Wireless Controller REC601/603 Product Guide

Similar documents
Waveguide Access Point WGA631. Product Guide

Remote Monitoring and REC 501 Control Unit Product Guide

TK800-Series Industrial GPRS / UMTS / LTE Router

TK C -25 C 95% RH EMC TK701G TK701U TK704G TK704U TK704W. TK-Series Cellular Router

Rack mounted telephone- and leased line modem for industrial applications

Telephone- and leased line modem for industrial applications TD-36

JNIOR. Overview. Get Connected. Get Results. JNIOR Model 310. JNIOR Model 312. JNIOR Model 314. JNIOR Model 410

ISIO 200. Binary Input/Output (I/O) Terminal with IEC Interface

Industrial RS-232/ RS-422/ RS-485 over Ethernet Media Converter

SOLARCARE SERIES PRODUCT AND APPLICATION GUIDE

T200, PTP/IEEE 1588 Grandmaster Clock and

Disturbance Recoder SPCR 8C27. Product Guide

ORION TELECOM NETWORKS INC. T1

User manual Compact Web PLC WP240 series IEC-line

ModBus Server - KNX. Gateway for integration of KNX equipment into Modbus (RTU and TCP) control systems.

VCL-PRI ISDN VALIANT COMMUNICATIONS LIMITED. Primary Rate (Euro-ISDN) Multiplexer. Product Brochure & Data Sheet

Chrome DIN Rail Power Supply 24V 30W 1 Phase (Class II & NEC Class 2) / DRC-24V30W1AZ

Zlinx Wireless I/O. Peer-to-Peer and Modbus I/O B&B ELECTRONICS PRODUCT INFORMATION

IntesisBox Modbus Server Fidelio IP

Application. Characteristics RTU560. Data Sheet Communication Unit 560CMD11. Communication Unit 560CMD11

EMR. WAN Compact Router for Industrial Ethernet Networks. A secure access to Ethernet industrial networks making use of the public operator networks

Communicate and view data from meters with one simple device

Indoor / Outdoor Antenna

Application/Connection Examples

Medium voltage products UniSec for Smart Grid Air-insulated medium-voltage secondary distribution switchgear

Voltage Regulator SPAU 341 C. Product Guide

SIMATIC S It s the Interplay that makes the difference. Siemens AG All Rights Reserved.

Communication Unit 560CMU05 Data sheet

Foxboro Evo Process Automation System

Chrome DIN Rail Power Supply 24V 91.2W 1 Phase (Class II & NEC Class 2) / DRC-24V100W1AZ

Overview. 1. GPS data tracking via GSM SMS / GPRS. 2. GPS data logging in internal memory. 3. Alarm alert via GSM SMS / Dialing / GPRS

Gain energy insight and control with PowerLogic. PowerLogic EGX300 integrated gateway-server

TM7BDM8B expansion block - TM7 - IP67-8 DI/DO - 24V DC A - M8 connector

User Manual Revision English Converter / Adapter Ethernet to RS232 / RS485 (Order Code: HD HD M HD HD M)


Designed for the needs of automation, telecommunications, remote supervision, and monitoring

Electronic timer CT-AHD.12 OFF-delayed with 1 c/o (SPDT) contact

Energy Depot GmbH PRODUCT AND APPLICATION GUIDE. Total Monitoring Solution for PV. Delivering Solutions for Energy Management

IntesisBox KNX Modbus TCP master

PCS0100en Persy Control Services B.V. Netherlands

Modbus Server SAMSUNG Air Conditioners

EZmoto V2. Product description Rev. 6 10/01/2014. EZmoto V2 Product description Rev.6 10/01/2014

Power Meter Series 700

LLB-OCMFM 2000 PORTABLE DOPPLER AREA-VELOCITY FLOWMETER

Firmware version: 1.10 Issue: 7 AUTODIALER GD30.2. Instruction Manual

HEOL-N103-OBD, GPS/GPRS Tracking Module with On Board Diagnostic

Loop-IP6510 Multiple WAN Router/Bridge

IntesisBox Modbus Server SAMSUNG Air Conditioners

Temperature & Humidity SMS Alert Controller

Millenium Web Server

5-port / 8-port 10/100BaseTX Industrial Ethernet Switch User Manual

Quick Connect. quick - simple - efficient.

