October, Wye/Wye Transformers & Tertiary Windings

Similar documents
Power System Harmonics

Triplen Harmonics Mitigation 3 Phase Four-Wire Electrical Distribution System Using Wye- Zig-Zag Transformers

Harmonics in your electrical system

Product Data Bulletin

SIZING THE PRIMARY POWER SYSTEM FOR RESISTANCE WELDERS

Survey of Harmonics Measurements in Electrical Distribution Systems

DESIGNING MODERN ELECTRICAL SYSTEMS WITH TRANSFORMERS THAT INHERENTLY REDUCE HARMONIC DISTORTION IN A PC-RICH ENVIRONMENT

POWER SYSTEM HARMONICS. A Reference Guide to Causes, Effects and Corrective Measures AN ALLEN-BRADLEY SERIES OF ISSUES AND ANSWERS

Introduction. Harmonics and IEEE 519 Page 1 of 19

How To Wire A Three Phase, Single Phase, Wye Transformer

TRANSFORMER: THREE PHASE

BALANCED THREE-PHASE CIRCUITS

Neutral Currents in Three Phase Wye Systems

PHASOR DIAGRAMS HANDS-ON RELAY SCHOOL WSU PULLMAN, WA. RON ALEXANDER - BPA

Power Voltage Transformers for Air Insulated Substations. THE PROVEN POWER.

Power Quality Issues, Impacts, and Mitigation for Industrial Customers

Unit 33 Three-Phase Motors

Single and Three Phase Transformer Testing Using Static Motor Circuit Analysis Techniques

HARMONIC DISTORTION IN THE ELECTRIC SUPPLY SYSTEM

The following table shows approximate percentage wise the

Chapter 24. Three-Phase Voltage Generation

Three-phase AC circuits

Three phase circuits

Survey of Harmonics Measurements in Electrical Distribution System of a Technical Institution

ACCURACY OF POTENTIALTRANSFORMERS

The Importance of the X/R Ratio in Low-Voltage Short Circuit Studies

HPS Universal. Single and Three Phase Potted. Buck-Boost Transformers. Buck-Boost Applications & Standard Specification... 80

SAFETY PRECAUTIONS AND INSTRUCTIONS FOR USE OF TECHNICAL INFORMATION

> Executive summary. The Role of Isolation Transformers in Data Center UPS Systems. White Paper 98 Revision 0. Contents.

Survey of Harmonics Measurements in Electrical Distribution Systems

Specifying a Variable Frequency Drive s

Paralleling Power Sources Which Share a Common Neutral

415V DISTRIBUTION FOR GREEN DATA CENTERS

Line Reactors and AC Drives

Interpreting IEEE Std 519 and Meeting its Harmonic Limits in VFD Applications

Table of Contents. TransformerIQ FAQs 1

UNDERSTANDING POWER FACTOR AND INPUT CURRENT HARMONICS IN SWITCHED MODE POWER SUPPLIES

ELECTRONIC POWER SYSTEMS

FREQUENCY CONTROLLED AC MOTOR DRIVE

21 st Century Facilities

Figure. 1 - Split Phase 240/120V circuit (180 phase shift)

(3 )Three Phase Alternating Voltage and Current

Transformerless UPS systems and the 9900 By: John Steele, EIT Engineering Manager

Principles of Adjustable Frequency Drives

JEFFERSON ELECTRIC, INC. Buck-Boost Transformer Application Manual

PM734F - Technical Data Sheet Winding 28

415V DISTRIBUTION FOR GREEN DATA CENTERS

Harmonic components: electrical network polluters. LV and MV networks are becoming increasingly polluted by current and voltage harmonics. Harmonics a

1 Introduction. 2 The Symmetrical Component Transformation. J.L. Kirtley Jr.

The Facts About Harmonics and Power Factor. Power Quality: Harmonics & Power Factor Correction

Discussion on Class I & II Terminology. IEEE PES Transformers Committee Fall Meeting 2011 Boston, MA

PHASE CONVERSION TECHNOLOGY OVERVIEW

Three-Phase Electric Power Distribution for Computer Data Centers

Performance of 3-Phase 4-Wire Solid State Transformer under Imbalanced Loads

Power System Harmonic Fundamental Considerations: Tips and Tools for Reducing Harmonic Distortion in Electronic Drive Applications

Generator Stator Protection, under/over voltage, under /over frequency and unbalanced loading. Ramandeep Kaur Aujla S.NO

UCI274C - Technical Data Sheet

UCI274H - Technical Data Sheet

Grounding of Electrical Systems NEW CODE: Grounding and Bonding

Radial Distribution Test Feeders

Chapter 12: Three Phase Circuits

SECTION 4 ELECTRIC MOTORS UNIT 17: TYPES OF ELECTRIC MOTORS

Grounding of AC generators and switching the neutral in emergency and standby power systems

