Roof Top Unit-50A5C040 TECHNICAL SPECIFICATIONS SUBMITTAL Project Embassy of the Philippines Replacement of (1unit) 40 ton packaged type/ roof top unit Specifications: 1) MODEL No.: 50DN-044-510XC 2) S/N: 2192F01583 Date Friday, July 21, 2016
RTU-1 RTU-1 Project: Embassy of Philippines 07/21/2016 RTU-1 Tag Cover Sheet Technical Specifications-replacement unit Unit Report Performance Report Page 2 of 7
RTU-1 Project: Embassy of Philippines 07/21/2016 TECHNICAL SPECIFICATIONS Objective: The Embassy of the Philippines in Washington DC intends to replace the existing 24- year old CARRIER-40 ton roof top unit (RTU) #1 servicing the First and Second floors including Basement 1 & 2 of the Main Embassy building located at 1600 Massachusetts Ave. NW, Washington DC, USA 20036 Purpose: To replace the roof top unit due to major leak and constant breakdown. All mechanical and electrical parts including R-22 Freon gas refrigerants (banned chemical substance) are no longer available in the market. The unit is now running using two refurbished compressors installed in the year 2011, inefficiently consuming far more electricity, which translated to higher cost, especially during winter and summer months. Scope of Work: Shut down power to defective Carrier unit and make safe for removal; Disconnect electrical and controls from the existing unit; New unit to have Stand-Alone Controls with a factory Scrolling Marquee Display; Disconnect supply and return ductwork and remove ducts back to the existing roof curb; Provide the crane & rigging to remove defective unit and place new unit back on existing roof curb. It is assumed a crane can setup on 17 th and N- Street during normal business hours. The crane service will provide all necessary street closure permits and traffic control. Note: building height-60 ft., crane to set up within 30 ft of building, load s setback on roof edge- 30 ft.; Also remove the supply and return ductwork from the roof and properly dispose of everything; Set up economizer and reconnect the electrical and controls to the new unit, reuse the existing fused safety disconnect; Trap condensate and terminate at roof away from unit; Provide new internally insulated supply and return ducts from existing roof curb to new unit; Seal all connections watertight and apply one coat of alumanation 301rustproofing to all new ductwork; The new package unit, voltage 208/230, 3-phase will have a capacity of 40 tons of cooling which matches existing. The largest electric heat available for this unit is 54 KW which is also included. New unit includes Differential Enthalpy Ultra Low Leakage Economizer, Variable Frequency Drive on the Supply Fan, Premium Efficiency 25 HP Motor, Outdoor or Return Air RH Sensor, AI/Cu Condenser, AI/Cu Evaporator Coils; All interface control wiring connecting to existing controls and to automatic transfer control (ATC) for the new unit is included; Perform a check, test and startup of new unit to verify proper operation; Provide all O & M manuals; close out documents to the customer and demonstration of new system. Page 3 of 7
Unit Report For RTU-1 Unit R eport Unit Parameters Unit Size:... 040 (40 Tons) Volts-Phase-Hertz:... 208-3-60 Supply / Return:... Horizontal/Horizontal Configuration:... VAV Evaporator Coil Type:... Standard Heating Capacity:... High Electric Heat 4 inch filter:...selected Shipping Dimensions Unit Length:... 17' 11'' Unit Width:... 7' 10'' Unit Height:... 6' 1'' :... Unit Shipping Weight:... 5188 lb ***Weights and Dimensions are approximate. Weight does not include curbs and accessories. Approximate dimensions are provided primarily for shipping purposes. For exact dimensions refer to certified drawings. ** Shipping Weight does not include extended leadtime options' weight. Controls Application Type:... VAV Control Expansion Module:...Selected Plugged Filter Indicator:...Selected Exhaust/Economizer Exhaust/Economizer:... No Exhaust Supply Fan Supply Fan Type:... Forward Curve Supply Fan Motor HP:... 20 HP Condenser Coil Cond. Coil Fin Coating:... MCHX Cond, Al/Cu Evap Hot Gas Bypass:...Selected Mixed-Air and Outdoor Filters Mixed-Air Filter:... 4 in. MERV 7 Pleated :... (5) 20 x 20 x 4, (5) 20 x 24 x 4 Outdoor Filter:... Economizer Filter: (8) 16 x 25 x 2, (4) 20 x 25 x 2 Warranty Information First Year - Parts Only (Standard) Start-up, First Unit Complete Unit- 1st Year Labor Compressor Years - 5 yrs.- Parts Only Ordering Information Accessories Part Number Description Quantity Rooftop Unit -50A5C040 (50KW, 40 ton) 1 Base Unit Differential Enthalpy Ultra Low Leak Economizer 115v Convenience Outlet: Field Wired 4" MERV 7 Pleated Filters Low Sound Condenser Fans Motormaster V Low Ambient High Electric Heat Premium Efficiency 20 HP w/ VFD Bypass MCHX Cond, Al/Cu Evap w/ HGBP Plugged Filter Indicator and Controls Expansion Board Domestic w/bacnet Communication Accessory Part # Description Quantity Outdoor or Return Air RH Sensor 2 Thermostat 1 Page 4 of 7
