INSTALLATION GUIDE FOR AO19 LOW ENERGY AUTOMATIC DOOR OPERATOR CONTROL MODULE B1000S SUPER SWING. User Manual. Date: July 3, 2008

Similar documents
Inductive Proximity Sensors

Solid State Timers Type F

INSTALLATION/PROGRAMMING INSTRUCTIONS E4KP ENTRYCHECK

OPERATING PRINCIPLES FOR PHOTOELECTRIC SENSORS

User Manual. ATX12V / EPS12V Power Supply TG-I460R (460W+460W) TG-I550R (550W+550W) Switching Power Supply User Manual

Digital Keypad Use s Manual

Impulse G+/VG+ Series 3, 24 VDC Interface Card Terminal Designations

Analog Control Wiring & Adjustment Manual for Gyro Tech Swing Door Operators

GENERATOR START CONTROL MODULE - MINI (2 Wire to 3 Wire)

Specifications for EM VDC 4 In/4 Out and EM VDC 4 In/4 Relay Out

Technical data. General specifications. Indicators/operating means. 30 Hz Multiplex operation 30 Hz / n, n = number of sensors, n 5

Advantium 2 Plus Alarm

*.ppt 11/2/ :48 PM 1

How To Control A Car Alarm On A Car With A Remote Control System

INSTRUCTION MANUAL for UNIBLITZ MODEL DM412 SHUTTER DRIVE MODULE

Sierra Dual 24 Volt Brushless DC Motor Controller Product Specification

Inductive Sensors Single or Dual Loop Detectors Type LD with teach-in

NC-12 Modbus Application

Manual for Fire Suppression & Methane Detection System

NST CDR REV_A

IO-RM3 3-Stage Relay Module

WD-AMX Water Detection Controllers

PHASED OUT. Digital dimmable ballasts for fluorescent lamps EXCEL one4all series. PCA TCL EXCEL one4all, W Compact and T5c fluorescent lamps

Programmable Room Thermostat 7 Day (5-2 Day) Models: / Power Supply: Battery / Mains

Datasheet of the Easy Servo Drive ES-D VDC, 8.2A Peak, Close-loop, No Tuning. Version

INSTALLATION & SERVICE MANUAL. Display Panel

DMX512 Switch (stand alone mode) DALI Touch Dimmer Switch

SECTION DETECTION AND ALARM

Model 5511 Filler Controller User s Manual Version 1.1 October 2011

FL ballasts Electronic dimming. PCA T5 BASIC lp Y II, W BASIC T5

AC-115 Compact Networked Single Door Controller. Installation and User Manual

APPENDIX A PIN-OUT OF RJ12 / RJ45 CONNECTORS. RJ12 connectors

Technical data. General specifications. Indicators/operating means. Electrical specifications Operating voltage U B Power consumption P 0 Interface

ZMR 80 STEREO MODULAR ZONER USERS MANUAL

Global Motion Technology Inc Web THCSA200. Capacitive sensor plasma & Oxy-fuel Torch Height Control

F(t) Forssell Technologies Inc


DORMA MODEL PS-406BB POWER SUPPLY INSTALLATION INSTRUCTIONS

LGAC-KNX PROGRAMMING MANUAL. Integrations V1.0 TECHNICAL SUPPORT. Tel (+34)

mecotron Safety relay ESTOP-2 For emergency stop monitoring

Brushless DC Motor Controller Product Specification Assembly 025F0129

Digital Expansion Modules Specifications

3FBD DC Motor Drive User Manual

Duct Humidity Transmitter

MDC Series

GSM AD05 Slave GSM Auto Dialer- Instruction Manual

How to read this guide

Self Monitoring Power Supply (BPSM)

Technote. Frese OPTIMA Compact actuators DN10-DN32. Application. Features thermic actuators. Features motoric actuators. Approval.

