HCFC-22 Retrofits. There has been increased emphasis on retrofitting R-22

Similar documents
Low GWP Replacements for R404A in Commercial Refrigeration Applications

Low-GWP Refrigerants for Air Conditioning and Refrigeration Applications. Samuel F Yana Motta

Repair, Retrofit, or Replace Choices for Servicing R-22 Equipment

Performance of R-438A in R-22 Refrigeration and Air Conditioning Systems

Performance of R-438A in R-22 Refrigeration and Air Conditioning Systems

Environmental and Safety Impacts of HFC Emission Reduction Options for Air Conditioning and Heat Pump Systems

RS-24 (R426A): Q & A

RS-52 (R428A) RS-52: PHYSICAL PROPERTIES RS-52 R502 Molecular weight Temperature glide o C Boiling point (1 atm)

Scroll compressors for Low GWP Heat Pumps using R290 natural refrigerant. Pierre Ginies, Next Heat Pump Generation 2015

THE REPLACEMENT OF R-22

SERVICE GUIDELINES HCFC R22 TO HFC REFRIGERANT BLENDS

RS-44 (R424A) : Q & A

Analysis of Alternative Refrigerants to HCFC-22

Refrigerant Changeover Guidelines R-22 to R-407C. Leading the Industry with Environmentally Responsible Refrigerant Solutions

How To Design A Refrigeration System

Refrigerant Changeover Guidelines R-22 to R-407C. Leading the Industry with Environmentally Responsible Refrigerant Solutions

PG Student (Heat Power Engg.), Mechanical Engineering Department Jabalpur Engineering College, India. Jabalpur Engineering College, India.

Refrigerant Changeover Guidelines HCFC R-22 to HFC R-404A/R-507. Leading the Industry with Environmentally Responsible Refrigerant Solutions

STUDY OF LUBRICANT CIRCULATION IN HVAC SYSTEMS

REFRIGERANT REFERENCE GUIDE

Scroll Compressor Development for Air-Source Heat Pump Water Heater Applications

R407C GUIDELINES FOR UTILIZATION OF. DATE: August 2009 REFERENCE DOCUMENT NO. RD-0005-E GUIDELINES FOR UTILIZATION OF R407C

Mohan Chandrasekharan #1

Engineering Recommendation on: Accumulators Revised Issued January 10, 1979 Page 1 of 7

UNIT 2 REFRIGERATION CYCLE

Commercial refrigeration has been in the environmental. Refrigerant. as a. Basics Considerations PART 1:

Chapter 3.4: HVAC & Refrigeration System

A Performance Comparison of Vapour Compression Refrigeration System Using Eco Friendly Refrigerants of Low Global Warming Potential

Troubleshooting an Air Conditioning system. R D Holder Eng. Roger D Holder MSME

Todd M. Rossi, Ph.D. President

Refrigerants for Residential and Commercial Air Conditioning Applications

Automobile Air Conditioning Primer

PERFORMANCE ANALYSIS OF VAPOUR COMPRESSION REFRIGERATION SYSTEM WITH R404A, R407C AND R410A

Impacts of Refrigerant Charge on Air Conditioner and Heat Pump Performance

Patech. Our Conviction. Quality Service Innovation PATECH FINE CHEMICALS CO., LTD

Refrigerant System for Vehicle Air- Conditioning NISSAN / ZEXEL. Phoenix Alternate Refrigerant Forum June,28----July,1 Phoenix, AZ

CONTAMINANT REMOVAL FROM CENTRIFUGAL SYSTEMS

Characteristics of Evaporators

Estimation Method For Thermal Stability Of Refrigeration Oil And Automatic Sealed Glass Tube Processing Device

A Comparison of an R22 and an R410A Air Conditioner Operating at High Ambient Temperatures

THEORETICAL AND EXPERIMENTAL EVALUATION OF AUTOMOBILE AIR-CONDITIONING SYSTEM USING R134A

2004 Standard For Performance Rating Of Positive Displacement Refrigerant Compressors And Compressor Units

Subject: 2005 Air Conditioning Service Guidelines

Refrigerant Changeover Guidelines R-502 to R-402A/R-408A. Leading the Industry with Environmentally Responsible Refrigerant Solutions

