Energy Storage Unit for Uninterruptible Power Supply

Similar documents
A MULTILEVEL INVERTER FOR SYNCHRONIZING THE GRID WITH RENEWABLE ENERGY SOURCES BY IMPLEMENTING BATTERY CUM DC-DC CONERTER

Power supplies. EE328 Power Electronics Assoc. Prof. Dr. Mutlu BOZTEPE Ege University, Dept. of E&E

Switch Mode Power Supply Topologies

Power Electronic Circuits

Closed Loop PWM Control for Induction Motor Drive Using Dual Output Three Phase Inverter

DC/DC BUCK Converter for Renewable Energy Applications Mr.C..Rajeshkumar M.E Power Electronic and Drives,

Modified Cascaded Five Level Multilevel Inverter Using Hybrid Pulse Width Modulation

Hybrid Power System with A Two-Input Power Converter

Bridgeless PFC Implementation Using One Cycle Control Technique

98% Efficient Single-Stage AC/DC Converter Topologies

Transformerless UPS systems and the 9900 By: John Steele, EIT Engineering Manager

High Intensify Interleaved Converter for Renewable Energy Resources

Design and Simulation of Soft Switched Converter Fed DC Servo Drive

Implementation of High Step-Up Solar Power Optimizer for DC Micro Grid Application

A bidirectional DC-DC converter for renewable energy systems

Development of High Frequency Link Direct DC to AC Converters for Solid Oxide Fuel Cells (SOFC)

Harmonics and Noise in Photovoltaic (PV) Inverter and the Mitigation Strategies

Boundary between CCM and DCM in DC/DC PWM Converters

Welcome to this presentation on Driving LEDs AC-DC Power Supplies, part of OSRAM Opto Semiconductors LED Fundamentals series. In this presentation we

Modeling and Simulation of a Novel Switched Reluctance Motor Drive System with Power Factor Improvement

Design of Four Input Buck-Boost DC-DC Converter for Renewable Energy Application

An Efficient AC/DC Converter with Power Factor Correction

Fundamentals of Power Electronics. Robert W. Erickson University of Colorado, Boulder

Survey of Harmonics Measurements in Electrical Distribution Systems

Selecting IHLP Composite Inductors for Non-Isolated Converters Utilizing Vishay s Application Sheet

Power Quality. Uninterruptible Power Supply

LOW COST MOTOR PROTECTION FILTERS FOR PWM DRIVE APPLICATIONS STOPS MOTOR DAMAGE

Design a Phase Interleaving PFC Buck Boost Converter to Improve the Power Factor

Novel Loaded-Resonant Converter & Application of DC-to-DC Energy Conversions systems

MODELING AND SIMULATION OF A THREE-PHASE INVERTER WITH RECTIFIER-TYPE NONLINEAR LOADS

Analysis of PV cell fed High Voltage Gain Seven and Nine level inverter with Reduced Switches

AC/DC Power Supply Reference Design. Advanced SMPS Applications using the dspic DSC SMPS Family

Design of an Auxiliary Power Distribution Network for an Electric Vehicle

SIMULATION OF CLOSED LOOP CONTROLLED BRIDGELESS PFC BOOST CONVERTER

Design A High Performance Buck or Boost Converter With Si9165

Chapter 20 Quasi-Resonant Converters

Line Reactors and AC Drives

Variable Frequency Drives - a Comparison of VSI versus LCI Systems

Modeling and Analysis of DC Link Bus Capacitor and Inductor Heating Effect on AC Drives (Part I)

Chapter 17 The Ideal Rectifier

LTR Series Uninterruptible Power Systems 700 VA KVA. General Specification

Design and Development of Speed Control of Induction motor drive using Pulse-Width Modulation

2012 San Francisco Colloquium

DC Voltage Regulation by Buck Converter Applicable for Stand Alone Micro Hydro Power Generation

High Power Factor Boost Converter with Bridgeless Rectifier

Parametric variation analysis of CUK converter for constant voltage applications

AN ULTRA-CHEAP GRID CONNECTED INVERTER FOR SMALL SCALE GRID CONNECTION

Grid Interconnection of Renewable Energy Sources Using Modified One-Cycle Control Technique

