Two different types of cables are used in primary airfield lighting circuits: - unshielded cables and - shielded cables



Similar documents
Fault location on power cables. Fault location on power cables

KNOW YOUR OPTIONS: 69 KV XLPE POWER CABLE

KNOW YOUR OPTIONS: 230 KV POWER CABLES

Section kv Power Cables

General Calculations. Excerpt from PRYSMIAN S WIRE AND CABLE ENGINEERING GUIDE

Cable Solutions for Servo and Variable Frequency Drives (VFD)

LEAD FREE FIREX. Interlock Armored Cables TECK90 and MC Industrial Cables. w w w. n e x a n s e n e r g y. c o m

APPLICATION ORIENTED DESIGN OF CABLES

Model 1756 Test Lead Kit

Industrial Cable Solutions for Variable Frequency Drives

Festoon 715 P PUR cable for flexible application in festoon systems

Screened cable and data cable segregation

IEEE POWER ENGINEERING SOCIETY CHICAGO CHAPTER THE OKONITE COMPANY WEDNESDAY JANUARY 11, 2006 JIM FITZGERALD ENGINEERING LINGO

Unarmored Variable Frequency Drive (VFD) Cable Termination Guide

UGVCL/SP/591/11KV HT AB CABLE

100% EMI Emission Containment

TAN δ (DELTA) CABLE TESTING OVERVIEW AND ANSWERS TO FREQUENTLY ASKED QUESTIONS. What Is Tan δ, Or Tan Delta?

PROFIBUS cable. for PROFIBUS-PA and -DP 10/ EN

SUITABILITY OF DIFFERENT TEST VOLTAGES FOR ON-SITE TESTING OF XLPE CABLE SYSTEMS

Network Standard Advice No. 1420C 9/6/2011

Gulf Cable & Electrical Ind. Co.

HIGH- AND EXTRA-HIGH-VOLTAGE GLOBAL CABLE SYSTEM SOLUTIONS Rely On Our Experience... Experience Our Capabilities

HARTING Ethernet Cabling 4-poles Overview

Guide to the electrical parameter classifications of IEC and IEC safety standards

4 IX D N E P P A Installation methods Current-carrying capacity and voltage drop for cables Reference method IET Wiring Matters

Pressure monitoring equipment for oil-sf 6. bushings, type GOEK

FIRE RESISTANT CABLE CONSTRUCTION OF CABLES

An Ethernet Cable Discharge Event (CDE) Test and Measurement System

Electrical Resistance Resistance (R)

Flexible and safe solutions, for decades. Cables for alarmand safety systems

Investigation of the Residual-charge Technique for Diagnosis of Water-tree Deteriorated Cross-linked Polyethylene Cable

Protection Systems. A UTC Fire & Security Company F Linear Heat Detector FEATURES DESCRIPTION APPLICATIONS BENEFITS

THE PATHWAY TO POWER HIGH-VOLTAGE CABLES

Lightning Arresters P KVA P KVA. Description & Installation

MV CABLE TYPE C

COAX Cables Radio Frequency Cables

Aerial Fibre Optics. Complete One Stop Solution for Aerial Fibre Optics. OPGW Cable and Fittings for OPGW

Commercial Coaxial Cable

MEASUREMENTS OF THRUST LOAD IN CABLE SYSTEMS SEMI-RIGIDLY INSTALLED IN DUCT / MANHOLE STRUCTURES

How To Monitor Water Penetration In A Cable Screen

Specification SFTP CAT6 Network Cable 23AWG CU

HV Submarine Cable Systems Design, Testing and Installation

Joslyn Clark Controls, Inc.

Dielectric Withstand Testing in a Production Environment

Industrial Ethernet The Perfect Cable for an Imperfect Environment

Explaining and avoiding faults Increasing availability

Cat7/Class F New Installation Concept New infrastructure. Handbook

Insulation Resistance Testing of Low Voltage Cables in the Field

East Central College HANSEN HALL LEVEL 300/400 RENOVATIONS PACKAGE

Cable Selection for Medium Voltage Capacitor Banks and Harmonic Filter Banks

Directions for use : Dosing chutes type DSX.

