COMMERCIAL BUILDING TELECOMMUNICATIONS STANDARD

Similar documents
The Evolution of Copper Cabling Systems from Cat5 to Cat5e to Cat6 Copper Cabling Standards and Technical Aspects

ANSI/TIA/EIA A, Commercial Building Telecommunications Cabling Standard.

ANSI/TIA/EIA A A Revisited. Residential Telecommunications Cabling Standard (Draft 6/22/99) Larry L. Hamlin, RCDD

Network Design. Yiannos Mylonas

Disclaimer This information is collected and composed by QUANG DUNG TECHNOLOGY from Cablingdb.com. All information is copyrighted by Cablingdb.com.

Evolution of Cabling Standards TIA/EIA ISO/IEC CENELEC. by Paul Kish NORDX/CDT Chair TIA TR 41.8

Part 1: General Requirements TELECOMMUNICATIONS INDUSTRY ASSOCIATION

DIVISION 27 COMMUNICATIONS. A. System design shall be completed by a Registered Communications Distribution Designer (RCDD).

HIGH SPEED COMMUNICATIONS PLENUM CABLE CATEGORY 5e CMP FEP JACKETED, PVC-FREE UNSHIELDED TWISTED PAIR (UTP)

Running 1000BASE-T Gigabit Ethernet over Copper Cabling 30 March 1999 Colin Mick/The Mick Group with Bruce Tolley/3Com and Willem Wery/Intel

Mixed High-Speed Ethernet Operations over Different Categories of Bundled UTP Cable

Structured and Point to Point Network Cabling for Industrial Automation

Planning for 10Gbps Ethernet over UTP Questions to Ask When Planning the Cabling Plant WHITE PAPER

European Normative EN system

Testing 10 Gb/s Performance of Category 6 and 6A Structured Copper Cabling Systems within the Unified Physical Infrastructure SM (UPI)

Installation Effects Upon Alien Crosstalk and Equal Level Far End Crosstalk

DIVISION 26 - ELECTRICAL SECTION CABLES FOR INSTRUMENTATION

Ethernet Patch Cord Wiring

Presenters Brett Weiss, Gabe Martinez, Brian Kroeger.

The Permanent Link in Field Certification Reasons, Advantages, Testing Challenges

SYSTIMAX Copper Solutions Designed for the Digital Generation

Implementing Fast Ethernet

Category-6 / Class-E Cabling

NORTH ORANGE COUNTY COMMUNITY COLLEGE DISTRICT SECTION STRUCTURE CABLING TESTING

Networking 101 (Networking Basics) Presentation to UCHUG - 1/03/07 G. Skalka

Gigabit Ethernet on Copper Cabling Infrastructures

How to Choose the Right Cable Category

HIGHSPEED ETHERNET THE NEED FOR SPEED. Jim Duran, Product Manager - Americas WHITE PAPER. Molex Premise Networks

An Engineer s Guide to Full Compliance for CAT 6A Connecting Hardware

Abstract: This document examines the alien NEXT performance of various bundled cables and measures the impact upon various networks performance.

White Paper: 10 Gigabit Ethernet over Twisted Pair Copper Systems

1.1 SYSTEM DESCRIPTION.1 Data system includes data outlets and wiring for office and school applications.

ATT-TP Ethernet Copper Cable & Ethernet Copper Assembly Specification

Performance Verification of GigaSPEED X10D Installations with Fluke Networks DTX 1800 CableAnalyzer

Nathan Dayton ADNET. ADNET SYSTEMS, Inc. Slide Number 1

Standards Affecting a Premise T-1 Installation

AMP NETCONNECT Data Center Cabling Solutions

INTERNATIONAL STANDARD

IT Cabling Solutions

Chapter 4 Connecting to the Internet through an ISP

Requirements for Modular Patch Cords (e.g. RJ45 patch cords for Cat5 and Cat6 cabling systems)

Cable Sharing in Commercial Building Environments

Enhanced Category 5 Cabling System Engineering for Performance

with Component Rating A Simple Perspective

Innovation. Volition Network Solutions. Leading the way in Network Migration through Innovative Connectivity Solutions. 3M Telecommunications

