Packaged Gas/Electric Rooftop Units
|
|
|
- Dwain Rice
- 9 years ago
- Views:
Transcription
1 Packaged Gas/Electric Rooftop Units Voyager 12½ 25 Tons 60 Hz December 2003
2 Introduction Voyager TM... a proven performer built to provide ultimate indoor comfort. Voyager continues to provide the highest standards in quality and reliability, comfort, ease of service, and the performance of Trane light commercial products. For contractors, Voyager saves time and money, increasing their ability to win jobs. It meets engineer s design criteria and offers solutions to cover many special applications. And, of course, Voyager carries the Trane reputation for excellence, quality and reliability American Standard Inc. All rights reserved
3 Contents Introduction Features and Benefits Application Considerations Selection Procedure Model Number Description General Data Performance Data Cooling Performance Fan Performance Heat Performance Controls Electric Power Dimension and Weights Mechanical Specifications
4 Features and Benefits Weather Tight Top and Cabinet Voyager units incorporate either a one piece top or the Trane-Tite-Top (T 3 ). Each part of the top (either two or three pieces) overlaps in such a way that water cannot leak into the unit. These overlapped edges are gasketed and sealed to ensure superior water integrity. Quick- Access (12½-25 tons) panels reduce the number of possible water entry points. For added water integrity, Voyager has a raised 1 1 / 8 " lip around the supply and return of the downflow units to prevent water from blowing into the ductwork. Quality And Reliability Testing The fan and idler arm assembly designs have been tested to over 300,000 cycles each. Our combined cycle testing is now over 7,000,000 cycles. All of Voyager s designs were rigorously rain tested at the factory to ensure water integrity. Actual shipping tests were performed to determine packaging requirements. Units were test shipped around the country to determine the best packaging. Factory shake and drop tests were used as part of the package design process to help assure that the unit arrives at the job site in top condition. Rigging tests include lifting a unit into the air and letting it drop one foot, assuring that the lifting lugs and rails hold up under stress. We perform a 100% coil leak test at the factory. The evaporator and condenser coils are leak tested at 200 psig and pressure tested to 450 psig. All parts are inspected at the point of final assembly. Sub-standard parts are identified and rejected immediately. Every unit receives a 100% unit run test before leaving the production line to make sure it lives up to rigorous Trane requirements. We test designs at our factory not on our customers! Conversionless Units The dedicated design units (either downflow or horizontal) require no panel removal or alteration time to convert in the field a major cost savings during installation. Horizontal units come complete with duct flanges so the contractor doesn t have to field fabricate them. These duct flanges are a time and cost saver. U-shaped Airflow U-shaped airflow allows for improved static capabilities. 4
5 Features and Benefits ReliaTel Several years ago, Trane was the first to introduce ReliaTel into the Light Commercial Market. That design, along with immeasurable experience, has provided the technology for Trane s second-generation ReliaTel microprocessor controls. ReliaTel: Provides unit control for heating, cooling, and ventilating by utilizing input from sensors that measure outdoor and indoor temperature. Improves quality and reliability through the use of time-tested microprocessor controls and logic. Prevents the unit from short cycling, considerably improving compressor life. Ensures that the compressor will run for a specific amount of time, which allows oil to return for better lubrication, enhancing the reliability of the compressor. Reduces the number of components required to operate the unit, thereby reducing possibilities for component failure. Eliminates the need for field-installed components with its built-in anti-shortcycle timer, time delay relay and minimum on time controls. These controls are factory tested to assure proper operation. Requires no special tools to run the unit through its paces during testing. Simply place a jumper between Test 1 and Test 2 terminals on the Low Voltage Terminal Board and the unit will stage through its operational steps. The unit automatically returns control after 60 minutes to the zone sensor after stepping through the test mode a single time, even if the jumper is left on the unit. As long as the unit has power and the LED is lit, the ReliaTel is operational. The light indicates that the ReliaTel is functioning properly. Features expanded diagnostic capabilities when used with Trane s Integrated Comfort TM Systems. As an energy benefit, softens electrical spikes by staging on fans, compressors and heaters. The Intelligent Fallback or Adaptive Control is a benefit to the building occupant. If a component goes astray, the unit will continue to operate at predetermined temperature set points. Intelligent Anticipation is a standard feature of the ReliaTel. Functioning constantly, the ReliaTel and zone sensors work together in harmony, to provide tight comfort control. 5
6 Features and Benefits Drum and Tube Heat Exchanger The heat exchanger is manufactured using aluminized steel with stainless steel components for maximum durability. The requirement for cycle testing of heat exchangers is 10,000 cycles by ANSI Z This is the standard required by both UL and AGA for cycle test requirements. Trane requires the design to be tested to 2½ times this current standard. The drum and tube design has been tested and passed over 150,000 cycles, which is over 15 times the current ANSI cycling requirements. The negative pressure gas valve will not allow gas flow unless the combustion blower is operating. This is one of our unique safety features. The forced combustion blower supplies pre-mixed fuel through a single stainless steel burner screen into a sealed drum where ignition takes place. It is more reliable to operate and maintain than a multiple burner system. The hot surface ignitor is a gas ignition device which doubles as a safety device utilizing a continuous test to prove the flame. The design is cycle tested at the factory for quality and reliability. Our gas/electric rooftops exceed all California seasonal efficiency requirements and perform even better than the California NOx emission requirements. Forced Combustion Blower Negative Pressure Gas Valve Hot Surface Ignitor Drum and Tube Heat Exchanger 6
7 Features and Benefits Easy Access Low Voltage Terminal Board Voyager s Low Voltage Terminal Board is external to the electrical control cabinet. It is extremely easy to locate and attach the thermostat wire. This is another cost and time saving installation feature. Standardized Components Components are placed in the same location on all Voyager units. Familiarize yourself with one Voyager and you are familiar with every Voyager. ReliaTel can fit all Voyager Packaged Gas/Electrics, Cooling with Electric Heat, and Heat Pump models. This provides standardization of parts for the contractors. Less money is tied up in inventory using the ReliaTel. Contractors/owners can stock fewer parts due to standardized components throughout Voyager units. Single Side Service Single side service is standard on all Voyager 12½-25 tons. Quick-Access Panels On The 12½-25 Tons Remove three or fewer screws for access to the standardized internal components and wiring. Low Voltage Connections The wiring of the low voltage connections to the unit and the zone sensors is as simple as 1-1, 2-2, and 3-3. This simplified system makes it easy for the installer to wire. Colored And Numbered Wiring You save time and money tracing wires and diagnosing the unit. VariTrac When Trane s changeover VAV System for light commercial applications is coupled with Voyager, it provides the latest in technological advances for comfort management systems and can allow thermostat control in every zone served by VariTrac. VariTrac Quick-Adjust Idler Arm With the Quick-Adjust Idler Arm, the belt and sheaves on all 12½-25 tons can be quickly adjusted without moving the mounted fan motor. The result is a major savings in time and money. Patent-Pending Condenser Coil Voyager boasts a patent-pending condenser coil, permanently gapped for easy cleaning. 7
8 Features and Benefits Capacity Modulation We offer low, medium, and high heat models. 12½-25 tons medium and high heat models provide 2-stage gas heating capabilities. 12½-25 tons standard efficiency provide 2-stage gas heating on low heat models. In cooling, the 12½-25 tons have dual compressors. Compressors Voyager contains the best compressor technology available to achieve the highest possible performance. The dual compressor models are outstanding for humidity control, light load cooling conditions and system back-up applications. Low Ambient Cooling All Voyager 12½-25 tons have cooling capabilities down to 0 F as standard. Power Exhaust Option This option is available on the 12½-25 tons downflow units. It provides exhaust of the return air, when using a downflow economizer, to maintain proper building pressurization. Great for relieving most building overpressurization problems. CO 2 Sensing The CO 2 sensor has the ability to monitor space occupancy levels within the building by measuring the parts per million of CO 2 (Carbon Dioxide) in the air. As the CO 2 levels increase, the outside air damper modulates to meet the CO 2 space ventilation requirements. The CO 2 sensor kit is available as a field installed accessory. Ventilation Override Accessory With the Ventilation Override Accessory installed, the unit can be set to transition to up to 3 different pre-programmed sequences for Smoke Purge, Pressurization, and Exhaust. The transition occurs when a binary input on the RTOM is closed (shorted). This would typically be a hard wired relay output from a smoke detector of fire control panel. The ventilation override kit is available as a field installed accessory. Flexible Applications Only two roof curbs for the entire Voyager line simplifies curb selection. Airflow is outstanding. The Voyager can replace an older machine with old ductwork and, in many cases, improve the comfort through better air distribution. A wide variety of Factory Installed Options (FIOPs) are available. Trane Communication Interface (TCI) Available factory or field installed. This module when applied with the Micro easily interfaces with Trane s Integrated Comfort TM System. Single Point Power A single electrical connection powers the unit. Sloped Drain Pans Standard on every unit. Downflow And Horizontal Economizers The economizers come with three control options dry bulb is standard, enthalpy and differential enthalpy are optional. High Static Drive Accessory Available on many models, this high static drive accessory extends the capability of the standard motor. Avoid expensive motors and operating costs by installing this optimized sheave accessory. Factory Built Roof Curbs Available for the downflow units. Zone Sensors Available in programmable, automatic and manual styles. The following options round-out the complete line of Voyager accessories: 0-25% manual outside air hood Motorized outside air for 12½ - 25 tons LP gas conversion kit One Of Our Finest Assets: Trane Sales Representatives are a Support group that can assist you with: Product Application Service Training Special Applications Specifications Computer Programs and much more Voyager has the features and benefits that make it first class in the light commercial rooftop market. Designed with input from field contractors and engineers, its U-shaped airflow performance is outstanding. If all of your customers knew about Voyager, all would insist on it. ReliaTel 8
9 Application Considerations Application of this product should be within the cataloged airflow and cooling considerations. Low Ambient Cooling This Voyager line features, as standard, low ambient cooling down to 0 F. Contact your local Trane Representative for more assistance with low ambient cooling applications. Barometric Relief This product offers an optional barometric relief damper included in the downflow economizer accessory. This accessory consists of gravity dampers which open with increased pressure. As the building air pressure increases, the pressure in the unit return air section also increases, opening the dampers and relieving the conditioned space. Heating Operation The heat exchanger is manufactured with aluminized steel. To prevent condensation within the heat exchanger, do not exceed 50% outside air. NOTE: THE EFFECTIVENESS OF BAROMETRIC RELIEF DAMPER DURING ECONOMIZING OPERATION IS SYSTEM RELATED. PRESSURE DROP OF THE RETURN AIR SYSTEM SHOULD BE CONSIDERED TO CONTROL BUILDING PRESSURIZATION. Power Exhaust Accessory The power exhaust accessory is available on all 12½-25 tons downflow units. This accessory can be field installed and will assist in relieving building pressurization. Condensate Trap The evaporator is a draw-thru configuration. A trap must be field provided prior to start-up on the cooling cycle. Clearance Requirements The recommended clearances identified with unit dimensions should be maintained to assure adequate serviceability, maximum capacity and peak operating efficiency. Actual clearances which appear inadequate should be reviewed with the local Trane sales personnel. Unit Pitch These units have sloped condensate drain pans. Units must be installed level; any unit slope must be toward access side of unit. 9
