SECTION 16437D MEDIUM VOLTAGE VACUUM CIRCUIT BREAKERS

Similar documents
2a. IEM Indoor Metal Clad Medium Voltage Switchgear 15KV a. Section INDOOR METAL CLAD MEDIUM VOLTAGE SWTICHGEAR (Std.

Specification Guide. for RVAC. Direct Replacement. AC Medium Voltage. Circuit Breakers

The following components are common to most cubicles; this example is an ABB HK cubicle.

MEDIUM VOLTAGE CE-BF SWITCHBOARDS. UP TO 40.5 kv. CE - BF - C - en - REV

Masterclad Medium Voltage Passive Arc-Resistant Switchgear

Dead Tank Circuit Breaker 72PM40-C Proven reliability through common platforms

Vacuum Circuit Breaker Type VAD-3

AutoLink Three-Phase Sectionalizer Specifications. Scope. General. Applicable Standards. Operating principle

Submit shop drawings for equipment provided under this section Shop drawings shall indicate:

SECTION 16346A METAL-CLAD MEDIUM VOLTAGE ARC RESISTANT SWITCHGEAR

SURGE PROTECTIVE DEVICES (SPDs) LOW VOLTAGE AC INTEGRATED SURGE PROTECTION FOR ELECTRICAL DISTRIBUTION SYSTEMS SECTION 16671A SECTION 16671A

Unified requirements for systems with voltages above 1 kv up to 15 kv

3.1.1 Full Type Tests & Routine Tests according to Clause 8 2 & Instructions For Installation, Operation & Maintenance

TWENTIES WORKSHOP, EWEA 2012 Unveiling the future energy system: full scale demonstrations to reach 2020 targets. 17th April 2012

PowlVac Type PVDST Replacement Vacuum Circuit Breaker Replacement for Federal Pacific Type DST Air-Magnetic Circuit Breakers

Medium Voltage Products. ZN1 12 kv arc-proof air-insulated switchgear for primary distribution

How To Build A Germany Power Plant

Sample - No Commercial Use

High-Voltage Compact Switchgear 3AP1 DTC for 145 kv and 245 kv

01.4IB.51200B PowlVac-AR Arc Resistant Switchgear. 5kV & 15kV 1200A, 2000A, 3000A, & 4000A Forced Cooled. Powered by Safety

Spending too much to maintain aging switchgear? Circuit breaker solutions from Square D Services.

WE-350 Series ¼ Turn Electric Actuator

Circuit Breaker LTB D with Motor Drive. Motor Drive. ABB PP/H/HV - Page 1. Ed

OUTDOOR DISCONNECTORS A division of ACTOM (Pty) Ltd

Voltage Rated operating voltage [kv] Rated power frequency withstand voltage [kv] Rated lightning impulse withstand voltage [kv]

UniGear ZS1. Medium voltage, arc proof, air insulated switchgear for primary distribution

Diesel Engine Driven Generators Page 1 of 6

PRODUCT GUIDE. SL Medium Voltage IEC Vacuum Contactors

Medium voltage VCP-W MR2 (integral racking)

3AH5 Vacuum Circuit-Breakers. Answers for energy. Medium-Voltage Equipment Selection and Ordering Data. Catalog HG

Contents. Description. Product Selection Guide

R.C.C.B. s two-pole LEXIC

UNIVERSITY OF WASHINGTON Facilities Services Design Guide. Electrical. Switchboards. Basis of Design. Design Evaluation

The standards mentioned in this document

7.2KV SL400 Withdrawable Vacuum Contactor-Fuse Combination Units

3.0 CHARACTERISTICS. AR Auxiliary Relay High Speed, High Threshold C

Low Voltage Products. Switches Automatic Transfer Switches

Our brand POWER DYNAMIC PASSION COMMITMENT CREATIVITY. A strong brand for strong products: 8PU Premium. MV Energy

Instructions for Installation, Operation and Maintenance of 24kV Type W-VAC Vacuum Circuit Breaker

SUGGESTED SPECIFICATION for Series 185 Service Entrance Rated Automatic Transfer Switches

Masterclad 5 15 kv Arc Resistant Metal-Clad Indoor Switchgear

The Intelligent AX1 Switchgear for Medium Voltage

IEC and IEEE Standards for High-Voltage Switchgear and Controlgear Present Situation and Future Evolution

Electrical Shore Connections / Cold Ironing

Advantages of Fixed Circuit Breaker Switchgear

Single-phase ( V) voltage monitoring: Undervoltage Overvoltage Window mode (overvoltage + undervoltage) Voltage fault memory selectable