EXPERIMENT 1 SINGLE-PHASE FULL-WAVE RECTIFIER AND LINEAR REGULATOR

Application Report SLVA057

Laboratory 4: Feedback and Compensation

MICRO HYDRO POWER PLANT WITH INDUCTION GENERATOR SUPPLYING SINGLE PHASE LOADS

T.FRANCIS, D.NARASIMHARAO

Considering the effects of UPS operation with leading power factor loads

Chapter 6: Converter circuits

International Journal of Science and Research (IJSR) ISSN (Online): Index Copernicus Value (2013): 6.14 Impact Factor (2014): 5.

Creating a Usable Power Supply from a Solar Panel

Power Quality Issues, Impacts, and Mitigation for Industrial Customers

Performance of 3-Phase 4-Wire Solid State Transformer under Imbalanced Loads

3-Phase Synchronous PWM Controller IC Provides an Integrated Solution for Intel VRM 9.0 Design Guidelines

AN2389 Application note

DC-DC Converter Basics

A COMPERATIVE PERFORMANCE ANALYSIS OF BRIDGELESS PFC BOOST CONVERTER WITH THE CONVENTIONAL CONVERTER

MULTI-INPUT DC-DC CONVERTER FOR RENEWABLE ENERGY SOURCES

Analysis of AC-DC Converter Based on Power Factor and THD

Performance Enhancement of Wound Rotor Induction Motor by VSI with Dynamic Capacitor Controlled Rotor Circuit

Design of Bidirectional Coupling Circuit for Broadband Power-Line Communications

Solar Energy Conversion using MIAC. by Tharowat Mohamed Ali, May 2011

Current Ripple Factor of a Buck Converter

Welcome to this presentation on Switch Mode Drivers, part of OSRAM Opto Semiconductors LED Fundamentals series. In this presentation we will look at:

POWER SYSTEM HARMONICS. A Reference Guide to Causes, Effects and Corrective Measures AN ALLEN-BRADLEY SERIES OF ISSUES AND ANSWERS

Analysis and Control of Three Phase Multi level Inverters with Sinusoidal PWM Feeding Balanced Loads Using MATLAB

Introduction to Power Supplies

MULTI-LEVEL INVERTER WITH DC LINK SWITCHES FOR RENEWABLE ENERGY SOURCES

Product Data Bulletin

Single-Stage High Power Factor Flyback for LED Lighting

Chapter 11 Current Programmed Control

UNINTERRUPTIBLE POWER SUPPLIES >9900AUPS UNINTERRUPTIBLE POWER SUPPLIES

See Horenstein 4.3 and 4.4

New Pulse Width Modulation Technique for Three Phase Induction Motor Drive Umesha K L, Sri Harsha J, Capt. L. Sanjeev Kumar

Control Development and Modeling for Flexible DC Grids in Modelica

Application Report SLVA061

The Flyback Converter

Engineering innovation

THE CONTINUOUS growth of the global energy demand

A NEW TWO SWITCH TOPOLOGY BUCK BOOST CONVERTOR IN UNIVERSAL INPUT PFC APPLICATION

Design and implementation of a modified DC- DC converter suitable for renewable energy application

Design and Construction of Variable DC Source for Laboratory Using Solar Energy

2 Topology and Control Schemes

Galleon 6-10K Online UPS. Voltronic Power Technology Corporation

A Design of DC/DC Converter of Photovoltaic Generation System for Streetcars

PRECISION CAPACITOR CHARGING SWITCHING POWER SUPPLIES

How To Simulate A Multilevel Inverter

Power Electronics for Renewable Energy Integration into Hybrid AC/DC Microgrids Kai SUN Aug 27, 2015

High Voltage Power Supplies for Analytical Instrumentation

Survey of Harmonics Measurements in Electrical Distribution Systems

SERIES-PARALLEL DC CIRCUITS

Properties of electrical signals

SIMULATION AND ASSESSMENT OF SINGLE PHASE SEMI-Z-SOURCE INVERTER (S-ZSI)

