Becker* High Pressure Pneumatic Valve Positioners

Similar documents
Fisher 657 and 667 Diaphragm Actuators

WILROY. Operation. Optional Diaphragm Rupture Detection HYDRAULICALLY ACTUATED DIAPHRAGM PUMP

KNC Model 3666 Automatic Pressure Calibration System

Bristol Series 5453 Indicating Pneumatic Pressure Controllers/Transmitters

PNEUMATIC CONTROLS Selection and Description

DOUBLE SEAT BRONZE BODY HIGH CAPACITY

General Information... 2

PRODUCT PROFILE FEATURES

BULLETIN OCTOBER DeZURIK ROTARY DIAPHRAGM ACTUATORS

Model 43AP Pneumatic Controller, Style B

GE Oil & Gas. Texsteam * Pumps: precise chemical injection pumping

Powers Controls TH 192 S Single Temperature Room Thermostat

Fisher C1 Pneumatic Controllers and Transmitters

Typical Aluminum GFM Mass Flow Meter

Morrison Bros. Co. General Product Specifications

OEM-EP Pressure Controllers

V46 Pressure-Actuated Water-Regulating Valve

POWERS CONTROL RC 195 Single Input Receiver-Controller

Fisher 377 Trip Valve

Type EZL Pressure Reducing Regulator for Low Differential Pressure Applications

GS-General Service Control Valves

Type and Type Pneumatic Control Valves Type 3510 Micro-flow Valve

1805 Series Relief Valves

Mustang Series PRESSURE REDUCING CONTROL VALVE WITH PRESSURE SUSTAINING FEATURE. M115-2 (Globe) M (Angle) Schematic. Standard Components

PRESSURE REDUCING CONTROL VALVE

Fisher 3710 and 3720 Positioners and 3722 Electro-Pneumatic Converter

API Marine. BMS Presentation. Ballast Measurement Systems

B-Series Switches Pressure, Differential Pressure & Hydraulic

COUNTERBALANCE VALVES

Fisher 2625, 2625SST, and 2625NS Volume Boosters

T-4000 Series Pneumatic Room Thermostats

REGULATORS 175/153 Series

Baumann Way Bronze or Stainless Steel Control Valve

Powers Controls Free Energy Band TH 193 HC Heating/Cooling Room Thermostat

CRITICAL MATERIALS HANDLING INVUE INTEGRATED FLOW CONTROLLERS NT6510, NT6520

167D Series Switching Valves

Digital inductive conductivity transmitter

Powers Controls TH 192 HC Heating/Cooling Room Thermostat

Solenoid Valve Type 3962

Index Page. Pumping Systems Intensifiers Gas Boosters High Pressure Generators

SOLFRUNT Pressure Gauges and Other Products for the Process Industries

Fluid Power and Fluid Control Solutions For Tire Manufacturing

Proportional pressure regulators VPPE

Vacuum Control. Vacuum Applications. Vacuum Regulators. Vacuum Breakers (Relief Valves) Vacuum Control Devices. Vacuum Terminology

Why and How we Use Capacity Control

289 Series Spring-Loaded Relief Valves

VG7000 Series Bronze Control Valves

Fisher 377 Trip Valve

Fisher 3610J and 3620J Positioners and 3622 Electro-Pneumatic Converter

S GATE KNIFE GATE VALVE WITH PNEUMATIC ACTUATOR

*Rated to 207 Bar/3000 PSI with Aluminum Body. Denotes New Winner s Circle Product Line. Catalog HY /US

% ^ ) 0.55 W Low Power Solenoid Valves Aluminum, Brass, or Stainless Steel Bodies 1/4" to 1" NPT. 2/2 3/2 4/2 5/2 5/3 SERIES Low Power

Model 4418F. Overview. Typical applications. Key features and benefits. Accreditations. Starting air/gas valve Vented fuel gas valve

Type 3353 Angle Seat Valve

Experience In Motion. Valtek Spring Cylinder Linear Actuators

Electronic pressure switch with display Model PSD-30, standard version Model PSD-31, with flush diaphragm

Kompressoren. Adsorption Dryer AD

MTI10 Insertion and MTL10 In-line Thermal Mass Flowmeter and Temperature Transmitter

Daniel. Liquid Control Valves Technical Guide. Technical Guide DAN-LIQ-TG-44-rev0813. DAN-LIQ-TG-44-rev0208. February 2008.