Explosion proof enclosures

Good EMC Design Principles: cable routing

SCHEDULE ' A' TECHNICAL SPECIFICATION FOR 11/22/33KV H.T.XLPE POWER CABLE FOR DISTRIBUTION NETWORK IN MAHARASHTRA (SPECIFICATION NO.

Crosstalk effects of shielded twisted pairs

ELECTRICAL INSULATION TESTING OF HV EQUIPMENT UP TO 33kV

HIGH VOLTAGE XLPE CABLE SYSTEMS. Technical User Guide

Outdoor Carrier Class Shielded Ethernet Cable. Datasheet. Models: PRO, CARRIER, Connectors. Increase Performance. Extreme Weatherproof

Transformer Bushings for GIS

M. GELDON Brugg Kabel CZ. Ing. D. RÚŽEK PREdistribuce. Switzerland Czech Rep. Czech Rep. Czech Rep., Switzerland Germany

The proof is here!! Ron Goethals, Philadelphia; June 18, 2014

Session 14 Cable Support Systems

Sheath fault location on power cables. Sheath testing, Sheath fault location and Location of earth faults

WIRE AND CABLE ENGINEERING GUIDE

A Study of a MV Cable Joint

Coaxial Cable Entry Panels, Coax and Grounding Connectors. Technical Note

MEDIUM VOLTAGE POWER CABLES

e-mobility Special cables for electric vehicles Coroplast Fritz Müller GmbH & Co. KG Tapes Cables Cable Assemblies

DRAFT. University of Pennsylvania Moore School of Electrical Engineering ESE319 Electronic Circuits - Modeling and Measurement Techniques

The Contractor shall furnish and install all shielded power cable suitable for use on this project.

HOW TO CORRECTLY CONNECT DEEP CYCLE BATTERIES AND CHOOSE THE RIGHT CABLE SIZING

Direction of current flow through conductor. Fig. 1 Magnetic field generated by current flow

ACCESSORIES FOR HV CABLES WITH EXTRUDED INSULATION

WHITEPAPER. Cable and Connector for Hiperface dsl motor drive applications

Temperatures of Bundled Electrical Cables Installed in Bored Holes in Residential Wood Framing

Respecting the environment

SICK AG WHITEPAPER. Information for cable manufacturers Note-2_03

High Voltage Systems. Today. The history of cables

Proposed Task Group: Electrical Cable and Condition Monitoring Codes and Standards for Nuclear Power Plants

BRÖCKSKES D-VIERSEN PV1-F 4,0 mm BRÖCKSKES D-VIERSEN PV1-F 4,0 mm d d 2 2 C VDE-REG.-Nr /2009

Planar versus conventional transformer

EE301 Lesson 14 Reading: , , and

Chapter 9. Bonding and Grounding

XLPE Land Cable Systems User s Guide. Rev 5

ALARMLINE ANALOGUE Linear Heat Detection System

EARTHING AND BONDING AT SECONDARY SUBSTATIONS

MEDIUM VOLTAGE CABLES Up to and including 36 KV

SUBJECT: NO MORE 300 VOLTS IN PLTC PRINT LEGEND

Trial Exams C. Standards and Regulations. Examination No: GH-08-C- 1 hour and 5 minutes plus 10 minutes reading time

Section B: Electricity

Understanding Shielded Cable

MiCAFIL. 1 RIP Technology. Bushings. Z. Zic 09/2003

E-Highway2050 WP3 workshop April 15 th, 2014 Brussels

Integrated Development and Assessment of New Thermoplastic High Voltage Power Cable Systems

DEHN + SÖHNE. DEHNconductor System No Problems with Proximities

ScottishPower Distribution Cables & Equipment. Metal Theft

SEISMIC VELOCITY TRANSDUCER T1-40

AutoLink Three-Phase Sectionalizer Specifications. Scope. General. Applicable Standards. Operating principle