10 Selection Procedures Cooling Capacity Step 1 Calculate the building s total and sensible cooling loads at design conditions. Use the American Standard calculation form or any other standard accepted method. Example: The following are the building requirements: a. Electrical Characteristics: 460/60/3 b. Summer Design Conditions: Entering Evaporator Coil: 80 DB/ 67 WB Outdoor Ambient: 95 DB c. Total Cooling Load: 220 MBh d. Sensible Cooling Load: 140 MBh e. Airflow: 8000 cfm External Static Pressure: in wg f. downflow configuration g. economizer Step 2 As a starting point, a rough determination must be made of the size of the unit. The final selection will be made after examining the performance at the given conditions. Divide the total cooling load by the nominal BTUH per ton (12 MBh per ton); then round up to the nearest unit size. 220 MBh / 12 MBh = (approx 20 tons). Step 3 Examine gross capacity: Table PD-4 shows that a YC*240B3 has a gross cooling capacity of 246 MBh and 176 MBh sensible capacity at 95 DB ambient and 8000 cfm with 80 DB/ 67 WB air entering the evaporator. To Find Capacity at Intermiediate Conditions Font in the Table When the design conditions are between two numbers that are in the capacity table, interpolation is required to approximate the capacity. Note: Extrapolation outside of the table conditions is not recommended. Step 4 Verify that there will be enough capacity by determining net capacity. In order to select the correct unit which meets the building's requirements, the fan motor heat must be deducted from the gross cooling capacity. The amount of heat that the fan motor generates is dependent on the effort by the motor - cfm and static pressure. To determine the total unit static pressure add the external static pressure to the additional static created by the added features: External Static (duct system) 0.45 wg Standard Filter 2 in. (from Table PD-27) 0.11 g Economizer (100% Return Air from Table PD-27) 0.05 wg Total static pressure 0.61 Note: The Evaporator Fan Performance Table PD-14 has already accounted for the pressure drop for standard filters and wet coils (see note below Table PD-14). Therefore the actual total static pressure is = 0.50 wg. With 8000 cfm and 0.50 inches external static pressure. Table PD-14 shows 3.96 bhp for this model. At these conditions, the note below the table gives a formula to calculate Fan Motor Heat: 3.15 X bhp = MBh 3.15 X 3.96 = MBh. Subtracting the fan motor heat from the gross cooling capacity of the unit: Net Total Cooling Capacity = 246 MBh = MBh Net Sensible Cooling Capacity = 176 MBh = MBh. Since the Net Total Cooling Capacity meets the cooling load requirements of 220 MBh, we are satisfied with this selection. Heating Capacity Step 1 Calculate the building heating load using the American Standard calculation form or other standard accepted method. Step 2 Size the system heating capacity to match the calculated building heating load. The following are building heating requirements: a. Total heating load of 165 MBh b cfm c. Fuel - Natural gas For the YC*240B3, there are two heating capacities available, 250 MBh and 400 MBh input models shown in Table PD-26. The output capacities of these furnaces are 175 MBh and 300 MBh respectively. The low heat model with 175 MBh best matches the building requirements, indicating a YC*240B3 should be selected. Air Delivery Selection External static pressure drop through the air distribution system has been calculated to be 0.50 inches of water. Enter Table PD-14 for a YC*240B3 at 8000 cfm and 0.50 static pressure. The standard motor at high speed will give the desired airflow. Accessory Selection Select accessories needed to accommodate the application. 10
11 Model Number Description Packaged Gas/Electric Unit Typical Model Nomenclature Y C D C 3 L 0 A A Digits 1, 2 - Product Type YC = Packaged Gas/Electric YF = With Factory Installed Options Digit 3 - Airflow Configuration D = Downflow H = Horizontal Digits 4, 5, 6 - Nominal Gross Cooling Capacity (MBh) 150 = 12½ Ton Standard Efficiency 151 = 12½ Ton High Efficiency 180 = 15 Ton Standard Efficiency 181 = 15 Ton High Efficiency 210 = 17½ Ton Standard Efficiency 211 = 17½ Ton High Efficiency 240 = 20 Ton Standard Efficiency 241 = 20 Ton High Efficiency 300 = 25 Ton Standard Efficiency 301 = 25 Ton High Efficiency Digit 7- Major Development Sequence Digit 8 - Electrical Characteristics 3 = /60/3 4 = 460/60/3 W = 575/60/3 K = 380/60/3 Digit 9 - Heating Capacity L = Low Heat M = Medium Heat H = High Heat Digit 10 - Factory-Installed Options 0 = Packed Stock, No Options A = Downflow Economizer B = Oversized Motor C = Downflow Economizer and Oversized Motor F = Trane Communications Interface (TCI) G = Downflow Economizer and TCI H = TXV/Face-Split Evaporator J = Oversized Motor and TXV/Face-Split Evaporator K = Downflow Economizer, Oversized Motor, and TXV/Face-Split Evaporator L = Downflow Economizer and TXV/Face- Split Evaporator Digit 11- Minor Design Sequence Digit 12- Service Digit 11
12 General Data (12½, 15 Ton) Standard Efficiency Table GD-1 General Data 12½ Ton Downflow and Horizontal Units 15 Ton Downflow and Horizontal Units YC*150D3,D4,DWL, DK YC*150D3,D4,DWH, DK YC*180B3,B4,BWL, BK YC*180B3,B4,BWH, BK Cooling Performance 1 Gross Cooling Capacity 150, ,000 EER 2 (Downflow/Horizontal) Nominal CFM / ARI Rated CFM 5,000/4,400 6,000/5,300 ARI Net Cooling Capacity 142, ,000 Integrated Part Load Value System Power (KW) Heating Performance 4 Heating Models Low High Low High Heating Input (Btuh) 150, , , ,000 1st Stage 100, , , ,000 Heating Output (Btuh) 122, , , ,000 1st Stage 81, , , ,000 AFUE (%) 5 (Downflow/Horizontal) / / / 79.1 Steady State Efficiency (%) No. Burners 1 1 No. Stages 2 2 Gas Supply Pressure (in. w.c) Natural or LP (minimum/maximum) 2.5/ /14.0 Gas Connection Pipe Size (in.) 1/2 1/2 3/4 Compressor No./Type 2/Climatuff Scroll 2/Trane 3-D Scroll/Climatuff Scroll Sound Rating (BELS) Outdoor Coil - Type Hi-Performance Hi-Performance Tube Size (in.) OD Face Area (sq ft) Rows/FPI 2/16 3/16 Indoor Coil - Type Hi-Performance Hi-Performance Tube Size (in.) Face Area (sq ft) Rows/FPI 2/15 2/15 Refrigerant Control Short Orifice Short Orifice Drain Connection No./Size (in.) 1/1.00 NPT 1/1.00 NPT Outdoor Fan - Type Propeller Propeller No. Used/Diameter (in.) 2/26 2/26 Drive Type/No. Speeds Direct/1 Direct/1 CFM 10,600 10,200 No. Motors/HP 2/.5 2/.50 Motor RPM 1,100 1,100 Indoor Fan - Type FC Centrifugal FC Centrifugal No. Used/Diameter (in.) 1/15 X 15 1/15 X 15 Drive Type/No. Speeds Belt/1 Belt/1 No. Motors 1 1 Motor HP (Standard/Oversized) 9 3.0/ /5.0 Motor RPM (Standard/Oversized) / /3450 Motor Frame Size (Standard/Oversized) 9 145T/145T 145T/145T Filters - Type Furnished Throwaway 8 Throwaway 8 (No.) Size Recommended Downflow (2) 20 X 20 X 2, (4) 20 X 25 X 2 (2) 20 X 20 X 2, (4) 20 X 25 X 2 Horizontal (2) 20 X 20 X 2, (4) 20 X 25 X 2 (2) 20 X 20 X 2, (4) 20 X 25 X 2 Refrigerant Charge (Lbs of R-22) 7 9.3/9.4/Circuit 17.5/9.5/ Circuit NOTES 1. Cooling Performance is rated at 95 F ambient, 80 F entering dry bulb, 67 F entering wet bulb. Gross capacity does not include the effect of fan motor heat. ARI capacity is net and includes the effect of fan motor heat. Units are suitable for operation to ±20% of nominal cfm. Certified in accordance with the unitary large equipment certification program, which is based on ARI Standard 340/ EER is rated at ARI conditions and in accordance with ARI Standard 210/240 or Integrated Part Load Value is rated in accordance with ARI Standard 210/240 or 360. Units are rated at 80 F ambient, 80 F entering dry bulb, and 67 F entering wet bulb at ARI rated cfm. 4. Heating Performance limit settings and rating data were established and approved under laboratory test conditions using American National Standards Institute standards. Ratings shown are for elevations up to 2000 feet. For elevations above 2000 feet, ratings should be reduced at the rate of 4% for each 1000 feet above sea level. 5. AFUE is rated in accordance with DOE test procedures. 6. Sound Rating shown is tested in accordance with ARI Standard 270 or Refrigerant charge is an approximate value. For a more precise value, see unit nameplate and service instructions. 8. An optional 2 inch pleated filter is also available. 9. For 380V/60Hz units, the oversized mtoor is used as the standard motor. Refer to oversized motor data. *Indicates both downflow and horizontal units. 12
13 General Data (17½, 20 Ton) Standard Efficiency Table GD-2 General Data 17½ Ton Downflow and Horizontal Units 20 Ton Downflow and Horizontal Units YC*210C3,C4,CWL, CK YC*210C3,C4,CWH, CK YC*240B3,B4,BWL, BK YC*240B3,B4,BWH, BK Cooling Performance 1 Gross Cooling Capacity 210, ,000 EER Nominal CFM / ARI Rated CFM 7,000/5,800 8,000/7,000 ARI Net Cooling Capacity 196, ,000 Integrated Part Load Value System Power (KW) Heating Performance 4 Heating Models Low High Low High Heating Input (Btuh) 250, , , ,000 1st Stage 175, , , ,000 Heating Output (Btuh) 203, , , ,000 1st Stage 142, , , ,000 AFUE (%) 5 Downflow/Horizontal 80.7 / / / / 79.7 Steady State Efficiency (%) No. Burners 1 1 No. Stages 2 2 Gas Supply Pressure (in. w.c) Natural or LP (minimum/maximum) 2.5/ /14.0 Gas Connection Pipe Size (in.) 1/2 3/4 1/2 3/4 Compressor No./Type 2/Trane 3-D Scroll 2/Trane 3-D Scroll Sound Rating (BELS) Outdoor Coil - Type Hi-Performance Hi-Performance Tube Size (in.) OD Face Area (sq ft) Rows/FPI 3/16 3/16 Indoor Coil - Type Hi-Performance Hi-Performance Tube Size (in.) Face Area (sq ft) Rows/FPI 4/15 2/15 Refrigerant Control Short Orifice Short Orifice Drain Connection No./Size (in.) 1/1.00 NPT 1/1.00 NPT Outdoor Fan - Type Propeller Propeller No. Used/Diameter (in.) 2/26 2/26 Drive Type/No. Speeds Direct/1 Direct/1 CFM 13,400 14,600 No. Motors/HP 2/1.0 2/1.0 Motor RPM 1,125 1,125 Indoor Fan - Type FC Centrifugal FC Centrifugal No. Used/Diameter (in.) 1/15 X 15 1/18 X 18 Drive Type/No. Speeds Belt/1 Belt/1 No. Motors 1 1 Motor HP (Standard/Oversized) 9 5.0/ /7.5 Motor RPM (Standard) / /3470 Motor Frame Size (Standard/Oversized) 9 56HZ/184T 145T/184T Filters - Type Furnished 8 Throwaway Throwaway (No.) Size Recommended Downflow (2) 20 X 20 X 2/(4) 20 X 25 X 2) (4) 20 X 20 X 2/(4) 20 X 25 X 2 Horizontal (2) 20 X 20 X 2/(4) 20 X 25 X 2) (8) 20 X 25 X 2 Refrigerant Charge (Lbs of R-22) 7 Downflow 21.0/14.3/Circuit 18.9/21.0/Circuit Horizontal 21.5/14.5/Circuit NOTES 1. Cooling Performance is rated at 95 F ambient, 80 F entering dry bulb, 67 F entering wet bulb. Gross capacity does not include the effect of fan motor heat. ARI capacity is net and includes the effect of fan motor heat. Units are suitable for operation to ±20% of nominal cfm. Certified in accordance with the Unitary Large Equipment certification program, which is based on ARI Standard 340/ EER is rated at ARI conditions and in accordance with ARI Standard 210/240 or Integrated Part Load Value is rated in accordance with ARI Standard 210/240 or 360. Units are rated at 80 F ambient, 80 F entering dry bulb, and 67 F entering wet bulb at ARI rated cfm. 4. Heating Performance limit settings and rating data were established and approved under laboratory test conditions using American National Standards Institute standards. Ratings shown are for elevations up to 2000 feet. For elevations above 2000 feet, ratings should be reduced at the rate of 4% for each 1000 feet above sea level. 5. AFUE is rated in accordance with DOE test procedures. 6. Sound Rating shown is tested in accordance with ARI Standard 270 or Refrigerant charge is an approximate value. For a more precise value, see unit nameplate and service instructions. 8. An optional 2 inch pleated filter is also available. 9. For 380V/60Hz units, the oversized mtoor is used as the standard motor. Refer to oversized motor data. *Indicates both downflow and horizontal units. 13
14 General Data (25 Ton) Standard Efficiency Table GD-3 General Data 25 Ton Downflow and Horizontal Units YC*300B3,B4,BWL, BK YC*300B3,B4,BWH, BK Cooling Performance 1 Gross Cooling Capacity 290,000 EER Nominal CFM / ARI Rated CFM 10,000 / 8,750 ARI Net Cooling Capacity 272,000 Integrated Part Load Value System Power (KW) Heating Performance 4 Heating Models Low High Heating Input (Btuh) 250, ,000 1st Stage 175, ,000 Heating Output (Btuh) 203, ,000 1st Stage 142, ,000 AFUE (%) 5 Downflow/Horizontal 80.2/ /79.7 Steady State Efficiency (%) 81.4/ /81.0 No. Burners 1 No. Stages 2 Gas Supply Pressure (in. w.c) Natural or LP (minimum/maximum) 2.5/14.0 Gas Connection Pipe Size (in.) 1/2 3/4 Compressor No./Type 2/Trane 3-D Scroll Sound Rating (BELS) Outdoor Coil - Type Hi-Performance Tube Size (in.) OD.375 Face Area (sq ft) Rows/FPI 2/16 Indoor Coil - Type Hi-Performance Tube Size (in.).375 Face Area (sq ft) Rows/FPI 3/15 Refrigerant Control Short Orifice Drain Connection No./Size (in.) 1/1.00 NPT Outdoor Fan - Type Propeller No. Used/Diameter (in.) 2/28 Drive Type/No. Speeds Direct/1 CFM 16,700 No. Motors/HP 2/1.0 Motor RPM 1,125 Indoor Fan - Type FC Centrifugal No. Used/Diameter (in.) 1/18 X 18 Drive Type/No. Speeds Belt/1 No. Motors 1 Motor HP (Standard/Oversized) 9 7.5/NA Motor RPM (Standard/Oversized) /NA Motor Frame Size (Standard/Oversized) 9 184T/NA Filters - Type Furnished 8 Throwaway (No.) Size Recommended Downflow (4) 20 X 20 X 2(4) 20 X 25 X 2 Horizontal (8) 20 X 25 X 2 Refrigerant Charge (Lbs of R-22) 7 Downflow Horizontal 17.0/Circuit NOTES 1. Cooling Performance is rated at 95 F ambient, 80 F entering dry bulb, 67 F entering wet bulb. Gross capacity does not include the effect of fan motor heat. ARI capacity is net and includes the effect of fan motor heat. Units are suitable for operation to ±20% of nominal cfm. YC*300B model ratings shown are tested in accordance with ARI Standard 340/ EER is rated at ARI conditions and in accordance with ARI Standard 210/240 or Integrated Part Load Value is rated in accordance with ARI Standard 210/240 or 360. Units are rated at 80 F ambient, 80 F entering dry bulb, and 67 F entering wet bulb at ARI rated cfm. 4. Heating Performance limit settings and rating data were established and approved under laboratory test conditions using American National Standards Institute standards. Ratings shown are for elevations up to 2000 feet. For elevations above 2000 feet, ratings should be reduced at the rate of 4% for each 1000 feet above sea level. 5. AFUE is rated in accordance with DOE test procedures. 6. Sound Rating shown is tested in accordance with ARI Standard 270 or Refrigerant charge is an approximate value. For a more precise value, see unit nameplate and service instructions. 8. An optional 2 inch pleated filter is also available. 9. For 380V/60Hz units, the oversized mtoor is used as the standard motor. Refer to oversized motor data. 14 *Indicates both downflow and horizontal units.
