Energy & Heat Transfer in Healthcare HVAC

Similar documents
UNIVERSITY OF MISSOURI Heating Ventilating and Air-Conditioning (HVAC) March

Fundamentals of HVAC Control Systems

Example Retrocommissioning Measure: Opening Throttled Discharge Valves

CHILLER PLANT CONTROL MULTIPLE CHILLER CONTROLS

REAL OPERATING COST SAVINGS FROM RETRO- COMMISSIONING OPPORTUNITIES FOR SAVINGS IN ACADEMIC MEDICAL CENTERS

Commissioning - Construction Documents (Page 1 of 6)


UNIFIED FACILITIES GUIDE SPECIFICATIONS

for Plans Examiners and Building Inspectors

Applying Pressure Independent Control Valves in H.V.A.C. Systems. A Presentation to: Orange Empire ASHRAE Santa Ana Nov. 17, 2009

KU DESIGN GUIDELINES APPENDIX XVI RECOMMENDED BAS I/O CONTROL POINTS BY EQUIPMENT / SYSTEM

Chilled Water System Commissioning: Variable Primary Flow. John D. Villani, P.E. Associate Grumman/Butkus Associates

Enclosed Football Stadium Design History and Lessons Learned

HVAC Systems: Overview

Presentation Outline. Common Terms / Concepts HVAC Building Blocks. Links. Plant Level Building Blocks. Air Distribution Building Blocks

ENHANCED LABORATORY HVAC SYSTEM

Rev. No. 0 January 5, 2009

HIGH PERFORMANCE CHILLED WATER SYSTEMS. EarthWise HVAC. EarthWise HVAC High Performance CHW Plants

Commissioning for Performance in Critical Healthcare Environments

NEBB STANDARDS SECTION-8 AIR SYSTEM TAB PROCEDURES

Central Plant Air Systems: Keeping the Heart and. Title Style. Better Buildings Summit May 2016

Dedicated Outdoor Air-Dual Wheel System Control Requirements

Advanced Energy Design Guide LEED Strategies for Schools. and High Performance Buildings

Building Performance With District Cooling

HVAC Simplified Approach Option

SPECIAL ISSUE: NATIONAL SCIENCE FOUNDATION WORKSHOP

Ener.co & Viridian Energy & Env. Using Data Loggers to Improve Chilled Water Plant Efficiency. Randy Mead, C.E.M, CMVP

Printing and Publishing Energy Savings Guide

Flexibility, Efficiency In San Antonio Arena

Data Centers WHAT S ONTHEHORIZON FOR NR HVAC IN TITLE ? SLIDE 1

CONTROL STRATEGIES FOR HVAC SYSTEMS

A. The Commissioning Authority (CxA) has been contracted or will be contracted directly with the Owner for this project.

3/29/2012 INTRODUCTION HVAC BASICS

Frequently Asked Questions

newsletter Let s take a high-level look at airside economizing: what it is, what it requires, and how it s done. How does economizer cooling work?

Variable Air Volume - VAV

Principals of Condensing Boiler System Design

Tips and Tricks for Estimating Energy Savings. Celeste Cizik, P.E. Project Manager E M C Engineers, Inc.

Dr. Michael K. West, PE 1 Dr. Richard S. Combes, PE 2 Advantek Consulting / Melbourne, Florida

Collaborative Laboratory Commissioning and Sustaining the Optimal Building. By E. Lon Brightbill, P.E Facility Dynamics

Optimization of Water - Cooled Chiller Cooling Tower Combinations

Seven Steps to Maximizing Central Plant Efficiency

OEH Energy Efficient HVAC for Business Training Course

85 F 80 F 50% 75 F 70 F 73.0/ F 10% Figure 1

newsletter engineers energy-saving strategies for Water-Source Heat Pump Systems volume 36 2 providing insights for today s hvac system designer

Digital Realty Data Center Solutions Digital Chicago Datacampus Franklin Park, Illinois Owner: Digital Realty Trust Engineer of Record: ESD Architect

HEATING AND COOLING GENERATION AND DISTRIBUTION SYSTEMS

HVAC Processes. Lecture 7

Scope of Work. See for resources available

Venice Library Humidity Study. for Williams Building Diagnostics, LLC th Street West Bradenton, FL Report April 13, 2015

CURBING THE COST OF DATA CENTER COOLING. Charles B. Kensky, PE, LEED AP BD+C, CEA Executive Vice President Bala Consulting Engineers

The main steam enters the building in the basement mechanical room; this is where the condensate line also leaves the building.

