AIR HANDLERS AIR HANDLERS AIR HANDLERS. RHLA- High Efficiency. featuring R-22 Refrigerant. RHLL- High Efficiency

Size: px
Start display at page:

Download "AIR HANDLERS AIR HANDLERS AIR HANDLERS. RHLA- High Efficiency. featuring R-22 Refrigerant. RHLL- High Efficiency"

Transcription

1 FORM NO. H11-52 REV. 3 Supersedes Form H11-52 Rev. 2 AIR HANDLERS AIR HANDLERS RHLA- Efficiency featuring R-22 Refrigerant RHLL- Efficiency featuring Earth-Friendly R-10A Refrigerant earth friendly refrigerant AIR HANDLERS RHSA- Standard Efficiency featuring R-22 Refrigerant RHSL- Standard Efficiency featuring Earth-Friendly R-10A Refrigerant Features earth friendly refrigerant RHLA/RHLL feature GE s new X-13 motor which provides enhanced SEER performance with most Rheem outdoor units. 1 1 /2 ton [5.3 kw] through 5 ton [17.6 kw] models are between 2 1 /2 to 55 1 /2 inches [1080 to 110 mm] tall and 22 inches [559 mm] deep. Versatile -way convertible design for upflow, downflow, horizontal left and horizontal right applications. Factory-installed high efficiency indoor coil. All models meet or exceed 330 to 00 CFM [156 to 189 L/s] per ton at.3 inches [.7 kpa] of external static pressure. Enhanced airflow up to.7" external static pressure. Sturdy construction with 1.0 inch [.2 kpa] of reinforced foil faced jacket insulation for excellent thermal and sound insulation. Field-installed auxiliary electric heater kits provide exact heat for indoor comfort. Kits include circuit breakers which meet UL and cul requirements for service disconnect.

2 Engineering Features RHLA/RHLL/RHSA/RHSL- Series The most compact unit design available, all standard heat air handler models only 2 1 /2 to 55 1 /2 inches [1079 to 109 mm] high. Attractive pre-painted cabinet exterior. Rugged wall steel cabinet construction, designed for added strength and versatility. 1.0" foil faced insulation mechanically retained in blower compartment for excellent thermal and sound performance. Four leg blower motor mount. Blower housing with controls, motor and blower. Slide out design for service and maintenance convenience. Traditional open wire element design for heat applications. Field convertible for vertical downflow, horizontal left hand or right hand air supply. 3 combustible floor base accessories fit all model sizes when required for downflow installations on combustible floors. Indoor coil design provides low air side pressure drop, high performance and extremely compact size. Expansion valve on indoor coil provides for operation with air conditioning or heat pump using the same coil. Coils are constructed of aluminum fins bonded to internally grooved copper tubing. Molded polymer corrosion resistant condensate drain pan is provided on all indoor coils. Supply duct flanges provided as standard on air handler cabinet. Provisions for field electrical, connections available from either side or top of the air handler cabinet. Connection point for high voltage wiring is inside the air handler cabinet. voltage connection is made on the outside of the air handler cabinet. Concentric knockouts are provided for power connection to cabinet. Installer may pull desired hole size up to 2 inches [51 mm] for 1 1 /2 inch [38 mm] conduit. Front refrigerant and drain connections. GENERAL TERMS OF LIMITED WARRANTY Rheem will furnish a replacement for any part of this product which fails in normal use and service within the applicable periods stated, in accordance with the terms of the limited warranty. Indoor Coil leaks caused by factory defects...five (5) Years Electric Heating Element...Five (5) Years Any Other Part...Five (5) Years For Complete Details of the Limited Warranty, Including Applicable Terms and Conditions, See Your Local Installer or Contact the Manufacturer for a Copy. 2 Rheem Manufacturing Company

3 Identification R H L A HM 2 17 J A Design Variation A = 1st Design R H S A HM J A Voltage A = 115/1/60 J = 208/20/1/60 Cabinet Size 17 = 17.5" [31.8 mm] ( CFM) 21 = 21" [533. mm] ( CFM) 2 = 2.5" [609.6 mm] ( CFM) Capacity 2 = 18,000/2,000 BTU/H [5.27/7.03 kw] 36 = 30,000/36,000 BTU/H [6.79/10.55 kw] 8 = 2,000/8,000 BTU/H [12.31/1.06 kw] 60 = 60,000 BTU/H [17.58 kw] HM = A/C or HP Multi-Position (Vertical Upflow/Horizontal Left is the factory configuration) Refrigerant A = R-22 L = R-10A L = Efficiency (X-13 ) Classification H = Air Handler Rheem Design Variation A = 1st Design Voltage A = 115/1/60 D = 80V-3-60 J = 208/20/1/60 Cabinet Size 17 = 17.5" [31.8 mm] ( CFM) 21 = 21" [533. mm] ( CFM) 2 = 2.5" [609.6 mm] ( CFM) Capacity 18 = 18,000 BTU/H [5.27 kw] 2 = 2,000 BTU/H [7.03 kw] 30 = 30,000 BTU/H [8.79 kw] 36 = 36,000 BTU/H [10.55 kw] 2 = 2,000 BTU/H [12.31 kw] 8 = 8,000 BTU/H [1.06 kw] 60 = 60,000 BTU/H [17.58 kw] Available s at A Voltage RHSA(L)-HM1817AA RHSA(L)-HM217AA RHSA(L)-HM3017AA RHSA(L)-HM3617AA RHSA(L)-HM221AA RHSA(L)-HM821AA RHLA(L)-HM217AA RHLA(L)-HM3617AA RHLA(L)-HM821AA RHLA(L)-HM82AA RHLA(L)-HM602AA Available s at J Voltage RHSA(L)-HM1817JA RHSA(L)-HM217JA RHSA(L)-HM3017JA RHSA(L)-HM3617JA RHSA(L)-HM3621JA RHSA(L)-HM221JA RHSA(L)-HM821JA RHSA(L)-HM82JA RHSA(L)-HM602JA* RHLA(L)-HM217JA RHLA(L)-HM3617JA RHLA(L)-HM821JA RHLA(L)-HM82JA RHLA(L)-HM602JA Available s at D Voltage RHSA(L)-HM3617DA RHSA(L)-HM3621DA RHSA(L)-HM221DA RHSA(L)-HM821DA RHSA(L)-HM82DA RHSA(L)-HM602DA *RHSA(L)-HM602JA is ARI rated for three phase application only. Supply circuit protective devices may be fuses or HACR type circuit breakers. Largest motor load is included in single circuit and multiple circuit. If non-standard fuse size is specified, use the next larger fuse size. J Voltage (230V) single-phase air handler is designed to be used with single or three phase 230 volt power. In the case of connecting 3-phase power to the air handler terminal block, bring only two leads to the terminal block. Cap, insulate and fully secure the third lead. The air handlers are shipped from the factory with the proper indoor coil installed, and cannot be ordered without a coil. The air handlers do not have an internal filter rack. An external filter rack or other means of filtration is required. HM = A/C or HP, Multi-Position (Vertical Upflow/Horizontal Left is the factory configuration) Refrigerant A = R-22 L = R-10A S = Standard (PSC ) Classification H = Air Handler Rheem Rheem Manufacturing Company 3

4 Unit Dimensions ELECTRICAL CONNECTIONS MAY EXIT TOP OR EITHER SIDE HIGH VOLTAGE CONNECTION 7/8 [22.2 mm], 13/32 [27.8 mm], 131/32 [50 mm] DIA. KNOCKOUTS. SUPPLY AIR 10 5 /16 [262 mm] NOTE: 2 CLEARANCE REQUIRED IN FRONT OF UNIT FOR FILTER AND COIL MAINTENANCE. W LOW VOLTAGE CONNECTION 5/8 [15.9 mm] AND 7/8 [22.2 mm] KNOCKOUT A Return Air Opening Dimensions Cabinet Size Return Air Opening Width (Inches) Return Air Opening Depth/Length (Inches) / / / / / / H AUXILIARY DRAIN CONNECTION 3/ [19.1 mm] FEMALE PIPE THREAD (NPT) HORIZONTAL APPLICATION ONLY PRIMARY DRAIN CONNECTION 3/ [19.1 mm] FEMALE PIPE THREAD (NPT) AUXILIARY DRAIN CONNECTION 3/ [19.1 mm] FEMALE PIPE THREAD (NPT) UPFLOW/DOWNFLOW APPLICATION ONLY LIQUID LINE CONNECTION COPPER (SWEAT) 19 1 /2 [95 mm] RETURN AIR OPENING /16 [551 mm] VAPOR LINE CONNECTION COPPER (SWEAT) UPFLOW UNIT SHOWN: UNIT MAY BE INSTALLED UPFLOW, DOWNFLOW, HORIZONTAL RIGHT OR LEFT AIR SUPPLY. HORIZONTAL ADAPTER KIT VAPOR LINE CONNECTION AUXILIARY HORIZONTAL DRAIN CONNECTION 5 15 /16 [151 mm] 1 /8 [105 mm] 3 1 /16 [76 mm] 1 3 /16 [8 mm] 11 /8 [29 mm] 1 1 /16 [27 mm] 1 3 /8 [35 mm] 2 13 /16 [71 mm] 5 1 / [133 mm] 5 3 /8 [136 mm] PRIMARY DRAIN CONNECTION AUXILIARY UPFLOW/DOWNFLOW DRAIN CONNECTION LIQUID LINE CONNECTION VERTICAL DRAIN PAN ( ) Designates Unit with Double Coil Cabinet Unit Dimensions & Weights Unit Unit Supply Air Flow Unit Weight/Shipping Weight (Lbs.) [kg] Width Height Duct CFM (Nom.) [L/s] Size Unit With W In. [mm] H In. [mm] A In. [mm] Lo Hi Coil (Max. KW) 1817/ /2 [5] 2 1 /2 [1080] 16 1 /2 [06] 600 [283] 800 [378] 82/96 [37/] 3017/ /2 [5] 2 1 /2 [1080] 16 1 /2 [06] 1000 [72] 1200 [566] 92/106 [37/8] /2 [533] 2 1 /2 [1080] 19 1 /2 [95] 1200 [566] 97/112 [/51] 221/ /2 [533] 50 1 /2 [1282] 19 1 /2 [95] 100 [661] 1600 [755] 150/166 [68/75] /2 [622] 55 1 /2 [110] 23 1 /2 [58] 1600 [755] 162/180 [73/81] /2 [622] 55 1 /2 [110] 23 1 /2 [58] 1800 [850] 181/198 [82/90] Rheem Manufacturing Company

5 Airflow Directions UPFLOW DOWNFLOW HORIZONTAL LEFT HAND AIRFLOW HORIZONTAL RIGHT HAND AIRFLOW Rheem Manufacturing Company 5

6 Airflow Performance Airflow performance data is based on cooling performance with a coil and no filter in place. Select performance table for appropriate unit size, voltage and number of electric heaters to be used. Make sure external static applied to unit allows operation within the minimum and maximum limits shown in table below for both cooling and electric heat operation. For optimum blower performance, operate the unit in the.3 [8 mm] to.7 inches [18 mm] W.C. external static range. Units with coils should be applied with a minimum of.1 inch [3 mm] W.C. external static range. Airflow Operating Limits Cabinet Size Cooling BTUH x 1,000 Cooling Tons Nominal Heat Pump or Air Conditioning Maximum Heat/Cool CFM [L/s] (37.5 CFM [18 L/s]/1,000 BTUH) (50 CFM [212 L/s]/Ton Nominal) Heat Pump or Air Conditioning Nominal Heat/Cool CFM [L/s] (33.3 CFM [16 L/s]/1,000 BTUH) (00 CFM [189 L/s]/Ton Nominal) Heat Pump or Air Conditioning Minimum Heat/Cool CFM [L/s] (30.0 CFM [1 L/s]/1,255 BTUH) (360 CFM [170 L/s]/Ton Nominal) Maximum kw Electric Heating & Minimum Electric Heat CFM [L/s] [319] 600 [283] 50 [255] [236] [25] 800 [378] 720 [30] [307] [531] 1000 [72] 900 [25] [08] [637] 1200 [566] 1080 [510] [00] [73] 100 [661] 1260 [595] [566] [850] 1600 [755] 10 [680] [600] [850] 1600 [755] 10 [680] [600] Maximum Electric Heat Rise F [ C] 85 [29] 85 [29] 85 [29] 85 [29] 85 [29] 85 [29] 85 [29] [911] 1800 [850] 1620 [765] [821] 85 [29] 6 Rheem Manufacturing Company