New Technology Developments and How They Impact Your Structured Wiring Choices

Giganet Copper Cabling Training

Transmission of High-Speed Serial Signals Over Common Cable Media

Network Topologies and Distances

WHITE PAPER December, 2001

SMARTen 24 STP Patch Panels

Security & Surveillance Cabling Systems

Specification SFTP CAT6 Network Cable 23AWG CU

Data Center. Pre-terminated. Patch Panel System. Cabling Systems Simplified. Patch Panels. 10G + Gigabit. Patch Cords. Plug & Play Installation

The High Cost of a Low-Cost Cable Certification Tester

B. Cross-Connect: A facility enabling the termination of cable elements and their interconnection or cross-connection.

Terminating 25-Pair Cable and 4-Pair Cross Connects

Cabling and Building Infrastructure for Technology

Total Solutions Verification

Telecommunications Infrastructure Standard for Data Centers Tutorial

Specifying an IT Cabling System

Category 6 UTP - Cabling System

SUBJECT: CENELEC VOTE FINAL DRAFT PR EN INFORMATION TECHNOLOGY -GENERIC CABLING SYSTEMS PART 1:GENERAL REQUIREMENTS AND OFFICE AREAS

Nexus Technology Review -- Exhibit A

Category 6 Solutions. 4. Category 6 Solutions. 09/ IN TrueNet Structured Cabling. Introduction Cable Patch Panels... 4.

1st Edition Ethernet/Data Connectivity

White Paper: 10GbE Fiber A Practical Understanding and Functional Approach

Physical Infrastructure trends and certification requirements for Datacenters. Psiber s Global Village

The Next Generation of Cable Technology. A technology primer from NORDX/CDT By, Eric d Allmen

VIDEO SURVEILLANCE OVER UTP WHITE PAPER INTRODUCING VIPER VIDEO SURVEILLANCE

Module 5. Broadcast Communication Networks. Version 2 CSE IIT, Kharagpur

SMARTen 24 UTP Patch Panels

PANDUIT TX6 10GIG SHIELDED COPPER CABLING SYSTEM. Innovative Connectivity Solution for Maximum Performance and Security

Data Center Design for 40/100G

SECTION VOICE AND DATA COMMUNICATION CABLING

Technical Information and System Application Guide

BIX Cross-Connect System Distribution Connectors, Multiplying Connectors and Modular Jack Connectors

Migration Strategy for 40G and 100G Ethernet over Multimode Fiber

KVM - DVI, USB 2.0, Cat 5 Extender

blackbox.com

R&Mfreenet Advanced Cat 6 A Unshielded Connection Module

SECTION TELECOMMUNICATIONS ACCEPTANCE TESTING

Future Stars. Grade X Manual Chapter 1 Networking and Telecommunication. telecommunication. Telephones, telegrams, radios and televisions help

Gigabit Ethernet over fiber optic cable.

Data Communications Competence Center

Standards. 5 ANSI/TIA/EIA-569-A (CSA T530)

The effect of temperature on the bandwidth of telecommunications cabling in commercial buildings. Focus on the IBDN System 4800LX from NORDX/CDT

Data Center Fiber Cabling Topologies and Lengths. Paul Kolesar IEEE HSSG, September 2006

Innovative Connectivity Solution for Maximum Performance and Security

CCNA Discovery Chapter Four

Copper Patch Cords. Impact On Network Performance and Reliability

ANSI/TIA-942 Telecommunications Infrastructure Standard for Data Centers

1. Furnish and install faceplate and modular jacks at each single gang outlet as described below:

Resolution of comments 242 and 267 on Insertion loss measurements of installed fiber cables. Steve Swanson May 5, 2009

10 Gigabit Ethernet over copper: Unshielded, unprotected?

This paper will explain some of the more important factors on how UTP wires work; specifically it will cover the following:

White Paper. Cat. 6A vs. Cat. 6 A. What s the Difference and Why Should I Care?