15 General Data (12½, 15 Ton) High Efficiency Table GD-4 General Data 12½ Ton Downflow and Horizontal Units 15 Ton Downflow and Horizontal Units YC*151C3,C4,CW YC*181C3,C4,CW Cooling Performance 1 Gross Cooling Capacity 154, ,000 EER Nominal CFM / ARI Rated CFM 5,000 / ,000 / 5,300 ARI Net Cooling Capacity 146, ,000 Integrated Part Load Value System Power (KW) Heating Performance 4 Heating Models Low High Low High Heating Input (Btuh) 150, , , ,000 1st Stage 100, , , ,000 Heating Output (Btuh) 122, , , ,000 1st Stage 81, , , ,000 AFUE% 5 (Downflow/Horizontal) 81.0 / / / / 79.1 Steady State Efficiency (%) No. Burners No. Stages Gas Supply Pressure (in. w.c) Natural or LP (minimum/maximum) 2.5/ /14.0 Gas Connection Pipe Size (in.) 1/2 1/2 1/2 3/4 Compressor No./Type 2/Copeland Scroll 2/Trane 3-D Scroll/Climatuff Scroll Sound Rating (BELS) Outdoor Coil - Type Hi-Performance Hi-Performance Tube Size (in.) OD Face Area (sq ft) Rows/FPI 3/16 3/16 Indoor Coil - Type Hi-Performance Hi-Performance Tube Size (in.) Face Area (sq ft) Rows/FPI 3/15 3/15 Refrigerant Control Short Orifice 10 Short Orifice 9 Drain Connection No./Size (in.) 1/1.0 NPT 1/1.0 NPT Outdoor Fan - Type Propeller Propeller No. Used/Diameter (in.) 2/26 2/26 Drive Type/No. Speeds Direct/1 Direct/1 CFM 10,400 11,000 No. Motors/HP 2/.50 2/.50 Motor RPM Indoor Fan - Type FC Centrifugal FC Centrifugal No. Used/Diameter (in.) 1/ 15 x 15 1/18 x 18 Drive Type/No. Speeds Belt/1 Belt/1 No. Motors 1 1 Motor HP (Standard/Oversized) 3.0/ /5.0 Motor RPM (Standard/Oversized) 1740/ /3450 Motor Frame Size (Standard/Oversized) 145T/145T 145T/145T Filters - Type Furnished 8 Throwaway Throwaway (No.) Size Recommended Downflow (2)20 X 20 X 2/(4)20 X 25 X 2 (4)20 X 20 X 2/(4)20 X 25 X 2 Horizontal (2)20 X 20 X 2/(4)20 X 25 X 2 (8)20 X 25 X 2 Refrigerant Charge (Lbs of R-22) 7 /Circuit 15.0/ / Cooling Performance is rated at 95 F ambient, 80 F entering dry bulb, 67 F entering wet bulb. Gross capacity does not include the effect of fan motor heat. ARI capacity is net and includes the effect of fan motor heat. Units are suitable for operation to ±20% of nominal cfm. Certified in accordance with the Unitary Large Equipment certification program, which is based on ARI Standard 340/ EER is rated at ARI conditions and in accordance with DOE test procedures. 3. Integrated Part Load Value is rated in accordance with ARI Standard 210/240 or 360. Units are rated at 80 F ambient, 80 F entering dry bulb, and 67 F entering wet bulb at ARI rated cfm. 4. Heating Performance limit settings and rating data were established and approved under laboratory test conditions using American National Standards Institute standards. Ratings shown are for elevations up to 2000 feet. For elevations above 2000 feet, ratings should be reduced at the rate of 4% for each 1000 feet above sea level. 5. AFUE and Steady State Efficiency is rated in accordance with DOE test procedures. 6. Sound Rating shown is tested in accordance with ARI Standard 270 or Refrigerant charge is an approximate value. For a more precise value, see unit nameplate and service instructions. 8. An optional 2 inch pleated filter is also available. 9. TXV/Face-Split Option (Downflow Only) YCD181C3,4,W (EER):11.4; (System Power kw): 15.79; (Refrigerant Control): Expansion Valve; (Refrigerant Charge): 26.0/ TXV/Face-Split Option (Downflow Only) YCD151C3,4,W (EER):11.3; (System Power kw): 12.92; (Refrigerant Control): Expansion Valve; (Refrigerant Charge): 13.4/12.0. *Indicates both downflow and horizontal units. 15
16 General Data (17½, 20, 25 Ton) High Efficiency Table GD-5 General Data 17½ Ton 20 Ton 25 Ton Units Downflow and Horizontal Units Downflow and Horizontal Units Downflow and Horizontal Units YC*211C3,C4,CW YC*241C3,C4,CW YC*301C3,C4,CW Cooling Performance 1 Gross Cooling Capacity 220, , ,000 EER Nominal CFM / ARI Rated CFM 7,000 / 6,200 8,000 / 7,000 10,000/8,750 ARI Net Cooling Capacity 208, , ,000 Integrated Part Load Value System Power (KW) Heating Performance 4 Heating Models Low High Low High Low High Heating Input (Btuh) 250, , , , , ,000 1st Stage 175, , , , , ,000 Heating Output (Btuh) 203, , , , , ,000 1st Stage 142, , , , , ,000 AFUE% 5 (Downflow/Horizontal) 80.2 / / / / / /79.7 Steady State Efficiency (%) No. Burners No. Stages Gas Supply Pressure (in. w.c) Natural or LP ((minimum/maximum) 2.5/ / /14.0 Gas Connection Pipe Size (in.) 1/2 3/4 1/2 3/4 1/2 3/4 Compressor No./Type 2/Trane 3-D Scroll/Copeland Scroll 2/Trane 3-D Scroll/Copeland Scroll 2/Trane 3-D Scroll Sound Rating (BELS) Outdoor Coil - Type High-Performance High-Performance High Performance Tube Size (in.) OD Face Area (sq ft) Rows/FPI 3/16 3/16 3/16 Indoor Coil - Type High-Performance High-Performance High Performance Tube Size (in.) Face Area (sq ft) Rows/FPI 4/15 4/15 4/15 Refrigerant Control Short Orifice Short Orifice 9 Short Orifice Drain Connection No./Size (in.) 1/1.0 NPT 1/1.0 NPT 1/1.0 NPT Outdoor Fan - Type Propeller Propeller Propeller No. Used/Diameter (in.) 2/26 2/26 2/26 Drive Type/No. Speeds Direct/1 Direct/1 Direct/1 CFM 12,800 13,700 13,700 No. Motors/HP 2/1.0 2/1.0 2/1.0 Motor RPM Indoor Fan - Type FC Centrifugal FC Centrifugal FC Centrifugal No. Used/Diameter (in.) 1/18 x 18 1/18 x 18 1/18x18 Drive Type/No. Speeds BELT/1 BELT/1 BELT/1 No. Motors Motor HP (Standard/Oversized) 5.0/ / Motor RPM (Standard/Oversized) 3450/ / Motor Frame Size (Standard/Oversized) 145T/184T 145T/184T 184T Filters - Type Furnished 8 Throwaway Throwaway Throwaway (No.) Size Recommended Downflow (4)20 X 20 X 2/(4)20 X 25 X 2 (4)20 X 20 X 2/(4)20 X 25 X 2 (4)20 X 20 X 2/(4)20 X 25 X 2 Horizontal (8)20 X 25 X 2 (8)20 X 25 X 2 (8)20 X 25 X 2 Refrigerant Charge (Lbs of R-22) 7 /Circuit 25.7/ / / Cooling Performance is rated at 95 F ambient, 80 F entering dry bulb, 67 F entering wet bulb. Gross capacity does not include the effect of fan motor heat. ARI capacity is net and includes the effect of fan motor heat. Units are suitable for operation to ±20% of nominal cfm. 17½-20 tons are certified in accordance with the Unitary Large Equipment certification program, which is based on ARI Standard 340/ ton model ratings shown are tested in accordance with ARI Standard 340/ EER is rated at ARI conditions and in accordance with DOE test procedures. 3. Integrated Part Load Value is rated in accordance with ARI Standard 210/240 or 360. Units are rated at 80 F ambient, 80 F entering dry bulb, and 67 F entering wet bulb at ARI rated cfm. 4. Heating Performance limit settings and rating data were established and approved under laboratory test conditions using American National Standards Institute standards Ratings shown are for elevations up to 2000 feet. For elevations above 2000 feet, ratings should be reduced at the rate of 4% for each 1000 feet above sea level. 5. AFUE and Steady State Efficiency is rated in accordance with DOE test procedures. 6. Sound Rating shown is tested in accordance with ARI Standard 270 or Refrigerant charge is an approximate value. For a more precise value, see unit nameplate and service instructions. 8. An optional 2 inch pleated filter is also available. 9. TXV/Face-Split Option (Downflow Only) YCD241C3,4,W (Gross Cooling Capacity):259,000; (ARI Net Cooling Capacity): 244,000; (System Power kw): 23.02; (Refrigerant Control): Expansion Valve; (Refrigerant Charge): 21.5/22.2 *Indicates both downflow and horizontal units. 16
17 Performance Data (12½ Ton) Standard Efficiency Table PD-1 Gross Cooling Capacities (MBH) 12½ Ton Three Phase YC*150D3, D4, DW, DK Ambient Temperature Enter Dry Entering Wet Bulb CFM Bulb Airflow (F) MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC All capacities shown are gross and have not considered indoor fan heat. To obtain net cooling subtract indoor fan heat. 2. MBH = Total Gross Cooling Capacity 3. SHC = Sensible Heat Capacity *Indicates both downflow and horizontal units. 17
18 Performance Data (15, 17½ Ton) Standard Efficiency Table PD-2 Gross Cooling Capacities (MBH) 15 Ton Three Phase YC*180B3, B4, BW, BK Ambient Temperature Enter. Dry Entering Wet Bulb CFM Bulb Airflow (F) MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC All capacities shown are gross and have not considered indoor fan heat. To obtain net cooling subtract indoor fan heat. 2. MBH = Total Gross Capacity 3. SHC = Sensible Heat Capacity Table PD-3 Gross Cooling Capacities (MBH) 17½ Ton Three Phase YC*210C3, C4, CW, CK Ambient Temperature Enter Dry Entering Wet Bulb CFM Bulb Airflow (F) MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC All capacities shown are gross and have not considered indoor fan heat. To obtain net cooling subtract indoor fan heat. 2. MBH = Total Gross Cooling Capacity 3. SHC = Sensible Heat Capacity *Indicates both downflow and horizontal units. 18
19 Performance Data (20, 25 Ton) Standard Efficiency Table PD-4 Gross Cooling Capacities (MBH) 20 Ton Three Phase YC*240B3, B4, BW, BK Ambient Temperature (F) Enter. Dry Entering Wet Bulb (F) CFM Bulb Airflow (F) MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC All capacities shown are gross and have not considered indoor fan heat. To obtain net cooling subtract indoor fan heat. 2. MBH = Total Gross Capacity 3. SHC = Sensible Heat Capacity Table PD-5 Gross Cooling Capacities (MBH) 25 Ton Three Phase YC*300B3, B4, BW, BK Ambient Temperature (F) Enter. Dry Entering Wet Bulb (F) CFM Bulb Airflow (F) MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC All capacities shown are gross and have not considered indoor fan heat. To obtain net cooling subtract indoor fan heat. 2. MBH = Total Gross Capacity 3. SHC = Sensible Heat Capacity 4. Table is for 460 volt capacity. For capacity at 230 volt, multiply table capacity by 101%. *Indicates both downflow and horizontal units. 19
20 Performance Data (12½ Ton) High Efficiency Table PD-6 Gross Cooling Capacities (MBH) 12½ Ton Three Phase YC*151C3, C4, CW Ambient Temperature Enter Dry Entering Wet Bulb CFM Bulb Airflow (F) MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC All capacities shown are gross and have not considered indoor fan heat. To obtain net cooling subtract indoor fan heat. 2. MBH = Total Gross Cooling Capacity 3. SHC = Sensible Heat Capacity *Indicates both downflow and horizontal units. 20
21 Performance Data (15, 17½ Ton) High Efficiency Table PD-7 Gross Cooling Capacities (MBH) 15 Ton Three Phase YC*181C3, C4, CW Ambient Temperature Enter. Dry Entering Wet Bulb CFM Bulb Airflow (F) MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC All capacities shown are gross and have not considered indoor fan heat. To obtain net cooling subtract indoor fan heat. 2. MBH = Total Gross Capacity 3. SHC = Sensible Heat Capacity Table PD-8 Gross Cooling Capacities (MBH)17½ Ton Three PhaseYC*211C3, C4, CW Ambient Temperature Enter Dry Entering Wet Bulb CFM Bulb Airflow (F) MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC All capacities shown are gross and have not considered indoor fan heat. To obtain net cooling subtract indoor fan heat. 2. MBH = Total Gross Cooling Capacity 3. SHC = Sensible Heat Capacity *Indicates both downflow and horizontal units. 21
22 Performance Data (20, 25 Ton) High Efficiency Table PD-9 Gross Cooling Capacities (MBH) 20 Ton Three Phase YC*241C3, C4, CW Ambient Temperature (F) Enter. Dry Entering Wet Bulb (F) CFM Bulb Airflow (F) MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC All capacities shown are gross and have not considered indoor fan heat. To obtain net cooling subtract indoor fan heat. 2. MBH = Total Gross Capacity 3. SHC = Sensible Heat Capacity Table PD-10 Gross Cooling Capacities (MBH)25 Ton Three PhaseYC*301C3, C4, CW Ambient Temperature (F) Enter. Dry Entering Wet Bulb (F) CFM Bulb Airflow (F) MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC All capacities shown are gross and have not considered indoor fan heat. To obtain net cooling subtract indoor fan heat. 2. MBH = Total Gross Capacity 3. SHC = Sensible Heat Capacity *Indicates both downflow and horizontal units. 22
23 Performance Data (12½ Ton) Standard Efficiency Table PD-11 Evaporator Fan Performance 12½ Ton YC*150D External Static Pressure (Inches of Water) CFM RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP 3 HP Standard Motor & Field Supplied Low Static Drive (1) 3 HP Standard Motor & Drive (2) Table PD- 11 Evaporator Fan Performance 12½ Ton YC*150D Continued External Static Pressure (Inches of Water) CFM RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP 3 HP Standard Motor 3 HP Standard Motor & High Static Drive Accessory (2) & Drive (2) HP Oversized Motor & Drive (3) 5 HP Oversized Motor & Drive (3) 3 HP Standard Motor & High Static Drive Accessory (2) 5 HP Oversized Motor & Field Supplied High Static Drive (3) For Standard Evaporator Fan Speed (RPM), reference Table PD-22. For Oversize Evaporator Fan Speed (RPM), reference Table PD-24. Data includes pressure drop due to filters and wet coils. No accessories or options are included in pressure drop data. Refer to Table PD-27 to determine add l static pressure drop due to other options/accessories Fan motor heat (MBH) = 3.15 x Fan Bhp. 1. Field Supplied Fan Sheave BK90 Required. Field Supplied Belt may be Necessary. 2 3 HP Standard Motor with Field Supplied Motor Sheave 1VP44 Required. Field Supplied Belt may be necessary HP Oversize Motor with Field Supplied Motor Sheave 1VP50 Required. Field Supplied Belt may be necessary. 4. For 380V/60 Hz units, the oversized motor is used as the standard motor, Refer to Motor and Sheave/Fan Speed tables to determine operating range. Trane s factory supplied motors, in commercial equipment, are definite purpose motors, specifically designed and tested to operate reliably and continuously at all cataloged conditions. Using the full horsepower range of our fan motors as shown in our tabular data will not result in nuisance tripping or premature motor failure. Our product s warranty will not be affected. 23
24 Performance Data (15 Ton) Standard Efficiency Table PD-12 Evaporator Fan Performance 15 Ton YC*180B External Static Pressure (Inches of Water) CFM RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP 3 HP Standard Motor & Field 3 HP Standard Motor & Drive Supplied Low Static Drive (1) HP Oversized Motor & Drive Table PD- 12 Evaporator Fan Performance 15 Ton YC*180B Continued External Static Pressure (Inches of Water) CFM RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP 3 HP Standard Motor & Drive 3 HP Standard Motor & High Static Drive Accessory HP Oversized Motor & Drive For Standard Evaporator Fan Speed (RPM), reference Table PD-22. For Oversize Evaporator Fan Speed (RPM), reference Table PD-24. For Standard Motor & High Static Drive Accessory Fan Speed (RPM), reference Table PD-23. Fan motor heat (MBH) = 3.15 x Fan Bhp. Data includes pressure Drop Due to Wet Coils and Filters. No accessories or options are included in pressure drop data. Refer to Table PD-27 to determine add l static pressure drop due to other options/accessories 1. Field Supplied Fan Sheave BK105 Required. Field Supplied Belt may be necessary HP Oversize Motor with Field Supplied Motor Sheave 1VP50 required. Field Supplied Belt may be necessary. 3. For 380V/60 Hz units, the oversized motor is used as the standard motor, Refer to Motor and Sheave/Fan Speed tables to determine operating range. 5 HP Oversized Motor & Field Supplied High Static Drive (2) Trane s factory supplied motors, in commercial equipment, are definite purpose motors, specifically designed and tested to operate reliably and continuously at all cataloged conditions. Using the full horsepower range of our fan motors as shown in our tabular data will not result in nuisance tripping or premature motor failure. Our product s warranty will not be affected. *Indicates both downflow and horizontal units. 24
25 Performance Data (17½ Ton) Standard Efficiency Table PD-13 Evaporator Fan Performance 17½ Ton YC*210C External Static Pressure (Inches of Water) CFM RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP 5 HP Standard Motor & Low Static Drive Accessory 5 HP Standard Motor & Drive HP Oversized Motor & Drive Table PD- 13 Evaporator Fan Performance 17½ Ton YC*210C Continued External Static Pressure (Inches of Water) CFM RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP 5 HP Standard Motor & Drive HP Oversized Motor & Drive For Standard Evaporator Fan Speed (RPM), reference Table PD-22. For Standard Motor and Low Static Drive, reference Table PD-25. For Oversize Evaporator Fan Speed (RPM), reference Table PD For 380V/60 Hz units, the oversized motor is used as the standard motor, Refer to Motor and Sheave/Fan Speed tables to determine operating range. Fan motor heat (MBH) = 3.15 x Fan Bhp. Data includes pressure Drop Due to West Coils and Filters. No accessories or options are included in pressure drop data. Refer to Table PD-27 to determine add l static pressure drop due to other options/accessories Trane s factory supplied motors, in commercial equipment, are definite purpose motors, specifically designed and tested to operate reliably and continuously at all cataloged conditions. Using the full horsepower range of our fan motors as shown in our tabular data will not result in nuisance tripping or premature motor failure. Our product s warranty will not be affected. *Indicates both downflow and horizontal units. 25