7 Airflow Performance Data RHSA/RHSL (PSC ) No with 13 kw -217 No -217 with 13 kw No with 18 kw -3617/-3621 No from Factory Manufacturer Recommended Air-Flow Range (Min/Max) CFM 517/711 CFM [2/336 L/s] 67/661 CFM [230/312 L/s] 67/888 CFM [305/19 L/s] 617/638 CFM [291/395 L/s] 86/100 CFM [08/7 L/s] 81/90 CFM [38/27 L/s] 110/128 CFM [521/589 L/s] Blower Size/ HP [W] # of 1/5 HP [19] 1/5 HP [19] 1/5 HP [19] 1/5 HP [19] 1/ HP [186] 1/ HP [186] 11x8 1/3 HP [29] PSC CFM [L/s] Air Delivery/RPM/Watts 20 Volts External Static Pressure Inches W.C. [kpa] 0.1 [.02] 0.2 [.05] 0.3 [.07] 0. [.10] 0.5 [.12] 0.6 [.15] 0.7 [.17] CFM 668 [315] 637 [301] 595 [281] 560 [26] 517 [2] RPM Watts CFM 711 [336] 662 [312] 61 [290] RPM Watts CFM 638 [301] 607 [286] 565 [267] 530 [250] 87 [230] RPM Watts CFM 661 [312] 612 [289] 56 [266] RPM Watts CFM 817 [386] 779 [368] 757 [357] 693 [327] 67 [305] RPM Watts CFM 888 [19] 828 [391] 77 [365] RPM Watts CFM 787 [371] 79 [353] 727 [33] 663 [313] 617 [291] RPM Watts CFM 838 [395] 778 [367] 72 [32] RPM Watts CFM 1022 [82] 987 [66] 90 [] 903 [26] 86 [08] RPM Watts CFM 100 [7] 951 [9] 883 [17] RPM Watts CFM 972 [59] 937 [2] 890 [20] 853 [03] 81 [38] RPM Watts CFM 90 [27] 851 [02] 783 [370] RPM Watts CFM 1229 [580] 1201 [567] 1170 [552] 111 [538] 110 [521] RPM Watts CFM 128 [589] 119 [563] 1133 [535] RPM Watts Notes: The above airflow table lists the airflow information for air handlers without heater and air handler with maximum heater allowed for each model. The following formula can be used to calculation the approximate airflow, if a smaller (N kw) than the maximum heater kit is installed. Approximate Airflow = Airflow without heater (Airflow without heater Airflow with maximum heater) x (N kw/maximum heater kw) Rheem Manufacturing Company 7

8 Airflow Performance Data RHSA/RHSL (PSC ) (con t.) -3617/3621 with 18 kw -221 No -221 with 20 kw -821/-82 No -821/-82 with 25 kw -602 No -602 with 30 kw from Factory Manufacturer Recommended Air-Flow Range (Min/Max) CFM 105/118 CFM [97/52 L/s] 121/1537 CFM [586/725 L/s] 1225/1500 CFM [553/678 L/s] 1572/182 CFM [72/861 L/s] 1225/1500 CFM [709/81 L/s] 1766/1965 CFM [833/927 L/s] 1225/1500 CFM [709/81 L/s] Blower Size/ HP [W] # of 1/3 HP [29] 1/2 HP [373] 1/2 HP [373] 11x11 11x11 PSC CFM [L/s] Air Delivery/RPM/Watts 20 Volts External Static Pressure Inches W.C. [kpa] 0.1 [.02] 0.2 [.05] 0.3 [.07] 0. [.10] 0.5 [.12] 0.6 [.15] 0.7 [.17] CFM 1179 [556] 1151 [53] 1120 [529] 1091 [515] 105 [97] RPM Watts CFM 118 [52] 109 [516] 1033 [87] RPM Watts CFM 1526 [720] 17 [696] 127 [673] 1307 [617] 121 [586] RPM Watts CFM 1537 [725] 118 [669] 133 [630] RPM Watts CFM 156 [687] 10 [663] 1357 [60] 1237 [58] 1171 [553] RPM Watts CFM 137 [678] 1318 [622] 123 [582] RPM Watts CFM 171 [822] 1719 [811] 1667 [787] 1628 [768] 1572 [72] RPM Watts CFM 182 [861] 1767 [83] 1653 [780] RPM Watts CFM 1671 [789] 169 [778] 1597 [75] 1558 [735] 1502 [709] RPM Watts CFM 172 [81] 1667 [787] 1553 [733] RPM Watts CFM 19 [917] 1912 [902] 1860 [878] 1813 [856] 1766 [833] RPM Watts CFM 1965 [927] 1908 [900] 185 [875] RPM Watts CFM 18 [870] 1812 [855] 1760 [831] 1713 [808] 1666 [786] RPM Watts CFM 1865 [880] 1808 [853] 175 [828] RPM Watts Notes: The above airflow table lists the airflow information for air handlers without heater and air handler with maximum heater allowed for each model. The following formula can be used to calculation the approximate airflow, if a smaller (N kw) than the maximum heater kit is installed. Approximate Airflow = Airflow without heater (Airflow without heater Airflow with maximum heater) x (N kw/maximum heater kw) 8 Rheem Manufacturing Company

9 115/208/80V Airflow Performance Data RHSA/RHSL (PSC ) No with 13 kw -217 No -217 with 13 kw No with 18 kw -3617/-3621 No from Factory Manufacturer Recommended Air-Flow Range (Min/Max) CFM 523/705 CFM [27/333 L/s] 93/655 CFM [233/309 L/s] 682/897 CFM [322/23 L/s] 652/87CFM [308/00 L/s] 883/1015 CFM [17/79 L/s] 833/915 CFM [393/32 L/s] 1062/119 CFM [501/563 L/s] Blower Size/ HP [W] # of 1/5 HP [19] 1/5 HP [19] 1/5 HP [19] 1/5 HP [19] 1/ HP [186] 1/ HP [186] 1/3 HP [29] PSC CFM [L/s] Air Delivery/RPM/Watts 115/208/80 Volts External Static Pressure Inches W.C. [kpa] 0.1 [.02] 0.2 [.05] 0.3 [.07] 0. [.10] 0.5 [.12] 0.6 [.15] 0.7 [.17] CFM 681 [321] 636 [300] 606 [286] 567 [268] 523 [27] RPM Watts CFM 705 [333] 650 [307] 599 [283] RPM Watts CFM 651 [307] 606 [286] 576 [272] 537 [253] 93 [233] RPM Watts CFM 655 [309] 600 [283] 59 [259] RPM Watts CFM 875 [13] 806 [380] 787 [371] 739 [39] 682 [322] RPM Watts CFM 897 [23] 851 [02] 765 [361] RPM Watts CFM 85 [399] 776 [366] 757 [357] 709 [335] 652 [308] RPM Watts CFM 87 [00] 801 [378] 715 [337] RPM Watts CFM 1038 [90] 1010 [77] 976 [61] 925 [37] 883 [17] RPM Watts CFM 1015 [79] 963 [5] 890 [20] RPM Watts CFM 988 [66] 960 [53] 926 [37] 875 [13] 833 [393] RPM Watts CFM 915 [32] 863 [07] 790 [373] RPM Watts CFM 1201 [567] 1170 [552] 111 [538] 110 [521] 1062 [501] RPM Watts CFM 119 [563] 113 [535] 1078 [509] RPM Watts Notes: The above airflow table lists the airflow information for air handlers without heater and air handler with maximum heater allowed for each model. The following formula can be used to calculation the approximate airflow, if a smaller (N kw) than the maximum heater kit is installed. Approximate Airflow = Airflow without heater (Airflow without heater Airflow with maximum heater) x (N kw/maximum heater kw) Rheem Manufacturing Company 9

10 115/208/80V Airflow Performance Data RHSA/RHSL (PSC ) -3617/3621 with 18 kw -221 No -221 with 20 kw -821/-82 No -821/-82 with 25 kw -602 No -602 with 30 kw from Factory Manufacturer Recommended Air-Flow Range (Min/Max) CFM 1012/109 CFM [78/516 L/s] 1211/151 CFM [571/71 L/s] 1225/1500 CFM [538/667 L/s] 152/1787 CFM [728/83 L/s] 1225/1500 CFM [695/796 L/s] 1710/1967 CFM [807/928 L/s] 1225/1500 CFM [695/796 L/s] Blower Size/ HP [W] # of 1/3 HP [29] 1/2 HP [373] 1/2 HP [373] 11x11 11x11 PSC CFM [L/s] Air Delivery/RPM/Watts 115/208/80V Volts External Static Pressure Inches W.C. [kpa] 0.1 [.02] 0.2 [.05] 0.3 [.07] 0. [.10] 0.5 [.12] 0.6 [.15] 0.7 [.17] CFM 1151 [53] 1120 [529] 1091 [515] 105 [97] 1012 [78] - - RPM Watts CFM 109 [516] 103 [88] 978 [62] RPM Watts CFM 193 [705] 19 [68] 1363 [63] 1287 [607] 1211 [571] RPM Watts CFM 151 [71] 111 [666] 1315 [621] RPM Watts CFM 123 [672] 1379 [651] 1293 [610] 1217 [57] 111 [538] RPM Watts CFM 11 [667] 1311 [619] 1215 [573] RPM Watts CFM 1711 [807] 1689 [797] 1637 [773] 1598 [75] 152 [728] RPM Watts CFM 1787 [83] 1679 [792] 1575 [73] RPM Watts CFM 161 [77] 1619 [76] 1567 [739] 1528 [721] 172 [695] RPM Watts CFM 1687 [796] 1579 [75] 175 [696] RPM Watts CFM 1866 [881] 1833 [865] 1806 [852] 1772 [836] 1710 [807] RPM Watts CFM 1967 [928] 1916 [90] 1863 [879] RPM Watts CFM 1796 [88] 1763 [832] 1736 [819] 1702 [803] 160 [77] RPM Watts CFM 1867 [881] 1816 [857] 1763 [832] RPM Watts Notes: The above airflow table lists the airflow information for air handlers without heater and air handler with maximum heater allowed for each model. The following formula can be used to calculation the approximate airflow, if a smaller (N kw) than the maximum heater kit is installed. Approximate Airflow = Airflow without heater (Airflow without heater Airflow with maximum heater) x (N kw/maximum heater kw) 10 Rheem Manufacturing Company

11 115V/208V/ Airflow Performance Data RHLA/RHLL (X-13 ) -217 No -217 with 13 kw -217 No -217 with 13 kw No with 18 kw No with 18 kw Tonnage Application 1.5 Ton 1.5 Ton 2 Ton 2 Ton 2.5 Ton 2.5 Ton 3 Ton 3 Ton From Factory Manufacturer Recommended Air-Flow Range (Min/Max) CFM 509/681 CFM [20/321 L/s] 90/666 CFM [231/31 L/s] 730/651 CFM [35/307 L/s] 711/626CFM [336/295 L/s] 935/108 CFM [1/512 L/s] 910/1059 CFM [29/500 L/s] 1130/1275 CFM [533/602 L/s] 1105/1250 CFM [521/590 L/s] Blower Size/ HP [W] X-13 CFM [L/s] Air Delivery/RPM/Watts 115/208/20 Volts External Static Pressure Inches W.C. [kpa] # of 0.1 [.02] 0.2 [.05] 0.3 [.07] 0. [.10] 0.5 [.12] 0.6 [.15] 0.7 [.17] CFM 689 [325] 6 [30] 602 [28] 563 [266] 509 [20] 2 RPM Watts /3 HP [29] 5 CFM 681 [321] 6 [30] 603 [285] 3 RPM Watts CFM 670 [316] 625 [295] 583 [275] 5 [257] 90 [231] 2 RPM Watts /3 HP [29] 5 CFM 666 [31] 629 [297] 588 [277] 3 RPM Watts CFM 875 [13] 839 [396] 80 [379] 762 [360] 730 [35] RPM Watts /3 HP [29] 5 CFM 651 [307] 61 [290] 573 [270] 5 RPM Watts CFM 856 [0] 820 [387] 785 [370] 73 [351] 711 [336] RPM Watts /3 HP [29] 5 CFM 626 [295] 589 [278] 58 [259] 5 RPM Watts CFM 1093 [516] 1050 [96] 1017 [80] 977 [61] 935 [1] 2 RPM Watts /2 HP [373] 5 CFM 108 [512] 100 [91] 1001 [72] 3 RPM Watts CFM 1068 [50] 1025 [8] 992 [68] 952 [9] 910 [29] 2 RPM Watts /2 HP [373] 5 CFM 1059 [500] 1015 [79] 976 [61] 3 RPM Watts CFM 1270 [599] 1237 [58] 1199 [566] 1165 [550] 1130 [533] RPM Watts /2 HP [373] 5 CFM 1275 [602] 12 [587] 1211 [571] 5 RPM Watts CFM 125 [588] 1212 [572] 117 [55] 110 [538] 1105 [521] RPM Watts /2 HP [373] 5 CFM 1250 [590] 1219 [575] 1186 [560] 5 RPM Watts Notes: The above airflow table lists the airflow information for air handlers without heater and air handler with maximum heater allowed for each model. The following formula can be used to calculation the approximate airflow, if a smaller (N kw) than the maximum heater kit is installed. Approximate Airflow = Airflow without heater (Airflow without heater Airflow with maximum heater) x (N kw/maximum heater kw) Rheem Manufacturing Company 11