CATEGORY 8: UNDERSTANDING THE NEW CATEGORY OF PERFORMANCE FOR BALANCED TWISTED PAIR CABLE

Session 2; Cabling Technology in the Data Centre Media Choices; Copper Twisted Pair

Transcription:

1 ANSI/TIA/EIA-568-A (CSA T529-95) The purpose of this standard is to provide the minimum requirements for telecommunications cabling within a commercial building or campus environment. The standard addresses the six major components of a structured wiring system: Entrance facility Main/Interconnect cross-connect Backbone distribution Horizontal cross-connect Horizontal distribution Work area. Backbone cables Intermediate and main cross-connects Mechanical terminations Patch cords or jumpers for backbone-to-backbone connections. Backbone Distribution GENERAL DESIGN GUIDELINES The useful life of backbone cable is at least ten years. Planning should consider the maximum amount of backbone cable, media additions (optical fiber) and number of connections required during this period. Scope of ANSI/TIA/EIA-568-A (CSA T529-95) ENTRANCE FACILITY The entrance facility contains the cables, connecting hardware, protection devices and other equipment required to connect outside plant facilities to premise cabling. The components within this room may be used for public or private network connections. The demarcation point between service providers and the customer owned premises cabling is typically located in this room. MAIN/INTERMEDIATE CROSS-CONNECT The telecommunications equipment room could be the same location as the main/intermediate cross-connect. Cabling practices that apply to telecommunications rooms (TR) apply to equipment rooms. BACKBONE DISTRIBUTION Backbone cable provides the interconnection between TRs, equipment rooms and entrance facilities. The components involved in backbone distribution include: Consider the proximity of metallic cables to possible sources of electromagnetic interference. TOPOLOGY The backbone distribution system is to follow a hierarchical star topology. Each horizontal cross-connect in a TR is cabled to a main crossconnect or an intermediate cross-connect and then a main cross-connect There cannot be more than two hierarchical levels of cross-connect. At most, one cross-connect can be passed through to go from the horizontal cross-connect to the main cross-connect Three or fewer cross-connects can be passed through to go from one horizontal cross-connect to a second horizontal crossconnect. Systems designed for non-star configurations (ring, bus or tree) can usually be accommodate by the hierarchical star topology. If special requirements for bus or ring configurations are expected, it is allowable to cable directly between telecommunications rooms. This cabling is in addition to the basic star topology. 1 10

ANSI/TIA/EIA-568-A (CSA T529-95) 1 RECOGNIZED BACKBONE DISTRIBUTION MEDIA Recognized media may be used individually or in combination. These media are: 100 UTP cable 50/125 µm optical fiber cable proposed additions/deleting in TIA568-B/standard (under development) 62.5/125 µm optical fiber cable single-mode optical fiber cable 50 coaxial or 150 STP-A cable proposed additions/deleting in TIA568-B/standard (under development). Cables are still a recognized media but are not recommended for new installations. HORIZONTAL CROSS-CONNECT The termination of horizontal cable is the primary function of the horizontal cross-connect that is housed in a telecommunications room. Cable of all media types are terminated on compatible connecting hardware. Backbone cable is also terminated on compatible hardware. Connecting hardware, jumper wire and patch cords are collectively referred to as the horizontal cross-connect. TELECOMMUNICATIONS ROOM FUNCTIONS The primary function is to contain horizontal cable terminations of all recognized types. MEDIA SELECTION CRITERIA The choice of backbone distribution media will depend on the characteristics of specific applications. Factors to consider in making a selection include: flexibility with respect to supported services required useful life of backbone cable site size and user population. IN-BUILDING AND INTER-BUILDING BACKBONE CABLING DISTANCES Recommended maximum distances are application dependent. It is not assured that all applications will function properly over the specified distances. Maximum backbone distribution distances Horizontal Horizontal Main cross- cross- crossconnect connect connect to to to Main Intermediate Intermediate Media type cross- cross- crossconnect connect connect UTP 800 m 500 m 300 m (2 624 ft) (1640 ft) (984 ft) 62.5/125 µm 2 000 m 300 m 1 700 m optical fiber (6 560 ft) (984 ft) (5 576 ft) Single-mode 3 000 m 300 m 2 700 m optical fiber (9 840 ft) (984 ft) (8 856 ft) Recognized types of backbone cable are also terminated here. Cross-connections of horizontal and backbone terminations using jumper wire or patch cords allow for flexibility to extend services to telecommunications outlet/connectors. The intermediate or main cross-connect for portions of the backbone cabling system may also be found in the telecommunications room separate from the horizontal cross-connect. CROSS-CONNECTIONS AND INTERCONNECTIONS Moves, add-ons or changes are to completed by performing crossconnects or interconnects. Cross-connects are connections between horizontal cabling and backbone or equipment connecting hardware (i.e,. patch panels). Connections made directly between equipment and horizontal cabling are called interconnects. Cross-Connection Inter-Connection For high-speed data applications the use of category 3, 4 or 5 100 UTP backbone cable shall be limited to a total distance of 90 m (295 ft); this assumes 5 m (16 ft) at each end for connection to equipment. The capability of single-mode optical may allow for distance up to 60 km (37 miles). However, this is outside the scope of the standard. 1 11

