1 Packaged Cooling with Electric Heat Rooftop Units Voyager 12½ - 25 Tons - 60 Hz December 2003 RT-PRC002-EN
2 Introduction Voyager TM... a proven performer built to provide ultimate indoor comfort. Voyager continues to provide the highest standards in quality and reliability, comfort, ease of service, and the performance of Trane light commercial products. For contractors, Voyager saves time and money, increasing their ability to win jobs. It meets engineer s design criteria and offers solutions to cover many special applications. And, of course, Voyager carries the Trane reputation for excellence, quality and reliability American Standard Inc. All rights reserved RT-PRC002-EN
3 Contents Introduction Features and Benefits Application Considerations Selection Procedure Model Number Description General Performance Cooling Performance Fan Performance Heat Performance Controls Electric Power Dimension and Weights Mechanical Specifications RT-PRC002-EN 3
4 Features and Benefits Weather Tight Top and Cabinet Voyager units incorporate either a one piece top or the Trane-Tite-Top (T 3 ). Each part of the top (either two or three pieces) overlaps in such a way that water cannot leak into the unit. These overlapped edges are gasketed and sealed to ensure superior water integrity. Quick- Access (12½-25 tons) panels reduce the number of possible water entry points. For added water integrity, Voyager has a raised 1 1 / 8 " lip around the supply and return of the downflow units to prevent water from blowing into the ductwork. Quality And Reliability Testing The fan and idler arm assembly designs have been tested to over 300,000 cycles each. Our combined cycle testing is now over 7,000,000 cycles. All of Voyager s designs were rigorously rain tested at the factory to ensure water integrity. Actual shipping tests were performed to determine packaging requirements. Units were test shipped around the country to determine the best packaging. Factory shake and drop tests were used as part of the package design process to help assure that the unit arrives at the job site in top condition. Rigging tests include lifting a unit into the air and letting it drop one foot, assuring that the lifting lugs and rails hold up under stress. We perform a 100% coil leak test at the factory. The evaporator and condenser coils are leak tested at 200 psig and pressure tested to 450 psig. All parts are inspected at the point of final assembly. Sub-standard parts are identified and rejected immediately. Every unit receives a 100% unit run test before leaving the production line to make sure it lives up to rigorous Trane requirements. We test designs at our factory not on our customers! Conversionless Units The dedicated design units (either downflow or horizontal) require no panel removal or alteration time to convert in the field a major cost savings during installation. Horizontal units come complete with duct flanges so the contractor doesn t have to field fabricate them. These duct flanges are a time and cost saver. U-shaped Airflow U-shaped airflow allows for improved static capabilities. 4 RT-PRC002-EN
5 Features and Benefits ReliaTel Several years ago, Trane was the first to introduce ReliaTel into the Light Commercial Market. That design, along with immeasurable experience, has provided the technology for Trane s second-generation ReliaTel microprocessor controls. ReliaTel: Provides unit control for heating, cooling, and ventilating by utilizing input from sensors that measure outdoor and indoor temperature. Improves quality and reliability through the use of time-tested microprocessor controls and logic. Prevents the unit from short cycling, considerably improving compressor life. Ensures that the compressor will run for a specific amount of time, which allows oil to return for better lubrication, enhancing the reliability of the compressor. Reduces the number of components required to operate the unit, thereby reducing possibilities for component failure. Eliminates the need for field-installed components with its built-in anti-shortcycle timer, time delay relay and minimum on time controls. These controls are factory tested to assure proper operation. Requires no special tools to run the unit through its paces during testing. Simply place a jumper between Test 1 and Test 2 terminals on the Low Voltage Terminal Board and the unit will stage through its operational steps. The unit automatically returns control after 60 minutes to the zone sensor after stepping through the test mode a single time, even if the jumper is left on the unit. As long as the unit has power and the LED is lit, the ReliaTel is operational. The light indicates that the ReliaTel is functioning properly. Features expanded diagnostic capabilities when used with Trane s Integrated Comfort TM Systems. As an energy benefit, softens electrical spikes by staging on fans, compressors and heaters. The Intelligent Fallback or Adaptive Control is a benefit to the building occupant. If a component goes astray, the unit will continue to operate at predetermined temperature set points. Intelligent Anticipation is a standard feature of the ReliaTel. Functioning constantly, the ReliaTel and zone sensors work together in harmony, to provide tight comfort control. RT-PRC002-EN 5
6 Features and Benefits Easy Access Low Voltage Terminal Board Voyager s Low Voltage Terminal Board is external to the electrical control cabinet. It is extremely easy to locate and attach the thermostat wire. This is another cost and time saving installation feature. Standardized Components Components are placed in the same location on all Voyager units. Familiarize yourself with one Voyager and you are familiar with every Voyager. ReliaTel can fit all Voyager Packaged Gas/Electrics, Cooling with Electric Heat, and Heat Pump models. This provides standardization of parts for the contractors. Less money is tied up in inventory using the ReliaTel. Contractors/owners can stock fewer parts due to standardized components throughout Voyager units. Single Side Service Single side service is standard on all Voyager 12½-25 tons. Quick-Access Panels On The 12½-25 Tons Remove three or fewer screws for access to the standardized internal components and wiring. Low Voltage Connections The wiring of the low voltage connections to the unit and the zone sensors is as simple as 1-1, 2-2, and 3-3. This simplified system makes it easy for the installer to wire. Colored And Numbered Wiring You save time and money tracing wires and diagnosing the unit. VariTrac When Trane s changeover VAV System for light commercial applications is coupled with Voyager, it provides the latest in technological advances for comfort management systems and can allow thermostat control in every zone served by VariTrac. VariTrac Quick-Adjust Idler Arm With the Quick-Adjust Idler Arm, the belt and sheaves on all 12½-25 tons can be quickly adjusted without moving the mounted fan motor. The result is a major savings in time and money. 6 RT-PRC002-EN
7 Features and Benefits Capacity Modulation The 12½-25 tons have dual compressors. Compressors Voyager utilizes the best compressor technology available to achieve the highest possible performance. The dual compressor models are outstanding for humidity control, light load cooling conditions and system back-up applications. Low Ambient Cooling All Voyager 12½-25 tons have cooling capabilities down to 0 F as standard. Power Exhaust Option This option is available on the 12½-25 tons downflow units. It provides exhaust of the return air, when using a downflow economizer, to maintain proper building pressurization. Great for relieving most building overpressurization problems. CO 2 Sensing The CO 2 sensor has the ability to monitor space occupancy levels within the building by measuring the parts per million of CO 2 (Carbon Dioxide) in the air. As the CO 2 levels increase, the outside air damper modulates to meet the CO 2 space ventilation requirements. The CO 2 sensor kit is available as a field installed accessory. Ventilation Override Accessory With the Ventilation Override Accessory installed, the unit can be set to transition to up to 3 different pre-programmed sequences for Smoke Purge, Pressurization, and Exhaust. The transition occurs when a binary input on the RTOM is closed (shorted). This would typically be a hard wired relay output from a smoke detector of fire control panel. The ventilation override kit is available as a field installed accessory. Flexible Applications Only three roof curbs for the entire Voyager line simplifies curb selection. Airflow is outstanding. The Voyager can replace an older machine with old ductwork and, in many cases, improve the comfort through better air distribution. A wide variety of Factory Installed Options (FIOPs) are available. Trane Communication Interface (TCI) Available factory or field installed. This module, when applied with the Micro, easily interfaces with Trane s Integrated Comfort TM System. Single Point Power A single electrical connection powers the unit. Sloped Drain Pans Standard on every unit. Downflow And Horizontal Economizers The economizers come with three control options dry bulb is standard, enthalpy and differential enthalpy are optional. High Static Drive Accessory Available on many models, this high static drive accessory extends the capability of the standard motor. Avoid expensive motors and operating costs by installing this optimized sheave accessory. Factory Built Roof Curbs Available for the downflow units. Zone Sensors Available in programmable, automatic and manual styles. The following options round out the complete line of Voyager accessories: 0-25% manual outside air hood Motorized outside air for 12½-25 tons One Of Our Finest Assets: Trane Sales Representatives are a Support group that can assist you with: Product Application Service Training Special Applications Specifications Computer Programs and much more Voyager has the features and benefits that make it first class in the light commercial rooftop market. Designed with input from field contractors and engineers, its U-shaped airflow performance is outstanding. If all of your customers knew about Voyager, all would insist on it. ReliaTel RT-PRC002-EN 7
8 Application Considerations Application of this product should be within the cataloged airflow and cooling considerations. Low Ambient Cooling This Voyager line features, as standard, low ambient cooling down to 0 F. Contact your local Trane Representative for more assistance with low ambient cooling applications. Barometric Relief This product line offers an optional barometric relief damper included in the downflow economizer accessory. This accessory consists of gravity dampers which open with increased pressure. As the building air pressure increases, the pressure in the unit return air section also increases, opening the dampers and relieving the conditioned space. NOTE: THE EFFECTIVENESS OF BAROMETRIC RELIEF DAMPER DURING ECONOMIZING OPERATION IS SYSTEM RELATED. PRESSURE DROP OF THE RETURN AIR SYSTEM SHOULD BE CONSIDERED TO CONTROL BUILDING PRESSURIZA- TION. Power Exhaust Accessory The power exhaust accessory is available on all 12½-25 ton downflow units. This accessory can be field installed and will assist in relieving building pressurization. Condensate Trap The evaporator is a draw-thru configuration. A trap must be field provided prior to start-up on the cooling cycle. Clearance Requirements The recommended clearances identified with unit dimensions should be maintained to assure adequate serviceability, maximum capacity and peak operating efficiency. Actual clearances which appear inadequate should be reviewed with the local Trane sales personnel. Unit Pitch These units have sloped condensate drain pans. Units must be installed level, any unit slope must be toward access side of unit. 8 RT-PRC002-EN
9 Selection Procedure Cooling Capacity Step 1 Calculate the building s total and sensible cooling loads at design conditions. Use the Trane calculation methods or any other standard accepted method. Factors used in unit selection: A Total Cooling Load: 180 MBh B Sensible Cooling Load: 129 MBh C Airflow: 6000 cfm D Electrical Characteristics: 460/60/3 E Summer Design Conditions: Entering Evaporator Coil: 80 DB, 67 WB Outdoor Ambient: 95 DB F External Static Pressure: 0.49 in. wg G Rooftop - downflow configuration H Accessories Roof curb Economizer Electric Heat I Heating Capacity 115 MBh 460 volt/3 phase Electric Heat at 6000 cfm Step 2 As a starting point, a rough determination must be made of the size of the unit. The final selection will be made after examining the performance at the given conditions. Divide the total cooling load by nominal BTUH per ton (12 MBh per ton); then round up to the nearest unit size. 180 MBh / 12 MBh = 15.0 Tons Step 3 Table PD - 2 shows that a TCD180b4 has a gross cooling capacity of 184 MBh and 130 MBh sensible capacity at 6000 cfm and 95 DB outdoor ambient with 80 DB, 67 WB air entering the evaporator. To Find Capacity at Intermediate Conditions Not in the Table When the design conditions are between two numbers that are in the capacity table, interpolation is required to approximate the capacity. Note: Extrapolation outside of the table conditions is not recommended. Step 4 In order to select the correct unit which meets the building s requirements, the fan motor heat must be deducted from the gross cooling capacity. The amount of heat that the fan motor generates is dependent on the effort by the motor - cfm and static pressure. To determine the total unit static pressure you add the external static pressure to the additional static related by the added features: External Static (duct system) 0.49 wg Standard Filter 1 in wg from Table PD - 26 Economizer 0.04 wg (100% Return Air) from Table PD-26 Electric Heater Size 36 kw from Table PD - 26 Total Static Pressure 0.07 wg 0.60 wg Note: The Evaporator Fan Performance Table PD - 12 has already accounted for the pressure drop for standard filters and wet coils (see note below Table PD - 12). Therefore, the actual total static pressure is (from Table PD - 26) = 0.50 wg. With 6000 cfm and 0.50 wg. Table PD - 12 shows 2.56 bhp for this unit. Note below the table gives a formula to calculate Fan Motor Heat, 3.15 x bhp = MBH x 2.56 = 8.06 MBH. Now subtract the fan motor heat from the gross cooling capacity of the unit: Net Total Cooling Capacity = 184 MBH = MBH. Net Sensible Cooling Capacity = 130 MBH = MBH. Step 5 If the performance will not meet the required load of the building -total or sensible cooling load, try a selection at the next higher size unit. Heating Capacity Step 1 Calculate the building heating load using the Trane calculation form or other standard accepted method. Step 2 Size the system heating capacity to match the calculated building heating load. The following are building heating requirements: A Total heating load of MBH B 6000 cfm C 460 volt/3 phase Power Supply The electric heat accessory capacities are listed in Table PD From the table, a 36 kw heater will deliver MBH at 480 volts. In order to determine capacity at 460 volts, the heater voltage correction factor from Table PD - 28 must be used. Therefore, MBH x.94 (voltage correction factor) = MBH. Air Delivery Selection External static pressure drop through the air distribution system has been calculated to be 0.50 inches of water. From Table PD - 26 static pressure drop through the economizer is 0.04 and the 36 kw heater is 0.07 inches of water ( ). Enter Table PD - 12 for a TCD180B4 at 6000 cfm and 0.50 static pressure. The standard motor at 777 rpm will give the desired airflow at a rated bhp of RT-PRC002-EN 9
