BALANCED THREE-PHASE CIRCUITS



Similar documents
Lecture Notes ELE A6

Chapter 11 Balanced Three-Phase Circuits

BALANCED THREE-PHASE AC CIRCUIT

Three Phase Circuits. Three Phase Circuits

UNIVERSITY OF NORTH CAROLINA AT CHARLOTTE. Department of Electrical and Computer Engineering

Chapter 12 Three-Phase Circuit

Three phase circuits

Power measurement in balanced 3 phase circuits and power factor improvement. 1 Power in Single Phase Circuits. Experiment no 1

ECE 431. Experiment #1. Three-Phase ac Measurements. PERFORMED: 26 January 2005 WRITTEN: 28 January Jason Wells

Chapter 24. Three-Phase Voltage Generation

3-Phase AC Calculations Revisited

Equipment: Power Supply, DAI, Variable resistance (8311), Variable inductance (8321)

1 Introduction. 2 The Symmetrical Component Transformation. J.L. Kirtley Jr.

1 Introduction. 2 Two Phases. J.L. Kirtley Jr.

How To Balance Three Phase Power In A Balanced System

THREE-PHASE POWER SYSTEMS ECE 454/554: Power Systems Laboratory

Basic Electrical Technology Dr. L. Umanand Department of Electrical Engineering Indian Institute of Science, Bangalore. Lecture phase System 4

Three-phase AC circuits

THREE PHASE CIRCUITS

How To Wire A Three Phase, Single Phase, Wye Transformer

Three-Phase AC Power Circuits

Chapter 12: Three Phase Circuits

Module 5. Three-phase AC Circuits. Version 2 EE IIT, Kharagpur

(3 )Three Phase Alternating Voltage and Current

Power System Harmonics

How To Understand The Power Control System

Unit 33 Three-Phase Motors

Motor Protection Voltage Unbalance and Single-Phasing

SYNCHRONOUS MACHINES

TRANSFORMER: THREE PHASE

Alternating current three-phase circuits

ACCURACY OF POTENTIALTRANSFORMERS

TESLA Recorder Power Metering Setup Configuration for 3 and 2 Element Watt/VAR Metering

PHASOR DIAGRAMS HANDS-ON RELAY SCHOOL WSU PULLMAN, WA. RON ALEXANDER - BPA

FUNDAMENTALS OF ENGINEERING (FE) EXAMINATION REVIEW

Figure. 1 - Split Phase 240/120V circuit (180 phase shift)

Single and Three Phase Transformer Testing Using Static Motor Circuit Analysis Techniques

SAMPLE OF THE STUDY MATERIAL PART OF CHAPTER 3. Symmetrical Components & Faults Calculations

Fault Analysis I PowerWorld Corporation

Instrument Transformer Wiring Troubleshooting Guide Three Phase Meters Revision 0, Initial Issue, April 26, 1993

USE OF A SINGLE ELEMENT WATTMETER OR WATT TRANSDUCER ON A BALANCED THREE-PHASE THREE-WIRE LOAD WILL NOT WORK. HERE'S WHY.

13 ELECTRIC MOTORS Basic Relations

ET 332b Ac Electric Machines and Power Systems

Radial Distribution Test Feeders

The generation and supply of electricity within the U.K is achieved through the use of a 3-phase system.

Genetic Algorithm approach to find excitation capacitances for 3- phase smseig operating single phase loads

SHIP SERVICE GENERATORS (AC)

Introduction to PowerWorld Simulator: Interface and Common Tools

Neutral to Earth Voltage Reduction Methods in Three-Phase Four Wire Distribution Systems

AC Generators. Basic Generator

EDEXCEL NATIONAL CERTIFICATE/DIPLOMA UNIT 5 - ELECTRICAL AND ELECTRONIC PRINCIPLES NQF LEVEL 3 OUTCOME 4 - ALTERNATING CURRENT

2. A conductor of length 2m moves at 4m/s at 30 to a uniform magnetic field of 0.1T. Which one of the following gives the e.m.f. generated?