Preliminary Final Proposal

The Chilled Water and Hot Water Building Deferential Pressure Setpoint Calculation Chilled Water and Hot Water Pump Speed Control

Hospital Application Guide. Cost-effective climate control for hospitals

Bring the fresh in. Dedicated Outside Air Systems

ULTRA-EFFICIENT HVAC DESIGN AND CONTROL

Data Center Design Guide featuring Water-Side Economizer Solutions. with Dynamic Economizer Cooling

Impact of Control System Technologies on Industrial Energy Savings

Continuous Energy Management at UC San Diego. Anna Levitt, P.E. Assistant Energy Manager June 13, 2013

APPLICATION GUIDE. Moisture Management in Waterborne Climate Systems

Florida Power & Light Company. Business Heating Ventilation & Air Conditioning ( HVAC ) Program Standards. Effective: November 9, 2015

IDEA Presentation SMALL CAMPUS CHILLED WATER PLANT OPTIMIZATION.

The Data Center Dilemma - A Case Study

High Altitude HVAC. Silvertip Integrated Engineering Consultants

PHCC Educational Foundation Contractor Library Engineering Continuing Education

6 MECHANICAL HVAC SYSTEMS

Case Study: Innovative Energy Efficiency Approaches in NOAA s Environmental Security Computing Center in Fairmont, West Virginia

Federal Wage System Job Grading Standards for Air Conditioning Equipment Operating, Table of Contents

Active Chilled Beam System Design & Layout

SAM HOUSTON STATE UNIVERSITY

Outline. CC objectives Site and building description Typical data floor overview CC measures Results Lessons learned

How To Design A Building In New Delhi

ENERGY EFFICIENT HVAC DESIGN FOR WARM-HUMID CLIMATE CLIMATE

Modeling and Simulation of HVAC Faulty Operations and Performance Degradation due to Maintenance Issues

Defining Quality. Building Comfort. Precision. Air Conditioning

DATA CENTER COOLING INNOVATIVE COOLING TECHNOLOGIES FOR YOUR DATA CENTER

Continuous Commissioning of the Dallas/Fort Worth International Airport

Energy Efficiency in Industrial HVAC Systems

5.6 Technical Specification: Premium Efficiency Electric Air Conditioning Equipment

Building Energy Systems. - HVAC: Heating, Distribution -

NetApp Data Center Design

Building Commissioning

Calculating System Flow Requirements

By Steven C. Severini, P.E., Member ASHRAE

CHILLED WATER PLANT PUMPING SCHEMES. James J. Nonnenmann, PE Stanley Consultants, Inc. Muscatine, Iowa

Heating, ventilation and air conditioning equipment. A guide to equipment eligible for Enhanced Capital Allowances

ASHRAE Rocky Mountain Chapter. RickPhillips Phillips, P.E., PE LEED AP Senior Mechanical Engineer The RMH Group, Inc.

Building Analytics Improve the efficiency, occupant comfort, and financial well-being of your building.

Denver International Airport Total Facility Optimization. Josh Foerschler Aurom Mahobian

Chilled Water HVAC Systems

OPTIMIZING CONDENSER WATER FLOW RATES. W. A. Liegois, P.E. Stanley Consultants, Inc. Muscatine, Iowa

Temperature Controls Design

HEATING, VENTILATION & AIR CONDITIONING

Using Time-of-Day Scheduling To Save Energy

Sample - Existing Building Commissioning Plan

SECTION TESTING, ADJUSTING, AND BALANCING FOR HVAC INTRODUCTORY INFORMATION

2 STEPS TO CONDUCTING YOUR HVAC ASSESSMENT

Automated Commissioning for Energy (ACE) Platform for Large Retail Property. Overview

How To Control Humidity With A Humidifier

Transcription:

Energy & Heat Transfer in Healthcare HVAC Shawn Wilson, PE TME, Inc. swilson@tmecorp.com 12/5/2013 HAAHE/TAFHM Facility Manager Basic Training 1

Why target HVAC Systems? Shifting the Paradigm Agenda Controls are the Key 4 Opportunities Chilled Water Pumping Cooling Tower Relief Air Handler Controls, Resets Air Terminal Controls, Troubleshooting Closing, Q&A 12/5/2013 HAAHE/TAFHM Facility Manager Basic Training 2

Hospital HVAC Unique regulatory requirements for temperature and RH, airflow, and pressure relationships. Special applications (Surgery, Lab, Pharmacy, Sterile Processing etc ) Energy intensive facilities. Complex Systems, Complex Controls 12/5/2013 HAAHE/TAFHM Facility Manager Basic Training 3

Hospital Operating Costs 10% 3% 7% People Supplies 20% 60% Debt Service Energy Other 12/5/2013 HAAHE/TAFHM Facility Manager Basic Training 4

Hospital Business Environment Higher Costs Lower Revenues Insufficient Margins for Reinvestment Mounting Backlog of Deferred Maintenance 12/5/2013 HAAHE/TAFHM Facility Manager Basic Training 5

Average $4.09/SF Hospital Energy Costs

Hospital Operating and Maintenance Budgeting Typical Hospital Operating and Maintenance Budget ($7 to $12 per SF) Energy 51% Staffing 27% 14% 8% Service Contracts Materials 12/5/2013 HAAHE/TAFHM Facility Manager Basic Training 7

Hospital Operating and Maintenance Budgeting Reduced Operating Budgets Staffing Levels are already too Low Staffing 27% Energy 51% 14% 8% Service Contracts Materials 12/5/2013 HAAHE/TAFHM Facility Manager Basic Training 8

Hospital Operating and Maintenance Budgeting Reduced Operating Budgets Staffing Levels are already too Low Higher Material Costs 27% Energy 51% Staffing 14% 8% Service Contracts Materials 12/5/2013 HAAHE/TAFHM Facility Manager Basic Training 9

Hospital Operating and Maintenance Budgeting Reduced Operating Budgets Staffing Levels are already too Low Higher Material Costs Higher Service Contract Costs Energy 51% Staffing 27% 8% Materials 14% Service Contracts 12/5/2013 HAAHE/TAFHM Facility Manager Basic Training 10

Hospital Operating and Maintenance Budgeting Reduced Operating Budgets Staffing Levels are already too Low Higher Material Costs Higher Service Contract Costs Energy Costs must be Reduced Energy 51% Staffing 27% 14% 8% Service Contracts Materials 12/5/2013 HAAHE/TAFHM Facility Manager Basic Training 11

Energy Use In Hospitals 12/5/2013 HAAHE/TAFHM Facility Manager Basic Training 12

Why target HVAC Systems? Shifting the Paradigm Agenda Controls are the Key 4 Opportunities Chilled Water Pumping Cooling Tower Relief Air Handler Controls, Resets Air Terminal Controls, Troubleshooting Closing, Q&A 12/5/2013 HAAHE/TAFHM Facility Manager Basic Training 13

Selecting Systems and Equipment based on First Cost Using the Same Design for Every Project Conservative Over-Sizing of Equipment Current Paradigm Selecting Systems and Equipment without Considering Current and Future Utility Rates Control Systems Designed by Control System Manufacturers (not the Engineer) Commissioning included but often becomes construction phase QC and documentation exercise. 12/5/2013 HAAHE/TAFHM Facility Manager Basic Training 14

Current Best Practices Don t Always Yield High Performance LEED Efficient Design Standard Commissioning 12/5/2013 HAAHE/TAFHM Facility Manager Basic Training 15

LEED Certification Some Buildings not Living up to Green Label By Mirya Navarro August 30, 2009 LEED Buildings are no more Energy Efficient than their Peers More than half of LEED Buildings not eligible for Energy Star Label 15% of LEED Buildings have an Energy Star Rating less than 30 LEED is not Bad 12/5/2013 HAAHE/TAFHM Facility Manager Basic Training 16