10 Model Number Description Packaged Cooling with Electric Heat Unit Typical Model Nomenclature T C D C A A Digits 1, 2 - Product Type TC = Packaged Cooling, Electric Heat TF = With Factory Installed Options Digit 3 - Airflow Configuration D = Downflow H = Horizontal Digits 4, 5, 6 - Nominal Gross Cooling Capacity (MBh) 150 = 12½ Tons Standard Efficiency 151 = 12½ Tons High Efficiency 180 = 15 Tons Standard Efficiency 181 = 15 Tons High Efficiency 210 = 17½ Tons Standard Efficiency 211 = 17½ Tons High Efficiency 240 = 20 Tons Standard Efficiency 241 = 20 Tons High Efficiency 300 = 25 Tons Standard Efficiency 301 = 25 Tons High Efficiency Digit 7- Major Development Sequence Digit 8 - Electrical Characteristics 3 = /60/3 4 = 460/60/3 W = 575/60/3 K = 380/60/3 Digit 9, 10 - Factory-Installed Options 00 = No Factory-installed Options 0A = Factory-installed Economizer 0B = Oversized Motor 0C = Downflow Economizer and Oversized Motor 0F = Trane Communications Interface (TCI) 0G = Downflow Economizer and TCI 0H = TXV/Face-Split Evaporator 0J = Oversized Motor and TXV/Face-Split Evaporator 0K = Downflow Economizer, Oversized Motor, and TXV/Face-Split Evaporator 0L = Downflow Economizer and TXV/Face- Split Evaporator Digit 11- Minor Design Sequence Digit 12- Service Digit 10 RT-PRC002-EN
11 General (12½, 15 Ton) Standard Efficiency Table GD - 1 General 12½ Ton Downflow and Horizontal Units 15 Ton Downflow and Horizontal Units TC*150D3, D4, DW, DK TC*180B3, B4, BW, BK Cooling Performance 1 Gross Cooling Capacity 150, ,000 EER Nominal CFM / ARI Rated CFM 5,000/4,400 6,000/5,300 ARI Net Cooling Capacity 142, ,000 Integrated Part Load Value System Power (KW) Compressor No./Type 2/Climatuff Scroll 2/Trane 3-D Scroll/Climatuff Scroll Sound Rating (BELS) Outdoor Coil Type Hi-Performance Hi-Performance Tube Size (in.) O.D Face Area (sq ft) Rows/FPI 2/16 3/16 Indoor Coil Type Hi-Performance Hi-Performance Tube Size (in.) Face Area (sq ft) Rows/FPI 2/15 2/15 Refrigerant Control Short Orifice Short Orifice Drain Connection No./Size (in.) 1/1.00 NPT 1/1.00 NPT Outdoor Fan Type Propeller Propeller No. Used/Diameter (in.) 2/26 2/26 Drive Type/No. Speeds Direct/1 Direct/1 CFM 10,600 10,200 No. Motors/HP 2/.50 2/.50 Motor RPM 1,100 1,100 Indoor Fan Type FC Centrifugal FC Centrifugal No. Used 1 1 Diameter x Width (in.) 15 x x 15 Drive Type/No. Speeds Belt/1 Belt/1 No. Motors 1 1 Motor HP (Standard/Oversized) 3.0/ /5.0 Motor RPM (Standard/Oversized) 1,740/3,450 1,740/3,450 Motor Frame Size (Standard/Oversized) 145T/145T 145T/145T Filters Type Furnished 6 Throwaway Throwaway (No.) Size Recommended (in.) Downflow (2) 20 x 20 x 2, (4) 20 x 25 x 2 (2) 20 x 20 x 2, (4) 20 x 25 x 2 Horizontal (2) 20 x 20 x 2, (4) 20 x 25 x 2 (2) 20 x 20 x 2, (4) 20 x 25 x 2 Refrigerant Charge (Lbs of R-22) 5 9.3/9.4/Circuit 17.5/9.5/Circuit 1. Cooling Performance is rated at 95 F ambient, 80 F entering dry bulb, 67 F entering wet bulb. Gross capacity does not include the effect of fan motor heat. ARI capacity is net and includes the effect of fan motor heat. Units are suitable for operation to ±20% of nominal cfm. Certified in accordance with the Unitary Large Equipment certification program, which is based on ARI Standard 340/ EER is rated at ARI conditions and in accordance with ARI Standard 210/240 or Integrated Part Load Value is based in accordance with ARI Standard 210/240 or 360. Units are rated at 80 F ambient, 80 F entering dry bulb, and 67 F entering wet bulb at ARI rated cfm. 4. Sound Rating shown is tested in accordance with ARI Standard 270 or Refrigerant charge is an approximate value. For a more precise value, see unit nameplate and service instructions. 6. Optional 2 inch pleated filters are also available. 7. For 380V/60Hz units, the oversized motor is used as the standard motor. Refer to oversized motor data. *Indicates both downflow and horizontal units. RT-PRC002-EN 11
12 General (17½, 20, 25 Ton) Standard Efficiency Table GD - 2 General 17½ Ton 20 Ton 25 Ton Downflow and Horizontal Units Downflow and Horizontal Units Downflow and Horizontal Units TC*210C3, C4, CW, CK TC*240B3, B4, BW, BK TC*300B3, B4, BW, BK Cooling Performance 1 Gross Cooling Capacity 210, , ,000 EER Nominal CFM / ARI Rated CFM 7,000/5,800 8,000/7,000 10,000/8,750 ARI Net Cooling Capacity 196, , ,000 Integrated Part Load Value System Power (KW) Compressor No./Type 2/Trane 3-D Scroll/Climatuff Scroll 2/Trane 3-D Scroll 2/Trane 3-D Scroll Sound Rating (BELS) Outdoor Coil Type Hi-Performance Hi-Performance Hi-Performance Tube Size (in.) O.D Face Area (sq ft) Rows/FPI 3/16 3/16 2/16 Indoor Coil Type Hi-Performance Hi-Performance Hi-Performance Tube Size (in.) Face Area (sq ft) Rows/FPI 4/15 2/15 3/15 Refrigerant Control Short Orifice Short Orifice Short Orifice Drain Connection No./Size (in.) 1/1.00 NPT 1/1.00 NPT 1/1.00 NPT Outdoor Fan Type Propeller Propeller Propeller No. Used/Diameter (in.) 2/26 2/26 2/28 Drive Type/No. Speeds Direct/1 Direct/1 Direct/1 CFM 13,400 14,600 16,700 No. Motors/HP 2/1.0 2/1.0 2/1.0 Motor RPM 1,125 1,125 1,125 Indoor Fan Type FC Centrifugal FC Centrifugal FC Centrifugal No. Used Diameter x Width (in.) 15 x x x 18 Drive Type/No. Speeds Belt / 1 Belt / 1 Belt / 1 No. Motors Motor HP (Standard/Oversized) 5.0/ / /NA Motor RPM (Standard/Oversized) 3,450/3,470 3,450/3,470 3,470/NA Motor Frame Size (Standard/Oversized) 145T/184T 145T/184T 184T/NA Filters Type Furnished 7 Throwaway Throwaway Throwaway (No.) Size Recommended (in.) Downflow (2) 20 x 20 x 2, (4) 20 x 25 x 2 (4) 20 x 20 x 2, (4) 20 x 25 x 2 (4) 20 x 20 x 2, (4) 20 x 25 x 2 Horizontal (2) 20 x 20 x 2, (4) 20 x 25 x 2 (8) 20 x 25 x 2 (8) 20 x 25 x 2 Refrigerant Charge (Lbs of R-22) /14.3/Circuit /21.0/Circuit 17.0/Circuit 1. Cooling Performance is rated at 95 F ambient, 80 F entering dry bulb, 67 F entering wet bulb. Gross capacity does not include the effect of fan motor heat. ARI capacity is net and includes the effect of fan motor heat. Units are suitable for operation to ±20% of nominal cfm. 17½ - 20 ton models are certified in accordance with the Unitary Large Equipment certification program, which is based on ARI Standard 340/ ton model ratings shown are tested in accordance with ARI Standard 340/ EER is rated at ARI conditions and in accordance with ARI Standard 210/240 or Integrated Part Load Value is based in accordance with ARI Standard 210/240 or 360. Units are rated at 80 F ambient, 80 F entering dry bulb, and 67 F entering wet bulb at ARI rated cfm. 4. Sound Rating shown is tested in accordance with ARI Standard 270 or Refrigerant charge is an approximate value. For a more precise value, see unit nameplate and service instructions. 6. Refrigerant charge for horizontal models is 21.5/14.5 per circuit. 7. Optional two inch pleated filters are also available. 8. For 380V/60Hz units, the oversized motor is used as the standard motor. Refer to oversized motor data. *Indicates both downflow and horizontal units. 12 RT-PRC002-EN
13 General (12½, Ton) High Efficiency Table GD - 3 General 12½ Ton Downflow and Horizontal Models TC*151C3,C4,CW Cooling Performance 1 Gross Cooling Capacity 154,000 EER Nominal CFM / ARI Rated CFM 5,000/4,400 ARI Net Cooling Capacity 146,000 Integrated Part Load Value System Power KW Compressor No./Type 2/Copeland Scroll Sound Rating (BELS) Outdoor Coil Type Hi-Performance Tube Size (in.) O.D Face Area (sq ft) Rows/FPI 3/16 Indoor Coil Type Hi-Performance Tube Size (in.) Face Area (sq ft) Rows/FPI 3/15 Refrigerant Control Short Orifice 9 Drain Connection No./Size (in.) 1/1.0 NPT Outdoor Fan Type Propeller No. Used/Diameter (in.) 2/26 Drive Type/No. Speeds Direct/1 CFM 10,400 No. Motors/HP 2/.50 Motor RPM 1100 Indoor Fan Type FC Centrifugal No. Used 1 Diameter x Width (in.) 15 x 15 Drive Type/No. Speeds BELT/1 No. Motors 1 Motor HP (Standard/Oversized) 3.0/5.0 Motor RPM (Standard/Oversized) 1740/3450 Motor Frame Size (Standard/Oversized) 145T/145T Filters Type/Furnished? Throwaway/Yes 8 (No.) Size Recommended (in.) (2)20 X 20 X 2/ (4)20 X 25 X 2 Refrigerant Charge (Lbs of R-22) 5 /Circuit 15.0/ Cooling Performance is rated at 95 F ambient, 80 F entering dry bulb, 67 F entering wet bulb. Gross capacity does not include the effect of fan motor heat. ARI capacity is net and includes the effect of fan motor heat. Units are suitable for operation to ±20% of nominal cfm. Certified in accordance with the Unitary Large Equipment certification program, which is based on ARI Standard 340/ EER is rated at ARI conditions and in accordance with DOE test procedures. 3. Integrated Part Load Value is based in accordance with ARI Standard 210/240 or 360. Units are rated at 80 F ambient, 80 F entering dry bulb, and 67 F entering wet bulb at ARI rated cfm. 4. Sound Rating shown is tested in accordance with ARI Standard 270 or Refrigerant charge is an approximate value. For a more precise value, see unit nameplate and service instructions. 6. Face area for Indoor Coil on horizontal models is Horizontal models have 4-20 x 25 x 2 filters. 8. Optional two inch pleated filters are also available for 12½ ton models. 9. TXV/Face-Split Option (Downflow Only) TCD151C3,4,W (Refrigerant Control): Expansion Valve; (Refrigerant Charge): 13.4/12.0. *Indicates both downflow and horizontal units. RT-PRC002-EN 13
14 General (15, 17½, 20, 25 Ton) High Efficiency Table GD - 4 General 15 Ton 17½ Ton 20 Ton 25 Ton Downflow and Horizontal Models TC*181C3,C4,CW TC*211C3,C4,CW TC*241C3,C4,CW TC*301C3,C4,CW Cooling Performance 1 Gross Cooling Capacity 189, , , , EER Nominal CFM / ARI Rated CFM 6,000/5,300 7,000/6,200 8,000/7,000 10,000/8,750 ARI Net Cooling Capacity 180, , , ,000 Integrated Part Load Value System Power KW Compressor No./Type Trane 3-D Scroll/Climatuff Scroll 2/Trane3-D Scroll/Copeland Scroll 2/Trane 3-D Scroll/Copeland Scroll 2/Trane 3-D Scroll Sound Rating (BELS) Outdoor Coil Type Hi-Performance Hi-Performance Hi-Performance Hi-Performance Tube Size (in.) O.D Face Area (sq ft) Rows/FPI 3/16 3/16 3/16 3/16 Indoor Coil Type Hi-Performance Hi-Performance Hi-Performance Hi-Performance Tube Size (in.) Face Area (sq ft) Rows/FPI 3/15 4/15 4/15 4/15 Refrigerant Control Short Orifice 8 Short Orifice Short Orifice 9 Short Orifice 11 Drain Connection No./Size (in.) 1/1.0 NPT 1 /1.0 NPT 1/1.0 NPT 1/1.0 NPT Outdoor Fan Type Propeller Propeller Propeller Propeller No. Used/Diameter (in.) 2/26 2/26 2/26 2/26 Drive Type/No. Speeds Direct/1 Direct/1 Direct/1 Direct/1 CFM 11,000 12,800 13,700 13,700 No. Motors/HP 2/.50 2/1.00 2/1.00 2/1.00 Motor RPM Indoor Fan Type FC Centrifugal FC Centrifugal FC Centrifugal FC Centrifugal No. Used Diameter x Width (in.) 18 x x x x 18 Drive Type/No. Speeds BELT/1 BELT/1 BELT/1 BELT/1 No. Motors Motor HP (Standard/Oversized) 3.0/ / / /NA Motor RPM (Standard/Oversized) 1740/ / / /NA Motor Frame Size (Standard/Oversized) 145T/145T 145T/184T 145T/184T 184T/NA Filters Type Furnished 7 Throwaway Throwaway Throwaway Throwaway (No.) Size Recommended (in.) (4/4)20 X 20 X 2/20 X 25 X 2 6 (4/4)20 X 20 X 2/20 X 25 X 2 6 (4/4)20 X 20 X 2/20 X 25 X 2 6 (4/4)20X20X2/20X25X2 6 Refrigerant Charge (Lbs of R-22) 5 / Circuit 25/ / / / Cooling Performance is rated at 95 F ambient, 80 F entering dry bulb, 67 F entering wet bulb. Gross capacity does not include the effect of fan motor heat. ARI capacity is net and includes the effect of fan motor heat ton models are certified in accordance with the Unitary Large Equipment certification program, which is based on ARI Standard 340/ ton model ratings shown are tested in accordance with ARI Standard 340/ EER is rated at ARI conditions and in accordance with DOE test procedures. 3. Integrated Part Load Value is based in accordance with ARI Standard 210/240 or 360. Units are rated at 80 F ambient, 80 F entering dry bulb, and 67 F entering wet bulb at ARI rated cfm. 4. Sound Rating shown is tested in accordance with ARI Standard 270 or Refrigerant charge is an approximate value. For a more precise value, see unit nameplate and service instructions. 6. Horizontal models have 8-20 x 25 x 2 filters. 7. Optional two inch pleated filters are also available. 8. TXV/Face-Split Option (Downflow Only) TCD181C3,4,W (EER):11.4; (System Power kw): 15.79; (Refrigerant Control): Expansion Valve; (Refrigerant Charge): 26.0/ TXV/Face-Split Option (Downflow Only) TCD241C3,4,W (Gross Cooling Capacity):259,000; (ARI Net Cooling Capacity): 244,000; (System Power kw): 23.02; (Refrigerant Control): Expansion Valve; (Refrigerant Charge): 21.5/ TXV/Face-Split Option (Downflow Only) TCD211C3,4,W Refrigerant Charge): 27.0/ TXV/Face-Split Option (Downflow Only) TCD301C3,4,W (EER): 10; (Gross Cooling Capacity): 294,000; (ARI Net Cooling Capacity): 272,000; (IPLV): 10.6; System Power kw): 27.2; Refrigerant Control: Expansion Valve; (Refrigerant Charge): 21.0/23.0 *Indicates both downflow and horizontal units. 14 RT-PRC002-EN
15 Performance (12½, 15 Ton) Standard Efficiency Table PD-1 Gross Cooling Capacities (MBH) 12½ Ton Three Phase TC*150D3, D4, DW, DK Ambient Temperature Enter Dry Entering Wet Bulb CFM Bulb Airflow (F) MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC All capacities shown are gross and have not considered indoor fan heat. To obtain net cooling subtract indoor fan heat. 2. MBH = Total Gross Cooling Capacity 3. SHC = Sensible Heat Capacity Table PD-2 Gross Cooling Capacities (MBH) 15 Ton Three Phase TC*180B3, B4, BW, BK Ambient Temperature Enter. Dry Entering Wet Bulb CFM Bulb Airflow (F) MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC All capacities shown are gross and have not considered indoor fan heat. To obtain net cooling subtract indoor fan heat. 2. MBH = Total Gross Capacity 3. SHC = Sensible Heat Capacity *Indicates both downflow and horizontal units. RT-PRC002-EN 15
16 Performance (17½, 20 Ton) Standard Efficiency Table PD-3 Gross Cooling Capacities (MBH) 17½ Ton Three Phase TC*210C3, C4, CW, CK Ambient Temperature Enter Dry Entering Wet Bulb CFM Bulb Airflow (F) MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC All capacities shown are gross and have not considered indoor fan heat. To obtain net cooling subtract indoor fan heat. 2. MBH = Total Gross Cooling Capacity 3. SHC = Sensible Heat Capacity Table PD-4 Gross Cooling Capacities (MBH) 20 Ton Three Phase TC*240B3, B4, BW, BK Ambient Temperature (F) Enter. Dry Entering Wet Bulb (F) CFM Bulb Airflow (F) MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC All capacities shown are gross and have not considered indoor fan heat. To obtain net cooling subtract indoor fan heat. 2. MBH = Total Gross Capacity 3. SHC = Sensible Heat Capacity *Indicates both downflow and horizontal units. 16 RT-PRC002-EN
17 Performance (25 Ton) Standard Efficiency Table PD-5 Gross Cooling Capacities (MBH) 25 Ton Three Phase TC*300B3, B4, BW, BK Ambient Temperature (F) Enter. Dry Entering Wet Bulb (F) CFM Bulb Airflow (F) MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC All capacities shown are gross and have not considered indoor fan heat. To obtain net cooling subtract indoor fan heat. 2. MBH = Total Gross Capacity 3. SHC = Sensible Heat Capacity 4. Table is for 460 volt capacity. For capacity at 230 volt, multiply table capacity by 101%. RT-PRC002-EN 17
18 Performance (12½ Ton) High Efficiency Table PD-6 Gross Cooling Capacities (MBH) 12½ Ton Three Phase TC*151C3, C4, CW Ambient Temperature Enter Dry Entering Wet Bulb CFM Bulb Airflow (F) MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC All capacities shown are gross and have not considered indoor fan heat. To obtain net cooling subtract indoor fan heat. 2. MBH = Total Gross Cooling Capacity 3. SHC = Sensible Heat Capacity *Indicates both downflow and horizontal units. 18 RT-PRC002-EN