26 Performance Data (20 Ton) Standard Efficiency Table PD-14 Evaporator Fan Performance 20 Ton YC*240B External Static Pressure (Inches of Water) CFM RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP 5 HP Standard Motor & Field 5 HP Standard Motor & Drive Supplied Low Static Drive (1) (2) 7.5 HP Oversized Motor & Drive Table PD- 14 Evaporator Fan Performance 20 Ton YC*240B Continued External Static Pressure (Inches of Water) CFM RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP 5 HP Standard Motor & Drive 5 HP Standard Motor & High Static Drive Accessory HP Oversized Motor & Drive For Standard Evaporator Fan Speed (RPM), reference Table PD-22. For Standatd Motor and High Static Drive Accessory/Fan Speed (RPM), reference Table PD-23. For Oversize Evaporator Fan Speed (RPM), reference Table PD-24. Fan motor heat (MBH) = 3.15 x Fan Bhp. Data includes pressure Drop Due to West Coils and Filters. No accessories or options are included in pressure drop data. Refer to Table PD-27 to determine add l static pressure drop due to other options/accessories 1. Field Supplied Fan Sheave BK190 Required. Field Supplied Belt may be necessary HP Oversize Motor with Field Supplied Motor Sheave 1VP50 Required. Field Supplied Belt may be necessary. 3. For 380V/60 Hz units, the oversized motor is used as the standard motor, Refer to Motor and Sheave/Fan Speed tables to determine operating range. Trane s factory supplied motors, in commercial equipment, are definite purpose motors, specifically designed and tested to operate reliably and continuously at all cataloged conditions. Using the full horsepower range of our fan motors as shown in our tabular data will not result in nuisance tripping or premature motor failure. Our product s warranty will not be affected. *Indicates both downflow and horizontal units. 26
27 Performance Data (25 Ton) Standard Efficiency Table PD-15 Evaporator Fan Performance 25 Ton YC*300B External Static Pressure (Inches of Water) CFM RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP 7.5 HP Standard Motor & Low Static Drive Accessory 7.5 HP Standard Motor & Drive HP Standard Motor & Drive 7.5 HP Standard Motor & High Static Drive Accessory Table PD-15 Evaporator Fan Performance 25 Ton YC*300B Continued External Static Pressure (Inches of Water) CFM RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP 7.5 HP Standard Motor & Drive HP Standard Motor & High Static Drive Accessory For Standard Evaporator Fan Speed (RPM), reference Table PD-22. For Standard Motor and High Static Drive, reference Table PD-23. For Standard Motor and Low Static Drive, reference Table PD For 380V/60 Hz units, the oversized motor is used as the standard motor, Refer to Motor and Sheave/Fan Speed tables to determine operating range. Data includes pressure drop due to filters and wet coils. No accessories or options are included in pressure drop data. Refer to Table PD-27 to determine add l static pressure drop due to other options/accessories Fan motor heat (MBH) = 3.15 x Fan Bhp Trane s factory supplied motors, in commercial equipment, are definite purpose motors, specifically designed and tested to operate reliably and continuously at all cataloged conditions. Using the full horsepower range of our fan motors as shown in our tabular data will not result in nuisance tripping or premature motor failure. Our product s warranty will not be affected. *Indicates both downflow and horizontal units. 27
28 Performance Data (12½ Ton) High Efficiency Table PD-16 Evaporator Fan Performance 12½ Ton YCD151C External Static Pressure (Inches of Water) CFM RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP 3 HP Standard Motor & Field 3 HP Standard Motor & Drive Supplied Low Static Drive (1) HP Oversized Motor & Drive 3 HP Standard Motor & High Static Drive Accessory Table PD- 16 Evaporator Fan Performance 12½ Ton YCD151C Continued External Static Pressure (Inches of Water) CFM RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP 3 HP Standard 3 HP Standard Motor & High Static Drive Accessory Motor & Drive HP Oversized Motor & Drive For Standard Evaporator Fan Speed (RPM), reference Table PD-22. For Standard Motor & High Static Drive Accessory/Fan Speed (RPM), reference Table PD-23. For Oversize Evaporator Fan Speed (RPM), reference Table PD-24. Data includes pressure drop due to filters and wet coils. No accessories or options are included in pressure drop data. Refer to Table PD-27 to determine add l static pressure drop due to other options/accessories Fan motor heat (MBH) = 3.15 x Fan Bhp. 1. Field Supplied Fan Sheave BK115 required. Field Supplied Belt may be necessary. Trane s factory supplied motors, in commercial equipment, are definite purpose motors, specifically designed and tested to operate reliably and continuously at all cataloged conditions. Using the full horsepower range of our fan motors as shown in our tabular data will not result in nuisance tripping or premature motor failure. Our product s warranty will not be affected. 28
29 Performance Data (12½ Ton) High Efficiency Table PD-17 Evaporator Fan Performance 12½ Ton YCH151C External Static Pressure (Inches of Water) CFM RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP 3 HP Standard Motor & Field 3 HP Standard Motor & Drive Supplied Low Static Drive (1) HP Standard Motor & Drive 5 HP Oversized Motor & Drive Table PD-17 Evaporator Fan Performance 12½ Ton YCH151C Continued External Static Pressure (Inches of Water) CFM RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP 3 HP Standard Motor & Drive 3 HP Standard Motor & High Static Drive HP Oversized Motor & Drive For Standard Evaporator Fan Speed (RPM), reference Table PD-22. For Standard Motor & High Static Drive Accessory/Fan Speed (RPM), reference Table PD-23. For Oversize Evaporator Fan Speed (RPM), reference Table PD-24. Data includes pressure drop due to filters and wet coils. No accessories or options are included in pressure drop data. Refer to Table PD-27 to determine add l static pressure drop due to other options/accessories Fan motor heat (MBH) = 3.15 x Fan Bhp. 1. Field Supplied Fan Sheave BK115 required. Field Supplied Belt may be necessary. Trane s factory supplied motors, in commercial equipment, are definite purpose motors, specifically designed and tested to operate reliably and continuously at all cataloged conditions. Using the full horsepower range of our fan motors as shown in our tabular data will not result in nuisance tripping or premature motor failure. Our product s warranty will not be affected. 29
30 Performance Data (15 Ton) High Efficiency Table PD-18 Evaporator Fan Performance 15 Ton YC*181C External Static Pressure (Inches of Water) CFM RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP 3 HP Standard Motor & Field Supplied Low Static Drive (1) 3 HP Standard Motor & Drive HP Oversized Motor & Drive Table PD-18 Evaporator Fan Performance 15 Ton YC*181C Continued External Static Pressure (Inches of Water) CFM RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP 3 HP Standard 3 HP Standard Motor & Field Motor & Drive Supplied High Static Drive HP Oversized Motor & Drive For Standard Evaporator Fan Speed (RPM), reference Table PD-22. For Standard Motor and High Static Drive (RPM), reference Table PD-23. For Oversize Evaporator Fan Speed (RPM), reference Table PD-24. Data includes pressure drop due to filters and wet coils. No accessories or options are included in pressure drop data. Refer to Table PD-27 to determine add l static pressure drop due to other options/accessories Fan motor heat (MBH) = 3.15 x Fan Bhp. 1. Field Supplied Fan Sheave BK120 required. Field Supplied Belt May be necessary. Trane s factory supplied motors, in commercial equipment, are definite purpose motors, specifically designed and tested to operate reliably and continuously at all cataloged conditions. Using the full horsepower range of our fan motors as shown in our tabular data will not result in nuisance tripping or premature motor failure. Our product s warranty will not be affected. *Indicates both downflow and horizontal units. 30
31 Performance Data (17½ Ton) High Efficiency Table PD-19 Evaporator Fan Performance 17½ Ton YC*211C External Static Pressure (Inches of Water) CFM RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP 5 HP Standard Motor & Field 5 HP Standard Motor & Drive Supplied Low Static Drive (1) HP Standard Motor & High Static Drive Accessory 7.5 HP Oversized Motor & Drive Table PD-19 Evaporator Fan Performance 17½ Ton YC*211C Continued External Static Pressure (Inches of Water) CFM RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP 5 HP Standard Motor & Drive 5 HP Standard Motor & High Static Drive Accessory HP Oversized Motor & Drive For Standard Evaporator Fan Speed (RPM), reference Table PD-22. For Standard Motor & High Static Drive Accessory/Fan Speed (RPM), reference Table PD-23. For Oversize Evaporator Fan Speed (RPM), reference Table PD-24. Data includes pressure drop due to filters and wet coils. No accessories or options are included in pressure drop data. Refer to Table PD-27 to determine add l static pressure drop due to other options/accessories Fan motor heat (MBH) = 3.15 x Fan Bhp. 1. Field Supplied Fan Sheave BK190 required. Field supplied belt may be necessary. Trane s factory supplied motors, in commercial equipment, are definite purpose motors, specifically designed and tested to operate reliably and continuously at all cataloged conditions. Using the full horsepower range of our fan motors as shown in our tabular data will not result in nuisance tripping or premature motor failure. Our product s warranty will not be affected. *Indicates both downflow and horizontal units. 31
32 Performance Data (20 Ton) High Efficiency Table PD-20 Evaporator Fan Performance 20 Ton YC*241C External Static Pressure (Inches of Water) CFM RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP 5 HP Standard Motor & Field 5 HP Standard Motor & Drive Supplied Low Static Drive (1) (2) 7.5 HP Oversized Motor & Drive Table PD-20 Evaporator Fan Performance 20 Ton YC*241C Continued External Static Pressure (Inches of Water) CFM RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP 5 HP Standard Motor & Drive 5 HP Standard Motor & High Static Drive Accessory HP Oversized Motor & Drive For Standard Evaporator Fan Speed (RPM), reference Table PD-22. For Standard Motor & High Static Drive Accessory/Fan Speed (RPM), reference Table PD-23. For Oversize Evaporator Fan Speed (RPM), reference Table PD-24. Data includes pressure drop due to filters and wet coils. No accessories or options are included in pressure drop data. Refer to Table PD-27 to determine add l static pressure drop due to other options/accessories Fan motor heat (MBH) = 3.15 x Fan Bhp. 1. Field Supplied Fan Sheave BK190 required. Field supplied belt may be necessary HP Oversize Motor with Field Supplied Motor Sheave 1VP50 required. Field Supplied Belt may be necessary. Trane s factory supplied motors, in commercial equipment, are definite purpose motors, specifically designed and tested to operate reliably and continuously at all cataloged conditions. Using the full horsepower range of our fan motors as shown in our tabular data will not result in nuisance tripping or premature motor failure. Our product s warranty will not be affected. *Indicates both downflow and horizontal units. 32
33 Performance Data (25 Ton) High Efficiency Table PD-21 Evaporator Fan Performance 25 Ton YC*301C External Static Pressure (Inches of Water) CFM RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP 7.5 HP Standard Motor & Low Static Drive Accessory 7.5 HP Standard Motor & Drive HP Standard Motor & High Static Drive Accessory Table PD-21 Evaporator Fan Performance 25 Ton YC*301C Continued External Static Pressure (Inches of Water) CFM RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP 7.5 HP Standard Motor & Drive HP Standard Motor & High Static Drive Accessory For Standard Evaporator Fan Speed (RPM), reference Table PD-22. For Standard Motor & Low Static Drive, reference Table PD-25. For Standard Motor & High Static Drive, reference Table PD-23. Data includes pressure drop due to filters and wet coils. No accessories or options are included in pressure drop data. Refer to Table PD-27 to determine add l static pressure drop due to other options/accessories Fan motor heat (MBH) = 3.15 x Fan Bhp. Trane s factory supplied motors, in commercial equipment, are definite purpose motors, specifically designed and tested to operate reliably and continuously at all cataloged conditions. Using the full horsepower range of our fan motors as shown in our tabular data will not result in nuisance tripping or premature motor failure. Our product s warranty will not be affected. *Indicates both downflow and horizontal units. 33
34 Performance Data (12½ - 25 Tons) Table PD-22 Standard Motor & Drive/Fan Speed (Rpm) Unit 6 Turns 5 Turns 4 Turns 3 Turns 2 Turns 1 Turn Tons Model No. Open Open Open Open Open Open Closed 12½ YC*150D3,4,W, YC*151C3,4,W NA YC*150DK N/A YC*180B3,4,W NA 15 YC*180BK N/A YC*181C3,4,W NA YC*210C3,4,W NA 17½ YC*210CK N/A YC*211C3,4,W NA 20 YC*240B3,4,W, YC*241C3,4,W NA YC*240BK N/A 25 YC*300B3,4,W, YC*301C3,4,W NA YC*300BK N/A Factory set at 3 turns open. Table PD-23 Standard Motor & High Static Drive Accessory/Fan Speed (Rpm) Unit 6 Turns 5 Turns 4 Turns 3 Turns 2 Turns 1 Turn Tons Model No. Open Open Open Open Open Open Closed 12½ YC*151C3,4,W NA 15 YC*180B3,4,W NA 15 YC*181B3,4,W NA 17½ YC*211C3,4,W NA 20 YC*240B/241C3,4,W NA 25 YC*300B/301C3,4,W NA Table PD-24 Oversized Motor & Drive/Fan Speed (Rpm) Unit 6 Turns 5 Turns 4 Turns 3 Turns 2 Turns 1 Turn Tons Model No. Open Open Open Open Open Open Closed 12½ YC*150D,151C3,4,W NA YC*180B3,4,W NA 15 YC*181C3,4,W NA 17½ YC*210C3,4,W NA YC*211C3,4,W NA 20 YC*240B3,4,W, YC*241C3,4,W NA Table PD-25 Low Static Fan Drive Unit 6 Turns 5 Turns 4 Turns 3 Turns 2 Turns 1 Turn Tons Model No. Open Open Open Open Open Open Closed 17½ YC*210C3,4,W NA 25 YC*300B3,4,W,301C3,4,W NA *Indicates both downflow and horizontal units. 34
35 Performance Data (12½ - 25 Tons) Table PD-26 Gas-Fired Heating Capacities Unit Heating Heating Air Temp. Tons Model No. Input MBH Output MBH Rise, F 12½ YC*150D-L1, YC*151C-L1 150/ / YC*150D-H1,YC*151C-H1 250/ / YC*180B-L1 250/ / YC*180B-H1,YC*181C-H1 350/ / YC*181C-L1 250/ / ½ YC*210C-L1, YC*211C-L1 250/ / YC*210C-H1,YC*211C-H1 350/ / YC*240B-L1, YC*241C-L1 250/ / YC*240B-H1,YC*241C-H1 400/ / YC*300B-L1,YC*301C-L1 250/ / YC*300B-H1,YC*301C-H1 400/ / NOTE: 1. Second stage is total heating capacity. Second Stage / First Stage. Table PD-27 Static Pressure Drops Through Accessories (Inches Water Column) Unit Standard 2 Inch Economizer with OA/RA Dampers 2 Tons Model No. CFM Filters 1 Pleated Filters 3 100% OA 100% RA ½ YC*150D,151C YC*180B / / YCD/YCH181C / / / / YC*210C ½ / / YCD/YCH211C / / / / YCD240C YCD241C YCH240C YCH241C YCD300B,301C YCH300B,301C Notes: 1. 2 filters standard on the 12½-25 tons. 2. OA = Outside Air and RA = Return Air. 3. Difference in pressure drop should be considered when utilizing optional 2 pleated filters. *Indicates both downflow and horizontal units. 35
36 Controls Field Installed Control Options Zone Sensors Zone sensors are the building occupant s comfort control devices. They replace the conventional electro-mechanical thermostats. The following zone sensor options are available for Voyager units with the ReliaTel control: Manual Changeover Heat, Cool or Off System Switch. Fan Auto or Off Switch. One temperature setpoint lever. Manual/Automatic Changeover Auto, Heat, Cool or Off System Switch. Fan Auto or Off Switch. Two temperature setpoint levers. Optional Status Indication LED lights, System On, Heat, Cool, or Service. Remote Sensor Sensor(s) available for all zone sensors to provide remote sensing capabilities. Dual Thermistor Remote Zone Sensor This sensor will allow the customer to reduce the total number of remote sensors to obtain space temperature averaging. This sensor should be utilized with ReliaTel controls. 36 Digital Display Zone Sensor The Digital LCD (Liquid Crystal Display) zone sensor has the look and functionality of standard zone sensors. This sensor includes a digital display of set point adjustment and space temperature in F (Fahrenheit) or C (Celsius). Includes FAN and SYSTEM buttons (supports the service functions of the standard sensor). E-squared memory stores last programmed set points. Requires 24 VAC (Volts AC). This sensor should be utilized with ReliaTel controls. Programmable Night Setback Auto or manual changeover with sevenday programming. Keyboard selection of Heat, Cool, Fan, Auto, or On. All programmable sensors have System On, Heat, Cool, Service LED/indicators as standard. Night Setback Sensors have one (1) Occupied, one (1) Un-occupied, and two (2) Override programs per day. Integrated Comfort TM System Sensor(s) available with optional temperature adjustment and override buttons to provide central control through a Trane Integrated Comfort TM system. CO 2 Sensing The CO2 sensor has the ability to monitor space occupancy levels within the building by measuring the parts per million of CO 2 (Carbon Dioxide) in the air. As the CO 2 levels increase, the outside air damper modulates to meet the CO 2 space ventilation requirements. The CO 2 sensor kit is available as a field installed accessory. Economizer Controls The standard equipment offering is a fixed dry bulb changeover control. In addition, there are two optional controls, Enthalpy and Differential Enthalpy Control. Enthalpy Control Replaces the dry bulb control with a wet bulb changeover controller which has a fully adjustable set point. Enthalpy control offers a higher level of comfort control, along with energy savings potential, than the standard dry bulb control. This is due to the additional wet bulb sensing capability. Differential Enthalpy Replaces the standard dry bulb control with two enthalpy sensors that compare total heat content of the indoor air and outdoor air to determine the most efficient air source. This control option offers the highest level of comfort control, plus energy efficiency, available. Remote Potentiometer Minimum position setting of economizer can be remotely adjusted with this accessory. Differential Pressure Switches This factory or field-installed option allows individual fan failure and dirty filter indication. The fan failure switch will disable all unit functions and flash the Service LED on the zone sensor. The dirty filter switch will light the Service LED on the zone sensor and will allow continued unit operation. Trane Communication Interface (TCI) This factory or field-installed microprocessor interface allows the unit to communicate to Trane s Integrated Comfort TM system.