Understanding Delta Conversion Online "Power Regulation" - Part 2

The Fundamentals of Three-Phase Power Measurements. Application Note

AP Physics Electricity and Magnetism #4 Electrical Circuits, Kirchoff s Rules

11. MEASUREMENT OF POWER CONSUMPTION OF THE NONBALANCED THREE-PHASE LOAD

Online EFFECTIVE AS OF JANUARY 2013

Triplen Harmonics Mitigation 3 Phase Four-Wire Electrical Distribution System Using Wye- Zig-Zag Transformers

University of Cape Town

The following table shows approximate percentage wise the

Simulation of Ungrounded Shipboard Power Systems in PSpice

SECTION POWER MONITOR FOR ELECTRICAL, STEAM CONDENSATE, AND WATER PART I - GENERAL

Understanding Power Factor and How it Affects Your Electric Bill. Presented by Scott Peele PE

Three-Phase Electric Power Distribution for Computer Data Centers

Prepared By: Sheilani Binti Shaari Department of Electrical Engineering/PKB

How to Graph Trigonometric Functions

How To Understand And Understand The Theory Of Electricity

Short Circuit Current Calculations

MODELING AND TESTING OF UNBALANCED LOADING AND VOLTAGE REGULATION. Prepared For: California Energy Commission Public Interest Energy Research Program

SOLID MECHANICS TUTORIAL MECHANISMS KINEMATICS - VELOCITY AND ACCELERATION DIAGRAMS

Open Phase Conditions in Transformers Analysis and Protection Algorithm

Definition AC Power Distribution

Rotary Phase Converters

Network Theory Question Bank

Product Data Bulletin

Rule Fast Track Analysis for National Life Insurance Co.

Fundamentals of Electrical Power Measurement

LABORATORY 10 TIME AVERAGES, RMS VALUES AND THE BRIDGE RECTIFIER. Bridge Rectifier

4.5 Transformer Connections

Neutral Currents in Three Phase Wye Systems

Modeling and Testing of Unbalanced Loading and Voltage Regulation

Loading Considerations When Paralleling Transformers

Effects of Phase Imbalance on Data Center Energy Management

Three-phase analysis of unbalanced systems

Scholars Research Library

DOE FUNDAMENTALS HANDBOOK ELECTRICAL SCIENCE Volume 3 of 4

CHAPTER 2 EXAMPLES AND TABLES

Basics of Electricity

8 Speed control of Induction Machines

System Grounding and Ground-Fault Protection Methods for UPS-Supplied Power Systems

CYCLOCONVERTERS. Fig.1 Block diagram of a cycloconverter

ELECTRONIC POWER SYSTEMS

Power Factor Correction for Power Systems First Semester Report Spring Semester 2007

Power Technology Issue 104. Modeling of Two-Winding Voltage Regulating Transformers for Positive Sequence Load Flow Analysis in PSS E

PROBLEM 2.9. sin 75 sin 65. R = 665 lb. sin 75 sin 40

Measurement of Power in single and 3-Phase Circuits. by : N.K.Bhati

Instruction Manual. EPM 6010 Multi-function Power Metering System. Chapter 1: * A1* GE Energy ISO 9001 LISTED

Induction Motor Theory

Transcription:

BALANCED THREE-PHASE CIRCUITS The voltages in the three-phase power system are produced by a synchronous generator (Chapter 6). In a balanced system, each of the three instantaneous voltages have equal amplitudes but are separated from the other voltages by a phase angle of 120 o. The three voltages (or phases) are typically labeled a, b and c. The common reference point for the three phase voltages is designated as the neutral connection and is labeled as n. We may define either a positive phase sequence (abc) or a negative phase sequence (acb) as shown below. The three sources V an, V bn and V cn are designated as the line-to-neutral voltages in the three-phase system.

LINE-TO-LINE VOLTAGES An alternative way of defining the voltages in a balanced three-phase system is to define the voltage differences between the phases. These voltages are designated as line-to-line voltages. The line-to-line voltages can be expressed in terms of the line-to-neutral voltages by applying Kirchoff s voltage law to the generator circuit, which yields Inserting the line-to-neutral voltages for a positive phase sequence into the line-to-line equations yields

If we compare the line-to-neutral voltages with the line-to-line voltages, we find the following relationships, Line-to-neutral voltages Line-to-line voltages

Line-to-line voltages in terms of line-to-neutral voltages The equations above show that the magnitudes of the line-to-line voltages in a balanced three-phase system with a positive phase sequence are %&3 times the corresponding line-to-neutral voltages and lead these voltages by 30 o.

