning systems commonly have built in humidity controls. In this way external conditions do not dictate reliability and uptime when outside the norms for free air cooling. Dust, Smoke and Airborne Pollutants When a data centre is adapted from a closed architecture to an open equivalent, pollutants carried by external ambient air become an issue. With fresh air free cooling using external air, ways to reduce such pollutants from entering the data centre are of key importance. Dust and other larger airborne pollutants can build up over time on equipment reducing its life span. Smoke is harder to control with finer filtering systems required. If smoke was to enter your data centre it can trigger fire prevention equipment thus stopping operations and increasing expensive downtime. It is also worth noting that no matter how advanced your filtering system, a percentage of contaminants will always make it into your data centre. With these potential problem areas the location of your data centre is of paramount importance when choosing which cooling system if right for you. Filtering equipment is another cost to take into account and will need regular cleaning/replacing if in a polluted or coastal area. This in turn increases the maintenance overhead and can work out more expensive in the long run than a conventional air conditioned cooling system. If your data centre for example is within the confines of a city, free air cooling is most likely to cause more problems than equivalent methods. A higher location in less built up areas will result in far lower pollution levels and in turn allow free air cooling to run efficiently. 7

8 5. Adiabatic/Evaporative Cooling An adiabatic system can be fitted to both fresh air free cooling and water side free cooling methods and used to further cool air or humidify air slightly if too dry. A fine spray of water is used to cool the air (fresh air free cooling) or to cool the coil (water side free cooling). Adiabatic cooling allows a wide range of temperatures to be covered, retaining the efficiency of your data centre without the need for air conditioning. An example of where this has been successful comes from Tony Pompa, Data Centre Manager at Bedford Borough Council who gets an additional 5⁰ C of cooling via adiabatic methods. So long as humidity is not too high evaporative cooling can provide inlet air temperatures of 22⁰ C when outside air is 30⁰ C. Beyond 80% relative humidity or above 27⁰ C we fall back onto conventional airconditioning, but we rarely use it. Energy costs are considerably lower enabling us to get a payback on the project in less than 4 years. This demonstrates how the relatively low average temperature of the UK can provide ideal conditions for free cooling systems almost year round providing your location is suitable. Also, having a backup air conditioning unit installed ensures if conditions do change, reliability of your data centre is retained avoiding costly downtime. Fig 4: Example of Evaporative Cooling 8

9 6. Maximising the Efficiency of your Data Centre Whilst the cooling systems mentioned have the potential to greatly reduce operational cost while retaining efficiency, careful evaluation of your data centre is critical when deciding which system(s) to install. Before deciding which system is right for you, a survey of your locations environment will allow you to determine whether free air cooling methods are suitable for your needs. As mentioned above pollutants in built up areas and salt levels in coastal regions can result in premature damage to your equipment leading to higher costs and reduced efficiency. In these cases air conditioning units or water side free cooling will be the most efficient, providing the lowest overall operational costs. Another factor to consider is your reputation for reliable service. The inability to provide customers with computing or storage resources due to downtime caused by insufficient cooling systems would quickly harm your reputation. Air conditioning systems on the other hand, create a largely sealed environment within your data centre, so external pollutants from the intake of fresh air are no longer an issue. This will of course lead to increased operational cost due to higher energy consumption. Dependent on your location, this will still be the cheapest and most reliable system with your equipment being protected from impurities and excursions in humidity. In many cases a combination of both a free cooling and air conditioning systems can be used to ensure your data centre is covered for all eventualities. As mentioned above by Tony Pompa, air conditioning units can be installed and used when external conditions are not suitable for free cooling. This reduces any downtime as the air conditioning system can replace the free cooling arrangement instantly as and when it needs to. Dependant on your location and requirements, you may be able to install solely a free air cooling system, like AIT Partnership Group has it its Reading office. This will result in savings on operational cost and an increased efficiency, although careful monitoring of the external conditions is critical. In conclusion it is clear that the development of different free cooling systems can offer data centre owners great savings and efficiency. By careful surveying and monitoring of your surroundings you will be able to discover which method is right for your data centre, whether it be free air cooling, water side free cooling, air conditioning or a combination to cover all eventualities. 9

10 References AIT Opens Data Centre Innovation Suite ASHRAE Guidelines Ambient Air Cooling Economizer Fundamentals: Smart Approaches to Energy-Efficient Free Cooling for Data Centres Energy Efficient Free Cooling for Data Centers Using Free Cooling in the Data Center Weatherbase 1 Southern Court South Street Reading RG1 4QS All rights reserved. The AIT Logo and name is a registered trademark of the AIT Partnership Group Ltd. All other company or product names may be trademarks or registered trademarks of their respective owners. Whilst every effort has been made to ensure accuracy, neither the author nor AIT takes responsibility for the information given herein. 10

Analysis of data centre cooling energy efficiency

Analysis of data centre cooling energy efficiency Analysis of data centre cooling energy efficiency An analysis of the distribution of energy overheads in the data centre and the relationship between economiser hours and chiller efficiency Liam Newcombe

More information

The Use of Fresh Air in the Data Centre

The Use of Fresh Air in the Data Centre The Use of Fresh Air in the Data Centre White paper of a round table debate by industry experts on this key topic. Hosted by Keysource with participants including the Uptime Institute. Sophistication Through