Rating Water-Source Heat Pumps Using ARI Standard 320 and ISO Standard

Refrigeration and Airconditioning Prof. M. Ramgopal Department of Mechanical Engineering Indian Institute of Technology, Kharagpur

Chapter 2 P-H Diagram Refrigeration Cycle Analysis & Refrigerant Flow Diagram

Centrifugal Water Chillers. Scott Meyerkord

SECTION 5 COMMERCIAL REFRIGERATION UNIT 22 CONDENSERS

Johnson Controls Parts Centre. Sabroe S68 refrigeration oil

Maintenance for Energy Efficiency

Technical Note: Comparing R407C and R410A as Alternatives for R22. A Technical Note from the Experts in Business-Critical Continuity

P08 Köldmedier med låg växthuseffekter

ThermoStar Refrigeration Air Dryers

D A T A S H E E T. TX6 Thermo Expansion Valves. Alco Controls TX6. Features. Introduction. Construction

How does solar air conditioning work?

A car air-conditioning system based on an absorption refrigeration cycle using energy from exhaust gas of an internal combustion engine

TEST REPORT #31. System Drop-in Test of Refrigerant R-32 in Split Air-conditioning System

How To Clean Water From An Ammonia Refrigeration System

Engineers Newsletter. HVAC Refrigerants: A Balanced Approach. providing insights for today s hvac system designer. volume Refrigerant History

It will be available soon as an 8.5 X 11 paperback. For easier navigation through the e book, use the table of contents.

Recommended Compressor Installation Practices

TEST REPORT #44. System Drop-in Tests of Refrigerant R-32 in Single Packaged Vertical Heat Pump (SPVH)

Update on a Low GWP Refrigerant: Fluid H

Lesson. 11 Vapour Compression Refrigeration Systems: Performance Aspects And Cycle Modifications. Version 1 ME, IIT Kharagpur 1

Experimental Analysis of an Automotive Air Conditioning System With Two-Phase Flow Measurements

REFRIGERANT 410A. Refrigeration Service Engineers Society 1666 Rand Road Des Plaines, Illinois Information compiled by Frank Prah, CMS

Evaluation Of Hybrid Air- Cooled Flash/Binary Power Cycle

Low Global Warming Fluids for Replacement of HFC-245fa and HFC-134a in ORC Applications

Guide to good leak testing

Production of R-134a

Why and How we Use Capacity Control

Ingersoll Rand. Heat-Of-Compression Air Dryers

Part A: Fluid properties

8. Heat pumps, heat pipes, cold thermal energy storage

COMMERCIAL HVAC CHILLER EQUIPMENT. Air-Cooled Chillers

HOW HVAC WORKS. How HVAC. Works PAGE 1

DERON Air/Water Swimming pool Heat Pump. CY/DY series for Heating/Cooling. Description

UNDERSTANDING REFRIGERANT TABLES

DESIGN OF AIR CONDITIONING SYSTEM IN AUTOMOBILE

Flushing and Cleaning the A/C System

Refrigerant Charging Unit ICOGD. 020AH1000 Operating Manual. FR İ-COLD Rev. 00

AUTOMOTIVE AIR CONDITIONING

SECTION PACKAGED ROOFTOP AIR CONDITIONING UNITS NON-CUSTOM

Access Server Rack Cabinet Compatibility Guide

DEVELOPMENT OF A TWIN SCREW EXPRESSOR AS A THROTTLE VALVE REPLACEMENT FOR WATER-COOLED CHILLERS

How To Understand Evaporator

Refrigeration Basics 101. By: Eric Nelson

Refrigerant identification and equipment issues in relation to HCFC phase-out. Ole Reinholdt Nielsen

ASHRAE Boston Chapter Meeting Designing AC Refrigeration Systems Lessons Learned February 11, 2014