19 Performance (15, 17½ Ton) High Efficiency Table PD-7 Gross Cooling Capacities (MBH) 15 Ton Three Phase TC*181C3, C4, CW Ambient Temperature Enter. Dry Entering Wet Bulb CFM Bulb Airflow (F) MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC All capacities shown are gross and have not considered indoor fan heat. To obtain net cooling subtract indoor fan heat. 2. MBH = Total Gross Capacity 3. SHC = Sensible Heat Capacity Table PD-8 Gross Cooling Capacities (MBH)17½ Ton Three Phase TC*211C3, C4, CW Ambient Temperature Enter Dry Entering Wet Bulb CFM Bulb Airflow (F) MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC All capacities shown are gross and have not considered indoor fan heat. To obtain net cooling subtract indoor fan heat. 2. MBH = Total Gross Cooling Capacity 3. SHC = Sensible Heat Capacity *Indicates both downflow and horizontal units. RT-PRC002-EN 19
20 Performance (20, 25 Ton) High Efficiency Table PD-9 Gross Cooling Capacities (MBH) 20 Ton Three Phase TC*241C3, C4, CW Ambient Temperature (F) Enter. Dry Entering Wet Bulb (F) CFM Bulb Airflow (F) MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC All capacities shown are gross and have not considered indoor fan heat. To obtain net cooling subtract indoor fan heat. 2. MBH = Total Gross Capacity 3. SHC = Sensible Heat Capacity Table PD-10 Gross Cooling Capacities (MBH)25 Ton Three PhaseTC*301C3, C4, CW Ambient Temperature (F) Enter. Dry Entering Wet Bulb (F) CFM Bulb Airflow (F) MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC All capacities shown are gross and have not considered indoor fan heat. To obtain net cooling subtract indoor fan heat. 2. MBH = Total Gross Capacity 3. SHC = Sensible Heat Capacity 20 RT-PRC002-EN
21 Performance (12½ Ton) Standard Efficiency Table PD-11 Evaporator Fan Performance 12½Ton TC*150D External Static Pressure (Inches of Water) CFM RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP 3 HP Standard Motor & Field 3 HP Standard Motor & Sheaves Supplied Low Static Drive Table PD-11 Evaporator Fan Performance 12½ Ton TC*150D Continued External Static Pressure (Inches of Water) CFM RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP 3 HP Standard Motor & Sheaves 3 HP Standard Motor & High Static Drive Accessory HP Oversize Motor & Sheaves For Standard Evaporator Fan Speed (RPM), reference Table PD-22. For Oversized Evaporator Fan Speed (RPM), reference Table PD-24. Fan motor heat (MBH) = 3.15 x Fan BHP includes pressure drop due to wet coils and filters No accessories or options are included in pressure drop data. Refer to Table PD-26 to determine add l static pressure drop due to other options/accessories. 1. Field Supplied Fan Sheave BK90 Required. Field Supplied Belt may be necessary HP Oversized Motor with Field Supplied Motor Sheave IVL40 Required. Field Supplied Belt may be necessary. 3. For 380V/60 Hz units, the oversized motor is used as the standard motor. Refer to Motor & Sheave/Fan Speed tables to determine operating range. 5 HP Oversize Motor & Field Supplied Drive Trane s factory supplied motors, in commercial equipment, are definite purpose motors, specifically designed and tested to operate reliably and continuously at all cataloged conditions. Using the full horsepower range of our fan motors as shown in our tabular data will not result in nuisance tripping or premature motor failure. Our product s warranty will not be affected. RT-PRC002-EN 21
22 Performance (15 Ton) Standard Efficiency Table PD-12 Evaporator Fan Performance 15 Ton TC*180B External Static Pressure (Inches of Water) CFM RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP 3 HP Standard Motor & Field 3 HP Standard Motor & Sheaves Supplied Low Static Drive (1) (2) 5 HP Oversized Motor & Sheaves Table PD-12 Evaporator Fan Performance 15 Ton TC*180B Continued External Static Pressure (Inches of Water) CFM RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP 3 HP Standard Motor & Sheaves 3 HP Standard Motor & High Static Drive Accessory HP Oversized Motor & Sheaves 5 HP OS Motor & Field Supplied Drive (3) For Standard Evaporator Fan Speed (RPM), reference Table PD-22. For Standard Motor & High Static Drive Accessory Fan Speed (RPM), reference Table PD-23. For Oversized Evaporator Fan Speed (RPM), reference Table PD-24. Fan motor heat (MBH) = 3.15 x Fan BHP includes pressure drop due to wet coils and filters No accessories or options are included in pressure drop data. Refer to Table PD-26 to determine add l static pressure drop due to other options/accessories. 1. Field Supplied Fan Sheave BK105 Required. Field Supplied Belt may be necessary HP Oversized Motor with Field Supplied Fan Sheave BK160 Required. Field Supplied Belt may be necessary HP Oversized Motor with Field Supplied Motor Sheave IVP50 Required. Field Supplied Belt may be necessary. 4. For 380V/60 Hz units, the oversized motor is used as the standard motor. Refer to Motor & Sheave/Fan Speed tables to determine operating range. Trane s factory supplied motors, in commercial equipment, are definite purpose motors, specifically designed and tested to operate reliably and continuously at all cataloged conditions. Using the full horsepower range of our fan motors as shown in our tabular data will not result in nuisance tripping or premature motor failure. Our product s warranty will not be affected. 22 RT-PRC002-EN
23 Performance (17½Ton) Standard Efficiency Table PD-13 Evaporator Fan Performance 17½ Ton TC*210C External Static Pressure (Inches of Water) CFM RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP 5 HP Standard Motor with Low Static Drive Accessory HP Oversize Motor & Sheaves 5 HP Standard Motor & Sheaves Table PD-13 Evaporator Fan Performance 17½ Ton TC*210C Continued External Static Pressure (Inches of Water) CFM RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP 5 HP Standard Motor & Sheaves For Standard Evaporator Fan Speed (RPM), reference Table PD-22. For Standard Motor & Low Static Drive Accessory Fan Speed (RPM), reference Table PD-25. For Oversized Evaporator Fan Speed (RPM), reference Table PD-24. NOTE: Fan motor heat (MBH) = 3.15 x Fan BHP includes pressure drop due to wet coils and filters No accessories or options are included in pressure drop data. Refer to Table PD-26 to determine add l static pressure drop due to other options/accessories. 1. For 380V/60 Hz units, the oversized motor is used as the standard motor. Refer to Motor & Sheave/Fan Speed tables to determine operating range. 7.5 HP Oversive Motor & Sheaves Trane s factory supplied motors, in commercial equipment, are definite purpose motors, specifically designed and tested to operate reliably and continuously at all cataloged conditions. Using the full horsepower range of our fan motors as shown in our tabular data will not result in nuisance tripping or premature motor failure. Our product s warranty will not be affected. *Indicates both downflow and horizontal units. RT-PRC002-EN 23
24 Performance (20 Ton) Standard Efficiency Table PD-14 Evaporator Fan Performance 20 Ton TC*240B External Static Pressure (Inches of Water) CFM RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP 5 HP Standard Motor & Field Supplied 5 HP Standard Motor & Sheaves Low Static Drive (1) HP Standard Motor & Sheaves (2) 7.5 HP Oversized Motor & Sheaves Table PD-14 Evaporator Fan Performance 20 Ton TC*240B Continued External Static Pressure (Inches of Water) CFM RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP 5 HP Standard Motor & Sheaves 5 HP Standard Motor & High Static Drive Accessory HP Oversized Motor & Sheaves For Standard Evaporator Fan Speed (RPM), reference Table PD-22. For Standard Motor & High Static Drive Accessory Fan Speed (RPM), reference Table PD-23. For Oversized Evaporator Fan Speed (RPM), reference Table PD-24. Fan motor heat (MBH) = 3.15 x Fan BHP includes pressure drop due to wet coils and filters No accessories or options are included in pressure drop data. Refer to Table PD-26 to determine add l static pressure drop due to other options/accessories. 1. Field Supplied Fan Sheave BK190 Required. Field Supplied Belt may be necessary HP Standard Motor with Field Supplied Motor Sheave IVP50 Required. Field Supplied Belt may be necessary. 3. For 380V/60 Hz units, the oversized motor is used as the standard motor. Refer to Motor & Sheave/Fan Speed tables to determine operating range. Trane s factory supplied motors, in commercial equipment, are definite purpose motors, specifically designed and tested to operate reliably and continuously at all cataloged conditions. Using the full horsepower range of our fan motors as shown in our tabular data will not result in nuisance tripping or premature motor failure. Our product s warranty will not be affected. *Indicates both downflow and horizontal units. 24 RT-PRC002-EN
25 Performance (25 Ton) Standard Efficiency Table PD-15 Evaporator Fan Performance 25 Ton TC*300B External Static Pressure (Inches of Water) CFM RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP 7.5 HP Standard Motor & Low Static Drive Accessory 7.5 HP Standard Motor & Sheaves HP Standard Motor & Sheaves 7.5 HP Standard Motor & High Static Drive Accessory Table PD-15 Evaporator Fan Performance 25 Ton TC*300B Continued External Static Pressure (Inches of Water) CFM RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP 7.5 HP Standard Motor & Sheaves HP Oversized Motor & High Static Drive Accessory For Standard Evaporator Fan Speed (RPM), reference Table PD-22. For Standard Motor & High Static Drive Accessory Fan Speed (RPM), reference Table PD-23. For Standard Motor & Low Static Drive Accessory Fan Speed (RPM), reference Table PD-25. Fan motor heat (MBH) = 3.15 x Fan BHP includes pressure drop due to wet coils and filters No accessories or options are included in pressure drop data. Refer to Table PD-26 to determine add l static pressure drop due to other options/accessories. 1. For 380V/60 Hz units, the oversized motor is used as the standard motor. Refer to Motor & Sheave/Fan Speed tables to determine operating range. Trane s factory supplied motors, in commercial equipment, are definite purpose motors, specifically designed and tested to operate reliably and continuously at all cataloged conditions. Using the full horsepower range of our fan motors as shown in our tabular data will not result in nuisance tripping or premature motor failure. Our product s warranty will not be affected. *Indicates both downflow and horizontal units. RT-PRC002-EN 25
26 Performance (12½ Ton) High Efficiency Table PD-16 Evaporator Fan Performance 12½Ton TCD151C External Static Pressure (Inches of Water) CFM RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP 3 HP Standard Motor & Field 3 HP Standard Motor & Drive Supplied Low Static Drive (1) HP Oversized Motor & Drive 3 HP Standard Motor & High Static Drive Accessory Table PD-16 Evaporator Fan Performance 12½ Ton TCD151C Continued External Static Pressure (Inches of Water) CFM RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP 3 HP Standard 3 HP Standard Motor & High Static Drive Accessory Motor & Drive HP Oversized Motor & Drive For Standard Evaporator Fan Speed (RPM), reference Table PD-22. For Standard Motor & High Static Drive Accessory Fan Speed (RPM), reference Table PD-23. For Oversized Evaporator Fan Speed (RPM), reference Table PD-24. NOTE: Fan motor heat (MBH) = 3.15 x Fan BHP includes pressure drop due to wet coils and filters No accessories or options are included in pressure drop data. Refer to Table PD-26 to determine add l static pressure drop due to other options/accessories. 1. Field Supplied Fan Sheave BK115 Required. Field Supplied Belt may be necessary. Trane s factory supplied motors, in commercial equipment, are definite purpose motors, specifically designed and tested to operate reliably and continuously at all cataloged conditions. Using the full horsepower range of our fan motors as shown in our tabular data will not result in nuisance tripping or premature motor failure. Our product s warranty will not be affected. 26 RT-PRC002-EN
27 Performance (12½ Ton) High Efficiency Table PD-17 Evaporator Fan Performance 12½Ton TCH151C External Static Pressure (Inches of Water) CFM RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP 3 HP Standard Motor & Field Supplied Low Static Drive (1) 3 HP Standard Motor & Drive HP Oversized Motor& Drive Table PD-17 Evaporator Fan Performance 12½ Ton TCH151C Continued External Static Pressure (Inches of Water) CFM RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP 3 HP Standard Motor & Drive 3 HP Standard Motor & High Static Drive Accessory HP Oversized Motor & Drive For Standard Evaporator Fan Speed (RPM), reference Table PD-22. For Standard Motor & High Static Drive Accessory Fan Speed (RPM), reference Table PD-23. For Oversized Evaporator Fan Speed (RPM), reference Table PD-24. NOTE: Fan motor heat (MBH) = 3.15 x Fan BHP includes pressure drop due to wet coils and filters No accessories or options are included in pressure drop data. Refer to Table PD-26 to determine add l static pressure drop due to other options/accessories. 1. Field Supplied Fan Sheave BK115 Required. Field Supplied Belt may be necessary. Trane s factory supplied motors, in commercial equipment, are definite purpose motors, specifically designed and tested to operate reliably and continuously at all cataloged conditions. Using the full horsepower range of our fan motors as shown in our tabular data will not result in nuisance tripping or premature motor failure. Our product s warranty will not be affected. RT-PRC002-EN 27
28 Performance (15 Ton) High Efficiency Table PD-18 Evaporator Fan Performance 15 Ton TC*181C External Static Pressure (Inches of Water) CFM RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP 3 HP Standard Motor & Field 3 HP Standard Motor & Drive Supplied Low Static Drive (1) HP Standard Motor & Drive 5 HP Oversized Motor& Drive Table PD-18 Evaporator Fan Performance 15 Ton TC*181C Continued External Static Pressure (Inches of Water) CFM RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP 3 HP Standard Motor & Drive 3 HP Standard Motor & High Static Drive Accessory HP Oversized Motor & Drive For Standard Evaporator Fan Speed (RPM), reference Table PD-22. For Standard Motor & High Static Drive Accessory Fan Speed (RPM), reference Table PD-23. For Oversized Evaporator Fan Speed (RPM), reference Table PD-24. NOTE: Fan motor heat (MBH) = 3.15 x Fan BHP includes pressure drop due to wet coils and filters No accessories or options are included in pressure drop data. Refer to Table PD-26 to determine add l static pressure drop due to other options/accessories. 1. Field Supplied Fan Sheave BK120 Required. Field Supplied Belt may be necessary. Field Supplied Belt may be necessary. Trane s factory supplied motors, in commercial equipment, are definite purpose motors, specifically designed and tested to operate reliably and continuously at all cataloged conditions. Using the full horsepower range of our fan motors as shown in our tabular data will not result in nuisance tripping or premature motor failure. Our product s warranty will not be affected. *Indicates both downflow and horizontal units. 28 RT-PRC002-EN
29 Performance (17½ Ton) High Efficiency Table PD-19 Evaporator Fan Performance 17½ Ton TC*211C External Static Pressure (Inches of Water) CFM RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP 5 HP Standard Motor & Field 5 HP Standard Motor & Drive Supplied Low Static Drive (1) HP Standard Motor & High Static Drive Accessory Table PD-19 Evaporator Fan Performance 17½ Ton TC*211C Continued External Static Pressure (Inches of Water) CFM RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP 5 HP Standard Motor & Drive 5 HP Standard Motor & High Static Drive Accessory HP Oversized Motor & Drive For Standard Evaporator Fan Speed (RPM), reference Table PD-22. For Standard Motor & High Static Drive Accessory Fan Speed (RPM), reference Table PD-23. For Oversized Evaporator Fan Speed (RPM), reference Table PD-24. NOTE: Fan motor heat (MBH) = 3.15 x Fan BHP includes pressure drop due to wet coils and filters No accessories or options are included in pressure drop data. Refer to Table PD-26 to determine add l static pressure drop due to other options/accessories. 1. Field Supplied Fan Sheave BK190 Required. Field Supplied Belt may be necessary. Trane s factory supplied motors, in commercial equipment, are definite purpose motors, specifically designed and tested to operate reliably and continuously at all cataloged conditions. Using the full horsepower range of our fan motors as shown in our tabular data will not result in nuisance tripping or premature motor failure. Our product s warranty will not be affected. *Indicates both downflow and horizontal units. RT-PRC002-EN 29