Houston Service Center Medium Voltage Service and Aftermarket Solutions

15VHK-VR Model 20 Replacement Circuit Breaker

Primary and Secondary Electrical Distribution Systems

HVL 5 38 kv Load Interrupter Switchgear. The Standard for Performance, Protection and Dependability

SURGE PROTECTIVE DEVICES (SPDs) LOW VOLTAGE AC EXTERNAL SIDEMOUNT SURGE PROTECTION FOR ELECTRICAL DISTRIBUTION SYSTEMS SECTION 16671B SECTION 16671B

Trade of Electrician. Three-phase Distribution Boards And Socket Circuits

MEDIUM VOLTAGE METAL CLAD SWITCHGEAR

CAT ATC POWER BREAKER & POWER CASE SWITCH AUTOMATIC TRANSFER SWITCH

Installation instructions for Series NRX INCOM communications adapter module

VC Series Zone Valves BALANCED 2-WAY AND 3-WAY HYDRONIC VALVES

0.8 U N /0.5 U N 0.8 U N /0.5 U N 0.8 U N /0.5 U N 0.2 U N /0.1 U N 0.2 U N /0.1 U N 0.2 U N /0.1 U N

PowlVac Vacuum Integrity Tester

High-Voltage Circuit-Breakers 3AP1/ kv up to 550 kv. Power Transmission and Distribution

3/2-way Solenoid Valve, direct-acting, NC or NO

SIRCOVER. Manual changeover switches from 125 to 3200 A. Changeover switches. Function. Advantages. The solution for.

COMPARISON OF ANSI/IEEE AND IEC REQUIREMENTS FOR LOW- VOLTAGE SWITCHGEAR

UFES Active protection for switchgear

Electronic overload relay EF65, EF96 and EF146

Electronic overload relay EF19 and EF45

Type K current limiting fuse canister Technical information and installation guide

Understanding Emergency Power Off (EPO)

Tmax MCCBs. Molded case circuit breakers. Tmax

ELECTRICAL INSULATION TESTING OF HV EQUIPMENT UP TO 33kV

Lightning Arresters P KVA P KVA. Description & Installation

Extend the Life of Existing Switchgear

Arc Terminator Active Arc-Resistant Switchgear

Eaton Safety & Reliability Solutions in the Oil & Gas Industry Electrical

FFI. Advances in Medium and Low Voltage Power Distribution ESS Metron Expo and Technical Seminars. Presented By: Greg Pelster & Robert Schmid

AMPSEAL* Automotive Plug Connector and Header Assembly

Trip circuit supervision relay. Type RXTCS

Linear Luminaire with LED Series EXLUX 6402/2

Installation Instructions

Low voltage Direct Current Network. Compact NSX DC PV. Circuit breakers and switch disconnectors for solar application.

understanding medium frequency induction melting furnace and its components

SECTION POWER MONITOR FOR ELECTRICAL, STEAM CONDENSATE, AND WATER PART I - GENERAL

Medium voltage indoor circuit breakers ANSI/IEC solutions

25-kV Apparatus Bushings B Series (bolt-in) for Elbow to Air-Insulated Service 200 Amp, 600 Amp and 1250 Amp

DATA CENTER UNIQUE CHARACTERISTICS AND THE ROLE OF MEDIUM VOLTAGE VACUUM CIRCUIT BREAKERS

Secondary Unit Substations

Distribution Dry Type Transformers

MV, HV AND EHV SWITCHGEAR TESTING & COMMISSIONING

Bulletin 150 Smart Motor Controllers SMC-3 Smart Motor Controller

Vacuum Circuit Breaker CESI, KERI, CCC, ISO 9001, ISO 14001

Type: DILM32 10(24V50HZ) Article No.:

IB PowlVac-ND ITE-HK 5kV Replacement Vacuum Circuit Breaker. Replacement for ABB Type ITE-HK Air Circuit Breaker.

Bypass transfer switch mechanisms

Medium Voltage Switchgear

Instruction Bulletin. MCS025 Sync-Check Module Installation Sheet

Vertical Break Parallel (VBP) / Vertical Break Slant (VBS)

Customer Substation Manual 08/05/02

SECTION COILING COUNTER DOORS. Display hidden notes to specifier. (Don't know how? Click Here)

New SACE Emax 2 for UL 1066 From Circuit Breaker to Power Manager

LVA Take Offs in Bid Manager

ANCILLARY EQUIPMENT AND ELECTRICAL EQUIPMENT Power Supply Systems and Electrical Equipment for Desalination Plants - Y.M. Hamud and A.H.