Max. Length of HTS Cables in the Future

EDS KV TRIPLEX CABLE

Transcription:

Two different types of cables are used in primary airfield lighting circuits: - unshielded cables and - shielded cables Classically both cables have a single AWG 8 copper conductor or a cross section of 6.0 mm 2. In most cases, the conductor is equipped with a conductor shield formed by a semi-conductive layer, covered by an XLPE insulation. Unshielded cables may have an outer sheath directly extruded above the insulation. The shielded version has another semi-conductive layer above the XLPE insulation covered by a metallic screen (braid or metallic foil) and an outer sheath. Both cables perform well in primary airfield lighting circuits. Nevertheless, the unshielded cable shows a rather high sensitivity to the tracking phenomenon under specific circumstances, leading to service interruption of the lighting circuit. 01. CCR, transformer, lights and cable The fig. 1 shows a typical primary airfield lighting circuit, where a constant current regulator (CCR) feeds the primary airfield cable, the transformers and the lights. fig. 1 T: Transformer L: Light Cable: Airfield Lighting Cable I C : Constant Current T 1, T 2 : CCR Terminals V: CCR Output Voltage 2

02. Shielded cables The screen of the cable determines a defined voltage across the dielectric of the cable. The screen is earthed and the voltage to earth is V/2 at the terminals of the CCR, V being the voltage generated by the CCR to draw the preset current I c. The transformers and the lights are represented in fig. 2 by their equivalent resistance R L. A voltage drop at each transformer and its light occurs and in case of a balanced circuit as shown in fig. 2, where the transformers are equally distributed along the cable path, the voltage appearing between conductor and screen is zero at a point situated somewhere in the middle of the circuit. Shielded Primary Airfield Lighting Cable V 03. Unshielded cables L : The local voltage across the dielectric of unshielded cables is not as well determined as is the case of shielded cables. The voltage drop across the transformer terminals and especially the capacitive voltage distribution along the cable path determines the voltage to earth. R L : Resistance Light + Transformer C C : Cable Capacitance I C : Constant Current V: CCR Output Voltage Local Voltage fig. 2 In proximity of the terminals T1 and T2, the voltage to earth is V/2. Along the cable path the voltage on the dielectric depends on the local earth resistance and the local capacitance of the cable to earth. In places where the cable lays in direct contact with a humid soil, the earth resistance is low and the capacitance is high. The voltage is fully supported by the insulation. The voltage-to-earth appearing in those places across the outer surface of the dielectric is very low. In other places, where the soil is dry, the resistance to earth is high and the local voltage is distributed between the cable insulation and the soil. The electric potential-to-earth appearing on the surface of the dielectric is high. If these two circumstances of wet and dry soil appear locally close to each other, a voltage difference V L is build up along the surface of the dielectric; this is shown schematically in fig. 3. Unshielded Primary Airfield Lighting Cable R L : Resistance Light + Transformer C 1... C n : Local Cable Capacitance R 1... R n : Local Earth Resistance V L : Local Voltage on Insulation Surface V: CCR Output Voltage I C : Constant Current fig. 3 3