More information

How To Improve Energy Efficiency In A Data Center

How To Improve Energy Efficiency In A Data Center Google s Green Data Centers: Network POP Case Study Table of Contents Introduction... 2 Best practices: Measuring. performance, optimizing air flow,. and turning up the thermostat... 2...Best Practice

More information

Excool Indirect Adiabatic and Evaporative Data Centre Cooling. World s Leading Indirect Adiabatic and Evaporative Data Centre Cooling

Excool Indirect Adiabatic and Evaporative Data Centre Cooling. World s Leading Indirect Adiabatic and Evaporative Data Centre Cooling Excool Indirect Adiabatic and Evaporative Data Centre Cooling World s Leading Indirect Adiabatic and Evaporative Data Centre Cooling Indirect Adiabatic and Evaporative Data Centre Cooling Solutions by

More information

Award-Winning Innovation in Data Center Cooling Design

Award-Winning Innovation in Data Center Cooling Design Award-Winning Innovation in Data Center Cooling Design Oracle s Utah Compute Facility O R A C L E W H I T E P A P E R D E C E M B E R 2 0 1 4 Table of Contents Introduction 1 Overview 2 Innovation in Energy

More information

Direct Fresh Air Free Cooling of Data Centres

Direct Fresh Air Free Cooling of Data Centres White Paper Introduction There have been many different cooling systems deployed in Data Centres in the past to maintain an acceptable environment for the equipment and for Data Centre operatives. The

More information

Energy Efficient Server Room and Data Centre Cooling. Computer Room Evaporative Cooler. EcoCooling

Energy Efficient Server Room and Data Centre Cooling. Computer Room Evaporative Cooler. EcoCooling Energy Efficient Server Room and Data Centre Cooling Computer Room Evaporative Cooler EcoCooling EcoCooling CREC Computer Room Evaporative Cooler Reduce your cooling costs by over 90% Did you know? An

More information

Technical Systems. Helen Bedford

Technical Systems. Helen Bedford Technical Systems in Data Centres Helen Bedford Technical Systems in Data Centres Overview Cooling IT and Peripheral Equipment Security: Access and Control Building Management System (BMS) Data Centre

More information

Climate solutions. evaporative cooling, adiabatic humidification and programmable controllers. energy saving solutions for data centers. carel.

Climate solutions. evaporative cooling, adiabatic humidification and programmable controllers. energy saving solutions for data centers. carel. Climate solutions evaporative cooling, adiabatic humidification and programmable controllers energy saving solutions for data centers carel.com Data center air-conditioning Data center air-conditioning

More information

Legacy Data Centres Upgrading the cooling capabilities What are the options?

Legacy Data Centres Upgrading the cooling capabilities What are the options? Legacy Data Centres Upgrading the cooling capabilities What are the options? Presentation Structure What is a Legacy Data Centre? What is CRAC cooling? ASHRAE Standards Overview Available Cooling Systems

More information

Environmental Data Center Management and Monitoring

Environmental Data Center Management and Monitoring 2013 Raritan Inc. Table of Contents Introduction Page 3 Sensor Design Considerations Page 3 Temperature and Humidity Sensors Page 4 Airflow Sensor Page 6 Differential Air Pressure Sensor Page 6 Water Sensor

More information

How High Temperature Data Centers and Intel Technologies Decrease Operating Costs

How High Temperature Data Centers and Intel Technologies Decrease Operating Costs Intel Intelligent Management How High Temperature Data Centers and Intel Technologies Decrease Operating Costs and cooling savings through the use of Intel s Platforms and Intelligent Management features

More information

Absolute and relative humidity Precise and comfort air-conditioning

Absolute and relative humidity Precise and comfort air-conditioning Absolute and relative humidity Precise and comfort air-conditioning Trends and best practices in data centers Compiled by: CONTEG Date: 30. 3. 2010 Version: 1.11 EN 2013 CONTEG. All rights reserved. No

More information

5 Reasons. Environment Sensors are used in all Modern Data Centers

5 Reasons. Environment Sensors are used in all Modern Data Centers 5 Reasons Environment Sensors are used in all Modern Data Centers TABLE OF CONTENTS 5 Reasons Environmental Sensors are used in all Modern Data Centers Save on Cooling by Confidently Raising Data Center

More information

Data Center Precision Cooling: The Need For A Higher Level Of Service Expertise. A White Paper from the Experts in Business-Critical Continuity

Data Center Precision Cooling: The Need For A Higher Level Of Service Expertise. A White Paper from the Experts in Business-Critical Continuity Data Center Precision Cooling: The Need For A Higher Level Of Service Expertise A White Paper from the Experts in Business-Critical Continuity Executive Summary Today s data centers are changing rapidly,

More information

Heat Recovery from Data Centres Conference Designing Energy Efficient Data Centres

Heat Recovery from Data Centres Conference Designing Energy Efficient Data Centres What factors determine the energy efficiency of a data centre? Where is the energy used? Local Climate Data Hall Temperatures Chiller / DX Energy Condenser / Dry Cooler / Cooling Tower Energy Pump Energy