MP8000 Series Pneumatic Valve Actuators

Micro Motion 3098 Gas Specific Gravity Meter

Type 99 Pressure Reducing Regulator

6 Crankcase Ventilation

Product Manual. CVS Type 67AFR Filter Regulator. Introduction. Installation. Description

Diaphragm Actuators Favorable Variety Pneumatic Diaphragm Actuators Electric Actuators Hydraulic Actuators

MODEL LP 225LP2 225LP4 Safety Relief Valves

B-Series Temperature Switches

2-Port Self-acting Temperature Control Valve Selection for Heating and Cooling Applications

Precision Regulator. Series IR1000/2000/3000 ARJ AMR ARM ARP IR IRV VEX1 SRH SRP SRF ARX20 VCHR ITV IC PVQ VER VEA VY2 AP100.

Thermostatic valve Type AVTA

Actuators & Positioners LP - Linear Pneumatic Piston Actuator. Cylinder Actuators. High resolution, sensitivity, and fast response

ball valves Flomite 71 Series 2-way Integral Panel Mount Ball Valves

RC 195 Multiple Input Receiver-Controller

BERMAD Waterworks. Pressure Relief/Sustaining Valve. 700 Series. Model 730. Features and Benefits. Major Additional Features

SIMPLIFIED VALVE CIRCUIT GUIDE

Flow controller with integrated control valve (PN 16, 25, 40*) AFQM, AFQM 6 - return and flow mounting

LINEAR MOTION CONTROL

Digital pressure gauge for industrial applications Model DG-10-S, Standard version Model DG-10-E, Enhanced version

The Unique Accelabar Flow Meter

Control- and feedback head for integrated mounting on Robolux valves Type 2036

Introduction. Angle/Flared/Sequence/Changeover Service Valves. Valves D

DMP 331. Industrial Pressure Transmitter for Low Pressure. Stainless Steel Sensor

Type 92S Pilot-Operated Steam Regulator

3 WAY (3/2) POPPET VALVES FOR AIR AND VACUUM SERVICE SOLENOID OR AIR ACTUATED BROCHURE N-223

Automation System TROVIS 6400 TROVIS 6493 Compact Controller

RUBBER SLEEVE KNIFE GATE VALVE

Fisher D3 Control Valve

POWERS Controls No. 4 Pneumatic Damper Actuator

Thermostatic expansion valves type TR6 REFRIGERATION AND AIR CONDITIONING. Technical leaflet

Pressure Relief and Regulating Valves

ThermoSorb Desiccant Dryers

F ox W hi t e Paper. Reduce Energy Costs and Enhance Emissions Monitoring Systems

Richter Twin Piston Quarter-turn Actuators

Electronic Flow Switches

MAKING MODERN LIVING POSSIBLE. Thermostatic valve AVTA. Technical brochure

The Breather Box. High Performance Grade-D Breathing Air Filtration system. BB50-cO

Instruction Manual Differential Pressure Transmitter

Seated valves (PN 16) VF 2 2-way valve, flange VF 3 3-way valve, flange

Baumann Little Scotty Bronze Control Valve

Transcription:

GE Oil & Gas Becker* High Pressure Pneumatic Valve Positioners HPP-SB: Single Acting Positioner Accurate Valve Positioning for Multiple Control Applications

GE s Becker HPP-SB Pneumatic Positioners Provide Accurate Positioning of Single-Acting Actuated Control Valves GE s Becker Products High Pressure Pneumatic (HPP) Single-Acting Positioners represent a breakthrough in valve control technology for the natural gas industry. They work with any Becker single-acting series actuator (spring and piston type) to accurately position valves in a variety of control applications, including pressure control, flow control, power plant type pressure control, power plant type flow control, and surge control. The product s design includes features that improve process performance, resist vibration under demanding conditions while continuing calibration, assure long service life, eliminate atmospheric bleed gas, and perform in fast-acting applications. HPP-SB Positioner Applications Pressure control Flow control Power plant type pressure control Power plant type flow control Surge control Compatible Actuators RPSR Series LPSR Series LD Series Figure 1 - HPP-SB Single-Acting Valve Positioner HPP-SB 4-20 ma signal I/P T-Ball Control Valve with RPDA Series Actuator MCV FD-1 Gas Supply System Figure 2 - HPP-SB positioner installed on GE s Becker Products RPSR Series Actuator installed on Becker RPSR Series Actuator The HPP-SB positioner may be utilized with any Becker single-acting series actuator (spring and piston type) for accurate positioning of control valves. The HPP-SB positioner is designed to accept a pneumatic instrument signal from an I/P transducer or a pneumatic controller. The HPP-SB positioner is available in both reverse and direct-acting with a variety of instrument signal input ranges. The configuration shows the HPP-SB positioner mounted on a Becker RPSR Series actuator. The HPP-SB positioner features ZERO bleed at steady state combined with high speed response. Schematic Legend Line Pressure Exhaust Power Supply Loading Pressure Sensing P 1 FLOW P 2 2