Switching Regulator IC Series Inductor Calculation for Buck Converter IC

Transcription:

Levitated Systems and Linear Drives, October 1-13, 211, Daejeon, Korea Energy Storage Unit for Uninterruptible Power Supply Sun Pil Kim and Feel-soon Kang Han National University, Dept. of Control and Instrumentation Engineering, Daejeon 35-719, KOREA feelsoon@ieee.org, feelsoon@han.ac.kr ABSTRACT: Uninterruptible power supply employing a series connected tery and capacitor as a -link is proposed to achieve a simple circuit configuration and higher system reliability. It reduces the number of switching devices by applying a common-arm scheme, and it shows fast response for a power failure owing to a -to- converter. Operational principles to normal, stored-energy, and bypass mode are discussed in detail. The validity of the proposed UPS system is verified by experimental results using a prototype. 1 INTRODUCTION Generally uninterruptible power supply (UPS) is used to maintain a stable electric power supply to critical loads with high quality power protecting them against unexpected power failure. For example, medical facilities and data-storage computer systems require fast response, compensation and immediate availability of electrical power. Considerably affect these characteristics is energy storage units like a tery bank. Energy storage units in UPS system should supply power to the load when the ac line fails. If they are not capable to implement this important role, then the whole UPS system fails even though it employs well-designed power electronics circuits. To satisfy the requirements, we propose a common-arm based UPS equipped with a -to- converter employing an energy storage unit. The proposed UPS consists of ac-to- and -to-ac converter sharing a common-arm, a static switch for bypassing, and the proposed -to- converter. The ac-to- converter is used for maintaining the input current sinusoidal and in phase with the input ac voltage to obtain high power factor. It also supplies the desired -link voltage suitable for proper operation of back-end inverter. The -link is a part of the proposed -to converter. It has a series connection of a tery bank and a capacitor. The -to-ac inverter needs to synthesize high quality output voltage wave. Operational mode is analyzed and the validity of the proposed UPS with the energy storage unit is verified by experimental results. 2 UPS WITH THE PROPOSED CONERTER 2.1 Circuit Configuration Generally, UPS system is divided into four parts: an ac-to- converter, an energy storage unit, a -toac inverter, and a static switch for bypassing. The acto- converter is used to produce high quality voltage for adequate operation of the back-end -toac inverter, and it also needs to obtain high power factor satisfying the corresponding regulation. The -to-ac inverter is to synthesize high quality ac output voltage to feed the load. The ac-to- converter charges the tery maintaining constant link voltage. To sustain high -link voltage, lots of tery cells need to be connected in series. It causes some problems related to system cost, space, reliability, and safety considerations to increase link voltage. To alleviate the high voltage tery problem, the most useful technique is to employ a bidirectional -to- converter. The main circuit configuration for power conversion is based on single-phase voltage regulator, which has a commonarm between the ac-to- converter and the -to-ac inverter. It steps down the high -link voltage to low tery voltage during the normal mode operation, and step up the low tery voltage to high -link voltage during the stored-energy mode operation. The