1 ANSI/TIA/EIA-568-A (CSA T529-95) HORIZONTAL DISTRIBUTION Horizontal distribution is the part of the telecommunications cabling system running from the work area to the horizontal cross-connect in the TR. Horizontal cabling includes: Horizontal distribution cables Telecommunications outlet/connector in the work area Mechanical termination of the cable media Patch cords/jumpers in the TR. GENERAL DESIGN GUIDELINES The horizontal distribution system must satisfy current requirements and should facilitate ongoing maintenance and relocation. Also consider future equipment and service changes. After installation, horizontal cabling is usually less accessible than other cabling Horizontal cabling is subject to the greatest amount of activity in the building (approx. 90%) Consider the diversity of possible services/applications to be used. Consider the proximity of cables to possible sources of electromagnetic interference. TOPOLOGY The horizontal distribution system must follow a star topology. The telecommunications outlet/connector in the work area is to be directly connected to a horizontal cross-connect in a telecommunications room located on the same floor as the work area Bridged taps and splices are not permitted. At the horizontal cross-connect the maximum length of patch cords/jumpers used to connect horizontal cable to equipment or backbone cable is not to exceed 6 m (20 ft) It is recommended the maximum length of cord used in the work area should not exceed 3 m (10 ft). RECOGNIZED HORIZONTAL DISTRIBUTION MEDIA Three types of media are recommended for use: Four-pair 100 unshielded twisted-pair (UTP cable Two-pair 150 shielded twisted-pair (STP-A) cable Two-fiber, 62.5/125 mm optical fiber cable 50 co-axial cable is still a recognized media but is not recommended for new installations. Hybrid cables (multiple types of media under a single sheath) may be used in the horizontal distribution system if each recognized cable type meets the transmission requirements and color-code specifications for that cable type. 100 UTP cables of mixed categories are not recommended under the same sheath Cross-talk specifications between cables of a hybrid cable should be met It must be possible to distinguish hybrid UTP cables from multipair UTP backbone cable Hybrid cable made up of optical fiber and copper conductors may be referred to as composite cable. MEDIA SELECTION CRITERIA Each work area must be equipped with at least two telecommunications outlets/connectors. One outlet may be associated with voice and the other with data. DISTANCES Regardless of the media type used for horizontal distribution, the maximum distance is 90 m (295 ft). This maximum distance is for the amount of cable required to get from the work area outlet to the horizontal cross-connect in the TR For each horizontal channel a maximum of 10 m (33 ft) is permitted for work area cords, patch cords, jumper wires and equipment cords (inclusive) The first outlet shall be a 4-pair 100 UTP cable, Category 3 or higher. The second outlet may be supported by one of the following media: Four-pair 100 UTP cable, Category 5 recommended Two-fiber 50/125 µm optical fiber cable Two-fiber, 62.5/125 µm optical fiber cable. 1 12

