AcuRev 2000 Multi-Circuit Power and Energy Meter

Similar documents
RISH EM 3490 DS Dual Source Energy Meter RISH EM 3490 DS. Application : Product Features:

Features. Display. Measurements. Intelligent. Accuracy. Models. Installation DEIF A/S. Multi-instrument D

User Manual V SDM220MODBUS. Single-Phase Two Module DIN rail Meters

Power-monitoring unit PowerLogic System. Technical data sheet. Power Meter Series 800

Applications. diris_826_a_1_gb_cat

A project to optimise quality and energy efficiency must include metering

Energy Management Energy Meter Type EM23 DIN

Polyphase kwh Electricity Meter

Quick Connect. quick - simple - efficient.

Power Meter Series 700

NC-12 Modbus Application

Metering for today s systems

EARTH LEAKAGE PROTECTION: CONTENTS

Panel Meters and Controllers Modular Panel Meter Type EDM 35

Energy Management Power Analyzer Type WM14-96 Basic Version

PCS0100en Persy Control Services B.V. Netherlands

Energy Depot GmbH PRODUCT AND APPLICATION GUIDE. Total Monitoring Solution for PV. Delivering Solutions for Energy Management

Application/Connection Examples

Digital and Analog I/O

Panorama Electricity meters For reliable values of energy consumption

ENERGY SOLUTIONS RESIDENTIAL STORAGE BATTERY SYSTEM

Programmable set for Ethernet Modbus/TCP in IP67 TI-BL67-PG-EN-2

March 15th 2005 EI Solutions - Submetering 1

MLC TM Maximum Productivity and Versatility for Control without Compromise!

Analogue Input, 4-fold, MDRC AE/S 4.1, GH Q R0001

LTR Series Uninterruptible Power Systems 700 VA KVA. General Specification

M2M The measure of efficiency

ABB PV + Storage REACT-3.6/4.6-TL 3.6 to 4.6 kw

POWERLOGIC Circuit Monitor Series 2000

RISH CON - Hz. Salient Features : Application : Product Features: FREQUENCY TRANSDUCER

Multilin EPM GE Grid Solutions. High Accuracy Power & Energy Measurement. Monitoring & Metering. Advanced Communications.

DRTS 33. The new generation of advanced test equipments for Relays, Energy meters, Transducers and Power quality meters

Indoor / Outdoor Antenna

Metering Devices IQ Analyzer 6400/6600 Series

Power quality monitoring and analysis with reliability

JNIOR. Overview. Get Connected. Get Results. JNIOR Model 310. JNIOR Model 312. JNIOR Model 314. JNIOR Model 410

Electrical Measuring Instruments

Table of Contents. TransformerIQ FAQs 1

RM17TE V AC. Main. Product or component type. Product specific application. Relay monitored parameters 250 V DC 5 A DC

Electronic Control Devices The European Product Catalogue 2007

Model: DC-A2IO Advanced HVAC Controller

Positive-guided relay outputs: 3 safety contacts (N/O), instantaneous. 1 auxiliary contact (N/C), instantaneous

Installation manual. Generator Paralleling Controller GPC multi-line C

T Substation Maintenance and Commissioning Test Equipment

Your Advantages For safety application up to PL e / Cat. 4 e.g. SIL 3 Manual or automatic start * see variants. Applications.

Temperature & Humidity SMS Alert Controller

MILLENIUM INSTALLATION MANUAL NTR 735 A. Simple Automation Control Module (MAS)

How Do You Reduce Energy Costs And Prolong The Life Of Your Equipment?

Thyristor-controlled power supplies and battery chargers

PRODUCT LIST Facility DDC Access WebXL DDC

RoHS APPROVAL SHEET. ituner 12V/6.6A SERIES NO. (E17) EA10953A. ( ) Edac Power Electronics (Suzhou) Co., Ltd. 59 No.59, Chang Sheng Road, Sheng Pu,

AIS750 Series Alarm Annunciator

One Meter Works for Both Energy Saving and Power Quality Surveillance

3-phase, bidirectional energy meter

ZC-24DO CANopen I/O Module: 24 Digital Outputs

RM35UA13MW. range V. Main. Product or component type. Relay monitored parameters

EATS16 EATS16N. Installation and user manual ENGLISH. Copyright 2015 EATON All rights reserved.