Levitated Systems and Linear Drives, October 1-13, 211, Daejeon, Korea bi-directional -to- converter is usually applied to on-line UPS system. in Iin A SS B Lin S1 S2 Static Switch S3 S4 S5 S6 Lf Cf Iout LOAD out The output terminal of the converter is composed of a series-connected a tery bank and a capacitor. The -link voltage becomes the sum of voltage across the capacitor ( ) and the tery voltage ( ), namely -link = +. Figure 2 shows the steady-state waveforms for continuous current conduction mode (CCM) operation where the inductor current flows continuously at i L (t)>. By applying a volt-second balance law to the inductor, the ratio of the output to the input voltage of the proposed converter is given by Proposed Circuit C vl Figure 1. UPS with the proposed converter. The proposed UPS system consists of ac-to- and -to-ac power converter sharing a common-arm, an energy storage unit, and a static switch for bypassing as given in Figure 1. The ac-to- converter includes an input boost inductor (L in ), switching devices (S 1 and S 2 ), and a -link which has a series connection of a tery bank and a capacitor ( and ). During a stored energy mode operation, the voltage across the -link is controlled by the proposed -to converter which consists of a switch, a diode, and an inductor. The objective of the ac-to- converter is to maintain the input current sinusoidal and in phase with the input ac voltage to obtain high power factor. It also supplies the desired -link voltage suitable for proper operation of back-end inverter during a normal mode operation. It needs to synthesize high quality output voltage wave. The -to-ac inverter consists of switching devices (S 5 and S 6 ), and common-arm switches (S 3 and S 4 ) are used to ac-to converter and -to-ac inverter at the same time. v L i L L DA SA t M link 1 ( D) (1) 1 D where D = t on /T S. From (1), we can notice that the voltage conduction ratio of the converter is exactly same with the boost converter. Therefore, the output voltage is always greater than the input voltage. On the other hand, the output voltage is always clamped by the sum of the tery voltage and the capacitor voltage. Reflecting this fact, the boosting rate of the output voltage to the tery voltage internally depends on that of the capacitor voltage, and thus we derive (2) from (1). M C D ( D) (2) 1 D Using (1) and (2), the ratio of the output voltage to the capacitor voltage is defined by link 1 1 D link 1 (3) 1 D D D From (2) and (3), the voltage conversion ratio M C (D), the ratio of the output capacitor voltage ( C ) to the tery voltage is equal to that of the buckboost converter, and the voltage relation between the -link voltage and the capacitor voltage is equal to that of buck converter. - il IL ton toff Ts Figure 2. Key waveforms of the proposed converter. t 2.2 Normal Mode Operation When the input ac voltage is within the allowable tolerance range, the UPS system operates in normal mode. The input power is transferred to the output load via the ac-to- converter and the -to-ac inverter. During this mode, voltage across the -link is maintained by the ac-to- converter. It means the tery bank is at 1 % state of charge. The

Levitated Systems and Linear Drives, October 1-13, 211, Daejeon, Korea selection switch (S s ) in the input stage is lying at position B. 2.3 Stored Energy Mode Operation When the input ac voltage is out of the allowable tolerance range or is not available at all, the UPS system changes its operational mode from normal mode to stored-energy mode. Power line disturbances include various statuses of power line faults and input voltage derivations such as power outage, voltage fluctuations, under or over voltage, surge, occasional frequency fluctuations, and voltage harmonics. When these kinds of faults are occurred, the input switch disconnects the UPS from the grid transferring the input from the ac line to current power source unit. During this mode, the switches of the ac-to- converter (S 1 and S 2 ) are not working. So the proposed converter should supply energy to the output load instead of the grid. By controlling of the switch S A, it can maintain voltage across the -link constant using the tery source. 2.4 Bypass Mode Operation The static switch is used to bypass the UPS system in case of failure or if maintenance is required. The UPS system also operates in bypass mode in case of malfunction. In this case, the output frequency should be equal to that of the ac line frequency to ensure transferring from normal to bypass mode and vice versa. 3 DESGN GUIDELINE arious approaches are allowable to design power stages, and some iteration may be required when performance differs from design predictions. From the analysis of the boundary condition of the proposed converter, the inductor (L) value can be calculated by TS L 2 I link OB D (4) Here, T s means the switching period, -link is the -link voltage controlled by the ac-to- converter. D is the duty ratio of the switch (S A ), and I OB is the average output current. Generally, the capacitor is selected to regulate ripple voltage to the level required by the specification, but in a ripple regulator such as this, the control circuit determines the output voltage ripple. The output voltage ripple is relatively independent of the output capacitor characteristics. Since output voltage ripple is set, the output capacitor is chosen to provide satisfactory response to fast load transients. In the proposed converter, assuming that all ripple current component of the diode current flows through the load resistor, the peak-to-peak voltage ripple is given as v link D TS TS D (5) RC link Here, is the time constant. Rearranging (5), the capacitor value yields as C D T S link (6) R v link Considering off state of the converter switch, the voltage rating of the switch ( SA ) should meet the following relation. S A v v (7) L Similarly, voltage rating of the freewheeling diode ( DA ) should satisfy the next relation. D A v link (8) 4 EXPERIMENTAL RESULTS The validity of the UPS system with the proposed converter was verified by a laboratory prototype. Input voltage is 22, 6 Hz, and the output voltage is generated to get the same values of the input voltage. oltage across the -link is controlled to 385. The operating frequency of the switch in the proposed converter is set to 1 khz. A digital controller based on a TMS32C24 was designed to ensure the stability and dynamic response of the UPS system. Figure 3 shows the operational waveforms of the proposed converter when the UPS is in the stored energy mode operation. It shows voltage across the capacitor, diode current, and inductor current in sequence. When the voltage across the -link is dropped by certain reasons, the switch in the