THREE-PHASE CONNECTIONS The sources and loads in a three-phase system can each be connected in either a wye (Y) or delta ()) configuration. Note that the wye connections are line-to-neutral while the delta connections are line-to-line with no neutral. Also note the convention on the node designations (lowercase letters at the source connections and uppercase letters at the load connections). Sources Loads Wye source Wye load Delta source Delta load

BALANCED WYE-WYE CONNECTION The balanced three-phase wye-wye connection is shown below. Note that the line impedance for each of the individual phases in included in the circuit. The line impedances are assumed to be equal for all three phases. The line currents (I aa, I bb and I cc ) are designated according to the source/load node naming convention. The source current, line current, and load current are all one in the same current for a given phase in a wye-wye connection. Wye source Wye load Assuming a positive phase sequence, the application of Kirchoff s voltage law around each phase gives where Z total is the total impedance in each phase and 2 Z is the phase angle associated with the total phase impedance. The preceding equations can be solved for the line currents.

Line Currents Line-to-neutral voltages Note that the line current magnitudes are equal and each line current lags the respective line-to-neutral voltage by the impedance phase angle 2 Z. Thus, the balanced voltages yield balanced currents. The phasor diagram for the line currents and the line-to-neutral voltages is shown below. If we lay the line-to-neutral voltage phasors end to end, they form a closed triangle (the same property is true for the line currents). The closed triangle shows that the sum of these phasors is zero.

The fact that the line currents sum to zero in the balanced wye-wye connection shows that the neutral current I n is zero in this balanced system. Thus, the impedance of the neutral is immaterial to the performance of the circuit under balanced conditions. However, any imbalance in the system (loads, line impedances, source variations, etc.) will produce a non-zero neutral current. In any balanced three-phase system (balanced voltages, balanced line and load impedances), the resulting currents are balanced. Thus, there is no real need to analyze all three phases. We may analyze one phase to determine its current, and infer the currents in the other phases based on a simple balanced phase shift (120 o phase difference between any two line currents). This technique is known as the per phase analysis. Example (Per phase analysis) A wye-wye balanced three-phase system with a phase voltage of 120 V-rms (positive phase sequence) has a line impedance of Z line = (1+j1) S and load impedance of Z Y = (20+j10) S. Determine the phasor line currents (I aa, I bb, I cc ) and the phasor load voltages (V AN, V BN, V CN ). Analyze the a-phase only.

To determine the b phase responses, subtract 120 o from the angle of the a phase results. To determine the c phase responses, subtract 240 o (add 120 o ) to the angle of the a phase results.

INSTANTANEOUS THREE-PHASE POWER In a balanced wye-wye three-phase system, we have found that the line currents and load voltages are balanced (equal magnitudes, phase angles at 120 o intervals). Thus, the rms phasor line currents may be written in general form as where we have assumed a positive phase sequence. The resulting phasor load voltages can be written in terms of the phasor line currents as The corresponding instantaneous line currents and load voltages are

The total instantaneous power delivered to the three-phase load is where the three terms represent the instantaneous power in the individual loads associated with the three phases. Inserting the instantaneous load voltages and line currents gives The cosine products in the equation above can be rewritten using the trigonometric identity used in the single phase power derivation: The instantaneous power then becomes The three double frequency terms in the instantaneous power expression add to zero according to the following trigonometric identity: The instantaneous power in the balanced three-phase load reduces to

Note that the balanced three-phase load instantaneous power is constant and equal to three times the average power in one phase. The time-invariant characteristic of the three-phase instantaneous power is in contrast to that of a single-phase system where the instantaneous power was shown to oscillate at twice the system frequency. The constant nature of the three-phase instantaneous power (smooth power delivery) is of particular importance in three-phase motors. The mechanical shaft torque is constant and vibration is minimized. The concept of complex power can be extended to a balanced threephase system by defining the three-phase complex power delivered to the wye load as where V load and I line are the load voltage and line current phasors for an individual phase of the three-phase system with a wye-connected load. Inserting the voltage and current phasors into the complex three-phase power equation gives Thus, the apparent, real and reactive power components in a three-phase wye load are

Note that the preceding equations are specialized for wye loads. A more general way of writing the complex power for any type of three-phase load is where Wye load Delta load V load Line-to-neutral voltage (V AN ) Line-to-line voltage (V AB ) I load Line current (I aa ) Load current (I AB ) S 3N = 3V AN I aa * S 3N = 3V AB I AB * The concepts of power factor and the complex power triangle can also be extended to a balanced three phase power system without loss of generality. The three-phase power factor is defined by the same singlephase equation since the relative angle between the voltage and current is equal in all three phases of a balanced three-phase system. The three-phase complex power triangle is identical to the single-phase power triangle with the apparent, real and reactive powers replaced by the corresponding three-phase values.