30 Performance (20 Ton) High Efficiency Table PD-20 Evaporator Fan Performance 20 Ton TC*241C External Static Pressure (Inches of Water) CFM RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP 5 HP Standard Motor & Field Supplied 5 HP Standard Motor & Drive Low Static Drive (1) (2) 7.5 HP Oversized Motor & Drive Table PD-20 Evaporator Fan Performance 20 Ton TC*241C Continued External Static Pressure (Inches of Water) CFM RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP 5 HP Standard Motor & Drive 5 HP Standard Motor & High Static Drive Accessory HP Oversized Motor & Drive For Standard Evaporator Fan Speed (RPM), reference Table PD-22. For Standard Motor & High Static Drive Accessory Fan Speed (RPM), reference Table PD-23. For Oversized Evaporator Fan Speed (RPM), reference Table PD-24. Fan motor heat (MBH) = 3.15 x Fan BHP includes pressure drop due to wet coils and filters No accessories or options are included in pressure drop data. 1. Field Supplied Fan Sheave BK190 Required. Field Supplied Belt may be necessary HP Standard Motor with Field Supplied Motor Sheave 1VP50 Required. Field Supplied Belt may be necessary. Trane s factory supplied motors, in commercial equipment, are definite purpose motors, specifically designed and tested to operate reliably and continuously at all cataloged conditions. Using the full horsepower range of our fan motors as shown in our tabular data will not result in nuisance tripping or premature motor failure. Our product s warranty will not be affected. *Indicates both downflow and horizontal units. 30 RT-PRC002-EN
31 Performance (25 Ton) High Efficiency Table PD-21 Evaporator Fan Performance 25 Ton TC*301C External Static Pressure (Inches of Water) CFM RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP 7.5 HP Standard Motor & Low Static Drive Accessory 7.5 HP Standard Motor & Drive HP Standard Motor & Drive Table PD-21 Evaporator Fan Performance 25 Ton TC*301C Continued External Static Pressure (Inches of Water) CFM RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP 7.5 HP Standard Motor & Drive HP Standard Motor & High Static Drive Accessory For Standard Evaporator Fan Speed (RPM), reference Table PD-22. For Standard Motor & High Static Drive Accessory Fan Speed (RPM), reference Table PD-23. For Standard Motor & Low Static Drive Accessory Fan Speed (RPM), reference Table PD-25. NOTE: Fan motor heat (MBH) = 3.15 x Fan BHP includes pressure drop due to wet coils and filters No accessories or options are included in pressure drop data. Refer to Table PD-26 to determine add l static pressure drop due to other options/accessories. Trane s factory supplied motors, in commercial equipment, are definite purpose motors, specifically designed and tested to operate reliably and continuously at all cataloged conditions. Using the full horsepower range of our fan motors as shown in our tabular data will not result in nuisance tripping or premature motor failure. Our product s warranty will not be affected. *Indicates both downflow and horizontal units. RT-PRC002-EN 31
32 Performance (12½-25 Ton) Table PD-22 Standard Motor & Drive/Fan Speed (Rpm) Unit 6 Turns 5 Turns 4 Turns 3 Turns 2 Turns 1 Turn Tons Model No. Open Open Open Open Open Open Closed 12½ TC*150D3,4,W, YC*151C3,4,W NA TC*150DK NA TC*180B3,4,W NA 15 TC*180BK N/A TC*181C3,4,W NA TC*210C3,4,W NA 17½ TC*210CK NA TC*211C3,4,W NA 20 TC*240B3,4,W, TC*241C3,4,W NA TC*240BK NA 25 TC*300B3,4,W, TC*301C3,4,W NA TC*300BK NA Factory set at 3 turns open. Table PD-23 Standard Motor & High Static Drive Accessory/Fan Speed (Rpm) Unit 6 Turns 5 Turns 4 Turns 3 Turns 2 Turns 1 Turn Tons Model No. Open Open Open Open Open Open Closed 12½ TC*151C3,4,W NA 15 TC*180B3,4,W NA TC*181B3,4,W NA 17½ TC*211C3,4,W NA 20 TC*240B/241C3,4,W NA 25 TC*300B/301C3,4,W NA Table PD-24 Oversized Motor & Drive/Fan Speed (Rpm) Unit 6 Turns 5 Turns 4 Turns 3 Turns 2 Turns 1 Turn Tons Model No. Open Open Open Open Open Open Closed 12½ TC*150D,151C3,4,W NA 15 TC*180B3,4,W NA TC*181C3,4,W NA 17½ TC*210C3,4,W NA TC*211C3,4,W NA 20 TC*240B3,4,W, TYC*241C3,4,W NA Table PD-25 Standard Motor & Low Static Fan Drive Unit 6 Turns 5 Turns 4 Turns 3 Turns 2 Turns 1 Turn Tons Model No. Open Open Open Open Open Open Closed 17½ TC*210C3,4,W NA 25 TC*300B3,4,W,301C3,4,W NA *Indicates both downflow and horizontal units. 32 RT-PRC002-EN
33 Performance (12½-25 Ton) Table PD-26 Static Pressure Drops Through Accessories (Inches Water Column) Economizer with Electric Heater Unit Standard 2 Inch OA/RA Dampers 2 Accessory (KW) 3 Tons Model No. CFM Filters 1 Pleated Filters 4 100% OA 100% RA TC*150D ½ TC*151C TC*180B /.03.07/ TCD/TCH181C /.05.10/ /.07.13/ TC*210C ½ /.05.09/ TCD/TCH211C /.07.13/ /.10.17/ TCD240B TCD241C TCH240B TCH241C TCD300B TCD301C TCH300B TCH301C Tested with: 2 filters 12½-25 tons 2. OA = Outside Air and RA = Return Air. 3. Nominal KW ratings at 240, 480, 600 volts. 4. Difference in pressure drop should be considered when utilizing optional 2 pleated filters. *Indicates both downflow and horizontal units. RT-PRC002-EN 33
34 Performance (12½-25 Ton) Table PD-27 Auxiliary Electric Heat Capacity Total2 Stage1 Stage 2 Unit KW MBH No. of KW MBH KW MBH Tons Model No. Input 1 Output 1 Stages Input 1 Output 1 Input 1 Output TC*150D3,D4,DW,DK ½-15 TC*180B3,B4,BW,BK TC*151 or 181C3,C4,CW TC*210C3,C4,CW,CK ½, 20, , 300B3,B4,BW,BK TC*211, 241, 301C3,C4,CW Does not include indoor fan power or heat. Voltage 2. Heaters are rated at 240v, 480v. and 600v. For other than rated voltage, CAP = ( x rated cap. 3. Not available on TC*210C. Rated Voltage) KW heater can be used with TCD181C4, TCD211C4, TCD241C4 andtcd301c4 only. Cannot be used with oversized motor. Table PD-28 Electric Heater Voltage Correction Factors (Applicable to Auxiliary Heat Capacity) Nominal Distribution Capacity Voltage Voltage Multiplier Table PD-29 Air Temperature Rise Across Electric Heaters (Degree F) 12½ Ton 15 Ton 17½ Ton 20 Ton 25 Ton 5000 CFM 6000 CFM 7000 CFM 8000 CFM 9000 CFM Three Phase Three Phase Three Phase Three Phase Three Phase TC*150 TC*180 TC*210 TC*240 TC*300 KW Stages TC*151 TC*181 TC*211 TC*241 TC* For minimum design airflow, see airflow performance table for each unit. To calculate temp rise at different air flow, use following formula: KW x 3413 Temp. Rise across Elect. Htr = 1.08 x CFM 1. Not available on TC*210 model KW heater can be used with TCD181C4, TCD211C4, TCD241C4 andtcd301c4 only. Cannot be used with oversized motor. 34 RT-PRC002-EN
35 Controls Field Installed Control Options Zone Sensors Zone sensors are the building occupant s comfort control devices. They replace the conventional electro-mechanical thermostats. The following zone sensor options are available for Voyager units with the ReliaTel control: Manual Changeover Heat, Cool or Off System Switch. Fan Auto or Off Switch. One temperature setpoint lever. Manual/Automatic Changeover Auto, Heat, Cool or Off System Switch. Fan Auto or Off Switch. Two temperature setpoint levers. Optional Status Indication LED lights, System On, Heat, Cool, or Service. Remote Sensor Sensor(s) available for all zone sensors to provide remote sensing capabilities. Dual Thermistor Remote Zone Sensor This sensor will allow the customer to reduce the total number of remote sensors to obtain space temperature averaging. This sensor should be utilized with ReliaTel controls. RT-PRC002-EN Digital Display Zone Sensor The Digital LCD (Liquid Crystal Display) zone sensor has the look and functionality of standard zone sensors. This sensor includes a digital display of set point adjustment and space temperature in F (Fahrenheit) or C (Celsius). Includes FAN and SYSTEM buttons (supports the service functions of the standard sensor). E-squared memory stores last programmed set points. Requires 24 VAC (Volts AC). This sensor should be utilized with ReliaTel controls. Programmable Night Setback Auto or manual changeover with sevenday programming. Keyboard selection of Heat, Cool, Fan, Auto, or On. All programmable sensors have System On, Heat, Cool, Service LED/indicators as standard. Night Setback Sensors have one (1) Occupied, one (1) Un-occupied, and two (2) Override programs per day. Integrated Comfort TM System Sensor(s) available with optional temperature adjustment and override buttons to provide central control through a Trane Integrated Comfort system. CO Sensing The CO 2 2 sensor has the ability to monitor space occupancy levels within the building by measuring the parts per million of CO 2 (Carbon Dioxide) in the air. As the CO 2 levels increase, the outside air damper modulates to meet the CO 2 space ventilation requirements. The CO 2 sensor kit is available as a field installed accessory. Economizer Controls The standard equipment offering is a fixed dry bulb changeover control. In addition, there are two optional controls, Enthalpy and Differential Enthalpy Control. Enthalpy Control Replaces the dry bulb control with a wet bulb changeover controller which has a fully adjustable set point. Enthalpy control offers a higher level of comfort control, along with energy savings potential, than the standard dry bulb control. This is due to the additional wet bulb sensing capability. Differential Enthalpy Replaces the standard dry bulb control with two enthalpy sensors that compare total heat content of the indoor air and outdoor air to determine the most efficient air source. This control option offers the highest level of comfort control, plus energy efficiency, available. Remote Potentiometer Minimum position setting of economizer can be remotely adjusted with this accessory. Differential Pressure Switches This factory or field-installed option allows individual fan failure and dirty filter indication. The fan failure switch will disable all unit functions and flash the Service LED on the zone sensor. The dirty filter switch will light the Service LED on the zone sensor and will allow continued unit operation. Trane Communication Interface (TCI) This factory or field-installed microprocessor interface allows the unit to communicate to Trane s Integrated Comfort system. 35
36 Electrical (Standard Efficiency) Table ED-1 Unit Wiring Standard Efficiency Standard Indoor Fan Motor Oversize Indoor Fan Motor Unit Minimum Maximum Fuse Minimum Maximum Fuse Unit Operating Circuit Size Or Maximum Circuit Size Or Maximum Tons Model No. Voltage Range Ampacity 2 Circuit Breaker 1 Ampacity 2 Circuit Breaker 1 TC*150D ½ TC*150D TC*150DW TC*150DK TC*180B TC*180B TC*180BW TC*180BK TC*210C ½ TC*210C TC*210CW TC*210CK TC*240B TC*240B TC*240BW TC*240BK TC*300B TC*300B TC*300BW TC*300BK NOTE: 1. HACR breaker per NEC. 2. Values do not include power exhaust accessory. *Indicates both downflow and horizontal units. 36 RT-PRC002-EN
37 Electrical (High Efficiency) Table ED-2 Unit Wiring High Efficiency Standard Indoor Fan Motor Oversize Indoor Fan Motor Unit Minimum Maximum Fuse Minimum Maximum Fuse Unit Operating Circuit Size Or Maximum Circuit Size Or Maximum Tons Model No. Voltage Range Ampacity 2 Circuit Breaker 1 Ampacity 2 Circuit Breaker 1 TC*151C ½ TC*151C TC*151CW TC*181C TC*181C TC*181CW TC*211C ½ TC*211C TC*211CW TC*241C TC*241C TC*241CW TC*301C N/A N/A 25 TC*301C N/A N/A TC*301CW N/A N/A NOTE: 1. HACR breaker per NEC. 2. Values do not include power exhaust accessory. Table ED-3 Unit Wiring TXV/Face-Split Evaporator Coil Option (Downflow Only) High Efficiency Standard Indoor Fan Motor Oversize Indoor Fan Motor Unit Minimum Maximum Fuse Minimum Maximum Fuse Unit Operating Circuit Size Or Maximum Circuit Size Or Maximum Tons Model No. Voltage Range Ampacity 2 Circuit Breaker 1 Ampacity 2 Circuit Breaker 1 TCD151C ½ TCD151C TCD151CW TCD181C TCD181C TCD181CW TCD211C ½ TCD211C TCD211CW TCD241C TCD241C TCD241CW TCD301C N/A N/A 25 TCD301C N/A N/A TCD301CW N/A N/A NOTE: 1. HACR breaker per NEC. 2. Values do not include power exhaust accessory. *Indicates both downflow and horizontal units. RT-PRC002-EN 37
38 Electrical Table ED-4 Electrical Characteristics Power Exhaust Accessory Accessory Accessory Operating Amps Tons Model Number Voltage Phase HP RPM FLA LRA 12½ 1, 2 BAYPWRX / , 17½ BAYPWRX / , 25 BAYPWRX / ½ Ton Standard Unit ½ Ton High Efficiency Unit. 38 RT-PRC002-EN
39 Electrical Table ED-5 Unit Wiring With Electric Heat (Single Point Connection) Standard Efficiency Standard Indoor Motor Oversize Indoor Motor To Use Heater Heater Control Max Fuse Size or Max Fuse Size or Tons With Model No. KW Rating 1 Stages MCA Max Circuit Breaker 2 MCA Max Circuit Breaker 2 208/230 Volts Three Phase AYDHTRF318A 13.5/ /68 80/80 69/76 80/80 12½ TCD150D3 AYDHTRF336A 27.0/ / / / /150 AYDHTRF354A 40.5/ / / / /200 AYDHTRK318A 13.5/ /78 100/100 84/84 100/ TCD180B3 AYDHTRK336A 27.0/ / / / /150 AYDHTRK354A 40.5/ / / / /200 17½ TCD210C3 AYDHTRL336A 27.0/ / / / /150 AYDHTRL354A 40.5/ / / / /200 AYDHTRL336A 27.0/ / / / / TCD240B3 AYDHTRL354A 40.5/ / / / /200 AYDHTRK372A 54.0/ / / / /250 AYDHTRL336A 27.0/ / / TCD300B3 AYDHTRL354A 40.5/ / /200 AYDHTRK372A 54.0/ / / Volts Three Phase AYDHTRL418A ½ TCD150D4 AYDHTRK436A AYDHTRK454A AYDHTRL418A TCD180B4 AYDHTRK436A AYDHTRK454A ½ TCD210C4 AYDHTRL436A AYDHTRL454A AYDHTRL436A TCD240B4 AYDHTRL454A AYDHTRK472A AYDHTRL436A TCD300B4 AYDHTRL454A AYDHTRK472A Volts Three Phase AYDHTRKW18A ½ TCD150DW AYDHTRMW36A AYDHTRKW54A AYDHTRKW18A TCD180BW AYDHTRMW36A AYDHTRKW54A ½ TCD210CW AYDHTRMW36A AYDHTRLW54A AYDHTRMW36A TCD240BW AYDHTRLW54A AYDHTRKW72A AYDHTRMW36A TCD300BW AYDHTRLW54A AYDHTRKW72A Heater kw ratings are at 208/240 for 208/230V unit, 480V for 460 unit and 600V for 575 unit. 2. HACR type circuit breaker per NEC. RT-PRC002-EN 39
40 Electrical Table ED-5 Unit Wiring With Electric Heat (Single Point Connection) Standard Efficiency continued Standard Indoor Motor Oversize Indoor Motor To Use Heater Heater Control Max Fuse Size or Max Fuse Size or Tons With Model No. KW Rating 1 Stages MCA Max Circuit Breaker 2 MCA Max Circuit Breaker Volts Three Phase AYDHTRE418A ½ TCD150D4 AYDHTRE436A AYDHTRE454A AYDHTRE418A TCD180B4 AYDHTRE436A AYDHTRE454A ½ TCD210C4 AYDHTRG436A AYDHTRG454A AYDHTRG436A TCD240B4 AYDHTRG454A AYDHTRH472A AYDHTRG436A TCD300B4 AYDHTRG454A AYDHTRH472A Heater kw ratings are at 380V for 380 unit. 2. HACR type circuit breaker per NEC. 40 RT-PRC002-EN
41 Electrical Table ED-6 Unit Wiring With Electric Heat (Single Point Connection) Standard Efficiency Standard Indoor Motor Oversize Indoor Motor To Use Heater Heater Control Max Fuse Size or Max Fuse Size or Tons With Model No. KW Rating 1 Stages MCA Max Circuit Breaker 2 MCA Max Circuit Breaker 2 208/230 Volts Three Phase AYHHTRN318A 13.5/ /68 80/80 69/76 80/80 12½ TCH150D3 AYHHTRN336A 27.0/ / / / /150 AYHHTRN354A 40.5/ / / / /200 AYHHTRN318A 13.5/ /78 100/100 84/84 100/ TCH180B3 AYHHTRP336A 27.0/ / / / /150 AYHHTRP354A 40.5/ / / / /200 17½ TCH210C3 AYHHTRQ336A 27.0/ / / / /150 AYHHTRQ354A 40.5/ / / / /200 AYHHTRN336A 27.0/ / / / / TCH240B3 AYHHTRN354A 40.5/ / / / /200 AYHHTRN372A 54.0/ / / / /250 AYHHTRN336A 27.0/ / / TCH300B3 AYHHTRN354A 40.5/ / /200 AYHHTRN372A 54.0/ / / Volts Three Phase AYHHTRN418A ½ TCH150D4 AYHHTRN436A AYHHTRP454A AYHHTRN418A TCH180B4 AYHHTRP436A AYHHTRP454A ½ TCH210C4 AYHHTRQ436A AYHHTRQ454A AYHHTRN436A TCH240B4 AYHHTRN454A AYHHTRN472A AYHHTRN436A TCH300B4 AYHHTRN454A AYHHTRN472A Volts Three Phase AYHHTRNW18A ½ TCH150DW AYHHTRPW36A AYHHTRPW54A AYHHTRNW18A TCH180BW AYHHTRPW36A AYHHTRPW54A AYHHTRPW36A ½ TCH210CW AYHHTRQW54A AYHHTRMW36A TCH240BW AYHHTRNW54A AYHHTRNW72A AYHHTRMW36A TCH300BW AYHHTRNW54A AYHHTRNW72A Heater kw ratings are at 208/240 for 208/230V unit, 480V for 460 unit and 600V for 575 unit.. 2. HACR type circuit breaker per NEC. RT-PRC002-EN 41
