Earth Fault Detection Basics in Theory



Similar documents
Unified requirements for systems with voltages above 1 kv up to 15 kv

How To Choose A Transformer

MV, HV AND EHV SWITCHGEAR TESTING & COMMISSIONING

Three-phase AC circuits

Requirements for Offshore Grid Connections. in the. Grid of TenneT TSO GmbH

Generator Stator Protection, under/over voltage, under /over frequency and unbalanced loading. Ramandeep Kaur Aujla S.NO

Current and voltage measuring relays

How To Understand The Electrical Power Supply Of A Power Supply System

Switchgear Application Issues for Mission Critical Power Systems, Part One

Current valve. for AC 24 V pulse/pause control of electrical loads up to 30 kw

4.5 Transformer Connections

Medium voltage product. Instrument transformers for indoor applications Product overview

100% Stator Ground Fault Detection Implementation at Hibbard Renewable Energy Center. 598 N. Buth Rd 3215 Arrowhead Rd

MEDIUM VOLTAGE CE-BF SWITCHBOARDS. UP TO 40.5 kv. CE - BF - C - en - REV

Chapter 24. Three-Phase Voltage Generation

ASK THE EXPERTS. Resistance Grounding Q&A. with industry experts

For a phase-to-phase voltage between 100 V and 1000 V. The standard ratings are: 400 V V V (at 50 Hz)

The following table shows approximate percentage wise the

e 2 ALPHA Medium Voltage Switchgear Data Sheet K EN

ANCILLARY EQUIPMENT AND ELECTRICAL EQUIPMENT Power Supply Systems and Electrical Equipment for Desalination Plants - Y.M. Hamud and A.H.

Instrument Transformers Application Guide

Reyrolle Protection Devices. 7PG17 - XR Intertripping, Interposing, Supervision and Special Purpose Relays. Answers for energy

..OR How To Protect your 3-Phase Equipment Investment with 3-Phase Monitors from Time Mark...

Using Current Transformers with the 78M661x

Application of Four-Pole Circuit Breakers within Data Centers

HIGH VOLTAGE CALCULATIONS / EVALUATIONS. West Virginia Office of Miners Health, Safety & Training

Part 1 System Modeling & Studies for Existing Systems

LIMITING SHORT-CIRCUIT CURRENTS IN MEDIUM-VOLTAGE APPLICATIONS

General Validation Test Program for Wind Power Plants Connected to the Hydro-Québec Transmission System

Quick Connect. quick - simple - efficient.

EMTP STUDIES PERFORMED TO INSERT LONG AC CABLES IN THE FRENCH GRID

Electrical Shore Connections / Cold Ironing

Fortune Oregon Data Center Increases Reliability with a High Resistance Grounding System

7. Reactive energy compensation

Fundamentals of Power

Medium voltage products UniSec for Smart Grid Air-insulated medium-voltage secondary distribution switchgear

Simulation of Ungrounded Shipboard Power Systems in PSpice

Digital Energy ITI. Instrument Transformer Basic Technical Information and Application

ACCURACY OF POTENTIALTRANSFORMERS

NATUS NES / NES-H Draw-out Type Medium Voltage Switchgear Systems. Safe energy distribution that meets the highest industrial requirements

Short Circuit Current Calculations

VOLTAGE REGULATOR AND PARALLEL OPERATION

Medium Voltage Products. ZN1 12 kv arc-proof air-insulated switchgear for primary distribution

HARMONIC DISTORTION IN THE ELECTRIC SUPPLY SYSTEM

Trip circuit supervision relay. Type RXTCS

Safe and reliable distribution network ABB portfolio for medium-voltage indoor applications

ABB 1 NEW. Three-phase monitoring relay for grid feeding CM-UFS.1. Data sheet. Features. Approvals. Marks. Order data. Order data - Accessories

Advantages of Fixed Circuit Breaker Switchgear

INTERNATIONAL POWER DISTRIBUTION CONGRESS CIDEL ARGENTINA 2002

HIGH VOLTAGE SHORE CONNECTION

UniGear ZS1. Medium voltage, arc proof, air insulated switchgear for primary distribution

THREE PHASE CIRCUITS

KOLMA and IHDA Indoor type Cable Current Transformers Catalogue ABB Power Distribution ABB Transmit 1 KKOLMA 1 GB

Guidelines on the Short Circuit Current Rating for Industrial Control Panels

Hyperlinks are Inactive

Power Plant Electrical Distribution Systems

ELECTRICAL INSULATION TESTING OF HV EQUIPMENT UP TO 33kV

Joslyn Clark Controls, Inc.

