TAC I/NETTM MR-VAV-AX. Application Specific MicroRegulator TM



Similar documents
TAC I/NETTM MR-AHU-HP. Application Specific Controller

TAC I/NETTM. Process Control Unit

Electronic Control Devices The European Product Catalogue 2007

Electronic Control Devices The European Product Catalogue 2007

Variable Air Volume - VAV

FX07 Field Controller

Zlinx Wireless I/O. Peer-to-Peer and Modbus I/O B&B ELECTRONICS PRODUCT INFORMATION

Installing the Tracer ZN517 Unitary Controller Ordering number: ,

Features. Display. Measurements. Intelligent. Accuracy. Models. Installation DEIF A/S. Multi-instrument D

M9102-AGA-2S, -3S and M9104-xxA-2S, -3S Series Electric Non-Spring Return Actuators

FX07 Field Controller

Model: DC-A2IO Advanced HVAC Controller

JNIOR. Overview. Get Connected. Get Results. JNIOR Model 310. JNIOR Model 312. JNIOR Model 314. JNIOR Model 410

PIEZOMETER AIRFLOW MEASURING RING

Ventostat Wall Mount. Telaire Wall Mount CO 2. , Humidity and Temperature Transmitters. GE Measurement & Control. Features:

THERMAL ANEMOMETRY ELECTRONICS, SOFTWARE AND ACCESSORIES

ETC TWO STAGE ELECTRONIC TEMPERATURE CONTROL

Duct Humidity Transmitter

N20xxA, N34xxA NON-SPRING RETURN DIRECT-COUPLED DAMPER ACTUATORS FOR FLOATING AND 2-POSITION CONTROL

MAKING MODERN LIVING POSSIBLE. AK-SC255 On-Site Installation Guide DANFOSS ELECTRONIC CONTROLS & SENSORS

CM705B - Universal Expander Module CM707B - Plug On Zone Expander Security Systems

How To Use A Ds340 (Dsp)

1115 4G SERIES GOVERNOR ma ANALOGUE DIGITAL SPEED SETTING

Durant PGM. For Sales and Support, Contact Walker EMD Toll-free: (800) Tel: (203) Fax: (203)

Model 5511 Filler Controller User s Manual Version 1.1 October 2011

Research RF Sputtering Packages

viii TAC I/NET Seven Installation Guide Process Control Unit for TAC I/NET Building Automation Systems TCON /10

CAMS. Combustion Airflow Management System. Proven solutions for a tough industry

Application/Connection Examples

920 Series. Dual-point heat-tracing control system. Product overview. 920*E4FWL*SIS302*SS3102 shown

T 3 Series VAV Diffusers Analog Diffuser Steel Square Panel Horizontal Pattern Model: T 3 SQ

Automation System TROVIS 6400 TROVIS 6493 Compact Controller

WEA-Base. User manual for load cell transmitters. UK WEA-Base User manual for load cell transmitters Version 3.2 UK

Ordering Part Numbers:

DC1100 & 1400 Energy Controllers. Satchwell DC1100 & DC1400 for energy-efficient temperature control in smaller buildings.

DPT-2015 Differential Pressure Transmitter for VAV Box Applications

Telephone- and leased line modem for industrial applications TD-36

T5000 T000 LCD Digital Fan Coil Thermostat

T7560A,B,C Digital Wall Module

SECTION DETECTION AND ALARM

O C M III. Open Channel Flow Monitor

Temperature & Humidity SMS Alert Controller

Technical Manual. FAN COIL CONTROLLER COOLING or HEATING ANALOG or PWM Art A

I nstallation. M100Q Series Proportional Actuator with R81Q Controller Board for Thermistor Sensor Applications. Tools Needed.

Auto-tune PID. Temperature Controller BRAINCHILD FEATURES

Established Leaders in Actuation Technology. Pakscan IIS sequencer master station. Publication S112E issue 09/04

Fiber Optic Selector Guide for Analog & Digital Data Links, Contact Closures & Multiplexers

DISCONTINUED PRODUCT. Infrastructure Management & Monitoring For Business-Critical Continuity. Liebert icom-do. User Manual

All of the above software and firmware are included in the VAV-B Package. Contact Customer Service or Technical Support for this, or for cables.