Standard Commissioning LEED Certified Facilities have been Commissioned Many low Performing Hospitals were Commissioned Standard Commissioning is not bad 12/5/2013 HAAHE/TAFHM Facility Manager Basic Training 17

Potential Causes of Low Performance Energy Efficient Features are frequently Value Engineered out of the Project Systems are too complex for O&M Staff to Operate and Maintain Drive By Commissioning does Occur Facility Performance is not Measured and Verified Commissioning Agent Design Reviews are restricted to Commissionability Only O&M Staff have traditionally focused on Regulatory Compliance, Infection Rates, Comfort, and not Energy Efficiency 12/5/2013 HAAHE/TAFHM Facility Manager Basic Training 18

Potential Causes of Low Performance Control System Programming is not Consistent with the Design Intent Energy Management Systems are under Utilized Air Terminal Air Flow Setpoints are not Programmed in Correctly O&M Staff Training by Contractors does not Focus on Energy Conservation CxA is not Responsible for Building Performance O&M Staff are not Vested in a Positive Outcome Excess Simultaneous Heating and Cooling 12/5/2013 HAAHE/TAFHM Facility Manager Basic Training 19

Shifting the Paradigm Albert Einstein s Definition of Insanity: Doing the same thing over and over again and expecting different results. 12/5/201 HAAHE/TAFHM Facility Manager Basic Training 20

ASHE s Commissioning Guidelines and Handbook Meeting the Energy Efficiency Goals is not Optional Current Best Practices don t always Work Causes of Low Performance are Known ASHE s Commissioning Guidelines and Handbook focus on Meeting Facility and Project Energy Efficiency Goals 12/5/2013 HAAHE/TAFHM Facility Manager Basic Training 21

Construction Costs and Operating Costs must be Considered Holistically New Paradigm Minimize Reheat Create Synergy between Systems that Remove and Generate BTUs Pay Attention to the Control Programming 12/5/2013 HAAHE/TAFHM Facility Manager Basic Training 22

Setting the Energy Efficiency Goal If you aim at nothing, you ll hit it every time. Zig Ziglar 12/5/2013 HAAHE/TAFHM Facility Manager Basic Training 23

Benchmarking EPA Target Finder Weather Adjusted Occupancy Adjusted Free Service Internet Based Simplified Input Percentile Ranking 12/5/2013 HAAHE/TAFHM Facility Manager Basic Training 24

Measurement and Verification Measuring on routine basis is critical. Review regularly. 12/5/2013 HAAHE/TAFHM Facility Manager Basic Training 25

Why target HVAC Systems? Shifting the Paradigm Agenda Controls are the Key 4 Opportunities Chilled Water Pumping Cooling Tower Relief Air Handler Controls, Resets Air Terminal Controls, Troubleshooting Closing, Q&A 12/5/2013 HAAHE/TAFHM Facility Manager Basic Training 26

Designing the Control System Consider Design Conditions and Off-Design Conditions Design should Include Diagram, Sequence of Operation, Point List, Valve Schedule, and Damper Schedule Design should be Detailed, but not Manufacturer Specific Control System Design, Sequence, and Programming have more Impact on Hospital Energy Efficiency than System and Equipment Selections 12/5/2013 HAAHE/TAFHM Facility Manager Basic Training 27

Goal is Optimum Performance Include Fail-Safe Provisions Identify Inputs, Loop Statements, Table Statements, Logical Operators, Setpoints, Local Variables, and Outputs Developing the Sequence of Operation Consider Using a Flow Chart to Convey Design Intent Must be Very Detailed to Prevent Misunderstandings Lack of a Detailed Sequence is the Reason why most Buildings Fail to Achieve their Energy Efficiency Goals 12/5/2013 HAAHE/TAFHM Facility Manager Basic Training 28