Benefits E Superior resolution and sensitivity and positioning capabilities for improved process performance High flow capacity of any valve positioner in the industry, makes well-suited for fast-acting applications including compressor surge control ZERO bleed when control valve is full open and full closed. Balanced seat design exhibits ZERO bleed when process is at steady state 1 D 2 C 3 Becker positioner s unique Bleed to Pressure System* (BPS) feature allows for complete elimination of atmospheric bleed gas by maintaining vent gas within the process piping B Stable, accurate positioning with minimal overshoot Vibration resistant design will perform in the most demanding applications and maintain calibration annual adjustments required Anodized AL 2024 Aluminum and Stainless Steel construction provide rugged durability for long life Figure 3 - HPP-SB Single-Acting Valve Positioner A HPP-SB Positioner Port Definitions Port Size Item Instrument Signal (Input) 1/4 FNPT A Power Gas Supply (Input) 1/2 FNPT B Actuator Loading (Input) 1/4 FNPT C Exhaust (Discharge) 1/4 FNPT D Breather Vent 1/4 FNPT E Reference Figure 3. Table 2 - HPP-SB Positioner Adjustments HPP-SB Positioner Adjustments Item Bias Adjustment (Zero/Offset) 1** Range Adjustment (Span) 2** Sensitivity (Deadband Adjustment) 3 Improve Performance and Minimize Bleed Gas Emissions If you already have existing Becker control valve actuators in service with older, obsolete Becker Model HPP-S positioner, the addition of an HPP-SB positioner can improve performance, reduce maintenance, and minimize bleed gas emissions. Becker HPP-SB positioners are compatible to retrofit older Becker Model HPP-S positioners originally installed on Becker RPSR Actuators. Consult your GE representative for more information. Reference Figure 3. ** Bias and range adjustments not shown 3

Precision Operation The HPP-SB positioner configuration shown below is closed on increasing instrument input signal, the control valve will fail open on loss of instrument input signal. The HPP-SB positioner is a force-balanced instrument that provides a control valve position proportional to a pneumatic instrument input signal. The energy to operate the control valve is obtained from the differential between supply gas pressure and discharge gas pressure. From a steady state position (Figure 4.1), an increase in the instrument signal causes the internal pistons to move up and load pressure to the actuator (Figure 4.2), closing the valve. As the force from the positioner range spring increases to a point equal to the diaphragm force created by the instrument input signal, the internal pistons will center. Centering of the internal pistons will close both of the balanced seats and cease loading of the control valve (Figure 4.1). At steady state, the control valve will remain in a fixed position with ZERO bleed. Decrease of the instrument input signal will result in the opposite reaction, opening the valve (Figure 4.3). Note that loss of instrument input signal causes the control valve to fail in the full open position (configuration shown). Steady Closed Figure 4.1 - Steady State Position (Fixed) At steady state, the instrumentation diaphragm force is equal to the feedback spring force, centering the internal pistons and closing the internal balanced seat valves. Steady state conditions exhibit ZERO bleed. Figure 4.2 - Increase in Instrument Input Signal to CLOSE Valve An increase in the instrument input signal causes the internal pistons to move up and load pressure to the actuator, closing the valve. Open Exhaust Pressure (Discharge) High Pressure Gas Actuator Loading Pressure (Medium Pressure) Actuator Loading Pressure (High Pressure) Actuator Loading Pressure (Low Pressure) Instrumental Signal Exhaust Pressure Figure 4.3 - Decrease in Instrument Input Signal to OPEN Valve A decrease in the instrument input signal causes the internal pistons to move down and exhaust pressure from the actuator, opening the valve. 4