37 Electrical Data Table ED-1 Electrical Characteristics Evaporator Fan Motors 60 Cycle Standard Evaporator Fan Motor Oversized Evaporator Fan Motor Unit Amps Amps Tons Model No. No. Volts Phase HP FLA LRA No. Volts Phase HP FLA LRA YC*150D3, YC*151C ½ YC*150D4, YC*151C YC*150DW,YC*151CW YC*150DK YC*180B3, YC*181C YC*180B4, YC*181C YC*180BW,YC*181CW YC*180BK YC*210C3, YC*211C ½ YC*210C4, YC*211C YC*210CW,YC*211CW YC*210CK YC*240B3, YC*241C YC*240B4, YC*241C YC*240BW,YC*241CW YC*240BK YC*300B3, YC*301C YC*300B4, YC*301C YC*300BW,YC*301CW YC*300BK *Indicates both downflow and horizontal units. 37
38 Electrical Data (Standard Efficiency) Table ED-2 Electrical Characteristics Compressor Motor And Condenser Motor 60 Cycle Std. Efficiency Compressor Motor Condenser Fan Motors Unit Amps1 Amps1 Tons Model No. No. Volts Phase HP 3 RPM RLA LRA No. Phase HP FLA LRA YC*150D ½ YC*150D YC*150DW YC*150DK YC*180B / / / YC*180B / / / YC*180BW / /7.4 85/ YC*180BK / / / YC*210C / / / ½ YC*210C / / / YC*210CW / /8.2 85/ YC*210CK / / / YC*240B YC*240B YC*240BW YC*240BK YC*300B YC*300B YC*300BW YC*300BK Amp draw for each motor; multiply value by number of motors to determine total amps. 2. HP for each compressor. *Indicates both downflow and horizontal units. 38
39 Electrical Data (High Efficiency) Table ED-3 Electrical Characteristics Compressor Motor And Condenser Motor 60 Cycle High Efficiency Compressor Motor Condenser Fan Motors Unit Amps1 Amps1 Tons Model No. No. Volts Phase HP 2 RPM RLA LRA No. Phase HP FLA LRA YC*151C ½ YC*151C YC*151CW YC*181C / / / YC*181C / / / YC*181CW / /6.6 85/ YC*211C / / / ½ YC*211C / / / YC*211CW / /8.2 92/ YC*241C YC*241C YC*241CW YC*301C YC*301C YC*301CW Amp draw for each motor; multiply value by number of motors to determine total amps. 2. HP for each compressor. Table ED-3a Electrical Characteristics Compressor Motor And Condenser Motor 60 Cycle TXV/Face-Split Evaporator Coil Option (Downflow Only) High Efficiency Compressor Motor Condenser Fan Motors Unit Amps 1 Amps 1 Tons Model No. No. Volts Phase HP 2 RPM RLA LRA No. Phase HP FLA LRA YCD151C / / / ½ YCD151C / /9.4 75/ YCD151CW / /7.4 54/ YCD181C / / / YCD181C / / / YCD181CW / /7.4 85/ YCD211C / / / ½ YCD211C / / / YCD211CW / /8.1 92/ YCD241C / / / / YCD241C / / / / YCD241CW / / / / YCD301C YCD301C YCD301CW Amp draw for each motor; multiply value by number of motors to determine total amps. 2. HP for each compressor. *Indicates both downflow and horizontal units. 39
40 Electrical Data (Standard Efficiency) Table ED-4 Unit Wiring - Standard Efficiency Standard Indoor Fan Motor Oversize Indoor Fan Motor Unit Minimum Maximum Fuse Minimum Maximum Fuse Unit Operating Circuit Size Or Maximum Circuit Size Or Maximum Tons Model No. Voltage Range Ampacity 2 Circuit Breaker 1 Ampacity 2 Circuit Breaker 1 YC*150D ½ YC*150D YC*150DW YC*150DK YC*180B YC*180B YC*180BW YC*180BK YC*210C ½ YC*210C YC*210CW YC*210CK YC*240B YC*240B YC*240BW YC*240BK YC*300B YC*300B YC*300BW YC*300BK HACR breaker per NEC. 2. MCA values do not include Power Exhaust accessory. See Table ED-7 for this information. *Indicates both downflow and horizontal units. 40
41 Electrical Data (High Efficiency) Table ED-5 Unit Wiring - High Efficiency Standard Indoor Fan Motor Oversize Indoor Fan Motor Unit Minimum Maximum Fuse Minimum Maximum Fuse Unit Operating Circuit Size Or Maximum Circuit Size Or Maximum Tons Model No. Voltage Range Ampacity 2 Circuit Breaker 1 Ampacity 2 Circuit Breaker 1 YC*151C ½ YC*151C YC*151CW YC*181C YC*181C YC*181CW YC*211C ½ YC*211C YC*211CW YC*241C YC*241C YC*241CW YC*301C N/A N/A 25 YC*301C N/A N/A YC*301CW N/A N/A 1. HACR breaker per NEC. 2. MCA values do not include Power Exhaust accessory. See Table ED-7 for this information. Table ED-5a Unit Wiring - TXV/Face-Split Evaporator Coil Option (Downflow Only) - High Efficiency Standard Indoor Fan Motor Oversize Indoor Fan Motor Unit Minimum Maximum Fuse Minimum Maximum Fuse Unit Operating Circuit Size Or Maximum Circuit Size Or Maximum Tons Model No. Voltage Range Ampacity 2 Circuit Breaker 1 Ampacity 2 Circuit Breaker 1 YCD151C ½ YCD151C YCD151CW YCD181C YCD181C YCD181CW YCD211C ½ YCD211C YCD211CW YCD241C YCD241C YCD241CW YCD301C N/A N/A 25 YCD301C N/A N/A YCD301CW N/A N/A 1. HACR breaker per NEC. 2. MCA values do not include Power Exhaust accessory. See Table ED-7 for this information. *Indicates both downflow and horizontal units. 41
42 Electrical Data Table ED-6 Electrical Characteristics Combustion Blower Motor Unit Heating Amps Model No. Heat Stages HP RPM Volts Phase FLA LRA YC*150, 151 Low 2 1/ / YC*180, 181, 210, 211, Low 2 1/ / YC*151-YC*301 High 2 1/ / High/Low Speed. Table ED-7 Electrical Characteristics Power Exhaust Accessory Accessory Accessory Operating Amps Tons Model Number Voltage Phase HP RPM FLA LRA BAYPWRX / ½ 1,12½ 2 BAYPWRX / ,17½, 20, 25 BAYPWRX / ½ Ton Standard Unit ½ Ton High Efficiency Unit. 42
43 Jobsite Connections ZONE SENSORS A DISCONNECT SWITCH (BY OTHERS) B ROOFTOP UNIT Zone Sensors Typical Number Of Wires A Manual Changeover... 4 Manual/Auto Changeover... 5 Manual/Auto Changeover with Status Indication LED s Programmable Night Setback with Status Indication LED s... 7 B 3 Power Wires + 1 Ground Wire (three phase) 2 Power Wires + 1 Ground Wire (single phase) For specific wiring information, see the installation instructions. All wiring except power wires is low voltage. All customer supplied wiring to be copper and must conform to NEC or CEC and local electrical codes. Wiring shown dotted is to be furnished and installed by the customer. 43
44 Typical Wiring (12½ - 25 Tons) 44
45 Typical Wiring (12½ - 25 Tons) PRINTED FROM
46 Typical Wiring (12½ - 25 Tons) 46
47 Typical Wiring (12½ - 25 Tons) B 47
48 Dimensional 12½ Ton High Efficiency Data 12½, 15, 17½ Ton Standard Efficiency All dimensions are in inches. NOTE: Duct flanges mount 7-7/16" down inside the curb on the 1-1/2" curb flanges. See recommended duct dimensions on the next page. Roofcurb is intended for downflow use only. 1 1/2" PERIMETER CURB FLANGE 14 1/16" 7 7/16" 2" 66 5/8" 63" 1 13/16" RETURN 1" 20 7/8" 17 1/8" 55 1/2" SUPPLY 1" 101 7/8" 1" 28 1/2" 102 1/4" 7 1/2" 67" Downflow Unit Clearance 48
49 Dimensional 12½ Ton High Efficiency Data 12½, 15, 17½ Ton Standard Efficiency All dimensions are in inches. 1" Downflow Duct Connections Field Fabricated 17 7/8" 59 7/16" 26 5/16" 52 1/2" 1" 14 1/16" 1 1\2" PERIMETER CURB FLANGE NOTE: Duct flanges mount 7-7/16" 7 7/16" RETURN SUPPLY Horizontal Unit Supply/Return and Unit Clearance 49
50 Dimensional Data Tons High Efficiency 20, 25 Ton Standard Efficiency All dimensions are in inches. 1 1/2" PERIMETER CURB FLANGE 7 7/16" 80 5/8" 77" 1 13/16" 22 1/4" 1" 23 1/4" 1" 116 7/8" 28 9/16" 1" 14 1/16" 2" RETURN 69 1/2" SUPPLY 117 3/16" 7 1/2" 81" 50
51 Dimensional Data Tons High Efficiency 20, 25 Ton Standard Efficiency All dimensions are in inches. 1" 19 5/16" 73 7/16" 26 5/16" 66 1/2" 1" 14 1/16" 1 1\2" PERIMETER CURB FLANGE 7 7/16" RETURN SUPPLY 51
52 Dimensional Data (12½ - 25 Tons) Accessories All dimensions are in inches. Note: When applying economizer to horizontal units, connecting ductwork must be run full size to allow proper operation of Economizer Damper. Table DD-1 Unit Model # A B 1 C 2 YC* ,210 17½ 53¾ 36 YC*181, ½ 64¾ Horizontal dimension only. Downfloweconomizer is width of end panel. 2. Power exhaust is applied on downflow economizer only. 52
53 Dimensional Data Factory Installed Options (FIOPS) All dimensions are in inches. Table DD-2 Unit Model # A B C YCD150, 151, 180, / / / 8 YCD / /
54 Dimensional Data Factory Installed Options (FIOPS) Fan Failure Switch Disconnect Switch or Circuit Breaker Clogged Filter Switch Powered Or Unpowered Convenience Outlet Trane Communication Interface Hinged Access Door Black Epoxy Coated Outdoor Coils Hinged Access Door Through the Base Electrical High Pressure Cut Out Supply and/or Return Smoke Detectors Through the Base Gas Piping 54
55 Dimensional Data (12½ - 25 Tons) Table DD-3 Standard Efficiency Units Condensate Drain Location Condensate Tons Downflow Only Drain Size Downflow Horizontal A B C D F G H E J E K 12½, 15, 17½ 26-7/ / /16 4-1/4 4-1/4 62-7/ /16 1 NPT 25-5/8 5-3/8 20, / / /16 4-1/4 4-1/4 76-5/ /16 1 NPT 26-3/4 5-3/8 Table DD-4 High Efficiency Units Condensate Drain Location Condensate Tons Downflow Only Drain Size Downflow Horizontal A B C D F G H E J E K 12½ 26-7/ / /16 4-1/4 4-1/4 62-7/ /16 1 NPT 25-5/ / / /16 4-1/4 4-1/4 76-5/ /16 1 NPT 26-3/4 5-3/8 55
56 Table W-1 Accessory Net Weights (Lbs) 1,2 Oversize LPG All High 4 Low 4 Weights (12½ - 25 Tons) Unit Economizer Outside Air Damper Roof 3 Motor Conversion Zone Power 3 Static Static Model No. Net Motorized Manual Curb Adder Kit Sensors Exhaust Drive Drive YCD180B,210C YCD150D,151C YCD240B YCD181,211,241C YCD300B,301C YCH180B,210C YCH150D,151C N/A N/A 2 YCH240B YCH181,211,241C N/A N/A 2 YCH300B, 301C N/A 5 1 N/A 2 1. Net weight should be added to unit weight when ordering factory installed accessories. 2. YC* factory installed options for economizers, multiply net capacity x.99, EER x.97. For oversize motors, multiply net capacity x.98, EER x.93. This is provided in compliance with ARI certification program. 3. Downflow only. 4. Not available on all models (See fan performance tables for specific models). Table W-2 Factory Installed Options (FIOPS) Net Weights (Lbs) 1,2,3 Accessory Model Accessory Number Weight FIYHEMT001, High Efficiency Motors FIYHEMT FIYHEMT Hinged Doors FIYHNGE001, FIYHNGE Powered Convenience Outlet FIYCOPO Through the Base Electrical FIYTBUE FIYTBUE Unit Mounted Circuit Breaker FIYUCB FIYUCB Unit Mounted Disconnect FIYUDC4150, FIYUDC Weights for FIOP accessories not listed are >5 lbs. 2. Net weight should be added to unit weight when ordering factory installed accessories. 3. See Table W-1 for standard factory installed economizer and oversized motors. 56
57 Weights (12½ - 25 Tons) Table W-3 Maximum Unit And Corner Weights (Lbs) And Center Of Gravity Dimensions (In.) Unit Maximum Weights (Lbs) 2 Corner Weights (Lbs)1 Center of Gravity (In.) Tons Model No. Shipping Net A B C D Length Width 12½ YC*150D/YC*151C 1826/ / / / / /370 46/45 29/30 15 YC*180B/YC*181C 2033/ / / / / /470 43/52 29/35 17½ YC*210C/YC*211C 2189/ / / / / /480 46/53 29/35 20 YC*240B/YC*241C 2547/ / / / / /494 51/53 34/34 25 YC*300B/YC*301C 2541/ / / / / /495 53/53 33/34 NOTE: 1. Corner weights are given for information only. 12½-25 ton must be supported continuously by a curb or equivalent frame support. 2. Weights are approximate. Horizontal and Downflow unit and corner weights may vary slightly. *Indicates both downflow and horizontal units. 57
58 Mechanical Specifications General Units shall be dedicated downflow or horizontal airflow. Operating range shall be between 115 F and 0 F cooling as standard from the factory for all units. Cooling performance shall be rated in accordance with DOE and/or ARI testing procedures. All units shall be factory assembled, internally wired, fully charged with R-22, and 100 percent runtested before leaving the factory. Wiring internal to the unit shall be colored and numbered for simplified identification. Units shall be UL listed and labeled, classified in accordance to ANSIZ21.47 for gas fired central furnaces and UL 1995/CAN/CSA No. 236-M90 for central cooling air conditioners. Canadian units shall be CSA certified. Casing Unit casing shall be constructed of zinc coated, heavy gauge, galvanized steel. Exterior surfaces shall be cleaned, phosphatized, and finished with a weather-resistant baked enamel finish. Unit s surface shall be tested 500 hours in a salt spray test in compliance with ASTM B117. Cabinet construction shall allow for all maintenance on one side of the unit. Service panels shall have lifting handles and be removed and reinstalled by removing not more than three screws on the 12½-25 tons while providing a water and air tight seal. All exposed vertical panels and top covers in the indoor air section shall be insulated with a 1/2 inch, 1 pound density matt-faced, fire-resistant, permanent, odorless, glass fiber material. The base of the downflow unit shall be insulated with 1/2 inch, 1 pound density foil-faced, closed-cell material. The downflow unit s base pan shall have no penetrations within the perimeter of the curb other than the raised 1 1 / 8 inch high supply/return openings to provide an added water integrity precaution, if the condensate drain backs up. The base of the unit shall have provisions for forklift and crane lifting. Unit Top The top cover shall be one piece, or where seams exist, double hemmed and gasket sealed to prevent water leakage. Filters Two inch filters shall be factory supplied on all units above 12½ tons. Optional two inch pleated media filters shall be available for 12½-25 tons. Compressors 12½-25 tons standard and high efficiency units shall have direct-drive, hermetic, scroll type compressors with centrifugal type oil pumps. Motor shall be suction gas-cooled and shall have a voltage utilization range of plus or minus 10 percent of unit nameplate voltage. Internal overloads shall be provided with the scroll compressors. All models (with the exception of 12½ ton standard efficiency) have crankcase heaters. Refrigerant Circuits Each refrigerant circuit has an independent fixed orifice or a thermal expansion valve device, service pressure ports, and refrigerant line filter driers factory-installed as standard. An area shall be provided for replacement suction line driers. Evaporator And Condenser Coils Internally finned, 3/8" copper tubes mechanically bonded to a configured aluminum plate fin shall be standard. Coils shall be leak tested at the factory to ensure pressure integrity. The evaporator coil and condenser coil shall be leak tested to 200 psig and pressure tested to 450 psig. Sloped condensate drain pans are standard. On all dual compressor models, the evaporator coil shall be intermingled or face-split configuration. Gas Heating Section The heating section shall have a drum and tube heat exchanger design using corrosion resistant steel components. A forced combustion blower shall supply premixed fuel to a single burner ignited by a pilotless hot surface ignition system. In order to provide reliable operation, a negative pressure gas valve shall be used that requires blower operation to initiate gas flow. On an initial call for heat, the combustion blower shall purge the heat exchanger 45 seconds before ignition. After three unsuccessful ignition attempts, the entire heating system shall be locked out until manually reset at the thermostat. Units shall be suitable for use with natural gas or propane (field installed kit) and shall also comply with California requirements for low NOx emissions. The 12½-25 tons shall have two stage heating. Outdoor Fans The outdoor fans shall be direct-drive, statically and dynamically balanced, draw-through in the vertical discharge position. The fan motor(s) shall be permanently lubricated and shall have built-in thermal overload protection. Indoor Fan Units shall have belt driven, FC centrifugal fans with adjustable motor sheaves. Units over 12½ tons shall have an adjustable idler-arm assembly for quick-adjustment to fan belts and motor sheaves. All motors shall be thermally protected. Oversized motors shall be available for high static operations. All indoor fan motors meet the U.S. Energy Policy Act of 1992 (EPACT). Controls Unit shall be completely factory wired with necessary controls and contactor pressure lugs or terminal block for power wiring. Units shall provide an external location for mounting a fused disconnect device. ReliaTel shall be provided for all 24 volt control functions. The resident control algorithms shall make all heating, cooling, and/or ventilating decisions in response to electronic signals from sensors measuring indoor and outdoor temperatures. The control algorithm maintains accurate temperature control, minimizes drift from set point, and provides better building comfort. A centralized control shall provide antishort cycle timing and time delay between compressors to provide a higher level of machine protection. 58
