Creating Data Center Efficiencies Using Closed-Loop Design Brent Goren, Data Center Consultant

Size: px
Start display at page:

Download "Creating Data Center Efficiencies Using Closed-Loop Design Brent Goren, Data Center Consultant"

Transcription

1 RESEARCH UNDERWRITER WHITE PAPER LEAN, CLEAN & GREEN Wright Line Creating Data Center Efficiencies Using Closed-Loop Design Brent Goren, Data Center Consultant Currently 60 percent of the cool air that is supplied from air-conditioning units in a typical data center is wasted. This whitepaper provides information to help achieve greater efficiencies within the data center by optimizing the physical cooling capacity, while maintaining expected levels of reliability. Publisher s Note: This co branded and copyrighted paper is published for inclusion in formal compilation of papers, presentations, and proceedings known as The Path Forward v4.0 Revolutionizing Data Center Efficiency of the annual Uptime Institute s Green Enterprise IT Symposium, April 13 16, 2009, New York City. It contains significant information value for the data center professional community which the Institute serves. Although written by a research underwriting partner of the Institute, the Institute maintains a vendor neutral policy and does not endorse any opinion, position, product or service mentioned in this paper. Readers are encouraged to contact this paper s author(s) directly with comments, questions or for any further information.

2 Data center trends have traditionally been focused on delivery of service and reliability. However, there has been a recent shift in focus to provide greater efficiency in data centers. Up until now, there has been little incentive for data center managers to optimize the efficiency of their data center and they are still primarily concerned about capital costs related to their data center s capacity and reliability. A study by research analyst firm IDC shows that for every dollar of new server spend in 2005, 48 cents was spent on power and cooling. This is a sharp increase from 2000, when the ratio was 21 cents per dollar of server spend. This ratio is expected to increase even further. Thus the immediate demand to create more efficient data centers will be at the forefront of most company s cost-saving initiatives. However, efficiency gains must be balanced to ensure there is no compromise in data center reliability and performance. Legacy Data Center Design Issues A legacy data center typically has the following characteristics: A open system that delivers cold air at about 55 F via overhead ducting or a raised-floor plenum Perforated tiles (in a raised-floor environment) used to channel the cold air from beneath the raised-floor plenum into the data center Rows of racks orientated 180 degrees from alternate rows to create hot and cold aisles Minimum of four feet separation between cold aisles and three feet between hot aisles 1 Precision air conditioning units located at the ends of each hot aisle. In practice, the airflow in a legacy data center is very unpredictable and has numerous inefficiencies, which proliferate as power densities increase. This is shown in Figure 1, where bypass air, recirculation, and air stratification are the dominant airflow characteristics throughout the data center. Figure 1. Bypass airflow, recirculation, and air stratification Bypass Airflow Bypass airflow is defined as conditioned air that doesn t reach computer equipment. 2 The most common form of bypass air occurs when air supplied from the precision air conditioning units is delivered directly back to the airconditioner intakes. Examples of this would be leakage areas such as air penetrating through cable cut-outs, holes under cabinets, or misplaced perforated tiles that blow air directly back to the air-conditioner intakes. Other examples of bypass airflow include air that escapes through holes in the computer room perimeter walls and non-sealed doors. In conventional legacy data centers, as little as 40 percent of the air delivered from precision air conditioning units may actually make its way to cool the existing IT equipment a great waste of energy as well as an excessive and unnecessary operational expense. Recirculation Recirculation occurs when hot air exhausted from rackmounted computing devices is fed into device inlets. This principally occurs in servers located at the highest points of a high-density enclosure. This is illustrated in Figure 2 by the large area shown in red. Recirculation can cause overheating damage to computing equipment and disruption to mission-critical services. 1 Recommendations as per ANSI/TIA/EIA -942, April Reducing Bypass Airflow Is Essential for Eliminating Hotspots, by Robert F. Sullivan, Ph.D. 2

3 Figure 2. Recirculation Hot and Cold Remixing and Air Stratification Air stratification in the data center is the layering effect of temperature gradients from the floor to the ceiling of the computer room. In a raised-floor environment, air is delivered at approximately 55ºF from under the raised floor through perforated tiles. The temperature, as the air first penetrates the perforated tile, remains the same as the supply temperature, but as the air moves vertically up the rack s front face, air temperatures gradually increase. This occurs because insufficient airflow is delivered through the perforated tiles, which allow the hot air exhaust to penetrate the cold-aisle region. In high-density enclosures, it s not uncommon for temperatures to exceed 90ºF at the server inlets mounted at the highest point of the enclosure. However, the recommended temperature range for server inlets as stated by the American Society of Heating, Refrigerating, and Air Conditioning Engineers (ASHRAE s) Mission-Critical Facilities Technical Committee 9.9 is between 64.4ºF and 80.6ºF. Thus, in a legacy data center design the computer room is actually being over-cooled, by sending extremely cold air under the raised floor to compensate for the wide range of temperatures at the device inlets. Data Center Heat Source: Processor Performance the Need for Speed In our modern economy, the fact remains that companies need to maintain growth and profitability, which demands delivery of better, faster, richer, and more reliable products and services to remain competitive. Thus, constant need for speed reflects the modern day business compulsion to consume increasing levels of computing performance to maintain or attain a competitive advantage. However, until recently most IT departments never related this exponential growth of processing power to how it affects power consumption. The fact is the ratio of processor performance with respect to power has increased significantly over the last several years. In other words, the processor manufacturers have made some significant technology breakthroughs to increase the performance of the processor while consuming less power. The actual culprit of the power consumption issue is related to the exponential growth in power densities. Processor manufacturers such as Intel and AMD are making the processors smaller and denser, such that server manufacturers can incorporate a greater number of processors in a smaller footprint. Data collected by Intel Corporation has shown that current processor technology consumes 24 percent of the power consumption to execute the same workload in roughly the same time period as processor technology used in That s less than onequarter of the power consumption of less than a decade ago. However, the power density (the amount of electric power consumed by the computer chip) has increased by a factor of 16X during the same period, which creates the fundamental cooling problem from the chip throughout the critical computing environment. Virtualization software has also significantly reduced power consumption in the data center by taking advantage of underutilized processing power within each server; in effect consolidating many physical servers into one. However, although the total power consumption considerably decreases with virtualization, the power density per physical server increases. These strategies provide tremendous impact in reducing energy consumption; the challenge is that these technological advances come with a cost. With increasing power densities per cabinet, traditional computer room cooling designs cannot prevent server exhaust recirculation and thus become unreliable as a means of cooling. Closed-Loop Heat Containment: What is a Closed-Loop Design? The legacy data center is an open system where air is allowed to move freely throughout the data center. A closed-loop design is a solution whereby all the air supplied by the computer-room air conditioners is delivered to the intakes of the rack-mounted computing equipment and all the hot air exhaust is delivered directly back to the intake of the air-conditioning system. 3