OZS Web server. For LPB/BSB plants

Electronic timer CT-VBS OFF-delayed without auxiliary voltage, for DC contactors Data sheet

RISH EM 3490 DS Dual Source Energy Meter RISH EM 3490 DS. Application : Product Features:

Quidway AR 18-1X Series Router Datasheet

Application. Key Features. Benefits. Contact us. Solution for GSM-R coverage. AIR Repeater RF/RF GSM-R 900. To ensure GSM-R coverage everywhere

XPress-Pro SW Series Hardened Ethernet Switches Enabling Communication for the Demanding Industrial Environment

TRACTION NETWORK MONITORING AND PROTECTION SYSTEM SMTN-3 CITY ELECTRIC TRANSPORT RAILWAYS METRO INDUSTRY

Thyristor-controlled power supplies and battery chargers

Technical Notes TN 1 - ETG FactoryCast Gateway TSX ETG 3021 / 3022 modules. How to Setup a GPRS Connection?

Ha-VIS FTS 3000 Introduction and features

Technical Information POWER PLANT CONTROLLER

Tele Eye DT Series. Installation Guide. Dialup CCTV Transmitter DT-103G DT-103P DT-103D

Technical Data. back-up time in minutes 100% load % load

STRATO LED Drivers 70W, Single output

Chrome DIN Rail Power Supply 12V 54W 1 Phase (Class II & NEC Class 2) / DRC-12V60W1AG

Power-monitoring unit PowerLogic System. Technical data sheet. Power Meter Series 800

How To Run An Nport I5000A Device Server

PCS300 Universal IP Reporting Module V1.0

/ Our accessories complement all PV systems, simplify installation and ensure that the system meets the required safety standards.

2014 GSM SHIELD COMPATIBLE WITH ARDUINO GSM SHIELD USING SIMCOMM (SIM900A)

Electronic Control Devices The European Product Catalogue 2007

ST Series POWER SUPPLIES USER INSTRUCTIONS

How To Use An Adh8012 Gsm Gprs Module With A Gsm (Gsm) Gpros (Gsp) Gpls (Geo) Gsp (Gpl) Gs

securityprobe 5E Standard

IPThermo206G. Offline/online data collector, SMS alarm sender, watchdog terminal for IPThermo Pro network

CliQ DIN Rail Power Supply 24V 120W 1 Phase / DRP024V120W1AA

USER MANUAL. PingBrother EPIW104 managed passive poe switch & IP watchdog

DCS Data and communication server

WIRELESS REMOTE MONITORING OF CATHODIC PROTECTION SYSTEMS. John Hawkyard MICorr Deputy General Manager Rawabi Corrosion Technology Co Ltd Al-Khobar

AC 800M. EtherNet/IP DeviceNet Linking Device LD 800DN. Power and productivity for a better world TM SP1134

Features. Display. Measurements. Intelligent. Accuracy. Models. Installation DEIF A/S. Multi-instrument D

SCADAPack 530E 535E. remote Programmable Automation Controller

HMI display Installation Guide

Overview of Cisco 2600 Series Routers

NGSS Data Consolidator (DC)

IntesisBox KNX Modbus RTU master

The BANDIT Device in the Network

Daker DK 1, 2, 3 kva. Manuel d installation Installation manual. Part. LE05334AC-07/13-01 GF

Applications. diris_826_a_1_gb_cat

PowerGem Pro Uninterruptible Power Supply

STEP-PS/1AC/12DC/1.5. Extract from the online catalog. Order No.: DIN rail power supply unit 12 V DC/1.5 A, primary switched-mode, 1- phase

MCR1900 Media Converter 19-Slot Chassis

G-TAP A Series // Data Sheet

Automation System TROVIS 6400 TROVIS 6493 Compact Controller

R-Win. Smart Wireless Communication Management System

33.6W Power over Ethernet Waterproof Adapter PoE Plus Single Port Injector for Outdoor Application