AHU Supply Air Temperature Reset Control Loops Cooling Loopout /Chilled Water Control Valve is equal to the output of the following PI loop: Action Direct Input Supply Air Temperature Setpoint Cooling Setpoint Minimum Output 0 Maximum Output 100 Developing the Sequence of Operation Supply Air Temperature: The supply air temperature setpoint ( cold deck temperature ) is increased and decreased from the minimum to the maximum and vice versa according to the following logic: Input Request for more cooling from Air Terminals Output Supply Air Temperature Setpoint. Equal to the lower of comparison of Calculated Supply Air Temperature Setpoint (reset based on polling zones described in this section) and Dehumidification Override Supply Air Temperature Setpoint (section 9.c). Minimum SAT Setpoint (60F) Maximum SAT Setpoint (65F) Sampling Rate/Rate of Change: 1F/5 mins 12/5/2013 HAAHE/TAFHM Facility Manager Basic Training 29

Why target HVAC Systems? Shifting the Paradigm Agenda Controls are the Key 4 Opportunities Chilled Water Pumping Cooling Tower Relief Air Handler Controls, Resets Air Terminal Controls, Troubleshooting Closing, Q&A 12/5/2013 HAAHE/TAFHM Facility Manager Basic Training 30

Chilled Water System Issues Improper Chiller, Cooling Tower, and/or Pump Sequencing Differential Pressure Setpoint Reset Overridden Condenser Water Supply Temperature Reset Overridden (or not programmed). Low Chilled Water Temperature Difference (Low Delta T) 12/5/2013 HAAHE/TAFHM Facility Manager Basic Training 31

CV Primary/ Variable Flow Secondary Chilled Water System First developed by B&G in 1954. 2 Hydraulically Independent loops via Decoupler bypass pipe ( neutral bridge ). Primary pumps interlocked with each Chiller to provide design (constant) gpm. Secondary pumps are modulated to meet system DP requirement. 12/5/2013 HAAHE/TAFHM Facility Manager Basic Training 32

CV Primary/ Variable Flow Secondary Chilled Water System Perfect world Primary Loop GPM = Secondary Loop GPM. No flow in Decoupler pipe. In the real world this is seldom the case. 12/5/2013 HAAHE/TAFHM Facility Manager Basic Training 33

CV Primary/ Variable Flow Secondary Chilled Water System 12/5/2013 HAAHE/TAFHM Facility Manager Basic Training 34

CV Primary/ Variable Flow Secondary Chilled Water System KEY PERFORMANCE INDICATORS Secondary Loop Delta T. Low Delta T indicates excessive pumping. Chillers, AHU Coils are more efficient at higher delta T. System Operating DP. High system differential pressure can mask other problems. Higher DP = higher pumping horsepower. High DP s can adversely affect control valve/coil performance. Btu/h 500 GPM T For a given load, Flow and ΔT are inversely proportional. As GPM increases, ΔT drops. 12/5/2013 HAAHE/TAFHM Facility Manager Basic Training 35

CV Primary/ Variable Flow Secondary Chilled Water System Control Sequence Reset DP setpoint based on actual AHU demand (chilled water valve positions). Stage chillers based on tonnage but watch the temperature of water in decoupler and secondary loop Delta T for fault detection. Add secondary loop Delta T to dashboard. 12/5/2013 HAAHE/TAFHM Facility Manager Basic Training 36

Variable Primary Chilled Water Variable Flow through Chillers Only 1 Set of Pumps Pumps Sequenced to Maintain Delta P and Minimum Flow Bypass Valve Modulates to Maintain Minimum Flow Requires Electronic Flow Safeties Lower Capital Cost, Energy Cost, and Maintenance Cost 12/5/2013 HAAHE/TAFHM Facility Manager Basic Training 37

Why target HVAC Systems? Shifting the Paradigm Agenda Controls are the Key 4 Opportunities Chilled Water Pumping Cooling Tower Relief Air Handler Controls, Resets Air Terminal Controls, Troubleshooting Closing, Q&A 12/5/2013 HAAHE/TAFHM Facility Manager Basic Training 38

Condenser Water Relief Still many plants control tower water to single setpoint (80F aquastat) Chiller Efficiency improves with colder condenser water. 12/5/2013 HAAHE/TAFHM Facility Manager Basic Training 39