Levitated Systems and Linear Drives, October 1-13, 211, Daejeon, Korea proposed converter starts to meet the voltage requirement. 2 i DA -2 2 i L Figure 3. Key waveforms of the proposed converter. Figure 4(a) shows experimental result waveforms of input voltage ( in ), input current (I in ), and output voltage ( out ), respectively. During the outage of 3 [sec], the proposed UPS system maintains the output voltage constant. Its magnified waveforms before and after the power interrupt are given in Figure 4(b) and Figure 4(c), respectively. The output voltage is regulated sufficiently well within 1 % regardless of the variation of input voltage. 3ms -2 (c) Figure 4. Operational waveforms with the outage of 3 seconds, (a) input current, input voltage, and output voltage during 5 seconds, (b) magnified waveforms when the outage is occurred, (c) magnified waveforms when the outage is finished. The input power factor is measured over.98, and the input current THD (total harmonic distortion) is less than 3 % regardless of the power rating. The overall system efficiency at normal mode operation was measured about 9 %, and 91 % at stored-energy mode operation. 1 % increasing of the efficiency comes from the reduction of switching losses by the ac-to- converter. 5 CONCLUSIONS 5s (a) 2-2 2-2 2 Uninterruptible power supply employing a series connected tery and capacitor as a -link is proposed and the validity of the UPS system equipped with the proposed converter is verified by experimental results using a prototype. Presentable achievements are summarized as: (1) Simple circuit configuration, (2) Fast response to outage, (3) High efficiency: over 9 [%]. As results, the proposed UPS system with the proposed converter employing an energy storage unit can be a powerful candidate in the UPS market. REFERENCES 3ms (b) -2 2-2 D. M. Divan, A new topology for single-phase UPS systems, IEEE IAS Conf., pp. 931-936, 1989. H. W. Park, S. J. Park, J. G. Park, and C. U. Kim, A novel high-performance voltage regulator for single-phase ac sources, IEEE Trans. Ind. Elect., vol. 48, no. 3, pp. 554-562, 21. I. Andoh, A. et al., Development of a high efficiency flywheel UPS using three arms inverter/converter inverter/converter, IEE Trans. Japan, vol. 116-D(11), pp. 1153-1158, 1996.

Levitated Systems and Linear Drives, October 1-13, 211, Daejeon, Korea J. Holtz, Pulse width modulation-a survey, IEEE Trans. Ind. Elect., vol. 39, pp. 41-42, 1992. K. Hirachi, A. Kajiyama, T. Mii, and M. Nakaoka, Costeffective bidirectional chopper-based tery link UPS with common input-output bus line and its control scheme, IEEE International on Industrial Electronics, vol. 3, pp. 1681-1686, 1996. Noriyuki Hirao, Tetsuichi Satonaga, Takeshi Uematsu, Teruhiko Johama, Tamotsu Ninomiya, and Masahito Shoyama, Analytical considerations on power loss in a three-arm-type uninterruptible power supply, IEEE Power Elect. Special Conf., pp. 1886-189, 1998. R. Krishnan and S. Srinivasan, Topologies for uninterruptible power supplies, IEEE International Symposium on Industrial Electronics, pp. 122-127. 1993. S. Bowes, Development in PWM switching strategies for micro-processor-controlled inverter drives, IEEE IAS Conf. pp. 323-329, 1987. Shamim Choudhury, Implementing triple conversion singlephase on-line UPS using TMS32C24, TI Application Report, SPRA589A, 1999.