12 115/208/ Airflow Performance Data RHLA/RHLL (X-13 ) (con t.) -821 No -821 with 20 kw -821 No -821 with 25 kw -82 No -82 with 25 kw -602 No -602 with 30 kw Tonnage Application 3.5 Ton 3.5 Ton Ton Ton Ton Ton 5 Ton 5 Ton From Factory Manufacturer Recommended Air-Flow Range (Min/Max) CFM 1337/17 CFM [631/683 L/s] 1297/1333 CFM [612/629 L/s] 1535/165 CFM [72/781 L/s] 195/161 CFM [706/762 L/s] 155/1732 CFM [729/817 L/s] 1505/1692 CFM [710/798 L/s] 1739/1905 CFM [821/899 L/s] 1699/1865 CFM [802/880 L/s] Blower Size/ HP [W] # of x x x x PSC CFM [L/s] Air Delivery/RPM/Watts 115/208/20 Volts External Static Pressure Inches W.C. [kpa] 0.1 [.02] 0.2 [.05] 0.3 [.07] 0. [.10] 0.5 [.12] 0.6 [.15] 0.7 [.17] CFM 173 [695] 12 [681] 101 [661] 1373 [68] 1337 [631] RPM Watts CFM 17 [683] 133 [676] 102 [662] RPM Watts CFM 133 [676] 102 [662] 1361 [62] 1333 [629] 1297 [612] RPM Watts CFM 1333 [629] 1300 [613] 1267 [598] RPM Watts CFM 1665 [786] 1631 [770] 1601 [756] 1572 [72] 1535 [72] RPM Watts CFM 165 [781] 162 [766] 1563 [738] RPM Watts CFM 1625 [767] 1591 [751] 1561 [737] 1532 [723] 195 [706] RPM Watts CFM 161 [762] 158 [78] 1523 [719] RPM Watts CFM 178 [825] 1669 [788] 1639 [773] 1599 [755] 155 [729] RPM Watts CFM 1732 [817] 1683 [79] 1630 [769] RPM Watts CFM 1708 [806] 1629 [769] 1599 [755] 1559 [736] 1505 [710] RPM Watts CFM 1692 [798] 163 [775] 1590 [750] RPM Watts CFM 1902 [898] 1862 [879] 1809 [85] 1781 [80] 1739 [821] RPM Watts CFM 1905 [899] 1866 [881] 1832 [865] RPM Watts CFM 1862 [879] 1822 [860] 1769 [835] 171 [822] 1699 [802] RPM Watts CFM 1865 [880] 1826 [862] 1792 [86] RPM Watts Notes: The above airflow table lists the airflow information for air handlers without heater and air handler with maximum heater allowed for each model. The following formula can be used to calculation the approximate airflow, if a smaller (N kw) than the maximum heater kit is installed. Approximate Airflow = Airflow without heater (Airflow without heater Airflow with maximum heater) x (N kw/maximum heater kw) 12 Rheem Manufacturing Company

13 RHSA/RHSL Electrical Data Blower Only No Electric Heat Cooling Capacity Tons Voltage Application Phase* Hertz HP [W] RPM s Amps. Minimum Ampacity 1 1 /2 1/5 [19] /5 [19] /2 1/ [186] /3 [29] /2 1/2 [373] / [559] /2 1/5 [19] /5 [19] /2 1/ [186] /20 1 & /3 [29] /2 1/2 [373] / [559] / / [559] /3 [29] / /3 [29] / [559] / [559] * Blower motors are all single phase motors. Maximum Protector RHLA/RHLL Electrical Data Blower Only No Electric Heat Cooling Capacity Tons 1 1 /2 & 2 Voltage Application Phase* Hertz HP [W] RPM s Amps. Minimum Ampacity 1/3 [29] /2 & 3 1/2 [373] /20 1 & /2 & 3/ [559] / [559] /2 & 2 1/3 [29] /2 & 3 1/2 [373] /2 & 3/ [559] / [559] * Blower motors are all single phase motors. Maximum Protector Rheem Manufacturing Company 13

14 RHSA/RHSL Electrical Data with Electric Heat Installation of the U.L. Listed original equipment manufacturer provided heater kits listed in the table below is recommended for all auxiliary heating requirements. Nominal Cooling Capacity Tons/ Cabinet Size 1 1/2 & 2/ /2 & 3/ 17 3/ 21 Rheem RXBH-17A03J RXBH-17A05J RXBH-17A07J kw 208/. PH/Hz Elements - kw Per Amps. Ampacity Minimum Ampacity Maximum Protection 2.25/3.0 1/ SINGLE 10.8/ /18 20/20 3.6/.8 1/ SINGLE 17.3/ /28 25/30 5./7.2 1/ SINGLE 26.0/ /0 35/0 RXBH-17A10J 7.2/9.6 1/ SINGLE 3.6/ /53 50/60 RXBH-17A13J 9./12.5 1/ SINGLE 5.1/ /68 60/70 RXBH-17A13J 3.1/.2 1/ MULTIPLE CKT / /2 25/25 6.3/8.3 1/ MULTIPLE CKT / / 0/5 RXBH-17A07C 5./7.2 3/ SINGLE 15.0/ /2 25/25 RXBH-17A10C 7.2/9.6 3/ SINGLE 20.0/ /31 30/35 RXBH-17A13C 9./12.5 3/ SINGLE 26.1/ /0 35/0 RXBH-17A03J 2.25/3.0 1/ SINGLE 10.8/ /19 20/20 RXBH-17A05J 3.6/.8 1/ SINGLE 17.3/ /29 25/30 RXBH-17A07J 5./7.2 1/ SINGLE 26.0/ /1 0/5 RXBH-17A10J 7.2/9.6 1/ SINGLE 3.6/ /5 50/60 RXBH-17A13J 9./12.5 1/ SINGLE 5.1/ /69 60/70 RXBH-17A13J 3.1/.2 1/ MULTIPLE CKT / /25 25/25 6.3/8.3 1/ MULTIPLE CKT / / 0/5 RXBH-17A15J 10.8/1. 1/ SINGLE 51.9/ /79 70/80 RXBH-17A15J 3.6/.8 1/ MULTIPLE CKT / /29 25/30 7.2/9.6 1/ MULTIPLE CKT 2 3.6/0.0 0 /50 5/50 RXBH-17A18J 12.8/17.0 1/ SINGLE 61.6/ /92 90/100 RXBH-17A18J.3/5.7 1/ MULTIPLE CKT / /33 30/35 8.5/11.3 1/ MULTIPLE CKT 2 1.1/ /59 60/60 RXBH-17A07C 5./7.2 3/ SINGLE 15.0/ /25 25/25 RXBH-17A10C 7.2/9.6 3/ SINGLE 20.0/ /32 30/35 RXBH-17A13C 9./12.5 3/ SINGLE 26.1/ /1 0/5 RXBH-17A15C 10.8/1. 3/ SINGLE 30.0/ /7 5/50 RXBH-17A18C 12.8/17.0 3/ SINGLE 35.5/ /55 50/60 RXBH-17A07D 7.2 3/ SINGLE RXBH-17A10D 9.6 3/ SINGLE RXBH-17A15D 1. 3/ SINGLE RXBH-17A18D 17 3/ SINGLE RXBH-2A05J 3.6/.8 1/ SINGLE 17.3/ /29 25/30 RXBH-2A07J 5./7.2 1/ SINGLE 26.0/ /1 0/5 RXBH-2A10J 7.2/9.6 1/ SINGLE 3.6/ /5 50/60 RXBH-2A15J 10.8/1. 1/ SINGLE 51.9/ /79 70/80 RXBH-2A15J 3.6/.8 1/ MULTIPLE CKT / /29 25/30 7.2/9.6 1/ MULTIPLE CKT 2 3.6/0.0 0 /50 5/50 RXBH-2A18J 12.8/17.0 1/ SINGLE 61.6/ /92 90/100 RXBH-2A18J 6./8.5 1/ MULTIPLE CKT / /8 5/50 6./8.5 1/ MULTIPLE CKT / /5 0/5 RXBH-2A07C 5./7.2 3/ SINGLE 15.0/ /25 25/25 RXBH-2A10C 7.2/9.6 3/ SINGLE 20.0/ /32 30/35 RXBH-2A15C 10.8/1. 3/ SINGLE 30.0/ /7 5/50 RXBH-2A18C 12.8/17.0 3/ SINGLE 35.5/ /55 50/60 RXBH-2A07D 7.2 3/ SINGLE RXBH-2A10D 9.6 3/ SINGLE RXBH-2A15D 1. 3/ SINGLE RXBH-2A18D 17 3/ SINGLE Supply circuit protective devices may be fused or HACR type circuit breakers. If non-standard fuse size is specified, use next size larger standard fuse size. If the kit is listed under both single and multiple circuits, the kit is shipped from factory as multiple circuits. For single phase application, Jumper bar kit RXBJ-A21 and RXBJ-A31 can be used to convert multiple circuits to a single supply circuit. Refer to Accessory Section for details. Largest motor load is included in single circuit or circuit 1 of multiple circuit. loads are balanced on 3 PH. models with 3 or 6 heaters only. Electric heater BTUH - (heater watts + motor watts) x 3.1 (see airflow table for motor watts.) No electrical heating elements are permitted to be used with A voltage (115V) air handler. J voltage (230V) single phase air handler is designed to be used with single or three phase 230 volt electric heaters. In the case of connecting 3 phase power to air handler terminal block without the heater, bring only two leads to terminal block. Cap, insulate and fully secure the third lead. Do not use 80 volts electrical heaters on 230 volts air handlers. Do not use 230 volts electrical heaters on 80 volts air handlers. 1 Rheem Manufacturing Company