Transcription:

SECTION 16437D MEDIUM VOLTAGE VACUUM CIRCUIT BREAKERS PART 1 GENERAL 1.01 1.02 1.03 1.04 This specification covers the design, testing and manufacturing requirements for medium voltage vacuum circuit breakers. The manufacturer shall furnish the equipment and material specified herein complete and operable. All work shall be performed and completed in a thorough manner and in accordance with the best practices in fabrication and manufacturing. All materials used in the construction of the medium voltage vacuum circuit breakers shall be new and selected as the best available. SCOPE The manufacturer shall furnish fully assembled medium voltage vacuum circuit breakers as detailed in these specifications. Drawings, instruction books, and other materials included with the inquiry shall be considered part of the specification. The vacuum circuit breakers shall be designed for maximum voltages of either 5 kv or 15 kv, as designated. RELATED SECTIONS REFERENCES Note to Spec. Writer For Non-Generator Breaker Applications delete references to IEEE Standards C37.013 and C37.013a. For Generator Breaker Applications only keep references to IEEE Standards C37.013 and C37.013a. The applicable codes and standards listed below shall be considered part of this specification. The latest revision in effect on the date the request for proposal was issued shall apply for all standards referenced. 1. IEEE C37.04 Standard Rating Structure for AC High Voltage Circuit Breakers 2. IEEE C37.06 AC High-Voltage Circuit Breakers Rated on Symmetrical Current Basis - Preferred Ratings and Related Required Capabilities 3. IEEE C37.09 Test Procedure for AC High-Voltage Circuit Breakers Rated on a Symmetrical Current Basis 4. IEEE C37.010 Application Guide for AC High-Voltage Circuit Breakers Rated on a Symmetrical Current Basis 5. IEEE C37.013 Standard for AC High-Voltage Generator Circuit Breakers Rated on a Symmetrical Current Basis 6. IEEE C37.013a Standard for AC High-Voltage Generator Circuit Breakers Rated on a Symmetrical Current Basis. Amendment 1: Supplement for Use with Generators Rated 10 100 MVA 16347D-1 03/07/16

1.05 1.06 QUALIFICATIONS It is the manufacturer s responsibility to employ designs and manufacturing practices that incorporate the latest revision of these standards. The equipment being proposed shall have passed applicable IEEE design tests. Copies of test certifications shall be provided to the Purchaser upon request. The manufacturer shall perform production tests required by applicable IEEE Standards and these specifications. Each circuit breaker shall be inserted into a switchgear cubicle or similar jigging device to verify mechanical alignment. Interchangeability of breakers of the same rating shall be verified. A set of production test reports shall be included in each instruction manual. D. The manufacturer shall have a minimum of 20 years experience in manufacturing vacuum circuit breakers and vacuum interrupters OPERATION AND MAINTENANCE MANUALS Equipment operation and maintenance manuals shall be provided with each assembly shipped and shall include instruction leaflets, instruction bulletins and renewal parts lists where applicable, for the complete assembly and each major component. PART 2 PRODUCTS 2.01 2.02 MANUFACTURERS Eaton *_ *_ The listing of specific manufacturers above does not imply acceptance of their products that do not meet the specified ratings, features and functions. Manufacturers listed above are not relieved from meeting these specifications in their entirety. Products in compliance with the specification and manufactured by others not named will be considered only if pre-approved by the Engineer ten (10) days prior to bid date. RATINGS Note to Spec. Writer Select either the vacuum circuit breaker table or the Generator Breaker table depending on the application. Fill in the table based on the desired ratings. Select drawout or fixed type breaker in section * Note to Spec. Writer Insert data in blanks 16347D-2 03/07/16

D. Preferred ANSI/IEEE ratings: 1. Each vacuum circuit breaker shall have the following characteristics: a. Rated Maximum Voltage kv, rms b. Rated Continuous Current A c. Frequency Hz d. Rated Voltage Factor (k) 1.0 e. Power Frequency Withstand kv, rms f. Basic Impulse Level (BIL) kv, peak g. Interrupting Capability ka h. Interrupting Time 3 or 5 cycles cycles i. 2-Second Short Time Current Carrying Capability ka, rms j. Closing and Latching Capability ka, peak k. Operating Sequence O 0.3 sec CO - sec CO l. Control Voltages m. Spring Charging Motor or Power Supply n. Close Coil o. Trip Coil Optional Accessories 1. 2nd Trip Coil 2. Undervoltage Trip Release (UVR) Special Duty Applications 1. Single bank capacitor bank current class C1 or C2/ A/ Hz 2. Back-to-Back capacitor bank current class C1 or C2/ A/ Hz 3. Cable Charging Current C1 or C2/ A/ Hz Each Generator Breaker shall have the following characteristics: 1. Rated Maximum Voltage kv, rms 2. Rated Continuous Current A, rms 3. Frequency Hz 4. Rated Voltage Factor (k) 1.0 5. Power Frequency Withstand Voltage kv, rms 6. Lightning Impulse Withstand Voltage kv, peak (Also known as Basic Impulse Level (BIL)) 7. Interrupting Time ms 8. Closing Time ms 9. Short-Circuit Current ka, rms 10. Asymmetrical Current Interrupting Capability % DC 11. Ref: Minimum Opening Time ms 12. Short-Time Current Carrying Capability ka, rms 13. Duration of Short-Time Current s 16347D-3 03/07/16