THE POSSIBILITY OF USING LIQUIFIED PETROLEUM GAS IN DOMESTIC REFRIGERATION SYSTEMS

PRETREATMENT TECHNICAL DATA SHEET WATER EMULSIFIABLE RUST PREVENTATIVE PRODUCT DESCRIPTION

Nordic Heat Pump Product Guide

2010 Report of the Refrigeration, Air Conditioning and Heat Pumps Technical Options Committee (RTOC)

The Trouble with R407c

D A T A S H E E T. TX3 Thermo Expansion Valves. Alco Controls TX3. Features. Introduction. Description of bulb charges

A/C refrigerant system, overview

Laboratory Test Report for Fujitsu 12RLS and Mitsubishi FE12NA Mini-Split Heat Pumps

In recent years, formicary corrosion has wreaked havoc on. Micro-channel

Transcription:

HCFC-22 Retrofits A c l o s e l o o k a t t h e r e f r i g e r a n t / l u b r i c a n t i n t e r a c t i o n s. B y S a m u e l F. Y a n a M o t t a, E l i z a b e t D. V e r a B e c e r r a, R o n V o g l a n d M a r k W. S p a t z All images courtesy of Honeywell International. There has been increased emphasis on retrofitting R-22 systems; this applies to both air-conditioning and refrigeration systems. Some end-users are performing retrofits without considering all the effects of the refrigerant change. Of particular concern are the blends of HFC with small amounts of hydrocarbons (HFC/HC blends). Some of these blends claim to be the best match to R-22 even when used with the existing mineral oil. There are differences between the performance of these refrigerants and the original R-22. In short, the systems under consideration for retrofit were designed to operate with R-22 and mineral-based oil. The HFC/hydrocarbon blend R-422A includes a small amount of hydrocarbon (isobutane), which is added to a mixture of HFC refrigerants (R-125, R-134a). Hydrocarbons that are Figure 1 Miscible and immiscible conditions. 14 RSES Journal MAY 2013 Mineral Oil Some end-users are performing retrofits without considering all the effects of the refrigerant change. miscible with mineral oils thin the mineral oil, helping its return back to the compressor. However, the small amount of HC included in R-422A does not make the blend itself miscible with mineral oils. Furthermore, the amount of hydrocarbon that can be added is typically limited to a few % to maintain an A1 (non-flammable) ASHRAE rating. Fundamentals definitions Solubility When applied to refrigerants and lubricant oils used in refrigeration systems, solubility is the property of the refrigerant (solute) to dissolve in the lubricant oil (solvent). The extent of the refrigerant solubility in the oil without seeing two phases is known as the saturation concentration. Immiscibility/Miscibility When the refrigerant reaches its solubility limit in the lubricant oil, adding more refrigerant results in precipitation, or phase separation, and this is typically referred to as an immiscible condition. On the other hand when you can keep adding refrigerant to the lubricant oil and still have a single liquid phase, it means that the refrigerant is fully miscible in the oil.

Practical cases of miscibility Refrigeration systems are usually designed for refrigerant/lubricant oil pairs that are fully miscible, or that otherwise show acceptable miscibility, at least at the concentration of lubricant oil circulating in the system and in the coolest parts of the system, but preferably over the range of operating conditions (evaporating and condensing temperatures). This will ensure proper oil return to the compressor as the refrigerant is able to carry the oil through the system. As for what is found in the field, Figure 1 shows the two most common cases: 1. A typical case of full miscibility is observed with R-22 and mineral oil. It is also observed with R-407C in POE oil. 2. On the opposite side, R-407C was found to be immiscible with mineral oil. This is also the case with the HFC/HC blend R-422A, which has some improved solubility due to the hydrocarbon presence. Still, it is fundamentally immiscible in mineral oil. System After Oil Separator Before Oil Separator Low Temperature 0.36% 0.47% Medium Temperature 0.05% 0.17% Table 1 Oil circulation ratio measured in a supermarket refrigerant: R-22 / oil: mineral oil. How much oil is in circulation in real systems? What is actually happening in a refrigeration system depends on several factors, for example: 1. Working fluids (refrigerant, lubricant); 2. Hardware (compressor type and age, connecting lines, heat exchangers, oil separators); and 3. Operating conditions. All systems have lubricant in circulation and the type and amount of lubricant varies with the above-listed parameters. Table 1 shows results of field studies performed in supermarket systems. The two supermarket systems studied used reciprocating compressors that were 10 years old on average. Samples were taken before and after the oil separators. This would allow studying systems with and without an oil separator. These findings show the worst-case scenario being low-temperature systems where the oil circulation ratio, or OCR, Circle Reader Service No. 39 MAY 2013 RSES Journal 15