59 Mechanical Specifications Accessories Roof Curb - Downflow The roof curb shall be designed to mate with the downflow unit and provide support and a watertight installation when installed properly. The roof curb design shall allow field-fabricated rectangular supply/return ductwork to be connected directly to the curb. Curb design shall comply with NRCA requirements. Curb shall be shipped knocked down for field assembly and shall include wood nailer strips. Economizer - Downflow This accessory shall be either field or factory installed. The assembly includes fully modulating percent motor and dampers, barometric relief, minimum position setting, preset linkage, wiring harness with plug, and fixed dry bulb control. Solid state enthalpy and differential enthalpy control shall be a factory-supplied, field-installed accessory. The factory-installed economizer arrives in the shipping position and shall be moved to the operating position by the installing contractor. Economizer - Horizontal This accessory shall be field-installed only. The horizontal economizer shall contain the same features as the downflow economizer with the exception of barometric relief. Remote Potentiometer The minimum position setting of economizer shall be adjusted with this accessory. Powered Exhaust The powered exhaust for 12½-25 tons downflow units shall assist the barometric relief damper in the economizer in relieving building pressurization. Motorized Outside Air Dampers Manually set outdoor air dampers shall provide up to 50 percent outside air. Once set, outdoor air dampers shall open to set position when indoor fan starts. The damper shall close to the full closed position when indoor fan shuts down. This option shall be available for 12½-25 tons. Manual Outside Air Damper Field installed rain hood and screen shall provide up to 25 percent outside air. Oversized Motors Field and factory installed oversized motors shall be available for high static applications. Low Static Drive Field installed low static drive option shall allow the standard motor to operate at lower static performance. (See Fan Performance tables.) High Static Drive Field installed high static drive option shall allow the standard motor to operate with improved external static capabilities. (See Fan Performance tables.) Control Options Trane Communication Interface (TCI) This option shall be provided to interface with the Trane Integrated Comfort TM systems. Zone Sensors This option shall be provided to interface with the Micro equipped Voyagers and shall be available in either manual, automatic programmable with night setback, with system malfunction lights or remote sensor options. Fan Failure/Clogged Filter Switches These field installed options allow for individual fan failure and dirty filter indication. The fan failure switch will disable all unit functions and flash the Service LED on the zone sensor. The dirty filter switch will light the Service LED on the zone sensor and will allow continued unit operation. LonTalk (COMM5) Communications Interface The LonTalk Communications Interface, when installed in a Voyager unit, allows the unit to communicate as a Tracer LCI- V device or directly with generic LonTalk Network Building Automation System Controls. CO 2 Sensing The CO 2 sensor has the ability to monitor space occupancy levels within the building by measuring the parts per million of CO 2 (Carbon Dioxide) in the air. As the CO 2 levels increase, the outside air damper modulates to meet the CO 2 space ventilation requirements. The CO 2 accessory kit is available as a field installed accessory. Ventilation Override Accessory With the Ventilation Override Accessory installed, the unit can be set to transition up to 3 different pre-programmed sequences for Smoke Purge, Pressurization, and Exhaust. The transition occurs when a binary input on the RTOM is closed (shorted). This would typically be a hard wired relay output from a smoke detector or fire control panel. The ventilation override kit is available as a field installed accessory. Digital Display Zone Sensor The Digital LCD (Liquid Crystal Display) zone sensor has the look and functionality of standard zone sensors. This sensor includes a digital display of set point adjustment and space temperature in F (Fahrenheit) or C (Celsius). Includes FAN and SYSTEM buttons (supports the service functions of the standard sensor). E-squared memory stores last programmed set points. Requires 24 VAC (Volts AC). This sensor should be utilized with ReliaTel controls. Dual Thermistor Remote Zone Sensor This sensor will allow the customer to reduce the total number of remote sensors to obtain space temperature averaging. This sensor should be utilized with ReliaTel controls. 59
60 Mechanical Specifications Additional Factory Installed Options (FIOPS) Through the Base Electrical With Disconnect Switch Factory installed 3-pole, molded case disconnect switch with provisions for through the base electrical connections are available. The disconnect switch will be installed in the unit in a water tight enclosure with access through a swinging door. Factory wiring will be provided from the switch to the unit high voltage terminal block. The switch will be UL/CSA agency recognized. Note: The disconnect switch will be sized per NEC and UL guidelines but will not be used in place of unit overcurrent protection. This option is available on all 12½-25 tons downflow models. Through the Base Electrical with Circuit Breaker This option is a factory installed thermal magnetic, molded case, HACR Circuit Breaker with provisions for through the base electrical connections. The circuit breaker will be installed in a water tight enclosure in the unit with access through a swinging door. Factory wiring will be provided from the switch to the unit high voltage terminal block. The circuit breaker will provide overcurrent protection, be sized per NEC and UL guidelines, and be agency recognized by UL/CSA. This option is available on all 12½-25 tons downflow models. Powered or Unpowered Convenience Outlet This option is a GFCI, 120v/15amp, 2 plug, convenience outlet, either powered or unpowered. When the convenience outlet is powered, a service receptacle disconnect will be available. The convenience outlet is powered from the line side of the disconnect or circuit breaker, and therefore will not be affected by the position of the disconnect or circuit breaker. This option can only be ordered when the Through the Base Electrical with either the Disconnect Switch, or Circuit Breaker, option is ordered. This option is available on all 12½-25 tons downflow models. Through the Base Gas Piping With this option, provision will be made in the unit for installing though the base gas piping. The option will have all piping necessary including, black steel, manual gas shut-off valve, elbows, and union. The manual shut-off valve shall include a 1/8" NPT pressure tap. This assembly will require minor field labor to install. This option is available on all 12½-25 tons downflow models and can only be ordered when the Through the Base Electrical Option with Disconnect, or Circuit Breaker, is ordered. Clogged Filter/Fan Failure Switch A dedicated differential pressure switch is available to achieve active fan failure indication and/or clogged filter indication. These indications will be registered with either a zone sensor with status indication lights or an Integrated Comfort System. Reference or Comparative Enthalpy Reference or Comparative Enthalpy option shall be available when a factory installed Downflow Economizer is ordered. This option is available on all 12½-25 tons downflow models. High Pressure Cutout This option is offered for units that do not have High Pressure cutout as standard. The Voyager units with High Pressure Cutout as standard are YC* B,C Hinged Access Doors Sheet metal hinges are available factory installed on the Filter/Evaporator Access Door and the Compressor/Control Access Door. This option is available on all 12½-25 tons downflow models. Trane Communications Interface (TCI) An option for a factory installed Trane Communication Interface is available to allow twisted wire pair communication with an Integrated Comfort System. Order this option when a combination of TCI and oversized motor is desired. 60
61 Mechanical Specifications Discharge Air Sensing Kit This option provides true discharge air sensing in heating models. This sensor is a status indicator readable through Tracer or Tracker. The kit is functional only with the ReliaTel Options Module. Coil Guards Quality, tooless hail/coil guards shall be either factory or field-installed for condenser coil protection. High Efficiency Motors This option is available with efficiency ratings from 86.5 up to Not available for all models. Supply and/or Return Air Smoke Detector With this option installed, if smoke is detected, all unit operation will be shut down. Reset will be manual at the unit. Return Air Smoke Detectors require minimum allowable airflow when used with certain models. See the Installation, Operation, and Maintenance (IOM) manual for the models affected and the minimum allowable airflow required. This option is available on all 12½-25 tons downflow models. Black Epoxy Coated Condenser Coil The coil provides corrosion protection to condenser coils for seacoast application. The protection is a factory applied thermoset vinyl coating, bonded to normal aluminum fin stock. The uniform thickness of the bonded vinyl layer exhibits excellent corrosion protection in salt spray tests performed in accordance with ASTM B117. Frostat This factory or field installed option is to be utilized as a safety device. The Frostat opens when temperatures on the evaporator coil fall below 10 F. The temperature will need to rise to 50 F before closing. This option should be utilized in low airflow or high outside air applications. Through the Base Utilities Access An electrical service entrance shall be provided allowing electrical access for both control and main power connections inside the curb and through the base of the unit. Option will allow for field installation of liquid-tight conduit and an external field installed disconnect switch. Novar Unit Controls Novar rooftop unit controls will be factory installed and tested. The Novar electronic thermostat module will interface to the unit microprocessor and will control the unit to the desired stage of cooling or heating. The Novar electronic thermostat module will monitor the following unit information: fan failure status, cooling stage 1-on status, cooling stage 2 on status, heating on status, clogged filter status or unit shutdown status, and discharge air temperature. The Novar electronic thermostat module will have the ability to enable the unit mounted economizer. Novar Return Air Sensor This option, when used in conjunction with Novar Controls, will contain a factory provided wired zone temperature sensor located in the return air stream. Two Inch Pleated Filters Two inch pleated media filters shall be available on all 12½-20 ton models. Thermal Expansion Valve / Face-Split Evaporator Coil Option All units shall have a short orifice refrigerant control metering device. For more exact refrigerant flow, when using units in low airflow or high outside air applications, a Thermal Expansion Valve option shall be available. This option also includes a Face Split evaporator coil which increases part load latent capacity. 61
62 62
63 63
64 *High Efficiency Units only Trane A business of American Standard Companies For more information contact your local dealer (distributor), local district office, or us at [email protected] Literature Order Number File Number Supersedes Stocking Location PL-UN-RT-YCD/YCH 12½-25 TONS-PRC001-EN Webb/Mason Electronic Only Trane has a policy of continuous product and product data improvement and reserves the right to change design and specifications without notice.
Packaged Cooling with Electric Heat Rooftop Units
Packaged Cooling with Electric Heat Rooftop Units Voyager 12½ - 25 Tons - 60 Hz December 2003 RT-PRC002-EN Introduction Voyager TM... a proven performer built to provide ultimate indoor comfort. Voyager
Packaged Gas/Electric Rooftop Units
Packaged Gas/Electric Rooftop Units Precedent 3-10 Tons 60 Hz October 2004 Introduction Packaged Rooftop Air Conditioners Through the years, Trane has designed and developed the most complete line of Packaged
TWE+TTA TWE+TWA 6.25-20 T.R.
TWE+TTA TWE+TWA 6.25-20 T.R. Main features : TWE indoor unit : Convertible cabinet, vertical or horizontal. Adjustable speed pulley-belt drive centrifugal fan motor. Aluminium fin coil with copper-tubes.