4 There are essentially two current methods available for achieving a closed-loop design. Cold-air containment. A cold-air containment system is one in which the cold air supply from the computer room air-conditioning unit is isolated, and the hot air is allowed to move freely throughout the room. This can be done by completely isolating the cold aisle in the data center or using a ducted enclosed channel attached to the front of the enclosure that draws cold air directly to the server intakes. Heat containment. Heat containment is achieved by capturing all the hot air that is exhausted from the rackmounted computing equipment and directing it to the intake of the computer room air conditioner without any cold air contamination. This can be accomplished by enclosing the hot aisle or enclosures and having a heat-rejection system pump the heat from these contained units out of the data center. Conversely, a ducting system that directs the hot air from the rear of the rack enclosure to the air-conditioner intakes can also be used. Closed-Loop Heat Containment Solutions Closed-loop design is an adaptive concept built on the premise of providing customers with ease of deployment that integrates with existing infrastructure. Not unlike LEGO building blocks, once the foundation is created, all the other pieces fit together. Once an adaptable enclosure frame is installed there are several solutions available to the customer. Each solution has its benefits to meet the customer s requirements. Passive exhaust system. This containment system incorporates a chimney attached to the back of an adaptable frame enclosure. In this case, the chimney is designed over the rear corner of the rack to ensure access to overhead cable management such as ladder trays. The heat containment system relies on all the hot-air exhaust to be directed through the chimney, thus much attention has been placed on minimizing any air leaks in the cabinet. The rack must be deployed with a sealed solid back door and a cover must be used on other exposed areas to ensure the air exhaust does not leak outside the cabinet. The passive system is dependent on computing equipment exhaust fans to deliver enough volume of airflow to pass through the chimney. Thus, in a passive exhaust system, one needs to be cognizant of potential pressurized backflow with lowflow exhaust configurations. Assisted exhaust system. This heat containment design uses fans within the attached enclosure chimney to assist the airflow through the ducted vent. This system should be used in conjunction with a fan speed controller to optimize the airflow volume within the rack. One of the advantages of the assisted system is the ability to control the flow of air. If the server exhaust is not strong enough, air from the surrounding room or the plenum can enter into the rear rack, causing remixing. The key strategy in using an assisted exhaust-based system is to control the flow of air such that there is a slight negative pressure at the very top of the enclosure and a zero static pressure throughout the rest of the rear portion of the rack. This strategy will optimize airflow performance to ensure the heat is exhausted, eliminating the risk of backflow. Application of Heat-Containment System Closed-loop heat containment solutions are designed to adapt to existing infrastructures and provide a solution for greenfield applications. The application of heat containment systems increase efficiencies within the data center by reducing bypass airflow and recirculation, thus allowing the heat to flow directly to the air-conditioner intakes. To achieve heat containment with the active- or passiveducted exhaust option, the hot air exhaust that flows through the enclosure s chimney attachment must be used in conjunction with other facilities to continue the flow directly back to the precision air-conditioner intakes without remixing. There are effectively two methods to achieve this task. Extending the adaptable enclosure s rear duct to a plenum ceiling. A closed-loop system can be attained by extending the rear duct from the back of the frame to a drop-ceiling plenum and adding a ducted return from the ceiling plenum back to the air-conditioner intakes. If a drop ceiling is in place, it has the advantage of minimizing the costs of building out a dedicated ducted heat return. Direct-ducted exhaust return. If no plenum ceiling exists, it may be possible to duct the hot air exhaust directly back to the air-conditioner intakes. This has the advantage of providing a more controlled heating, ventilating, and air conditioning (HVAC) environment, since the air path is 100 percent dedicated to heat containment. 4

5 Quantifying Closed-Loop Efficiencies Recent articles make generalizations about an enclosure s ability to cool based on power densities within the rack. Specifically, the enclosure is essentially a passive device 3 that doesn t provide any cooling. Thermally, the function of the enclosure is to ensure that adequate airflow can be provided to computing equipment intakes and that the heat generated from the equipment is not trapped within the enclosure. However, with the recent increases in power densities and data center energy costs, the enclosure has evolved into a critical piece of the data center and now needs to be a part of an integrated strategy for achieving greater efficiencies. The foundations of closed loop design efficiency savings can be established by optimizing four conditions: 1. Provide consistent air temperature between 64.4 F and 80.6 F to all computing equipment (this is a statement of reliability as provided by ASHRAE TC9.9). 2. Ensure the air temperature leaving the server exhaust matches as closely as possible the intake temperature of the computer room air conditioner. 3. Make certain there is sufficient air flowing to the inlets of all the computing equipment. 4. Ensure the computer room is sealed as much as possible and avoid air leakages wherever they occur. In open legacy infrastructures, the only way to maintain ASHRAE s recommended temperature range for reliability in high-density environments is to oversupply the amount of cooling in the room. In some cases this can be as much as 50 percent of the necessary airflow required. Therefore, the cost of ensuring reliability comes by reducing the overall efficiency and significantly increasing the amount of bypass airflow in the room. On the other hand, by supplying only the necessary amount of volumetric airflow, the traditional data center cooling design cannot prevent the server exhaust from feeding back to the device inlets, thus reducing the reliability of the IT equipment. In a legacy data center, there is a tradeoff between efficiency and reliability; increasing one negatively affects the other. In a closed-loop heat containment system, because the hot and cold air streams are isolated, there is little effect on recirculation as the cooling supply is optimized to meet demand requirements and thus there is no reliability penalty when increasing efficiency. In traditional data centers, cold air is supplied from the precision air conditioners at very cold temperatures (approximately 55ºF). The reason the air is supplied at such cold temperatures is to counter the effects of high temperatures detected at the top of many enclosures caused by hot and cold air remixing. However, if the heat can be contained and not remixed with the cold air, there is no reason to supply such cold temperatures under the raised floor. Studies have shown that increasing the chilled water supply temperature from 45ºF to 55ºF, or by raising the air supply temperature to 65ºF, will achieve a 16 percent energy savings consumed by the chiller. 4 Closed-loop heat containment systems can further increase efficiency when combined with air-side economizers. During the appropriate seasonal conditions, outside air can be used to cool the data center as opposed to consuming large amounts of energy using mechanical cooling. Providing the outdoor environment has favorable humidification conditions, significant energy savings can be attained by taking advantage of the hours during the year that both the supply and return temperatures are higher than the outside air. In a legacy environment, the typical supply and return temperatures are 54ºF and 70ºF. In contrast, the closed-loop heat containment system could typically have supply and return temperatures between 68ºF and 95ºF. Depending on location, this can have a tremendous effect on the number of hours necessary to provide mechanical cooling in the data center. For example, a city such as Los Angeles can use economized cooling 86 percent of the hours in a year if 3 With the exceptions of enclosures that include internal heat exchangers 4 A Strategic Approach to Datacenter Cooling, by Dr. James Fulton, Associate Professor of Mathematics, Suffolk County Community College, Selden, New York. April

