The Different Types of UPS Systems



Similar documents
The Different Types of UPS Systems

The Different Types of UPS Systems

Increasing Data Center Efficiency by Using Improved High Density Power Distribution

Efficiency and Other Benefits of 208 Volt Over 120 Volt Input for IT Equipment

Electrical Efficiency Modeling of Data Centers

AC vs DC Power Distribution for Data Centers

Calculating Total Cooling Requirements for Data Centers

Power Quality. Uninterruptible Power Supply

Impact of Leading Power Factor on Data Center Generator Systems

Technical Comparison of On-line vs. Line-interactive UPS designs

Selecting a UPS Topology for your Data Center. by Dr. Daniel Becker, Ph.D., Methode Active Energy Solutions

Calculating Total Power Requirements for Data Centers

A Comparison of AC and DC Power Distribution in the Data Center Transcript

Electrical Efficiency Modeling for Data Centers

A COMPARISON OF TYPICAL UNINTERRUPTIBLE POWER SUPPLY (UPS) DESIGNS IN TODAY S MARKETS

Understanding Power Factor, Crest Factor, and Surge Factor. White Paper #17

Avoiding Costs from Oversizing Data Center and Network Room Infrastructure

Considering the effects of UPS operation with leading power factor loads

UNINTERRUPTIBLE POWER SUPPLIES >9900AUPS UNINTERRUPTIBLE POWER SUPPLIES

High-Efficiency AC Power Distribution for Data Centers

Qualitative Analysis of Power Distribution Configurations for Data Centers

Use of the Signal Reference Grid in Data Centers

Product Data Bulletin

AC vs. DC Power Distribution for Data Centers

AC vs DC for Data Centers and Network Rooms

Strategies for Deploying Blade Servers in Existing Data Centers

How To Calculate Total Cooling Requirements For Data Center

Avoiding Costs from Oversizing Data Center and Network Room Infrastructure

Implementing Energy Efficient Data Centers

Design a Phase Interleaving PFC Buck Boost Converter to Improve the Power Factor

Top 12 Questions to Consider When Choosing UPS Systems for Network/Server Applications

Electrical Systems. <Presenter>

Cooling Strategies for IT Wiring Closets and Small Rooms

PRODUCT PRESENTATION PROTECT B.PRO YEAR 2013 NOVEMBER 2012 DATA & IT, SBU C-UPS, PM/SR

> Executive summary. The Role of Isolation Transformers in Data Center UPS Systems. White Paper 98 Revision 0. Contents.

Selecting an Industry-Standard Metric for Data Center Efficiency

Overload Protection in a Dual-Corded Data Center Environment

Re-examining the Suitability of the Raised Floor for Data Center Applications

UPS Topologies & Architectures. Don Lemmon Tubbesing Solutions (214) don@tubbesing.com

Variable Frequency Drives - a Comparison of VSI versus LCI Systems

A Scalable, Reconfigurable, and Efficient Data Center Power Distribution Architecture

Theoretical review. Contents

415V DISTRIBUTION FOR GREEN DATA CENTERS

415V DISTRIBUTION FOR GREEN DATA CENTERS

Liebert GXT MT+ CX UPS, 1000VA VA Intelligent, Reliable UPS Protection. AC Power for Business-Critical Continuity

Guidelines for Specification of Data Center Power Density

Transformerless UPS systems and the 9900 By: John Steele, EIT Engineering Manager

7-41 POWER FACTOR CORRECTION

APC Smart-UPS RT. GUIDE SPECIFICATIONS FOR 3000VA, 5000VA and 6000 VA Smart-UPS RT 230VAC Uninterruptible Power Supply

Improving Rack Cooling Performance Using Airflow Management Blanking Panels

A Scalable, Reconfigurable, and Efficient Data Center Power Distribution Architecture

Understanding Delta Conversion Online "Output Power Factor Ratings" - Part 7

Galleon 6-10K Online UPS. Voltronic Power Technology Corporation

The full wave rectifier consists of two diodes and a resister as shown in Figure

GE Digital Energy. TLE Series UPS kw three phase 400 Vac. with best-in-class efficiency. gimagination at work

LTR Series Uninterruptible Power Systems 700 VA KVA. General Specification

Power Quality For The Digital Age INVERTING SOLAR POWER A N E N V IRONME N TA L P OT E N T I A L S W HI T E PA PER

POWER SYSTEM HARMONICS. A Reference Guide to Causes, Effects and Corrective Measures AN ALLEN-BRADLEY SERIES OF ISSUES AND ANSWERS

Fairchild On-Line Design Tool: Power Supply WebDesigner Step-by-Step Guide

UNDERSTANDING POWER FACTOR AND INPUT CURRENT HARMONICS IN SWITCHED MODE POWER SUPPLIES

NO-BREAK KS 7e. Concentrated Energy kva (50Hz) 3000 kva (60Hz) DIESEL ROTARY UNINTERRUPTIBLE POWER SUPPLY SYSTEM