42 Electrical Table ED-6 Unit Wiring With Electric Heat (Single Point Connection) Standard Efficiency continued Standard Indoor Motor Oversize Indoor Motor To Use Heater Heater Control Max Fuse Size or Max Fuse Size or Tons With Model No. KW Rating 1 Stages MCA Max Circuit Breaker 2 MCA Max Circuit Breaker Volts Three Phase AYHHTRK418A ½ TCH150DK AYHHTRK436A AYHHTRK454A AYHHTRK418A TCH180BK AYHHTRK436A AYHHTRK454A ½ TCH210CK AYHHTRL436A AYHHTRL454A AYHHTRR436A TCH240BK AYHHTRR454A AYHHTRR472A AYHHTRR436A TCH300BK AYHHTRR454A AYHHTRR472A Heater kw ratings are at 380V for 380 unit. 2. HACR type circuit breaker per NEC. 42 RT-PRC002-EN
43 Electrical Table ED-7 Unit Wiring With Electric Heat (Single Point Connection) High Efficiency Standard Indoor Motor Oversize Indoor Motor To Use Heater Heater Control Max Fuse Size or Max Fuse Size or Tons With Model No. KW Rating Stages MCA Max Circuit Breaker 1 MCA Max Circuit Breaker 2 208/230 Volts Three Phase AYDHTRK318A 13.5/ /68 80/80 70/76 90/90 12½ TCD151C3 AYDHTRK336A 27.0/ / / / /150 AYDHTRK354A 40.5/ / / / /200 AYDHTRK318A 13.5/ /74 100/100 80/80 100/ TCD181C3 AYDHTRK336A 27.0/ / / / /150 AYDHTRK354A 40.5/ / / / /200 AYDHTRL336A 27.0/ / / / /150 17½ TCD211C3 AYDHTRL354A 40.5/ / / / /200 AYDHTRK372A 54.0/ / / / /250 AYDHTRL336A 27.0/ / / / / TCD241C3 AYDHTRL354A 40.5/ / / / /200 AYDHTRK372A 54.0/ / / / /250 AYDHTRL336A 27.0/ / / TCD301C3 AYDHTRL354A 40.5/ / /200 AYDHTRK372A 54.0/ / / Volts Three Phase AYDHTRL418A ½ TCD151C4 AYDHTRK436A AYDHTRK454A AYDHTRL418A AYDHTRK427A TCD181C4 AYDHTRK436A AYDHTRK454A AYDHTRL427A AYDHTRL436A ½ TCD211C4 AYDHTRL454A AYDHTRK472A AYDHTRL427A AYDHTRL436A TCD241C4 AYDHTRL454A AYDHTRK472A AYDHTRL436A AYDHTRL427A TCD301C4 AYDHTRL454A AYDHTRK472A Volts Three Phase TCD151CW AYDHTRKW18A ½ TCD151CW AYDHTRMW36A TCD151CW AYDHTRKW54A TCD181CW AYDHTRKW18A TCD181CW AYDHTRMW36A TCD181CW AYDHTRKW54A TCD211CW AYDHTRMW36A ½ TCD211CW AYDHTRLW54A TCD211CW AYDHTRKW72A TCD241CW AYDHTRMW36A TCD241CW AYDHTRLW54A TCD241CW AYDHTRKW72A TCD301CW AYDHTRMW36A TCD301CW AYDHTRLW54A TCD301CW AYDHTRKW72A HACR type circuit breaker per NEC. 2. Values do not include power exhaust accessory. RT-PRC002-EN 43
44 Electrical Table ED-8 Unit Wiring With Electric Heat (Single Point Connection) High Efficiency Standard Indoor Motor Oversize Indoor Motor To Use Heater Heater Control Max Fuse Size or Max Fuse Size or Tons With Model No. KW Rating Stages MCA Max Circuit Breaker 1 MCA Max Circuit Breaker 2 208/230 Volts Three Phase AYHHTRN318A 13.5/ /68 80/80 70/76 90/90 12½ TCH151C3 AYHHTRP336A 27.0/ / / / /150 AYHHTRP354A 40.5/ / / / /200 AYHHTRM318A 13.5/ /74 100/100 80/80 100/ TCH181C3 AYHHTRM336A 27.0/ / / / /150 AYHHTRM354A 40.5/ / / / /200 AYHHTRN336A 27.0/ / / / /150 17½ TCH211C3 AYHHTRN354A 40.5/ / / / /200 AYHHTRN372A 54.0/ / / / /250 AYHHTRN336A 27.0/ / / / / TCH241C3 AYHHTRN354A 40.5/ / / / /200 AYHHTRN372A 54.0/ / / / /250 AYHHTRN336A 27.0/ / / TCH301C3 AYHHTRN354A 40.5/ / /200 AYHHTRN372A 54.0/ / / Volts Three Phase AYHHTRN418A ½ TCH151C4 AYHHTRP436A AYHHTRP454A AYHHTRM418A TCH181C4 AYHHTRM436A AYHHTRM454A AYHHTRN436A ½ TCH211C4 AYHHTRN454A AYHHTRN472A AYHHTRN436A TCH241C4 AYHHTRN454A AYHHTRN472A AYHHTRN436A TCH301C4 AYHHTRN454A AYHHTRN472A Volts Three Phase AYHHTRNW18A ½ TCH151CW AYHHTRPW36A AYHHTRPW54A AYHHTRMW18A TCH181CW AYHHTRMW36A AYHHTRMW54A AYHHTRMW36A ½ TCH211CW AYHHTRNW54A AYHHTRNW72A AYHHTRMW36A TCH241CW AYHHTRNW54A AYHHTRNW72A AYHHTRMW36A TCH301CW AYHHTRNW54A AYHHTRNW72A HACR type circuit breaker per NEC. 2. Values do not include power exhaust accessory. 44 RT-PRC002-EN
45 Electrical Table ED-9 Unit Wiring With Electric Heat (Single Point Connection) TXV/Face-Split Evaporator Coil Option (Downflow Only) High Efficiency Standard Indoor Motor Oversize Indoor Motor To Use Heater Heater Control Max Fuse Size or Max Fuse Size or Tons With Model No. KW Rating Stages MCA Max Circuit Breaker 2 MCA Max Circuit Breaker 1,2 208/230 Volts Three Phase AYDHTRK318A 13.5/ /68 70/70 68/76 80/80 12½ TCD151C3 AYDHTRK336A 27.0/ / / / /150 AYDHTRK354A 40.5/ / / / /200 AYDHTRK318A 13.5/ /74 100/100 80/80 90/90 15 TCD181C3 AYDHTRK336A 27.0/ / / / /150 AYDHTRK354A 40.5/ / / / /200 AYDHTRL336A 27.0/ / / / /150 17½ TCD211C3 AYDHTRL354A 40.5/ / / / /200 AYDHTRK372A 54.0/ / / / /250 AYDHTRL336A 27.0/ / / / / TCD241C3 AYDHTRL354A 40.5/ / / / /200 AYDHTRK372A 54.0/ / / / /250 AYDHTRL336A 27.0/ / / TCD301C3 AYDHTRL354A 40.5/ / /200 AYDHTRK372A 54.0/ / / Volts Three Phase AYDHTRL418A ½ TCD151C4 AYDHTRK436A AYDHTRK454A AYDHTRL418A AYDHTRK427A TCD181C4 AYDHTRK436A AYDHTRK454A AYDHTRL427A AYDHTRL436A ½ TCD211C4 AYDHTRL454A AYDHTRK472A AYDHTRL427A AYDHTRL436A TCD241C4 AYDHTRL454A AYDHTRK472A AYDHTRL427A AYDHTRL436A TCD301C4 AYDHTRL454A AYDHTRK472A Volts Three Phase AYDHTRKW18A ½ TCD151CW AYDHTRMW36A AYDHTRKW54A AYDHTRKW18A TCD181CW AYDHTRMW36A AYDHTRKW54A AYDHTRMW36A ½ TCD211CW AYDHTRLW54A AYDHTRKW72A AYDHTRMW36A TCD241CW AYDHTRLW54A AYDHTRKW72A AYDHTRMW36A TCD301CW AYDHTRLW54A AYDHTRKW72A HACR type circuit breaker per NEC. 2. Values do not include power exhaust accessory. 3. Do not use with oversized motor. RT-PRC002-EN 45
46 Electrical Table ED-10 Electrical Characteristics Evaporator Fan Motor 60 Cycle Standard Evaporator Fan Motor Oversized Evaporator Fan Motor Unit Amps Amps Tons Model No. No. Volts Phase HP FLA LRA No. Volts Phase HP FLA LRA TC*150D3, TC*151C ½ TC*150D4, TC*151C TC*150DW, TC*151CW TC*150DK TC*180B3, TC*181C TC*180B4, TC*181C TC*180BW, TC*181CW TC*180BK TC*210C3, TC*211C ½ TC*210C4, TC*211C TC*210CW, TC*211CW TC*210CK TC*240B3, TC*241C TC*240B4, TC*241C TC*240BW, TC*241CW TC*240BK TC*300B3, TC*301C TC*300B4, TC*301C TC* 300BW, TC*301CW TC*300BK *Indicates both downflow and horizontal units. 46 RT-PRC002-EN
47 Electrical (Standard Efficiency) Table ED-11 Electrical Characteristics Compressor Motor And Condenser Motor 60 Cycle Standard Efficiency Compressor Motors Condenser Fan Motors Unit Amps 1 Amps 1 Tons Model No. No. Volts Phase HP 2 RPM RLA LRA No. Phase HP FLA LRA TC*150D TC*150D ½ TC*150DW TC*150DK TC*180B / / / TC*180B / / / TC*180BW / /7.4 85/ TC*180BK / / / TC*210C / / / ½ TC*210C / / / TC*210CW / /8.2 85/ TC*210CK / / / TC*240B TC*240B TC*240BW TC*240BK TC*300B TC*300B TC*300BW TC*300BK Amp draw for each motor; multiply value by numbers of motors to determine total amps. 2. HP for each compressor. *Indicates both downflow and horizontal units. RT-PRC002-EN 47
48 Electrical (High Efficiency) Table ED-12 Electrical Characteristics Compressor Motor And Condenser Motor 60 Cycle High Efficiency Compressor Motors Condenser Fan Motors Unit Amps 1 Amps 1 Tons Model No. No. Volts Phase HP 2 RPM RLA LRA No. Phase HP FLA LRA TC*151C ½ TC*151C TC*151CW TC*181C / / / TC*181C / / / TC*181CW / /6.6 85/ TC*211C / / / ½ TC*211C / / / TC*211CW / /8.2 92/ TC*241C TC*241C TC*241CW TC*301C TC*301C TC*301CW Amp draw for each motor; multiply value by numbers of motors to determine total amps. 2. HP for each compressor. Table ED-13 Electrical Characteristics Compressor Motor And Condenser Motor 60 Cycle TXV/Face-Split Evaporator Coil Option (Downflow Only) High Efficiency Compressor Motors Condenser Fan Motors Unit Amps 1 Amps 1 Tons Model No. No. Volts Phase HP 2 RPM RLA LRA No. Phase HP FLA LRA TCD151C / ½ TCD151C / TCD151CW / TCD181C / / / TCD181C / / / TCD181CW / /7.4 85/ TCD211C / / / ½ TCD211C / / / TCD211CW / /8.1 92/ TCD241C / / / / TCD241C / / / / TCD241CW / / / / TCD301C TCD301C TCD301CW Amp draw for each motor; multiply value by numbers of motors to determine total amps. 2. HP for each compressor. *Indicates both downflow and horizontal units. 48 RT-PRC002-EN
49 Jobsite Connections ZONE SENSORS DISCONNECT SWITCH (BY OTHERS) ROOFTOP UNIT Zone Sensors Typical Number Of Wires A Manual Changeover... 4 Manual/Auto Changeover... 5 Manual/Auto Changeover with Status Indication LED s Programmable Night Setback with Status Indication LED s... 7 B 3 Power Wires + 1 Ground Wire (three phase) 2 Power Wires + 1 Ground Wire (single phase) For specific wiring information, see the installation instructions. All wiring except power wires is low voltage. All customer supplied wiring to be copper and must conform to NEC or CEC and local electrical codes. Wiring shown dotted is to be furnished and installed by the customer. RT-PRC002-EN 49
50 Typical Wiring (12½-25 Ton) 50 RT-PRC002-EN
51 Typical Wiring (12½-25 Ton) Typical wiring diagram. For specific wiring, see individual Service Facts. RT-PRC002-EN 51
52 Typical Wiring (12½-25 Ton) 52 RT-PRC002-EN
53 Typical Wiring (12½-25 Ton) RT-PRC002-EN 53
54 Dimensional (12½ Ton) High Efficiency (12½, 15, 17½ Ton) Std. Efficiency All dimensions are in inches. NOTE: Duct flanges mount 7-7/16" down inside the curb on the 1½" curb flanges. See recommended duct dimensions on the next page. Roofcurb is intended for downflow use only. Downflow Unit Clearance 54 RT-PRC002-EN
55 Dimensional (12½ Ton) High Efficiency (12½, 15, 17½ Ton) Std. Efficiency All dimensions are in inches. Downflow Duct Connections Field Fabricated 1" 17 7/8" 59 7/16" 26 5/16" 52 1/2" 1" 7 7/16" 14 1/16" RETURN SUPPLY 1 1\2" PERIMETER CURB FLANGE NOTE: Duct flanges mount 7-7/16" down inside the curb on the 1½" curb flanges. Roofcurb is intended for downflow use only. Horizontal Unit Supply/Return and Unit Clearance RT-PRC002-EN 55
56 Dimensional (15-25 Ton) High Efficiency (20, 25 Ton) Std. Efficiency All dimensions are in inches. NOTE: Duct flanges mount 7-7/16" down inside the curb on the 1½" curb flanges. See recommended duct dimensions on the next page. Roofcurb is intended for downflow use only. Downflow Unit Clearance 56 RT-PRC002-EN
57 Dimensional (15-25 Ton) High Efficiency (20, 25 Ton) Std. Efficiency All dimensions are in inches. Downflow Duct Connections Field Fabricated 1" 19 5/16" 73 7/16" 26 5/16" 66 1/2" 1" 7 7/16" 14 1/16" RETURN SUPPLY 1 1\2" PERIMETER CURB FLANGE NOTE: Duct flanges mount 7-7/16" down inside the curb on the 1½" curb flanges. Roofcurb is intended for downflow use only. Horizontal Unit Supply/Return and Unit Clearance RT-PRC002-EN 57
58 Dimensional (12½-25 Ton) Accessories All dimensions are in inches. Note: When applying economizer to horizontal units, connecting ductwork must be run full size to allow proper operation of Economizer Damper. Table DD-1 Unit Model # A B 1 C 2 TC*150, , /2 53¾ 36 TC*181, /2 64¾ Horizontal dimension only. Downflow economizer is width of end panel. 2. Power exhaust is applied on downflow economizer only. 58 RT-PRC002-EN
59 Dimensional Factory Installed Options (FIOPS) All dimensions are in inches. Table DD-2 Unit Model # A B C TCD150, 151, 180, / / 8 31 TCD181, / /2 RT-PRC002-EN 59
60 Dimensional Factory Installed Options (FIOPS) Fan Failure Switch Disconnect Switch or Circuit Breaker Clogged Filter Switch Powered Or Unpowered Convenience Outlet Hinged Access Door Trane Communication Interface Black Epoxy Coated Outdoor Coils Hinged Access Door Through the Base Electrical High Pressure Cut Out Supply and/or Return Smoke Detectors 60 RT-PRC002-EN
61 Dimensional (12½-25 Ton) Table DD-3 Standard Efficiency Units Condensate Condensate Drain Location Tons Downflow Only Drain Size Downflow Horizontal A B C D F G H E J E K 12½, 15, 17½ 26 7/ / / / 4 4 1/ / / 16 1 NPT 25 5/ , / / / / 4 4 1/ / / 16 1 NPT 26 3/ 4 5 3/ 8 Table DD-4 High Efficiency Units Condensate Condensate Drain Location Tons Downflow Only Drain Size Downflow Horizontal A B C D F G H E J E K 12½ 26 7/ / / / 4 4 1/ / / 16 1 NPT 25 5/ / / / / 4 4 1/ / / 16 1 NPT 26 3/ 4 5 3/ 8 RT-PRC002-EN 61
62 Table W-1 Accessory Net Weights (Lbs) 1, 7 Oversized High 5 Low 5 Weights (12½-25 Ton) Economizer Outside Air Damper Power Roof Motor Static Static Model No. Net Manual Motorized Exhaust 4 Curb 4 Adder Drive Drive TCD150D,180B TCD121,151C, TCD210C TCD240B TCD181,211,241C TCD300B.301C N/A N/A 2 TCH150D, 180B, 210C TCH121,151C TCH240B TCH181,211,241C TCH300B,301C N/A N/A 2 Table W-1 Continued Electric Heaters Unit All Zone 6-23 KW KW 54 KW 72 KW Model No. Sensors 240/480V /480V /480V /480V 2 3 TCD150D, 180B, 210C 1 28/ /27 38/32 TCD121,151,181C TCD240B 1 33/27 40/32 43/34 TCD211,241C TCD300B,301C 1 33/27 40/32 43/34 TCH150D, 180B, 210C 1 28/ /27 38/32 TCH121,151,181C TCH240B 1 33/27 40/32 43/34 TCH211, 241C TCH300B, 301C 1 33/27 40/32 43/34 1. Net weight should be added to unit weight when ordering factory installed accessories. 2. For 600V heaters net weights are same as 480V heaters. 3. To estimate shipping weight add 5 lbs to net weight. 4. Downflow only. 5. Not available on all models (See Fan Performance tables for specific models) KW Heaters not available for TC*210C. 7. TC factory installed options for economizers, multiply net capacity x.99, EER x.97. For oversized motors, multiply net capacity x.98, EER x.93. This is provided in compliance with ARI certification program. 62 RT-PRC002-EN
63 Weights Table W-2 Maximum Unit And Corner Weights (Lbs) And Center Of Gravity Dimensions (In.) Unit Maximum Weights (Lbs) Corner Weights (Lbs) 1 Center of Gravity (In.) Tons Model No. Shipping 2 Net A B C D Length Width 12½ TC*150D/TC*151C 1687/ / / / / /337 46/45 29/30 15 TC*180B/TC*181C 1866/ / / / / /431 42/52 28/35 17½ TC*210C/TC*211C 2022/ / / / / /442 46/53 29/35 20 TC*240B/TC*241C 2372/ / / / / /453 51/53 34/34 25 TC*300B/ TC*301C 2365/ / / / / /454 53/53 33/34 1. Corner weights are given for information only. 12½-25 ton models must be supported continuously by a curb or equivalent frame support. 2. Weights are approximate. Horizontal and downflow unit and corner weights may vary slightly. *Indicates both downflow and horizontal units. RT-PRC002-EN 63
64 Weights Table W-3 Factory Installed Options (FIOPS) Net Weights (Lbs) 1,2,3 Model Accessory Number Weight FIYHEMT High Efficiency Motors FIYHEMT Hinged Doors FIYHNGE Powered Convenience Outlet FIYCOPO Through the Base Electrical FIYTBUE Tool-less Hail Guard FIYGARD001,002, FIYGARD003, Unit Mounted Circuit Breaker FIYUCB FIYUCB Unit Mounted Disconnect FIYUDC4150, FIYUDC Weights for FIOP accessories not listed are <5 lbs. 2. Net weight should be added to unit weight when ordering factory installed accessories. 3. See Table W-1 for standard factory installed economizer, electric heater and oversized motor. 64 RT-PRC002-EN