14. ka, peak 15. ka, rms DC 16. 17. ka, rms DC 18. 19. kv/µs a. b. Ops Ops 20. 21. 22. Closing and Latching Capability MEDIUM VOLTAGE VACUUM CIRCUIT BREAKERS First Generator-Source Symmetrical Current Interrupting Capability First Generator-Source Asymmetrical Current Interrupting Capability % Second Generator-Source Symmetrical Current Interrupting Capability Second Generator-Source Asymmetrical Current Interrupting Capability % Prospective TRV Rate of Rise of Recovery Voltage (RRRV) Transient Recovery Voltage Peak (E2 = 1.84 x V) kv, peak Transient Recovery Voltage Time to Peak (T2 = 0.62 x V) µs Load Current Switching Endurance Capability No-Load Mechanical Endurance Capability Out of-phase Current Switching Capability 23. 90⁰ Out-of-Phase Power Frequency Recovery Voltage kv, rms (= 1.5 x sqrt (2/3) x V) E. ka 24. 90⁰ Out-of-Phase Inherent TRV Rate of Rise of Recovery kv/µs Voltage (RRRV) a. Transient Recovery Voltage Peak (E2 = 2.6 x V) kv, peak b. Transient Recovery Voltage Time to Peak (T2 = 0.89 x V) µs 25. Operating Sequence 26. Control Voltages (Specify AC or DC in addition to voltage) a. Spring Charging Motor or Power Supply b. Close Coil c. Trip Coil 27. a. b. Optional Accessories 2nd Trip Coil Undervoltage Trip Release (UVR) CO 30 sec CO Breakers shall be horizontal draw-out (fixed) vacuum type. All breakers of the same rating shall be mechanically and electrically interchangeable. 2.03 CONSTRUCTION All materials shall be new and unused. No reconditioned or used parts from used circuit breakers shall be reused in the new circuit breaker. The manufacturer of the vacuum Circuit breaker shall also be the manufacturer of the vacuum interrupter and breaker operating mechanism with a minimum of 20 years of experience. 16347D-4 03/07/16

2.04 D. E. F. MAJOR COMPONENTS Vacuum interrupter Assembly 1. Each circuit breaker shall contain three vacuum interrupters separately mounted in a self-contained, removable self-aligning pole unit. 2. The vacuum interrupter assembly shall be manufactured by Eaton and labeled as such. 3. The components shall be inspected and assembled in a class 1000 clean room prior to sealing the components. 4. The components shall be inserted into a vacuum heat chamber and sealed under vacuum. Pinch tubes are not acceptable. 5. A stainless steel corrugated bellows shall achieve isolation of the ambient air and the vacuum. The moving contact stem of the vacuum interrupter shall have a machined groove to prevent rotation of the contact within the vacuum chamber. The contacts shall be self-aligning and shall not require adjustments for the life of the vacuum interrupter assembly. Manual Trip and Close 1. It shall be possible to manually trip or close the breaker from the front of the circuit breaker, once the stored energy device is charged. 2. In the event of a loss of secondary power, an emergency manual open feature is required and must be an integral part of the circuit breaker. A tool, separate from the circuit breaker, is not permitted as a means of manually opening the circuit breaker. The mechanism shall have front accessible manual close and trip operators that are directly connected to the breaker operating mechanism and are an integral part of the electrical close and trip coils. The manual close and trip buttons shall be labeled accordingly. The opening and closing speed of the contacts shall be independent of the control voltage. Common Pole Shaft 1. The circuit breaker mechanism shall open and close all three phases and any auxiliary devices via a common operating shaft to ensure consistent and simultaneous operation of the main contacts. The shaft shall be supported at the ends and along its length with bearings. The main drive shaft shall be connected to the individual vacuum interrupters via insulated drive links. Shock Absorber System 1. The mechanism shall contain a shock absorber system to dampen the opening force of the circuit breaker. The shock absorber shall have sufficient resilience to prevent contact bounce that could cause a re-strike of the main contacts during the opening of the circuit breaker or during a spring discharge. The shock absorber shall have a design life of 10,000 breaker opening and closing cycles without the need for repair, replacement or adjustment. Front Cover 1. Each breaker shall have a full front metal shield. It shall be possible to access and maintain the operating mechanism from the front of the breaker. The front metal shield shall serve to enclose the breaker in its own grounded metal compartment when the breaker is in the fully connected position. Operations Counter 16347D-5 03/07/16