ABB RTU560A Series CMU & Modules

QuickSpecs. HP Compaq t5525 Thin Client. Overview

Transcription:

Product Guide

Contents 1. Description...3 2. Applications...4 3. Battery condition monitoring...7 4. Motor overload protection...7 5. Inputs and outputs/physical interfaces...8 6. Communication...12 7. Technical data...13 8. Mounting methods...18 9. Ordering data...18 10. Accessories and ordering data...19 11. Tools...19 12. Terminal diagrams...21 13. References...22 14. Document revision history...22 Disclaimer The information in this document is subject to change without notice and should not be construed as a commitment by ABB. ABB assumes no responsibility for any errors that may appear in this document. Copyright 2014 ABB. All rights reserved. Trademarks ABB and Relion are registered trademarks of the ABB Group. All other brand or product names mentioned in this document may be trademarks or registered trademarks of their respective holders.abb is a registered trademark of the ABB Group. All other brand or product names mentioned in this document may be trademarks or registered trademarks of their respective holders. 2 ABB

Issued: 2014-08-18 Revision: C 1. Description The Wireless Controllers are compact, solution based devices for remote controlling and monitoring of secondary substations such as network disconnectors, load break switches and Ring Main Units (RMU s) in distribution networks. The Wireless Controllers enable the SCADA system to wirelessly monitor and control the field devices over the public communication infrastructure (GPRS). The Wireless Controllers utilize the built-in GPRS features for reliable and secure end-to-end communication providing remote monitoring and control of a single object with Wireless Controller REC601, or up to three (3) objects with Wireless Controller REC603. The use of Wireless Controllers in distribution networks improves the quality of power distribution and dramatically reduces the outage time in affected areas. Areas directly adjacent to these affected areas would also show reduced outages and overall effects. It also reduces the capital expenditures in the distribution network by limiting the replacement of legacy devices and contributes to more direct cost savings by facilitating preventative maintenance. Wireless Controllers are also ideally suited to be retrofitted to existing disconnectors and thus enabling remote control of these devices and further extending the life cycle of the disconnector. SCADA (ABB MicroSCADA) IEC-104 M2M Gateway Static IP addresses Firewall and VPN GPRS Secure end-to-end VPN tunneling in public network TCP/IP IEC-104 IEC-104 TCP/IP SPA IEC-101 Wireless Controller Wireless Gateway RER601/603 ABB IED ABB load break switches GUID-5BB3E76A-52DD-4A42-A1EE-122D795C95E6 V1 EN Figure 1. Typical communication system example - GPRS For the existing installations with IEC101 line or modem, supports IEC101 communication (including dialup) to SCADA system. ABB 3

2. Applications The Wireless Controllers are important and powerful components in an automated distribution network. Connected to the central control system (SCADA/DMS) that manages the utility network, they serve as the core of the secondary substation automation system. These devices are recommended devices for multiple disconnector or distribution transformer applications in distribution networks that require specifications and/or features like listed below. Highly reliable control and monitoring of upto three objects (per REC603) Disconnector position indications with front LEDs Separate LED indicators for earthing status Supports both local and remote disconnector control More than one Wireless Controller can be connected in a single location to facilitate the Ethernet enabled control and monitoring of more than three disconnectors Overload protection of actuator motors Load current measured in the motor circuit Measurement of object transition time Energy limit based motor overload protection ( software fuse ) Fault Indicator support over Modbus for improved fault management Always on two-way communication based on GPRS through M2M gateway Redundant IEC 60870-5-104 connections provide extra availability Communication monitoring and automatic connection reestablishment High level data security through internal VPN and Firewall Support for Patrol communication status monitoring and diagnostics application Possibility to act as an IEC 60870-5-101 master (router) for another communicating sub-device (for example metering unit or fault passage indicator) Built-in battery charger with advanced battery control Temperature compensated charging Battery monitoring/testing (condition monitoring) Deep discharge protection IEC 60870-5-101 slave (including dial-up) to support existing system installations Possibility for future migration from IEC101 to IEC104 is made possible as selection is done using parameter settings. Operation mode - Unbalanced Slave Heater control to limit effects of ambient temperature variations, such as condensation, etc. Robust aluminium casing design for easy DIN rail mounting GUID-B0E0CD80-91B5-4437-B5B0-0BB47638EBFD V1 EN Figure 2. Distribution automation system overview 4 ABB