POWER FACTOR CORRECTION

SPECIAL TOPICS ON GROUND FAULT PROTECTION AND PROTECTION COORDINATION IN INDUSTRIAL AND COMMERCIAL POWER SYSTEMS

Metal Clad Indoor Instrument Transformer for Plug-In Systems

AUTOMATIC TRANSFER SWITCH. Changeover Type from 250A to 2500A

Electronic timer CT-VBS OFF-delayed without auxiliary voltage, for DC contactors Data sheet

SIPROTEC Protection Technology

Grounding of Electrical Systems NEW CODE: Grounding and Bonding

The following components are common to most cubicles; this example is an ABB HK cubicle.

Checking Capacitor Banks for Failed Capacitors

Nuclear Power Plant Electrical Power Supply System Requirements

BETA Switching. Switching Devices. 5TT5 8 Insta contactors, AC technology. Overview

ELECTRICAL ENGINEERING DESIGN CRITERIA APPENDIX F

CAPACITOR BANK TESTING SWP

Low Voltage Switchgear

Federal Wage System Job Grading Standards for Electric Power Controlling, Table of Contents

TDA4605 CONTROL CIRCUIT FOR SWITCH MODE POWER SUPPLIES USING MOS TRANSISTORS

PacifiCorp Original Sheet No. 476 FERC Electric Tariff, Substitute 6 th Rev Volume No. 11 APPENDIX 2 TO SGIP

Line to Ground Voltage Monitoring on Ungrounded and Impedance Grounded Power Systems

World Leader in HV Testing Technology

Electrical network protection. Protection guide. Guide G 51G 51G 51G 51G. network protection solutions

QUESTIONS and ANSWERS RFB , Metal Clad Switchgear and Power Control Room

MEDIUM AND HIGH VOLTAGE CAPACITORS, CAPACITOR BANKS AND SYSTEMS

of the LED control gear Compact dimming Uconverter LCAI 55W 900mA 1750mA ECO SR ECO series

Anti-blackout system for grid connected solar installations (Solsafe concept)

Extend the Life of Existing Switchgear

Submit shop drawings for equipment provided under this section Shop drawings shall indicate:

3) What is the difference between "Insulating", "Isolating", and "Shielded Winding" transformers?

Engineering innovation

Thermistor motor protection relays CM-MSS.22 and CM-MSS.23

ESP 120 M1, ESP 208 M1, ESP 240 M1, ESP 415 M1, ESP 277 M1, ESP 480 M1 and M1R variants. Installation instructions ESP M1/M1R mains protectors

USER MANUAL CHARGING STATIONS FOR ELECTRIC VEHICLES

Electrical Resistance Resistance (R)

NATIONAL CERTIFICATE (VOCATIONAL)

Thermistor motor protection

Residual Current Circuit Breaker

Power factor correction and harmonic filtering. Rectimat 2 Automatic capacitor banks. Catalogue. Building a New Electric World

Fusible Disconnect Switch

CHAPTER 2 EXAMPLES AND TABLES

(2) Words and expressions used and not defined in these regulations but defined in the Act shall have the meaning assigned to them in the Act.

CONTROLS DATA MANAGEMENT PROCESS AUTOMATION EUROCUBE. General purpose single phase thyristors and solid state relays Product data.

Power Voltage Transformers for Air Insulated Substations. THE PROVEN POWER.