More information

Improving Data Center Energy Efficiency Through Environmental Optimization

Improving Data Center Energy Efficiency Through Environmental Optimization Improving Data Center Energy Efficiency Through Environmental Optimization How Fine-Tuning Humidity, Airflows, and Temperature Dramatically Cuts Cooling Costs William Seeber Stephen Seeber Mid Atlantic

More information

DataCenter 2020: hot aisle and cold aisle containment efficiencies reveal no significant differences

DataCenter 2020: hot aisle and cold aisle containment efficiencies reveal no significant differences DataCenter 2020: hot aisle and cold aisle containment efficiencies reveal no significant differences November 2011 Powered by DataCenter 2020: hot aisle and cold aisle containment efficiencies reveal no

More information

Data Center Design Guide featuring Water-Side Economizer Solutions. with Dynamic Economizer Cooling

Data Center Design Guide featuring Water-Side Economizer Solutions. with Dynamic Economizer Cooling Data Center Design Guide featuring Water-Side Economizer Solutions with Dynamic Economizer Cooling Presenter: Jason Koo, P.Eng Sr. Field Applications Engineer STULZ Air Technology Systems jkoo@stulz ats.com

More information

System solution for data centres

System solution for data centres 1 System solution for data centres Energy-efficient air conditioning with ServeLine Cooling IT infrastructure, high availability, low energy costs and communication with DCIM systems all in one from your

More information

How To Find A Sweet Spot Operating Temperature For A Data Center

How To Find A Sweet Spot Operating Temperature For A Data Center Data Center Operating Temperature: The Sweet Spot A Dell Technical White Paper Dell Data Center Infrastructure David L. Moss THIS WHITE PAPER IS FOR INFORMATIONAL PURPOSES ONLY, AND MAY CONTAIN TYPOGRAPHICAL

More information

Bring the fresh in. Dedicated Outside Air Systems

Bring the fresh in. Dedicated Outside Air Systems Bring the fresh in. Dedicated Outside Air Systems The inside story on outside air. On average, we breathe in 3,400 gallons of air each day. Ambient indoor air pollution is a major problem, affecting health

More information

PERCENT OUTDOOR AIR (%OA) CALCULATION AND ITS USE

PERCENT OUTDOOR AIR (%OA) CALCULATION AND ITS USE PERCENT OUTDOOR AIR (%OA) CALCULATION AND ITS USE APPLICATION NOTE TI-138 TSI s IAQ-CALC TM Indoor Air Quality Meter and TH-CALC TM Thermohygrometer calculate Percent Outdoor Air (%OA). In order to take

More information

Sensor Monitoring and Remote Technologies 9 Voyager St, Linbro Park, Johannesburg Tel: +27 11 608 4270 ; www.batessecuredata.co.

Sensor Monitoring and Remote Technologies 9 Voyager St, Linbro Park, Johannesburg Tel: +27 11 608 4270 ; www.batessecuredata.co. Sensor Monitoring and Remote Technologies 9 Voyager St, Linbro Park, Johannesburg Tel: +27 11 608 4270 ; www.batessecuredata.co.za 1 Environment Monitoring in computer rooms, data centres and other facilities

More information

The Different Types of Air Conditioning Equipment for IT Environments

The Different Types of Air Conditioning Equipment for IT Environments The Different Types of Air Conditioning Equipment for IT Environments By Tony Evans White Paper #59 Executive Summary Cooling equipment for an IT environment can be implemented in 10 basic configurations.

More information

Guide to Minimizing Compressor-based Cooling in Data Centers

Guide to Minimizing Compressor-based Cooling in Data Centers Guide to Minimizing Compressor-based Cooling in Data Centers Prepared for the U.S. Department of Energy Federal Energy Management Program By: Lawrence Berkeley National Laboratory Author: William Tschudi

More information

DATA CENTER COOLING INNOVATIVE COOLING TECHNOLOGIES FOR YOUR DATA CENTER

DATA CENTER COOLING INNOVATIVE COOLING TECHNOLOGIES FOR YOUR DATA CENTER DATA CENTER COOLING INNOVATIVE COOLING TECHNOLOGIES FOR YOUR DATA CENTER DATA CENTERS 2009 IT Emissions = Aviation Industry Emissions Nations Largest Commercial Consumers of Electric Power Greenpeace estimates

More information

How High Temperature Data Centers & Intel Technologies save Energy, Money, Water and Greenhouse Gas Emissions

How High Temperature Data Centers & Intel Technologies save Energy, Money, Water and Greenhouse Gas Emissions Intel Intelligent Power Management Intel How High Temperature Data Centers & Intel Technologies save Energy, Money, Water and Greenhouse Gas Emissions Power and cooling savings through the use of Intel

More information

Free Cooling in Data Centers. John Speck, RCDD, DCDC JFC Solutions

Free Cooling in Data Centers. John Speck, RCDD, DCDC JFC Solutions Free Cooling in Data Centers John Speck, RCDD, DCDC JFC Solutions Why this topic Many data center projects or retrofits do not have a comprehensive analyses of systems power consumption completed in the

More information

Dehumidification Frequently Asked Questions

Dehumidification Frequently Asked Questions Dehumidification Basics Why do you want to keep indoor Rh between 30-60%? ASHRAE recommends keeping the relative humidity in a home between 30-60% to limit the effects of many unwanted conditions and harmful