Power and Cooling Capacity Management for Data Centers

Data center energy efficiency and power quality: an alternative approach with solid state transformer

Harmonics and Noise in Photovoltaic (PV) Inverter and the Mitigation Strategies

Intelligent Power Distribution in the Data Center

Improving Rack Cooling Performance Using Airflow Management Blanking Panels

Evaluating the Opportunity for DC Power in the Data Center

Common Power Problems & Power Protection Solutions

2012 San Francisco Colloquium

DESIGNING MODERN ELECTRICAL SYSTEMS WITH TRANSFORMERS THAT INHERENTLY REDUCE HARMONIC DISTORTION IN A PC-RICH ENVIRONMENT

Data Center Projects: Project Management

Mitigating data center harmonics

TLE Series UPS kva/kw three phase 400 Vac with best-in-class efficiency

SSPI-APPN OTES: PARALLEL C ONNECTIONS

A Low Cost Power Quality and Energy Savings Laboratory for Undergraduate Education and Research

Yam Hong 施 耐 德 電 機 亞 太 日 本 區 (APJ) 三 相 關 鍵 電 源 市 場 開 發 經 理. Schneider Electric - Division - Name Date

CHAPTER 2B: DIODE AND APPLICATIONS. D.Wilcher

Power Supplies. 1.0 Power Supply Basics. Module

Single Phase UPS Management, Maintenance, and Lifecycle

Introduction. Harmonics and IEEE 519 Page 1 of 19

Avoiding AC Capacitor Failures in Large UPS Systems

New High Current MOSFET Module Offers 177 µω R DS(on)

Series 7400 M (10/20/30/40/60 kva) Maximum Protection For Mission Critical Network Applications. Series 7400 M

Experts speak on UPS output Watt, VA, and Power Factor ratings.

Wireless Networks and Power Quality

CEMEP UPS. The high environmental performance solution for power supply to high-availability data centers

Smart-UPS 3 Phase And MGE Galaxy 3500

The Quest for Energy Efficiency. A White Paper from the experts in Business-Critical Continuity

Tough Decision: On-Line or Line-Interactive UPS?

Improvements of Reliability of Micro Hydro Power Plants in Sri Lanka

Working definitions of terms: Commercial vs. Industrial UPS Systems:

SmartOnline V 6kVA 4.2kW On-Line Double-Conversion UPS, Extended Run, SNMP, Webcard, 6U Rack/Tower, DB9 Serial, Hardwire

98% Efficient Single-Stage AC/DC Converter Topologies

Buffer Op Amp to ADC Circuit Collection

LAP ENERGIA PARA DATACENTERS

APC Smart-UPS RT. GUIDE SPECIFICATIONS FOR 1000VA, 2000VA & 3000VA Smart-UPS RC 230VAC Uninterruptible Power Supply

HVDC-VSC: transmission technology of the future

Transcription:

The Different Types of UPS Systems By Neil Rasmussen White Paper #1 Revision 5

Executive Summary There is much confusion in the marketplace about the different types of UPS systems and their characteristics. Each of these UPS types is defined, practical applications of each are discussed, and advantages and disadvantages are listed. With this information, an educated decision can be made as to the appropriate UPS topology for a given need. 2

Introduction The varied types of UPSs and their attributes often cause confusion in the data center industry. For example, it is widely believed that there are only two types of UPS systems, namely standby UPS and online UPS. These two commonly used terms do not correctly describe many of the UPS systems available. Many misunderstandings about UPS systems are cleared up when the different types of UPS topologies are properly identified. UPS topology indicates the basic nature of the UPS design. Various vendors routinely produce models with similar designs, or topologies, but with very different performance characteristics. Common design approaches are reviewed here, including brief explanations about how each topology works. This will help you to properly identify and compare systems. UPS types A variety of design approaches are used to implement UPS systems, each with distinct performance characteristics. The most common design approaches are as follows: Standby Line Interactive Standby-Ferro Double Conversion On-Line Delta Conversion On-Line The Standby UPS The Standby UPS is the most common type used for Personal Computers. In the block diagram illustrated in Figure 1, the transfer switch is set to choose the filtered input as the primary power source (solid line path), and switches to the battery / inverter as the backup source should the primary source fail. When that happens, the transfer switch must operate to switch the load over to the battery / inverter backup power source (dashed path). The inverter only starts when the power fails, hence the name "Standby." High efficiency, small size, and low cost are the main benefits of this design. With proper filter and surge circuitry, these systems can also provide adequate noise filtration and surge suppression. SURGE SUPPRESSOR Figure 1 Standby UPS FILTER TRANSFER CHARGER 3