Application examples MV REC601 AC aux Battery charging +24V DC Remote on off M + ma - Relay Battery test Heater control O I O I Hall sensor UEMC 50 GUID-2EA84B83-9D8A-4B3F-AC97-D99930FCB53B V3 EN Figure 3. Within the UEMC 50 the REC601 unit is used for the remote control of a disconnector. The motor operating device is placed in the same UEMC 50 enclosure as the other equipment. ABB 5

SF 6 Alarm 80-265V ac/dc or 18-80V dc REC603 aux Battery charging +24V DC Remote on off M M Battery test + ma - O I O I I>> FI Relay Heater control O I O I Hall sensor Serial port MV LV compartment in RMU kwh kvarh LV A REC603 unit used for remote control of a Ring Main Unit and fault indication. GUID-FA91F00E-70D2-404C-8F7A-AEA72FB7F30B V3 EN Figure 4. A REC603 unit used for remote control of a Ring Main Unit and fault indication 6 ABB

MV M AC REC601 aux Battery charging +24V DC Remote on off + ma - Relay Battery test Heater control O I O I Hall sensor UEMC Control Cabinet GUID-D6E454C7-00B1-4D98-8EFE-62048B5E37D4 V3 EN Figure 5. Within the UEMC control cabinet the REC601 unit is used for remote control of a disconnector. The motor operating device is fitted to the disconnector. 3. Battery condition monitoring The Wireless Controllers are equipped with condition based functionality that make the conditioning monitoring of the built-in battery of the device possible and optimize the lifetime and maintenance intervals of the back-up batteries in the control assembly. The back-up battery could periodically (scheduled by operator) be tested by switching off the charger and switching on the dummy load. Current and voltage measurements are taken for a defined period of time (discharging time period). Based on these measurements of the battery s current and voltage levels, an assessment is made regarding the battery s condition and remaining operational capacity (in Ah). If the assessment shows that the battery has a significant depletion in capacity an IEC 60870-5-104 alarm event would then be generated in the system. Also the Wireless Controllers feature the ability to protect the battery against complete discharge. This is achieved by the fact that the battery voltage is always measured in network fault conditions (primary power source is disconnected). If the measured battery voltage level is below a defined limit (assumed as a battery failure ) an IEC 60870-5-104 alarm event would then be generated in the system and the load is disconnected from the battery. 4. Motor overload protection The Wireless Controllers are equipped with condition based functionality that assists in the monitoring and management of the disconnector motor by using over ABB 7

current detection and shut down of the motor that is connected to the device. The over current detection is initialized as soon as a switchon command is received by the motor. This overload detection process is based on measurements done by a Hall- Effect Current Transducer (optional accessory) for load current and control duration measurements. As soon as a predefined energy limit is exceeded, as shown by the mentioned measurements, the motor is shut down by disconnecting it via the relay output on the Wireless Controllers. 5. Inputs and outputs/physical interfaces The Wireless Controllers are equipped with numerous input and output connections to manage control operations that are communicated via the wireless (GPRS) capabilities of the devices. Wireless Controller REC603 has 15 binary inputs (REC601 has five) for monitoring and alarms, and six binary outputs for disconnector (open/close) control (REC601 has two). REC601 and REC603 devices have binary output and analog input for battery condition monitoring function (test load and load measurement). Additionally, they have binary outputs (relay out, normally closed) for overcurrent motor control (load cut) and external heater control. In the default configuration, there are also two binary inputs, one relay output and one analog input free for other use. Additionally the devices are equipped with a transducer input and heater control output. The Wireless Controllers also has two serial ports (with DIP switches for serial port 2 hardware configuration) and an Ethernet connector for communication and data transfer. There is also a SIM card insertion slot with SIM card tray and antenna connector. The status of the operational system is shown by various groupings of LED light indicators. More detailed information can be sourced via the supported Web HMI. Front panel LEDs The Wireless Controllers are equipped with eight groups of LEDs indicating the complete operational status of the device. They are located on the device s front panel and are identified by accompanying labels. 8 ABB