More information

Energy Saving Fact Sheet Air Conditioning

Energy Saving Fact Sheet Air Conditioning Energy Saving Fact Sheet Air Conditioning Get your air conditioning into better shape Everyone wants air conditioning. But don t let your existing system, or one that you re considering installing, burn

More information

Economizer Fundamentals: Smart Approaches to Energy-Efficient Free-Cooling for Data Centers

Economizer Fundamentals: Smart Approaches to Energy-Efficient Free-Cooling for Data Centers A White Paper from the Experts in Business-Critical Continuity TM Economizer Fundamentals: Smart Approaches to Energy-Efficient Free-Cooling for Data Centers Executive Summary The strategic business importance

More information

Liebert EFC from 100 to 350 kw. The Highly Efficient Indirect Evaporative Freecooling Unit

Liebert EFC from 100 to 350 kw. The Highly Efficient Indirect Evaporative Freecooling Unit Liebert EFC from 100 to 350 kw The Highly Efficient Indirect Evaporative Freecooling Unit Liebert EFC, the Highly Efficient Indirect Evaporative Freecooling Solution Emerson Network Power delivers innovative

More information

CURBING THE COST OF DATA CENTER COOLING. Charles B. Kensky, PE, LEED AP BD+C, CEA Executive Vice President Bala Consulting Engineers

CURBING THE COST OF DATA CENTER COOLING. Charles B. Kensky, PE, LEED AP BD+C, CEA Executive Vice President Bala Consulting Engineers CURBING THE COST OF DATA CENTER COOLING Charles B. Kensky, PE, LEED AP BD+C, CEA Executive Vice President Bala Consulting Engineers OVERVIEW Compare Cooling Strategies in Free- Standing and In-Building

More information

State of the Art Energy Efficient Data Centre Air Conditioning

State of the Art Energy Efficient Data Centre Air Conditioning - White Paper - State of the Art Energy Efficient Data Centre Air Conditioning - Dynamic Free Cooling - Release 2, April 2008 Contents ABSTRACT... 3 1. WHY DO I NEED AN ENERGY EFFICIENT COOLING SYSTEM...

More information

Rittal White Paper 508: Economized Data Center Cooling Defining Methods & Implementation Practices By: Daniel Kennedy

Rittal White Paper 508: Economized Data Center Cooling Defining Methods & Implementation Practices By: Daniel Kennedy Rittal White Paper 508: Economized Data Center Cooling Defining Methods & Implementation Practices By: Daniel Kennedy Executive Summary Data center owners and operators are in constant pursuit of methods

More information

Greening Commercial Data Centres

Greening Commercial Data Centres Greening Commercial Data Centres Fresh air cooling giving a PUE of 1.2 in a colocation environment Greater efficiency and greater resilience Adjustable Overhead Supply allows variation in rack cooling

More information

DataCenter 2020: first results for energy-optimization at existing data centers

DataCenter 2020: first results for energy-optimization at existing data centers DataCenter : first results for energy-optimization at existing data centers July Powered by WHITE PAPER: DataCenter DataCenter : first results for energy-optimization at existing data centers Introduction

More information

Take the complication out of cooling. Data center cooling equipment and service from Alfa Laval

Take the complication out of cooling. Data center cooling equipment and service from Alfa Laval Take the complication out of cooling Data center cooling equipment and service from Alfa Laval How to make cooling less complicated As data grows, so does the demand for new data centers with increased

More information

Alfa Laval Abatigo. Redefining adiabatic cooling

Alfa Laval Abatigo. Redefining adiabatic cooling Alfa Laval Abatigo Redefining adiabatic cooling Experience and expertise recognized throughout the world With decades of broad experience and practical expertise in heat transfer, Alfa Laval is today a

More information

A discussion of condensate removal systems for clarifier and thickener drives for water and wastewater facilities.

A discussion of condensate removal systems for clarifier and thickener drives for water and wastewater facilities. A discussion of condensate removal systems for clarifier and thickener drives for water and wastewater facilities. Richard L. Dornfeld, BSME, P.E. Staff Engineer September 25, 2014 Moisture can be a problem

More information

Thermal Monitoring Best Practices Benefits gained through proper deployment and utilizing sensors that work with evolving monitoring systems

Thermal Monitoring Best Practices Benefits gained through proper deployment and utilizing sensors that work with evolving monitoring systems NER Data Corporation White Paper Thermal Monitoring Best Practices Benefits gained through proper deployment and utilizing sensors that work with evolving monitoring systems Introduction Data centers are

More information

Chiller-less Facilities: They May Be Closer Than You Think

Chiller-less Facilities: They May Be Closer Than You Think Chiller-less Facilities: They May Be Closer Than You Think A Dell Technical White Paper Learn more at Dell.com/PowerEdge/Rack David Moss Jon Fitch Paul Artman THIS WHITE PAPER IS FOR INFORMATIONAL PURPOSES

More information

AERMEC DATA CENTRE SOLUTIONS THE COMPLETE RANGE OF AERMEC SOLUTIONS FOR DATA CENTRES

AERMEC DATA CENTRE SOLUTIONS THE COMPLETE RANGE OF AERMEC SOLUTIONS FOR DATA CENTRES AERMEC DATA CENTRE SOLUTIONS THE COMPLETE RANGE OF AERMEC SOLUTIONS FOR DATA GLOBAL DATA CENTRE IP TRAFFIC WILL TRIPLE WITHIN 5 YEARS Global data centre IP traffic has set a constant growth path, with