Understanding the Alternator

SAMPLE OF THE STUDY MATERIAL PART OF CHAPTER 3. Symmetrical Components & Faults Calculations

Power Technology Issue 104. Modeling of Two-Winding Voltage Regulating Transformers for Positive Sequence Load Flow Analysis in PSS E

CHAPTER 5 PHOTOVOLTAIC SYSTEM DESIGN

Scholars Research Library

System Grounding and Ground-Fault Protection Methods for UPS-Supplied Power Systems

100% Stator Ground Fault Detection Implementation at Hibbard Renewable Energy Center. 598 N. Buth Rd 3215 Arrowhead Rd

Equipment: Power Supply, DAI, Variable resistance (8311), Variable inductance (8321)

HCM434F - Winding 311 APPROVED DOCUMENT. Technical Data Sheet

3-Phase AC Calculations Revisited

Selecting IHLP Composite Inductors for Non-Isolated Converters Utilizing Vishay s Application Sheet

Standards of Power Quality with reference to the Code of Practice for Energy Efficiency of Electrical Installations

The full wave rectifier consists of two diodes and a resister as shown in Figure

Rule Fast Track Analysis for National Life Insurance Co.

ASYMMETRY IN DISTRIBUTION SYSTEMS: CAUSES, HARMFUL EFFECTS AND REMEDIES. A Thesis

PI144K - Winding 311 APPROVED DOCUMENT. Technical Data Sheet. Generator Solutions AS

PI044E - Winding 311 APPROVED DOCUMENT. Technical Data Sheet

Electromagnetic Compatibility (EMC) Low-Frequency Standards. Standards on Low-Frequency Emission: IEC

Basics of Electricity

Digital Energy ITI. Instrument Transformer Basic Technical Information and Application

AC Generators. Basic Generator

Power Quality For The Digital Age INVERTING SOLAR POWER A N E N V IRONME N TA L P OT E N T I A L S W HI T E PA PER

Line to Ground Voltage Monitoring on Ungrounded and Impedance Grounded Power Systems

98% Efficient Single-Stage AC/DC Converter Topologies

Variable Frequency Drive Troubleshooting with U1610A/U1620A

Power Supplies. 1.0 Power Supply Basics. Module

How To Limit Voltage Unbalance

Transformers. Special transformers Reactors products

Analysis of AC-DC Converter Based on Power Factor and THD

BALANCED THREE-PHASE AC CIRCUIT

Current and Temperature Ratings

AC-Synchronous Generator

Chapter 4: Power Factor Correction

Three Phase Circuits. Three Phase Circuits

Power Quality Standards for Electric Service

AC/DC Power Supply Reference Design. Advanced SMPS Applications using the dspic DSC SMPS Family

Transcription:

October, 2013 Wye/Wye Transformers & Tertiary Windings Although care must be exercised when using a wye-wye connected transformer, it has important advantages over other three-phase transformer connections. The primary and secondary circuits are in phase (no phase angle displacements). This is an important advantage where transformers are used to interconnect systems of different voltages in a cascading manner. As an example, suppose there are four systems operating at 500, 230, 138, and 69 kv that need to be interconnected. Substations can be constructed using wye-wye transformer connections to interconnect any two of these voltages. The 500 kv system can be tied with the 69 kv system through a single 500 to 69 kv transformation or through a series of cascading transformations at 230, 138, and 69 kv. If the neutral end of a Y-connected winding is grounded, reduced levels of insulation are required at the neutral end of the winding. A winding that is connected across the phases (delta) requires full insulation throughout the winding. The first advantage is the major reason that wye-wye connected transformers are frequently found in substation installations. They may be appropriate when one is confident that the secondary load is sinusoidal and not comprised of non-linear loads such as variable speed drives and rectifier feeds. When providing power to non-sinusoidal loads however, serious consideration must be made to address and manage the following: Triplen harmonics can pass through the transformer. Triplen harmonics are comprised of the odd multiples of the 3rd harmonic (ex. 3rd, 9th, 15th, 21st etc.). A harmonic is a component of a wave at a frequency that is a multiple of the fundamental (usually 60 Hz) power line frequency. Harmonics are attributed to loading from large amounts of electronic devices, using solid state power switching supplies for converting incoming AC to DC and/or industrial loads for rectifier feeds and induction heating. These non linear loads create harmonics by drawing current in abrupt short pulses, rather than in a smooth sinusoidal manner. Ground faults on the transformer secondary are seen as ground faults on the primary since the zero sequence (neutral) current passes directly through the transformer, making relay protection difficult. With a delta-wye transformer, the secondary ground faults do not cause zero sequence current to flow in the primary circuit. Pacific Crest Transformers 300 West Antelope Road Medford, Oregon 97503 Tel : (541) 826 2113 Fax : (541) 826-8847