15 RHSA/RHSL Electrical Data with Electric Heat (con t.) Installation of the U.L. Listed original equipment manufacturer provided heater kits listed in the table below is recommended for all auxiliary heating requirements. Nominal Cooling Capacity Tons/ Cabinet Size 3 1/2 & / 21 and / 2 5/ 2 kw 208/. PH/Hz Elements - kw Per Amps. Ampacity Minimum Ampacity Maximum Protection RXBH-2A05J 3.6/.8 1/ SINGLE 17.3/ /30 30/30 RXBH-2A07J 5./7.2 1/ SINGLE 26.0/ /3 0/5 RXBH-2A10J 7.2/9.6 1/ SINGLE 3.6/ /55 50/60 RXBH-2A15J 10.8/1. 1/ SINGLE 51.9/ /80 70/80 RXBH-2A15J 3.6/.8 1/ MULTIPLE CKT / /30 30/30 7.2/9.6 1/ MULTIPLE CKT 2 3.6/ /50 5/50 RXBH-2A18J 12.8/17 1/ SINGLE 61.6/ /9 90/100 RXBH-2A18J 6./8.5 1/ MULTIPLE CKT /35..0 /50 5/50 6./8.5 1/ MULTIPLE CKT / /5 0/5 RXBH-2A20J 1./19.2 1/ SINGLE 69.2/ / /110 RXBH-2A20J 7.2/9.6 1/ MULTIPLE CKT 1 3.6/ /55 50/60 7.2/9.6 1/ MULTIPLE CKT 2 3.6/ /50 5/50 RXBH-2A25J 18.0/2.0 1/ SINGLE 86./ / /150 RXBH-2A25J (-ton only) 6.0/8.0 1/ MULTIPLE CKT / /7 5/50 6.0/8.0 1/ MULTIPLE CKT / /2 0/5 6.0/8.0 1/ MULTIPLE CKT / /2 0/5 RXBH-2A07C 5./7.2 3/ SINGLE 15.0/ /27 25/30 RXBH-2A10C 7.2/9.6 3/ SINGLE 20.0/ /3 30/35 RXBH-2A15C 10.8/1. 3/ SINGLE 30.0/ /9 5/50 RXBH-2A18C 12.8/17.0 3/ SINGLE 35.6/ /57 50/60 RXBH-2A20C 1./19.2 3/ SINGLE 0.0/ /63 60/70 RXBH-2A20C 7.2/9.6 3/ MULTIPLE CKT / /3 30/35 7.2/9.6 3/ MULTIPLE CKT / /29 25/30 RXBH-2A25C 18.0/2.0 3/ SINGLE 50.0/ /78 70/80 RXBH-2A25C (-ton only) 9.0/12.0 3/ MULTIPLE CKT / /2 0/5 9.0/12.0 3/ MULTIPLE CKT / /37 35/0 RXBH-2A07D 7.2 3/ SINGLE RXBH-2A10D 9.6 3/ SINGLE RXBH-2A15D 1. 3/ SINGLE RXBH-2A18D 17 3/ SINGLE RXBH-2A20D / SINGLE RXBH-2A25D (-ton only) 2.0 3/ SINGLE RXBH-2A07C 5./7.2 3/ SINGLE 15.0/ /28 25/30 RXBH-2A10C 7.2/9.6 3/ SINGLE 20.0/ /35 35/35 RXBH-2A15C 10.8/1. 3/ SINGLE 30.0/3.6. 3/9 5/50 RXBH-2A18C 12.8/17.0 3/ SINGLE 35.6/ /57 50/60 RXBH-2A20C 1./19.2 3/ SINGLE 0.0/ /6 60/70 RXBH-2A20C 7.2/9.6 3/ MULTIPLE CKT / /35 35/35 7.2/9.6 3/ MULTIPLE CKT / /29 25/30 RXBH-2A25C 18.0/2.0 3/ SINGLE 50.0/ /78 70/80 RXBH-2A25C 9.0/12.0 3/ MULTIPLE CKT / /2 0/5 9.0/12.0 3/ MULTIPLE CKT / /37 35/0 RXBH-2A30C 21.6/28.8 3/ SINGLE 60.0/ /93 90/100 RXBH-2A30C 10.8/1. 3/ MULTIPLE CKT /3.7. 3/9 5/ /1. 3/ MULTIPLE CKT / / 0/5 RXBH-2A07D 7.2 3/ SINGLE RXBH-2A10D 9.6 3/ SINGLE RXBH-2A15D 1. 3/ SINGLE RXBH-2A18D 17 3/ SINGLE RXBH-2A20D / SINGLE RXBH-2A25D 2.0 3/ SINGLE RXBH-2A30D / SINGLE Supply circuit protective devices may be fused or HACR type circuit breakers. If non-standard fuse size is specified, use next size larger standard fuse size. If the kit is listed under both single and multiple circuits, the kit is shipped from factory as multiple circuits. For single phase application, Jumper bar kit RXBJ-A21 and RXBJ-A31 can be used to convert multiple circuits to a single supply circuit. Refer to Accessory Section for details. Largest motor load is included in single circuit or circuit 1 of multiple circuit. loads are balanced on 3 PH. models with 3 or 6 heaters only. Electric heater BTUH - (heater watts + motor watts) x 3.1 (see airflow table for motor watts.) No electrical heating elements are permitted to be used with A voltage (115V) air handler. J voltage (230V) single phase air handler is designed to be used with single or three phase 230 volt electric heaters. In the case of connecting 3 phase power to air handler terminal block without the heater, bring only two leads to terminal block. Cap, insulate and fully secure the third lead. Do not use 80 volts electrical heaters on 230 volts air handlers. Do not use 230 volts electrical heaters on 80 volts air handlers. Rheem Manufacturing Company 15

16 RHLA/RHLL Electrical Data with Electric Heat Installation of the U.L. Listed original equipment manufacturer provided heater kits listed in the table below is recommended for all auxiliary heating requirements. Nominal Cooling Capacity Tons/ Cabinet Size 1 1 /2 & 2/ /2 & 3/ /2 & / 21 Rheem KW 208/ PH/HZ Elements - KW Per Type Supply Single Multiple Amps. Ampacity Minimum Ampacity Maximum Protection RXBH-17A03J 2.25/3.0 1/ SINGLE 10.8/ /18 20/20 RXBH-17A05J 3.6/.8 1/ SINGLE 17.3/ /27 25/30 RXBH-17A07J 5./7.2 1/ SINGLE 26.0/ /0 35/0 RXBH-17A10J 7.2/9.6 1/ SINGLE 3.6/ /52 50/60 RXBH-17A13J 9./12.5 1/ SINGLE 5.1/ /68 60/70 RXBH-17A13J 3.1/.2 1/ MULTIPLE CKT / /2 25/25 6.3/8.3 1/ MULTIPLE CKT / / 0/5 RXBH-17A07C 5./7.2 3/ SINGLE 15.0/ /2 25/25 RXBH-17A10C 7.2/9.6 3/ SINGLE 20.0/ /31 30/35 RXBH-17A13C 9./12.5 3/ SINGLE 26.1/ /0 35/0 RXBH-17A03J 2.25/3.0 1/ SINGLE 10.8/ /19 20/20 RXBH-17A05J 3.6/.8 1/ SINGLE 17.3/ /29 25/30 RXBH-17A07J 5./7.2 1/ SINGLE 26.0/ /1 0/5 RXBH-17A10J 7.2/9.6 1/ SINGLE 3.6/ /5 50/60 RXBH-17A13J 9./12.5 1/ SINGLE 5.1/ /69 60/70 RXBH-17A13J 3.1/.2 1/ MULTIPLE CKT / /26 25/30 6.3/8.3 1/ MULTIPLE CKT / / 0/5 RXBH-17A15J 10.8/1. 1/ SINGLE 51.9/ /79 70/80 RXBH-17A15J 3.6/.8 1/ MULTIPLE CKT / /29 25/30 7.2/9.6 1/ MULTIPLE CKT 2 3.6/0.0 0 /50 5/50 RXBH-17A18J 12.8/17.0 1/ SINGLE 61.6/ /92 90/100 RXBH-17A18J.3/5.7 1/ MULTIPLE CKT / /33 30/35 8.5/11.3 1/ MULTIPLE CKT 2 1.1/ /59 60/60 RXBH-17A07C 5./7.2 3/ SINGLE 15.0/ /25 25/25 RXBH-17A10C 7.2/9.6 3/ SINGLE 20.0/ /33 30/35 RXBH-17A13C 9./12.5 3/ SINGLE 26.1/ /1 0/5 RXBH-17A15C 10.8/1. 3/ SINGLE 30.0/ /7 5/50 RXBH-17A18C 12.8/17.0 3/ SINGLE 35.5/ /55 50/60 RXBH-2A05J 3.6/.8 1/ SINGLE 17.3/ /30 30/30 RXBH-2A07J 5./7.2 1/ SINGLE 26.0/ /3 0/5 RXBH-2A10J 7.2/9.6 1/ SINGLE 3.6/ /55 50/60 RXBH-2A15J 10.8/1. 1/ SINGLE 51.9/ /80 70/80 RXBH-2A15J 3.6/.8 1/ MULTIPLE CKT / /30 30/30 7.2/9.6 1/ MULTIPLE CKT 2 3.6/ /50 5/50 RXBH-2A18J 12.8/17 1/ SINGLE 61.6/ /9 90/100 RXBH-2A18J 6./8.5 1/ MULTIPLE CKT / /9 5/50 6./8.5 1/ MULTIPLE CKT / /5 0/5 RXBH-2A20J 1./19.2 1/ SINGLE 69.2/ / /110 RXBH-2A20J 7.2/9.6 1/ MULTIPLE CKT 1 3.6/ /55 50/60 7.2/9.6 1/ MULTIPLE CKT 2 3.6/ /50 5/50 RXBH-2A25J 18.0/2.0 1/ SINGLE 86./ / / /8.0 1/ MULTIPLE CKT / /7 5/50 RXBH-2A25J 6.0/8.0 1/ MULTIPLE CKT / /2 0/5 (-ton only) 6.0/8.0 1/ MULTIPLE CKT / /2 0/5 RXBH-2A07C 5./7.2 3/ SINGLE 15.0/ /27 25/30 RXBH-2A10C 7.2/9.6 3/ SINGLE 20.0/ /3 30/35 RXBH-2A15C 10.8/1. 3/ SINGLE 30.0/ /8 5/50 RXBH-2A18C 12.8/17.0 3/ SINGLE 35.6/ /56 50/60 RXBH-2A20C 1./19.2 3/ SINGLE 0.0/ /63 60/70 RXBH-2A20C 7.2/9.6 3/ MULTIPLE CKT / /3 30/35 7.2/9.6 3/ MULTIPLE CKT / /29 25/30 RXBH-2A25C 18.0/2.0 3/ SINGLE 50.0/ /77 70/80 RXBH-2A25C (-ton only) Supply circuit protective devices may be fused or HACR type circuit breakers. If non-standard fuse size is specified, use next size larger standard fuse size. If the kit is listed under both single and multiple circuits, the kit is shipped from factory as multiple circuits. For single phase application, Jumper bar kit RXBJ-A21 and RXBJ-A31 can be used to convert multiple circuits to a single supply circuit. Refer to Accessory Section for details. Largest motor load is included in single circuit or circuit 1 of multiple circuit. loads are balanced on 3 PH. models with 3 or 6 heaters only. Electric heater BTUH - (heater watts + motor watts) x 3.1 (see airflow table for motor watts.) 9.0/12.0 3/ MULTIPLE CKT / /1 0/5 9.0/12.0 3/ MULTIPLE CKT / /37 35/0 No electrical heating elements are permitted to be used with A voltage (115V) air handler. J voltage (230V) single phase air handler is designed to be used with single or three phase 230 volt electric heaters. In the case of connecting 3 phase power to air handler terminal block without the heater, bring only two leads to terminal block. Cap, insulate and fully secure the third lead. Do not use 80 volts electrical heaters on 230 volts air handlers. Do not use 230 volts electrical heaters on 80 volts air handlers. 16 Rheem Manufacturing Company