More information

Challenges In Intelligent Management Of Power And Cooling Towards Sustainable Data Centre

Challenges In Intelligent Management Of Power And Cooling Towards Sustainable Data Centre Challenges In Intelligent Management Of Power And Cooling Towards Sustainable Data Centre S. Luong 1*, K. Liu 2, James Robey 3 1 Technologies for Sustainable Built Environments, University of Reading,

More information

IMPROVING DATA CENTER EFFICIENCY AND CAPACITY WITH AISLE CONTAINMENT

IMPROVING DATA CENTER EFFICIENCY AND CAPACITY WITH AISLE CONTAINMENT DATA CENTER RESOURCES WHITE PAPER IMPROVING DATA CENTER EFFICIENCY AND CAPACITY WITH AISLE CONTAINMENT BY: STEVE HAMBRUCH EXECUTIVE SUMMARY Data centers have experienced explosive growth in the last decade.

More information

Air-Conditioning Buying Guide

Air-Conditioning Buying Guide Air-Conditioning Buying Guide Buying a new air-conditioning system is a big decision. This Air-Conditioning Buying Guide can help you make the right choice, save energy and money. Shop with confidence

More information

Datacenter Efficiency

Datacenter Efficiency EXECUTIVE STRATEGY BRIEF Operating highly-efficient datacenters is imperative as more consumers and companies move to a cloud computing environment. With high energy costs and pressure to reduce carbon

More information

Cooling Small Server Rooms Can Be. - Jim Magallanes Computer Room Uptime: www.cruptime.com Uptime Racks: www.uptimeracks.com

Cooling Small Server Rooms Can Be. - Jim Magallanes Computer Room Uptime: www.cruptime.com Uptime Racks: www.uptimeracks.com Cooling Small Server Rooms Can Be Inexpensive, Efficient and Easy - Jim Magallanes Computer Room Uptime: www.cruptime.com Uptime Racks: www.uptimeracks.com Server Rooms Description & Heat Problem Trends

More information

Bytes and BTUs: Holistic Approaches to Data Center Energy Efficiency. Steve Hammond NREL

Bytes and BTUs: Holistic Approaches to Data Center Energy Efficiency. Steve Hammond NREL Bytes and BTUs: Holistic Approaches to Data Center Energy Efficiency NREL 1 National Renewable Energy Laboratory Presentation Road Map A Holistic Approach to Efficiency: Power, Packaging, Cooling, Integration

More information

Raising Inlet Temperatures in the Data Centre

Raising Inlet Temperatures in the Data Centre Raising Inlet Temperatures in the Data Centre White paper of a round table debate by industry experts on this key topic. Hosted by Keysource with participants including the Uptime Institute. Sophistication

More information

How High Temperature Data Centers & Intel Technologies save Energy, Money, Water and Greenhouse Gas Emissions

How High Temperature Data Centers & Intel Technologies save Energy, Money, Water and Greenhouse Gas Emissions Intel Intelligent Power Management Intel How High Temperature Data Centers & Intel Technologies save Energy, Money, Water and Greenhouse Gas Emissions Power savings through the use of Intel s intelligent

More information

Free Cooling for Data Centers

Free Cooling for Data Centers Free Cooling for Data Centers Release 1, September 2015 Contents 1. Abstract... 3 2. Introduction... 3 3. Data Center Temperatures and Free Cooling... 4 4. Direct Free Cooling... 4 5. Indirect Free Cooling...

More information

AIR-SITE GROUP. White Paper. Green Equipment Room Practices

AIR-SITE GROUP. White Paper. Green Equipment Room Practices AIR-SITE GROUP White Paper Green Equipment Room Practices www.air-site.com Common practices to build a green equipment room 1 Introduction Air-Site (www.air-site.com) is a leading international provider

More information

Improve competiveness of IDC and enterprise data centers with DCIM

Improve competiveness of IDC and enterprise data centers with DCIM Improve competiveness of IDC and enterprise data centers with DCIM This paper studies the implementation of modern DCIM systems for data centers to improve operational competitiveness with ATEN's DCIM

More information

Green Data Centre Design

Green Data Centre Design Green Data Centre Design A Holistic Approach Stantec Consulting Ltd. Aleks Milojkovic, P.Eng., RCDD, LEED AP Tommy Chiu, EIT, RCDD, LEED AP STANDARDS ENERGY EQUIPMENT MATERIALS EXAMPLES CONCLUSION STANDARDS

More information

The Benefits of Supply Air Temperature Control in the Data Centre

The Benefits of Supply Air Temperature Control in the Data Centre Executive Summary: Controlling the temperature in a data centre is critical to achieving maximum uptime and efficiency, but is it being controlled in the correct place? Whilst data centre layouts have

More information

BCA-IDA Green Mark for Existing Data Centres Version EDC/1.0

BCA-IDA Green Mark for Existing Data Centres Version EDC/1.0 BCA-IDA Green Mark for Existing Data Centres Version EDC/1.0 To achieve GREEN MARK Award Pre-requisite Requirement All relevant pre-requisite requirements for the specific Green Mark Rating are to be complied