RISH CON - Hz. Salient Features : Application : Product Features: FREQUENCY TRANSDUCER

SMART SENSOR COLLECTION

HVAC-32A. Operation Manual. Specifications. Digital Multistage Air Conditioning Controller with inbuilt Outside Air Economy function

DCS Series 1 kw, 1.2 kw, & 3 kw

Electrical data Nominal voltage AC/DC 24 V Nominal voltage frequency

HMI display Installation Guide

FOSTCDR. Industrial Serial to Multimode Fiber Optic Converter PRODUCT INFORMATION B&B ELECTRONICS. Specifications Serial Technology

Contents. Document information

Introduction to Building Automation Systems (BAS)

Inwall Room Temperature Unit

6ES7313-5BF03-0AB0. Supply voltages Rated value 24 V DC Yes permissible range, upper limit (DC) circuit breaker type B, min. 4 A

DS DRTE. AIR ROOM TEMPERATURE SENSOR with fan speed control switches

DTW Works Master Specification Version 2006

Product Catalog BAS-PRC010-E4. Tracker Version 12 Building Automation System. August 2010

INTREPID Perimeter Intrusion Detection System

SMS Alarm Messenger. Setup Software Guide. SMSPro_Setup. Revision [Version 2.2]

Perimeter Security System

BACnet Automation Interface Module (Network Version)

Unidirectional Transmitter/ Receiver Units Introduction

Tracer Summit Web Server

An internal gyroscope minimizes the influence of dynamic linear acceleration on slope sensor readings.

VLT 6000 HVAC. Contents

Rackmount Intelligent Pressure Scanners

HARDWARE MANUAL. Ixx24-A 1/20. Val Controls A/S Limfjordsvej 3 DK-6715 Esbjerg N Tel vc@valcontrols.com

Workshop 7 PC Software - Tracker

NETWORK ENABLED EQUIPMENT MONITOR

THYRISTORS T1-1PH from 850A to 2700A Specifications Universal 1 Phase Thyristor Unit , March 2012

QSE-CI-NWK-E Control Interface

This chart is intended for selection purposes only. For complete product application information, refer to individual product specification sheets.

MTII4200 level Transmitter Installation, Operation & Maintenance Instructions

IntesisBox Modbus Server SAMSUNG Air Conditioners

CAUTION! THE 7I29 USES VOLTAGE AND POWER LEVELS THAT REPRESENT A HAZARD TO LIFE AND LIMB.

DUCT SMOKE DETECTOR D4120

SECTION FIRE AND SMOKE ALARM SYSTEM. City of San Diego, CWP Guidelines

Repeaters and Mimics Data Sheet

Air damper actuators

This Datasheet for the IC697CPM790. GMR Redundancy CPU, 486, 2K Triplex (voted) I/O.

L5354 ControlNet Communications Interface

EQUIPMENT SPECIFICATIONS

INSTALLATION INSTRUCTIONS

On-line Machine Condition Monitoring [The CMS System]

Technical Specifications: The specifications represent a particular hardware platform. Application-specific software is provided.

sip Sanyo Modbus Guide Technical Specification Pinouts, Cable Connections & Wiring Issue 2: February 2009 Synapsys Solutions Ltd, all rights reserved

PRODUCT PROFILE FEATURES

CD-Pxx-00-1 Series Duct Mount CO 2 Transmitter

RAINCONTROL LCD Special

TECHNICAL APPLICATION AND PROGRAMMING GUIDE

Belimo Gateway MP to Modbus RTU - UK24MOD

SECTION 16002C CAMPUS CENTRAL METERING SYSTEM DESIGN CRITERIA 1. General

ADDENDUM TO THE CONTRACT. for the. Bartlett Regional Hospital Server Room Cooling System Replacement. Contract No. E12-149

Model SETR-50 and SETR-51 Trim Tab Control

Transcription:

TAC I/NETTM TM TAC s TM has an extensive range ofpre-engineered VAV control sequences, which combined with a fully integrated actuator and airflow transducer, makes it a low Total Installed Cost solution for most VAV terminal unit control applications.