Automation System TROVIS 6400 TROVIS 6493 Compact Controller

DAM Series DAM124 4DIN+8AI+4DO Module Model No.:DAM124 WebSite:

Application Note: Monitoring Branch Circuit Loads in Critical Facilities

Multifunction devices

Device Support in PowerLogic ION Enterprise 5.6 Service Pack 2

APC. DIN Rail Control Panel Mounting Uninterruptible Power Supply. Catalog

Phase Modular Finally the benefits of Modular ups are for all

SOLARCARE SERIES PRODUCT AND APPLICATION GUIDE

Rack mounted telephone- and leased line modem for industrial applications

ADM1TE 5/30A DIN rail single phase two wire energy meter

OZW30. Central Unit SYNERGYR

AUTOMATIC TRANSFER SWITCH CONTROL UNIT OPERATOR S MANUAL

Main catalog. Electricity meters For modular enclosures and DIN rail

Intelligent chart recorder for compressed air and gases. Measurement - control - indication - alarm - recording - evaluation

SHARKY 775 COMPACT ENERGY METER ULTRASONIC

Control Devices Catalogue. Control Devices. Preferred and Standard Products

SM6 Series Circuit Breaker Monitors CONSOLIDATED. Electronics, Inc. MONITORING THE FUTURE

DC UPS. RTB.e A. IMB.e/ITB.e kva. E2001.e/E3001.e kva. Input voltage: 110/125/220 Vdc. 115/120/230 Vac, 1-phase (IMB.

Digital multimeters DMG

Digital input modules

APC Matrix-UPS 5kVA 208V/240V In 120/208/240V Out

SIMATIC S It s the Interplay that makes the difference. Siemens AG All Rights Reserved.

Technical note NT588 NT604 NT695 NT782

HMI display Installation Guide

UNINTERRUPTIBLE POWER SUPPLIES >9900AUPS UNINTERRUPTIBLE POWER SUPPLIES

AIS 3000 APC AIS kVA 208V w/2 Batt. Module Exp. To 4, Start-Up 5X8, Internal Maintenance Bypass

4 non-safe digital I/O channels 2 IO-Link Master V1.1 slots. Figure 1. Figure 2. Type code. TBPN-L1-FDIO1-2IOL Ident no

Manual. IP Sensor and Watchdog IPSW2210. I P S W M a n u a l P a g e 1. Relay Output. Power input. 12VDC adapter LED Indicators. 2 Dry.

FLOW CALCULATOR INSTRUCTION MANUAL MESURES BAMOPHOX M1 02 E MES FLOW CALCULATOR /1

Portal Software GSM-PRO Run LED displays module activity Com LED displays activity on the GSM network GSM-PRO

Safety technique. Emergency stop module BO 5988 safemaster

CRITICAL POWER MONITORING CPM20/CPM21 DETAILS

Telephone- and leased line modem for industrial applications TD-36

Section TELEPHONE AUTOMATIC DIALER SYSTEM

Disturbance Recoder SPCR 8C27. Product Guide

PowerLogic power-monitoring units. PM5350 power meter. Technical data sheet

Communicate and view data from meters with one simple device

AS-i 3.0 Gateways, PROFIsafe via PROFIBUS or PROFINET

MAJORSINE Power Inverter

PHASED OUT. Digital dimmable ballasts for fluorescent lamps EXCEL one4all series. PCA TCL EXCEL one4all, W Compact and T5c fluorescent lamps

SHARKY 775 COMPACT ENERGY METER ULTRASONIC

PHASED OUT. Digital dimmable ballasts for fluorescent lamps ECO series. PCA TCL ECO, W Compact and T5c fluorescent lamps

Modular I/O System Analog and Digital Interface Modules

Transcription:

AcuRev 2000 Multi-Circuit Power and Energy Meter ISO9001 Certified

Comply to IEC 62053-22 Measurement Standard Support up to 18 Individual Channels for Energy Measurement Multifunction Power Metering, Monitoring and System Analysis Data Logging and Load Status Recording Multiple Communication Ports Modular Design Extented Power Supply (100-415 Vac) Data (Pulse) Collection from Water and Gas Meter DESCRIPTION The AcuRev 2000 Series is the next generation multifunction energy meter developed and manufactured by Accuenergy. It performs real-time metering, measures energy consumption and monitors quality for up to 18 single phase circuits (or 6 three phase circuits) in one unit. AcuRev 2000 series meter is ideal for multi-tenants submetering applications such as in commercial facilities, residential apartments and industrial environments. Communication options include infrared, serial communication and Ethernet. There are also multiple I/O options which can support pulse counting from water and gas meters as well as provide a kwh pulse output. Due to its communication capability, compact size and ease of use, the AuRev 2000 series is a simple, intelligent and cost effective solution for any energy management system. APPLICATIONS Commercial Complex and Malls Schools, Colleges and Universities Public Services and Establishments Hotels and Office Buildings Intelligent Distribution Systems Condominium and Apartment Complexes Energy Management Systems Utilities and Industrial Applications Power and Load Monitoring Systems Railway and Subway Systems AcuRev 2000 Series Meter Functions and measuring parameters for the two AcuRev 2000 series meters (AcuRev 2010 - kwh meter only; AcuRev 2020 - multifunction energy meter) are listed below: Function Parameter AcuRev2010 AcuRev2020 Energy Ep ENERGY Reactive Energy Eq Apparent Energy Es TIME OF USE 4 Tarrifs, 14 Schedules TOU POWER DEMAND Power Demand Demand_P Peak Power Demand Demand_P_max CURRENT DEMAND Current Demand Peak Current Demand Phase Voltage V1,V2,V3 Line Voltage V12,V23,V31 Current REAL TIME METERING Power Reactive Power Apparent Power Power Factor Frequency F Total Harmonic Distortion THD Individual Harmonics 2nd ~ 31st (Voltage and Current) POWER QUALITY Current K Factor KF Voltage Crest Factor CF Voltage Unbalance U_unbl Current Unbalance I_unbl TIME Real Time Clock (Year, Month, Date, Hour, Minute, Second) ALARMING Over/Under Limit Alarming DATA LOGGING Up to 8MB memory storage Infrared COMMUNICATION Modbus(R)-RTU PORT Ethernet Modbus(R)-TCP, HTTP, SMTP, SNMP, SNTP Option Option 2 Channel Pulse Output, Second Pulse, Demand Cycle I/O OPTION 8 Channel Digital Input with 15Vdc Power Supply Option Option 4 Channel Relay Output for Alarming Purpose Option Option DISPLAY Screen Display