6 the supply temperature is above 70ºF. However, if the supply temperature is below 53ºF, it can only use full air side economization cycles 6 percent of the hours in a year. 5 Thus, substantial savings can be achieved by increasing the supply return temperatures and a closed-loop heat containment solution can effectively deliver the result, while ensuring the reliability of the IT equipment. About the Author Brent Goren, PE, is a data center consultant with Wright Line, where he provides technical expertise to assist clients in designing scalable, reliable, and efficient data centers. Brent has in-depth knowledge in both power and cooling in the data center and, most recently, has taken a lead role in building a practice surrounding computational fluid dynamics (CFD) modeling and airflow management. Brent has over 15 years experience working within IT environments in various roles and capacities, with the last three years prior to working with Wright Line dedicated to data center consolidation and relocation projects. Brent received his BA in Electrical Engineering, from the University of Manitoba. Mr. Goren can be reached at brent.goran@wrightline.com. About Wright Line Wright Line provides a wide range of innovative data center solutions developed through direct collaboration with its customers. From server enclosures and power distribution units (PDUs) to its new patent-pending heat containment system, Wright Line can help you improve your data center infrastructure efficiency (DCiE) and power usage effectiveness (PUE). Wright Line doesn t advocate a one-size-fits-all product development methodology, but rather a consultative, collaborative approach that maximizes your data center operations. Its industry-leading enclosures, coupled with its broad range of accessories, power distribution, keyboard/video display/mouse (KVM) switches and monitoring products, are designed to store, cool, power, manage and secure your mission-critical equipment. About the Uptime Institute Uptime Institute is a leading global authority on data centers. Since 1993, it has provided education, consulting, knowledge networks, and expert advisory for data center Facilities and IT organizations interested in maximizing site infrastructure uptime availability. It has pioneered numerous industry innovations, including the Tier Classification System for data center availability, which serves as a de facto industry standard. Site Uptime Network is a private knowledge network with 100 global corporate and government members, mostly at the scale of Fortune 100-sized organizations in North America and EMEA. In 2008, the Institute launched an individual Institute membership program. For the industry as a whole, the Institute certifies data center Tier level and site resiliency, provides site sustainability assessments, and assists data center owners in planning and justifying data center projects. It publishes papers and reports, offers seminars, and produces an annual Green Enterprise IT Symposium, the premier event in the field focused primarily on improving enterprise IT and data center computing energy efficiency. It also sponsors the annual Green Enterprise IT Awards and the Global Green 100 programs. The Institute conducts custom surveys, research and product certifications for industry manufacturers. All Institute published materials are 2009 Uptime Institute, Inc., and protected by international copyright law, all rights reserved, for all media and all uses. Written permission is required to reproduce all or any portion of the Institute s literature for any purpose. To download the reprint permission request form, uptimeinstitute.org/resources. Uptime Institute, Inc Rodeo Park Drive East Building 100 Santa Fe, NM Corporate Offices: Fax: uptimeinstitute.org 2009 Uptime Institute, Inc. and Wright Line 5 Data from Best Practices for Datacom Facility Energy Efficiency ASHRAE Series, ISBN

Measuring Power in your Data Center

Measuring Power in your Data Center RESEARCH UNDERWRITER WHITE PAPER LEAN, CLEAN & GREEN Raritan Measuring Power in your Data Center Herman Chan, Director, Power Solutions Business Unit, and Greg More, Senior Product Marketing Manager There

More information

Rack Hygiene. Data Center White Paper. Executive Summary

Rack Hygiene. Data Center White Paper. Executive Summary Data Center White Paper Rack Hygiene April 14, 2011 Ed Eacueo Data Center Manager Executive Summary This paper describes the concept of Rack Hygiene, which positions the rack as an airflow management device,

More information

Benefits of. Air Flow Management. Data Center

Benefits of. Air Flow Management. Data Center Benefits of Passive Air Flow Management in the Data Center Learning Objectives At the end of this program, participants will be able to: Readily identify if opportunities i where networking equipment

More information

Three Steps To Perfectly Green

Three Steps To Perfectly Green R E S E A R C H U N D E R W R I T E R W H I T E P A P E R LEAN, CLEAN & GREEN Deerns Consulting Engineers Three Steps To Perfectly Green By Wouter M. Kok, Manager, Cleanroom, Laboratory, and Data Center

More information

Dealing with Thermal Issues in Data Center Universal Aisle Containment

Dealing with Thermal Issues in Data Center Universal Aisle Containment Dealing with Thermal Issues in Data Center Universal Aisle Containment Daniele Tordin BICSI RCDD Technical System Engineer - Panduit Europe Daniele.Tordin@Panduit.com AGENDA Business Drivers Challenges

More information

Managing Data Centre Heat Issues

Managing Data Centre Heat Issues Managing Data Centre Heat Issues Victor Banuelos Field Applications Engineer Chatsworth Products, Inc. 2010 Managing Data Centre Heat Issues Thermal trends in the data centre Hot Aisle / Cold Aisle design

More information

Unified Physical Infrastructure (UPI) Strategies for Thermal Management

Unified Physical Infrastructure (UPI) Strategies for Thermal Management Unified Physical Infrastructure (UPI) Strategies for Thermal Management The Importance of Air Sealing Grommets to Improving Smart www.panduit.com WP-04 August 2008 Introduction One of the core issues affecting

More information

How to Meet 24 by Forever Cooling Demands of your Data Center

How to Meet 24 by Forever Cooling Demands of your Data Center W h i t e P a p e r How to Meet 24 by Forever Cooling Demands of your Data Center Three critical aspects that are important to the operation of computer facilities are matching IT expectations with the

More information

How To Run A Data Center Efficiently

How To Run A Data Center Efficiently A White Paper from the Experts in Business-Critical Continuity TM Data Center Cooling Assessments What They Can Do for You Executive Summary Managing data centers and IT facilities is becoming increasingly

More information

Unified Physical Infrastructure SM (UPI) Strategies for Smart Data Centers

Unified Physical Infrastructure SM (UPI) Strategies for Smart Data Centers Unified Physical Infrastructure SM (UPI) Strategies for Smart Data Centers Deploying a Vertical Exhaust System www.panduit.com WP-09 September 2009 Introduction Business management applications and rich

More information

Supporting Cisco Switches In Hot Aisle/Cold Aisle Data Centers

Supporting Cisco Switches In Hot Aisle/Cold Aisle Data Centers CABINETS: ENCLOSED THERMAL MOUNTING MANAGEMENT SYSTEMS WHITE PAPER Supporting Cisco Switches In Hot Aisle/Cold Aisle Data Centers 800-834-4969 techsupport@chatsworth.com www.chatsworth.com All products

More information

DataCenter 2020: first results for energy-optimization at existing data centers

DataCenter 2020: first results for energy-optimization at existing data centers DataCenter : first results for energy-optimization at existing data centers July Powered by WHITE PAPER: DataCenter DataCenter : first results for energy-optimization at existing data centers Introduction

More information

Data center upgrade proposal. (phase one)

Data center upgrade proposal. (phase one) Data center upgrade proposal (phase one) Executive Summary Great Lakes began a recent dialogue with a customer regarding current operations and the potential for performance improvement within the The

More information

Hot Air Isolation Cools High-Density Data Centers By: Ian Seaton, Technology Marketing Manager, Chatsworth Products, Inc.