Catalog EN. Content Transformers for industrial applications

Transcription:

Earth Fault Detection Basics in Theory Author: Dipl.-Ing. Ingo Kühnen Woodward Power Solutions Krefelder Weg 47 47906 Kempen, Germany Kempen, 16.04.2010 Earth_Fault_Detection_20100416.doc page 1

1. Star Point Treatment of Generators Due to the fact that the outgoing utility transformers of power stations are delta connected, i.e. separated from the neutral earthing system of medium voltage side, the rating of earth fault currents of the MV - System only depends on the star point treatment of the generators. The following star point treatments of generators are feasible: 1. isolated, i.e. unearthed star point 2. compensated star point, i.e. star point earthed via Peterson earth fault neutralizer 3. indirectly earthed star point, i.e. a.) earthed via reactor or transformer or b.) earthed via resistor 4. directly, i.e. solidly earthed star point. This document is to compare the different methods of treating generator star points taking into account the requirements and conditions of the majority of power stations. Earth_Fault_Detection_20100416.doc page 2

1.1. Isolated Star Point The rating of the earth fault currents at isolated star points is mainly depending on the cable capacities of the network system, because of the fact that the earth fault circuit is only closed via cable capacities and earth fault location. Consequently, this method is only feasible, provided that the cable capacities within the network are relatively high and do not vary, which may particularly apply to cable network systems that are strongly intermeshed and quite complex. In most of the power stations, however, these conditions are not prevailing since the various existing operating modes and switching states on their own will result in very different network cable capacities. In case of an earth fault of one conductor, the system voltage of the remaining two healthy conductors against earth will increase by the factor 3, thus achieving the line-to-line voltage. The following shall apply: I = 3 I 3 U ω 0 Δ C E U,healthy conductor 3 U = U Δ E with I E : earth fault current at earth fault location C E : earthing capacitance = zero-capacitance of the network ω: 2πf = angular frequency 1.2. Compensated Star Point In this case, cable capacities of the entire network system are largely compensated through the inductance of a Petersen earth fault neutralizer. In case of an earth fault, the residual currents still available then, are very low. These currents are frequently detected by means of watt hour metering. This method of star point treatment is even more dependent on the cable capacities of the network system though the rating of cable capacities will additionally determine the rating of the Petersen earth fault neutralizer. Consequently, this method of star point treatment is inapplicable, as well. Earth_Fault_Detection_20100416.doc page 3

1.3. Indirectly Earthed Star Point 1.3.1. Earthed via Reactor or Transformer By earthing the generator star point via reactor, it is possible to determine the value for the earth fault current. When this method is applied, the earth fault current will only depend on the network system s cable capacity as shown hereafter: 1 I E 3 U Δ j ωce 3ωL 1 IE 3 UΔ ωce 3ωL U,healthy conductor 14. U with I E : earth fault current at earth fault location L D C E : inductance of reactor or transformer earthing capacitance of the network D D ω: 2πf = angular frequency In case of an one phase earth fault the system voltage of the remaining two healthy conductors against earth will increase by approximation of a max. factor 1.4 due to earth fault factor f E. It is also possible to connect a reactor or a transformer with the generator bus bar and operate the generator star points separately. The reactor (or the transformer) will then be acting as a so-called star point creator. In this case, it is necessary to determine a defined load for the reactor (or transformer). This method of star point earthing via reactor or transformer is thus applicable for most of the power plant network systems. Earth_Fault_Detection_20100416.doc page 4

1.3.2. Earthed via Resistor R E By earthing the generator star point via a resistor, it is possible to control the attitude of the protection system in comparison to the isolated star point method. The resistor defines the amount of the earth fault current and is only slightly dependent on the network system s cable capacities. The mostly low resistances R N of a less extensive unmeshed network are usually negligible. The following shall apply: I E 1 3 U Δ 3R E + jω CE 1 3R I 3 U + ( C ) E Δ ω E U,healthy conductor 14. U with I E : earth fault current at earth fault location R E C E : 2 earthing resistance earthing capacitance of the network ω: 2πf = angular frequency In that case, too, if there is an earth fault of one phase conductor the system voltage of the two healthy conductors against earth will increase by approximation of a max. factor 1.4 due to earth fault factor f E. Proportionate to this, the load affecting the insulation of these conductors as well as connected voltage transformers etc. will increase accordingly. Therefore this method of star point treatment is also applicable. E 2 Earth_Fault_Detection_20100416.doc page 5