On three-phase power systems, neutral current is the sum of the three line-to neutral currents. With balanced three-phase linear currents consisting of sine waves spaced 120 electrical degrees apart, the sum at any instant in time is zero, and so there is no neutral current. In most threephase power systems supplying single-phase loads however, there will be some phase current imbalance and some neutral current. Small neutral current resulting from slightly unbalanced loads does cause problems for typical power distribution systems. Nonlinear loads however, such as rectifiers and power supplies, have phase currents which are not sinusoidal. The sum of balanced, non-sinusoidal, three-phase currents can be substantially above zero. These nonsinusoidal components are referred to as harmonics. Harmonics loading can result in waveform distortion. The triplen harmonics are of primary concern since their effect on the fundamental waveform are additive. Figure 1 Figure1 depicts three-phase fundamental waveforms space 120 degrees. It also shows the third harmonic waveform. Note that the harmonic waveform is in phase with all three fundamental waveforms and has the same phase relationship to the 2nd and 3rd fundamental waveforms as it does with the 1st. With each positive half-cycle of the fundamental waveforms, there are two positive half-cycles and one negative half-cycle of the harmonic waveform. The 3rd-harmonic waveforms of three 120 degree phase-shifted fundamental frequency waveforms are therefore in phase with one other. Further, since the angular displacement is at 120 degrees and the triplen harmonics are comprised of the odd multiples of 3 (3, 9, 15, 21, etc.) all triplens would precisely overlap and appear as a single, unified waveform. 2

Figure 2 Although the triplen harmonics waveform is uniform, the values of each are additive. Heavy harmonic loading therefore can result in significant fundamental waveform distortion. Figure 2 depicts a single phase fundamental waveform with compound triplen harmonic loading. The resultant distortion of the fundamental is significant. Depending on the method of operation, load side equipment can be affected in a variety of ways by the distortion of the fundamental waveform. Significant harmonic content can lead to overheating in motors which may result in the degradation of insulation and loss of life. Other equipment may be dependent on accurate waveshapes and may malfunction when harmonics are present. Harmonics due to multiple single phase distorting loads can result in neutral currents that exceed rated line current which in turn may result in a reduction in electrical distribution system wiring life and the possibility of fire. For the transformer itself, unmanaged harmonics may result in increased winding and core losses which may lead to overheating and loss of service life due to gassing and degradation of the insulation system. Transformers that are connected delta-delta, delta-wye, and wye-delta have balanced voltages due to the absence of a floating neutral. A floating neutral is however the case with a wye-wye connected transformer. The primary and secondary windings are connected in a wye configuration with the neutral and phase winding terminated at the bushings. To accommodate and mitigate the propagation of harmonics, a third winding connected in a delta configuration can be buried as a tertiary (stabilizing) winding. The tertiary winding provides a circulating path for the harmonics that are produced with the power frequency. 3

The addition of a delta connected tertiary winding within a wye-wye transformer provides a path for the balancing current to flow when the secondary must supply an unbalanced load and the neutral point on the primary winding cannot be connected to the system neutral. Without the tertiary winding, an unbalanced load would result in a voltage shift on the secondary neutral and nonsymmetrical voltages. Figure 3 Figure 3 represents a wye-wye connected transformer with a buried tertiary winding. The primary and secondary windings terminate at the transformers HV and LV bushings. It is not necessary to terminate the delta connected tertiary external to the tank when it is used solely to accommodate harmonic loading. The tertiary windings can however, be used to provide supplemental power in which case they can be terminated on their own tank bushings. The rating of the tertiary winding until recently has been managed casually by specifiers and manufacturers. Recently however, the IEEE Transformers Committee met and approved the following: The group has been working for three years to resolve the subject of default kva rating for stabilizing windings. A new clause was prepared by the group for inclusion in C57.12.00, and the following text was surveyed among the Performance Characteristics and Insulation Life Subcommittees prior to this meeting. 5. 11.1.2 Thermal Rating for Stabilizing Windings (buried tertiary) In addition to the short circuit duty stabilizing windings shall be designed to withstand the transient and continuous thermal duty as specified by the user and in accordance with the allowable temperature limits of 5.11.1. In the event no continuous thermal duty for the stabilizing winding can be established from the user s specification, the manufacturer shall design the stabilizing winding considering the 4

circulating current in that winding, resulting from a full single phase load in the largest main secondary winding. The manufacturer shall determine kva rating for the stabilizing winding based on the transformer s equivalent circuit for single phase loading condition. In the event of a line to ground fault on primary or secondary, the fault current in the tertiary winding will be 1/3 of that in the main winding. Therefore, to insure sufficient mechanical withstand strength in the total winding, the tertiary winding capacity must be designed to equal or exceed 1/3 of the transformer kva. Above is an image of a nameplate drawing for a transformer recently supplied by PCT. Note the buried tertiary. The transformer was designed for generator step-up duty.. Pacific Crest Transformers: Providing innovative solutions for today s complex challenges 5