Hot Air Isolation Cools High-Density Data Centers By: Ian Seaton, Technology Marketing Manager, Chatsworth Products, Inc. Business Management Magazine Winter 2008 Hot Air Isolation Cools High-Density Data Centers By: Ian Seaton, Technology Marketing Manager, Chatsworth Products, Inc. Contrary to some beliefs, air is quite

More information

Reducing Room-Level Bypass Airflow Creates Opportunities to Improve Cooling Capacity and Operating Costs

Reducing Room-Level Bypass Airflow Creates Opportunities to Improve Cooling Capacity and Operating Costs WHITE PAPER Reducing Room-Level Bypass Airflow Creates Opportunities to Improve Cooling Capacity and Operating Costs By Lars Strong, P.E., Upsite Technologies, Inc. 505.798.000 upsite.com Reducing Room-Level

More information

Power and Cooling for Ultra-High Density Racks and Blade Servers

Power and Cooling for Ultra-High Density Racks and Blade Servers Power and Cooling for Ultra-High Density Racks and Blade Servers White Paper #46 Introduction The Problem Average rack in a typical data center is under 2 kw Dense deployment of blade servers (10-20 kw

More information

Choosing Close-Coupled IT Cooling Solutions

Choosing Close-Coupled IT Cooling Solutions W H I T E P A P E R Choosing Close-Coupled IT Cooling Solutions Smart Strategies for Small to Mid-Size Data Centers Executive Summary As high-density IT equipment becomes the new normal, the amount of

More information

Energy Efficiency Opportunities in Federal High Performance Computing Data Centers

Energy Efficiency Opportunities in Federal High Performance Computing Data Centers Energy Efficiency Opportunities in Federal High Performance Computing Data Centers Prepared for the U.S. Department of Energy Federal Energy Management Program By Lawrence Berkeley National Laboratory

More information

Thermal Optimisation in the Data Centre

Thermal Optimisation in the Data Centre Thermal Optimisation in the Data Centre Best Practices for achieving optimal cooling performance and significant energy savings in your data centre 1. Thermal analysis 2. Cold-Aisle-Containment 3. Seal

More information

AisleLok Modular Containment vs. Legacy Containment: A Comparative CFD Study of IT Inlet Temperatures and Fan Energy Savings

AisleLok Modular Containment vs. Legacy Containment: A Comparative CFD Study of IT Inlet Temperatures and Fan Energy Savings WH I TE PAPE R AisleLok Modular Containment vs. : A Comparative CFD Study of IT Inlet Temperatures and Fan Energy Savings By Bruce Long, Upsite Technologies, Inc. Lars Strong, P.E., Upsite Technologies,

More information

White Paper. Data Center Containment Cooling Strategies. Abstract WHITE PAPER EC9001. Geist Updated August 2010

White Paper. Data Center Containment Cooling Strategies. Abstract WHITE PAPER EC9001. Geist Updated August 2010 White Paper Data Center Containment Cooling Strategies WHITE PAPER EC9001 Geist Updated August 2010 Abstract Deployment of high density IT equipment into data center infrastructure is now a common occurrence

More information

How Row-based Data Center Cooling Works

How Row-based Data Center Cooling Works How Row-based Data Center Cooling Works White Paper 208 Revision 0 by Paul Lin and Victor Avelar Executive summary Row-based data center cooling is normally regarded as a cold air supply architecture that

More information

Optimizing Network Performance through PASSIVE AIR FLOW MANAGEMENT IN THE DATA CENTER

Optimizing Network Performance through PASSIVE AIR FLOW MANAGEMENT IN THE DATA CENTER Optimizing Network Performance through PASSIVE AIR FLOW MANAGEMENT IN THE DATA CENTER Lylette Macdonald, RCDD Legrand Ortronics BICSI Baltimore 2011 Agenda: Discuss passive thermal management at the Rack

More information

Data Centre Cooling Air Performance Metrics

Data Centre Cooling Air Performance Metrics Data Centre Cooling Air Performance Metrics Sophia Flucker CEng MIMechE Ing Dr Robert Tozer MSc MBA PhD CEng MCIBSE MASHRAE Operational Intelligence Ltd. info@dc-oi.com Abstract Data centre energy consumption

More information

Improving Rack Cooling Performance Using Airflow Management Blanking Panels

Improving Rack Cooling Performance Using Airflow Management Blanking Panels Improving Rack Cooling Performance Using Airflow Management Blanking Panels By Neil Rasmussen White Paper #44 Revision 3 Executive Summary Unused vertical space in open frame racks and rack enclosures

More information

Cooling Capacity Factor (CCF) Reveals Stranded Capacity and Data Center Cost Savings

Cooling Capacity Factor (CCF) Reveals Stranded Capacity and Data Center Cost Savings WHITE PAPER Cooling Capacity Factor (CCF) Reveals Stranded Capacity and Data Center Cost Savings By Lars Strong, P.E., Upsite Technologies, Inc. Kenneth G. Brill, Upsite Technologies, Inc. 505.798.0200

More information

Selecting Rack-Mount Power Distribution Units For High-Efficiency Data Centers

Selecting Rack-Mount Power Distribution Units For High-Efficiency Data Centers C P I P O W E R M A N A G E M E N T WHITE PAPER Selecting Rack-Mount Power Distribution Units For High-Efficiency Data Centers By Anderson Hungria Sr. Product Manager of Power, Electronics & Software Published

More information

Education Evolution: Scalable Server Rooms George Lantouris Client Relationship Manager (Education) May 2009

Education Evolution: Scalable Server Rooms George Lantouris Client Relationship Manager (Education) May 2009 Education Evolution: Scalable Server Rooms George Lantouris Client Relationship Manager (Education) May 2009 Agenda Overview - Network Critical Physical Infrastructure Cooling issues in the Server Room

More information

Data Center Components Overview

Data Center Components Overview Data Center Components Overview Power Power Outside Transformer Takes grid power and transforms it from 113KV to 480V Utility (grid) power Supply of high voltage power to the Data Center Electrical Room

More information

High Density Data Centers Fraught with Peril. Richard A. Greco, Principal EYP Mission Critical Facilities, Inc.