can be as high as 0.47% when no oil separator is used, and 0.36% when using an oil separator (see Table 1). It can be concluded that systems with oil separators have lower OCRs than systems with no oil separators. Nevertheless, few old-wear compressors where OCR values were as high as 3.5% were also observed. Such compressors should be replaced, but this hardly happens in practical applications, as detecting these high OCRs is difficult. Even higher values are also mentioned in the field (e.g. up to around 8%), but no detailed description of the compressor type and age is usually shown. Figure 2 Pressure-drop penalty due to excessive oil hold-up in the suction line when using HFC/HC blend R-422A. Refrigerant/oil relationship in systems What happens in simple systems without a liquid receiver? Figure 3 Observations and results for a horizontal liquid receiver when working with the three refrigerants indicated and mineral oil. Outlet Inlet 16 RSES Journal MAY 2013

Refrigerant Inlet OCR (% by weight) Horizontal Receiver Outlet OCR (% by weight) R-22 0.40% 0.40% R-407C 0.40% 0.00% R-422A 0.40% 0.33% Table 2 Oil circulation ratio measured before and after the high-side liquid receiver for R-22, R-407C and R-422A with mineral oil. To investigate the effectiveness of the HFC/HC blend R- 422A, an R-22 low-temperature refrigeration system that uses mineral oil was used as a baseline. Both oil retention in vertical riser and the resultant pressure drop were measured. Overall, the system performed adequately with no significant drop in oil level in the compressor. R-422A was tested next. Figure 2 shows the additional pressure drop due to oil retention in vertical suction lines when employing this HFC/HC blend (R-422A) with the same mineral oil. The OCR simulated in this test was of 3.5% (oil in the refrigerant flow by weight). Oil retention was 30% higher than for R-22. Moreover, pressure drop was 70% mtwfsusa.com DON T MISS US AT NRA MAY 18-21 BOOTH 3401/3601 Overachieving undercounter Presenting NEO, the everywhere you need ice machine. By providing increased levels in performance, intelligence and convenience, Manitowoc s new ice machine offers an all-in-one solution to your undercounter ice cube needs. 2013 Manitowoc Ice All Rights Reserved Thirsty for more? Talk with Manitowoc Ice. 1-920-682-0161 ManitowocIce.com/NEO Overachieve_7.125x4.875.indd 1 Circle Reader Service No. 40 4/11/13 8:04 AM MAY 2013 RSES Journal 17