Table 1. Description of available LEDs on the front panel LED LED status Description VPN On VPN connection is up Blink Off VPN connection is starting VPN connection is disabled Power/Error On Operating power is turned on Off Operating power is turned off Function On Device is starting Blink Device is operating normally Eth On Ethernet link is up Blink Off Ethernet link is transferring data Ethernet link is down GPRS Blink GPRS is starting or transferring data Off GPRS is inactive AC and LINK LEDs AC Connected to AC power LINK IEC 60870-5-104 control link to SCADA is active Disconnector 1) OPEN Open position indication CLOSE LOCAL/REMOTE Close position indication Local/remote control indication Grounding disconnector 2) OPEN Open position indication CLOSE Close position indication 1) Applicable for disconnectors 1, 2 or 3 (for REC603 REC601 only has 1 disconnector) 2) Applicable for grounding disconnectors 1, 2 or 3 (for REC603 REC601 only has 1 grounding disconnector) ABB 9

Front panel description 1 2 3 4 5 6 7 8 GUID-38343AB8-2790-4E25-BD31-DBB0C237712F V1 EN Figure 6. Front panel 1. System status LEDs 2. X2.1 connector 3. X2.3 connector 4. X4 connector 5. AC and LINK LEDs 6. X3 connector 7. Disconnector status LEDs 8. Grounding disconnector status LEDs 10 ABB

Serial panel description 1 2 3 4 5 6 GUID-E93D22FF-C310-4B4E-929D-8AB8800F0241 V1 EN Figure 7. Serial panel 1. Console serial port (DIP switch selectable application or console port RS1) 2. Power switch 3. Serial console switch (RS1) 4. Serial port 2 hardware configuration DIP switches 5. Serial port 2 6. Ethernet connector Antenna panel description Both Wireless Controllers REC 601/603 have a SIM card insertion slot with SIM card tray and antenna connector on the antenna panel. ABB 11

1 2 3 GUID-35D4C58E-AD09-401B-91D1-09917E75F5C2 V1 EN Figure 8. Antenna panel 1. SIM card tray connector 2. SIM card tray release button 3. Antenna connector (FME male) 6. Communication The Wireless Controllers have wireless functionality that allows the use of wireless applications within the customer defined operator s network. High-speed wireless data transfer speed can be supported if needed, however the practical data transfer rates depend on the subscription details and wireless network capacity and bandwidth. Operating within these wireless networks (GPRS/GSM) the Wireless Controllers may utilize the supported communication protocols. This offers flexibility in system design, allowing users to develop solutions for their own applications with high data availability and reliability. The devices are designed to withstand the operational requirements of most secondary substation environments and offer industrial quality connectivity devices for the IEC 60870 protocol family. The IEC 60870 protocol family is a vendorindependent communication standard for the power distribution industry. Additionally, with the Wireless Controllers conventional IEC 60870-5-101 devices can be attached to a modern TCP/IP based IEC 60870-5-104 control system. Ethernet and GPRS/GSM data network interfaces provide a seamless communication solution for most of the applications. REC 601/603 provides support for pre-selected Modbus parameters for Fault Passage Indicators. Currently, Horstmann Compass B and Kries IKI-50 are supported. The device polls the fault indicator devices using Modbus and converts the values to IEC 60870-5-104. Up to four fault indicators can be connected to the device. IEC 60870-5-104 is used to communicate towards a SCADA via an approved M2M Gateway (available from ABB) over the available customer chosen GPRS/GSM data network. In the opposite direction IEC 60870-5-101 can be used to communicate with the devices in the field via the serial ports. This communication can also be done using the Ethernet port and a RJ-45 cable between the controlled device and the Wireless Controllers. The Wireless Controllers have two application serial ports. Serial port 1 is configurable to either console or data mode and supports only RS-232, while serial port 2 is configurable to multiple serial modes (RS-232/422/485). Serial port connectors are 9-pin D-sub (male) connectors. More information is available in the Technical Data section of this product guide or technical manual available at www.abb.com/substationautomation. 12 ABB