High Density Data Centers Fraught with Peril. Richard A. Greco, Principal EYP Mission Critical Facilities, Inc. High Density Data Centers Fraught with Peril Richard A. Greco, Principal EYP Mission Critical Facilities, Inc. Microprocessors Trends Reprinted with the permission of The Uptime Institute from a white

More information

APC APPLICATION NOTE #112

APC APPLICATION NOTE #112 #112 Best Practices for Deploying the InfraStruXure InRow SC By David Roden Abstract The InfraStruXure InRow SC (ACSC100 and ACSC101) is a self-contained air conditioner for server rooms and wiring closets.

More information

Environmental Data Center Management and Monitoring

Environmental Data Center Management and Monitoring 2013 Raritan Inc. Table of Contents Introduction Page 3 Sensor Design Considerations Page 3 Temperature and Humidity Sensors Page 4 Airflow Sensor Page 6 Differential Air Pressure Sensor Page 6 Water Sensor

More information

Ten Steps to Solving Cooling Problems Caused by High- Density Server Deployment

Ten Steps to Solving Cooling Problems Caused by High- Density Server Deployment Ten Steps to Solving Cooling Problems Caused by High- Density Server Deployment By Peter Hannaford White Paper #42 Revision 1 Executive Summary High-density servers present a significant cooling challenge.

More information

Great Lakes Data Room Case Study

Great Lakes Data Room Case Study Great Lakes Data Room Case Study WeRackYourWorld.com Problem: During a warm summer period in 2008, Great Lakes experienced a network outage due to a switch failure in the network enclosure. After an equipment

More information

APC APPLICATION NOTE #92

APC APPLICATION NOTE #92 #92 Best Practices for Designing Data Centers with the InfraStruXure InRow RC By John Niemann Abstract The InfraStruXure InRow RC is designed to provide cooling at the row and rack level of a data center

More information

Small Data / Telecommunications Room on Slab Floor

Small Data / Telecommunications Room on Slab Floor Small Data / Telecommunications Room on Slab Floor Small Data / Telecommunications Room on Slab Floor During a warm summer period in 2008, Great Lakes experienced a network outage due to a switch failure

More information

Improving Rack Cooling Performance Using Airflow Management Blanking Panels

Improving Rack Cooling Performance Using Airflow Management Blanking Panels Improving Rack Cooling Performance Using Airflow Management Blanking Panels White Paper 44 Revision 4 by Neil Rasmussen > Executive summary Unused vertical space in open frame racks and rack enclosures

More information

Rethinking Data Center Design

Rethinking Data Center Design Rethinking Data Center Design Building the room around the rack can ease cooling challenges and save money By John Collins Segment Manager, Data Centers Eaton Corporation Executive summary For decades,

More information

AIR-SITE GROUP. White Paper. Green Equipment Room Practices

AIR-SITE GROUP. White Paper. Green Equipment Room Practices AIR-SITE GROUP White Paper Green Equipment Room Practices www.air-site.com Common practices to build a green equipment room 1 Introduction Air-Site (www.air-site.com) is a leading international provider

More information

THE GREEN DATA CENTER

THE GREEN DATA CENTER GREEN IT THE GREEN DATA CENTER WHERE ECOLOGY MEETS ECONOMY We truly live in an information age. Data Centers serve a very important purpose they provide the global community with nearly unlimited access

More information

GUIDE TO ICT SERVER ROOM ENERGY EFFICIENCY. Public Sector ICT Special Working Group

GUIDE TO ICT SERVER ROOM ENERGY EFFICIENCY. Public Sector ICT Special Working Group GUIDE TO ICT SERVER ROOM ENERGY EFFICIENCY Public Sector ICT Special Working Group SERVER ROOM ENERGY EFFICIENCY This guide is one of a suite of documents that aims to provide guidance on ICT energy efficiency.

More information

Specialty Environment Design Mission Critical Facilities

Specialty Environment Design Mission Critical Facilities Brian M. Medina PE Associate Brett M. Griffin PE, LEED AP Vice President Environmental Systems Design, Inc. Mission Critical Facilities Specialty Environment Design Mission Critical Facilities March 25,

More information

Rittal Liquid Cooling Series

Rittal Liquid Cooling Series Rittal Liquid Cooling Series by Herb Villa White Paper 04 Copyright 2006 All rights reserved. Rittal GmbH & Co. KG Auf dem Stützelberg D-35745 Herborn Phone +49(0)2772 / 505-0 Fax +49(0)2772/505-2319 www.rittal.de

More information

Power and Cooling Guidelines for Deploying IT in Colocation Data Centers

Power and Cooling Guidelines for Deploying IT in Colocation Data Centers Power and Cooling Guidelines for Deploying IT in Colocation Data Centers White Paper 173 Revision 0 by Paul Lin and Victor Avelar Executive summary Some prospective colocation data center tenants view

More information

- White Paper - Data Centre Cooling. Best Practice

- White Paper - Data Centre Cooling. Best Practice - White Paper - Data Centre Cooling Best Practice Release 2, April 2008 Contents INTRODUCTION... 3 1. AIR FLOW LEAKAGE... 3 2. PERFORATED TILES: NUMBER AND OPENING FACTOR... 4 3. PERFORATED TILES: WITH

More information

Cooling Capacity Factor (CCF) Reveals Stranded Capacity and Data Center Cost Savings

Cooling Capacity Factor (CCF) Reveals Stranded Capacity and Data Center Cost Savings WHITE PAPER Cooling Capacity Factor (CCF) Reveals Stranded Capacity and Data Center Cost Savings By Kenneth G. Brill, Upsite Technologies, Inc. Lars Strong, P.E., Upsite Technologies, Inc. 505.798.0200

More information

Center Thermal Management Can Live Together

Center Thermal Management Can Live Together Network Management age e and Data Center Thermal Management Can Live Together Ian Seaton Chatsworth Products, Inc. Benefits of Hot Air Isolation 1. Eliminates reliance on thermostat 2. Eliminates hot spots

More information

A Comparative Study of Various High Density Data Center Cooling Technologies. A Thesis Presented. Kwok Wu. The Graduate School

A Comparative Study of Various High Density Data Center Cooling Technologies. A Thesis Presented. Kwok Wu. The Graduate School A Comparative Study of Various High Density Data Center Cooling Technologies A Thesis Presented by Kwok Wu to The Graduate School in Partial Fulfillment of the Requirements for the Degree of Master of

More information

Raised Floor Data Centers Prepared for the Future

Raised Floor Data Centers Prepared for the Future Raised Floor Data Centers Prepared for the Future Raised Floors Protect My Investment by Providing a Foundation for Current and Future Technologies. Creating the Future Proof Data Center Environment The

More information

IMPROVING DATA CENTER EFFICIENCY AND CAPACITY WITH AISLE CONTAINMENT

IMPROVING DATA CENTER EFFICIENCY AND CAPACITY WITH AISLE CONTAINMENT DATA CENTER RESOURCES WHITE PAPER IMPROVING DATA CENTER EFFICIENCY AND CAPACITY WITH AISLE CONTAINMENT BY: STEVE HAMBRUCH EXECUTIVE SUMMARY Data centers have experienced explosive growth in the last decade.