27 1 /2 to 50 Ton - 60 Hz Voyager Commercial
RT-DS-9 May 1998 First Printing July 1998 Packaged Rooftop Air Conditioners RT-DS-9 27 1 /2 to 50 Ton - 60 Hz Voyager Commercial Features and Benefits SM Over the years the Voyager product line has developed
SECTION 23 81 03 - PACKAGED ROOFTOP AIR CONDITIONING UNITS NON-CUSTOM
SECTION 23 81 03 - PACKAGED ROOFTOP AIR CONDITIONING UNITS NON-CUSTOM PART 1 - GENERAL 1.1 SUMMARY A. Section Includes: 1. Packaged rooftop air conditioning unit (5 tons and smaller). 2. Roof curb. 1.2
48/50EJ,EK,EW,EY038, 044, 048 SINGLE-PACKAGE COOLING UNITS VARIABLE VOLUME CONSTANT VOLUME FACTORY-INSTALLED OPTIONAL HEAT
48/50E-4SB 48/50EJ,EK,EW,EY038, 044, 048 SINGLE-PACKAGE COOLING UNITS VARIABLE VOLUME CONSTANT VOLUME FACTORY-INSTALLED OPTIONAL HEAT GAS HEAT ELECTRIC HEAT PERFORMANCE DATA CERTIFIED DIMENSION PRINT CERTIFIED
SECTION 15750 PACKAGED ROOFTOP AIR CONDITIONING UNITS
SECTION 15750 PART 1 - GENERAL 1.01 DESCRIPTION A. Section includes requirements for roof mounted, self-contained units, with electric cooling, and electric or reverse refrigeration cycle (heat pump) heating
M7RL Series TECHNICAL SPECIFICATIONS. FEATURES and BENEFITS. High Efficiency / Direct Vent Condensing Downflow Gas Furnace
TECHNICAL SPECIFICATIONS M7RL Series High Efficiency / Direct Vent Condensing Downflow Gas Furnace Induced Draft - 9%+ AFUE Input 4,000 thru 7,000 Btuh The high efficiency downflow gas furnace is especially
Commercial Gas Furnace Upflow
Commercial Gas Furnace Upflow Model G24-200 80% A.F.U.E. 200,000 Btuh Input Heating Cap. 7.5 or 10 Tons Nominal Add-On Cooling GUK FEATURES Certified by A.G.A./C.G.A. Laboratories. Heavy gauge painted
Cooling/Heat Pump Convertible Air Handlers
Cooling/Heat Pump Convertible Air Handlers 2/4TEC3F18-60A1000A 1½ 5 Ton PUB. NO. 22-1774-01-0905 (EN) Features and Benefits 13.0 SEER Ships horizontal converts to vertical by standing unit on end. Six-way
XV80 UPFLOW/HORIZONTAL 2-STAGE, VARIABLE SPEED GAS-FIRED FURNACE
UPF/HORIZONTAL 2-, VARIABLE SPEED GAS-FIRED FURNACE XV80 MODELS TUD2B060A9V3VB, TUD2B080A9V3VB TUD2C080A9V4VB, TUD2C080B9V4VB TUD2B00A9V3VB, TUD2C00A9V5VB TUD2C00B9V5VB, TUD2DA9V5VB TUD2DB9V5VB, TUD2DA9V5VB
Cooling Capacity CFM range @.5 in. w.c. (125 Pa)
N8MXL Product Specifications 80% ECM Single Stage Heating Furnace EASIER TO SELL 80% AFUE Flame roll out sensors standard Category I venting Blocked vent switch 24 VAC humidifier terminal Electronic air
SECTION 23 81 43 HEAT PUMPS
SECTION 23 81 43 HEAT PUMPS PART 1 GENERAL 1.1 SUMMARY A. Section Includes: 1. Packaged rooftop heat pumps. 1.2 REFERENCES A. American Society of Heating, Refrigerating and Air-Conditioning Engineers:
GCS16 GCS20 WARNING CAUTION
Service Literature Corp. 0110 L6 Revised 12 2004 GCS16/GCS20 SERIES UNITS GCS16 GCS20 2 to 5 Ton GCS16/20 series units in the 2 to 5 ton (7.0 to 17.0 kw) cooling size are packaged combination gas heat
CE6500 Energy Recovery Ventilator
ADVANCED COMMERCIAL Energy Recovery Ventilator PRODUCT SPECIFICATIONS & TECHNICAL DATA Features NOMINAL CAPACITY 5500-7000 CFM CASING Double-wall cabinet White exterior paint, -gauge galvanized steel -gauge
HVAC Basic Science - System Capacity
HVAC Basic Science - System Capacity Btu/hour, btu/h, b/h, btuh. btu?? 1 MBH = 1000 btu/hour 1 KBH = 1000 btu/hour 1 ton of cooling= 12,000 btu/hour 1 watt = 3.414 btu/hour 1 kilowatt = 1000 watts = 3,414
Evaluate, Clean, and Tune Guidance
Evaluate, Clean, and Tune Guidance The Evaluate, Clean and Tune (ECT) process serves three essential purposes in the Weatherization Assistance Program (WAP). The first is to evaluate the existing system
XV 95. Upflow/ Horizontal Left, Downflow/ Horizontal Right Variable Speed Two Stage Condensing Gas-Fired Furnace PUB. NO.
Upflow/ Horizontal Left, Downflow/ Horizontal Right Speed Two Stage Condensing Gas-Fired Furnace XV 95 TUH2B060A9V3VB TUH2B080A9V3VB TUH2B080A9V4VB TUH2C100A9V4VB TUH2C100A9V5VB TUH2D120A9V5VB Direct Vent
Cooling Capacity CFM range @.5 in. w.c. (125 Pa)
96% AFUE, Two Stage ECM Gas Furnace EASIER TO SELL 96% AFUE, all models, all positions Two stage heating operation Xtra SEER ECM blower motor Supports two stage cooling units Dehumidification feature in
Bring the fresh in. Dedicated Outside Air Systems
Bring the fresh in. Dedicated Outside Air Systems The inside story on outside air. On average, we breathe in 3,400 gallons of air each day. Ambient indoor air pollution is a major problem, affecting health
Split System Cooling Product Data
Split System Cooling Product XL16i 1½ 5 Tons PUB. NO. 22-1890-01 Features and Benefits Climatuff compressor Efficiency up to 16.0 SEER and 9.0 HSPF All aluminum Spine Fin coil WeatherGuard fasteners Quick-Sess
VertiCool Space Saver 2 to 15 tons Water-Cooled and Chilled Water
2 to 15 tons Water-Cooled and Chilled Water Unique Solutions for Challenging HVAC Projects Your Choice for Limited Space Applications Water-Cooled Chilled Water The VertiCool Space Saver allows installation
Cooling Capacity CFM range @.5 in. w.c. (125 Pa)
96% AFUE, Single Stage, ECM Gas Furnace EASIER TO SELL 96% AFUE, all models all positions Xtra SEER ECM blower motor Supports two stage cooling units Dehumidification feature in cooling California NOx
TECHNICAL GUIDE 95.5% SINGLE STAGE GAS-FIRED RESIDENTIAL MULTI-POSITION GAS FURNACES MODELS: TG9S DESCRIPTION FEATURES
TECHNICAL GUIDE 95.5% SINGLE STAGE GAS-FIRED RESIDENTIAL MULTI-POSITION GAS FURNACES MODELS: TG9S NATURAL GAS 40-130 MBH INPUT Due to continuous product improvement, specifications are subject to change
USER S, MAINTENANCE and SERVICE INFORMATION MANUAL
CONTENTS SAFETY INFORMATION................ 2 FOR YOUR SAFETY....................... 2 SYSTEM OPERATION.................. 2 THERMOSTATS........................... 2 INTERMITTENT IGNITION DEVICE...........
FTQ. Daikin Inverter Ducted Heat Pump
FTQ Daikin Inverter Ducted Heat Pump A TRADITIONAL CENTRAL AIR SYSTEM MADE BETTER WITH DAIKIN CONSTANT COMFORT INVERTER TECHNOLOGY. The Daikin Inverter Ducted Heat Pump line is a cost effective alternative
MAC-120HE-01 Air-Cooled Chiller
MAC-120HE-01 Air-Cooled Chiller 10 Ton / 120,000 BTUH Air-Cooled Chiller 208/230-1-50/60 1 HVAC Guide Specifications Air-Cooled Liquid Chiller Nominal Size: 10 Tons Multiaqua Model Number: MAC-120HE-01
HIGH EFFICIENCY RTU. www.reznorhvac.com HIGH EFFICIENCY, PACKAGED SPACE CONDITIONING. DX System IEER> 13.2 Gas Heat Efficiency > 92% Capacities Tons
Capacities 10-25 Tons 100-400 MBH HIGH EFFICIENCY, PACKAGED SPACE CONDITIONING DX System IEER> 13.2 Gas Heat Efficiency > 92% HIGH EFFICIENCY RTU 30-120 kw 3,000-11,550 CFM Comfort Comfort is determined
Installation Instructions
05,06 Single Package, Displacement Ventilation or Single Zone Variable Airflow Rooftop Units Electric Cooling with PURONr (R---410A) Refrigerant and COMFORTLinkt Controls Installation Instructions IMPORTANT:
F9MXE. Product Specifications
96% AFUE, Single Stage, ECM Gas Furnace EASIER TO SELL 96% AFUE, all models all positions Select models earn the ENERGY STAR (See below, indicated with check mark.) Xtra SEER ECM blower motor Supports
Split System Cooling Product Data
Split System Cooling Product Data XR17 4TTR7 2, 3, 4 & 5 Tons PUB. NO. 22-1884-01 Features and Benefits CLIMATUFF 2-stage scroll compressor Efficiency up to 18.0 SEER All Aluminum SPINE FIN coil DURATUFF
Gas Unit Heaters Duct Furnaces Horizontal - 60 HZ Form No. LF24-100-400 (10/2011) LF24 Standard
LF Standard Features Horizontal unit heaters are compact in design and easy to install. Steady State Efficiencies of up to 80.%. Ideal for economical commercial heating systems. Shipped completely assembled
1. What percent of a commercial business s energy usage comes from their HVAC system? A. 13% B. 23% C. 33% D. 43% E. 53%
1 1. What percent of a commercial business s energy usage comes from their HVAC system? A. 13% B. 23% C. 33% D. 43% E. 53% 2. How much money do commercial facilities spend per square foot on energy costs
How To Buy A Lennox Power System
HVAC for Schools A Comprehensive Look at Products for a Clean, Comfortable Learning Environment Why Schools Choose Lennox Even as resources for schools continue to be constrained, education leaders and
The formula for finding CFM is: CFM = BTUH OUTPUT_ Temp Rise (ACF)* *Altitude correction factor below 1000ft = 1.08
Air Volume Requirement Air conditioning systems are engineered with a specific amount of indoor air passing across the surface of the evaporator coil. The amount of air is measured in cubic feet per minute.
Aluminum Cased Cooling Coils 2-5 Ton 4CXC PUB. NO. 22-1839-03
Aluminum Cased Cooling Coils 2-5 Ton 4CXC PUB. NO. 22-1839-03 Aluminum Cooling Coil Nomenclature 4 C X C B 0 3 6 C C 3 C U A A Refrigerant Type 4 - R410A Product Family T-Premium (Heat Pump or Convertible
SECTION 15732 AIR CONDITIONING UNIT
SECTION 15732 AIR CONDITIONING UNIT PART 1 GENERAL 1.01 SUMMARY A. Section includes: 1. Packaged, split system air conditioning unit No. 1. 1.02 REFERENCES A. Air-Conditioning, Heating, and Refrigeration
ARMSTRONG AIR HEAT PUMPS www.armstrongair.com
INDEX ELECTRIC FURNACE MODULAR AIR SYSTEM EFC/EFV... 5-10 electric Heat Kits... 5-11 evaporator coils EC1P / EM1P UPFLOW / COUNTERFLOW APPLICATIONS and upflow / horizontal applications (CASED)... 5-6 5-7
Mechanical Rooftop Custom Capabilities
Mechanical Rooftop Custom Capabilities Mechanical Construction Capabilities Price manufactures a wide range of custom gas heat and DX cooled units to meet your new construction and retrofit needs. In addition
1932 Lexington Houston, Texas 77098-4220 (713) 524-4877. Recommendations for installation of cooling systems
1932 Lexington Houston, Texas 77098-4220 (713) 524-4877 The purpose for this information is to provide a better understanding of the HVAC equipment, components, designs, and installations, of HVAC system
M SERIES REFRIGERANT COIL MODULE REFRIGERANT COILS for R-22, R-407C, R-410A
Bulletin 20-20.2 / July 2012 M SERIES REFRIGERANT COIL MODULE REFRIGERANT COILS for R-22, R-407C, R-410A ➀ ➁ ➂ Model Number Key M 2430 C L 1 - A - ➀ Unit Type M=Modular Nominal Capacity 2430=24000 to 30000
ModPac II 1 to 5-Ton Vertical Wall Mount Air Conditioners Models AVPA12-20-24-30-36-42-48-60
ModPac II 1 to 5-Ton Vertical Wall Mount Air Conditioners Models AVPA12-20-24-30-36-42-48-60 General Description The Marvair ModPac II air conditioner is a vertical, wall mounted, cost effective air conditioner
Heating Ventilation and Air Conditioning Diagnostics for Single Family Homes
Heating Ventilation and Air Conditioning Diagnostics for Single Family Homes Vincent Pedalino FSL Home Improvements Phoenix, AZ 1 HVAC Basics Ways to improve the performance of existing air conditioning
Lower Energy Costs with Rooftop Air-Conditioning Package Units
Lower Energy Costs with Rooftop Air-Conditioning Package Units Sponsored by Mike West, PhD, PE Advantek Consulting, Inc Package Unit Efficiency Factors Sensible and latent performance ratings Unit efficiency
G26 Corp. 9721-L11 Revised 07-2001 LENNOXOEMPARTS.COM. Service Literature G26 SERIES UNITS
Service Literature G26 SERIES UNITS G26 series units are high-efficiency upflow gas furnaces manufactured with DuralokPlust aluminized steel clamshell-type heat exchangers. G26 units are available in heating
GCS16-024-030-036-048-060
Packaged Unit & Gas Heat 2-5 Ton Capacity 50,000-120,000 Btuh Input Heating Capacity GCS16-024-030-036-048-060 FEATURES Designed for outdoor rooftop or ground level installations Down-flow or horizontal
K-Series Rooftop Units 60 HZ ASHRAE 90.1 COMPLIANT
PRODUCT SPECIFICATIONS PACKAGED GAS ELECTRIC KG K-Series Rooftop Units 60 HZ Bulletin No. KGA-092-50 (3/206) ASHRAE 90. COMPLIANT 7.5 to 2.5 Tons Net Cooling Capacity 86,000 to 38,000 Btuh Gas Input Heat
Split System Heat Pump Product Data
Split System Heat Pump Product Silver 14 4A6H4 1 1 /2-5 Tons PUB. NO. 12-1175-07 Contents Features and Benefits 2 Model Nomenclature 3 General 4 Product Specifications 4 A-weighted Sound Power Level [db(a)]
AIR HANDLERS AIR HANDLERS AIR HANDLERS. RHLA- High Efficiency. featuring R-22 Refrigerant. RHLL- High Efficiency
FORM NO. H11-52 REV. 3 Supersedes Form H11-52 Rev. 2 AIR HANDLERS AIR HANDLERS RHLA- Efficiency featuring R-22 Refrigerant RHLL- Efficiency featuring Earth-Friendly R-10A Refrigerant earth friendly refrigerant
NAVIEN AMERICA INC. 17855 FITCH AVENUE
Navien America Inc. Specification Details for the Navien models: CC-240 CC-240A For Potable Water Heating and Space Heating NAVIEN AMERICA INC. 17855 FITCH AVENUE IRVINE, CALIFORNIA, USA 92614 Toll Free:
Cased/Uncased Coils For Gas And Oil Furnaces
Indoor Coils Cased/Uncased Coils For Gas And Oil Furnaces RCFL- Series featuring Industry Standard R-410A Refrigerant Airflow Capacity 600-1,900 CFM [283-897 L/s] Rheem Indoor Coils are designed for use
Glossary of Heating, Ventilation and Air Conditioning Terms
Glossary of Heating, Ventilation and Air Conditioning Terms Air Change: Unlike re-circulated air, this is the total air required to completely replace the air in a room or building. Air Conditioner: Equipment
G9MXE. Product Specifications
Up to 96% AFUE, Single Stage, ECM Gas Furnace EASIER TO SELL Up to 96% AFUE, all models all positions California NOx approved Select models earn the ENERGY STAR (See below, indicated with check mark.)