7. Technical data Table 2. Dimensions Description Width x Height x Depth Value 150 x 177 x 135 mm (without antenna) Table 3. Power Supply Description Input voltage Frequency range Input current, 100% load, 230 VAC Value 85...200 VDC/ 90...264 VAC 45...65 Hz 0.8 A Efficiency, typical (230 VAC, 100% load) >83% Isolation Inrush current 25Cº, 230 VAC Input fuse Overvoltage transient protection Holdup time (230 V, 100% load) Power consumption Input / ground 1500 VAC RMS 50 Hz 1 min Input / output 3000 VAC RMS 50 Hz 1 min Output / ground 500 VDC <25 A <5 ms T3.15 A high breaking VDR 275 VAC 72 J >50 ms 10 W (not charging) 60 W (full charging) Table 4. Battery recommendations Description Yasa NP 17-12 Yasa NPL 24-12 Rated voltage 12 V 12 V Capacity 17 Ah 24 Ah long life Weight 6.1 kg 9 kg Size (LxWxH) 181 x 76 x 167 mm 166 x 175 x 125 mm Table 5. Supply for external devices and input circuits (X2.1 pin 6) Description Output voltage Output current Output overvoltage protection level Value 21...29 V 1 A continuous, 3 A peak 30.5 V Table 6. Temperature-compensated charger for batteries Description Value Rated charging voltage 27.4 V at 20 C Output power Fuse Temperature compensation Output overvoltage protection level 60 W 4 A -40 mv/ C 30.5 V ABB 13

Table 7. Hardware Description Value Processor Environment Processor 32 bit RISC Memory 8 MB FLASH 32 MB SDRAM Other Sensor Temperature Internal clock Real time Approvals CE Environmental conditions Temperature ranges -40...+70 C (operation) -40...+85 C (transport and storage) Relative Humidity 5 to 85 % RH Table 8. Software Description Network protocols Tunneling (VPN) Value PPP, IP, ICMP, UDP, TCP, ARP, DNS, DHCP, FTP, TFTP, HTTP, POP3, SMTP SSH-VPN client (requires M2M Gateway) L2TP-VPN client (requires M2M Gateway) SSH client Management Routing and firewall Serial device connectivity WWW, SSH, Telnet and console FTP, TFTP and HTTP software update Static routing, proxy ARP, port forwarding, IP masquerading/nat, firewall Device server application (IEC 60870-5-104 GW) Simultaneous GPRS, CSD and SMS SMS configuration and status reporting IEC 60870-5-104 and IEC 60870-5-101 IEC 60870-5-104 over TCP or UDP IEC 60870-5-101 FT 1.2 framing Local IEC 60870-5-101 polling ASDU replacer Packet compressor 14 ABB

Table 9. Physical interfaces Description REC601 REC603 Binary Analog Binary Analog Inputs/Outputs I O I NTC I O I NTC Physical signals 17 10 2 1 17 10 2 - Application RTU default configuration Disconnector control - 2 - - - 6 - - Disconnector status 2 - - - 6 - - - Grounding disconnector status 2 - - - 6 - - - L/R status 1 - - - 3 - - - Load control - 1 - - - 1 - - Test load - 1 - - - 1 - - Heater - 1 - - - 1 - - Load measurement - - 1 - - - 1 - Temperature measurement - - - 1 - - - 1 General purpose input 12-1 - 2-1 - General purpose output - 5 - - - 1 - - Table 10. Digital inputs Description Value Number of digital inputs 17 Operating range Current drain Power consumption / input Input polarity Isolation 18 60 VDC 3.5 12.5 ma < 0.8 W Bipolar 3 kv Table 11. Digital outputs Description Value Number of digital outputs 10 Max system voltage Continuous carry 30 VDC Continuous carry 110 VDC 110 VDC 1 A 0.3 A Contact material AgSnO 2 ABB 15