More information

DataCenter 2020: hot aisle and cold aisle containment efficiencies reveal no significant differences

DataCenter 2020: hot aisle and cold aisle containment efficiencies reveal no significant differences DataCenter 2020: hot aisle and cold aisle containment efficiencies reveal no significant differences November 2011 Powered by DataCenter 2020: hot aisle and cold aisle containment efficiencies reveal no

More information

Data Center Power Consumption

Data Center Power Consumption Data Center Power Consumption A new look at a growing problem Fact - Data center power density up 10x in the last 10 years 2.1 kw/rack (1992); 14 kw/rack (2007) Racks are not fully populated due to power/cooling

More information

Airflow Management Solutions

Airflow Management Solutions Data Center Products Airflow Management Solutions Switch N to Eaton. Computational Fluid Dynamics (CFD) model of an optimized data center illustrating cold-aisle isolation and Eaton s Heat Containment

More information

Data Center Rack Level Cooling Utilizing Water-Cooled, Passive Rear Door Heat Exchangers (RDHx) as a Cost Effective Alternative to CRAH Air Cooling

Data Center Rack Level Cooling Utilizing Water-Cooled, Passive Rear Door Heat Exchangers (RDHx) as a Cost Effective Alternative to CRAH Air Cooling Data Center Rack Level Cooling Utilizing Water-Cooled, Passive Rear Door Heat Exchangers (RDHx) as a Cost Effective Alternative to CRAH Air Cooling Joshua Grimshaw Director of Engineering, Nova Corporation

More information

Data Center 2020: Delivering high density in the Data Center; efficiently and reliably

Data Center 2020: Delivering high density in the Data Center; efficiently and reliably Data Center 2020: Delivering high density in the Data Center; efficiently and reliably March 2011 Powered by Data Center 2020: Delivering high density in the Data Center; efficiently and reliably Review:

More information

Layer Zero. for the data center

Layer Zero. for the data center Layer Zero for the data center Preparefor the Data centers are the foundations of enterprises, vital to the daily operation of the entire organization - they no longer simply store data. Virtualization,

More information

Case Study: Opportunities to Improve Energy Efficiency in Three Federal Data Centers

Case Study: Opportunities to Improve Energy Efficiency in Three Federal Data Centers Case Study: Opportunities to Improve Energy Efficiency in Three Federal Data Centers Prepared for the U.S. Department of Energy s Federal Energy Management Program Prepared By Lawrence Berkeley National

More information

Green Data Centre Design

Green Data Centre Design Green Data Centre Design A Holistic Approach Stantec Consulting Ltd. Aleks Milojkovic, P.Eng., RCDD, LEED AP Tommy Chiu, EIT, RCDD, LEED AP STANDARDS ENERGY EQUIPMENT MATERIALS EXAMPLES CONCLUSION STANDARDS

More information

Cooling Audit for Identifying Potential Cooling Problems in Data Centers

Cooling Audit for Identifying Potential Cooling Problems in Data Centers Cooling Audit for Identifying Potential Cooling Problems in Data Centers By Kevin Dunlap White Paper #40 Revision 2 Executive Summary The compaction of information technology equipment and simultaneous

More information

Liquid Cooling Solutions for DATA CENTERS - R.M.IYENGAR BLUESTAR LIMITED.

Liquid Cooling Solutions for DATA CENTERS - R.M.IYENGAR BLUESTAR LIMITED. Liquid Cooling Solutions for DATA CENTERS - R.M.IYENGAR BLUESTAR LIMITED. Presentation Goals & Outline Power Density Where we have been- where we are now - where we are going Limitations of Air Cooling

More information

How To Cool A Data Center

How To Cool A Data Center Overview and Design of Data Center Cabinets In today s technology-dependent world, a reliably operating data center is a core necessity for small and large businesses alike. Without properly running network

More information

Data Center Cooling: Fend Off The Phantom Meltdown Of Mass Destruction. 670 Deer Road n Cherry Hill, NJ 08034 n 877.429.7225 n

Data Center Cooling: Fend Off The Phantom Meltdown Of Mass Destruction. 670 Deer Road n Cherry Hill, NJ 08034 n 877.429.7225 n Data Center Cooling: Fend Off The Phantom Meltdown Of Mass Destruction How To Preserve Your Servers And Prevent Overheating Your high-performance, multiprocessor servers are working hard, computing tons

More information

Technology Corporation

Technology Corporation 1 White Paper Meeting The Increased Demand For Efficient Computer Room Cooling Server Cooling Problems: An Overview As microprocessors and other electronic components in servers grow more powerful, they

More information

IT White Paper MANAGING EXTREME HEAT: COOLING STRATEGIES FOR HIGH-DENSITY SYSTEMS

IT White Paper MANAGING EXTREME HEAT: COOLING STRATEGIES FOR HIGH-DENSITY SYSTEMS IT White Paper MANAGING EXTREME HEAT: COOLING STRATEGIES FOR HIGH-DENSITY SYSTEMS SUMMARY As computer manufacturers pack more and more processing power into smaller packages, the challenge of data center

More information

Verizon SMARTS Data Center Design Phase 1 Conceptual Study Report Ms. Leah Zabarenko Verizon Business 2606A Carsins Run Road Aberdeen, MD 21001

Verizon SMARTS Data Center Design Phase 1 Conceptual Study Report Ms. Leah Zabarenko Verizon Business 2606A Carsins Run Road Aberdeen, MD 21001 Verizon SMARTS Data Center Design Phase 1 Conceptual Study Report Ms. Leah Zabarenko Verizon Business 2606A Carsins Run Road Aberdeen, MD 21001 Presented by: Liberty Engineering, LLP 1609 Connecticut Avenue

More information

Overview & Design of Data Center Cabinets

Overview & Design of Data Center Cabinets Overview & Design of Data Center Cabinets Power & Cooling Overview pg. 3 Enclosure Overview & Discussion pg. 9 Cabinet Configurations pg. 14 Best Practices pg. 28 2 2 2 2 OVERVIEW & DESIGN OF In today

More information

Driving Data Center Efficiency Through the Adoption of Best Practices

Driving Data Center Efficiency Through the Adoption of Best Practices Data Center Solutions 2008 Driving Data Center Efficiency Through the Adoption of Best Practices Data Center Solutions Driving Data Center Efficiency Through the Adoption of Best Practices Executive Summary