Table 3 - Technical Specifications for Model HPP-SB Positioner Technical Specifications Steady State Gas Consumption ZERO (See Table 3) Supply Gas Dry, filtered (100 micron gas 500 psig maximum Maximum Flow Capacity 2400 scfh (40 scmh) Maximum Supply-Discharge Differential 150 psig (1034 kpa) Minimum Supply-Discharge Differential 50 psig (348 kpa) Operative Ambient Temperature Range -20 F to +160 F (-29 C to +71 C) Approximate Weight 12 lbs. (5.4 kg) Minimum Deadband 0.2% instrument signal Independent Linearity ± 1.0% positioning range Resolution 0.1% of position range Instrument (Input) Signal Ratings 3-15 psig, 6-30 psig (standard) (See Table 2) Available Stroke Lengths 2, 4, 6, 8, 12 (See Table 4) reverse-acting/direct acting Housing Meets NEMA 3 Classification Installation Orientation Vertical position recommended Materials of Construction External Parts Anodized AL2024, 316SS available (for marine environments) Springs 316 SS and anodized AL 2024 Diaphragms Buna-n reinforced by nylon fabric Seats and O-rings Buna-n Tubing and Tubing Fittings 316 SS 2-1/2 dial liquid filled brass connection w/stainless steel Gauges case (standard issue with units of pisg dual units of psig/ kpa available Notes 1. Direct-Acting: increasing instrument signal causes control valve to close (fail-open upon loss of instrument signal) 2. Reverse-Acting: decreasing instrument signal causes control valve to close (fail-closed upon loss of instrument signal) Table 4 - Bleed rates (consumption) for Becker Control Instrumentation Becker Control Instrumentation features low bleed and ZERO bleed technologies to minimize fugitive natural gas emissions and environmental impact. VRP-CH Pilot VRP-B-CH Pilot VRP-SB-CH Pilot Bleed Rates (Consumption) Steady State Bleed 3 ~100 <10 zero zero zero ~100 <10 zero zero Non-Bleed Y 1 Y 2 Y Y Y Y 1 Y 2 Y Y Full-Open/Full-Closed Bleed to Pressure System (BPS) 4 Y N Y Y N Y Y Y Y Notes 1. Requires Model PS-2 or NBV Non-Bleed Device to eliminate bleed 2. Requires Model DPS-2 or NBV Non-Bleed Device to eliminate bleed 3. Bleed rates are estimated utilizing Supply Gas Pressure = 100 psig 4. Bleed to Pressure System (BPS) eliminates all atmospheric bleed VRP-SB-GAP Pilot VRP-SB-PID Pilot HPP-4 Positioner HPP-5 Positioner HPP-SB Positioner DNGP Positioner 12 in. (305 mm) 10 in. (254 mm) Figure 5 - Overall dimensions of HPP-SB positioner (standard range) 5

Table 5 - Bias and Range Spring Part Numbers for Specific Model HPP-SB Positioner Actuator Stroke Lengths Signal Range Spring Type 2 (51 mm) 4 (102 mm) 6 (152 mm) 8 (203 mm) 12 (305 mm) 3-15 psig (21-103 kpa) 6-30 psig (41-207 kpa) 3-9 psig (21-62 kpa) 9-15 psig (62-103 kpa) 6-24 psig (41-166 kpa) 18-30 psig (124-207 kpa) Range Spring 25-1151 25-1151 25-1152 25-1153 25-1154 Bias Spring Not Required Range Spring 25-1218 25-1218 25-1219 25-1220 25-1221 Bias Spring Not Required Range Spring 01-6288 01-6288 01-6287 01-6287 01-6801 Bias Spring Green (20-2592) Range Spring 01-6288 01-6288 01-6287 01-6287 01-6801 Bias Spring Blue (25-1036) Range Spring 25-1599 25-1599 25-1600 25-1601 25-1602 Bias Spring Silver (25-1038) Range Spring 25-1151 25-1151 25-1152 25-1153 25-1154 Bias Spring Red (25-1037) Standard model range springe and bias spring part numbers for the Model HPP-SB positioner. Other configurations are available upon request. Repair or Rebuild? Becker instrumentation rebuild kits are available from stock for regular maintenance or emergency needs. To order repair kits for your Becker products call us toll-free at (800) 323-8844, or contact your local sales representative. Model HPP-SB Pneumatic Positioner Repair Kit* (Standard Range) Part Number 35-0210 *Includes all rubber goods and finite life items for rebuild or repair for HPP-SB. Figure 6 - Becker HPP-SB Pneumatic Positioners Becker HPP-SB positioners are available in both reverse-acting and direct-acting. Standard instrument signal ranges are 3-15 psig and 6-30 psig. Alternate instrument ranges are available for split range control to enable staging of control valve runs. Figure 6.1 - Model HPP-SB Reverse-Acting Positioner (Standard Range) Figure 6.2 - Model HPP-SB Reverse-Acting Positioner (Split Range) Figure 6.3 - Model HPP-SB Direct-Acting Positioner (Standard Range) Figure 6.4 - Model HPP-SB Direct-Acting Positioner (Split Range) 6