17 RHLA/RHLL Electrical Data with Electric Heat (con t.) Installation of the U.L. Listed original equipment manufacturer provided heater kits listed in the table below is recommended for all auxiliary heating requirements. Nominal Cooling Capacity Tons/ Cabinet Size & 5/ 2 Rheem KW 208/ PH/HZ Elements - KW Per Type Supply Single Multiple Amps. Ampacity Minimum Ampacity Maximum Protection RXBH-2A07J 5./7.2 1/ SINGLE 26.0/ / 0/5 RXBH-2A10J 7.2/9.6 1/ SINGLE 3.6/ /56 50/60 RXBH-2A15J 10.8/1. 1/ SINGLE 51.9/ /81 80/90 RXBH-2A15J 3.6/.8 1/ MULTIPLE CKT / /31 30/35 7.2/9.6 1/ MULTIPLE CKT 2 3.6/0.0 0 /50 5/50 RXBH-2A18J 12.8/17 1/ SINGLE 61.6/ /95 90/100 RXBH-2A18J 6./8.5 1/ MULTIPLE CKT / /50 5/50 6./8.5 1/ MULTIPLE CKT / /5 0/5 RXBH-2A20J 1./19.2 1/ SINGLE 69.2/ / /110 RXBH-2A20J 7.2/9.6 1/ MULTIPLE CKT 1 3.6/ /56 50/60 7.2/9.6 1/ MULTIPLE CKT 2 3.6/0.0 0 /50 5/50 RXBH-2A25J 18.0/2.0 1/ SINGLE 86./ / / /8.0 1/ MULTIPLE CKT / /8 5/50 RXBH-2A25J 6.0/8.0 1/ MULTIPLE CKT / /2 0/5 6.0/8.0 1/ MULTIPLE CKT / /2 0/5 RXBH-2A30J 21.6/28.8 1/ SINGLE 103.8/ / / /9.6 1/ MULTIPLE CKT 1 3.6/ /56 50/60 RXBH-2A30J 7.2/9.6 1/ MULTIPLE CKT 2 3.6/0.0 0 /50 5/50 (5-ton only) 7.2/9.6 1/ MULTIPLE CKT 3 3.6/0.0 0 /50 5/50 RXBH-2A07C 5./7.2 3/ SINGLE 15.0/ /28 25/30 RXBH-2A10C 7.2/9.6 3/ SINGLE 20.0/ /35 35/35 RXBH-2A15C 10.8/1. 3/ SINGLE 30.0/3.6.6 /9 5/50 RXBH-2A18C 12.8/17.0 3/ SINGLE 35.6/ /57 60/60 RXBH-2A20C 1./19.2 3/ SINGLE 0.0/ /6 60/70 RXBH-2A20C 7.2/9.6 3/ MULTIPLE CKT / /35 35/35 7.2/9.6 3/ MULTIPLE CKT / /29 25/30 RXBH-2A25C 18.0/2.0 3/ SINGLE 50.0/ /78 70/80 RXBH-2A25C 9.0/12.0 3/ MULTIPLE CKT / /2 0/5 9.0/12.0 3/ MULTIPLE CKT / /37 35/0 RXBH-2A30C 21.6/28.8 3/ SINGLE 60.0/ /93 90/100 RXBH-2A30C (5-ton only) 10.8/1. 3/ MULTIPLE CKT /3.7.6 /50 5/ /1. 3/ MULTIPLE CKT / / 0/5 Supply circuit protective devices may be fused or HACR type circuit breakers. If non-standard fuse size is specified, use next size larger standard fuse size. If the kit is listed under both single and multiple circuits, the kit is shipped from factory as multiple circuits. For single phase application, Jumper bar kit RXBJ-A21 and RXBJ-A31 can be used to convert multiple circuits to a single supply circuit. Refer to Accessory Section for details. Largest motor load is included in single circuit or circuit 1 of multiple circuit. loads are balanced on 3 PH. models with 3 or 6 heaters only. Electric heater BTUH - (heater watts + motor watts) x 3.1 (see airflow table for motor watts.) No electrical heating elements are permitted to be used with A voltage (115V) air handler. J voltage (230V) single phase air handler is designed to be used with single or three phase 230 volt electric heaters. In the case of connecting 3 phase power to air handler terminal block without the heater, bring only two leads to terminal block. Cap, insulate and fully secure the third lead. Do not use 80 volts electrical heaters on 230 volts air handlers. Do not use 230 volts electrical heaters on 80 volts air handlers. Rheem Manufacturing Company 17

18 Electrical Wiring: Power Wiring Field wiring must comply with the National Electrical Code (C.E.C. in Canada) and any applicable local ordinance. Supply wiring must be 75 C minimum copper conductors only. See electrical data for product Ampacity rating and Protector requirement. Grounding This product must be sufficiently grounded in accordance with National Electrical Code (C.E.C. in Canada) and any applicable local ordinance. A grounding lug is provided. Accessories-Kits Parts Combustible Floor Base RXHB- Cabinet Size Jumper Bar Kit 3 Ckt. to 1 Ckt. RXBJ-A31 is used to convert single phase multiple three circuit units to a single supply circuit. Kit includes cover and screw for line side terminals. Jumper Bar Kit 2 Ckt. to 1 Ckt. RXBJ-A21 is used to convert single phase multiple two circuit units to a single supply circuit. Kit includes cover and screw for line side terminals. Note: No jumper bar kit is available to convert three phase multiple two circuit units to a single supply circuit. Auxiliary Horizontal Overflow Pan Accessory RXBM- Nominal Cooling Capacity-Tons External Filter Rack RXHF-B17, B21, B2 Cabinet Size *Accommodates 1" filter Filter Size In. [mm] x 20 [06 x 508] x 20 [508 x 508] 2 25 x 20 [635 x 508] Combustible Floor Base Number RXHB-17 RXHB-21 RXHB-2 Auxiliary Horizontal Overflow Pan Accessory Number 1 1 /2-3 RXBM-AC8 3 1 /2-5 RXBM-AC61 Part Number* RXHF-B17 RXHF-B21 RXHF-B2 A B Auxiliary Electric Kits RXBH- Kits include circuit breakers which meet UL and cul requirements for service disconnect. See the Electric Heat Electrical Data in this specification sheet for specific Kit numbers. Horizontal Adapter Kit RXHH- This horizontal adapter kit is used to convert Upflow/Downflow only models to horizontal flow. See the following table to order proper horizontal adapter kit. Coil Horizontal Adapter Kit Number (Single Qty.) 21 RXHH-A RXHH-A /3621 RXHH-A03 External Filter Base RXHF- Cabinet Size *Accommodates 1" or 2" filter Filter Size In. [mm] x 20 [06 x 508] x 20 [508 x 508] Horizontal Adapter Kit Number (10-Pack Qty.) RXHH-A01 x 10 RXHH-A02 x 10 RXHH-A03 x /82 RXHH-A0 RXHH-A0 x RXHH-A05 RXHH-A05 x 10 Part Number* RXHF-17 RXHF x 20 [635 x 508] RXHF A B RXHF-B RXHF- 1 1 /2 [38 mm] B A 18 Rheem Manufacturing Company

19 NOTES Rheem Manufacturing Company 19

20 Before proceeding with installation, refer to installation instructions packaged with each model, as well as complying with all Federal, State, Provincial, and Local codes, regulations, and practices. RHEEM AIR CONDITIONING DIVISION 5600 Old Greenwood Road, Fort Smith, Arkansas In keeping with its policy of continuous progress and product improvement, Rheem reserves the right to make changes without notice. PRINTED IN U.S.A DC FORM NO. H11-52 REV. 3 Supersedes Form H11-52 Rev. 2

INDOOR COILS. RCFM- featuring Earth-Friendly R-410A Refrigerant CASED/UNCASED COILS FOR GAS AND OIL FURNACES

INDOOR COILS. RCFM- featuring Earth-Friendly R-410A Refrigerant CASED/UNCASED COILS FOR GAS AND OIL FURNACES FORM NO. C11-212 REV. 1 Supersedes Form No. C11-212 INDOOR COILS RCFM- featuring Earth-Friendly R-410A Refrigerant earth friendly refrigerant CASED/UNCASED COILS FOR GAS AND OIL FURNACES AIRFLOW CAPACITIES

More information

INDOOR COILS. RCFA- featuring R-22 Refrigerant RCFL- featuring Earth-Friendly R-410A Refrigerant CASED/UNCASED COILS FOR GAS AND OIL FURNACES

INDOOR COILS. RCFA- featuring R-22 Refrigerant RCFL- featuring Earth-Friendly R-410A Refrigerant CASED/UNCASED COILS FOR GAS AND OIL FURNACES FORM NO. C11-211 REV. 3 Supersedes Form No. C11-211 Rev. 2 INDOOR COILS RCFA- featuring R-22 Refrigerant RCFL- featuring Earth-Friendly R-410A Refrigerant earth friendly refrigerant CASED/UNCASED COILS

More information

INDOOR COILS. RCFL- featuring Industry Standard R-410A Refrigerant CASED/UNCASED COILS FOR GAS AND OIL FURNACES

INDOOR COILS. RCFL- featuring Industry Standard R-410A Refrigerant CASED/UNCASED COILS FOR GAS AND OIL FURNACES FORM NO. C11-211 REV. 7 Supersedes Form No. C11-211 Rev. 6 INDOOR COILS RCFL- featuring Industry Standard R-410A Refrigerant CASED/UNCASED COILS FOR GAS AND OIL FURNACES AIRFLOW CAPACITIES 600-1,900 CFM

More information

INDOOR COILS. RCFN- featuring Industry Standard R-410A Refrigerant CASED/UNCASED COILS FOR GAS AND OIL FURNACES

INDOOR COILS. RCFN- featuring Industry Standard R-410A Refrigerant CASED/UNCASED COILS FOR GAS AND OIL FURNACES FORM NO. C11-213 REV. 4 Supersedes Form No. C11-213 Rev. 3 INDOOR COILS RCFN- featuring Industry Standard R-410A Refrigerant CASED/UNCASED COILS FOR GAS AND OIL FURNACES AIRFLOW CAPACITIES 600-1,900 CFM

More information

Cased/Uncased Coils For Gas And Oil Furnaces

Cased/Uncased Coils For Gas And Oil Furnaces Indoor Coils Cased/Uncased Coils For Gas And Oil Furnaces RCFL- Series featuring Industry Standard R-410A Refrigerant Airflow Capacity 600-1,900 CFM [283-897 L/s] Rheem Indoor Coils are designed for use

More information

Cooling/Heat Pump Convertible Air Handlers

Cooling/Heat Pump Convertible Air Handlers Cooling/Heat Pump Convertible Air Handlers 2/4TEC3F18-60A1000A 1½ 5 Ton PUB. NO. 22-1774-01-0905 (EN) Features and Benefits 13.0 SEER Ships horizontal converts to vertical by standing unit on end. Six-way

More information

ARMSTRONG AIR HEAT PUMPS www.armstrongair.com

ARMSTRONG AIR HEAT PUMPS www.armstrongair.com INDEX ELECTRIC FURNACE MODULAR AIR SYSTEM EFC/EFV... 5-10 electric Heat Kits... 5-11 evaporator coils EC1P / EM1P UPFLOW / COUNTERFLOW APPLICATIONS and upflow / horizontal applications (CASED)... 5-6 5-7

More information

Cooling Capacity CFM range @.5 in. w.c. (125 Pa)

Cooling Capacity CFM range @.5 in. w.c. (125 Pa) N8MXL Product Specifications 80% ECM Single Stage Heating Furnace EASIER TO SELL 80% AFUE Flame roll out sensors standard Category I venting Blocked vent switch 24 VAC humidifier terminal Electronic air

More information

Split System Cooling Product Data

Split System Cooling Product Data Split System Cooling Product XL16i 1½ 5 Tons PUB. NO. 22-1890-01 Features and Benefits Climatuff compressor Efficiency up to 16.0 SEER and 9.0 HSPF All aluminum Spine Fin coil WeatherGuard fasteners Quick-Sess

More information

Split System Heat Pump Product Data

Split System Heat Pump Product Data Split System Heat Pump Product Silver 14 4A6H4 1 1 /2-5 Tons PUB. NO. 12-1175-07 Contents Features and Benefits 2 Model Nomenclature 3 General 4 Product Specifications 4 A-weighted Sound Power Level [db(a)]

More information

F9MXE. Product Specifications

F9MXE. Product Specifications 96% AFUE, Single Stage, ECM Gas Furnace EASIER TO SELL 96% AFUE, all models all positions Select models earn the ENERGY STAR (See below, indicated with check mark.) Xtra SEER ECM blower motor Supports

More information

OIL FURNACES CLASSIC PREMIUM CLASS UPFLOW OIL FURNACES. ROBD- SERIES Heating Capacities 56,000 to 151,200 BTU/HR [16.41 to 44.

OIL FURNACES CLASSIC PREMIUM CLASS UPFLOW OIL FURNACES. ROBD- SERIES Heating Capacities 56,000 to 151,200 BTU/HR [16.41 to 44. FORM NO. O11-608 REV. 2 Supersedes Form No. O11-608 Rev. 1 OIL FURNACES CLASSIC PREMIUM CLASS UPF OIL FURNACES ROBD- SERIES Heating Capacities 56,000 to 151,200 BTU/HR [16.41 to 44.30 kw] The Rheem Classic

More information

CB29M Bulletin #490071 February 1996

CB29M Bulletin #490071 February 1996 ENGINEERING DT MTCHED REMOTE SYSTEMS 50hz S LOWER UNITS 50hz ELITE 10 MULTI POSITION LOWER UNITS 20 100 to 49 00 tuh (5.9 to 14.4 kw) Cooling Capacity 19 700 to 49 100 tuh (5.8 to 14.4 kw) Heat Pump Heating

More information

Cooling Capacity CFM range @.5 in. w.c. (125 Pa)

Cooling Capacity CFM range @.5 in. w.c. (125 Pa) 96% AFUE, Single Stage, ECM Gas Furnace EASIER TO SELL 96% AFUE, all models all positions Xtra SEER ECM blower motor Supports two stage cooling units Dehumidification feature in cooling California NOx

More information

Commercial Gas Furnace Upflow

Commercial Gas Furnace Upflow Commercial Gas Furnace Upflow Model G24-200 80% A.F.U.E. 200,000 Btuh Input Heating Cap. 7.5 or 10 Tons Nominal Add-On Cooling GUK FEATURES Certified by A.G.A./C.G.A. Laboratories. Heavy gauge painted

More information

Aluminum Cased Cooling Coils 2-5 Ton 4CXC PUB. NO. 22-1839-03

Aluminum Cased Cooling Coils 2-5 Ton 4CXC PUB. NO. 22-1839-03 Aluminum Cased Cooling Coils 2-5 Ton 4CXC PUB. NO. 22-1839-03 Aluminum Cooling Coil Nomenclature 4 C X C B 0 3 6 C C 3 C U A A Refrigerant Type 4 - R410A Product Family T-Premium (Heat Pump or Convertible

More information

G9MXE. Product Specifications

G9MXE. Product Specifications Up to 96% AFUE, Single Stage, ECM Gas Furnace EASIER TO SELL Up to 96% AFUE, all models all positions California NOx approved Select models earn the ENERGY STAR (See below, indicated with check mark.)