More information

Using Simulation to Improve Data Center Efficiency

Using Simulation to Improve Data Center Efficiency A WHITE PAPER FROM FUTURE FACILITIES INCORPORATED Using Simulation to Improve Data Center Efficiency Cooling Path Management for maximizing cooling system efficiency without sacrificing equipment resilience

More information

2006 APC corporation. Cooling Solutions and Selling Strategies for Wiring Closets and Small IT Rooms

2006 APC corporation. Cooling Solutions and Selling Strategies for Wiring Closets and Small IT Rooms Cooling Solutions and Selling Strategies for Wiring Closets and Small IT Rooms Agenda Review of cooling challenge and strategies Solutions to deal with wiring closet cooling Opportunity and value Power

More information

Free Cooling in Data Centers. John Speck, RCDD, DCDC JFC Solutions

Free Cooling in Data Centers. John Speck, RCDD, DCDC JFC Solutions Free Cooling in Data Centers John Speck, RCDD, DCDC JFC Solutions Why this topic Many data center projects or retrofits do not have a comprehensive analyses of systems power consumption completed in the

More information

Combining Cold Aisle Containment with Intelligent Control to Optimize Data Center Cooling Efficiency

Combining Cold Aisle Containment with Intelligent Control to Optimize Data Center Cooling Efficiency A White Paper from the Experts in Business-Critical Continuity TM Combining Cold Aisle Containment with Intelligent Control to Optimize Data Center Cooling Efficiency Executive Summary Energy efficiency

More information

Improving Data Center Energy Efficiency Through Environmental Optimization

Improving Data Center Energy Efficiency Through Environmental Optimization Improving Data Center Energy Efficiency Through Environmental Optimization How Fine-Tuning Humidity, Airflows, and Temperature Dramatically Cuts Cooling Costs William Seeber Stephen Seeber Mid Atlantic

More information

Element D Services Heating, Ventilating, and Air Conditioning

Element D Services Heating, Ventilating, and Air Conditioning PART 1 - GENERAL 1.01 OVERVIEW A. This section supplements Design Guideline Element D3041 on air handling distribution with specific criteria for projects involving design of a Data Center spaces B. Refer

More information

Reducing the Annual Cost of a Telecommunications Data Center

Reducing the Annual Cost of a Telecommunications Data Center Applied Math Modeling White Paper Reducing the Annual Cost of a Telecommunications Data Center By Paul Bemis and Liz Marshall, Applied Math Modeling Inc., Concord, NH March, 2011 Introduction The facilities

More information

Rack Blanking Panels To Fill or Not to Fill

Rack Blanking Panels To Fill or Not to Fill Rack Blanking Panels To Fill or Not to Fill A Dell Technical White Paper Dell Data Center Infrastructure David L. Moss Joyce F. Ruff Learn more at Dell.com/PowerEdge/Rack THIS WHITE PAPER IS FOR INFORMATIONAL

More information

Blade Servers and Beyond: Adaptive Cooling for the Next Generation of IT Systems. A White Paper from the Experts in Business-Critical Continuity

Blade Servers and Beyond: Adaptive Cooling for the Next Generation of IT Systems. A White Paper from the Experts in Business-Critical Continuity Blade Servers and Beyond: Adaptive Cooling for the Next Generation of IT Systems A White Paper from the Experts in Business-Critical Continuity Executive Summary In enterprise data centers, designers face

More information

How To Improve Energy Efficiency Through Raising Inlet Temperatures

How To Improve Energy Efficiency Through Raising Inlet Temperatures Data Center Operating Cost Savings Realized by Air Flow Management and Increased Rack Inlet Temperatures William Seeber Stephen Seeber Mid Atlantic Infrared Services, Inc. 5309 Mohican Road Bethesda, MD

More information

CURBING THE COST OF DATA CENTER COOLING. Charles B. Kensky, PE, LEED AP BD+C, CEA Executive Vice President Bala Consulting Engineers

CURBING THE COST OF DATA CENTER COOLING. Charles B. Kensky, PE, LEED AP BD+C, CEA Executive Vice President Bala Consulting Engineers CURBING THE COST OF DATA CENTER COOLING Charles B. Kensky, PE, LEED AP BD+C, CEA Executive Vice President Bala Consulting Engineers OVERVIEW Compare Cooling Strategies in Free- Standing and In-Building

More information

Data Center Technology: Physical Infrastructure

Data Center Technology: Physical Infrastructure Data Center Technology: Physical Infrastructure IT Trends Affecting New Technologies and Energy Efficiency Imperatives in the Data Center Hisham Elzahhar Regional Enterprise & System Manager, Schneider

More information

Data Centers. Mapping Cisco Nexus, Catalyst, and MDS Logical Architectures into PANDUIT Physical Layer Infrastructure Solutions

Data Centers. Mapping Cisco Nexus, Catalyst, and MDS Logical Architectures into PANDUIT Physical Layer Infrastructure Solutions Data Centers Mapping Cisco Nexus, Catalyst, and MDS Logical Architectures into PANDUIT Physical Layer Infrastructure Solutions 1 Introduction The growing speed and footprint of data centers is challenging

More information

DATA CENTER ASSESSMENT SERVICES

DATA CENTER ASSESSMENT SERVICES DATA CENTER ASSESSMENT SERVICES ig2 Group Inc. is a Data Center Science Company which provides solutions that can help organizations automatically optimize their Data Center performance, from assets to

More information

Data Center Energy Profiler Questions Checklist

Data Center Energy Profiler Questions Checklist Data Center Energy Profiler Questions Checklist Step 1 Case Name Date Center Company State/Region County Floor Area Data Center Space Floor Area Non Data Center Space Floor Area Data Center Support Space

More information

Data Center Equipment Power Trends

Data Center Equipment Power Trends Green field data center design 11 Jan 2010 by Shlomo Novotny Shlomo Novotny, Vice President and Chief Technology Officer, Vette Corp. explores water cooling for maximum efficiency - Part 1 Overview Data

More information

Challenges In Intelligent Management Of Power And Cooling Towards Sustainable Data Centre

Challenges In Intelligent Management Of Power And Cooling Towards Sustainable Data Centre Challenges In Intelligent Management Of Power And Cooling Towards Sustainable Data Centre S. Luong 1*, K. Liu 2, James Robey 3 1 Technologies for Sustainable Built Environments, University of Reading,

More information

Sealing Gaps Under IT Racks: CFD Analysis Reveals Significant Savings Potential

Sealing Gaps Under IT Racks: CFD Analysis Reveals Significant Savings Potential TECHNICAL REPORT Sealing Gaps Under IT Racks: CFD Analysis Reveals Significant Savings Potential By Lars Strong, P.E., Upsite Technologies, Inc. Bruce Long, Upsite Technologies, Inc. +1.888.982.7800 upsite.com

More information

Enclosure and Airflow Management Solution

Enclosure and Airflow Management Solution Enclosure and Airflow Management Solution CFD Analysis Report Des Plaines, Illinois December 22, 2013 Matt Koukl- DECP Mission Critical Systems Affiliated Engineers, Inc. Contents Executive Summary...