Table 12. Network interfaces Description Ethernet Value 10/100 Base-T. Shielded RJ-45 1.5 kv isolation transformer Ethernet IEEE 802-3, 802-2 CSD (GSM data) Up to 14.4 kbps V.110 Non-transparent mode USSD support FME external antenna connector (50Ω) (Stub antenna included) GPRS Bandwidth Quad band (850/900/1800/1900 MHz) Module Internal module and SIM card socket Class Multi-slot class 20 Mobile station class B Downlink speed Uplink speed Coding schemes Max. 85.6 kbps Max. 85.6 kbps CS1...4 Antenna connector FME (50 Ω) Security Via encrypted VPN Serial Ports Serial 1 / Console RS-232 IEC 60870-5-101 protocol support Serial 2 RS-232/422/485 (selectable) IEC 60870-5-101 protocol support Table 13. Communication protocols Master protocol Slave protocol (RS1/RS2) IEC 60870-5-104 IEC 60870-5-101 Modbus profile for Kries IKI-50 Modbus profile for Horstmann Compass B Serial gateway 1) IEC 60870-5-101 Modbus profile for Kries IKI-50 Modbus profile for Horstmann Compass B 1) Serial port data stream is sent over TCP/IP 16 ABB

Table 14. Electromagnetic compatibility tests Description Type test value Reference Electrostatic discharge test: EN 61000-4-2 Contact discharge: Indirect contact discharge: 4 kv 4 kv Conducted RF Immunity test: EN 61000-4-6 150 khz...80 MHz 3 V (rms) Radiated RF Immunity test: EN 61000-4-3 80...2700 MHz 3 V/m (rms) Fast transient disturbance tests: EN 61000-4-4 All ports 1 kv Surge immunity test: EN 61000-4-5 AC power input ports 2 kv, line-to-earth 1 kv, line-to-line Voltage dips and short interruptions 0 % / 1 cycle EN 61000-4-11 40 % / 10 cycles 70 % / 25 cycles Emission tests: CISPR 22 (EN 55022), Class B Conducted 0.15...0.50 MHz < 66 db(µv) quasi peak < 56 db(µv) average 0.5...5 MHz < 56 db(µv) quasi peak < 46 db(µv) average 5...30 MHz < 60 db(µv) quasi peak < 50 db(µv) average Radiated 30...230 Mhz < 35 db(µv/m) quasi peak, measured at 3 m distance 230...1000 MHz < 42 db(µv/m) quasi peak, measured at 3 m distance 1000...3000 MHz < 70 db(µv/m) quasi peak, < 50 db(µv/m) average, measured at 3 m distance 3000...6000 MHz < 74 db(µv/m) quasi peak, < 54 db(µv/m) average, measured at 3 m distance ABB 17

Table 15. EMC compliance Description Reference Standard ETSI EN 301489-1 (V1.8.1 2008-04) IEC 61000-6-1 (Second edition 2005 01) IEC 61000-6-3 (2006 07) Table 16. RoHS and REACH compliance Description Complies with RoHS directive 2002/95/EC Complies with REACH directive 2006/1907/EC 8. Mounting methods The devices have been equipped with mounting arrangements that are specially designed to enable wall or rack DIN rail mounting inside the control cabinets. A set of DIN rail mounting clips is included with the devices. The specific mounting position is dependent on the intended application of the device, preferably inside a robust, weatherproof control cabinet. Use the ABB Library to access the selection and ordering information and to generate the order number. As the device uses GPRS radio waves for data transmission, the surrounding environment can negatively affect the efficacy of these radio signals. Therefore, if you are using a device with the antenna mounted directly attached to the antenna connector (device with standard antenna without optional extension cable), try to avoid placing the unit in a location where the radio signal might be shadowed, and therefore deteriorated by nearby obstacles or enclosures. Note also that large metallic surfaces, racks or walls with metallic structures (cabling, concrete iron, etc.) may degrade the antenna performance to a very high extent. In this case it is highly recommended to use the optional external antenna with appropriate cable. This allows for better positioning of the devices, antennas and thus optimal performance. Another restriction to the positioning of the device, when installing it, is that it should be mounted in such a way that the required environmental conditions that are set in the Technical Data section of this Product Guide would also be met. 9. Ordering data Product label is found on the top of the device and it contains the basic information about the product (for example product name) as well as unique data regarding the unit such as serial number and Ethernet MAC address. The order number consists of a string of codes generated from the device's hardware and software modules. 18 ABB