More information

Greensource iseries HY Model Unitary Air Handler/Fan Coil

Greensource iseries HY Model Unitary Air Handler/Fan Coil Engineering Submittal Sheet Overview Model Nomenclature HY 035 00-1 HY - HYDRONIC AIR HANDLER NOMINAL CAPACITY IN THOUSANDS OF BTUH VOLTAGE DESIGNATION 1 = 208-230/1/60 ELECTRIC HEAT KW 00 - NO ELECTRIC

More information

Split System Cooling Product Data

Split System Cooling Product Data Split System Cooling Product Data XR17 4TTR7 2, 3, 4 & 5 Tons PUB. NO. 22-1884-01 Features and Benefits CLIMATUFF 2-stage scroll compressor Efficiency up to 18.0 SEER All Aluminum SPINE FIN coil DURATUFF

More information

Cooling Capacity CFM range @.5 in. w.c. (125 Pa)

Cooling Capacity CFM range @.5 in. w.c. (125 Pa) 96% AFUE, Two Stage ECM Gas Furnace EASIER TO SELL 96% AFUE, all models, all positions Two stage heating operation Xtra SEER ECM blower motor Supports two stage cooling units Dehumidification feature in

More information

DESCRIPTION FEATURES HORIZONTAL DUCT HD. ISO 9001 Certified Quality Management System

DESCRIPTION FEATURES HORIZONTAL DUCT HD. ISO 9001 Certified Quality Management System TECHNICAL GUIDE ADD - ON COILS FOR USE WITH SPLIT-SYSTEM COOLING & HEAT PUMPS MODELS: MC, PC, FC, HD, UC 600-2000 CFM 1.5-5 TON COILS UPFLOW/DOWNFLOW FULL CASED FC UPFLOW PARTIAL CASED PC UPFLOW UNCASED

More information

Split System Heat Pump Product Data

Split System Heat Pump Product Data Split System Heat Pump Product Data XL20i 4TWZ0024, 036, 048 & 060 with ComfortLink II and Charge Assist 2, 3, 4 & 5 Tons PUB. NO. 22-1826-01 Features and Benefits Two Climatuff compressors Efficiency

More information

GCS16 GCS20 WARNING CAUTION

GCS16 GCS20 WARNING CAUTION Service Literature Corp. 0110 L6 Revised 12 2004 GCS16/GCS20 SERIES UNITS GCS16 GCS20 2 to 5 Ton GCS16/20 series units in the 2 to 5 ton (7.0 to 17.0 kw) cooling size are packaged combination gas heat

More information

SPLIT-SYSTEM CONDENSING UNITS. 10.00 SEER HRA018 thru 060 (1.5 thru 5 Nominal Tons) DESCRIPTION FEATURES

SPLIT-SYSTEM CONDENSING UNITS. 10.00 SEER HRA018 thru 060 (1.5 thru 5 Nominal Tons) DESCRIPTION FEATURES 550.46 -TG1Y (196) SPLIT-SYSTEM CONDENSING S 0 SEER HRA018 thru 060 (1.5 thru 5 Nominal Tons) DESCRIPTION The HRA Series condensing unit is the outdoor part of a versatile system of air conditioning. It

More information

Product Data. FV4C Performancet Series Fan Coil Sizes 002 Thru 006 PREMIUM ENVIRONMENTALLY SOUND FAN COIL

Product Data. FV4C Performancet Series Fan Coil Sizes 002 Thru 006 PREMIUM ENVIRONMENTALLY SOUND FAN COIL Performancet Series Fan Coil Sizes 002 Thru 006 Product Data PREMIUM ENVIRONMENTALLY SOUND FAN COIL The is the premium air handler combining the proven technology of Carrier fan coils with environmentally

More information

RHEEM RESIDENTIAL AIR CONDITIONING www.rheem.com

RHEEM RESIDENTIAL AIR CONDITIONING www.rheem.com INDEX ACCESSORIES... 3-6 barb nylon fittings... 3-6 condensor pads... 3-6 condensor wall bracket... 3-7 electrical... 3-7 PIPE INSULATION... 3-7 REFRIGERATION SERVICE TUBING COPPER... 3-7 COILS INDOOR

More information

TECHNICAL GUIDE 95.5% SINGLE STAGE GAS-FIRED RESIDENTIAL MULTI-POSITION GAS FURNACES MODELS: TG9S DESCRIPTION FEATURES

TECHNICAL GUIDE 95.5% SINGLE STAGE GAS-FIRED RESIDENTIAL MULTI-POSITION GAS FURNACES MODELS: TG9S DESCRIPTION FEATURES TECHNICAL GUIDE 95.5% SINGLE STAGE GAS-FIRED RESIDENTIAL MULTI-POSITION GAS FURNACES MODELS: TG9S NATURAL GAS 40-130 MBH INPUT Due to continuous product improvement, specifications are subject to change

More information

M SERIES REFRIGERANT COIL MODULE REFRIGERANT COILS for R-22, R-407C, R-410A

M SERIES REFRIGERANT COIL MODULE REFRIGERANT COILS for R-22, R-407C, R-410A Bulletin 20-20.2 / July 2012 M SERIES REFRIGERANT COIL MODULE REFRIGERANT COILS for R-22, R-407C, R-410A ➀ ➁ ➂ Model Number Key M 2430 C L 1 - A - ➀ Unit Type M=Modular Nominal Capacity 2430=24000 to 30000

More information

E2 Series Electric Furnaces

E2 Series Electric Furnaces E2 Series Electric Furnaces Service Manual Table of Contents Electrical Requirements... 10 Codes, Specifications Requirements... 10 Connection Supply Service Wires... 10 Furnace Sequence of Operation...

More information

Split System Cooling Product Data

Split System Cooling Product Data Split System Cooling Product Data 4TTB3018-060 1½ 5 Tons PUB. NO. 22-1843-14 Features and Benefits Efficiency up to 13.25 SEER All aluminum Spine Fin coil WeatherGuard fasteners Quick-Sess cabinet, easy

More information

Product Data. FV4B Performancet Series Fan Coil Sizes 002 Thru 006 PREMIUM ENVIRONMENTALLY SOUND FAN COIL

Product Data. FV4B Performancet Series Fan Coil Sizes 002 Thru 006 PREMIUM ENVIRONMENTALLY SOUND FAN COIL Performancet Series Fan Coil Sizes 002 Thru 006 Product Data PREMIUM ENVIRONMENTALLY SOUND FAN COIL The is the premium air handler combining the proven technology of Carrier fan coils with environmentally

More information

WON0502-B INSTALLATION INSTRUCTIONS FOR ELECTRIC FURNACES. Bulletin 30-34 / March 2013

WON0502-B INSTALLATION INSTRUCTIONS FOR ELECTRIC FURNACES. Bulletin 30-34 / March 2013 Bulletin 30-34 / March 2013 INSTALLATION INSTRUCTIONS FOR ELECTRIC FURNACES General The information on the following pages is to provide the installer the necessary information to properly install the

More information

Local Dealer: www.cebrands.com

Local Dealer: www.cebrands.com Local Dealer: C.E. LLC - Miami, FL USA www.cebrands.com Res2012-Rev2 QUALITY YOU CAN FEEL Residential Product Line >TCA7,9 Tempstar SmartComfort TXT + Air Conditioner Featuring The Observer Communication

More information

M7RL Series TECHNICAL SPECIFICATIONS. FEATURES and BENEFITS. High Efficiency / Direct Vent Condensing Downflow Gas Furnace

M7RL Series TECHNICAL SPECIFICATIONS. FEATURES and BENEFITS. High Efficiency / Direct Vent Condensing Downflow Gas Furnace TECHNICAL SPECIFICATIONS M7RL Series High Efficiency / Direct Vent Condensing Downflow Gas Furnace Induced Draft - 9%+ AFUE Input 4,000 thru 7,000 Btuh The high efficiency downflow gas furnace is especially

More information

Split System Heat Pump Product Data

Split System Heat Pump Product Data Split System Heat Pump Product Data XR 13 4TWR3018-060 1½ 5 Tons PUB. NO. 22-1795-12 Features and Benefits Climatuff compressor All aluminum Spine Fin coil Quick-Sess cabinet, service access and refrigerant

More information

Split System Cooling Product & Performance Data

Split System Cooling Product & Performance Data Split System Cooling Product & Performance Data XR 13 4TTR3018-060 1½ 5 Tons PUB. NO. 22-1790-02-2607 (EN) Features and Benefits Climatuff compressor Efficiency up to 14.00 SEER All aluminum Spine Fin

More information

G26 Corp. 9721-L11 Revised 07-2001 LENNOXOEMPARTS.COM. Service Literature G26 SERIES UNITS

G26 Corp. 9721-L11 Revised 07-2001 LENNOXOEMPARTS.COM. Service Literature G26 SERIES UNITS Service Literature G26 SERIES UNITS G26 series units are high-efficiency upflow gas furnaces manufactured with DuralokPlust aluminized steel clamshell-type heat exchangers. G26 units are available in heating

More information

TWE+TTA TWE+TWA 6.25-20 T.R.

TWE+TTA TWE+TWA 6.25-20 T.R. TWE+TTA TWE+TWA 6.25-20 T.R. Main features : TWE indoor unit : Convertible cabinet, vertical or horizontal. Adjustable speed pulley-belt drive centrifugal fan motor. Aluminium fin coil with copper-tubes.

More information

Split System Heat Pump Product Data

Split System Heat Pump Product Data Split System Heat Pump Product Three Phase 4TWA3030A3000C 4TWA3030A4000C 4TWA3036A3000C 4TWA3036A4000C 4TWA3042B3000A 2½ 5 Tons 4TWA3042B4000A 4TWA3048A3000C 4TWA3048A4000C 4TWA3060B3000A 4TWA3060B4000A

More information

How To Install An Evaporator Coil

How To Install An Evaporator Coil EVAPORATOR COIL INSTALLATION INSTRUCTIONS EVAPORATOR COIL SAFETY... INSTALLATION REQUIREMENTS... Tools and Parts... System Requirements... Location Requirements... Drain Requirements... INSTALLATION INSTRUCTIONS...