More information

HIGHLY EFFICIENT COOLING FOR YOUR DATA CENTRE

HIGHLY EFFICIENT COOLING FOR YOUR DATA CENTRE HIGHLY EFFICIENT COOLING FOR YOUR DATA CENTRE Best practices for airflow management and cooling optimisation AIRFLOW MANAGEMENT COLD AND HOT AISLE CONTAINMENT DC ASSESSMENT SERVICES Achieving true 24/7/365

More information

The Efficient Enterprise. Juan Carlos Londoño Data Center Projects Engineer APC by Schneider Electric

The Efficient Enterprise. Juan Carlos Londoño Data Center Projects Engineer APC by Schneider Electric Ee The Efficient Enterprise Juan Carlos Londoño Data Center Projects Engineer APC by Schneider Electric Keystrokes Kilowatts Heat OUT Electricity IN Need for bandwidth exploding Going hyperbolic! 30,000

More information

Optimum Climate Control For Datacenter - Case Study. T. Prabu March 17 th 2009

Optimum Climate Control For Datacenter - Case Study. T. Prabu March 17 th 2009 Optimum Climate Control For Datacenter - Case Study T. Prabu March 17 th 2009 Agenda 2 About EDEC (Emerson) Facility Data Center Details Design Considerations & Challenges Layout Design CFD Analysis Of

More information

BICSInews. plus. july/august 2012. + Industrial-grade Infrastructure. + I Say Bonding, You Say Grounding + Data Center Containment.

BICSInews. plus. july/august 2012. + Industrial-grade Infrastructure. + I Say Bonding, You Say Grounding + Data Center Containment. BICSInews m a g a z i n e july/august 2012 Volume 33, Number 4 plus + Industrial-grade Infrastructure and Equipment + I Say Bonding, You Say Grounding + Data Center Containment & design deployment The

More information

2010 Best Practices. for the EU Code of Conduct on Data Centres. Version 2.0.0 Release Public Review Public

2010 Best Practices. for the EU Code of Conduct on Data Centres. Version 2.0.0 Release Public Review Public 2010 Best Practices for the EU Code of Conduct on Data Centres Version 2.0.0 Release Public Review Public 1 Document Information 1.1 Version History Version 1 Description Version Updates Date 2.0.0 2010

More information

WHITE PAPER. Creating the Green Data Center. Simple Measures to Reduce Energy Consumption

WHITE PAPER. Creating the Green Data Center. Simple Measures to Reduce Energy Consumption WHITE PAPER Creating the Green Data Center Simple Measures to Reduce Energy Consumption Introduction Energy Awareness Driving Decisions in the DataCenter The continued thirst for energy is a recurring

More information

Airflow Simulation Solves Data Centre Cooling Problem

Airflow Simulation Solves Data Centre Cooling Problem Airflow Simulation Solves Data Centre Cooling Problem The owner s initial design for a data centre in China utilized 40 equipment racks filled with blade servers spread out in three rows along the length

More information

GREEN FIELD DATA CENTER DESIGN WATER COOLING FOR MAXIMUM EFFICIENCY. Shlomo Novotny, Vice President and Chief Technology Officer, Vette Corp.

GREEN FIELD DATA CENTER DESIGN WATER COOLING FOR MAXIMUM EFFICIENCY. Shlomo Novotny, Vice President and Chief Technology Officer, Vette Corp. GREEN FIELD DATA CENTER DESIGN WATER COOLING FOR MAXIMUM EFFICIENCY Shlomo Novotny, Vice President and Chief Technology Officer, Vette Corp. Overview Data centers are an ever growing part of our economy.

More information

abstract about the GREEn GRiD

abstract about the GREEn GRiD Guidelines for Energy-Efficient Datacenters february 16, 2007 white paper 1 Abstract In this paper, The Green Grid provides a framework for improving the energy efficiency of both new and existing datacenters.

More information

Data Center Design Guide featuring Water-Side Economizer Solutions. with Dynamic Economizer Cooling

Data Center Design Guide featuring Water-Side Economizer Solutions. with Dynamic Economizer Cooling Data Center Design Guide featuring Water-Side Economizer Solutions with Dynamic Economizer Cooling Presenter: Jason Koo, P.Eng Sr. Field Applications Engineer STULZ Air Technology Systems jkoo@stulz ats.com

More information

In Row Cooling Options for High Density IT Applications

In Row Cooling Options for High Density IT Applications In Row Cooling Options for High Density IT Applications By Ramzi Y. Namek, PE, LEED AP, BD+C; Director of Engineering 1 Users wishing to deploy high density IT racks have several In Row Cooling solutions

More information

International Telecommunication Union SERIES L: CONSTRUCTION, INSTALLATION AND PROTECTION OF TELECOMMUNICATION CABLES IN PUBLIC NETWORKS

International Telecommunication Union SERIES L: CONSTRUCTION, INSTALLATION AND PROTECTION OF TELECOMMUNICATION CABLES IN PUBLIC NETWORKS International Telecommunication Union ITU-T TELECOMMUNICATION STANDARDIZATION SECTOR OF ITU Technical Paper (13 December 2013) SERIES L: CONSTRUCTION, INSTALLATION AND PROTECTION OF TELECOMMUNICATION CABLES

More information

COMPARISON OF EFFICIENCY AND COSTS BETWEEN THREE CONCEPTS FOR DATA-CENTRE HEAT DISSIPATION

COMPARISON OF EFFICIENCY AND COSTS BETWEEN THREE CONCEPTS FOR DATA-CENTRE HEAT DISSIPATION COMPARISON OF EFFICIENCY AND COSTS BETWEEN THREE CONCEPTS FOR DATA-CENTRE HEAT DISSIPATION 1/16 Contents: 1. Introduction: the increasing importance of energy efficiency 1.1 Power consumers in the data

More information

DOE FEMP First Thursday Seminar. Learner Guide. Core Competency Areas Addressed in the Training. Energy/Sustainability Managers and Facility Managers

DOE FEMP First Thursday Seminar. Learner Guide. Core Competency Areas Addressed in the Training. Energy/Sustainability Managers and Facility Managers DOE FEMP First Thursday Seminar Achieving Energy Efficient Data Centers with New ASHRAE Thermal Guidelines Learner Guide Core Competency Areas Addressed in the Training Energy/Sustainability Managers and

More information