65 Mechanical Specifications General The units shall be dedicated downflow or horizontal airflow. The operating range shall be between 115 F and 0 F in cooling as standard from the factory for all units. Cooling performance shall be rated in accordance with ARI testing procedures. All units shall be factory assembled, internally wired, fully charged with R-22, and 100 percent run tested to check cooling operation, fan and blower rotation, and control sequence before leaving the factory. Wiring internal to the unit shall be colored and numbered for simplified identification. Units shall be UL listed and labeled, classified in accordance to UL 1995/CAN/CSA No. 236-M90 for Central Cooling Air Conditioners. Canadian units shall be CSA Certified. Casing Unit casing shall be constructed of zinc coated, heavy gauge, galvanized steel. Exterior surfaces shall be cleaned, phosphatized, and finished with a weather-resistant baked enamel finish. Unit s surface shall be tested 500 hours in a salt spray test in compliance with ASTM B117. Cabinet construction shall allow for all maintenance on one side of the unit. Service panels shall have lifting handles and be removed and reinstalled by removing not more than three screws on the 12½-25 ton units while providing a water and air tight seal. All exposed vertical panels and top covers in the indoor air section shall be insulated with a 1/2 inch, 1 pound density matt-faced, fireresistant, permanent, odorless, glass fiber material. The base of the downflow unit shall be insulated with 1/2 inch, 1 pound density foil-faced, closed-cell material. The downflow unit s base pan shall have no penetrations within the perimeter of the curb other than the raised 1 1 / 8 inch high supply/return openings to provide an added water integrity precaution, if the condensate drain backs up. The base of the unit shall have provisions for forklift and crane lifting. Unit Top The top cover shall be one piece, or where seams exist, double hemmed and gasket sealed to prevent water leakage. Filters Two inch standard filters shall be factory supplied on all units. An optional 2 pleated filter shall be available for 12½-25 ton models. Compressors 12½ to 25 ton standard and high efficiency units shall have direct-drive, hermetic, scroll type compressors with centrifugal type oil pumps. Motor shall be suction gas-cooled and shall have a voltage utilization range of plus or minus 10 percent of unit nameplate voltage. Internal overloads shall be provided with the scroll compressors. All models (with the exception of 12½ ton standard efficiency) have crankcase heaters. Refrigerant Circuits Each refrigerant circuit shall have independent fixed orifice expansion devices or thermal expansion valve, service pressure ports, and refrigerant line filter driers factory-installed as standard. An area shall be provided for replacement suction line driers. Evaporator and Condenser Coils Internally finned, 3/8" copper tubes mechanically bonded to a configured aluminum plate fin shall be standard. Coils shall be leak tested at the factory to ensure the pressure integrity. The evaporator coil and condenser coil shall be leak tested to 200 psig and pressure tested to 450 psig. On all dual compressor models, the evaporator coil shall be intermingled or face-split configuration. Outdoor Fans The outdoor fan shall be direct-drive, statically and dynamically balanced, draw-through in the vertical discharge position. The fan motor(s) shall be permanently lubricated and shall have built-in thermal overload protection. Indoor Fan Units shall have belt driven, FC, centrifugal fans with adjustable motor sheaves. 12½-25 ton units shall have an adjustable idler-arm assembly for quick adjustment of fan belts and motor sheaves. All motors shall be thermally protected. Oversized motors will be available for high static operations. All indoor fan motors meet the U.S. Energy Policy Act of 1992 (EPACT). Controls Unit shall be completely factory wired with necessary controls and contactor pressure lugs or terminal block for power wiring. Units shall provide an external location for mounting a fused disconnect device. ReliaTel shall be provided for all 24 volt control functions. The resident control algorithms shall make all heating, cooling, and/or ventilating decisions in response to electronic signals from sensors measuring indoor and outdoor temperatures. The control algorithm maintains accurate temperature control, minimizes drift from set point, and provides better building comfort. A centralized control shall provide anti-short cycle timing and time delay between compressors to provide a higher level of machine protection. Accessories Electric Heaters Electric heat modules shall be available for installation within basic unit. Electric heater elements shall be constructed of heavy-duty nickel chromium elements internally delta connected for 240 volt, wye connected for 480 and 600 volt. Staging shall be achieved through ReliaTel. Each heater package shall have automatically reset high limit control operating through heating element contactors. All heaters shall be individually fused from the factory, where required, and shall meet all NEC and CEC requirements when properly installed. Power assemblies shall provide singlepoint connection. Electric heat modules shall be UL listed or CSA certified. RT-PRC002-EN 65
66 Mechanical Specifications Roof Curb - Downflow The roof curb shall be designed to mate with the downflow unit and provide support and a water tight installation when installed properly. The roof curb design shall allow field-fabricated rectangular supply/return ductwork to be connected directly to the curb. Curb design shall comply with NRCA requirements. Curb shall be shipped knocked down for field assembly and shall include wood nailer strips. Economizer - Downflow This accessory shall be either field or factory installed. The assembly includes fully modulating percent motor and dampers, barometric relief, minimum position setting, preset linkage, wiring harness with plug, and fixed dry bulb control. The barometric relief damper shall be standard with the downflow economizer and shall provide a pressure operated damper that shall be gravity closing and shall prohibit entrance of outside air during the equipment off cycle. Solid state enthalpy and differential enthalpy control shall be factory supplied, field installed option. Economizer - Horizontal This accessory shall be field installed only. The horizontal economizer shall be available and contain the same features as the downflow economizer with the exception of barometric relief. Remote Potentiometer The minimum position setting of the economizer shall be adjusted with this accessory. Powered Exhaust The field installed powered exhaust shall provide exhaust of return air, when using an economizer, to maintain better building pressurization. Manual Outside Air Damper Field installed rain hood and screen shall provide up to 25 percent outside air. Motorized Outside Air Dampers Manually set outdoor air dampers shall provide up to 50 percent outside air. Once set, outdoor air dampers shall open to set position when indoor fan starts. The damper shall close to the full closed position when indoor fan shuts down. High Static Drive Field installed high static drive option shall allow the standard motor to operate with improved external static capabilities. (See Fan Performance tables). Low Static Drive Field installed low static drive option shall allow the standard motor to operate at lower static performance. (See Fan Performance tables). Oversized Motors Factory or field installed oversized motors shall be available for high static applications. Control Options Trane Communication Interface (TCI) This option shall be provided to interface with the Trane Integrated Comfort TM System. Zone Sensors This option shall be provided to interface with the ReliaTel equipped Voyagers and shall be available in either manual, automatic programmable with night setback, with system malfunction lights, or remote sensor options. Differential Pressure Switches These field installed options allow for individual fan failure and dirty filter indication. The fan failure switch will disable all unit functions and flash the Service LED on the zone sensor. The dirty filter switch will light the Service LED on the zone sensor and will allow continued unit operation. LonTalk Communications Interface The LonTalk Communications Interface, when installed in a Voyager unit, allows the unit to communicate as a Tracer LCI-V device or directly with generic LonTalk Network Building Automation System Controls. CO 2 Sensing The CO 2 sensor has the ability to monitor space occupancy levels within the building by measuring the parts per million of CO 2 (Carbon Dioxide) in the air. As the CO 2 levels increase, the outside air damper modulates to meet the CO 2 space ventilation requirements. The CO 2 accessory kit is available as a field installed accessory. Ventilation Override Accessory With the Ventilation Override Accessory installed, the unit can be set to transition up to 3 different pre-programmed sequences for Smoke Purge, Pressurization, and Exhaust. The transition occurs when a binary input on the RTOM is closed (shorted). This would typically be a hard wired relay output from a smoke detector or fire control panel. The ventilation override kit is available as a field installed accessory. Digital Display Zone Sensor The Digital LCD (Liquid Crystal Display) zone sensor has the look and functionality of standard zone sensors. This sensor includes a digital display of set point adjustment and space temperature in F (Fahrenheit) or C (Celsius). Includes FAN and SYSTEM buttons (supports the service functions of the standard sensor). E-squared memory stores last programmed set points. Requires 24 VAC (Volts AC). This sensor should be utilized with ReliaTel controls. Dual Thermistor Remote Zone Sensor This sensor will allow the customer to reduce the total number of remote sensors to obtain space temperature averaging. This sensor should be utilized with ReliaTel controls. 66 RT-PRC002-EN
67 Mechanical Specifications Additional Factory Installed Options (FIOPS) Electric Heaters Factory installed and wired electric heaters are available for all 3 phase horizontal and downflow 12½ - 25 ton models. If ordering the Through the Base Electrical option with an Electric Heater, the heater must be factory installed Through the Base Electrical With Disconnect Switch Factory installed 3-pole, molded case, disconnect switch with provisions for through the base electrical connections are available. The disconnect switch will be installed in the unit in a water tight enclosure with access through a swinging door. Factory wiring will be provided from the switch to the unit high voltage terminal block. The switch will be UL/CSA agency recognized. Note: The disconnect switch will be sized per NEC and UL guidelines but will not be used in place of unit overcurrent protection. This option is available on all 12½-25 ton downflow models. Through the Base Electrical with Circuit Breaker This option is a factory installed, thermal magnetic, molded case, HACR Circuit Breaker with provisions for through the base electrical connections. The circuit breaker will be installed in a water tight enclosure in the unit with access through a swinging door. Factory wiring will be provided from the switch to the unit high voltage terminal block. The circuit breaker will provide overcurrent protection, be sized per NEC and UL guidelines, and be agency recognized by UL/CSA. This option is available on all 12½-25 ton downflow models. Powered or Unpowered Convenience Outlet This option is a GFCI, 120v/15amp, 2 plug, convenience outlet, either powered or unpowered. When the convenience outlet is powered, a service receptacle disconnect will be available. The convenience outlet is powered from the line side of the disconnect or circuit breaker, and therefore will not be affected by the position of the disconnect or circuit breaker. This option can only be ordered when the Through the Base Electrical with either the Disconnect Switch or Circuit Breaker option is ordered. This option is available on all 12½ -25 ton downflow models. Clogged Filter/Fan Failure Switch A dedicated differential pressure switch is available to achieve active fan failure indication and/or clogged filter indication. These indications will be registered with either a zone sensor with status indication lights or an Integrated Comfort System. Reference or Comparative Enthalpy Reference or Comparative Enthalpy option shall be available when a factory installed Downflow Economizer is ordered. This option is available on all 12½-25 ton downflow models. High Pressure Cutout This option is offered for units that do not have High Pressure cutout as standard. The units with High Pressure Cutout as standard are TC* B,C. Hinged Access Doors Sheet metal hinges are available factory installed on the Filter/Evaporator Access Door and the Compressor/Control Access Door. This option is available on all 12½- 25 ton downflow models. Trane Communications Interface (TCI) An option for a factory installed Trane Communication Interface is available to allow twisted wire pair communication with an Integrated Comfort System. Order this option when a combination of TCI and oversized motor is desired. Discharge Air Sensing Kit This kit provides true discharge air sensing in heating models. This sensor is a status indicator readable through Tracer or Tracker. The kit is functional only with the ReliaTel Options Module. Coil Guards Quality, tooless hail/coil guards shall be either factory or field-installed for condenser coil protection. High Efficiency Motors This option is available with efficiency ratings from 86.5 up to Not available for all models. Supply and/or Return Air Smoke Detector With this option installed, if smoke is detected, all unit operation will be shut down. Reset will be manual at the unit. Return Air Smoke Detectors require minimum allowable airflow when used with certain models. See the Installation, Operation, and Maintenance (IOM) manual for the models affected and the minimum allowable airflow required. This option is available on all 12½-25 ton downflow models. Black Epoxy Coated Condenser Coil The coil provides corrosion protection to condenser coils for seacoast application. The protection is a factory applied thermoset vinyl coating, bonded to normal aluminum fin stock. The uniform thickness of the bonded vinyl layer exhibits excellent corrosion protection in salt spray tests performed in accordance with ASTM B117. RT-PRC002-EN 67
68 Mechanical Specifications Frostat This factory or field installed option is to be utilized as a safety device. The Frostat opens when temperatures on the evaporator coil fall below 10 F. The temperature will need to rise to 50 F before closing. This option should be utilized in low airflow or high outside air applications. Novar Unit Controls Novar rooftop unit controls will be factory installed and tested. The Novar electronic thermostat module will interface to the unit microprocessor and will control the unit to the desired stage of cooling or heating. The Novar electronic thermostat module will monitor the following unit information: fan failure status, cooling stage 1 on status, cooling stage 2 on status, heating on status, clogged filter status or unit shutdown status, and discharge air temperature. The Novar electronic thermostat module will have the ability to enable the unit mounted economizer. Novar Return Air Sensor This option, when used in conjunction with Novar Controls, will contain a factory provided wired zone temperature sensor located in the return air stream. Through the Base Utilities Access An electrical service entrance shall be provided allowing electrical access for both control and main power connections inside the curb and through the base of the unit. Option will allow for field installation of liquid-tight conduit and an external field installed disconnect switch. Two Inch Permanent Filters Optional two inch permanent filters shall be available for 12½-25 ton models. Thermal Expansion Valve/Face-Split Evaporator Coil Option All units shall have a short orifice refrigerant control metering device. For more exact refrigerant flow, when using units in low airflow or high outside air applications, a Thermal Expansion Valve option shall be available. This option includes a face-split evaporator coil which increases part load and latent capacity. 68 RT-PRC002-EN
69 RT-PRC002-EN 69
70 70 RT-PRC002-EN
71 RT-PRC002-EN 71
72 *High Efficiency Units only Trane A business of American Standard Companies For more information contact your local dealer (distributor), local district office, or us at [email protected] Literature Order Number File Number Supersedes Stocking Location RT-PRC002-EN PL-UN-RT-TCD/TCH12½-25TONS-PRC002-EN RT-PRC002-EN Webb/Mason Trane has a policy of continuous product and product data improvement and reserves the right to change design and specifications without notice.