02 Features An intelligent I/STAT TM interface for independent local control and an interface to a TAC I/NET TM Distributed Control System are standard options. Product AT A GLANCE Fully Integrated Actuator, Airflow Transducer and Controller in a single, low profile package. Standalone and Networked Applications Extensive VAV Control Sequences: Two Stage Heating, Multiple Modes Series/Parallel Fan Local/Remote Occupancy Override Local/Remote Central Plant Heat or Morning Warm-up Control Local/Remote Shut Down Override (fire, failure, etc.) Indoor Air Quality Airflow Setpoint Override Demand Control Setpoint Override Minimum and Maximum Airflow Parameters for heating and cooling Complete Out-of-the-Box Installation, Configuration and Commissioning DIP Switch Configuration and Network Addressing with Local/Remote Override Completely mount and secure with one box screw and two damper shaft screws Travel Limit Settings Automatic calibration of Airflow and Temperature Sensors Autoconfiguration of Heating Stages Prove It function for Performance Verification Automatic Database Distribution for Networked Configurations Default Parameter Values (continued) Operation The has been designed to minimize the total installation, setup, configuration and commissioning costs typically associated with VAV controllers. Installation costs have been reduced by integrating the actuator, airflow transducer and controller into a single, low profile, plenum-rated package that can be completely mounted and secured with one box screw and two damper shaft screws. Setup costs have been reduced by the provision of DIP switches that can be set during installation and before power is applied. For most applications, default parameters will allow the controller to run immediately from startup based on these switch settings. The is also supplied with an extensive range of pre-engineered and tested control sequences and therefore, no application programming is required. All configuration parameters are pre-installed with the most typical default values. However, they can be overwritten either by an I/STAT, an M/STAT (a portable I/ STAT) or the Operator Station PC. Heating stage setpoints, proportional bands and delays are automatically calculated and set in the controller based on the controller setup selection. Commissioning costs have been reduced by the use of several automated processes. Airflow conversion parameters are automatically calculated once the box duct diameter and the manufacturer s K-factor are entered. By measuring and entering the low and high airflow values for the box, automatic calibration of the installed airflow transducer is then performed. Automatic calibration of the temperature sensor is also initiated once a measured value is entered into the controller.

03 Features (continued) Dimensional Drawing Configuration and Commissioning by I/STAT, M/STAT or PC Auto-rescaling of velocity transducer in low flow applications Self-Test Diagnostics I/STAT and M/STAT Support Standard Local Display - 3 Digit & Decimal Local Point Control - Analog or Digital Local Override & Setpoint Adjustment Service Mode for Commissioning and Calibration User-Defined Passwords Slide/STAT Support Standard Slide Setpoint Override Occupancy Override Integral Port for M/STAT Connection Inputs Integrated Airflow Transducer Thermistor or Discrete Low Voltage Triac Outputs for Series/Parallel Fan Control First Stage Heater Control (Two Position, Frequency Modulated, Pulse Width Modulated or Floating Control Modes) Second Stage Heater Control (Two Position Control only) Integrated Actuator A Prove It function allows a complete verification of the control sequence from an I/STAT or M/STAT. Once initiated, the space temperature is placed in Test Mode and can be increased or decreased by the buttons on the I/STAT. As the temperature value is changed through the control range, the I/STAT displays the airflow values and the state of the fan and auxiliary heating. This allows confirmation of the thermodynamic process from end to end.

04 Features (continued) Finally, in a networked environment, the database for the MicroController Interface or an I/SITE LAN can be automatically generated by an upload of all the data in the connected Application Specific MicroRegulators. This database can also include a unique eight-character name for each controller as part of each point descriptor. In a standalone configuration, the controller provides auxiliary inputs for VAV Shutdown (e.g. fire alarm), Occupancy Override (e.g. Timer, Pushbutton or Occupancy Sensor) and Central Plant Heat or Morning Warm-Up Override (e.g. contacts from a central plant). In a network environment, these signals can be provided locally for the standalone mode or via the network. If these inputs are not used for local override signals, then they can be designated as free and used for any auxiliary input condition monitoring desired in a networked environment (e.g. supply air temperature). This is also applicable to any unused outputs. They can become available for control applications resident in the MCI or I/SITE LAN (e.g. lighting control). A networked environment of controllers can provide an extensive range of global interlocks. These include Demand Mode setpoint override, Central Plant Heat/Morning Warm-up, Smoke Control (purge and isolate), Indoor Air Quality (IAQ), Minimum Airflow setpoint override, Temperature Setpoint override and Occupancy override. Model Number TCON147 TCON148 TCON149 Description, 1 I/STAT Port, Integrated Airflow Transducer, 4 Thermistor or Discrete Inputs, 3 Low Voltage Triac Outputs, Integrated Actuator, 24Vac Installation Guide Installation Sheet Pocket Guide Also, the current damper actuator position is continuously calculated and available as an Analog Output value that is a percentage of full damper stroke. This eliminates the need for expensive feedback potentiometers and analog voltage controlled (0-10 Vdc) damper actuators. This analog output point can be overridden either manually from an operator station or automatically via an application program in the MCI or I/SITE LAN and the actuator driven to any desired absolute position. The controller can also provide an analog value of the current controller loading as a percentage value of full load for both cooling and heating modes. This value can be used in the networked system to provide an accurate signal to the central plant controllers of actual system load requirements.