An example illustrates this situation in a very simple manner, as shown in fig. 4. The unshielded cable is placed on an earthed metallic cable-ladder. On the steps, the cable surface has a low resistance to earth; between the steps, the resistance to earth is very high. Thus the electric potential to earth on the surface laying on the steps is zero while the electric potential on the cable surface laying between the steps is high; the voltage across the cable surface and the steps corresponds approximately to the applied voltage, e.g. V/2, when this cable ladder is used close to the constant current regulator. From a safety point of view the potential difference on the cable surface in such a situation can reach a dangerous level. Additionally there is a risk of surface tracking when the cable surface is wet or dirty. The risk increases at higher CCR output voltage level. Earthed Metallic Plate (1) Unshielded Primary Airfield Lighting Cable Earthed Metallic Plate (2) Conductor Insulation Air Conductor Insulation Surface Earth fig. 4 04. Unshielded cables placed on or over a metallic plate Fig. 5 shows an unshielded cable placed at a height h over an earthed metallic plate. The electric field is unequally distributed in the cable dielectric and the air between the dielectric and the metallic plate. The following table gives the maximum electric field strength in that air gap in function of the height h for an unshielded 5 kv AWG 8 - cable with 2,8 mm XLPE insulation according to FAA Specification L-824. The field E is given in kv/mm for a peak voltage of 1 kv conductor to earth. Unshielded Cable over Metallic Plate Insulation Metallic Plate h fig. 5 Height h/mm E air (peak) kv/mm 0 1,18 0,1 1,10 0,2 0,95 0,5 0,75 1,0 0,58 2,0 0,42 Table 1: Electric field in air gap; conductor to metallic plate voltage is 1 kv 4

05. Measurements Voltage measurements have been realised on several 10 kva CCR with a digital storage oscilloscope. The latter is equipped with one differential input composed by one inverting and one non-inverting input; both inputs are fitted with HV-probes; the oscilloscope is earthed. Fig. 6 shows the voltage of a normally working CCR; the RMS voltage is 1,23 kv; the peak voltage to earth 2,12 kv. Fig. 7 shows the voltage of a circuit, where several lights were blown out. In this case, the cores of the transformers of these lights go into magnetic saturation and the CCR therefore delivers a much higher peak voltage. Under these circumstances the measured peak voltage is 2,72 kvp to earth. fig. 6 CCR voltage to earth under normal condition fig. 7 CCR voltage to earth with blown out lights 5

06. Risk of tracking discharges If the unshielded cable is laying on a metallic plate, the field in the air gap between the cable and the plate will be for h = 0,1 mm and 1 kvp (see table 1): E air = 1,1 kv/mm At the measured peak voltage of 2.72 kv, the electrical field strength in the air gap will be: E air = 1.1 * 2.72 kv/mm = 2.99 kv/mm This field strength corresponds to the disruptive field strength in air; an electrical discharge starts at each half cycle of the voltage; ozone formation and erosion of the dielectric risk to damage the cable surface by tracking. 07. Recommendations The described tracking risk doesn t exist with shielded cables; also from a safety point of view the use of shielded cables is to be preferred. The risk introduced by the tracking phenomenon is well known and introduced in different standards. The US Standard ICEA-S-66 524, 4.2.2, applicable to airfield lighting cables, states: "Shielding should be considered where any of the following conditions exits: 1. connections to aerial lines; 2. transition from conducting to non conducting environment; 3. transition from moist to dry earth; 4. dry soil, such in the desert; or 5. damp conduits." In the Appendix G "Shielding" of this standard several other provisions are made concerning the use of shielding, especially in G3.1.3: "Likewise, damage to non-shielded cable may result when the surface of the cable is moist or covered with soot, soapy grease, or other conducting film and the external field is partly confined by such conducting film so that the charging current is carried by the film to some spot where it can discharge to ground. The resultant intensity of discharge may be sufficient to cause burning of the insulation or jacket." 6

08. Conclusions The use of unshielded cables introduces several problems especially if the CCR output voltage exeeds the 2000 V-level: safety: the risks of electrical discharges should not be neglected. tracking: the cable may be damaged and cable failures will provoke more maintenance and repair costs. burning: under unfavourable circumstances, fire hazard becomes a reality. The use of shielded cables avoids those problems: no safety problems: the cable jacket may be touched without any risk. no tracking phenomenon: drastically reduced outages. reduced fire hazard. costs: reduced maintenance and repair costs. long lasting investment. 7

Malmedyer Str. 9-4700 EUPEN - BELGIUM Tel.: +32(0)87.59.70.00 Fax: +32(0)87.59.70.66 http://www.eupen.com e-mail:industrial_projects@eupen.com ISO Certified Company 03/2013-100