USER MANUAL MODEL

System components portfolio overview. Power supplies, electromagnetic locks, electric strikes and system accessories


M68EVB908QL4 Development Board for Motorola MC68HC908QL4

LIFESTYLE SYSTEM CABLES

[F/T] [5] [KHz] [AMP] [3] [V] 4 ) To set DC offset to -2.5V press the following keys [OFS] [+/-] [2] [.] [5] [V]

Fiber Optic Selector Guide for Analog & Digital Data Links, Contact Closures & Multiplexers

DOEPFER MIDI TO SYNC INTERFACE MSY2. User's Guide (English)

500r+ Installation and User Guide

Magnum IV Control Wiring & Adjustment Manual for Gyro Tech Swing Door Operators

User manual Rev. 1.2 (17/04/2015)

How To Control A Power Supply With A Mini Transmitter And Switch (Power Supply)

KCIEN KCIENSBP. Heavy Duty Stainless Steel Illuminated Keypads INSTALLATION MANUAL. Range: DIGICODE (Stand-Alone Keypad)

SMPTE Time Code Generator/Reader

MODEL DK-26 DIGITAL KEYPAD SYSTEM INSTALLATION AND OPERATING INSTRUCTIONS

HAM841K ALARM CONTROL PANEL FOR COMMERCIAL AND RESIDENTIAL SECURITY SYSTEMS

Unattended Answering Device Instruction Manual

HERZ-Thermal Actuators

How To Program An Autodialer

ELITE-L Series. ELITE - Low Voltage / Dry contact Remote Control System

AUTOMATIC TRANSFER SWITCH. Changeover Type from 250A to 2500A

Eaton s E-Series protective relay family

CM705B - Universal Expander Module CM707B - Plug On Zone Expander Security Systems

Shutter Actuator Standard, 4-fold, 230 VAC, MDRC RA/S , GH Q R0111. ABB i-bus EIB

HCS-3300/3302/3304 USB Remote Programmable Laboratory Grade Switching Mode Power Supply

USER GUIDE. Studio Hotline Multi-line System Phone Flasher and Door/Alert Indicator Input Module and Indicator. DM Engineering. Version 1.

2.0 Installation 1. Remove the cover using a small flat blade screwdriver. Figure 2: Cover Removal

Software Manual RS232 Laser Merge Module. Document # SU Rev A

AUTOMATIC TRANSFER SWITCH CONTROL UNIT OPERATOR S MANUAL

TG24 / 48 LIGHTING CONTROLLER

RS - SPM. Serial parallel translator module

Operating instructions IV / 2007

UltraCade Multi-Game System Frequently Asked Questions

Technical Specifications: The specifications represent a particular hardware platform. Application-specific software is provided.

ViZion Installation Guide

Positive-guided relay outputs: 3 safety contacts (N/O), instantaneous. 1 auxiliary contact (N/C), instantaneous

INSTALLATION MANUAL VEHICLE SECURITY SYSTEM CE-SS200

F2400 FOM II Series Fiber Optic Modem Technical Manual

Centro-Matic Automatic Lubrication Systems System Controls

LG Air Conditioning Multi F(DX) Fault Codes Sheet. Multi Split Units

PCAN-B10011S Bus Converter High-speed CAN to Truck Trailer CAN. User Manual. Document version ( )

DRTS 33. The new generation of advanced test equipments for Relays, Energy meters, Transducers and Power quality meters

THE INPUT/OUTPUT SYSTEM. Key Points

EMF/EMR. Holder/Release Devices with Integral Door Closers

In regard to calculating system power requirements, refer to DBK Basics located near the front of this manual.

OEM Manual MODEL 2350 ELECTRONIC DUAL CYLINDER SCALE

PCS0100en Persy Control Services B.V. Netherlands

Contractors Guide Central Inverter System Installation

Electrical data Nominal voltage AC/DC 24 V Nominal voltage frequency

TSC 800 TRANSFER SWITCH CONTROLLER INSTALLATION, OPERATING & SERVICE MANUAL

PRODUCTIVITY THROUGH INNOVATION 600 CONTROL DIRECT DRIVE TECHNICAL/OPERATION MANUAL

Transcription:

INSTALLATION GUIDE FOR AO19 LOW ENERGY AUTOMATIC DOOR OPERATOR CONTROL MODULE B1000S SUPER SWING User Manual Date: July 3, 2008 Note: This product is a low energy automatic door operator and must be installed / serviced by a qualified person. The service technician must be familiar with the latest ANSI /BHMA A156.10/19 standards. NEVER sacrifice the safe operation of the automatic door for an incomplete solution. Call the factory for technical support. P/N 103188 1

AO19 Low Energy Automatic Door Operator Module Description / Connector Pinouts ISP / Synchronization Connector J 1 ISP (In System Programmer ) FACTORY USE ONLY Synchronization This connector is used to synchronize two modules together (For Dual door operator ). Synchronization cable, part number 104785. When the synchronization cable is used, the activation switch (es) can be wired to only one module. All signals, except for the Delayed Activation, are shared between the two modules via the synchronization cable. When the Delayed Activation Timer expires, an activation signal is sent to mate control. Note: Using the synchronization cable will not synchronize the door speeds are kept separately.. The speeds 2