More information

Green Building Handbook for South Africa Chapter: Heating, Ventilation and Cooling Luke Osburn CSIR Built Environment

Green Building Handbook for South Africa Chapter: Heating, Ventilation and Cooling Luke Osburn CSIR Built Environment Green Building Handbook for South Africa Chapter: Heating, Ventilation and Cooling Luke Osburn CSIR Built Environment The heating, ventilation and cooling loads of typical commercial office space can range

More information

Combining Cold Aisle Containment with Intelligent Control to Optimize Data Center Cooling Efficiency

Combining Cold Aisle Containment with Intelligent Control to Optimize Data Center Cooling Efficiency A White Paper from the Experts in Business-Critical Continuity TM Combining Cold Aisle Containment with Intelligent Control to Optimize Data Center Cooling Efficiency Executive Summary Energy efficiency

More information

IEC DATA CENTRE INDIRECT EVAPORATIVE COOLING SYSTEM

IEC DATA CENTRE INDIRECT EVAPORATIVE COOLING SYSTEM DATA CENTRE INDIRECT EVAPORATIVE COOLING SYSTEM THE GLOBAL DATA CENTRE MARKET The data centre air conditioning market is expected to grow with a CAGR (compound annual growth rate) of about 12% in the next

More information

Dealing with Thermal Issues in Data Center Universal Aisle Containment

Dealing with Thermal Issues in Data Center Universal Aisle Containment Dealing with Thermal Issues in Data Center Universal Aisle Containment Daniele Tordin BICSI RCDD Technical System Engineer - Panduit Europe Daniele.Tordin@Panduit.com AGENDA Business Drivers Challenges

More information

DCIM Data Center Infrastructure Monitoring

DCIM Data Center Infrastructure Monitoring DCIM Data Center Infrastructure Monitoring ServersCheck offers a flexible, modular and affordable DCIM solution. It is based on our range of IP & SNMP hardware environmental sensors and management software.

More information

Data Center 2020: Delivering high density in the Data Center; efficiently and reliably

Data Center 2020: Delivering high density in the Data Center; efficiently and reliably Data Center 2020: Delivering high density in the Data Center; efficiently and reliably March 2011 Powered by Data Center 2020: Delivering high density in the Data Center; efficiently and reliably Review:

More information

2008 ASHRAE Environmental Guidelines for Datacom Equipment -Expanding the Recommended Environmental Envelope-

2008 ASHRAE Environmental Guidelines for Datacom Equipment -Expanding the Recommended Environmental Envelope- 2008 ASHRAE Environmental Guidelines for Datacom Equipment -Expanding the Recommended Environmental Envelope- Overview: The current recommended environmental envelope for IT Equipment is listed in Table

More information

Interested in conducting your own webinar? Email webinars@bnpmedia.com

Interested in conducting your own webinar? Email webinars@bnpmedia.com Interested in conducting your own webinar? Email webinars@bnpmedia.com Improving Efficiencies by Integrating Data Center Systems August 30 th, 2012 Audio Abstract Presenter Info Slides Handouts Group Chat

More information

Poor Performing AC? High Electric Bills? High Humidity?

Poor Performing AC? High Electric Bills? High Humidity? Poor Performing AC? High Electric Bills? High Humidity? If you answered yes to any or all of these questions, it may be time to consider a new Air Conditioning system. Read on for useful information when

More information

I-STUTE Project - WP2.3 Data Centre Cooling. Project Review Meeting 8, Loughborough University, 29 th June 2015

I-STUTE Project - WP2.3 Data Centre Cooling. Project Review Meeting 8, Loughborough University, 29 th June 2015 I-STUTE Project - WP2.3 Data Centre Cooling Project Review Meeting 8, Loughborough University, 29 th June 2015 Topics to be considered 1. Progress on project tasks 2. Development of data centre test facility

More information

The Data Center Dilemma - A Case Study

The Data Center Dilemma - A Case Study Second Place: Industrial Facilities or Processes, Existing The TCS data center makes use of white cabinets and reflective surfaces as one method to reduce power for its lights and cooling. Data Center

More information

AERIS DATA CENTRE INDIRECT EVAPORATIVE COOLING SYSTEM

AERIS DATA CENTRE INDIRECT EVAPORATIVE COOLING SYSTEM DATA CENTRE INDIRECT EVAPORATIVE COOLING SYSTEM THE GLOBAL DATA CENTRE MARKET The data centre air conditioning market is expected to grow with a CAGR (compound annual growth rate) of about 12% in the next

More information

International Telecommunication Union SERIES L: CONSTRUCTION, INSTALLATION AND PROTECTION OF TELECOMMUNICATION CABLES IN PUBLIC NETWORKS

International Telecommunication Union SERIES L: CONSTRUCTION, INSTALLATION AND PROTECTION OF TELECOMMUNICATION CABLES IN PUBLIC NETWORKS International Telecommunication Union ITU-T TELECOMMUNICATION STANDARDIZATION SECTOR OF ITU Technical Paper (13 December 2013) SERIES L: CONSTRUCTION, INSTALLATION AND PROTECTION OF TELECOMMUNICATION CABLES