05 Specifications Communication Ports Microregulator Lan RS-485, 9600 baud, asynchronous, polling. Network Wiring Requirements MR LAN Length 5000 ft (1500 m) Cable Supported Twisted pair, shielded. 24 AWG or larger, 30pF/ft or less between conductors, 55pF/ft or less conductor to shield, 85 to 150 Ohm impedance. Belden 9841 or equivalent Processor Processor Zilog 86C193 Memory EPROM: 32Kbytes RAM: 464Bytes NOVRAM: 4096Bytes. Physical Description Dimensions 7.75 L x 6.25 W x 2.5 H (19.7 cm x 15.9 cm x 6.3 cm). Enclosure Meets UL94-5V UL flammability for plenum applications. Power Requirements 24Vac, +10%, 50/60 Hz (9VA, plus triac load, 4A fused) Operating Temperature 32 F to 122 F (0 C to 50 C) Operating Humidity 10-90% RH, non-condensing Software Point Capacity 20 resident points. Hardware (external) points are a function of model selected and software (internal) points activated. Input/Output Space Sensor Input Supports I/STAT, Slide/STAT or 10K Ohm NTC Thermistor (Dale 1M1002-C3) Accuracy: 1 F (0.6 C) Resolution: 0.32 F (0.18 C) @ 77 F (25 C) Inputs May be either thermistor or discrete per the following specifications. Analog Inputs 10K Ohm NTC Thermistor (Dale 1M1002-C3) Accuracy: 1% Resolution: 0.4% Span A/D Digital Filtering: Median value filter and 60 Hz notch filter Calibration Coefficients: Factory set in NOVRAM, field adjustable, 6 individual pairs Digital Inputs Dry contact input Contact Excitation: 5V @ 0.5 ma Discrete Outputs Low Voltage Triac: 24Vac @ 0.5A maximum (voltage sourcing), fused Point Scan Interval 1-255 seconds

06 Specifications (continued) Velocity Pressure Input Operating Range: 0.0 to 1 of W.C. (0 to 250Pa) Sensitivity: 0.0029 W.C. (0.73Pa) below midscale and 0.0049 W.C. (1.10Pa) above midscale. Tubing Connections: Barb fittings for 0.170 (4.3 mm) I.D. FRPE polyethylene tubing or 0.25 O.D./0.125 I.D. 6.3 mm/3.2 mm) tygon tubing Tubing Length: 4 ft (1.2 m) maximum each tube Actuator Outputs Torque Rating: 53 lb-in (6 Nm) Stroke: Fully adjustable from 0 to 95 Timing: 2 sec/degree rotation (60 Hz), 2.4 sec/degree rotation (50Hz) Position Indication: Visual Indication Provided Manual Override: Push-button clutch release to allow manual positioning of damper Damper Linkage: 0.5 D (12.7 mm) round shaft extending a minimum of 1 (25 mm) from the box, 3/8 shaft adapter optional. Terminations Terminal Blocks Removable screw terminal connectors Indications LEDs MR LAN activity (transmitting & receiving - each channel), test mode (microprocessor check, EPROM check, NOVRAM check) Dip Switch SW1-5: Address (0 to 31) SW6-12: Function Selection Agency Approval FCC Part 15 UL916 Energy Management Equipment UL94-5V UL Requirements for Plenum Application MicroRegulator Interface (MRI) Available Platforms 7792 MRI 7793 MCI 7798 I/SITE LAN All brand names, trademarks and registered trademarks are the property of their respective owners. Information contained within this document is subject to change without notice. On October 1st, 2009, TAC became the Buildings Business of its parent company Schneider Electric. This document reflects the visual identity of Schneider Electric, however there remains references to TAC as a corporate brand in the body copy. As each document is updated, the body copy will be changed to reflect appropriate corporate brand changes. 2006-2009 Schneider Electric. All rights reserved. May 2006 pdw