1.4. Directly Earthed Star Point By means of this star point treatment, in the event of external earth faults, high one phase short-circuit currents result, which might be a multiple of the generator s nominal current. These voltages are too high for the generator windings. The following shall apply: " " 3 IK, 1P IK, 3P X 0 2 + X at a ratio of X 0 X1 52. for the effectively earthed network. 1 1.5. Summary After consideration of the different star point treatments of the generators, for the most power stations only the indirect methods turn out to be practicable such as earthing of the generator star point via an neutral earthing resistor R E earthing of the generator star point via a neutral earthing reactor or neutral earthing transformer with a defined load earthing of the busbar of the generators via neutral earthing transformers as a star point creator with a defined load. Earth_Fault_Detection_20100416.doc page 6

2. Star Point Treatment via Neutral Earthing Resistor R E When comparing the various possibilities of generator star point treatment dealt with in chapter 1, the way of earthing generator star points via a neutral earthing resistor seems to be the most practicable one since this method offers economic advantages and can normally rather easily be retrofitted and it is more independent with regard to subsequent system extensions or modifications. In the figure 2-1 below, the star point treatment of the generator by means of a neutral earthing resistor R E is illustrated in a diagram. T2 T2 G 3 G1 G 3 G2 star point star point T1 T1 Q E Q E ϑ> R E T E Figure 2-1 Diagram of the generator star point treatment via neutral earthing resistor R E with: R E earthing resistance with temperature supervision ϑ> R E 318 Ω, I RE(10s) = 20A rated for a period of 10s and I RE(cont.) = 15A continuously, U RE = 11kV/ 3 Q E : single-phase vacuum contactor of the series 12, 400A, with very short switching times T E : cable type current transformer for backup earth fault detection at neutral earthing resistor R E 50/1A with 2.5VA, for max. 120min. at 10% I N T1,T2: cable type current transformers for earth fault detection within the generators (restricted earth fault: 64REF), data as T E Earth_Fault_Detection_20100416.doc page 7

In general, only one generator star point connected to the bus bar is grounded via the neutral earthing resistor. This applies to each MV busbar section. With the aid of the appropriate single-phase vacuum contactor Q E, the star point of the generator that was connected first to the MV switchgear, is switched to the neutral earthing resistor R E. During this, only the star point of the generator that was initially connected will be earthed via the neutral earthing resistor R E. In case that the generator circuit breaker of the generator whose star point was connected with, the neutral earthing resistor is switched off by the corresponding star point contactor and the neutral earthing resistor will be switched over to the contactor of that generator in operation, whose circuit breaker will be closed next. As regards circuitry, it has to be ensured, that not more than only one generator star point will be earthed via the neutral earthing resistor since otherwise it might happen that transient currents of the third harmonic would flow between the generator star points. To protect the system against ferroresonance (these are oscillations in electric circuits provoked by capacities and inductance in the iron core, whereby there is not always a stable operating point produced in the power voltage diagram, as the inductance depends on the current and therefore modifies the inherent frequency of the oscillating circuit!) in case of ungrounded generators (floating), the tertiary windings(open delta / e-n winding) of the voltage transformers are switched in an open triangle and are burdened with a resistor. Earth_Fault_Detection_20100416.doc page 8