INDOOR COILS. RCFM- featuring Earth-Friendly R-410A Refrigerant CASED/UNCASED COILS FOR GAS AND OIL FURNACES
FORM NO. C11-212 REV. 1 Supersedes Form No. C11-212 INDOOR COILS RCFM- featuring Earth-Friendly R-410A Refrigerant earth friendly refrigerant CASED/UNCASED COILS FOR GAS AND OIL FURNACES AIRFLOW CAPACITIES
ENGINEERING GUIDE. Water-Cooled Self-Contained Units C-Series, Vertical
ENGINEERING GUIDE Water-Cooled Self-Contained Units C-Series, Vertical TABLE OF CONTENTS Introduction...2 Product Overview...3 Nomenclature...4 General Data...5 Cooling Performance Data....6 Evaporator
Greensource iseries HY Model Unitary Air Handler/Fan Coil
Engineering Submittal Sheet Overview Model Nomenclature HY 035 00-1 HY - HYDRONIC AIR HANDLER NOMINAL CAPACITY IN THOUSANDS OF BTUH VOLTAGE DESIGNATION 1 = 208-230/1/60 ELECTRIC HEAT KW 00 - NO ELECTRIC
SASO XXXX:2016. (Including the modifications approved in Saudi Council Board No. XXX/2016) LARGE CAPACITY AIR CONDITIONERS
SASO XXXX:2016 (Including the modifications approved in Saudi Council Board No. XXX/2016) LARGE CAPACITY AIR CONDITIONERS PERFORMANCE REQUIREMENTS AND METHODS OF TESTING 1 LARGE CAPACITY AIR CONDITIONERS
INDOOR COILS. RCFA- featuring R-22 Refrigerant RCFL- featuring Earth-Friendly R-410A Refrigerant CASED/UNCASED COILS FOR GAS AND OIL FURNACES
FORM NO. C11-211 REV. 3 Supersedes Form No. C11-211 Rev. 2 INDOOR COILS RCFA- featuring R-22 Refrigerant RCFL- featuring Earth-Friendly R-410A Refrigerant earth friendly refrigerant CASED/UNCASED COILS
Explosion-Proof Electric Unit Heaters
Type FX4 FX4 Explosion-Proof Electric Air Heaters FX4 heaters are UL listed and/or CSA certified for use in hazardous locations. They are designed for dry indoor industrial applications such as oil refineries,
INDOOR COILS. RCFL- featuring Industry Standard R-410A Refrigerant CASED/UNCASED COILS FOR GAS AND OIL FURNACES
FORM NO. C11-211 REV. 7 Supersedes Form No. C11-211 Rev. 6 INDOOR COILS RCFL- featuring Industry Standard R-410A Refrigerant CASED/UNCASED COILS FOR GAS AND OIL FURNACES AIRFLOW CAPACITIES 600-1,900 CFM
HEATING AND COOLING SYSTEMS THAT FIT COMFORTABLY WITHIN YOUR BUDGET.
HEATING AND COOLING SYSTEMS THAT FIT COMFORTABLY WITHIN YOUR BUDGET. AFFORDABLE SOLUTIONS FROM AMERISTAR. We know that heating and cooling systems can be a major investment for homeowners. Our goal is
5.6 Technical Specification: Premium Efficiency Electric Air Conditioning Equipment
5.6 Technical Specification: Premium Efficiency Electric Conditioning Equipment Small Premium Project Type: For Premium Conditioning Retrofit Projects: Projects that voluntarily replace existing unitary
Energy Efficiency in Industrial HVAC Systems
Energy Efficiency in Industrial HVAC Systems Heating, ventilation and air conditioning (HVAC) constitutes up to 35 percent of energy used in manufacturing facilities. This fact sheet is geared towards
Service Facts. WARNING: HAZARDOUS VOLTAGE - DISCONNECT POWER and DISCHARGE 4TTM3-SF-1. Split System Cooling 4TTM3018-4TTM3060
4TTM3-SF-1 Service Facts Split System Cooling 4TTM3018-4TTM3060! CAUTION UNIT CONTAINS R-410A REFRIGERANT! R-410A OPERATING PRESSURE EXCEEDS THE LIMIT OF R-22. PROPER SERVICE EQUIPMENT IS REQUIRED. FAILURE
Installer s Guide 18-AH39D1-13
18-AH39D1-13 Cased Aluminum "Convertible" Coils 4TXCA018BC3HC** 4TXCA024BC3HC** 4TXCB025BC3HC** 4TXCB026BC3HC** 4TXCB031BC3HC** 4TXCB032BC3HC** ALL phases of this installation must comply with NATIONAL,
ROOFTOP - HEAT PUMP UNIT. This document applies when installing into an air handler or as part of an air handling system.
ROOFTOP - HEAT PUMP UNIT Technical data Applies to Model YNRA R410A This document applies when installing into an air handler or as part of an air handling system. CONTENTS 1. General description... 2
SECTION 23 00 01 HEATING, VENTILATION AND AIR CONDITIONING EQUIPMENT
SECTION 23 00 01 HEATING, VENTILATION AND AIR CONDITIONING EQUIPMENT PART 1 - GENERAL 1.1 DESCRIPTION A. The Work specified in this Section consists of designing, furnishing and installing factory-assembled
HVAC Simplified Approach Option
HVAC Simplified Approach Option Part I Project Address: City: HVAC System Designer of Record: Date: Zip: Qualification The building is 2 stories or less in height and has a gross floor area is less than
HVAC Systems: Overview
HVAC Systems: Overview Michael J. Brandemuehl, Ph.D, P.E. University of Colorado Boulder, CO, USA Overview System Description Secondary HVAC Systems Air distribution Room diffusers and air terminals Duct
york air-conditioning products Residential & VRF News 2015
york air-conditioning products Residential & VRF News 2015 york air-conditioning products Catalogue Content Split Systems Pag. High wall High Efficiency Inverter YWHJZH 09 to 24 K 6 High wall Inverter
Product Data. FV4C Performancet Series Fan Coil Sizes 002 Thru 006 PREMIUM ENVIRONMENTALLY SOUND FAN COIL
Performancet Series Fan Coil Sizes 002 Thru 006 Product Data PREMIUM ENVIRONMENTALLY SOUND FAN COIL The is the premium air handler combining the proven technology of Carrier fan coils with environmentally
Johnson Air-Rotation Systems
AR Series TM Johnson Air-Rotation Systems Solution TM D Series TM FF Series TM 80/20 PR Series TM Johnson Air-Rotation systems announces a major addition to its product line, completing its line of high
Split System Heat Pump Product Data
Split System Heat Pump Product Data XL20i 4TWZ0024, 036, 048 & 060 with ComfortLink II and Charge Assist 2, 3, 4 & 5 Tons PUB. NO. 22-1826-01 Features and Benefits Two Climatuff compressors Efficiency
TECHNICAL MANUAL GDS8 & GHS8
TECHNICAL MANUAL AL GDS8 & GHS8 33-3/8" 80% Gas Furnace Units Refer to Service Manual RS6610004 for installation, operation, and troubleshooting information. All safety information must be followed as
PACKAGE COOLING, PACKAGE HEAT PUMP & PACKAGE GAS UNITS
PACKAGE COOLING, PACKAGE HEAT PUMP & PACKAGE GAS UNITS SERVICE INSTRUCTIONS AMANA REFRIGERATION, INC., AMANA, IOWA 52204 MANUFACTURING NUMBERS COVERED IN THIS MANUAL SEE MODEL AND MANUFACTURING NUMBERS
DESCRIPTION TECHNICAL GUIDE SINGLE PACKAGE HEAT PUMP UNITS BQ 036, 048 & 060 254575-XTG-C-0109
TECHNICAL GUIDE SINGLE PACKAGE HEAT PUMP UNITS BQ 036, 048 & 060 3, 4 & 5 NOMINAL TONS (Export 50 Hz) DESCRIPTION YORK Sunline 2000 TM heat pumps are convertible single package units with a common cabinet
DESIGN STANDARDS SECTION 23 60 00
PART 1 - GENERAL 1.01 Work included: A. Piping, tubing and fittings. B. Piping specialties. C. Special duty valves. D. Refrigerants. E. Chillers. F. Refrigerant monitors. 1.02 General requirements: A.
Product Data. Split System Cooling 22-1904-1F-EN. March 2015
Product Data Split System Cooling 4TTR4018L1000A 4TTR4024L1000A 4TTR4025L1000A 4TTR4030L1000A 4TTR4031L1000A 4TTR4036L1000A 4TTR4037L1000A 4TTR4042L1000A 4TTR4043L1000A 4TTR4048L1000A 4TTR4060L1000A Note:
Presentation Outline. Common Terms / Concepts HVAC Building Blocks. Links. Plant Level Building Blocks. Air Distribution Building Blocks
Presentation Outline Common Terms / Concepts HVAC Building Blocks Plant Level Building Blocks Description / Application Data Green opportunities Selection Criteria Air Distribution Building Blocks same
INDOOR COILS. RCFN- featuring Industry Standard R-410A Refrigerant CASED/UNCASED COILS FOR GAS AND OIL FURNACES
FORM NO. C11-213 REV. 4 Supersedes Form No. C11-213 Rev. 3 INDOOR COILS RCFN- featuring Industry Standard R-410A Refrigerant CASED/UNCASED COILS FOR GAS AND OIL FURNACES AIRFLOW CAPACITIES 600-1,900 CFM
Residential/Commercial Gas Condensing High Efficiency Tankless Water Heaters
Residential/Commercial Gas Condensing High Efficiency Tankless Water Heaters FEATURES ULTRA-LOW NOx CONDENSING TECHNOLOGY PROVIDES UNPRECEDENTED 0.95 ENERGY FACTOR DURABLE HEAT EXCHANGER Primary Heat Exchanger
T CLASS ROOFTOP UNITS 60 HZ Bulletin No. 210392 August 2007 Supersedes May 2007
E N G I N E E R I N G D A T A P A C K A G E D G A S / E L E C T R I C TG T CLASS ROOFTOP UNITS 60 HZ Bulletin No. 210392 August 2007 Supersedes May 2007 MODEL NUMBER IDENTIFICATION ASHRAE 90.1 COMPLIANT
SPLIT-SYSTEM CONDENSING UNITS. 10.00 SEER HRA018 thru 060 (1.5 thru 5 Nominal Tons) DESCRIPTION FEATURES
550.46 -TG1Y (196) SPLIT-SYSTEM CONDENSING S 0 SEER HRA018 thru 060 (1.5 thru 5 Nominal Tons) DESCRIPTION The HRA Series condensing unit is the outdoor part of a versatile system of air conditioning. It
Split System Cooling Product Data
Split System Cooling Product Data 4TTB3018-060 1½ 5 Tons PUB. NO. 22-1843-14 Features and Benefits Efficiency up to 13.25 SEER All aluminum Spine Fin coil WeatherGuard fasteners Quick-Sess cabinet, easy
Energy Efficiency. Energy Efficient Home Cooling:
Energy Efficiency Energy Efficient Home Cooling: Choosing an air conditioning system is an important decision. A poor choice may be costly to purchase and operate and yet fail to provide the desired cooling
SECTION 11 78 13 MORTUARY REFRIGERATORS
PART 1 - GENERAL 1.1 DESCRIPTION SECTION 11 78 13 MORTUARY REFRIGERATORS SPEC WRITER NOTE: Delete between //---// if not applicable to project. Also delete any other item or paragraph not applicable in
THE WALL-MOUNT ONE TON AIR CONDITIONER GREEN REFRIGERANT R-410A. 10,800 Btuh 9.00 EER Right Side Control Panel. Engineered Features
THE WALL-MOUNT ONE TON AIR CONDITIONER W2A,800 Btuh 9.00 EER Right Side Control Panel 60Hz GREEN REFRIGERANT R-A The Bard Wall-Mount One Ton Air Conditioner is a self contained energy efficient heating
180, 210, AND 240 MODELS LCA PACKAGED COOLING & ELECTRIC HEAT LGA PACKAGED COOLING & GAS HEAT LHA PACKAGED HEAT PUMP
ENGINEERING DATA 180, 210, AND 240 MODELS LCA PACKAGED COOLING & ELECTRIC HEAT LGA PACKAGED COOLING & GAS HEAT LHA PACKAGED HEAT PUMP PACKAGED L SERIES 50hz 15, 17.5 & 20 Ton (52.8, 61.5 & 70.3 ) *Net
QUESTIONS TO ASK WHEN REPLACING YOUR HVAC TOGETHERWESAVE.COM
QUESTIONS TO ASK WHEN REPLACING YOUR HVAC TOGETHERWESAVE.COM TOGETHERWESAVE.COM IS IT TIME TO REPLACE YOUR HVAC SYSTEM? If your heating and cooling system is 15 to 20 years old and is experiencing problems,
AABC Specifications for Testing and Balancing HVAC Systems
AABC Specifications for Testing and Balancing HVAC Systems The Associated Air Balance Council (AABC) Total System Balancing Specifications for HVAC Testing, Balancing and Performance Verification TOTAL
Split System Heat Pump Product Data
Split System Heat Pump Product Data XR 13 4TWR3018-060 1½ 5 Tons PUB. NO. 22-1795-12 Features and Benefits Climatuff compressor All aluminum Spine Fin coil Quick-Sess cabinet, service access and refrigerant
Installation Manual. Rental Services. Air Handling Units CHS-SVN01A-EN. July 2008
Installation Manual Rental Services Air Handling Units July 2008 CHS-SVN01A-EN Copyright 2008 Trane All rights reserved This document and the information in it are the property of Trane and may not be
50LC Ultra High Efficiency Cooling Only/Electric Heat Packaged Rooftop 3 to 5 Nominal Tons Product Data
Ultra High Efficiency Cooling Only/Electric Heat Packaged Rooftop 3to5NominalTons Product Data C11536 Carrier s Most Efficient Commercial Rooftop Ever! TABLE OF CONTENTS PAGE UNIT FEATURES... 4 MODEL NUMBER
DESCRIPTION FEATURES HORIZONTAL DUCT HD. ISO 9001 Certified Quality Management System
TECHNICAL GUIDE ADD - ON COILS FOR USE WITH SPLIT-SYSTEM COOLING & HEAT PUMPS MODELS: MC, PC, FC, HD, UC 600-2000 CFM 1.5-5 TON COILS UPFLOW/DOWNFLOW FULL CASED FC UPFLOW PARTIAL CASED PC UPFLOW UNCASED
Packaged Rooftop Air Conditioners
Packaged Rooftop Air Conditioners IntelliPak Rooftops with Evaporative-Cooled Condensers 24-116 Tons 60 Hz June 2006 Introduction IntelliPak Rooftops with Evaporative-Cooled Condensers Why Choose IntelliPak
Commercial Packaged Rooftop Units 3- to 50-Ton LC/LG Models. Up to 17.0 SEER, Up to 12.8 EER
Commercial Packaged Rooftop Units 3- to 50-Ton LC/LG Models Up to 17.0 SEER, Up to 12.8 EER SAVING ENERGY WITH INTELLIGENCE Designed to intelligently achieve the lowest total cost of ownership Energence
Innovent LASER Packaged Fresh Air Conditioning Units
LASER Latent And Sensible Energy Reduction Latent And Sensible Energy Reduction For Outside Air Innovent LASER Packaged Fresh Air Conditioning Units Innovent LASER units provide both sensible and latent
PLP - TERMS AND CONDITIONS
PLP - TERMS AND CONDITIONS 2014-2015 Philadelphia Gas Works Residential Parts & Labor Plan Contract This Residential Parts & Labor Plan Contract (this Plan ) is available to customers of the Philadelphia
Product Data. FV4B Performancet Series Fan Coil Sizes 002 Thru 006 PREMIUM ENVIRONMENTALLY SOUND FAN COIL
Performancet Series Fan Coil Sizes 002 Thru 006 Product Data PREMIUM ENVIRONMENTALLY SOUND FAN COIL The is the premium air handler combining the proven technology of Carrier fan coils with environmentally
NEBB STANDARDS SECTION-8 AIR SYSTEM TAB PROCEDURES
NEBB STANDARDS SECTION-8 AIR SYSTEM TAB PROCEDURES 8.1 INTRODUCTION Testing, adjusting, and balancing of HVAC systems can best be accomplished by following a series of systematic procedures. The NEBB TAB