FEATURES Metering Voltage: Phase voltage V1, V2, V3; line voltage V12, V23, V31 Current: Total current and current for each circuit Power and Power Factor: P, Q, S and PF for total and each circuit Frequency: System frequency F Demand: Power and current demand for total and each circuit Time of Use (TOU) TOU can be used according to different regional billing requirements. AcuRev 2000 series supports up to 4 tarrifs, 14 schedules, 14 segments, weekend and holiday programming as well as energy (kwh) pulse output. Statistics The AcuRev 2000 series has a built in self-check and validation function. Upon various conditions (such as energy and demand resetting, system parameter updates or alarming) the meter will record the event and time stamp it into the statistical log. Relay outputs can also then be triggered when any of the conditions are met. Over/Under Limit Alarming Over/under limit alarming parameters can be set according to user's preference. If an indicated parameter is over/under its setting limit and persists over the specified time interval, an alarm signal will be activated via its relay output ports. Alarm records and time stamps are stored in the memory. Data Logging With 8MB of onboard memory, AcuRev 2000 series can log real-time metering parameters, I/O status, and energy measurement. This information can be used for historical trending and system analysis. Display and Installation The AcuRev 2000 Series has a scrolling display LCD screen for multi-circuits parameter readout. The display module is factory installed together with the base unit or can be ordered as a remote panel mountable display. To provide easy installation and to cut costs, an internal current transformer option is also available. This allows 20A to 80A current to be directly connected to the meter, therefore eliminating the need for external CT's. However the use of external CT's is another available configuration to allow for retrofit or higher current applications. Power Quality Analysis Power quality parameters such as voltage and current THD, individual voltage and current harmonics, voltage crest factor, current K factor, voltage and current unbalance, etc. will be monitored. I/O Option I/O ports from the AcuRev 2000 series expands the capability and functionality of the energy meter. Standard output ports provide energy (kwh) pulse output and time pulse output; digital inputs (DI) provide pulse counting from water, electricity and gas meter, and monitor switch status; relay outputs (RO) react upon alarming conditions. Communication The AcuRev 2000 series supports multiple communication options including: Modbus-RTU via serial port Modbus-TCP, SMTP, SNMP, SNTP, HTTP Infrared data port DIMENSIONS The AcuRev 2000 series base unit and modules are designed to be mounted on a 35mm DIN rail (EN 50022 standard). Type Dimension Base Unit L W H 140 105.4 77.7mm EM Module L W H 67 105.4 77.7mm DM Module L W H 153 105.4 77.7mm External Display Module L W H 72 72 26.5mm Meter Base 140 (5.51) 35 (0.13) 77.7 (3.05) Display Module Display Module is designed with flexiblity in mind, it can be installed together with the base unit or can be mounted on a panel.* * (when ordered as a separate module. Please see ordering information for details). 71.5 (2.81) 10 (0.39) 15.5 (0.61) 67 (2.63) 72 (2.83) 67 (2.63) 67 (2.63) Cut Out Cutout

EM Module 67(2.63) 35 (0.13) 77.7 (3.05) DM Module 153 (6.02) 35 (0.13) 77.7 (3.05) Current Transformer (Solid Core) figure-a Unit: mm CCT-20/CCT-80 CCT-150/CCT-200 figure-b Unit: mm Bottom view Side View Front View Red Black Type Φ Height (mm) Width (mm) Thickness (mm) Figure CCT-20 12 53 46 25 CCT-80 20 53 46 25 figure-a CCT-150 26 63.5 78 21 CCT-200 26 63.5 78 21 figure-b

Current Transformer (Solid Core) SCT-20/SCT-80/SCT-150/SCT-200 SCT-250/SCT-1000 figure-c Bottom view figure-d Bottom view Type Φ Height (mm) Width (mm) Thickness (mm) Figure SCT-20 25 75 98 22 SCT-80 25 75 98 22 SCT-150 25 75 98 22 figure-c SCT-200 25 75 98 22 SCT-250 45 107 107 26 SCT-1000 45 107 107 26 figure-d

TYPICAL WIRING External CT Mounting Wiring Diagram C ZKK B A LOAD N 33 34 35 36 37 38 39 40 41 42 43 44 45 46 47 48 49 50 51 52 53 54 V1 V2 V3 VN I11 I12 I21 I22 I31 I32 I41 I42 I51 I52 I61 I62 I71 I72 I81 I82 I91 I92 Voltage Current Cable Auxiliary L N G 14 13 12 A B S 1 2 3 Ethernet NET Digital input (option) V- DI1 DI2 DI3 DI4 DI5 DI6 DI7 DI8 V+ 15 16 17 18 19 20 21 22 23 24 AcuRev 2000 Relay output (option) RO11 RO12 RO21 RO22 RO31 RO32 RO41 RO42 25 26 27 28 29 30 31 32 pulse 2 pulse 1 Demand period Second pulse Display module DISP E C E C E C E C 4 5 6 7 8 9 10 11 Auxiliary 5V Auxiliary Vaux Interface Relay Direct Connection Wiring Diagram Circuit Breaker Load C B A N ZKK 76 73 74 75 VN V1 V2 V3 A1 A2 A3 B1 B2 B3 C1 C2 C3 77 78 79 80 81 82 83 84 85 N Cable Auxiliary L N G 14 13 12 A B S 1 2 3 Ethernet NET Digital input (option) V- DI1 DI2 DI3 DI4 DI5 DI6 DI7 DI8 V+ 15 16 17 18 19 20 21 22 23 24 AcuRev 2000 Relay output (option) RO11 RO12 RO21 RO22 RO31 RO32 RO41 RO42 25 26 27 28 29 30 31 32 pulse 2 pulse 1 Demand period Second pulse Display module DISP E C E C E C E C 4 5 6 7 8 9 10 11 Auxiliary 5V Auxiliary Vaux Interface Relay