G. 1. Each breaker mechanism shall have a five (5) digit non-resetting mechanical operations counter connected to the operating shaft as manufactured by Veeder-Root or an engineerapproved equal. Spring Charged Indicator 1. Each operating mechanism shall be equipped with a visible indicator to show the state of the stored energy mechanism. The indicator shall show when the spring is fully charged or discharged. H. I. J. K. L. M. N. Mechanical Status Indicator 1. Each new vacuum circuit breaker shall have a mechanical status indicator, mechanically linked to the operating mechanism, with the word "CLOSED" on a red background when the breakers are closed and the word "OPEN" on a green background when the breakers are open. Auxiliary Contacts 1. The breaker shall have a low inertia, rotary operated auxiliary switch connected to the main pole shaft assembly. Insulated Pole Assemblies 1. Pole assemblies shall be insulated from ground with non-hydroscopic insulating materials manufactured from glass-reinforced polyester, epoxy or cycloaliphatic epoxy. Trip Free Operation 1. The new circuit breaker operating mechanism shall be a true Trip-Free design. When the trip function is mechanically engaged and held and the close function is initiated either electrically or mechanically, the contacts shall not close. The contact travel shall be restricted to 10% of the total travel and shall be in compliance with the requirements of IEEE/ANSI C37.06. Control Circuit Wiring 1. Control wiring shall be SIS, cross-linked polyethylene, #14 AWG minimum except for short runs such as coil and motor leads. Insulated terminals shall be used. No splices shall be allowed. Stored Energy Discharge 1. The vacuum circuit breaker shall incorporate a manual and an automatic system to completely discharge all stored energy before the circuit breaker is fully withdrawn from the switchgear housing. The system shall not automatically discharge the stored energy while in the connected position. Second Shunt Trip 1. For vacuum circuit breakers equipped with a second shunt trip, it is mandatory to provide two separate opening coils/devices. One opening coil/device on two different circuits is not permitted. 2.05 FEATURES [DRAWOUT ONLY] Interlocks 16347D-6 03/07/16

1. Interlocks shall be provided to prevent closing of a breaker between operating and test positions, to trip breakers upon insertion or removal from stationary structure, and to discharge stored energy mechanisms upon insertion or removal from the stationary structure. The breaker shall be secured positively in the stationary structure between and including the operating and test positions. The mechanism shall have a passive interlock to block the insertion or removal of a closed breaker. The system shall prevent the insertion of the levering tool, if used, anytime the breaker is in the closed position. D. E. F. Automatic Secondary Contact Block 1. Secondary control circuits shall be connected automatically through a selfaligning and self-engaging plug and receptacle arrangement when the circuit breaker is racked into the connected position. Cell Coding System 1. The breaker manufacturer shall supply or interface with the cell coding system to prevent the accidental insertion of a breaker into a cell of a different voltage, current, interrupting capacity or physical arrangement than the type intended for the switchgear cell receiving the breaker. Primary Connections 1. Primary connections (finger clusters) shall be designed to carry the full nameplate rating of the circuit breaker without exceeding the allowable temperature rise. In addition, the primary connections shall be capable of withstanding the full momentary/close and latch rating. Ground Contacts 1. The circuit breaker frame shall be continuously grounded whenever it is installed in the cubicle by use of a sliding contact on the circuit breaker that mates with a ground bar in the bottom of the breaker cell. A plated, self-coupling, separable grounding contact shall be supplied to adequately ground the breaker frame to the cell ground bus. No ground wires shall be required to tie the frame components to ground. Locking Means 1. Locking means shall be provided to lock the circuit breaker while in the fully connected or disconnected positions. The lock shall prevent the insertion or removal of the breaker. The lock shall not prevent the breaker from being operated while in the fully connected position. PART 3 EXECUTION 3.01 DESIGN AND CERTIFICATION (TYPE) TESTING The vacuum breaker supplied shall have type tests performed on its design. Written test reports, data logs and digital reproductions are required to be on hand for review by the 16347D-7 03/07/16

buyer. Non-compliance with these base type tests or the failure to produce evidence of such test shall result in the immediate disqualification without obligation to the buyer. 16347D-8 03/07/16