Packaged Gas/Electric Rooftop Units
Packaged Gas/Electric Rooftop Units Voyager 12½ 25 Tons 60 Hz December 2003 Introduction Voyager TM... a proven performer built to provide ultimate indoor comfort. Voyager continues to provide the highest
Packaged Gas/Electric Rooftop Units
Packaged Gas/Electric Rooftop Units Precedent 3-10 Tons 60 Hz October 2004 Introduction Packaged Rooftop Air Conditioners Through the years, Trane has designed and developed the most complete line of Packaged
TWE+TTA TWE+TWA 6.25-20 T.R.
TWE+TTA TWE+TWA 6.25-20 T.R. Main features : TWE indoor unit : Convertible cabinet, vertical or horizontal. Adjustable speed pulley-belt drive centrifugal fan motor. Aluminium fin coil with copper-tubes.
27 1 /2 to 50 Ton - 60 Hz Voyager Commercial
RT-DS-9 May 1998 First Printing July 1998 Packaged Rooftop Air Conditioners RT-DS-9 27 1 /2 to 50 Ton - 60 Hz Voyager Commercial Features and Benefits SM Over the years the Voyager product line has developed
SECTION 23 81 03 - PACKAGED ROOFTOP AIR CONDITIONING UNITS NON-CUSTOM
SECTION 23 81 03 - PACKAGED ROOFTOP AIR CONDITIONING UNITS NON-CUSTOM PART 1 - GENERAL 1.1 SUMMARY A. Section Includes: 1. Packaged rooftop air conditioning unit (5 tons and smaller). 2. Roof curb. 1.2
48/50EJ,EK,EW,EY038, 044, 048 SINGLE-PACKAGE COOLING UNITS VARIABLE VOLUME CONSTANT VOLUME FACTORY-INSTALLED OPTIONAL HEAT
48/50E-4SB 48/50EJ,EK,EW,EY038, 044, 048 SINGLE-PACKAGE COOLING UNITS VARIABLE VOLUME CONSTANT VOLUME FACTORY-INSTALLED OPTIONAL HEAT GAS HEAT ELECTRIC HEAT PERFORMANCE DATA CERTIFIED DIMENSION PRINT CERTIFIED
SECTION 15750 PACKAGED ROOFTOP AIR CONDITIONING UNITS
SECTION 15750 PART 1 - GENERAL 1.01 DESCRIPTION A. Section includes requirements for roof mounted, self-contained units, with electric cooling, and electric or reverse refrigeration cycle (heat pump) heating
Cooling/Heat Pump Convertible Air Handlers
Cooling/Heat Pump Convertible Air Handlers 2/4TEC3F18-60A1000A 1½ 5 Ton PUB. NO. 22-1774-01-0905 (EN) Features and Benefits 13.0 SEER Ships horizontal converts to vertical by standing unit on end. Six-way
SECTION 23 81 43 HEAT PUMPS
SECTION 23 81 43 HEAT PUMPS PART 1 GENERAL 1.1 SUMMARY A. Section Includes: 1. Packaged rooftop heat pumps. 1.2 REFERENCES A. American Society of Heating, Refrigerating and Air-Conditioning Engineers:
CE6500 Energy Recovery Ventilator
ADVANCED COMMERCIAL Energy Recovery Ventilator PRODUCT SPECIFICATIONS & TECHNICAL DATA Features NOMINAL CAPACITY 5500-7000 CFM CASING Double-wall cabinet White exterior paint, -gauge galvanized steel -gauge
FTQ. Daikin Inverter Ducted Heat Pump
FTQ Daikin Inverter Ducted Heat Pump A TRADITIONAL CENTRAL AIR SYSTEM MADE BETTER WITH DAIKIN CONSTANT COMFORT INVERTER TECHNOLOGY. The Daikin Inverter Ducted Heat Pump line is a cost effective alternative
MAC-120HE-01 Air-Cooled Chiller
MAC-120HE-01 Air-Cooled Chiller 10 Ton / 120,000 BTUH Air-Cooled Chiller 208/230-1-50/60 1 HVAC Guide Specifications Air-Cooled Liquid Chiller Nominal Size: 10 Tons Multiaqua Model Number: MAC-120HE-01
Aluminum Cased Cooling Coils 2-5 Ton 4CXC PUB. NO. 22-1839-03
Aluminum Cased Cooling Coils 2-5 Ton 4CXC PUB. NO. 22-1839-03 Aluminum Cooling Coil Nomenclature 4 C X C B 0 3 6 C C 3 C U A A Refrigerant Type 4 - R410A Product Family T-Premium (Heat Pump or Convertible
GCS16 GCS20 WARNING CAUTION
Service Literature Corp. 0110 L6 Revised 12 2004 GCS16/GCS20 SERIES UNITS GCS16 GCS20 2 to 5 Ton GCS16/20 series units in the 2 to 5 ton (7.0 to 17.0 kw) cooling size are packaged combination gas heat
Split System Cooling Product Data
Split System Cooling Product XL16i 1½ 5 Tons PUB. NO. 22-1890-01 Features and Benefits Climatuff compressor Efficiency up to 16.0 SEER and 9.0 HSPF All aluminum Spine Fin coil WeatherGuard fasteners Quick-Sess
Installation Instructions
05,06 Single Package, Displacement Ventilation or Single Zone Variable Airflow Rooftop Units Electric Cooling with PURONr (R---410A) Refrigerant and COMFORTLinkt Controls Installation Instructions IMPORTANT:
5.6 Technical Specification: Premium Efficiency Electric Air Conditioning Equipment
5.6 Technical Specification: Premium Efficiency Electric Conditioning Equipment Small Premium Project Type: For Premium Conditioning Retrofit Projects: Projects that voluntarily replace existing unitary
HIGH EFFICIENCY RTU. www.reznorhvac.com HIGH EFFICIENCY, PACKAGED SPACE CONDITIONING. DX System IEER> 13.2 Gas Heat Efficiency > 92% Capacities Tons
Capacities 10-25 Tons 100-400 MBH HIGH EFFICIENCY, PACKAGED SPACE CONDITIONING DX System IEER> 13.2 Gas Heat Efficiency > 92% HIGH EFFICIENCY RTU 30-120 kw 3,000-11,550 CFM Comfort Comfort is determined
Bring the fresh in. Dedicated Outside Air Systems
Bring the fresh in. Dedicated Outside Air Systems The inside story on outside air. On average, we breathe in 3,400 gallons of air each day. Ambient indoor air pollution is a major problem, affecting health
50LC Ultra High Efficiency Cooling Only/Electric Heat Packaged Rooftop 3 to 5 Nominal Tons Product Data
Ultra High Efficiency Cooling Only/Electric Heat Packaged Rooftop 3to5NominalTons Product Data C11536 Carrier s Most Efficient Commercial Rooftop Ever! TABLE OF CONTENTS PAGE UNIT FEATURES... 4 MODEL NUMBER
1932 Lexington Houston, Texas 77098-4220 (713) 524-4877. Recommendations for installation of cooling systems
1932 Lexington Houston, Texas 77098-4220 (713) 524-4877 The purpose for this information is to provide a better understanding of the HVAC equipment, components, designs, and installations, of HVAC system
Greensource iseries HY Model Unitary Air Handler/Fan Coil
Engineering Submittal Sheet Overview Model Nomenclature HY 035 00-1 HY - HYDRONIC AIR HANDLER NOMINAL CAPACITY IN THOUSANDS OF BTUH VOLTAGE DESIGNATION 1 = 208-230/1/60 ELECTRIC HEAT KW 00 - NO ELECTRIC
ENGINEERING GUIDE. Water-Cooled Self-Contained Units C-Series, Vertical
ENGINEERING GUIDE Water-Cooled Self-Contained Units C-Series, Vertical TABLE OF CONTENTS Introduction...2 Product Overview...3 Nomenclature...4 General Data...5 Cooling Performance Data....6 Evaporator
Commercial Gas Furnace Upflow
Commercial Gas Furnace Upflow Model G24-200 80% A.F.U.E. 200,000 Btuh Input Heating Cap. 7.5 or 10 Tons Nominal Add-On Cooling GUK FEATURES Certified by A.G.A./C.G.A. Laboratories. Heavy gauge painted
Split System Cooling Product Data
Split System Cooling Product Data XR17 4TTR7 2, 3, 4 & 5 Tons PUB. NO. 22-1884-01 Features and Benefits CLIMATUFF 2-stage scroll compressor Efficiency up to 18.0 SEER All Aluminum SPINE FIN coil DURATUFF
Lower Energy Costs with Rooftop Air-Conditioning Package Units
Lower Energy Costs with Rooftop Air-Conditioning Package Units Sponsored by Mike West, PhD, PE Advantek Consulting, Inc Package Unit Efficiency Factors Sensible and latent performance ratings Unit efficiency
HVAC Basic Science - System Capacity
HVAC Basic Science - System Capacity Btu/hour, btu/h, b/h, btuh. btu?? 1 MBH = 1000 btu/hour 1 KBH = 1000 btu/hour 1 ton of cooling= 12,000 btu/hour 1 watt = 3.414 btu/hour 1 kilowatt = 1000 watts = 3,414
ModPac II 1 to 5-Ton Vertical Wall Mount Air Conditioners Models AVPA12-20-24-30-36-42-48-60
ModPac II 1 to 5-Ton Vertical Wall Mount Air Conditioners Models AVPA12-20-24-30-36-42-48-60 General Description The Marvair ModPac II air conditioner is a vertical, wall mounted, cost effective air conditioner
Installation Manual. Rental Services. Air Handling Units CHS-SVN01A-EN. July 2008
Installation Manual Rental Services Air Handling Units July 2008 CHS-SVN01A-EN Copyright 2008 Trane All rights reserved This document and the information in it are the property of Trane and may not be
Cased/Uncased Coils For Gas And Oil Furnaces
Indoor Coils Cased/Uncased Coils For Gas And Oil Furnaces RCFL- Series featuring Industry Standard R-410A Refrigerant Airflow Capacity 600-1,900 CFM [283-897 L/s] Rheem Indoor Coils are designed for use
ROOFTOP - HEAT PUMP UNIT. This document applies when installing into an air handler or as part of an air handling system.
ROOFTOP - HEAT PUMP UNIT Technical data Applies to Model YNRA R410A This document applies when installing into an air handler or as part of an air handling system. CONTENTS 1. General description... 2
GCS16-024-030-036-048-060
Packaged Unit & Gas Heat 2-5 Ton Capacity 50,000-120,000 Btuh Input Heating Capacity GCS16-024-030-036-048-060 FEATURES Designed for outdoor rooftop or ground level installations Down-flow or horizontal
VertiCool Space Saver 2 to 15 tons Water-Cooled and Chilled Water
2 to 15 tons Water-Cooled and Chilled Water Unique Solutions for Challenging HVAC Projects Your Choice for Limited Space Applications Water-Cooled Chilled Water The VertiCool Space Saver allows installation
DESCRIPTION TECHNICAL GUIDE SINGLE PACKAGE HEAT PUMP UNITS BQ 036, 048 & 060 254575-XTG-C-0109
TECHNICAL GUIDE SINGLE PACKAGE HEAT PUMP UNITS BQ 036, 048 & 060 3, 4 & 5 NOMINAL TONS (Export 50 Hz) DESCRIPTION YORK Sunline 2000 TM heat pumps are convertible single package units with a common cabinet
Achieving ENERGY EFFICIENCY with Standard Air-Conditioning Units. Mike West, PhD, PE Advantek Consulting, Inc
Achieving ENERGY EFFICIENCY with Standard Air-Conditioning Units Mike West, PhD, PE Advantek Consulting, Inc Standard Air Conditioning Unit Packaged Unit Split System DX (not chilled water) Air-cooled
Packaged Rooftop Air Conditioners
Packaged Rooftop Air Conditioners IntelliPak Rooftops with Evaporative-Cooled Condensers 24-116 Tons 60 Hz June 2006 Introduction IntelliPak Rooftops with Evaporative-Cooled Condensers Why Choose IntelliPak
INDOOR COILS. RCFA- featuring R-22 Refrigerant RCFL- featuring Earth-Friendly R-410A Refrigerant CASED/UNCASED COILS FOR GAS AND OIL FURNACES
FORM NO. C11-211 REV. 3 Supersedes Form No. C11-211 Rev. 2 INDOOR COILS RCFA- featuring R-22 Refrigerant RCFL- featuring Earth-Friendly R-410A Refrigerant earth friendly refrigerant CASED/UNCASED COILS
M SERIES REFRIGERANT COIL MODULE REFRIGERANT COILS for R-22, R-407C, R-410A
Bulletin 20-20.2 / July 2012 M SERIES REFRIGERANT COIL MODULE REFRIGERANT COILS for R-22, R-407C, R-410A ➀ ➁ ➂ Model Number Key M 2430 C L 1 - A - ➀ Unit Type M=Modular Nominal Capacity 2430=24000 to 30000
Presentation Outline. Common Terms / Concepts HVAC Building Blocks. Links. Plant Level Building Blocks. Air Distribution Building Blocks
Presentation Outline Common Terms / Concepts HVAC Building Blocks Plant Level Building Blocks Description / Application Data Green opportunities Selection Criteria Air Distribution Building Blocks same
Split System Heat Pump Product Data
Split System Heat Pump Product Silver 14 4A6H4 1 1 /2-5 Tons PUB. NO. 12-1175-07 Contents Features and Benefits 2 Model Nomenclature 3 General 4 Product Specifications 4 A-weighted Sound Power Level [db(a)]
USER S, MAINTENANCE and SERVICE INFORMATION MANUAL
CONTENTS SAFETY INFORMATION................ 2 FOR YOUR SAFETY....................... 2 SYSTEM OPERATION.................. 2 THERMOSTATS........................... 2 INTERMITTENT IGNITION DEVICE...........