Signal and Sensor Power Connector P2 High - Low Pin Signal Definition Low Energy High Energy use and must conform to ANSI/BHMA A156.10 J2.1 Logic ground J2.2 Activation 1 J2.3 Activation 2 J2.4 Safety A J2.5 Safety B J2.6 Delayed Activation J2.7 Hold Open J2.8 Low Voltage ON/OFF J2.9 Data + J2.10 Logic ground/data - J2.11 (+24VDC) Ground reference for signals and power. This signal to ground will activate the operator. If the module is in the ON mode (Low voltage ON/OFF must be to ground) and no current fault is present. Note: Manual use of the door will not enable this input. This signal is active when the door is in motion. IF the module is in the ON mode (Low voltage ON/OFF must be to ground) and no current fault is present. Note: Manual use of the door will not enable this mode. When the door is fully closed, this signal to ground will prevent an activation. During the opening cycle (with lockout option to OFF), the door will go to safety speed when this signal is to ground. During the closing cycle (with lockout position to OFF), the door will go to a very slow speed when this signal is to ground. When the door is fully opened, this signal to ground will prevent the door from entering the closing cycle. When the door is fully closed, this signal to ground will prevent an activation. During the opening cycle, the door will go to safety speed when this signal is to ground. When the door is fully opened, this signal to ground will prevent the door from entering the closing cycle. This signal to ground will start the delayed activation timer. When the timer expires, an activation is generated. This signal is used to do door sequencing. This signal to ground will hold the door opened. If the module is in the ON mode, (Low voltage ON/OFF must be to ground) and no current fault is present. This signal to ground enables the module. This module is disabled if this signal is not to ground. This is a signal output for sensor which requires door status information. When door is closed, Data output is 0V When door is in the opening cycle, Data output is 12V When door is closing (in motion), Data output is 8V Ground reference for signals and power DC power to sensors (300mA max.) Low Energy ANSI/ BHMA A156.19 J2.12 (24VAC) J2.13 (24VAC) J2.14 Electric lock switch (Common) J2.15 Electric lock switch (normally open) J2.16 Electric lock switch (normally close) AC power for sensor This connection is the common to drive an electric lock. (Active when electric lock option is set to ON) This connection is the normally open (NO) to drive an electric lock (Active when electric lock option is set to ON ) This connection is the normally closed (NC) to drive an electric lock (Active when electric lock option is set to ON ) Power Source (120VAC input connector ) J3 Pin Signal Definition J3.1 AC Line - BLK J3.2 AC Neutral - WHT J3.3 AC Ground - GRN Power required is 120 VAC 50/60 Hz (Maximum current is 3Amperes 3

Refer to ANSI/BHMA A156.10 / 19 4

5

Refer to ANSI /BHMA A156.10 / 19 for more information 6

Refer to ANSI /BHMA A156.10 / 19 for more information 7

Point to Point Dwg for AO19 Low Energy Automatic Door Operator Refer to ANSI/BHMA A156.10 / 19 for more information, or Call factory at 1-800-729-3839 24VAC Strike (if used) 8

Dual Door Operator Sync Cable P /N 104785 For dual door operator, plug Sync Cable P/N 104785 as shown below. When using the Sync cable, only one control maybe wired to the switches. All signals are shared between the two controls using the sync cable, except for the Delayed Activation input. When the Delayed Activation Timer expires, an activation signal is sent to the mate control Sensor power can be supplied by both controls for a total of 600mA. Master Controller In dual/twin mode, set the Activation timer and Push & Go timer trimmers to the value needed. Note: The Sync cable, P/N 104785, has two wires switched at one end of the cable. Slave Controller Important : In dual/twin mode, set the Activation timer and Push & Go timer trimmers to the maximum value (Fully clockwise) for the slave controller. Electric lock for twin doors For one controller to control the electric lock (s), wire the electric lock(s) to one controller. Set the option #3 to ON for that controller only. Wire the activation signal(s) to the controller that is wired to the electric lock. For two controllers to control the electric locks (to keep the electric locks independent), wire the first lock to the first controller, the second electric lock to the second controller. Set the option # 3 to ON on both controllers. Wire J2 pin 2 (Activation 1) of the first controller to J 2 pin 2 (Activation 1) of the second controller. 9