THREE-PHASE CONNECTIONS INVOLVING DELTA SOURCES OR LOADS In addition to the wye-wye three-phase connection, there are three other possible configurations of wye and delta sources and loads. Delta-Delta Connection Wye-Delta Connection

Delta-Wye Connection The most efficient way to handle three-phase circuits containing delta sources and/or loads is to transform all delta connections into wye connections. Delta-Wye Source Transformation Given that a delta source is defined in terms of line-to-line voltages while the wye source is defined in terms of line-to-neutral voltages, we can use the previously determined relationship between line-to-line voltages and line-to-neutral voltages to perform the transformation.

Thus, line-to-neutral voltages in a wye-connected source that are equivalent to the line-to-line voltages in the delta-connected source are Thus, we simply divide the appropriate line-to-line voltage in the delta source by %&3 and subtract 30 o from its phase angle to find the corresponding line-to-neutral voltages for the wye source. Example (Wye-Delta source transformation) Given a delta-connected source with the following rms voltages: determine the equivalent wye-connected source (208/%&3 =120). Y

Delta Source - Source Current and Line Current Relationship The delta source line currents (I aa, I bb, I cc ) are related to the corresponding source currents (I ba, I cb, I ac ) according to Kirchoff s current law. Assuming a balanced three-phase system with source currents defined by the resulting phasor diagram relating the source and line currents is shown below.

The phasor diagram shows that the source currents in a delta source lead the line currents by 30 o and are 1/%&3 times the magnitude. Summary: Delta Source (I s, V s) in terms of Wye Source (I s, V s)

Delta Load - Load Current and Line Current Relationship The line currents in the delta-connected load (I aa, I bb, I cc ) are related to the corresponding delta load currents (I AB, I BC, I CA ) according to Kirchoff s current law. Given a balanced three-phase system, the currents flowing into the deltaconnected load can be defined by The resulting phasor diagram relating the line currents to the deltaconnected load currents follows the same pattern as the delta-connected source.

The phasor diagram shows that the load currents in a delta load lead the line currents by 30 o and are 1/%&3 times the magnitude.

Wye Load - Line-to-line Voltage and Load Voltage Relationship Note that the load voltages in a wye-connected load are the line-to-neutral voltages at the load. The line-to-line voltages of a wye-connected load are related to the line-to-neutral voltages by For a balanced three-phase system, the line-to-neutral voltages may be written as The phasor diagram relating the line-to-line voltages to the load voltages is shown below.

The load voltages and the line-to-line voltages in a wye-connected load are related by

Delta-Wye Load Transformation A delta-connected three-phase load can be replaced by an equivalent wye-connected load if the two loads are equivalent (draw the same line currents from the three-phase source). Note that the line-to-line voltages at the delta-connected load are the load voltages. The a phase line currents for the wye and delta loads are defined by Delta Load Wye Load The line currents are equal if The same results are found for the other two line currents. Thus, a deltaconnected load can be replaced by a wye-connected load with one-third the impedance per phase.

Example (Delta-load transformation, three-phase power) A balanced 120 V-rms wye-connected three-phase source with positive phase sequence is connected to two balanced three-phase loads connected in parallel. Load #1 is wye-connected with Z Y1 = (30 + j40) S and Load #2 is delta-connected with Z )2 = (60! j45) S. The line impedance per phase is Z line = (2 + j4) S. Determine (a.) the per phase line current (b.) the total real and reactive power drawn from the source (c.) the per phase line-to-neutral voltage across the parallel load (d.) the per phase load current in the wye and delta loads and (e.) the total real and reactive three-phase power delivered to each load and the line. Transforming the delta-connected load #2 into a wye-connected load gives

(a.) The load impedance in the per phase equivalent circuit is the parallel combination of the two wye load impedances. The total impedance seen by the phase a source voltage is The resulting phase a line current is (b.) The total complex power supplied by the three-phase source is

(c.) The per phase line-to-neutral voltage across the parallel load is (d.) The per phase load currents in the two wye-connected loads are To determine the load current in the original delta-connected load, we utilize the relationship between the line and load currents in a deltaconnected load. The load current in the wye-connected load #2 represents the equivalent line current for the original delta-connected load #2. Thus, the load current in the original delta-connected load #2 is (e.) The total three-phase power delivered to each load is

The power delivered to the transmission line is given by Note that the total power drawn from the source equals the total powered delivered to the line and the load.