ANSI/TIA/EIA-568-A (CSA T529-95) 1 WORK AREA Work area components are from the outlet to the work area equipment. It is assumed a maximum of 3 m (10 ft) is used for the modular cord at the work area. Four-pair UTP cables are terminated in 8-position modular jacks at the work area. The recommended pin/pair assignment is referred to as T568A-ISDN. However, if required, T568B-ALT can also be used. WORK AREA COMPONENTS Work area components fall outside the scope of the standard. Work area equipment includes a large variety of equipment. Included are telephones, fax machines, data terminals and computers. Work areas are generally considered to be non-permanent, and are expected to change. Therefore, work areas should be designed to be relatively easy to change. TELECOMMUNICATIONS OUTLET/CONNECTOR Pin/pair assignment for 100 UTP cable is recommended to follow the T568A configuration. To accommodate certain cabling systems, the T568B configuration is accepted. SPECIAL ADAPTATIONS If application specific adaptations such as impedance matching devices are required, they must be external to the telecommunications outlet/connector. Some commonly used adapters include the following: A special cable or adapter when the equipment connector is different from the outlet/connector Y adapters to permit two services to run on a single cable Passive adapters used when the horizontal cable type is different from that required by the equipment Active adapters when connecting devices using different signaling schemes Adapters allowing pair transposition for compatibility purposes Termination resistors. Consider adapter compatibility with premises cabling and equipment. Adapters may have detrimental effects on the transmission performance of the telecommunications cabling system. U.S. Federal Government publication FIPS PUB 174 recognizes designation T568A only. Front view of telecommunications outlet WORK AREA CORDS The horizontal distribution system assumes a maximum cord length of 3 m (10 ft). Cables and connectors should meet or exceed patch cord recommended requirements. 1 13

1 ANSI/TIA/EIA-568-A (CSA T529-95) ADDENDUM 1: PROPAGATION DELAY AND DELAY SKEW SPECIFICATIONS FOR 100 4-PAIR CABLE (SEPT. 97). The introduction of high-speed applications has created needs for additional transmission requirements such as propagation delay and delay skew for 100 4-pair cabling systems. The effects of these parameters are mostly found when applications require multiple pairs for parallel transmission. It is important to specify that although these are new specifications, most of the existing TIA/EIA-568-A compliant cable will likely meet these two additional parameters. This addendum was created to set a standard in the cables manufacturing business. It was developed to ensure that all recognized 4-pair cables manufactured to the TIA/EIA 568-A standard comply with known application requirements, such as 100BASE-T4. The new parameters are: Propagation Delay is the time needed for the transmission of a signal over a single pair of 100 4-pair cable. Delay Skew is the difference in the propagation delay between any two pairs within the same cable sheath. The worst case scenario for delay skew is obtained when the difference is calculated between the fastest and the slowest pair in the cable. ADDENDUM 2: CORRECTIONS AND ADDITIONS TO TIA/EIA-568-A (AUGUST 98). This addendum was created to modify certain requirements in the existing TIA/EIA-568-A and provide additional requirements, for items effected by the fast growth of technology. Some changes include additional references to the documents TSB 72: Centralized Optical Fiber Cabling Guidelines and TSB 67: Transmission Performance Testing Specifications for Field Testing of UTP Cabling Systems. Also this addendum provides additional details on Resistance Measurement, common mode termination for cabling components and the required test set-up configuration for those components. It will complete the information found in the standard TIA/EIA-568-A. ADDENDUM 3: HYBRID AND BUNDLED CABLES (DEC. 98). The purpose of this one page addendum is to add a new definition for bundled cable and additional requirements. A Bundled Cable is a cable assembly containing two or more recognized cables continuously bound together to form a single cable entity. A Hybrid Cable is a cable assembly containing two or more recognized cables of the same type or different types of conductors covered by a single sheath. Additional requirements are specified and can be applied to both Hybrid and Bundled cables. Bundled or Hybrid Cables may be use as horizontal cabling if each recognized cable type meets the transmission and colorcoded as specified by that type of cable. The PowerSum NEXT loss caused by all pairs external to the disturbed pair s jacket within the bundled or hybrid cable assembly shall be 3 db better than the specified pair-to-pair NEXT loss of that recognized type of cable at all of the specified frequencies. *Note: Hybrid cable consisting of optical fiber and copper conductors can also be referred to as composite cable. ADDENDUM 4: PRODUCTION MODULAR CORD NEXT LOSS TEST METHOD AND REQUIREMENTS FOR UTP CABLING (AUGUST 99). The objective of this addendum is to provide to the manufacturers of modular plug cord assemblies, a simple and effective method to ensure modular plug cords are compatible with the performance requirements given by ANSI/TIA/EIA-568-A. It provides a nondestructive methodology to test modular plug cords for the NEXT Loss parameter. The 8-pin modular plug cords are use in a channel configuration as an equipment cord, a patch cord or a work area cord. The test method used to measure the NEXT loss of an 8-pin modular plug is called de-embedded NEXT (DNEXT). This test method defines the construction of a reference jack that is measured for NEXT and the procedure for obtaining the NEXT loss (both magnitude and phase) of the reference jack at all specified frequencies. This reference jack is then used as a test head for testing plugs or patch cords. The de-embedded NEXT of a test plug is obtained by subtracting the NEXT of the reference jack from the mated plug/reference jack measurement. The difference is called the DNEXT of the plug. Plugs with different DNEXT values are used to test the mated NEXT of connecting hardware, which can be used to determine plug and mated plug/jack performance. This will determine backward compatibility and interoperability. 1 14