K-Series Rooftop Units 60 HZ ASHRAE 90.1 COMPLIANT
PRODUCT SPECIFICATIONS PACKAGED GAS ELECTRIC KG K-Series Rooftop Units 60 HZ Bulletin No. KGA-092-50 (3/206) ASHRAE 90. COMPLIANT 7.5 to 2.5 Tons Net Cooling Capacity 86,000 to 38,000 Btuh Gas Input Heat
ARMSTRONG AIR HEAT PUMPS www.armstrongair.com
INDEX ELECTRIC FURNACE MODULAR AIR SYSTEM EFC/EFV... 5-10 electric Heat Kits... 5-11 evaporator coils EC1P / EM1P UPFLOW / COUNTERFLOW APPLICATIONS and upflow / horizontal applications (CASED)... 5-6 5-7
INDOOR COILS. RCFL- featuring Industry Standard R-410A Refrigerant CASED/UNCASED COILS FOR GAS AND OIL FURNACES
FORM NO. C11-211 REV. 7 Supersedes Form No. C11-211 Rev. 6 INDOOR COILS RCFL- featuring Industry Standard R-410A Refrigerant CASED/UNCASED COILS FOR GAS AND OIL FURNACES AIRFLOW CAPACITIES 600-1,900 CFM
PACKAGE COOLING, PACKAGE HEAT PUMP & PACKAGE GAS UNITS
PACKAGE COOLING, PACKAGE HEAT PUMP & PACKAGE GAS UNITS SERVICE INSTRUCTIONS AMANA REFRIGERATION, INC., AMANA, IOWA 52204 MANUFACTURING NUMBERS COVERED IN THIS MANUAL SEE MODEL AND MANUFACTURING NUMBERS
THE WALL-MOUNT ONE TON AIR CONDITIONER GREEN REFRIGERANT R-410A. 10,800 Btuh 9.00 EER Right Side Control Panel. Engineered Features
THE WALL-MOUNT ONE TON AIR CONDITIONER W2A,800 Btuh 9.00 EER Right Side Control Panel 60Hz GREEN REFRIGERANT R-A The Bard Wall-Mount One Ton Air Conditioner is a self contained energy efficient heating
Split System Heat Pump Product Data
Split System Heat Pump Product Data XL20i 4TWZ0024, 036, 048 & 060 with ComfortLink II and Charge Assist 2, 3, 4 & 5 Tons PUB. NO. 22-1826-01 Features and Benefits Two Climatuff compressors Efficiency
1. What percent of a commercial business s energy usage comes from their HVAC system? A. 13% B. 23% C. 33% D. 43% E. 53%
1 1. What percent of a commercial business s energy usage comes from their HVAC system? A. 13% B. 23% C. 33% D. 43% E. 53% 2. How much money do commercial facilities spend per square foot on energy costs
INDOOR COILS. RCFM- featuring Earth-Friendly R-410A Refrigerant CASED/UNCASED COILS FOR GAS AND OIL FURNACES
FORM NO. C11-212 REV. 1 Supersedes Form No. C11-212 INDOOR COILS RCFM- featuring Earth-Friendly R-410A Refrigerant earth friendly refrigerant CASED/UNCASED COILS FOR GAS AND OIL FURNACES AIRFLOW CAPACITIES
Evaluate, Clean, and Tune Guidance
Evaluate, Clean, and Tune Guidance The Evaluate, Clean and Tune (ECT) process serves three essential purposes in the Weatherization Assistance Program (WAP). The first is to evaluate the existing system
M7RL Series TECHNICAL SPECIFICATIONS. FEATURES and BENEFITS. High Efficiency / Direct Vent Condensing Downflow Gas Furnace
TECHNICAL SPECIFICATIONS M7RL Series High Efficiency / Direct Vent Condensing Downflow Gas Furnace Induced Draft - 9%+ AFUE Input 4,000 thru 7,000 Btuh The high efficiency downflow gas furnace is especially
york air-conditioning products Residential & VRF News 2015
york air-conditioning products Residential & VRF News 2015 york air-conditioning products Catalogue Content Split Systems Pag. High wall High Efficiency Inverter YWHJZH 09 to 24 K 6 High wall Inverter
HVAC Simplified Approach Option
HVAC Simplified Approach Option Part I Project Address: City: HVAC System Designer of Record: Date: Zip: Qualification The building is 2 stories or less in height and has a gross floor area is less than
Product Data. FV4C Performancet Series Fan Coil Sizes 002 Thru 006 PREMIUM ENVIRONMENTALLY SOUND FAN COIL
Performancet Series Fan Coil Sizes 002 Thru 006 Product Data PREMIUM ENVIRONMENTALLY SOUND FAN COIL The is the premium air handler combining the proven technology of Carrier fan coils with environmentally
XV80 UPFLOW/HORIZONTAL 2-STAGE, VARIABLE SPEED GAS-FIRED FURNACE
UPF/HORIZONTAL 2-, VARIABLE SPEED GAS-FIRED FURNACE XV80 MODELS TUD2B060A9V3VB, TUD2B080A9V3VB TUD2C080A9V4VB, TUD2C080B9V4VB TUD2B00A9V3VB, TUD2C00A9V5VB TUD2C00B9V5VB, TUD2DA9V5VB TUD2DB9V5VB, TUD2DA9V5VB
SPLIT-SYSTEM CONDENSING UNITS. 10.00 SEER HRA018 thru 060 (1.5 thru 5 Nominal Tons) DESCRIPTION FEATURES
550.46 -TG1Y (196) SPLIT-SYSTEM CONDENSING S 0 SEER HRA018 thru 060 (1.5 thru 5 Nominal Tons) DESCRIPTION The HRA Series condensing unit is the outdoor part of a versatile system of air conditioning. It
HVAC Efficiency Definitions
HVAC Efficiency Definitions Term page EER - 2 SEER - 3 COP - 4 HSPF - 5 IPLV - 6 John Mix May 2006 Carrier Corporation 1 Energy Efficiency Ratio (EER) The energy efficiency ratio is used to evaluate the
Service Facts. WARNING: HAZARDOUS VOLTAGE - DISCONNECT POWER and DISCHARGE 4TTM3-SF-1. Split System Cooling 4TTM3018-4TTM3060
4TTM3-SF-1 Service Facts Split System Cooling 4TTM3018-4TTM3060! CAUTION UNIT CONTAINS R-410A REFRIGERANT! R-410A OPERATING PRESSURE EXCEEDS THE LIMIT OF R-22. PROPER SERVICE EQUIPMENT IS REQUIRED. FAILURE
AIR HANDLERS AIR HANDLERS AIR HANDLERS. RHLA- High Efficiency. featuring R-22 Refrigerant. RHLL- High Efficiency
FORM NO. H11-52 REV. 3 Supersedes Form H11-52 Rev. 2 AIR HANDLERS AIR HANDLERS RHLA- Efficiency featuring R-22 Refrigerant RHLL- Efficiency featuring Earth-Friendly R-10A Refrigerant earth friendly refrigerant
NEBB STANDARDS SECTION-8 AIR SYSTEM TAB PROCEDURES
NEBB STANDARDS SECTION-8 AIR SYSTEM TAB PROCEDURES 8.1 INTRODUCTION Testing, adjusting, and balancing of HVAC systems can best be accomplished by following a series of systematic procedures. The NEBB TAB
catalog Single Package Vertical Air Conditioners and Heat Pumps
catalog Single Package Vertical Air Conditioners and Heat Pumps Catalog: SK145.00-EG1 (1008) TABLE OF CONTENTS Single Package Vertical Units Introduction...............................................................................
Recirculating Roof Fans Models ESRMD, ESRMDF and ERD
Recirculating Roof Fans Models ESRMD, ESRMDF and ERD Four-Way Fan Exhaust Supply Mix Recirculate BUILDING VALUE IN AIR. October 2005 Recirculating Roof Fans Exhaust/Supply/Recirculation/Mix Model ESRMD
SECTION 15732 AIR CONDITIONING UNIT
SECTION 15732 AIR CONDITIONING UNIT PART 1 GENERAL 1.01 SUMMARY A. Section includes: 1. Packaged, split system air conditioning unit No. 1. 1.02 REFERENCES A. Air-Conditioning, Heating, and Refrigeration
HVAC Systems: Overview
HVAC Systems: Overview Michael J. Brandemuehl, Ph.D, P.E. University of Colorado Boulder, CO, USA Overview System Description Secondary HVAC Systems Air distribution Room diffusers and air terminals Duct
Split System Cooling Product Data
Split System Cooling Product Data 4TTB3018-060 1½ 5 Tons PUB. NO. 22-1843-14 Features and Benefits Efficiency up to 13.25 SEER All aluminum Spine Fin coil WeatherGuard fasteners Quick-Sess cabinet, easy
AABC Specifications for Testing and Balancing HVAC Systems
AABC Specifications for Testing and Balancing HVAC Systems The Associated Air Balance Council (AABC) Total System Balancing Specifications for HVAC Testing, Balancing and Performance Verification TOTAL
ECOCIAT. Domestic hot water heat recovery unit
Heat recovery unit Domestic hot water High energy efficiency with R410A Compact and quiet Scroll compressors Brazed-plate heat exchangers Heating Heat recovery ENVIRONMENTALLY HFC R410A PROTECTION DE FRIENDLY
Product Data. Split System Cooling 22-1904-1F-EN. March 2015
Product Data Split System Cooling 4TTR4018L1000A 4TTR4024L1000A 4TTR4025L1000A 4TTR4030L1000A 4TTR4031L1000A 4TTR4036L1000A 4TTR4037L1000A 4TTR4042L1000A 4TTR4043L1000A 4TTR4048L1000A 4TTR4060L1000A Note:
New Deluxe Wall Mounted Heat Pump Series EXTERIOS
New Deluxe Wall Mounted Heat Pump Series EXTERIOS May 2013 New Deluxe Wall Mounted Heat Pump Series Panasonic Adding New Air Conditioner Lineup Setting Another Mile Stone in the US Ductless Split History
Split System Cooling Product & Performance Data
Split System Cooling Product & Performance Data XR 13 4TTR3018-060 1½ 5 Tons PUB. NO. 22-1790-02-2607 (EN) Features and Benefits Climatuff compressor Efficiency up to 14.00 SEER All aluminum Spine Fin
INSTALLATION INSTRUCTIONS
2008 Lennox Industries Inc. Dallas, Texas, USA WARNING Improper installation, adjustment, alteration, service or maintenance can cause personal injury, loss of life, or damage to property. Installation
Installer s Guide 18-AH39D1-13
18-AH39D1-13 Cased Aluminum "Convertible" Coils 4TXCA018BC3HC** 4TXCA024BC3HC** 4TXCB025BC3HC** 4TXCB026BC3HC** 4TXCB031BC3HC** 4TXCB032BC3HC** ALL phases of this installation must comply with NATIONAL,
Split System Heat Pump Product Data
Split System Heat Pump Product Data XR 13 4TWR3018-060 1½ 5 Tons PUB. NO. 22-1795-12 Features and Benefits Climatuff compressor All aluminum Spine Fin coil Quick-Sess cabinet, service access and refrigerant
INDOOR COILS. RCFN- featuring Industry Standard R-410A Refrigerant CASED/UNCASED COILS FOR GAS AND OIL FURNACES
FORM NO. C11-213 REV. 4 Supersedes Form No. C11-213 Rev. 3 INDOOR COILS RCFN- featuring Industry Standard R-410A Refrigerant CASED/UNCASED COILS FOR GAS AND OIL FURNACES AIRFLOW CAPACITIES 600-1,900 CFM
180, 210, AND 240 MODELS LCA PACKAGED COOLING & ELECTRIC HEAT LGA PACKAGED COOLING & GAS HEAT LHA PACKAGED HEAT PUMP
ENGINEERING DATA 180, 210, AND 240 MODELS LCA PACKAGED COOLING & ELECTRIC HEAT LGA PACKAGED COOLING & GAS HEAT LHA PACKAGED HEAT PUMP PACKAGED L SERIES 50hz 15, 17.5 & 20 Ton (52.8, 61.5 & 70.3 ) *Net
STANDARD COMMISSIONING PROCEDURE FOR PACKAGED HEAT PUMP (AIR-TO-AIR) & AIR CONDITIONING UNITS
STANDARD COMMISSIONING PROCEDURE FOR PACKAGED HEAT PUMP (AIR-TO-AIR) & AIR CONDITIONING UNITS BUILDING NAME: APPLICATION #: BUILDING ADDRESS: NAME & FIRM OF PERSON(S) DOING TEST: DATE(S) OF TEST: General
Explosion-Proof Electric Unit Heaters
Type FX4 FX4 Explosion-Proof Electric Air Heaters FX4 heaters are UL listed and/or CSA certified for use in hazardous locations. They are designed for dry indoor industrial applications such as oil refineries,
Product Data. FV4B Performancet Series Fan Coil Sizes 002 Thru 006 PREMIUM ENVIRONMENTALLY SOUND FAN COIL
Performancet Series Fan Coil Sizes 002 Thru 006 Product Data PREMIUM ENVIRONMENTALLY SOUND FAN COIL The is the premium air handler combining the proven technology of Carrier fan coils with environmentally
Florida Power & Light Company. Business Heating Ventilation & Air Conditioning ( HVAC ) Program Standards. Effective: November 9, 2015
Florida Power & Light Company Business Heating Ventilation & Air Conditioning ( HVAC ) Program Standards Effective: November 9, 2015 Table of Contents Eligibility Requirements - Chiller... 2 Rebate Amount
SASO XXXX:2016. (Including the modifications approved in Saudi Council Board No. XXX/2016) LARGE CAPACITY AIR CONDITIONERS
SASO XXXX:2016 (Including the modifications approved in Saudi Council Board No. XXX/2016) LARGE CAPACITY AIR CONDITIONERS PERFORMANCE REQUIREMENTS AND METHODS OF TESTING 1 LARGE CAPACITY AIR CONDITIONERS
technical data air conditioning systems RXS20-25-35E (single phase) FBQ-B8V1-B8V3B Split Heat Pump Condensing Units Split Sky Air
technical data RXS20-25-35E FBQ-B8V-B8V3B (single phase) Split Heat Pump Condensing Units air conditioning systems Split Sky Air Outdoor Units R-40A RXS-E2VB Split Sky Air Outdoor Units Features O u t
Installation, Operation, and Maintenance
Installation, Operation, and Maintenance Packaged Rooftop Air Conditioners Precedent Gas/Electric 5 to 10 Tons 50 Hz SAFETY Only qualified personnel should install and service the equipment. The installation,
INSTALLATION INSTRUCTIONS Fan Coil Replacement Coil Kit EBX & EBXX
Fan Coil Replacement Coil Kit EBX & EBXX These instructions must be read and understood completely before attempting installation. These instructions covers the installation of replacement coil kit into
WON0502-B INSTALLATION INSTRUCTIONS FOR ELECTRIC FURNACES. Bulletin 30-34 / March 2013
Bulletin 30-34 / March 2013 INSTALLATION INSTRUCTIONS FOR ELECTRIC FURNACES General The information on the following pages is to provide the installer the necessary information to properly install the
Defining Quality. Building Comfort. Precision. Air Conditioning
Defining Quality. Building Comfort. Precision Air Conditioning Today s technology rooms require precise, stable environments in order for sensitive electronics to operate optimally. Standard comfort air
SECTION 11 78 13 MORTUARY REFRIGERATORS
PART 1 - GENERAL 1.1 DESCRIPTION SECTION 11 78 13 MORTUARY REFRIGERATORS SPEC WRITER NOTE: Delete between //---// if not applicable to project. Also delete any other item or paragraph not applicable in
How To Design A Building In New Delhi
ENERGY EFFICIENT HVAC DESIGN FOR COMPOSITE CLIMATE Overview of Design Conditions: Air conditioning system consumes most of the energy that a building needs in its operation. In order to reduce energy consumption
Variable Air Volume - VAV
Mode Enable Sensor Options Variable Air Volume - VAV The temperature of this sensor will determine if the unit is in heating, cooling or vent mode during occupied operation. The following options are available:
DESCRIPTION FEATURES HORIZONTAL DUCT HD. ISO 9001 Certified Quality Management System
TECHNICAL GUIDE ADD - ON COILS FOR USE WITH SPLIT-SYSTEM COOLING & HEAT PUMPS MODELS: MC, PC, FC, HD, UC 600-2000 CFM 1.5-5 TON COILS UPFLOW/DOWNFLOW FULL CASED FC UPFLOW PARTIAL CASED PC UPFLOW UNCASED
INSTALLATION INSTRUCTIONS COMMERCIAL ROOM VENTILATORS WITH EXHAUST
INSTALLATION INSTRUCTIONS COMMERCIAL ROOM VENTILATORS WITH EXHAUST MODEL CHCRV-5 For Use with Bard CH Series 3, 4 & 5 Ton 2-Stage Wall Mount Heat Pumps AND W38H, W43H, W49H and W61H Single Stage Wall Mount
SECTION 23 00 01 HEATING, VENTILATION AND AIR CONDITIONING EQUIPMENT
SECTION 23 00 01 HEATING, VENTILATION AND AIR CONDITIONING EQUIPMENT PART 1 - GENERAL 1.1 DESCRIPTION A. The Work specified in this Section consists of designing, furnishing and installing factory-assembled
Cooling Capacity CFM range @.5 in. w.c. (125 Pa)
N8MXL Product Specifications 80% ECM Single Stage Heating Furnace EASIER TO SELL 80% AFUE Flame roll out sensors standard Category I venting Blocked vent switch 24 VAC humidifier terminal Electronic air
Split System Cooling Product Data
Split System Cooling Product Data Three Phase 4TTA3 2½ 5 Tons PUB. NO. 22-1791-12 Features and Benefits All aluminum Spine Fin coil WeatherGuard fasteners Quick-Sess cabinet, service access and refrigerant
T 3 Series VAV Diffusers Analog Diffuser Steel Square Panel Horizontal Pattern Model: T 3 SQ
TSQ--0 7-7-07 T Series VAV Diffusers Analog Diffuser Steel Square Panel Horizontal Pattern Model: T SQ Model Configuration T SQ- Heating / Cooling Border Type (Lay-In) Full Face Nominal Round Duct Size
AIR-COOLED CONDENSERS Technical Guide
BN-ACCTB0306 March, 2006 AIR-COOLED CONDENSERS Technical Guide Monarch and Ambassador Series TABLE OF CONTENTS Overview... 2, 3 Features & Options... 3, 4 Three Solutions...5 Nomenclature...6 Condenser
DESIGN STANDARDS SECTION 23 60 00
PART 1 - GENERAL 1.01 Work included: A. Piping, tubing and fittings. B. Piping specialties. C. Special duty valves. D. Refrigerants. E. Chillers. F. Refrigerant monitors. 1.02 General requirements: A.
INSTALLATION INSTRUCTIONS WALL MOUNTED PACKAGE AIR CONDITIONERS
INSTALLATION INSTRUCTIONS WALL MOUNTED PACKAGE AIR CONDITIONERS MODEL: WA121 Bard Manufacturing Company Bryan, Ohio 43506 Since 1914...Moving ahead, just as planned. Manual : 2100-234 E Supersedes: 2100-234
The formula for finding CFM is: CFM = BTUH OUTPUT_ Temp Rise (ACF)* *Altitude correction factor below 1000ft = 1.08
Air Volume Requirement Air conditioning systems are engineered with a specific amount of indoor air passing across the surface of the evaporator coil. The amount of air is measured in cubic feet per minute.
ENERGY EFFICIENT HVAC DESIGN FOR WARM-HUMID CLIMATE CLIMATE
ENERGY EFFICIENT HVAC DESIGN FOR WARM-HUMID CLIMATE CLIMATE Overview of Design Conditions: Air conditioning system consumes most of the energy that a building needs in its operation. In order to reduce
Cooling Capacity CFM range @.5 in. w.c. (125 Pa)
96% AFUE, Two Stage ECM Gas Furnace EASIER TO SELL 96% AFUE, all models, all positions Two stage heating operation Xtra SEER ECM blower motor Supports two stage cooling units Dehumidification feature in