Protection in case of external earth faults In the event of a station earth fault beyond the generator protection range, the earth fault current I E that is primary determined by the dimension of the neutral earthing resistance (and only secondary by the cable capacities of the network) will be flowing through the earth fault source. In case of selectivity, it is possible to separate the faulty segment by means of staggering and IDMT earth fault relays. Protection in case of internal earth faults In case of an internal earth fault, the stator earth fault relay of the defective generator will disconnect the defective generator only. The cable type current transformers T1 and T2 are applied to detect earth faults within the generator s protection range, in particular for the detection of stator earth faults (ANSI - Code: 64REF). These cable type current transformers must have the same transmission ratio and shall be connected anti-parallel, as shown in figure 2-2. S1 T2 S2 MRI B2 B1 S2 T1 S1 Figure 2-2 Diagram illustrating the wiring of stator earth fault protection devices During faultless condition and in case of an earth fault occurring outside of the protection range of current transformers T1 and T2, the current rating is approximately the same. Antiparallel connection of the transformers leads to the neutralization of the currents. Earth faults within the protection range of both current transformers T1 and T2 result in the addition of the currents. For this purpose, the earth fault relays are adjusted as to disconnect the generator circuit breaker after maximum 10 sec. at detected currents of more than 5A or soonest possible at an earth fault current of more than 15A. In case of a stator earth fault on an ungrounded generator the earth current limited by the resistor will flow to the grounded generator in operation. By interconnecting the ring core current transformer on the main connectors (L1, L2, L3) and the ring core current transformer on the star point side, only the earth current of the defective generator will be detected by its own earth fault relay. Earth_Fault_Detection_20100416.doc page 9

The current on the earth fault relay of the non-defective but grounded generator is zero due to the anti-parallel connection of the ring core circuit transformers and does therefore not cause a fault. Protection of the Neutral Earthing Resistor R E The cable type current transformer T E is used to detect residual currents in the current path of the resistor. Should the preceding earth fault relays of the station not pick-up in case of an external fault, an appropriate earth fault relay has to be provided in order to prevent the neutral earthing resistor s overload. According to the rating of the neutral earthing resistor, this earth fault relay will be adjusted as to pick-up after 10s at the latest. To protect the resistor from overheating, the neutral earthing resistor is furthermore equipped with an overtemperature detection facility. This element is another back-up protection that may only lead to tripping if no other earth fault relay picks-up. A prerequisite for both, tripping of the back-up overload protection and tripping of the back-up overtemperature protection is the separation of the generator s star point from the neutral earthing resistor. In that case, the system earth fault protection should operate for a certain maximum time. After expiry of this time the generators should be isolated from the grid since earth fault protection can no longer be ensured. Earth_Fault_Detection_20100416.doc page 10

Prerequisites for the use of star point treatment via Neutral Earthing Resistor R E The generator star points have to be lead out and accessible. It is only permitted to earth that generator via neutral earthing resistor R E which is connected first to the power station. It is never permitted to earth more than one generator star points via the earthing resistor R E since this might lead to undesirable transient currents between the generator star points related hereto. Therefore the neutral earthing vacuum contactors have to be interlocked. All relevant network elements as insulation of conductors, voltage transformers etc. must be capable of withstanding the increased voltage generated between the healthy phases and earth during an earth fault. Earth_Fault_Detection_20100416.doc page 11

3. Dimensioning of the Neutral Earthing Resistor R E The earth fault current which is defined by the neutral earthing resistor R E is limited by the following circumstances: On one hand, the earth fault current within the total direct-connected network has to be at least high enough to energize the selective earth fault relays and the back-up protection relays. On the other hand, the earth fault current should be maintained low enough to avoid further damages resulting from the earth fault current. This means that the rating of the neutral earthing resistance results from the current s pick-up values of the earth fault relay, taking into account the fact that earth fault currents must not become too high to maintain damages that might occur as slight as possible. After due consideration on principles for the adjustment of these pick-up values there should be a minimal earth fault current of 80A. The earthing resistor has to be dimensiond for this earh fault current rating. The following shall apply: UΔ RE 3 IEmin = 318 Ω dimensioned for I E 20A at 10sec. (15A continuously) R E with R E : rating of the neutral earthing resistance I E, min : minimum defined earth fault current U Δ : 11kV If vacuum contactors with low switching times far below 1s are selected for switching off the neutral earthing resistor, the resistor can be dimensioned for a load time of 10s (having regard to maximal staggering times of approximately 3sec.). Earth_Fault_Detection_20100416.doc page 12

This information undergoes continuous further development and is subject to changes without prior notice. If you need any further information please contact: Woodward Power Solutions GmbH Krefelder Weg 47 D - 47906 Kempen (Germany) Phone: +49 (0) 21 52 145 1 Internet homepage http://www.woodward-seg.com Earth_Fault_Detection_20100416.doc page 13