SPECIFICATIONS MEASURE Parameter Accuracy ± (%rdg) Range kwh 0.5% 0~999999.9kwh V 0.5% 10~400V I 0.5% 5mA~10000A P 0.5% 4000.0kW Q 0.5% 4000.0kvar S 0.5% 4000.0kVA PF 0.5% -1.000~1.000 Freq 0.2% 45~65Hz Demand 0.5% 4000.0kW Current Demand 0.5% 5mA~10000A Harmonic 1% 0~100% Unbalance 1% 0~100% Meter Running Time 0~999999.9 hours Voltage Input Nominal Full Scale Withstand Input Impedance Metering Frequency PT Burden INPUT Current Input (wired directly or through CT) Through CT Directly Operating Range Burden ORDERING INFORMATION 400Vac L-N,690Vac L-L 1500Vac continuous, 2500Vac, 50/60Hz for 1 minute 2Mohm per phase 45Hz~65Hz <0.2VA See ordering information. Each loop current limit: 20A-80A POWER SUPPLY 100-415Vac, 50-60Hz; 100-300Vdc 10VA Digital Input (DI) Input Style Input Current (MAX) Input Voltage Range Start Voltage Stop Voltage Pulse Frequency (MAX) SOE Resolution Auxiliary Power of DI Output Voltage Rated Power Relay Output (RO) Switching Voltage(MAX) Load Current Set Time Contact Resistance Isolation Voltage Mechanical Life Operation temperature Storage temperature Humidity Altitude IO Dry node 2mA 15~30V 12V 10V 100Hz, 50% Duty cycle 2ms 24VDC 1W 250Vac, 30Vdc 3A 10ms ( MAX) 100mΩ ( MAX) 2500V 1.5x10 7 OPERATING ENVIORNMENT -25 C~ 70 C -40 C~ 85 C 5%~95% non-condensing 3000m MEASUREMENT STANDARD Measurement Standard IEC 62053-22 (Class 0.5s) ANSI C12.20 (Class 0.2s) Environment Standard IEC 60068-2 Safety Standard IEC 61010-1 AcuRev 20 0 Frequency Model option Current option 50 : 50Hz 60 : 60Hz RO DI AcuRev 2010 AcuRev 2020 Ethernet 0RO : None Protocol Display 4RO : 4 Relay output D : Built-in display E : External mountable display MODBUS: Modbus-RTU NC : None NET : Ethernet interface 0DI : No DI 8DI : 8DI (include 15V DI auxiliary ) 1EM : 1EM module (external CT) maximum 9 circuits. 2EM : 2EM modules (external CT) maximum 18 circuits. CT Ordering Information Solid Core design (can not open, install CT first when wiring) CCT-20 (MAX 20A) CCT-80 (MAX 80A) CCT-150 (MAX150A) CCT-200 (MAX200A) Specification: length of secondary line is about 1.5m SCT-20 (MAX 20A) SCT-80 (MAX 80A) SCT-150 (MAX150A) SCT-200 (MAX200A) SCT-250 (MAX250A) SCT-1000 (MAX1000A) 1EM-V: 1EM modules, support 333 mv standard CT, maximum 9 circuits (CT provided by tuser himself). 2EM-V: 2EM modules, support 333 mv standard CT, maximum 18 circuits (CT provided by tuser himself). 1DM20 : 1 DM module (internal CT, wire directly), maximum 9 circuits. 20A-80A current input is allowed. 2DM20 : 2 DM modules (internal CT, wire directly), maximum 18 circuits. 20A-80A current input is allowed. Split Core design CCT- SCT- Accuenergy Corporation Los Angeles-Toronto-Beijing North America Toll Free: 1-877-721-8908 Web: www.accuenergy.com Email: marketing@accuenergy.com Revision Date: Mar., 2013 Document # 2012E1201