Figure 4 Capacity and cop penalty due to mineral oil circulating in the system with ocr up to 3.5%. higher. In looking at these results, one could conclude that systems with no liquid receiver may be successfully retrofitted to this HFC/HC blend (R-422A) if the system is close coupled and the oil circulation rate is low enough. Still, the overall performance will be affected due to the additional pressure drop in the suction line, and also due to oil logging in the evaporator, which can negatively affect heat transfer and pressure drop. What happens in systems with high-side liquid receivers? As mentioned before, the small amount of hydrocarbon used in the HFC/HC blend R-422A is not enough to make it fully miscible with mineral oils. This is clearly shown in high-side liquid receivers where a significant retention of mineral oil is observed. These studies (Figure 3) show that a layer of oil will form on the surface of the liquid R-407C or HFC/HC blend R-422A. These studies were done using a horizontal liquid receiver, which was modified to add large sight glasses in the two extremes. Tests were done using oilcirculation values for a system with an oil separator (Table 2). The OCR values shown were measured by sampling before and after the liquid receiver. Looking at the imbalance of OCRs for R-407C and the HFC/HC blend R-422A (OCR at inlet higher than OCR at outlet), one can conclude that these blends are not reliable for retrofitting systems that use mineral oil as lubricant. Performance Some HFC blends such as R-407C come close to duplicating R-22 s performance at certain operating conditions, however a closer look will show that both the system capacity and efficiency may have been impacted due to oil circulation. 18 RSES Journal MAY 2013 Figure 4 shows how much the performance is affected because of the presence of oil in circulation. These tests were performed in a 1.8-ton refrigeration system. Three cases were considered: R-22/MO, R-407C/MO and R-422A/MO. The initial tests were performed using two very-high-efficiency oil separators so OCR was near zero. These initial points represent the performance of each fluid without any oil effects. When oil is taken into account, all the refrigerants experience some reduction of capacity and efficiency. Even R-22 would suffer some degradation when oil accumulates in the suction line for usual OCRs (1% 2%). Moreover, with the HFC/HC blend R-422A, a more dramatic degradation was observed, as more oil accumulates in the system, causing an increase of pressure drop. General guidelines/conclusions Giving a general recipe for R-22 retrofits is not possible, but general recommendations are possible, from the results of these studies, and other in-house technical knowledge: Air-conditioners and refrigeration systems without liquid receiver According to these studies, the least demanding system would be a typical air-conditioner without a liquid receiver where the main effects would be on the connecting lines. In general, the effects would not be as dramatic due to the relatively high evaporating temperatures (example: 45 F SST). At these conditions, any solubility of the refrigerant like R-422A in the oil will be reasonable. Next, refrigeration systems without a liquid receiver were considered, where the additional challenge is the fact that the evaporating temperatures can be significantly lower (example:

Giving a general recipe for R-22 retrofits is not possible, but general recommendations are possible, from the results of these studies, and other in-house technical knowledge. -25 F SST). In these systems, the HFC/HC blend R-422A can be used, because the compressor will get the desired oil return. Still, the user will experience some performance degradation as shown in the previous section (see Figure 3). Refrigeration systems with high-side liquid receiver Next in the degree of difficulty are systems with a high-side liquid receiver. These systems will need a greater degree of solubility in the oil, which could not be provided by the HFC/HC blend R-422A that were studied. In these cases, based on this work, adding some amount of POE oil would help to increase solubility to the point to get the oil through the liquid receiver. Tests indicated that at least 20% of the oil system needs to be of the POE type. Heat pumps with low-side suction accumulator Even more difficult are the systems with a low-side suction accumulator where the liquid accumulation occurs at low temperatures and pressures. At these conditions, any solubility of the refrigerant in the oil will be reduced. For these types of systems, a greater degree of solubility is needed. Based on this work, a full change to POE oil would advisable for refrigerants such as R-407C and R-422A. In conclusion, there is no perfect replacement for R-22. These findings indicate that the performance of certain HFC and HFC/HC blends, namely R-407C and R-422A, can be impacted by the type and amount of oil in circulation (OCR). If economically feasible, a change to POE oil will result in the best system performance, durability and trouble-free operation for refrigerants such as R-407C and R-422A. As for the HFC/HC blend R-422A, some specific A/C and refrigeration systems (no liquid receivers or suction accumulators) have been identified where they can be cautiously used. Still users should be aware of some system performance impact coming from this choice. DISCLAIMER: Although all statements and information contained herein are believed to be accurate and reliable, they are presented without guarantee or warranty of any kind, expressed or implied. Information provided herein does not relieve the user from the responsibility of carrying out their own tests and experiments, and the user assumes all risks and liability for use of the information and results obtained. Statements or suggestions concerning the use of materials and processes are made without representation or warranty that any such use is free of patent infringement and are not recommendations to infringe on any patents. The user should not assume that all toxicity data and safety measures are indicated herein or that other measures may not be required. Samuel F. Yana Motta, Refrigerants R&D Leader; Elizabet D. Vera Becerra, Engineer R&D; Ron Vogl, Refrigerants Marketing Manager; and Mark W. Spatz, Refrigerants Technology Leader, work with Honeywell International located in Buffalo, NY. The research discussed in this feature occurred at Honeywell s Buffalo Research Laboratory. For more information, e-mail samuel. yanamotta@honeywell.com or visit www.honeywell.com. Circle Reader Service No. 41 MAY 2013 RSES Journal 19