Lots of hours of operation even in South Texas

It s all about LIFT Condensing temperature minus the suction temperature Two ways to decrease Lift by adjusting DDC: Lower Condenser Water Temperature Raise Chilled Water Supply Temperature 12/5/2013 HAAHE/TAFHM Facility Manager Basic Training 41

Condenser Water Relief Implementation for Constant Volume Pumping Tower fan energy versus lower chiller kw Reset loop setpoint based on wet bulb and run the condenser loop as cold as possible 2 tower cells paired with 1 Chiller Be aware of lower limit. 12/5/2013 HAAHE/TAFHM Facility Manager Basic Training 42

Variable Volume Condenser Water System Valves Modulate to Maintain Proper Flow Flow at Design with Minimum Refrigerant Lift Override Chillers can Operate with Very Cold Condenser Water (eliminates transition issues with hydronic free cooling) Any Chiller with any Tower with any Pump Pumps Sequenced in a Best Efficiency Manner Towers Sequenced in Best Efficiency Manner 12/5/2013 HAAHE/TAFHM Facility Manager Basic Training 43

3.0 GPM per Ton Condenser Water Flow Rate 12/5/2013 HAAHE/TAFHM Facility Manager Basic Training 44

Why target HVAC Systems? Shifting the Paradigm Agenda Controls are the Key 4 Opportunities Chilled Water Pumping Cooling Tower Relief Air Handler Controls, Resets Air Terminal Controls, Troubleshooting Closing, Q&A 12/5/2013 HAAHE/TAFHM Facility Manager Basic Training 45

Air Handling Unit Issues Static Pressure Setpoint Reset Overridden Malfunctioning Control Valves Supply Air Temperature Setpoint Reset Overridden Failed Air Flow Measuring Stations Malfunctioning Dampers Weekly Schedules Overridden Simultaneous Heating and Cooling 12/5/2013 HAAHE/TAFHM Facility Manager Basic Training 46

Multiple Loop Temperature Control Loop 1 Loop 4 Loop 2 Loop 3 12/5/2013 HAAHE/TAFHM Facility Manager Basic Training 47

Multiple Loops 2022 Loop (0, Input, Output, Setpoint, P, I, D, Min, Max, Bias) 4 Setpoints 4 Sets of Proportional and Integral Gains Setpoints may Inadvertently Overlap Tuning is very Difficult Outputs will Overlap due to Hunting Simultaneous Heating and Cooling 12/5/2013 HAAHE/TAFHM Facility Manager Basic Training 48

Multiple Loops Mixed Air Preheat CHW Coils Time Mixed Air Temperature Mixed Air Setpoint Output Preheat Temperature Coil Leaving Preheat Setpoint Output Air Temperature Supply Supply Air Air Temperature Setpoint Output 3:00 55.3 55 51 55.3 50 0 40.7 47.5 48 24 3:05 48.0 55 76 57.6 50 24 41.6 48.1 48 27 3:10 57.7 55 42 57.7 50 0 42.0 48.9 48 26 3:15 60.5 55 33 60.5 50 0 42.2 48.3 48 30 3:20 54.9 55 51 54.9 50 0 40.9 47.2 48 23 3:25 47.5 55 79 54.7 50 18 41.0 47.6 48 23 3:30 58.3 55 39 58.3 50 0 41.8 48.4 48 28 3:35 62.0 55 29 62.0 50 0 42.3 48.7 48 33 3:40 54.1 55 55 54.1 50 0 41.4 48.2 48 21 3:45 48.5 55 75 52.9 50 11 41.1 47.6 48 20 12/5/2013 HAAHE/TAFHM Facility Manager Basic Training 49

Overlapping Setpoints Mixed Air Preheat CHW Coils Time Mixed Air Temperature Mixed Air Setpoint Output Preheat Temperature Coil Leaving Preheat Setpoint Output Air Temperature Supply Supply Air Air Temperature Setpoint Output 3:00 55.3 55 51 55.3 50 0 40.7 47.5 48 24 3:05 48.0 55 76 57.6 50 24 41.6 48.1 48 27 3:10 57.7 55 42 57.7 50 0 42.0 48.9 48 26 3:15 60.5 55 33 60.5 50 0 42.2 48.3 48 30 3:20 54.9 55 51 54.9 50 0 40.9 47.2 48 23 3:25 47.5 55 79 54.7 50 18 41.0 47.6 48 23 3:30 58.3 55 39 58.3 50 0 41.8 48.4 48 28 3:35 62.0 55 29 62.0 50 0 42.3 48.7 48 33 3:40 54.1 55 55 54.1 50 0 41.4 48.2 48 21 3:45 48.5 55 75 52.9 50 11 41.1 47.6 48 20 12/5/2013 HAAHE/TAFHM Facility Manager Basic Training 50 50