10. Accessories and ordering data Certain equipment accessories can be attached to the devices to increase the flexibility and/or functionality of the devices according to the application requirements within the network. More information regarding these additions should be requested and discussed when planning and ordering the equipment from ABB Distribution Automation. Replacement parts for the devices are also available from ABB. This includes all external parts or components of the sold device that could have been damaged or lost. ABB does not supply internal components or parts. The external replacement parts, on the other hand, can be ordered from ABB After-Sales Service via Parts-OnLine www.abb.com/partsonline. More information is also available from aftersales.relays@fi.abb.com Table 17. Accessories Item Hall-effect current transducer Test load resistor Null-modem cable Roof antenna with 150cm cable Order number 2RCA028227 2RCA028171 2RCA027558 2RCA028207 Table 18. Supporting product Item M2M Gateway M2M Gateway Enterprise Edition Order number 2RCA028228 2RCA028229 11. Tools The devices can be configured using a graphical user interface via a Web based browser (Internet Explorer 7 or later). A conventional console interface is also provided. Software updates or configuration adjustments for the devices can be made remotely by uploads over the network from the central control center. For the purpose of configuring the device the default IP address configuration and configuration methods can be found from the Quick Start Guide provided with every device. All other documentation is available online from www.abb.com/substationautomation. ABB 19

GUID-DABD1A6E-5A92-4286-9AB6-8C74E0A4ACDE V1 EN Figure 9. WebHMI 20 ABB

12. Terminal diagrams AC STATUS SA DC AC SB SC RA L N NTC_A PE NTC_B 24VDC GND GND GND GUID-217F2A86-3BBB-4FBD-9BE1-BD8F8D6EC3EF V1 EN Figure 10. X2.1 connector schematics OPENED 1 CLOSED 1 OPENED 2 CLOSED 3 LOC/REM 1 LOC/REM 2 CLOSE 1 OPEN 1 CLOSE2/ OPEN 2 HEATER GUID-1087841A-5BD0-4724-B006-C7D415167D17 V1 EN Figure 11. X2.3 connector schematics DISCONNECTOR 3 STATUS & CONTROL GROUNDING DISCONNECTORS STATUS OPENED 3 CLOSED 3 LOC/REM 3 CLOSE 3 OPEN 3 GO1 GC1 GO2 GC2 GO3 GC3 GUID-6BC1CF09-EDED-406C-8065-EE3284251506 V1 EN Figure 12. X3 connector schematics ABB 21

1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 LOAD/CUT LOAD CURRENT TEST LOAD HEATER -5...5 V 1) EXTRA INPUTS EXTRA OUTPUT GUID-4A4FF16A-8E32-41CD-989E-AC0900D9C845 V2 EN Figure 13. X4 connector schematics 1) Can be used as a 4...20 ma input using external resistor 13. References The www.abb.com/substationautomation portal offers you information about the distribution automation product and service range. You will find the latest relevant information on the above mentioned devices on the product pages. The download area on the right hand side of the Web page contains the latest product documentation. The selection tool on the Web page helps you find the documents by the document category and language. The Features and Application tabs contain product related information in a compact format. 14. Document revision history Document revision/date Product version History A/2011-09-02 1.0 First release B/2013-02-15 1.1 Content updated C/2014-08-18 1.2 Content updated 22 ABB

23

Contact us ABB Oy Medium Voltage Products, Distribution Automation P.O. Box 699 FI-65101 VAASA, Finland Phone +358 10 22 11 Fax +358 10 22 41094 www.abb.com/substationautomation Copyright 2014 ABB. All rights reserved.