More information

Guideline for Water and Energy Considerations During Federal Data Center Consolidations

Guideline for Water and Energy Considerations During Federal Data Center Consolidations Guideline for Water and Energy Considerations During Federal Data Center Consolidations Prepared for the U.S. Department of Energy Federal Energy Management Program By Lawrence Berkeley National Laboratory

More information

Maximize energy savings Increase life of cooling equipment More reliable for extreme cold weather conditions There are disadvantages

Maximize energy savings Increase life of cooling equipment More reliable for extreme cold weather conditions There are disadvantages Objectives Increase awareness of the types of economizers currently used for data centers Provide designers/owners with an overview of the benefits and challenges associated with each type Outline some

More information

Data Centre Cooling Technologies. Jon Pettitt, EMEA DataCenter Business Development Manager

Data Centre Cooling Technologies. Jon Pettitt, EMEA DataCenter Business Development Manager Data Centre Cooling Technologies 1 Jon Pettitt, EMEA DataCenter Business Development Manager Munters Group Key facts 3.000 Employees 30 Countries Turnover of 470 M HQ in Sweden Global DC Support 25+ Data

More information

- White Paper - Data Centre Cooling. Best Practice

- White Paper - Data Centre Cooling. Best Practice - White Paper - Data Centre Cooling Best Practice Release 2, April 2008 Contents INTRODUCTION... 3 1. AIR FLOW LEAKAGE... 3 2. PERFORATED TILES: NUMBER AND OPENING FACTOR... 4 3. PERFORATED TILES: WITH

More information

Data Centre Infrastructure Assessment

Data Centre Infrastructure Assessment Data Centre Infrastructure Assessment Prepared for: ACME INC SAMPLE REPORT Attention: Mr DC Manager This report represents a generic sample data centre audit for a generic customer by Focus Group Technologies.

More information

Data Centre Cooling Air Performance Metrics

Data Centre Cooling Air Performance Metrics Data Centre Cooling Air Performance Metrics Sophia Flucker CEng MIMechE Ing Dr Robert Tozer MSc MBA PhD CEng MCIBSE MASHRAE Operational Intelligence Ltd. info@dc-oi.com Abstract Data centre energy consumption

More information

Performance 17 Two-Stage Air Conditioner with Puron Refrigerant

Performance 17 Two-Stage Air Conditioner with Puron Refrigerant Performance 17 Two-Stage Air Conditioner with Puron Refrigerant TM Enhanced Comfort, Tax Credit Eligible Cooling Things to Consider Before You Buy Puron Refrigerant Puron refrigerant is environmentally

More information

Drives and motors. A guide to using variable-speed drives and motors in data centres

Drives and motors. A guide to using variable-speed drives and motors in data centres Drives motors A guide to using variable-speed drives motors in data centres The power behind the data Private public businesses, from banks to supermarkets, to telecommunications companies internet providers

More information

Control of Computer Room Air Handlers Using Wireless Sensors. Energy Efficient Data Center Demonstration Project

Control of Computer Room Air Handlers Using Wireless Sensors. Energy Efficient Data Center Demonstration Project Control of Computer Room Air Handlers Using Wireless Sensors Energy Efficient Data Center Demonstration Project About the Energy Efficient Data Center Demonstration Project The project s goal is to identify

More information

The Mean Green Cooling MachineTM www.aqua-chill.com

The Mean Green Cooling MachineTM www.aqua-chill.com The Mean Green Cooling MachineTM www.aqua-chill.com Runs Less. Cools More. What is AquaChill? AquaChill is not a swamp cooler. Aqua Chill is a water cooled evaporative air conditioner. A water cooled system

More information

Humidification Strategies for Data Centers and Network Rooms

Humidification Strategies for Data Centers and Network Rooms Humidification Strategies for Data Centers and Network Rooms By Tony Evans White Paper #58 Revision 1 Executive Summary The control of humidity in Information Technology environments is essential to achieving

More information

Reducing Data Center Loads for a Large-Scale, Net Zero Office Building

Reducing Data Center Loads for a Large-Scale, Net Zero Office Building rsed Energy Efficiency & Renewable Energy FEDERAL ENERGY MANAGEMENT PROGRAM Reducing Data Center Loads for a Large-Scale, Net Zero Office Building Energy Efficiency & Renewable Energy Executive summary

More information

Case Study: Innovative Energy Efficiency Approaches in NOAA s Environmental Security Computing Center in Fairmont, West Virginia

Case Study: Innovative Energy Efficiency Approaches in NOAA s Environmental Security Computing Center in Fairmont, West Virginia Case Study: Innovative Energy Efficiency Approaches in NOAA s Environmental Security Computing Center in Fairmont, West Virginia Prepared for the U.S. Department of Energy s Federal Energy Management Program

More information

How To Use A Water Source Heat Pump

How To Use A Water Source Heat Pump Geothermal Energy Using Water-Source Heat Pumps By VIRSTAR Corporation Geothermal Expertise Since 1978 All information contained herein is the exclusive property of VIRSTAR Corporation, all rights reserved.