The Line Interactive UPS The Line Interactive UPS, illustrated in Figure 2, is the most common design used for small business, Web, and departmental servers. In this design, the battery-to- power converter (inverter) is always connected to the output of the UPS. Operating the inverter in reverse during times when the input power is normal provides battery charging. When the input power fails, the transfer switch opens and the power flows from the battery to the UPS output. With the inverter always on and connected to the output, this design provides additional filtering and yields reduced switching transients when compared with the Standby UPS topology. In addition, the Line Interactive design usually incorporates a tap-changing transformer. This adds voltage regulation by adjusting transformer taps as the input voltage varies. Voltage regulation is an important feature when low voltage conditions exist, otherwise the UPS would transfer to battery and then eventually down the load. This more frequent battery usage can cause premature battery failure. However, the inverter can also be designed such that its failure will still permit power flow from the input to the output, which eliminates the potential of single point failure and effectively provides for two independent power paths. High efficiency, small size, low cost and high reliability coupled with the ability to correct low or high line voltage conditions make this the dominant type of UPS in the 0.5-5kVA power range. Figure 2 Line Interactive UPS TRANSFER < CHARGING (NORMAL) DISCHARGING (POWER FAIL) > The Standby-Ferro UPS The Standby-Ferro UPS was once the dominant form of UPS in the 3-15kVA range. This design depends on a special saturating transformer that has three windings (power connections). The primary power path is from input, through a transfer switch, through the transformer, and to the output. In the case of a power failure, the transfer switch is opened, and the inverter picks up the output load. In the Standby-Ferro design, the inverter is in the standby mode, and is energized when the input power fails and the transfer switch is opened. The transformer has a special "Ferro-resonant" capability, which provides limited voltage regulation and output waveform "shaping". The isolation from power transients provided 4

by the Ferro transformer is as good as or better than any filter available. But the Ferro transformer itself creates severe output voltage distortion and transients, which can be worse than a poor connection. Even though it is a standby UPS by design, the Standby-Ferro generates a great deal of heat because the Ferro-resonant transformer is inherently inefficient. These transformers are also large relative to regular isolation transformers; so standby-ferro UPS are generally quite large and heavy. Standby-Ferro UPS systems are frequently represented as On-Line units, even though they have a transfer switch, the inverter operates in the standby mode, and they exhibit a transfer characteristic during an power failure. Figure 3 illustrates this Standby-Ferro topology. Figure 3 Standby-Ferro UPS TRANSFER TRANSFORMER CHARGER High reliability and excellent line filtering are this design s strengths. However, the design has very low efficiency combined with instability when used with some generators and newer power-factor corrected computers, causing the popularity of this design to decrease significantly. The principal reason why Standby-Ferro UPS systems are no longer commonly used is that they can be fundamentally unstable when operating a modern computer power supply load. All large servers and routers use Power Factor Corrected power supplies which draw only sinusoidal current from the utility, much like an incandescent bulb. This smooth current draw is achieved using capacitors, devices which lead' the applied voltage, Ferro resonant UPS system utilize heavy core transformers which have an inductive characteristic, meaning that the current 'lags' the voltage. The combination of these two items form what is referred to as a 'tank' circuit. Resonance or 'ringing' in a tank circuit can cause high currents, which jeopardize the connected load. 5

The Double Conversion On-Line UPS This is the most common type of UPS above 10kVA. The block diagram of the Double Conversion On-Line UPS, illustrated in Figure 4, is the same as the Standby, except that the primary power path is the inverter instead of the main. Figure 4 Double Conversion On-Line UPS STATIC BYPASS RECTIFIER In the Double Conversion On-Line design, failure of the input does not cause activation of the transfer switch, because the input is charging the backup battery source which provides power to the output inverter. Therefore, during an input power failure, on-line operation results in no transfer time. Both the battery charger and the inverter convert the entire load power flow in this design, resulting in reduced efficiency with its associated increased heat generation. This UPS provides nearly ideal electrical output performance. But the constant wear on the power components reduces reliability over other designs and the energy consumed by the electrical power inefficiency is a significant part of the life-cycle cost of the UPS. Also, the input power drawn by the large battery charger is often non-linear and can interfere with building power wiring or cause problems with standby generators. The Delta Conversion On-Line UPS This UPS design, illustrated in Figure 5, is a newer, 10 year old technology introduced to eliminate the drawbacks of the Double Conversion On-Line design and is available in sizes ranging from 5kVA to 1.6MW. Similar to the Double Conversion On-Line design, the Delta Conversion On-Line UPS always has the inverter supplying the load voltage. However, the additional Delta Converter also contributes power to the inverter output. Under conditions of failure or disturbances, this design exhibits behavior identical to the Double Conversion On-Line. 6