Simultaneous Heating and Cooling Mixed Air Preheat CHW Coils Time Mixed Air Temperature Mixed Air Setpoint Output Preheat Temperature Coil Leaving Preheat Setpoint Output Air Temperature Supply Supply Air Air Temperature Setpoint Output 3:00 55.3 55 51 55.3 50 0 40.7 47.5 48 24 3:05 48.0 55 76 57.6 50 24 41.6 48.1 48 27 3:10 57.7 55 42 57.7 50 0 42.0 48.9 48 26 3:15 60.5 55 33 60.5 50 0 42.2 48.3 48 30 3:20 54.9 55 51 54.9 50 0 40.9 47.2 48 23 3:25 47.5 55 79 54.7 50 18 41.0 47.6 48 23 3:30 58.3 55 39 58.3 50 0 41.8 48.4 48 28 3:35 62.0 55 29 62.0 50 0 42.3 48.7 48 33 3:40 54.1 55 55 54.1 50 0 41.4 48.2 48 21 3:45 48.5 55 75 52.9 50 11 41.1 47.6 48 20 12/5/2013 HAAHE/TAFHM Facility Manager Basic Training 51

What is the Problem? Mixed Air Preheat CHW Coils Time Mixed Air Temperature Mixed Air Setpoint Output Preheat Temperature Coil Leaving Preheat Setpoint Output Air Temperature Supply Supply Air Air Temperature Setpoint Output 3:00 55.3 55 51 55.3 50 0 40.7 47.5 48 24 3:05 48.0 55 76 57.6 50 24 41.6 48.1 48 27 3:10 57.7 55 42 57.7 50 0 42.0 48.9 48 26 3:15 60.5 55 33 60.5 50 0 42.2 48.3 48 30 3:20 54.9 55 51 54.9 50 0 40.9 47.2 48 23 3:25 47.5 55 79 54.7 50 18 41.0 47.6 48 23 3:30 58.3 55 39 58.3 50 0 41.8 48.4 48 28 3:35 62.0 55 29 62.0 50 0 42.3 48.7 48 33 3:40 54.1 55 55 54.1 50 0 41.4 48.2 48 21 3:45 48.5 55 75 52.9 50 11 41.1 47.6 48 20 12/5/2013 HAAHE/TAFHM Facility Manager Basic Training 52

Table Statement Output Single Loop Temperature Control 100 80 Preheat Valve 60 First Stage Economizer Cycle (Maximum OSA Damper) 40 20 Stage 1 Stage 2 Stage 3 Stage 4 Stage 5 Second Stage Economizer Cycle (Return Air and Relief Air Dampers) Secondary Chilled Water Valve 0 0 20 40 60 80 100 Primary Chilled Water Valve Supply Air Temperature Control Statement Output 12/5/2013 HAAHE/TAFHM Facility Manager Basic Training 53

Table Statement Output Single Loop Humidity Control 100 80 60 40 Disable Second Stage of Economizer Cycle (Opens Return and Closes Relief Dampers) Disable First Stage of Economizer Cycle (Closes Maximum OSA Damper) 20 Stage 1 Stage 2 Stage 3 Humidifier Steam Valve 0 0 20 40 60 80 100 Return Air Humidity Control Statement Output 12/5/2013 2012 American Society for Healthcare Engineering of the American Hospital Association 54

Adaptive Resets Reset Supply Air Temperature ( Cold Deck Reset ). Reset Duct Static Pressure Setpoint ASHRAE 90.1, Energy Code 12/5/2013 HAAHE/TAFHM Facility Manager Basic Training 55