More information

INSTALLATION INSTRUCTIONS

INSTALLATION INSTRUCTIONS 2008 Lennox Industries Inc. Dallas, Texas, USA WARNING Improper installation, adjustment, alteration, service or maintenance can cause property damage, personal injury or loss of life. Installation and

More information

Split System Cooling Product Data

Split System Cooling Product Data Split System Cooling Product Data Three Phase 4TTA3 2½ 5 Tons PUB. NO. 22-1791-12 Features and Benefits All aluminum Spine Fin coil WeatherGuard fasteners Quick-Sess cabinet, service access and refrigerant

More information

Glossary of Heating, Ventilation and Air Conditioning Terms

Glossary of Heating, Ventilation and Air Conditioning Terms Glossary of Heating, Ventilation and Air Conditioning Terms Air Change: Unlike re-circulated air, this is the total air required to completely replace the air in a room or building. Air Conditioner: Equipment

More information

TECHNICAL MANUAL GDS8 & GHS8

TECHNICAL MANUAL GDS8 & GHS8 TECHNICAL MANUAL AL GDS8 & GHS8 33-3/8" 80% Gas Furnace Units Refer to Service Manual RS6610004 for installation, operation, and troubleshooting information. All safety information must be followed as

More information

48/50EJ,EK,EW,EY038, 044, 048 SINGLE-PACKAGE COOLING UNITS VARIABLE VOLUME CONSTANT VOLUME FACTORY-INSTALLED OPTIONAL HEAT

48/50EJ,EK,EW,EY038, 044, 048 SINGLE-PACKAGE COOLING UNITS VARIABLE VOLUME CONSTANT VOLUME FACTORY-INSTALLED OPTIONAL HEAT 48/50E-4SB 48/50EJ,EK,EW,EY038, 044, 048 SINGLE-PACKAGE COOLING UNITS VARIABLE VOLUME CONSTANT VOLUME FACTORY-INSTALLED OPTIONAL HEAT GAS HEAT ELECTRIC HEAT PERFORMANCE DATA CERTIFIED DIMENSION PRINT CERTIFIED

More information

XV80 UPFLOW/HORIZONTAL 2-STAGE, VARIABLE SPEED GAS-FIRED FURNACE

XV80 UPFLOW/HORIZONTAL 2-STAGE, VARIABLE SPEED GAS-FIRED FURNACE UPF/HORIZONTAL 2-, VARIABLE SPEED GAS-FIRED FURNACE XV80 MODELS TUD2B060A9V3VB, TUD2B080A9V3VB TUD2C080A9V4VB, TUD2C080B9V4VB TUD2B00A9V3VB, TUD2C00A9V5VB TUD2C00B9V5VB, TUD2DA9V5VB TUD2DB9V5VB, TUD2DA9V5VB

More information

Low Profile Unit Cooler

Low Profile Unit Cooler Super-Flo Now available with EC Motors High Efficiency / High Reliability Low Profile Unit Cooler Publication No. 411.4 November, 2008 S A N I T A T I O N F O U N D A T I O N A L N A T I O N Air Defrost

More information

INSTALLATION INSTRUCTIONS

INSTALLATION INSTRUCTIONS 2008 Lennox Industries Inc. Dallas, Texas, USA WARNING Improper installation, adjustment, alteration, service or maintenance can cause personal injury, loss of life, or damage to property. Installation

More information

GCS16-024-030-036-048-060

GCS16-024-030-036-048-060 Packaged Unit & Gas Heat 2-5 Ton Capacity 50,000-120,000 Btuh Input Heating Capacity GCS16-024-030-036-048-060 FEATURES Designed for outdoor rooftop or ground level installations Down-flow or horizontal

More information

RHF High Efficiency Remote Heat Pumps and Matching Blower Coils

RHF High Efficiency Remote Heat Pumps and Matching Blower Coils Heating&Air Conditioning RHF High Efficiency Remote Heat Pumps and Matching Blower Coils Amana RHF heat pumps and matching blower coils offer economy, superior heating and cooling comfort, plus installation

More information

MAC-120HE-01 Air-Cooled Chiller

MAC-120HE-01 Air-Cooled Chiller MAC-120HE-01 Air-Cooled Chiller 10 Ton / 120,000 BTUH Air-Cooled Chiller 208/230-1-50/60 1 HVAC Guide Specifications Air-Cooled Liquid Chiller Nominal Size: 10 Tons Multiaqua Model Number: MAC-120HE-01

More information

Installer s Guide 18-AH39D1-13

Installer s Guide 18-AH39D1-13 18-AH39D1-13 Cased Aluminum "Convertible" Coils 4TXCA018BC3HC** 4TXCA024BC3HC** 4TXCB025BC3HC** 4TXCB026BC3HC** 4TXCB031BC3HC** 4TXCB032BC3HC** ALL phases of this installation must comply with NATIONAL,

More information

Liebert DS Thermal Management Unit

Liebert DS Thermal Management Unit Liebert DS Thermal Management Unit System Design Manual - 28-105kW (8-30 Tons), Downflow/Upflow, 60Hz Floor Mounted, Air-Cooled, Water/Glycol-Cooled, GLYCOOL Economizer Coil, Dual-Cool DX with Secondary

More information

Auxiliary HVAC RAM ProMaster. Standard Tie-in Extreme Climate System

Auxiliary HVAC RAM ProMaster. Standard Tie-in Extreme Climate System Auxiliary HVAC RAM ProMaster Standard Tie-in Extreme Climate System Auxiliary HVAC High performance aftermarket heating and cooling systems engineered for vehicle specific platforms that minimize install

More information

Explosion-Proof Electric Unit Heaters

Explosion-Proof Electric Unit Heaters Type FX4 FX4 Explosion-Proof Electric Air Heaters FX4 heaters are UL listed and/or CSA certified for use in hazardous locations. They are designed for dry indoor industrial applications such as oil refineries,

More information

Installation Instructions

Installation Instructions H5HK Series Installation Instructions 3 Phase Electric Heater Kits 7.5 and 0 TON Package A/C Systems Description Installation of 08/40V and 480V H5HK 3 Phase Heater Kits in 7.5 and 0 TON Packaged Air Conditioners.

More information

ARUF Series. Multi-Position, Multi-speed Air Handler with PSC Motor 1½ to 5 Tons. Contents. Product Features

ARUF Series. Multi-Position, Multi-speed Air Handler with PSC Motor 1½ to 5 Tons. Contents. Product Features Series Multi-Position, Multi-speed Air Handler with PSC Motor 1½ to 5 Tons Contents Nomenclature... 2 Product Specifications... 3 Heater Kit Nomenclature... 3 Dimensions... 4 Airflow Data... 5 Heat Kit

More information

LH and GH/GL Series UNIT COOLERS. Technical Bulletin: LHGH_001_071015. Products that provide lasting solutions.

LH and GH/GL Series UNIT COOLERS. Technical Bulletin: LHGH_001_071015. Products that provide lasting solutions. LH and GH/GL Series UNIT COOLERS Technical Bulletin: LHGH_001_07101 Products that provide lasting solutions. LH Series Unit Coolers Dual Discharge Low Hite Series At 9 1/ maximum height, the LH Series

More information

Evaporator Coil Installation Instructions

Evaporator Coil Installation Instructions Part # 96654008 July 2010 Evaporator Coil Installation Instructions A-Coil Page 4 Multi-position A-Coil Page 4-7 Slab Coil Page 5 Horizontal A-Coil Top Connection Page 5 Horizontal A-Coil Side Connection

More information

WMSLW / WMBLWH Series Hydronic Upflow/Horizontal Left or Right, Heating and Cooling Air Handler

WMSLW / WMBLWH Series Hydronic Upflow/Horizontal Left or Right, Heating and Cooling Air Handler WMSLW / WMBLWH Series Hydronic Upflow/Horizontal Left or Right, Heating and Cooling Air Handler Installation Operation Maintenance The WMSLW/WMBLW series is designed for installation in a closet, utility

More information

ModPac II 1 to 5-Ton Vertical Wall Mount Air Conditioners Models AVPA12-20-24-30-36-42-48-60

ModPac II 1 to 5-Ton Vertical Wall Mount Air Conditioners Models AVPA12-20-24-30-36-42-48-60 ModPac II 1 to 5-Ton Vertical Wall Mount Air Conditioners Models AVPA12-20-24-30-36-42-48-60 General Description The Marvair ModPac II air conditioner is a vertical, wall mounted, cost effective air conditioner

More information

Submitted to Reference Approval Construction Unit Designation Schedule #

Submitted to Reference Approval Construction Unit Designation Schedule # SUBMITTAL AQV09JA High Wall 9,000 Btu/h Heat Pump Nom Cooling Capacity (Btu/h) 9,000 SEER 20.0 Cool Capacity Range (Btu/h) 3,100 to 11,900 Nom Heating Capacity (Btu/h) 11,950 HSPF 10.0 Heating COP 3.7

More information

XV 95. Upflow/ Horizontal Left, Downflow/ Horizontal Right Variable Speed Two Stage Condensing Gas-Fired Furnace PUB. NO.

XV 95. Upflow/ Horizontal Left, Downflow/ Horizontal Right Variable Speed Two Stage Condensing Gas-Fired Furnace PUB. NO. Upflow/ Horizontal Left, Downflow/ Horizontal Right Speed Two Stage Condensing Gas-Fired Furnace XV 95 TUH2B060A9V3VB TUH2B080A9V3VB TUH2B080A9V4VB TUH2C100A9V4VB TUH2C100A9V5VB TUH2D120A9V5VB Direct Vent

More information

AVPTC. Multi-Position, Variable-Speed ECM Based Air Handler with Internal TXV Comfortnet Compatible 1½ to 5 Tons. Contents.

AVPTC. Multi-Position, Variable-Speed ECM Based Air Handler with Internal TXV Comfortnet Compatible 1½ to 5 Tons. Contents. Multi-Position, Variable-Speed ECM Based Air Handler with Internal TXV Comfortnet Compatible 1½ to 5 Tons Contents Air Handler Nomenclature... Heater Kit Nomenclature... Product Specifications... 3 Dimensions...

More information

Installation Manual CLIFC Fan & Coil Variable Speed

Installation Manual CLIFC Fan & Coil Variable Speed Installation Manual CLIFC Fan & Coil Variable Speed General Description GENERAL DESCRIPTION FANS EQUIPMENT Totally Factory assembled within the unit all piping, wiring, and required controls for operation

More information

Installation Manual. Rental Services. Air Handling Units CHS-SVN01A-EN. July 2008

Installation Manual. Rental Services. Air Handling Units CHS-SVN01A-EN. July 2008 Installation Manual Rental Services Air Handling Units July 2008 CHS-SVN01A-EN Copyright 2008 Trane All rights reserved This document and the information in it are the property of Trane and may not be

More information

Single Package Vertical Air Conditioners. Vert-I-Pak

Single Package Vertical Air Conditioners. Vert-I-Pak Single Package Vertical Air Conditioners Vert-I-Pak Installs easily in a closet for quiet operation and provides a more homelike appearance for your guests. THE EXPERTS IN ROOM AIR CONDITIONING A Better

More information

SINGLE PACKAGE VERTICAL AIR CONDITIONERS

SINGLE PACKAGE VERTICAL AIR CONDITIONERS SINGLE PACKAGE VERTICAL AIR CONDITIONERS AIR CONDITIONERS l HEAT PUMPS l ELECTRIC HEAT QUIETER BY DESIGN SIMPLE TO INSTALL CONCEALED INSTALLATION www.friedrich.com VERT-I-PAK ideal for extended stay properties,

More information

INSTALLER'S GUIDE. Supplementary Electric Heaters 18-GJ08D1-1. Table of Contents

INSTALLER'S GUIDE. Supplementary Electric Heaters 18-GJ08D1-1. Table of Contents INSTALLER'S GUIDE ALL phases of this installation must comply with NATIONAL, STATE AND LOCAL CODES Models: BAYEAAC051A BAYEAAC05LG1A BAYEAAC081A BAYEAAC08LG1A BAYEAAC101A BAYEAAC10LG1A BAYEABC151A BAYEABC201A

More information

york air-conditioning products Residential & VRF News 2015

york air-conditioning products Residential & VRF News 2015 york air-conditioning products Residential & VRF News 2015 york air-conditioning products Catalogue Content Split Systems Pag. High wall High Efficiency Inverter YWHJZH 09 to 24 K 6 High wall Inverter

More information

Gas Unit Heaters Duct Furnaces Horizontal - 60 HZ Form No. LF24-100-400 (10/2011) LF24 Standard

Gas Unit Heaters Duct Furnaces Horizontal - 60 HZ Form No. LF24-100-400 (10/2011) LF24 Standard LF Standard Features Horizontal unit heaters are compact in design and easy to install. Steady State Efficiencies of up to 80.%. Ideal for economical commercial heating systems. Shipped completely assembled

More information

IMPORTANT: BEFORE INSTALLING ANY HEATING TERMINAL UNIT TO A DOMESTIC WATER HEATER, CONSULT THE LOCAL PLUMBING CODES.

IMPORTANT: BEFORE INSTALLING ANY HEATING TERMINAL UNIT TO A DOMESTIC WATER HEATER, CONSULT THE LOCAL PLUMBING CODES. QUIET-ONE Environmental Products 2000 Kickspace Heater Series Models: KS 2004, KS 2006 KS 2008, KS 2010 INSTALLATION OPERATING MAINTENANCE Please read these instructions thoroughly before beginning your

More information

Evaporator Coils. Upflow/Downflow Vertical N-Coil Transition Upflow/Downflow N-Coil Horizontal N-coil. Upflow/Downflow Uncased Vertical N-Coil

Evaporator Coils. Upflow/Downflow Vertical N-Coil Transition Upflow/Downflow N-Coil Horizontal N-coil. Upflow/Downflow Uncased Vertical N-Coil Upflow/Downflow Vertical N-Coil Transition Upflow/Downflow N-Coil Horizontal N-coil Upflow/Downflow Uncased Vertical N-Coil Upflow/Downflow Uncased A-Coil Slab Coil Cased Horizontal 50 51 Payne Upflow/Downflow

More information

SPACE COOLERS. P.O. Box 956 Paoli, PA 19301 (800) 523-7590 FAX (610) 251-0805 www.coilcompany.com. The leader in packaged Space Cooling.