Table 6 - Selection table for Becker Control Valves and Actuators VRP-CH Pilot VRP-B-CH Pilot VRP-SB-CH Pilot VRP-SB-GAP Pilot VRP-SB-PID Pilot HPP-4 Positioner HPP-5 Positioner HPP-SB Positioner DNGP Positioner NOTES Applications Pressure Control 1,2 Flow Control 2 Power Plant Type Pressure Control 3 Power Plant Type Flow Control 3 Surge Control On/Off Compatible Actuators RPDA Series (Small Models) 4 RPSR Series (Large Models) 5 RPSR Series LPDA Series (Small Models) 4 LPDA Series (Large Models) 5 LPSR Series LD Series 6 Instrumentation Options Bleed to Pressure System BPS 7 AB Series Atmospheric Bleed Control NBV Series No-Bleed Valve 8 DPS-2 Series Non Bleed Sensor 9 PS-2 Series Non Bleed Sensor 9 SP Series Setpoint Pump RSM Series Remote Setpoint Module Panel Mounting Stainless Steel Option VB Series Volume Booster 10 QEV Series Quick Exhaust Valve I/P Transducer SLV Series Signal Lock Valve 1. Pressure control applications include: pressure letdown, primary regulation, monitors, standby, overpressure protection, underpressure protection, and relief valve. 2. All positioners require controller device to perform pressure control or flow control. 3. Power plant regulation includes all power plants and fast-acting short systems. 4. RPDA and LPDA Small Models are defined as actuator sizes 14L and smaller (< 2000 in3 / 0.033m 3 ) 5. RPDA and LPDA Large Models are defined as actuator sizes 12T and larger ( 2000 in3 / 0.033m 3 ). 6. LD Series Actuators are limited to Becker CVE Series Globe Valves. 7. BPS is limited to discharge pressure systems below 300 psig (2068 kpa). Consult Becker for application assistance. 8. NBV No-Bleed Valves may only be utilized when P discharge 60 psig (414 kpa) and/or P supply 150 psig (1034 kpa). 9. PS-2 and DPS-2 Non-Bleed Sensors must be utilized when P discharge > 60 psig (414 kpa) and/or P Supply > 150 psig (1034 kpa). 10. VB Series Volume Boosters are necessary for power plant regulation, surge control applications, or when large model RPDA are utilized. The HPP-SB Positioner provides high performance for the Becker Surge Control Valve GE s Becker Surge Control Valve is a key control valve for protection of centrifugal natural gas compressors. The Surge Control Valve offers: Accurate control Fast action Friction free design Repeatability Stability Vibration resistance The HPP-SB positioner is the ideal choice for this demanding application. The HPP-SB positioner provides all the necessary performance combined with these environmentallyfriendly features: ZERO bleed at steady state ZERO bleed when control valve is at full open position ZERO bleed when control valve is at full closed position Complete elimination of atmospheric bleed gas emissions with the Becker positioner s unique Bleed to Pressure System (BPS) feature. 7

GE Oil & Gas 16250 Port Northwest Houston TX 77041 +1 866 754 3562 www.geoilandgas.com *Denotes trademakr of General Electric Company. 2014 General Electric Company. All Rights Reserved. GEA19589 09/2014