Performance Summary For RTU-1 Certified Dr aw Unit Refrigerant:... R410A EER (ARI 360):... 10.5 IEER:... 13.2 Shipping Dimensions Unit Length:... 17' 11'' Unit Width:... 7' 10'' Unit Height:... 6' 1'' Unit Shipping Weight:... 5188 lb Unit Heating Type:... E Supply/Return:... Horizontal/Horizontal Application Type:... VAV Voltage:... 208-3-60 Cooling Airflow:... 16000 CFM Altitude:... 0 ft Cond. Ent. Air Temp:... 95.0 F Ent. Air Dry Bulb:... 80.0 F Ent. Air Wet Bulb:... 67.0 F Ent. Air Enthalpy:... 31.44 BTU/lb Lvg. Air Dry Bulb:... 58.0 F Lvg. Air Wet Bulb:... 57.5 F Lvg. Air Enthalpy:... 24.71 BTU/lb Gross Cooling Capacity:... 484.70 MBH Gross Sensible Clg. Cap:... 380.40 MBH Compressor Power:... 33.2 kw Coil Bypass Factor:... 0.07 Part Load(%) Operation Standard Capacity Steps:... 14,25,50,75,100 Electric Heating Data: Heating Airflow:... 16000 CFM Heating Ent. Air Temp:... 68.0 F Heating Lvg. Air Temp:... 78.7 F Heating Capacity:... 54.0 kw Supply Fan Information: Ext.Static Pressure:... 1.30 in wg 4 in. Filter Loss:... 0.04 in wg Selection Static Pressure:... 1.34 in wg Supply Fan RPM:... 1057 * Supply Fan BHP:... 18.92 BHP Supply Fan Motor HP:... 20 HP *Field supplied and installed sheave package may be required* Electrical Data Compressor #A1 RLA:... 28.2 Compressor #A1 LRA:... 239 Compressor #A2 RLA:... 28.2 Compressor #A2 LRA:... 239 Compressor #B1 RLA:... 28.2 Compressor #B1 LRA:... 239 Compressor #B2 RLA:... 28.2 Compressor #B2 LRA:... 239 Actual Electric Heater kw:... 54 Electric Heater FLA:... 150.1 Indoor Fan Motor HP:... 20 Indoor Fan Motor FLA:... 59.4 Condenser Fan Motor Qty:... 4 Page 5 of 7
Performance Summary For RTU-1 Condenser Fan Motor FLA (ea):... 6.5 Power Supply MCA:... 224 Power Supply MOCP (Fuse or HACR):... 250 Electrical Convenience Outlet:... None Acoustic Information Discharge, Lw Inlet, Lw Outdoor, Lw 63 Hz 95.5 92.4 53.1 125 Hz 89.6 78.3 76.2 250 Hz 85.8 73.5 83.1 500 Hz 89.9 70.4 87.6 1000 Hz 92.4 71.8 88.1 2000 Hz 90.3 67.1 83.7 4000 Hz 86.0 63.4 79.4 8000 Hz 79.3 59.1 67.9 Discharge / Inlet Duct Sound Power test data rated in accordance with the AHRI 260 Standard Calculation methods used in this program are patterned after the ASHRAE (American Society of Heating, Refrigeration and Air-Conditioning Engineers) Guide; other ASHRAE Publications and the AHRI Acoustical Standards. While a very significant effort has been made to insure the technical accuracy of this program, it is assumed that the user is knowledgeable in the art of system sound estimation and is aware of the tolerances involved in real world acoustical estimation. This program makes certain assumptions as to the dominant sound sources and sound paths which may not always be appropriate to the real system being estimated. Because of this, no assurances can be offered that this software will always generate an accurate sound prediction from user supplied input data. If in doubt about the estimation of expected sound levels in a space, an Acoustical Engineer or a person with sound prediction expertise should be consulted. Advanced Acoustics Advanced Accoustics Parameters 1. Unit height above ground:... 30.0 ft 2. Horizontal distance from unit to receiver:... 50.0 ft 3. Receiver height above ground:... 5.7 ft Detailed Acoustics Information Octave Band Center Freq. Hz 63 125 250 500 1k 2k 4k 8k Overall A 53.1 76.2 83.1 87.6 88.1 83.7 79.4 67.9 92.5 Lw B 26.9 60.1 74.5 84.4 88.1 84.9 80.4 66.8 91.4 LwA C 19.8 42.9 49.8 54.3 54.8 50.4 46.1 34.6 59.2 Lp D -6.4 26.8 41.2 51.1 54.8 51.6 47.1 33.5 58.0 LpA Legend A Sound Power Levels at Unit's Acoustic Center, Lw B A-Weighted Sound Power Levels at Unit's Acoustic Center, LwA C Sound Pressure Levels at Specific Distance from Unit, Lp D A-Weighted Sound Pressure Levels at Specific Distance from Unit, LpA Page 6 of 7
Performance Summary For RTU-1 S t a t ic P r e s s u r e ( in. w g. 4 3 2 1 S u p p l y S y s t e m Cu r v e 1 0 0 0 R P M1 1 0 0 RM P MS E 1 2 0 0 R P M 1 3 0 0 R P M 9 0 0 R P M 8 0 0 R P M 7 0 0 R P M S C 6 0 0 R P M 3 0. 0 0 B H P R P 2 5. 0 0 B H P 5 0 0 R P M 2 0. 0 0 B H P 1 5. 0 0 B H P 4 0 0 R P M 3 0 0 R P M 0 0 2 4 6 8 1 0 1 2 1 4 1 6 1 8 2 0 2 2 A ir f lo w ( C F M - t h o u s a n d s ) = 1 0 5 7 B H P = 1 8. 9 2 M a x i m u m R P M = 1 3 0 0 M a x i m u m H P = 2 S C - S y s t e m C u r v e R P - R a t e d P o i n t Page 7 of 7