SPACE COOLERS. P.O. Box 956 Paoli, PA 19301 (800) 523-7590 FAX (610) 251-0805 www.coilcompany.com. The leader in packaged Space Cooling. SPACE COOLERS P.O. Box 956 Paoli, PA 19301 (800) 523-7590 FAX (610) 251-0805 www.coilcompany.com The leader in packaged Space Cooling. 2 Table of Contents Description Space Cooler from Coil Company. A

More information

AIR-COOLED CONDENSERS Technical Guide

AIR-COOLED CONDENSERS Technical Guide BN-ACCTB0306 March, 2006 AIR-COOLED CONDENSERS Technical Guide Monarch and Ambassador Series TABLE OF CONTENTS Overview... 2, 3 Features & Options... 3, 4 Three Solutions...5 Nomenclature...6 Condenser

More information

Product Data. FX4D Comfort Series Fan Coil Sizes 019 thru 061 AIR HANDLER TECHNOLOGY AT ITS FINEST

Product Data. FX4D Comfort Series Fan Coil Sizes 019 thru 061 AIR HANDLER TECHNOLOGY AT ITS FINEST Comfort eries Fan Coil izes 019 thru 061 Product Data AIR HANDLER TECHNOLOGY AT IT FINET The fan coils combine the proven technology of Carrier fan coil units with Puron, the environmentally sound refrigerant.

More information

ENGINEERING GUIDE. Water-Cooled Self-Contained Units C-Series, Vertical

ENGINEERING GUIDE. Water-Cooled Self-Contained Units C-Series, Vertical ENGINEERING GUIDE Water-Cooled Self-Contained Units C-Series, Vertical TABLE OF CONTENTS Introduction...2 Product Overview...3 Nomenclature...4 General Data...5 Cooling Performance Data....6 Evaporator

More information

HA HE Series. Solutions for Your needs. fl exible and confi gure-to-order coils. Healthy Solutions coils

HA HE Series. Solutions for Your needs. fl exible and confi gure-to-order coils. Healthy Solutions coils Series air handlers evaporator coils HA HE Series Healthy Solutions coils unit heaters fl exible and confi gure-to-order coils Solutions for Your needs our features. your benefits. Easy Installation and

More information

SECTION 15732 AIR CONDITIONING UNIT

SECTION 15732 AIR CONDITIONING UNIT SECTION 15732 AIR CONDITIONING UNIT PART 1 GENERAL 1.01 SUMMARY A. Section includes: 1. Packaged, split system air conditioning unit No. 1. 1.02 REFERENCES A. Air-Conditioning, Heating, and Refrigeration

More information

ECOCIAT. Domestic hot water heat recovery unit

ECOCIAT. Domestic hot water heat recovery unit Heat recovery unit Domestic hot water High energy efficiency with R410A Compact and quiet Scroll compressors Brazed-plate heat exchangers Heating Heat recovery ENVIRONMENTALLY HFC R410A PROTECTION DE FRIENDLY

More information

C26 Bulletin #210061 November 1997 Supersedes January 1997 (Coil/Furnace Match Up Charts)

C26 Bulletin #210061 November 1997 Supersedes January 1997 (Coil/Furnace Match Up Charts) NGINRING T loset Installation With Pulse21 Furnace and lectronic ir leaner Typical pplications UNS N FULL S UP- VPORTOR OILS IR-ONITIONING N HT PUMP 2 To 5 Ton (7.0 To 17.6 kw) Nominal Size OILS LOWR OILS

More information

Product Data. Split System Cooling 22-1904-1F-EN. March 2015

Product Data. Split System Cooling 22-1904-1F-EN. March 2015 Product Data Split System Cooling 4TTR4018L1000A 4TTR4024L1000A 4TTR4025L1000A 4TTR4030L1000A 4TTR4031L1000A 4TTR4036L1000A 4TTR4037L1000A 4TTR4042L1000A 4TTR4043L1000A 4TTR4048L1000A 4TTR4060L1000A Note:

More information

SECTION 23 81 03 - PACKAGED ROOFTOP AIR CONDITIONING UNITS NON-CUSTOM

SECTION 23 81 03 - PACKAGED ROOFTOP AIR CONDITIONING UNITS NON-CUSTOM SECTION 23 81 03 - PACKAGED ROOFTOP AIR CONDITIONING UNITS NON-CUSTOM PART 1 - GENERAL 1.1 SUMMARY A. Section Includes: 1. Packaged rooftop air conditioning unit (5 tons and smaller). 2. Roof curb. 1.2

More information

AquaFREE System. Technical Catalogue. Outdoor units: RAS-(3~5)HVRNE RAS-(4/5)HRNE. Indoor units: RWM-(3~5)FSN1E RWM-(3~5)FSN1E-(4.

AquaFREE System. Technical Catalogue. Outdoor units: RAS-(3~5)HVRNE RAS-(4/5)HRNE. Indoor units: RWM-(3~5)FSN1E RWM-(3~5)FSN1E-(4. AquaFREE System Technical Catalogue Outdoor units: RAS-(3~5)HVRNE RAS-(4/5)HRNE Indoor units: RWM-(3~5)FSN1E RWM-(3~5)FSN1E-(4.5/6)H(1/3) Specifications in this manual are subject to change without notice

More information

Residential/Commercial Gas Condensing High Efficiency Tankless Water Heaters

Residential/Commercial Gas Condensing High Efficiency Tankless Water Heaters Residential/Commercial Gas Condensing High Efficiency Tankless Water Heaters FEATURES ULTRA-LOW NOx CONDENSING TECHNOLOGY PROVIDES UNPRECEDENTED 0.95 ENERGY FACTOR DURABLE HEAT EXCHANGER Primary Heat Exchanger

More information

VertiCool Space Saver 2 to 15 tons Water-Cooled and Chilled Water

VertiCool Space Saver 2 to 15 tons Water-Cooled and Chilled Water 2 to 15 tons Water-Cooled and Chilled Water Unique Solutions for Challenging HVAC Projects Your Choice for Limited Space Applications Water-Cooled Chilled Water The VertiCool Space Saver allows installation

More information

catalog Single Package Vertical Air Conditioners and Heat Pumps

catalog Single Package Vertical Air Conditioners and Heat Pumps catalog Single Package Vertical Air Conditioners and Heat Pumps Catalog: SK145.00-EG1 (1008) TABLE OF CONTENTS Single Package Vertical Units Introduction...............................................................................

More information

26 AND 27 SLEEVES. IDEAL for NEW CONSTRUCTION, RETROFITS and REMODELS.

26 AND 27 SLEEVES. IDEAL for NEW CONSTRUCTION, RETROFITS and REMODELS. T H R U - T H E - W A L L A I R C O N D I T I O N E R S 26 AND 27 SLEEVES. IDEAL for NEW CONSTRUCTION, RETROFITS and REMODELS. W A L L M A S T E R T H R U - T H E - W A L L A I R C O N D I T I O N E R

More information

Element D Services Heating, Ventilating, and Air Conditioning

Element D Services Heating, Ventilating, and Air Conditioning PART 1 - GENERAL 1.01 OVERVIEW A. This section supplements Design Guideline Element D3041 on air handling distribution with specific criteria for projects involving design of a Data Center spaces B. Refer

More information

DUCTLESS MINI-SPLITS SINGLE & MULTI-ZONE HORIZONTAL AIR CONDITIONERS PORTABLE UNITS FREE MATCH COMPONENTS

DUCTLESS MINI-SPLITS SINGLE & MULTI-ZONE HORIZONTAL AIR CONDITIONERS PORTABLE UNITS FREE MATCH COMPONENTS DUCTLESS MINI-SPLITS SINGLE & MULTI-ZONE HORIZONTAL AIR CONDITIONERS PORTABLE UNITS FREE MATCH COMPONENTS AN EXCELLENT CHOICE IN COOLING, COMFORT AND CONVENIENCE Why choose a Mini-Split system? Installing

More information

INSTALLATION AND OPERATION INSTRUCTIONS - (LOW FLOW MODELS) (Before installation, compare electrical needed for the model of heater selected)

INSTALLATION AND OPERATION INSTRUCTIONS - (LOW FLOW MODELS) (Before installation, compare electrical needed for the model of heater selected) CHRONOMITE INSTANT-FLOW WATER HEATER INSTALLATION AND OPERATION INSTRUCTIONS - (LOW FLOW MODELS) (Before installation, compare electrical needed for the model of heater selected) TABLE 1 Model No. Wattage

More information

CASED & UNCASED UPFLOW & DOWNFLOW EVAPORATOR COILS

CASED & UNCASED UPFLOW & DOWNFLOW EVAPORATOR COILS CASED & UNCASED UPFLOW & DOWNFLOW EVAPORATOR COILS Description / Application Compact, versatile, right or left horizontal position May be used in closet, utility room, or basement Standard Finish Fully

More information

TABLE 1. Rugged cast aluminum alloy casing,celcon waterways with nichrome parts White (unless stainless steel housing)

TABLE 1. Rugged cast aluminum alloy casing,celcon waterways with nichrome parts White (unless stainless steel housing) CHRONOMITE INSTANT-FLOW MICRO WATER HEATER INSTALLATION AND OPERATION INSTRUCTIONS - (LOW FLOW MODELS) (Before installation, compare electrical needed for the model of heater selected) TABLE 1 Model No.

More information

SECTION 23 81 43 HEAT PUMPS

SECTION 23 81 43 HEAT PUMPS SECTION 23 81 43 HEAT PUMPS PART 1 GENERAL 1.1 SUMMARY A. Section Includes: 1. Packaged rooftop heat pumps. 1.2 REFERENCES A. American Society of Heating, Refrigerating and Air-Conditioning Engineers:

More information

Operation and Installation Manual. Max Series

Operation and Installation Manual. Max Series Operation and Installation Manual Max Series Models 95MAX 155MAX 155ECM 155MAXRX 200MAX 200MAXRX MAXTOP 195DCS 300DCS 200ERV 200ERVD New Auto Dehumidistat Function prevents unwanted use of the dehumidistat

More information

CAB LCAB HACAB RMP/AMP CC CY/YY RVP CUSTOM CU

CAB LCAB HACAB RMP/AMP CC CY/YY RVP CUSTOM CU GENERAL PURPOSE (ORDINARY) LOCATION Custom Controls provides the petro-chemical and offshore industries with HVAC equipment of the highest quality and reliability on the market at an economical price.

More information

FTQ. Daikin Inverter Ducted Heat Pump

FTQ. Daikin Inverter Ducted Heat Pump FTQ Daikin Inverter Ducted Heat Pump A TRADITIONAL CENTRAL AIR SYSTEM MADE BETTER WITH DAIKIN CONSTANT COMFORT INVERTER TECHNOLOGY. The Daikin Inverter Ducted Heat Pump line is a cost effective alternative

More information

Evaporator Coil. Installation Instructions GENERAL

Evaporator Coil. Installation Instructions GENERAL IM-HAC-0966540-12 December 2013 Evaporator Coil Installation Instructions TABLE OF CONTENTS PAGE General... 1 Vertical... 2 Horizontal... 2 Multi-Position... 3-5 Metering Device... 6 Condensate Drain...

More information

Installation Instructions

Installation Instructions 05,06 Single Package, Displacement Ventilation or Single Zone Variable Airflow Rooftop Units Electric Cooling with PURONr (R---410A) Refrigerant and COMFORTLinkt Controls Installation Instructions IMPORTANT:

More information

3Aftermarket Systems. Air Conditioners and Kombos.. 411. Heater/Pressurizer...440. System Matrix...441. Aftermarket System Requirements...

3Aftermarket Systems. Air Conditioners and Kombos.. 411. Heater/Pressurizer...440. System Matrix...441. Aftermarket System Requirements... 3Aftermarket Systems Air Conditioning & Heating Replacement Parts Aftermarket Systems Air Conditioners and Kombos.. 411 KA-300 Air Conditioner... 411 KK-315 Heater/Air Conditioner Kombo...412 KA-400 Air

More information