Dedicated Outside Air AHU Pre-treat ventilation air. Ducted to outside air damper on individual AHUs. 12/5/2013 HAAHE/TAFHM Facility Manager Basic Training 56

Air-Side Economizer Cycles Air-Side Economizer Cycles often incorrectly programmed/configured and difficult to maintain. 12/5/2013 HAAHE/TAFHM Facility Manager Basic Training 57

3:00 3:05 3:10 3:15 3:20 3:25 3:30 3:35 3:40 3:45 Economizer Damper Control Loop not Tuned 90 80 70 60 50 40 30 20 10 0 Economizer Damper Output Mixed Air Setpoint Mixed Air Temperature 12/5/2013 HAAHE/TAFHM Facility Manager Basic Training 58

Air-Side Economizer Cycles on AHU s with Humidifiers ASHRAE Standard 90.1 Requires Hydronic Free Cooling if Humidification Dewpoint is > 35 deg. F (30% RH at 68 deg. F) Cooling Savings are more than Offset by Higher Humidification Costs Air-Side Economizer Cycles are Costly to Implement and Difficult to Maintain 12/5/2013 HAAHE/TAFHM Facility Manager Basic Training 59

Operating Room Challenges Surgeons/staff want 60F/50% rh Difficult if not impossible to achieve with typical chilled water system 12/5/2013 HAAHE/TAFHM Facility Manager Basic Training 60

Operating Room Challenges 12/5/2013 HAAHE/TAFHM Facility Manager Basic Training 61

Operating Room Challenges Desiccant Technology provides lower dewpoints. Dedicated OSA AHU with Type III passive dessicant wheel shown. 12/5/2013 HAAHE/TAFHM Facility Manager Basic Training 62

Operating Room Challenges Air change rates, pressure differentials difficult to optimize often are not reset based on occupancy. 12/5/2013 HAAHE/TAFHM Facility Manager Basic Training 63

Unoccupied/Occupied Reset for Operating Rooms Occupied 15 to 25 ACH Unoccupied 5 to 8 ACH DP 0.01 w.g.

Why target HVAC Systems? Shifting the Paradigm Agenda Controls are the Key 4 Opportunities Chilled Water Pumping Cooling Tower Relief Air Handler Controls, Resets Air Terminal Controls, Troubleshooting Closing, Q&A 12/5/2013 HAAHE/TAFHM Facility Manager Basic Training 65

Air Terminal Issues Failed Averaging Velocity Sensors Malfunctioning Terminal Dampers Malfunctioning Heating Water Control Valves Insufficient Air Flow to Accommodate Space Sensible Cooling Load Incorrect Air Flow Setpoints Deadband too Small Thermostat Range not Restricted Weekly Schedules Overridden Occupancy Sensors Overridden Failed Points Simultaneous Heating and Cooling 12/5/2013 HAAHE/TAFHM Facility Manager Basic Training 66

VAV Air Terminal with Heating 12/5/2013 HAAHE/TAFHM Facility Manager Basic Training 67

VAV Air Terminal with Heating Minimizing Reheat Best Practice: Modulate HW Valve to a Discharge Setpoint and Reset the Setpoint from Minimum up to Maximum before Increasing Air Flow. 12/5/2013 HAAHE/TAFHM Facility Manager Basic Training 68

VAV Air Terminal Troubleshooting Failed Averaging Velocity Sensors Malfunctioning Terminal Dampers Malfunctioning Heating Water Control Valves Insufficient Air Flow to Accommodate Space Sensible Cooling Load Don t apply a system wide correction to a zone level problem. 12/5/2013 HAAHE/TAFHM Facility Manager Basic Training 69

You can t manage what you don t measure. Closing Thoughts The code is the key. Get it right and good things happen. Don t use a sledge hammer to drive a finish nail. 12/5/2013 HAAHE/TAFHM Facility Manager Basic Training 70

Thank You! Questions? The only constant is change. - Heraclitus It is not the strongest of the species that survives, nor the most intelligent that survives. It is the one that is the most adaptable to change. Charles Darwin 12/5/201 2012 American Society for Healthcare Engineering of the American Hospital Association 71