More information

Data Center Environments

Data Center Environments Data Center Environments ASHRAE s Evolving Thermal Guidelines By Robin A. Steinbrecher, Member ASHRAE; and Roger Schmidt, Ph.D., Member ASHRAE Over the last decade, data centers housing large numbers of

More information

Recommendations for Measuring and Reporting Overall Data Center Efficiency

Recommendations for Measuring and Reporting Overall Data Center Efficiency Recommendations for Measuring and Reporting Overall Data Center Efficiency Version 2 Measuring PUE for Data Centers 17 May 2011 Table of Contents 1 Introduction... 1 1.1 Purpose Recommendations for Measuring

More information

Cooling Capacity Factor (CCF) Reveals Stranded Capacity and Data Center Cost Savings

Cooling Capacity Factor (CCF) Reveals Stranded Capacity and Data Center Cost Savings WHITE PAPER Cooling Capacity Factor (CCF) Reveals Stranded Capacity and Data Center Cost Savings By Lars Strong, P.E., Upsite Technologies, Inc. Kenneth G. Brill, Upsite Technologies, Inc. 505.798.0200

More information

Data Center Cooling & Air Flow Management. Arnold Murphy, CDCEP, CDCAP March 3, 2015

Data Center Cooling & Air Flow Management. Arnold Murphy, CDCEP, CDCAP March 3, 2015 Data Center Cooling & Air Flow Management Arnold Murphy, CDCEP, CDCAP March 3, 2015 Strategic Clean Technology Inc Focus on improving cooling and air flow management to achieve energy cost savings and

More information

Data Centers: Definitions, Concepts and Concerns

Data Centers: Definitions, Concepts and Concerns Data Centers: Definitions, Concepts and Concerns Arash Mousavi DCC September 2013 Agenda 1. Introduction 2. Issues in Modern Data Centers: Siemens Integrated Data Center Solutions 3. Issues in Modern Data

More information

Overview of Green Energy Strategies and Techniques for Modern Data Centers

Overview of Green Energy Strategies and Techniques for Modern Data Centers Overview of Green Energy Strategies and Techniques for Modern Data Centers Introduction Data centers ensure the operation of critical business IT equipment including servers, networking and storage devices.

More information

Economizer Modes of Data Center Cooling Systems

Economizer Modes of Data Center Cooling Systems Economizer Modes of Data Center Cooling Systems White Paper 132 Revision 0 by John Niemann John Bean Victor Avelar > Executive summary In certain climates, some cooling systems can save over 70% in annual

More information

7 Best Practices for Increasing Efficiency, Availability and Capacity. XXXX XXXXXXXX Liebert North America

7 Best Practices for Increasing Efficiency, Availability and Capacity. XXXX XXXXXXXX Liebert North America 7 Best Practices for Increasing Efficiency, Availability and Capacity XXXX XXXXXXXX Liebert North America Emerson Network Power: The global leader in enabling Business-Critical Continuity Automatic Transfer

More information

Design Best Practices for Data Centers

Design Best Practices for Data Centers Tuesday, 22 September 2009 Design Best Practices for Data Centers Written by Mark Welte Tuesday, 22 September 2009 The data center industry is going through revolutionary changes, due to changing market

More information

Server room guide helps energy managers reduce server consumption

Server room guide helps energy managers reduce server consumption Server room guide helps energy managers reduce server consumption Jan Viegand Viegand Maagøe Nr. Farimagsgade 37 1364 Copenhagen K Denmark jv@viegandmaagoe.dk Keywords servers, guidelines, server rooms,

More information

BEST PRACTICES RESEARCH

BEST PRACTICES RESEARCH 2013 Frost & Sullivan 1 We Accelerate Growth Product Line Strategy Leadership Award Data Center Cooling North America, 2013 Frost & Sullivan s Global Research Platform Frost & Sullivan is in its 50th year

More information

Data Center Industry Leaders Reach Agreement on Guiding Principles for Energy Efficiency Metrics

Data Center Industry Leaders Reach Agreement on Guiding Principles for Energy Efficiency Metrics On January 13, 2010, 7x24 Exchange Chairman Robert Cassiliano and Vice President David Schirmacher met in Washington, DC with representatives from the EPA, the DOE and 7 leading industry organizations

More information

Defining Quality. Building Comfort. Precision. Air Conditioning

Defining Quality. Building Comfort. Precision. Air Conditioning Defining Quality. Building Comfort. Precision Air Conditioning Today s technology rooms require precise, stable environments in order for sensitive electronics to operate optimally. Standard comfort air

More information

A NEW DESICCANT EVAPORATIVE COOLING CYCLE FOR SOLAR AIR CONDITIONING AND HOT WATER HEATING

A NEW DESICCANT EVAPORATIVE COOLING CYCLE FOR SOLAR AIR CONDITIONING AND HOT WATER HEATING A NEW DESICCANT EVAPORATIVE COOLING CYCLE FOR SOLAR AIR CONDITIONING AND HOT WATER HEATING John Archibald American Solar Roofing Company 8703 Chippendale Court Annandale, Va. 22003 e-mail: jarchibald@americansolar.com

More information

3-2. Using the air conditioning system and defogger Automatic air conditioning system

3-2. Using the air conditioning system and defogger Automatic air conditioning system Automatic air conditioning system Airflow and outlets are automatically adjusted according to the temperature setting. Press to display the air conditioning operation screen. Air conditioning operation

More information