ANSI/TIA/EIA-568-A (CSA T529-95) 1 ADDENDUM 5: TRANSMISSION PERFORMANCE SPECIFICATIONS FOR 4-PAIR 100 CATEGORY 5e CABLING (JANUARY 2000). This document has been approved for publication by ANSI in January 2000 as ANSI/TIA/EIA 568-A-5. It covers the following topics: Definitions, test configurations and transmission requirements for Category 5e components Field test requirements and test procedures for Category 5e channels and basic links including power sum near-end crosstalk (PSNEXT), power sum equal level far-end crosstalk (PSELFEXT) and return loss Accuracy requirements for enhanced level II (Level II-E) testers New de-embedded test procedures and requirements for modular test plug qualification New test procedures and requirements for the return loss of Category 5e modular patch cords New channel model for the development of component return loss limits. The most noteworthy changes to the enhanced Category 5 cabling standard are summarized in Tables 1, 2 and 3 for channels, cables and connectors, respectively. WHAT IS THE SIGNIFICANCE OF THE ENHANCED CATEGORY 5 STANDARD? The new transmission parameters and requirements are a major improvement over Category 5. These performance improvements will enable Category 5e cabling to support gigabit applications such as 1000BASE-T for worst-case channel topologies that can include up to four connectors and 100 meters of cabling. The most demanding requirements are on cabling return loss performance. A higher return loss in db requires a more uniform cable impedance (more precise manufacturing process), better patch cords (stable impedance) and better impedance matching between components. This will translate into a cleaner signal and more reliable transmission performance (fewer data errors). TRANSMISSION REQUIREMENTS FOR A CATEGORY 5e CHANNEL CHANNEL (100 M) CATEGORY 5 TIA/EIA 568-A/TSB-67 CATEGORY 5e TIA/EIA 568-A-5 PSNEXT @ 100 MHz not specified 27.1 db PSELFEXT @ 100 MHz not specified 14.4 db Return Loss @ 20 MHz not specified 17 db Return Loss @ 100 MHz not specified 10 db TRANSMISSION REQUIREMENTS FOR CATEGORY 5e CABLES CABLE (100 M) CATEGORY 5 TIA/EIA 568-A/TSB-67 CATEGORY 5e TIA/EIA 568-A-5 PSNEXT @ 100 MHz not specified 32.3 db PSELFEXT @ 100 MHz not specified 20.8 db Return Loss @ 20 MHz not specified 25 db Return Loss @ 100 MHz not specified 20.1 db/19.0 db* *designates stranded cable TRANSMISSION REQUIREMENTS FOR CATEGORY 5e CONNECTORS CONNECTOR (100 M) Category 5 TIA/EIA 568-A/TSB-67 Category 5e TIA/EIA 568-A-5 NEXT @ 100 MHz 40 db 43 db FEXT @ 100 MHz not specified 35.1 db Return Loss @ 20 MHz 23 db 34 db Return Loss @ 100 MHz 14 db 20 db 1 15