Figure 5 Delta Conversion On-Line UPS STATIC BYPASS DELTA TRANSFORMER DELTA CONVERTER MAIN A simple way to understand the energy efficiency of the delta conversion topology is to consider the energy required to deliver a package from the 4th floor to the 5th floor of a building as shown in Figure 6. Delta Conversion technology saves energy by carrying the package only the difference (delta) between the starting and ending points. The Double Conversion On-Line UPS converts the power to the battery and back again whereas the Delta Converter moves components of the power from input to the output. Figure 6 Analogy of Double Conversion vs. Delta Conversion 4th Floor DOUBLE CONVERSION X 5th Floor 4th Floor DELTA CONVERSION X 5th Floor In the Delta Conversion On-Line design, the Delta Converter acts with dual purposes. The first is to control the input power characteristics. This active front end draws power in a sinusoidal manner, minimizing harmonics reflected onto the utility. This ensures optimal utility and generator system compatibility, reducing heating and system wear in the power distribution system. The second function of the Delta Converter is to control input current in order to regulate charging of the battery system. 7

The Delta Conversion On-Line UPS provides the same output characteristics as the Double Conversion On- Line design. However, the input characteristics are often different. Delta conversion on-line designs provide dynamically-controlled, power factor corrected input, without the inefficient use of filter banks associated with traditional solutions. The most important benefit is a significant reduction in energy losses. The input power control also makes the UPS compatible with all generator sets and reduces the need for wiring and generator oversizing. Delta Conversion On-Line technology is the only core UPS technology today protected by patents and is therefore not likely to be available from a broad range of UPS suppliers. During steady state conditions the Delta Converter allows the UPS to deliver power to the load with much greater efficiency than the Double Conversion design. Summary of UPS types The following table shows some of the characteristics of the various UPS types. Some attributes of a UPS, like efficiency, are dictated by the choice of UPS type. Since implementation and manufactured quality more strongly impact characteristics such as reliability, these factors must be evaluated in addition to these design attributes. Practical Power Range (kva) Voltage Conditioning Cost per VA Efficiency Inverter always operating Standby 0-0.5 Low Low Very High No Line Interactive 0.5-5 Design Dependent Medium Very High Design Dependent Standby Ferro 3-15 High High Low - Medium No Double Conversion On-Line Delta Conversion On-Line 5-5000 High Medium Low - Medium Yes 5-5000 High Medium High Yes Use of UPS types in the industry The current UPS industry product offering has evolved over time to include many of these designs. The different UPS types have attributes that make them more or less suitable for different applications and the APC product line reflects this diversity as shown in the table below: 8

Standby Line Interactive Commercial Products Benefits Limitations APC s Findings APC Back-UPS Tripp-Lite Internet Office APC Smart-UPS Powerware 5125 Standby Ferro BEST Ferrups Double Conversion On-Line Delta Conversion On-Line APC Symmetra Powerware 9170 APC Silcon Low cost, high efficiency, compact High reliability, High efficiency, Good voltage conditioning Excellent voltage Conditioning, High reliability Excellent voltage conditioning, ease of paralleling Excellent voltage conditioning, High efficiency Uses battery during brownouts, Impractical over 2kVA Impractical over 5kVA Low efficiency, unstable in combination with some loads and generators Low efficiency, Expensive under 5kVA Impractical under 5kVA Best value for personal workstations Most popular UPS type in existence due to high reliability, ideal for rack or distributed servers and/or harsh power environments Limited application because low efficiency and instability issues are a problem, and N+1 On-Line design offers even better reliability Well suited for N+1 designs High efficiency reduces the substantial life-cycle cost of energy in large installations Conclusions Various UPS types are appropriate for different uses, and no single UPS type is ideal for all applications. The intent of this paper is to contrast the advantages and disadvantages of the various UPS topologies on the market today. Significant differences in UPS designs offer theoretical and practical advantages for different purposes. Nevertheless, the basic quality of design implementation and manufactured quality are often dominant in determining the ultimate performance achieved in the customer application. About the Author: Neil Rasmussen is a founder and the Chief Technical Officer of American Power Conversion. At APC, Neil directs the world s largest R&D budget devoted to Power, Cooling, and Rack infrastructure for critical networks, with principal product development centers in Massachusetts, Missouri, Denmark, Rhode Island, Taiwan, and Ireland. Neil is currently leading the effort at APC to develop modular scalable data center solutions. Prior to founding APC in 1981, Neil received his Bachelors and Masters degrees from MIT in electrical engineering where he did his thesis on the analysis of a 200MW power supply for a Tokamak Fusion reactor. From 1979 to 1981 he worked at MIT Lincoln Laboratories on flywheel energy storage systems and solar electric power systems. 9